Water-to-Water Heat Pump

Product Data Catalog


for R-410A or R-134a Refrigerant

For Modules:
MS010XN-410A, MS015XN-410A, MS020XN-410A, MS030XN-410A, MS050XN-410A, MS070XN-410A
MS010AN-134a, MS015AN-134a, MS020AN-134a, MS030AN-134a, MS050AN-134a, MS070AN-134a

Table of Contents
Product Introduction......................................................................................................................... 3
Chiller Options................................................................................................................................... 5
General Data..................................................................................................................................... 9
Performance Data for R410A Refrigerant.......................................................................................... 10
Performance Data for R134a Refrigerant.......................................................................................... 16
Electrical Data................................................................................................................................. 18
Controller Schematics...................................................................................................................... 20
Sample Piping Schematics................................................................................................................ 21
Mechanical Specifications................................................................................................................ 22

Model Number Nomenclature


Existing
MS
50
New

MS

X
050

1
X

H
N

R-410A
1

-410A

Refrigerant
Condenser6
Evaporator5
AHRI Version - if applicable
Application4
Voltage3
Configuration2

Module Number (1 - single, 2 - multiple)

AHRI Certified (C - certified, N - Not certified)


Compressor Type1
Module Nominal Capacity (10 - 160 tons)
Series
1 B: Bristol, C: Trane Cornerstone, R: Bitzer Screw, S: Trane Scroll, T: Danfoss Turbocor, Z: Copeland scroll (old elec), X: Copeland Scroll (ZP), A: Copeland Scroll (ZR)
2 1- Standard, 2- Total access, 3 - Evap extended headers, 4 - Cond extended headers, 5 - Both extended headers, V - others
3 A - 208/3/60, L - 230/3/60, H - 460/3/60, C - 575/3/60, D - 200/3/50, E - 400/3/50, F - 380/3/60, S - 220/230/1/60, V - other
4 C - Single module temp controller, A-Air Cooled split, D - Cond unit, F - Fluid cooler (high temp),H - Heat recovery, R - Heat pump, W - Water cooled
5 A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, V - Other
6 A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, E - Double wall brazed, V - Other

Water-to-Water Heat Pump


PRODUCT INTRODUCTION
Applications for a Multistack Heat Pump
Laundry Water Heating
Swimming Pool Heating
Process Heating and Cooling
Domestic Hot Water
Building Heat
Reheat Coils
VAV Reheat
Typical Buildings for Heat Pump Applications
Hotels and Motels
Resorts
Recreational Facilities
Schools
Hospitals
Nursing Homes
Process Cooling and Heating
Data Centers
Call Centers
Campus Cooling and Heating Plants
Benefits
Reduced CO2 emissions
Easy retrofit for any mechanical room
Payback in less than three years typically
More efficient than a gas boiler
Heating COP with R-410A can exceed 5.0
Heating COP with R-134a can exceed 3.0
Cooling EER with R-410A can exceed 15.0
Cooling EER with R-134a can exceed 7.0
Low load efficiency
Apply for Leed points
ASHRAE 15 / B-52 compliant without monitoring or ventilation
equipment.

Easy To Install
Compact modules fit through standard doorways and into elevators
Modules interconnect easily and quickly
All refrigeration systems are factory charged and run tested
Single point power up to 500 MCA
Programmable Logic Controller (PLC) System
Manual switch allows redundancy control as each module has a
processor allowing it to run even if master controller fails
Display at each module
Remote display option
Optional BAS Interface
Design Flexibility
Wide array of module combinations
Install only the capacity required at the time
Variable or constant flow options
Simple To Service
Service can often be performed on a convenient, non-emergency basis
Most components are standard, off the shelf design
Able to service one module while system is in operation

Side View
Load Water
Lockable High Voltage Circuit Breaker
Bussbar Duct
Low Voltage Controls
Compressors

Features
Independent refrigerant circuits
Highly Dependable
Multiple independent systems for redundancy
Comprehensive computer monitoring of operations (optional)
Automatic diagnostic recording of fault conditions
Rotates lead compressor every 24 hours
Simple To Operate
Large LCD screen displays information in plain English
Simple keypad provides control of unit operations
Source/Sink Water

Water-to-Water Heat Pump


CHILLER OPTIONS

*Standardized drawing of sample customer installation

Standard Modules (Constant Flow Design)

Dimensions
Standard

32

Width (A)

49 1/8

Depth (B)

64

Height (C)

