SUBMITTAL
Cooling (Btu/h)
Heating (Btu/h)
Model
Type
Output (W)
Sound Level
Accessories
AVXDUH145CE
Drain Pump
Wireless Receiver Kit
MDP-M075SGU2
MRK-A01/MRW-10A
Safety Certifications ETL & ETLc
14 1/8
25 5/8
115
43/40
MSP (Medium static pressure) Ducted Fan Coil (Heat Pump & Heat Recovery
Systems)
R410A
Electronic Expansion Valve
3/8"
5/8"
VP25 (OD 1 1/4, D 1")
47 1/4
Specifications
Heating High
Standard ("WC)
Min-Max ("WC)
Airflow (CFM)
External
Static
Pressure
High/Low (Db)
48,000
54,000
9.8
1/208-230/60
2.45
Single Sirocco Fan
YDK-370S65023-01
Non Feedback SSR
218
Supply Duct Connection
1236
1236
0.3
0.25 - 0.40
Cooling High
39 3/8" X 10"
Dimensions
Motor
Fan
Type
Depth (inches)
Height (inches)
Width (inches)
Weight (lbs.)
Control Method
Type
Refrigerant
Piping
Connections
(inches)
Liquid (flare)
Drain (Quick Lock)
Suction (flare)
Performance
Capacity
Condensate (pints/hour)
Power
Voltage (/V/Hz)
Running Current (amps)
www.SamsungSystemAC.com
QS-DVM-0312A
Quietside maintains a policy of ongoing development, specifications are subject to change without notice.
*Nominal cooling capacities are based on: ndoor temperature: 80F DB, 67F WB. Outdoor temperature: 95F DB, 75F WB.
*Nominal heating capacities are based on: ndoor temperature: 70F DB, 60F WB. Outdoor temperature: 47F DB, 43F WB.
Job Name Location
Purchaser Engineer
Submitted to Reference
Unit Designation Schedule #
Approval Construction
Construction
Unit Shall be made from galvanized steel
Heat Exchanger
The heat exchanger shall be mechanically
bonded fin to copper tube
Indoor Fan
Indoor fan is twin backward curved
centrifugal type with a single fan motor
Three fan speed settings
Controls
The unit shall be operated via a remote
control with DDC type signal
The unit shall integrate with the Samsung
Controls Network Solution
Controls shall integrate with a BMS system
Control wiring shall be 16AWG shielded
wire
Air Filtration
As standard the unit has no air filtration
Filtration is field installed, pressure drop
across the filter must be factored into the
total ESP
SUBMITTAL AVXDUH145CE Page 2 of 2
MSP (Medium static pressure) Ducted Fan Coil (Heat Pump & Heat
Recovery Systems)
www.SamsungSystemAC.com
Unit: inches
888-699-6067
6
1
2
3
4
5
7
8
1
2
3
4
5
6
7
8
Liquid Pipe Connection
Gas Pipe Connection
Drain Pipe Connection, Without Optional Condensate Pump
Drain Pipe Connection, With Optional Condensate Pump
Controls Box
Conduit for Power & Communication Wiring
Return Air Side
Supply Air Outlet Duct Flange
No. Name Description
3/8" Flare
5/8" Flare
OD 1 1/4", ID 1"
Quick Lock
-
-
-
-
Supply Side
Discharge
Suction
Unit Bottom 3
Recommended Service Access (min.)
(Verify Local Codes)
Suction
35 3/8" Supply Outlet Duct Flange
Suspension Bolt Hanger
47 1/4"
48 5/8" Suspension Point
6 3/4"
9 5/8"
11 3/4"
3 1/8"
2
1
"

S
u
s
p
e
n
s
i
o
n

P
o
i
n
t
8

3
/
4
"
3

3
/
8
"
2
5

5
/
8
"
1
4

1
/
8
"
1
0
"
O
u
t
l
e
t

F
l
a
n
g
e
TOP
13/16" or more
13/16" or more
Ceiling
Structure
Service Access
Unit
Unit Clearance From Structure
U
n
i
t

D
e
p
t
h

+

2
"
Unit Width (W)
A=W+4"
Inspection Opening Requirements
In applications where there is not a tile ceiling, an inspection hole is required.
(verify state and local codes).
If height between ceiling and structure is 3.25' or more, inspection opening "B" is recommended.
If height between ceiling and structure is less than 3.25', inspection opening "A" and "B" is recommended.
B=23 5/8"