NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1

Copper conductor, PVC insulated and PVC sheathed cable

1 Core

DIMENSIONAL & MECHANICAL DATA


Nominal crosssectional area

Nominal Thickness
No of wire and
conductor shape

mm2

pcs

1.5
1.5
2.5
2.5
4
4
6
6
10
10
16
25
35
50
70
95
120
150
185
240
300
400
500

1
7
1
7
1
7
1
7
1
7
7
7
7
19
19
19
67
37
37
61
61
61
61

re
rm
re
rm
re
rm
re
rm
re
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm
rm

Approximately

Insulation

Outer sheath

Overall
diameter

0.8
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1

6
7
7
7
8
8
8
9
9
9
11
12
13
15
17
19
21
23
25
29
32
35
39

Bending radius Standard delivery


length
min

Net Weight
Kg/Km

mm

34

80
90
90
90
100
100
100
110
110
110
140
150
160
180
210
230
260
280
300
350
390
420
470

1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000

55
66
70
91
97
113
121
157
168
234
344
445
578
793
1,079
1,319
1,622
2,009
2,612
3,236
4,077
5,139

1,000
500

ELECTRICAL DATA
Current Carrying Capacity at 30 C

Resistance at 20 C
Nominal cross-sectional
area

In AIR
DC conductor max

mm2

/Km

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366

Short circuit current of


conductor at 0 sec

33
45
58
74
98
107
138
185
196
240
289
329
374
418
481
552
632
730

0.19
0.32
0.50
0.73
1.20
1.91
2.96
4.13
5.87
8.19
11.09
13.98
17.46
21.50
27.86
34.79
41.50
51.84

MKm

50
50
50
50
50
40
40
40
30
30
30
30
20
20
20
20
20
20

In GROUND

Insulation min

26
25
46
58
80
100
135
170
205
260
320
375
430
490
590
680
825
960

kA

www.sucaco.com

:<79,4,

3V^=VS[HNL
7=*05:<3(;,+*HISLZ

NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1

Copper conductor, PVC insulated and PVC sheathed cable

DIMENSIONAL & MECHANICAL DATA

2 Cores
Nominal Thickness

Nominal crossNo of wire and conductor shape


sectional area

Insulation

Approximately

Outer sheath

Overall
diameter

Net Weight

Bending radius
Standard
min
delivery length

mm2

pcs

mm

mm

mm

Kg/Km

mm

1.5
1.5
2.5
2.5
4
4
6
6
10
10
16

1
7
1
7
1
7
1
7
1
7
7

0.8
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.0

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

12
13
13
14
15
16
16
17
18
18
21

205
213
243
259
326
351
390
422
514
557
744

150
160
160
170
180
200
200
210
220
220
260

1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000

25
35
50
70
95
120
150
185
240
300

7
7
19
19
19
37
37
37
61
61

re
rm
re
rm
re
rm
re
rm
re
rm
rm
rm

1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.6
2.7

24
26
30
33
39
42
46
51
58
64

1,066
1,342
1,735
2,331
3,159
3,829
4,667
5,805
7,482
9,253

290
320
360
400
470
510
560
620
700
770

1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500

rm
rm
rm
rm
rm
rm
rm
rm
rm

ELECTRICAL DATA
Resistance at 20 C
Nominal cross-sectional
area

Current Carrying Capacity at 30 C

DC conductor max

Insulation min

mm 2

/Km

MKm

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

50
50
50
50
50
40
40
40
30
30
30
30
20
20
20
20

In AIR
A

21
29
38
48
66
90
120
150
180
230
275
320
375
430
510
590

Short circuit current of


conductor at 10 sec

In GROUND
kA

27
36
47
59
78
102
134
160
187
230
280
320
355
409
472
525

0.19
0.32
0.50
0.73
1.20
1.91
2.96
4.13
5.87
8.19
11.09
13.98
17.46
21.50
27.86
34.79

www.sucaco.com

SUPREME
S
UPREME

3V^=VS[HNL*HISLZ
3V^
3V
^ =V
=VS[
S[HN
S[
HNL
HN
L *H
*HIS
ISLZ
IS
LZ
Z

NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1

Copper conductor, PVC insulated and PVC sheathed cable

DIMENSIONAL & MECHANICA

3 Cores
Nominal Thickness

Nominal crosssectional area

No of wire and
conductor shape

Insulation

mm2

pcs

1.5
1.5
2.5
2.5
4
4
6
6
10
10
16
25
35
35
50
70
95
120
150
185
240
300

1
7
1
7
1
7
1
7
1
7
7
7
7
19
19
19
19
37
37
37
37
37

re
rm
re
rm
re
rm
re
rm
re
rm
rm
rm
rm
sm
sm
sm
sm
sm
sm
sm
sm
sm

Outer sheath

Approximately
Overall
diameter

Net Weight

mm

0.8

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.1
2.2
2.3
2.5
2.7
3.1

0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

Kg/Km

13
13
14
14
16
16
17
17
28
19
22
25
28
28
28
31
36
38
43
47
53
59

Bending
radius min

Standard
delivery length

mm

160
160
170
170
200
200
210
210
220
230
270
300
340
300
340
380
440
460
520
570
640
710

229
237
276
295
377
406
459
495
620
669
912
1,325
1,688
1,411
1,829
2,527
3,404
4,155
5,119
6,324
8,224
10,304