Water-to-Water Heat Pump


CHILLER OPTIONS, Contd

*Standardized drawing of sample customer installation

Extended Headers

Dimensions

Variable Flow Design for Load and Source/Sink


Extended Headers on Load Side and Source/Sink Side

SOURCE/SINK
LOAD

32

Width (A)

78 1/8

Depth (B)

64

Height (C)

Water-to-Water Heat Pump


CHILLER OPTIONS, Contd

*Standardized drawing of sample customer installation

Variable Flow Design for Load Water


Constant Flow for Source/Sink
Extended Headers on Load Side

SOURCE/SINK
LOAD

Dimensions
Extended Headers (Load)

32

Width (A)

63 5/8

Depth (B)

64

Height (C)

Water-to-Water Heat Pump


CHILLER OPTIONS, Contd

*Standardized drawing of sample customer installation

Extended Headers (Source/Sink)

Dimensions

Variable Flow Design for Source/Sink Water


Constant Flow for Load Water
Extended Headers on Source/Sink Side

SOURCE/SINK
LOAD

32

Width (A)

63 5/8

Depth (B)

64

Height (C)

Water-to-Water Heat Pump


CHILLER OPTIONS, Contd

Variable Flow* or Constant Flow for Source/Sink


and/or Load Water Total Access Design
Standardized drawing of sample customer installation
*Required optional actuators.

Width (A)

56

56

Depth (B)

67

67

Height (C)

Dimensions

34

67

32

56

MS050X

34

MS010X, MS015X, MS020X, MS030X


MS070X

Water-to-Water Heat Pump


GENERAL DATA
MS010*
Compressor Type

Scroll

General Data Table


MS015*
MS020*
MS030*
Scroll

Dry Weight (lbs. each)


Normal Capacity (tons each)
Quantity
Oil Charge (pints)

Scroll

89
135
5
8.5
2
2
3.5
6.9
Brazed Plate Brazed Plate
Evaporator (Brazed Plate)
Weight (lbs. each)
80
80
Water Storage (gallons each)
1.9
1.9
Circuit Configuration
Dual
Dual
Quantity
1
1
Header System (gallons leaving water)
6
6
Brazed Plate Brazed Plate
Condenser
Weight (lbs. each)
90
90
Water Storage (gal. each)
2.4
2.4
Circuit Configuration
Dual
Dual
Quantity
1
1
Header System (gallons entering water)
6
6
R410A/R134a R410A/R134a
Refrigerant Type
Charge (lbs./circuit)
6.5
6.5
Number of Circuits
2
2
1110
1200
Operating Weight (lbs.)
950
1040
Shipping Weight (lbs.)

135
10
2
6.9
Brazed Plate
80
1.9
Dual
1
6
Brazed Plate
90
2.4
Dual
1
6
R410A/R134a
8
2
1200
1040

Scroll

MS050*

MS070*

MS085*

Scroll

Scroll

Scroll

146
353
390
15
25
32
2
2
2
6.9
14.4
13.3
Brazed Plate Brazed Plate Brazed Plate
105
180
243
2.9
4.8
7.3
Dual
Dual
Dual
1
1
1
6
6
6
Brazed Plate Brazed Plate Brazed Plate
135
220
313
4.1
6.6
10.1
Dual
Dual
Dual
1
1
1
6
6
6
R410A/R134a R410A/R134a R410A/R134a
12
18
24
2
2
2
1625
2000
2200
1450
1730
1900

Call Factory
Brazed Plate

Call Factory

Brazed Plate

Call Factory

R410A/R134a
Call Factory
Call Factory
Call Factory

*Covers both R-410A and R-134a refrigerants.

Multistack Glycol Solution Information


Low Temperature Operation with Glycol
In chilled water systems where water temperatures of less than 40F and ambient temperatures of 32 F are likely to occur, it is necessary to add a glycol-based heat transfer fluid to
the system. Both Ethylene and Propylene are available and they offer the same basic freeze and corrosion protection although there are performance differences in the solutions.
Note:
1. Ethylene and propylene glycol ratings are outside the scope of AHRI Standard 550/590 Certifications.
2. The effect of glycol in the condenser is negligible as it tends to mirror the properties of water as its temperature increases. No emphasis on derate on condenser capacity with
glycol is necessary in the selection process.

