PROJECT : SAN COKE STRUCTURE : HRSG FRAME (Boiler Structure) LOCATION: KENTUCKY, USA SEISMIC LOAD CALCULATION Code

: ASCE 7-2005 / Ky Bldg Code/IBC-2006 Where : E = Eh + Ev , equation 12.4-1 E = Eh - Ev , equation 12.4-2 Eh = V Ev = 0.2SDSW V = CSW , Seismic Base Shear W = Effective Seismic Weight CS = SDS (R/Ie) E = Seismic Load Effect Ev = Effect of Vertical Seismic Force Eh = Effect of Horizontal Seismic Force

, Seismic Respone Coefficient

R = Response modification factor (Table 12.2-1) Rx = 3.25 , for steel ordinary braced frame Rz= 3.5 , for steel ordinary moment frames Ie = 1.00 , Seismic Importance factor (sec 11.5.1) Risk Category = II , defined at table 1-1 Site Class = D , stiff soil profile (sec 11.4.2) SDS = (2/3) SMS ,design spectral response acceleeation parameter in short period (sec. 11.4.4) SMS = FaSS , spectral response acceleration parameter for short period SD1 = (2/3) SM1 SM1 = FvS1 SS = S1 = Fa = Fv = 0.211 0.074 1.6 2.4 ,design spectral response acceleeation parameter at period of 1 s (sec. 11.4.4) , spectral response acceleration parameter at period of 1 s , spectral response acceleration parameter for short period shown on Fig. 22-1 , spectral response acceleration parameter at a period of 1 s shown on Fig. 22-2 , site coefficients shown in table 11.4-1 , site coefficients shown in table 11.4-2 , Fundamental Period (sec. 12.8.2.1) , structural height from base

T = Cthna hn = 16.55

Calculation for Period : @ x-direction Ctx = 0.0731 a = 0.75 Tx = 0.6 sec @ z-direction Ctz = 0.0724 a = 0.8 Tz = 0.68 sec Seismic Base Shear Calculation : SMS = SDS = CSx = CSz = 0.338 0.225 0.069 0.064 TL= <not govern> <not govern> 12 sec , long-period transition period shown in Fig 22-12 SM1= SD1 = 0.178 0.118

, for steel ordinary braced frame (table 12.8-2) , for steel ordinary braced frame (table 12.8-2) , fundamental period of structure at x-direction , for steel moment resisting frame (table 12.8-2) , for steel moment resisting frame (table 12.8-2) , fundamental period of structure at z-direction

Maximum Base Shear (Max Cs), sec. 12.8.1.1 T< TL : SD1 Tx (Rx/Ie) = 0.061 <used> SD1 Tz (Rz/Ie) <used>

Max Csx =

Max Csz =

= 0.049

Minimum Base Shear (Min Cs), sec. 12.8.1.1 Min Cs = 0.044 SDS Ie > 0.01 = 0.010 SEISMIC LOAD : Vx = Vz = Ev = 0.2SDSw = 0.061W 0.049W 0.045W , Seismic Base Shear at X-Direction , Seismic Base Shear at Z-Direction , vertical seismic load

PROJECT : SAN COKE STRUCTURE : HRSG FRAME (Boiler Structure) LOCATION: KENTUCKY, USA WIND LOAD CALCULATION Code : ASCE 7-2005 V = 40 m/sec Risk Category = II Exposure = C Kd = 0.85 Kzt = I= G= 1.0 1.0 0.85
, basic wind speed (from fig. 6-1) , defined at table 1.-1 , Open Terrain with Scattered obstruction , Wind Directionality Factor (Table 6-4) , Topographic Factor, (sec 6.5.7) , Wind Importance Factor (Table 6-1) , Gust Effect Factor (sec6.5.8)

2 qz = 0.613KzKztKdV2I , Velosity Pressure (N/m ); V in m/s

Kz, Velocity Pressure Exposure Coefficients Hz (m) Kz


qz (kN / m2)

0~4.6 0.85 0.71 5 0.87 0.72 6.1 0.90 0.75 7 0.93 0.77 8 0.95 0.80 9 0.98 0.82 10 1.00 0.83 11 1.02 0.85 12 1.04 0.87 13 1.06 0.88 14 1.07 0.90 15 1.09 0.91 16 1.11 0.92 17 1.12 0.93 * design values for Kz and qz are based on exposure C p = qz (GCp - GCpi) (Design Wind Pressure, N/m2) Wall external pressure Coefficients, Cp from fig. 6-6 Windward = Leeward = Sidewalls = Roof = Roof = h0.8 0.5 0.7 1.03 (0 to h/2 from windward edge) 0.7 (>h/2 from windward egde) Mean roof height

Internal Pressure Coeficient (GCPi)= 0.18 (+/-)

(from table 6-5)