1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
300

ELECTRICAL DATA
Resistance at 20 C
Nominal crosssectional area

DC conductor max

Insulation min

mm2

/Km

MKm

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

50
50
50
50
50
40
40
40
30
30
30
30
20
20
20
20

Current Carrying Capacity at 30 C


In AIR

In GROUND

kA

18
25
34
44
60
80
105
130
160
200
245
285
325
370
435
500

Short circuit current of


conductor at 10 sec

24
32
41
52
69
89
116
138
165
205
245
285
315
355
415
465

0.19
0.32
0.50
0.73
1.20
1.91
2.96
4.13
5.87
8.19
11.09
13.98
17.46
21.50
27.86
34.79

www.sucaco.com

:<79,4,

3V^=VS[HNL
7=*05:<3(;,+*HISLZ

NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1

Copper conductor, PVC insulated and PVC sheathed cable

DIMENSIONAL & MECHANICAL DATA


Nominal crosssectional area

3 Cores + 1 ground
Approximately

Nominal Thickness
No of wire and conductor shape
Insulation

Outer sheath

Overall
diameter

Net Weight

Bending
radius min

Standard
delivery length

mm2

pcs

mm

3 x 25 + 16

7/7

rm/rm

1.2/1.0

1.8

27

1,501

330

1,000

3 x 35 + 16

7/7

rm/rm

1.2/1.0

1.8

29

1,846

350

1,000

3 x 35 + 16

19/7

sm/rm

1.2/1.0

1.8

28

1,668

340

1,000

3 x 50 + 25

19/7

sm/rm

1.4/1.2

1.9

32

2,224

390

1,000

3 x 70 + 35

19/7

sm/rm

1.4/1.2

2.0

36

3,024

440

1,000

3 x 95 + 50

19/19

sm/rm

1.6/1.4

2.2

40

4,051

480

1,000

3 x 120 + 70

37/19

sm/rm

1.6/1.4

2.3

44

5,083

530

500

3x 150 + 70

37/19

sm/rm

1.8/1.4

2.4

49

6,052

590

500

mm

Kg/Km

3 x 185 + 95

37/19

sm/rm

2.0/1.6

2.6

53

7,535

640

500

3x 240 + 120

37/37

sm/rm

2.2/1.6

2.8

60

9,725

720

300

3 x 300 + 150

37/37

sm/rm

2.4/1.8

2.9

65

11,983

780

300

ELECTRICAL DATA
Resistance at 20 C
Nominal crosssectional area

DC conductor max

Insulation min

mm2

/Km

MKm

3 x 25 + 16
3 x 35 + 16

0.727/1.15
0.524/1.15

40
40

3 x 50 + 25

0.387/0.727

3 x 70 + 35

0.268/0.524

3 x 95 + 50

Current Carrying Capacity at 30 C

In AIR

Short circuit current of


conductor at 10 sec

In GROUND
A

kA

105
130

116
138

2.96
4.13

30

160

165

5.87

30

200

205

8.19

0.193/0.387.

30

245

245

11.09

3 x 120 + 70

0.153/0.268

30

285

285

13.98

3x 150 + 70

0.124/0.268

20

325

315

17.46

3 x 185 + 95

0.0991/0.193

20

370

355

21.50

3x 240 + 120

0.0754/0.153

20

435

415

27.86

3 x 300 + 150

0.0601/0.124

20

500

465

34.79

www.sucaco.com

SUPREME
S
UPREME

3V^=VS[HNL*HISLZ
3V^
3V
^ =V
=VS[
S[HN
S[
HNL
HN
L *H
*HIS
ISLZ
IS
LZ

NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1

Copper conductor, PVC insulated and PVC sheathed cable

DIMENSIONAL & MECHANICAL DATA


Nominal crosssectional area
mm

1.5
1.5
2.5
2.5
4
4
6
6
10
10
16
25
35
35
50
70
95
120
150
185
240
300

4 Cores
Nominal Thickness

No of wire and
conductor shape
pcs

1
7
1
7
1
7
1
7
1
7
7
7
7
19
19
19
19
37
37
37
37
37

re
rm
re
rm
re
rm
re
rm
re
rm

Insulation

Outer sheath

0.8
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.1
2.2
2.3
2.5
2.7
2.9
3.1

Approximately
Overall
diameter

Net Weight

mm

rm
rm
sm
sm
sm
sm
sm
sm
sm
sm
sm

14
14
15
15
17
18
18
19
20
21
24
28
30
28
32
36
40
44
49
53
60
66

Bending
radius min

Standard
delivery length

Kg/Km

mm

262
272
320
343
443
477
546
589
749
807
1,113
1,630
2,092
1,869
2,491
3,381
4,534
5,596
6,877
8,462
10,999
13,616

170
170
180
180
210
220
220
230
240
260
290
340
360
340
390
440
480
530
590
640
720
800

1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
300
300

ELECTRICAL DATA
Resistance at 20 C
Current Carrying Capacity at 30 C

Nominal crosssectional area

DC conductor max

Insulation min

mm 2

/Km

MKm

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601

50
50
50
50
50
40
40
40
30
30
30
30
20
20
20
20

In AIR

In GROUND
A

18
25
34
44
60
80
105
130
160
200
245
285
325
370
435
500

Short circuit current of


conductor at 10 sec

kA

24
32
41
52
69
89
116
138
165
205
245
285
315
355
415
465

0.19
0.32
0.50
0.73
1.20
1.91
2.96
4.13
5.87
8.19
11.09
13.98
17.46
21.50
27.86
34.79