ETHYLENE GLYCOL
Ethylene %
10
20
30
40
50

Freeze Point
F
C
26
18
7
-7
-28

-3.3
-7.8
-13.9
-21.7
-33.3

Capacity

Power

Flow

Pressure Drop

0.996
0.986
0.978
0.966
0.955

0.999
0.998
0.996
0.993
0.991

1.035
1.06
1.092
1.131
1.182

1.096
1.219
1.352
1.53
1.751

PROPYLENE GLYCOL
Propylene %
10
20
30
40
50

Freeze Point
F
C
26
19
9
-5
-27

-3
-7
-13
-21
-33

Capacity

Power

Flow

Pressure Drop

0.987
0.975
0.962
0.946
0.929

0.992
0.985
0.978
0.971
0.965

1.01
1.028
1.05
1.078
1.116

1.068
1.147
1.248
1.366
1.481
9

Water-to-Water Heat Pump


HEATING PERFORMANCE: R-410A REFRIGERANT

MS010XN
Leaving Source
Water F
30F
35F
40F
45F
50F
55F
MS015XN
Leaving Source
Water F
30F
35F
40F
45F
50F
55F
MS020XN
Leaving Source
Water F
30F
35F
40F
45F
50F
55F
MS030XN
Leaving Source
Water F
30F
35F
40F
45F
50F
55F

Power
(kW)
11.5
11.3
11.2
11.1
11.0
10.9
Power
(kW)
15.8
15.8
15.8
15.8
15.9
15.9
Power
(kW)
20.8
20.7
20.6
20.6
20.6
20.6
Power
(kW)
29.8
29.9
30.0
30.2
30.4
30.7

110F
Heat
(MBH)
116.7
126.9
137.7
149.4
161.9
175.6
110F
Heat
(MBH)
173.4
187.1
202.1
218.5
236.3
255.9
110F
Heat
(MBH)
229.6
249.6
271.1
294.7
319.7
346.7
110F
Heat
(MBH)
343.3
371.9
402.9
436.5
472.7
511.8

LEAVING HOT WATER

Heat
COP
3.0
3.3
3.6
3.9
4.3
4.7
Heat
COP
3.2
3.5
3.7
4.0
4.4
4.7
Heat
COP
3.2
3.5
3.8
4.2
4.5
4.9
Heat
COP
3.4
3.6
3.9
4.2
4.6
4.9

120F
Power Heat
(kW) (MBH)
12.8 112.3
12.7 122.0
12.6 132.4
12.4 143.5
12.3 155.4
12.2 168.3
120F
Power Heat
(kW) (MBH)
17.7 170.2
17.7 183.1
17.7 197.1
17.7 212.3
17.7 228.9

120F
Power Heat
(kW) (MBH)
23.8 223.9
23.6 242.0
23.5 262.0
23.4 283.6
23.3 307.3
23.3 332.7
120F
Power Heat
(kW) (MBH)
33.3 334.4
33.4 360.9
33.5 389.8
33.7 420.9
33.8 454.7
34.1 491.3

Heat
COP
2.6
2.8
3.1
3.4
3.7
4.1
Heat
COP
2.8
3.0
3.3
3.5
3.8
Heat
COP
2.8
3.0
3.3
3.6
3.9
4.2
Heat
COP
2.9
3.2
3.4
3.7
3.9
4.2

125F
Power Heat
(kW) (MBH)
13.5 110.0
13.4 119.6
13.3 129.7
13.2 140.5
13.0 152.0
12.9 164.5
125F
Power Heat
(kW) (MBH)
18.8 168.6
18.8 181.1
18.8 194.6
18.8 209.3
18.8 225.2

125F
Power Heat
(kW) (MBH)
25.5 221.8
25.3 238.7
25.1 257.7
25.0 278.4
24.9 301.0
24.8 325.6
125F
Power Heat
(kW) (MBH)
35.3 330.0
37.5 350.2
35.5 383.2
35.6 413.3
35.8 445.7
36.0 480.7

Heat
COP
2.4
2.6
2.9
3.1
3.4
3.7
Heat
COP
2.6
2.8
3.0
3.3
3.5
Heat
COP
2.5
2.8
3.0
3.3
3.5
3.8
Heat
COP
2.7
2.9
3.2
3.4
3.7
3.9

130F
Power Heat
(kW) (MBH)
14.3 107.7
14.2 117.1
14.1 126.9
14.0 137.5
13.8 148.7
13.7 160.8
130F
Power Heat
(kW) (MBH)
19.9 167.0
19.9 179.1
19.9 192.2
19.9 206.3
19.9 221.7
130F
Power Heat
(kW) (MBH)
27.3 220.0
27.0 236.0
26.8 253.6
26.6 273.3
26.5 294.9
26.4 318.4
130F
Power Heat
(kW) (MBH)
37.4 325.9
37.5 350.2
37.6
37.6
37.7 405.4
35.8 436.6
38.0 470.3

Heat
COP
2.2
2.4
2.6
2.9
3.2
3.4
Heat
COP
2.5
2.6
2.8
3.0
3.3
Heat
COP
2.4
2.6
2.8
3.0
3.3
3.5
Heat
COP
2.6
2.7
2.9
3.2
3.4
3.6

135F
Power Heat
(kW) (MBH)
15.2 105.4
15.1 114.5
15.0 124.2
14.8 134.4
14.7 145.3
14.5 157.0
135F
Power Heat
(kW) (MBH)
21.2 165.3
21.2 177.0
21.2 189.7
21.1 203.4
21.1 218.2
135F
Power Heat
(kW) (MBH)
29.3 218.9
28.9 233.5
28.6 250.0
28.4 268.4
28.3 288.9
28.1 311.3
135F
Power Heat
(kW) (MBH)
39.6 321.8
39.7 345.0
39.8 370.2
39.9 397.7
40.0 427.4
40.2 459.7

Heat
COP
2.0
2.2
2.4
2.7
2.9
3.2
Heat
COP
2.3
2.5
2.6
2.8
3.0
Heat
COP
2.2
2.4
2.6
2.8
3.0
3.2
Heat
COP
2.4
2.5
2.7
2.9
3.1
3.4

For non-published performance ranges, please contact Multistack.

10

Water-to-Water Heat Pump


HEATING PERFORMANCE: R-410A REFRIGERANT

MS050XN
Leaving Source Power
Water F
(kW)
30F
46.1
35F
46.3
40F
46.6
45F
46.9
50F
47.2
55F
47.5
MS070XN
Leaving Source Power
Water F
(kW)
30F
59.7
35F
60.0
40F
60.4
45F
60.8
50F
61.3
55F
61.9
MS085XN
Leaving Source Power
Water F
(kW)
30F
35F
40F
45F
50F
55F

110F
Heat
(MBH)
558.1
605.5
656.7
712.5
773.4
839.4
110F
Heat
(MBH)
729.8
792.5
859.9
932.8
1011.5
1096.0
110F
Heat
(MBH)

LEAVING HOT WATER

Heat
COP
3.6
3.8
4.1
4.5
4.8
5.2
Heat
COP
3.6
3.9
4.2
4.5
4.8
5.2
Heat
COP

120F
Power Heat
(kW) (MBH)
51.4 544.6
51.7 588.6
52.0 636.4
52.3 688.5
52.6 745.1
52.8 806.4
120F
Power Heat
(kW) (MBH)
66.8 711.2
67.1 770.2
67.4 833.5
67.8 901.8
68.3 974.9
68.9 1053.2
120F
Power Heat
(kW) (MBH)

Heat
COP
3.1
3.3
3.6
3.9
4.2
4.5
Heat
COP
3.1
3.4
3.6
3.9
4.2
4.5
Heat
COP

125F
Power Heat
(kW) (MBH)
54.3 538.3
54.7 580.7
55.0 626.5
55.2 676.7
55.5 731.2
55.8 790.3
125F
Power Heat
(kW) (MBH)
70.7 702.3
71.0 759.4
71.3 820.7
71.7 886.2
72.2 956.8
72.7 1032.4
125F
Power Heat
(kW) (MBH)

Heat
COP
2.9
3.1
3.3
3.6
3.9
4.2
Heat
COP
2.9
3.1
3.4
3.6
3.9
4.2
Heat
COP

130F
Power Heat
(kW) (MBH)
57.4 532.2
57.8 572.8
58.1 617.1
58.4 665.2
58.7 717.6
58.9 774.6
130F
Power Heat
(kW) (MBH)
74.8 693.3
75.1 748.4
75.4 807.5
75.8 870.8
76.3 938.9
76.8 1011.7
130F
Power Heat
(kW) (MBH)

Heat
COP
2.7
2.9
3.1
3.3
3.6
3.9
Heat
COP
2.7
2.9
3.1
3.4
3.6
3.9
Heat
COP

135F
Power Heat
(kW) (MBH)
60.6 526.6
61.0 565.5
61.4 607.8
61.7 653.9
62.0 704.0
62.3 758.7
135F
Power Heat
(kW) (MBH)
79.4
79.8
80.2
80.6
81.2

737.7
794.5
855.5
921.1
990.6
135F
Power Heat
(kW) (MBH)

Heat
COP
2.5
2.7
2.9
3.1
3.3
3.6
Heat
COP
2.7
2.9
3.1
3.3
3.6
Heat
COP

r
o
t
c
a
Call F

For non-published performance ranges, please contact Multistack.

11

Water-to-Water Heat Pump


COOLING PERFORMANCE: R-410A REFRIGERANT

MS010XN
Leaving Source
Water F
75F
80F
85F
90F
95F
105F
MS015XN
Leaving Source
Water F
75F
80F
85F
90F
95F
105F
MS020XN
Leaving Source
Water F
75F
80F
85F
90F
95F
105F
MS030XN
Leaving Source
Water F
75F
80F
85F
90F
95F
105F

Power
(kW)
7.0
7.4
7.8
8.3
8.7
9.7
Power
(kW)
10.3
10.8
11.4
12.1
12.7
14.2
Power
(kW)
13.7
14.2
14.8
15.5
16.3
18.3
Power
(kW)
20.4
21.3
22.2
23.3
24.4
27.0

42F
Cool
(Tons)
11.6
11.3
11.1
10.8
10.5
9.8
42F
Cool
(Tons)
16.9
16.4
15.9
15.4
15.0
14.1
42F
Cool
(Tons)
23.0
22.5
22.0
21.4
20.8
22.7
42F
Cool
(Tons)
33.6
32.9
32.1
31.3
30.5
28.7

LEAVING CHILLED WATER

Cool
(EER)
19.9
18.4
17.0
15.7
14.5
12.2

Power
(kW)
7.0
7.4
7.8
8.2
8.7
9.7

Cool
(EER)
19.7
18.1
16.7
15.4
14.1
11.9

Power
(kW)
10.3
10.9
11.5
12.1
12.8
14.2

Cool
(EER)
20.2
19.1
17.9
16.6
15.3
14.9

Power
(kW)
13.7
14.2
14.8
15.5
16.3
18.2

Cool
(EER)
19.8
18.6
17.4
16.1
15.0
12.7

Power
(kW)
20.5
21.4
22.3
23.4
24.5
27.1

44F
Cool
(Tons)
12.0
11.8
11.5
11.2
10.9
10.3
44F
Cool
(Tons)
17.6
17.1
16.6
16.1
15.6
14.7
44F
Cool
(Tons)
23.8
23.3
22.8
22.2
21.6
20.2
44F
Cool
(Tons)
34.9
34.1
33.4
32.5
31.7
29.8

Cool
(EER)
20.7
19.2
17.7
16.4
15.1
12.7
Cool
(EER)
20.5
18.8
17.3
16.0
14.7
12.4
Cool
(EER)
20.9
19.7
18.5
17.2
15.9
13.3
Cool
(EER)
20.4
19.2
17.9
16.7
15.5
13.2

46F
Power Cool
(kW) (Tons)
7.0
12.5
7.4
12.3
7.8
12.0
8.2
11.7
8.6
11.4
9.6
10.7
46F
Power Cool
(kW) (Tons)
10.3
18.3
10.9
17.7
11.5
17.2
12.1
16.7
12.8
16.2
14.2
15.2
46F
Power Cool
(kW) (Tons)
13.7
24.6
14.2
24.2
14.8
23.6
15.5
23.0
16.3
22.4
18.3
21.0
46F
Power Cool
(kW) (Tons)
20.7
36.2
21.5
35.4
22.5
34.6
23.5
33.8
24.7
32.9
27.2
31.0

Cool
(EER)
21.6
20.0
18.5
17.1
15.8
13.3
Cool
(EER)
21.3
19.6
18.0
16.7
15.3
12.9
Cool
(EER)
21.5
20.4
19.1
17.8
16.5
13.8
Cool
(EER)
21.0
19.7
18.5
17.2
16.0
13.7

48F
Power Cool
(kW) (Tons)
6.9
13
7.3
12.7
7.7
12.4
8.2
12.1
8.6
11.8
9.6
11.1
48F
Power Cool
(kW) (Tons)
10.3
19.0
10.9
18.5
11.5
17.9
12.1
17.4
12.8
16.9
14.2
15.9
48F
Power Cool
(kW) (Tons)
13.7
25.5
14.2
25.0
14.8
24.5
15.5
23.9
16.3
23.3
18.3
21.8
48F
Power Cool
(kW) (Tons)
20.9
37.5
21.7
36.7
22.6
35.9
23.7
35.1
24.8
34.1
27.3
32.2

Cool
(EER)
22.5
20.9
19.3
17.9
16.5
13.9
Cool
(EER)
22.1
20.3
18.7
17.2
15.9
13.4
Cool
(EER)
22.2
21.1
19.8
18.4
17.1
14.3
Cool
(EER)
21.6
20.3
19.0
17.8
16.5
14.1

50F
Power Cool
(kW) (Tons)
6.9
13.5
7.3
13.2
7.7
12.9
8.1
12.6
8.6
12.3
9.5
11.6
50F
Power Cool
(kW) (Tons)
10.3
19.8
10.9
19.2
11.5
18.6
12.1
18.1
12.8
17.5
14.2
16.5
50F
Power Cool
(kW) (Tons)
13.8
26.3
14.3
25.9
14.9
25.3
15.6
24.8
16.4
24.1
18.3
22.7
50F
Power Cool
(kW) (Tons)
21.1
38.9
21.9
38.1
22.8
37.3
23.8
36.4
24.9
35.4
27.4
33.4

Cool
(EER)
23.4
21.7
20.2
18.7
17.2
14.6
Cool
(EER)
23.0
21.1
19.4
17.9
16.5
13.9
Cool
(EER)
22.9
21.7
20.4
19.1
17.7
14.9
Cool
(EER)
22.1
20.9
19.6
18.3
17.7
14.6

For non-published performance ranges, please contact Multistack.

12

Water-to-Water Heat Pump


COOLING PERFORMANCE: R-410A REFRIGERANT

MS050XN
Leaving Source Power
Water F
(kW)
75F
32.6
80F
34.1
85F
35.7
90F
37.5
95F
39.5
105F
43.8
MS070XN
Leaving Source Power
Water F
(kW)
75F
42.2
80F
44.1
85F
46.3
90F
48.6
95F
51.1
105F
53.8
MS085XN
Leaving Source Power
Water F
(kW)
75F
80F
85F
90F
95F
105F

42F
Cool
(Tons)
54.6
53.3
51.9
50.5
49.1
46.0
42F
Cool
(Tons)
71.4
69.7
67.9
66.1
64.3
62.4
42F
Cool
(Tons)

LEAVING CHILLED WATER

Cool
(EER)
20.1
18.8
17.4
16.1
14.9
12.6
Cool
(EER)
20.3
18.9
17.6
16.3
15.1
13.9
Cool
(EER)

44F
Power Cool
(kW) (Tons)
32.8
56.8
34.3
55.4
35.9
54.0
37.7
52.5
39.6
51.0
43.9
47.9
44F
Power Cool
(kW) (Tons)
42.5
74.2
44.4
72.4
46.5
70.6
48.8
68.8
51.3
66.8
54.0
64.9
44F
Power Cool
(kW) (Tons)

Cool
(EER)
20.8
19.4
18.0
16.7
15.5
13.1
Cool
(EER)
21.0
19.6
18.2
16.9
15.6
14.4
Cool
(EER)

46F
Power Cool
(kW) (Tons)
33.0
59.0
34.4
57.6
36.1
56.1
37.8
54.6
39.7
53.1
44.1
49.8
46F
Power Cool
(kW) (Tons)
42.8
77.1
44.7
75.3
46.8
73.4
49.1
71.4
51.5
69.5
54.2
67.4
46F
Power Cool
(kW) (Tons)

Cool
(EER)
21.5
20.1
18.7
17.3
16.0
13.6
Cool
(EER)
21.6
20.2
18.8
17.5
16.2
14.9
Cool
(EER)

48F
Power Cool
(kW) (Tons)
33.2
61.3
34.6
59.8
36.2
58.3
38.0
56.7
39.9
55.1
44.2
51.8
48F
Power Cool
(kW) (Tons)
43.1
80.1
45.0
78.2
47.1
76.2
49.3
74.2
51.8
72.1
54.5
70.0
48F
Power Cool
(kW) (Tons)

Cool
(EER)
22.2
20.7
19.3
17.9
16.6
14.1
Cool
(EER)
22.3
20.8
19.4
18.1
16.7
15.4
Cool
(EER)

50F
Power Cool
(kW) (Tons)
33.4
63.7
34.8
62.1
36.4
60.6
38.1
58.9
40.0
57.3
44.3
53.8
50F
Power Cool
(kW) (Tons)
43.5
83.1
45.3
81.1
47.4
79.1
49.6
77.0
52.0
74.9
54.7
72.7
50F
Power Cool
(kW) (Tons)

Cool
(EER)
22.9
21.4
20.0
18.6
17.2
14.6
Cool
(EER)
22.9
21.5
20.0
18.6
17.3
15.9
Cool
(EER)

r
o
t
c
a
Call F

For non-published performance ranges, please contact Multistack.

13

Water-to-Water Heat Pump


HEATING PERFORMANCE: R134a REFRIGERANT

MS010AN
Leaving Source
Water F
55F
53F
51F
49F
47F
45F
MS015AN
Leaving Source
Water F
55F
53F
51F
49F
47F
45F
MS020AN
Leaving Source
Water F
55F
53F
51F
49F
47F
45F
MS030AN
Leaving Source
Water F
55F
53F
51F
49F
47F
45F

LEAVING HOT WATER


Power
(kW)
9.8
9.8
9.8
9.8
9.7
9.7
Power
(kW)
15.3
15.3
15.3
15.3
15.3
15.3
Power
(kW)
19.9
19.9
19.9
19.8
19.8
19.7
Power
(kW)
25.1
25.1
25.0
25.0
25.0
25.0

140F
Heat
(MBH)
108.8
105.2
101.8
98.5
95.3
95.3
140F
Heat
(MBH)
151.1
147.1
143.1
139.3
135.6
135.6
140F
Heat
(MBH)
197.2
191.2
185.4
179.8
174.4
169.0
140F
Heat
(MBH)
269.1
260.7
252.4
244.4
236.5
228.7

Heat
COP
3.2
3.1
3.0
3.0
2.9
2.9

Power
(kW)
11.0
11.0
11.0
11.0
11.0
11.0

Heat
COP
2.9
2.8
2.7
2.7
2.6
2.6

Power
(kW)
17.2
17.2
17.2
17.3
17.3
17.3

Heat
COP
2.9
2.8
2.7
2.7
2.6
2.5

Power
(kW)
22.1
22.0
22.0
22.0
21.9
21.9

Heat
COP
3.1
3.0
3.0
2.9
2.8
2.7

Power
(kW)
28.1
28.1
28.1
28.1
28.1
28.0

150F
Heat
(MBH)
105.9
102.7
99.5
96.5
93.7
93.7
150F
Heat
(MBH)
146.2
142.4
138.8
135.2
131.8
131.8
150F
Heat
(MBH)
191.1
185.5
180.2
175.0
170.0
165.0
150F
Heat
(MBH)
260.3
252.1
244.1
236.3
228.5
221.0

Heat
COP
2.8
2.7
2.7
2.6
2.5
2.5
Heat
COP
2.5
2.4
2.4
2.3
2.2
2.2
Heat
COP
2.5
2.5
2.4
2.3
2.3
2.2
Heat
COP
2.7
2.6
2.5
2.5
2.4
2.3

155F
Power Heat
(kW) (MBH)
11.7 104.6
11.7 101.5
11.6
98.5
11.6
95.7
11.7
92.9
11.7
90.4
155F
Power Heat
(kW) (MBH)
18.3 143.6
18.3 140.0
18.3 136.5
18.4 133.2
18.4 129.9
18.4 129.9
155F
Power Heat
(kW) (MBH)
23.2 188.1
23.2 182.8
23.2 177.7
23.1 172.7
23.1 172.7
23.0 163.2
155F
Power Heat
(kW) (MBH)
29.8 255.8
29.8 247.7
29.8 239.8
29.7 232.1
29.7 224.4
28.0 221.0

Heat
COP
2.6
2.6
2.5
2.4
2.3
2.3
Heat
COP
2.3
2.2
2.2
2.1
2.1
2.1
Heat
COP
2.4
2.3
2.2
2.2
2.2
2.1
Heat
COP
2.5
2.4
2.4
2.3
2.2
2.3

160F
Power Heat
(kW) (MBH)
12.4 103.4
12.4 100.4
12.4
97.6
12.4
94.9
12.4
92.3

Heat
COP
2.5
2.4
2.3
2.2
2.2

160F
Power Heat
(kW) (MBH)
19.5 141.1
19.5 137.7
19.5 134.3
19.5 131.1
19.6 127.9

Heat
COP
2.1
2.1
2.0
2.0
1.9

160F
Power Heat
(kW) (MBH)
24.4 185.2
24.4 180.1
24.3 175.3
24.3 170.5
24.2 165.9

Heat
COP
2.2
2.2
2.1
2.1
2.0

160F
Power Heat
(kW) (MBH)
31.6 251.2
31.6 243.3
31.5 235.5
31.5 227.8
31.5 220.2

Heat
COP
2.3
2.3
2.2
2.1
2.0

175F
Power Heat
(kW) (MBH)
14.7 100.0
14.7
97.5
14.8
95.2
14.9
93.0

Heat
COP
2.0
1.9
1.9
1.8

175F
Power Heat
(kW) (MBH)
23.5 133.3
23.5 130.3
23.6 127.3
23.6 124.5

Heat
COP
1.7
1.6
1.6
1.5

175F
Power Heat
(kW) (MBH)
28.3 177.0
28.2 172.7
28.1 168.5
28.1 164.4

Heat
COP
1.8
1.8
1.8
1.7

175F
Power Heat
(kW) (MBH)
37.6 237.1
37.5 229.4
37.5 221.9
27.5 214.5

Heat
COP
1.8
1.8
1.7
1.7

For non-published performance ranges, please contact Multistack.

14

Water-to-Water Heat Pump


HEATING PERFORMANCE: R134a REFRIGERANT

MS050AN
Leaving Source Power
Water F
(kW)
55F
43.3
53F
43.2
51F
43.1
49F
42.9
47F
42.8
45F
42.7
MS070AN
Leaving Source Power
Water F
(kW)
55F
55.2
53F
55.1
51F
54.9
49F
54.7
47F
54.6
45F
54.4
MS085AN
Leaving Source Power
Water F
(kW)
55F
53F
51F
49F
47F
45F

140F
Heat
(MBH)
511.4
494.8
478.9
463.5
448.7
434.5
140F
Heat
(MBH)
662.2
640.6
619.9
599.8
580.6
562.1
140F
Heat
(MBH)

LEAVING HOT WATER

Heat
COP
3.5
3.4
3.3
3.2
3.1
3.0
Heat
COP
3.5
3.4
3.3
3.2
3.1
3.0
Heat
COP

150F
Power Heat
(kW) (MBH)
48.5 502.5
48.4 486.9
48.4 472.3
48.3 458.1
48.3 444.5
48.3 431.5
150F
Power Heat
(kW) (MBH)
61.9 650.1
61.8 630.1
61.7 610.9
61.6 592.4
61.6 574.7
61.6 557.7
150F
Power Heat
(kW) (MBH)

Heat
COP
3.0
2.9
2.9
2.8
2.7
2.6
Heat
COP
3.1
3.0
2.9
2.8
2.7
2.7
Heat
COP

155F
Power Heat
(kW) (MBH)
51.5 499.1
51.5 484.4
51.5 470.2
51.5 456.7
51.5 443.8
51.6 431.6
155F
Power Heat
(kW) (MBH)
65.7 645.5
65.7 626.3
65.7 607.9
65.7 590.3
65.7 573.6
65.8 557.5
155F
Power Heat
(kW) (MBH)

Heat
COP
2.9
2.8
2.7
2.6
2.5
2.5
Heat
COP
2.9
2.8
2.7
2.6
2.6
2.5
Heat
COP

160F
Power Heat
(kW) (MBH)
54.9 496.7
54.9 482.6
54.9 469.2
55.0 456.5
55.1 444.3

Heat
COP
2.7
2.6
2.5
2.4
2.4

160F
Power Heat
(kW) (MBH)
70.0 642.1
70.0 623.8
70.1 606.5
70.2 589.7
70.3 573.7

Heat
COP
2.7
2.6
2.5
2.5
2.4

160F
Power Heat
(kW) (MBH)

Heat
COP

175F
Power Heat
(kW) (MBH)
67.1 496.3
67.4 484.7
67.7 473.4
68.1 463.0

Heat
COP
2.2
2.1
2.0
2.0

175F
Power Heat
(kW) (MBH)
85.7 640.8
86.0 625.4
86.4 610.7
86.8 597.0

Heat
COP
2.2
2.1
2.1
2.0

175F
Power Heat
(kW) (MBH)

Heat
COP

y
r
o
t
c
ll Fa

Ca

For non-published performance ranges, please contact Multistack.

15

Water-to-Water Heat Pump


COOLING PERFORMANCE: R134a REFRIGERANT

MS010AN
Leaving Source
Water F
100F
105F
110F
115F
120F
125F
MS015AN
Leaving Source
Water F
100F
105F
110F
115F
120F
125F
MS020AN
Leaving Source
Water F
100F
105F
110F
115F
120F
125F
MS030AN
Leaving Source
Water F
100F
105F
110F
115F
120F
125F

Power
(kW)
5.6
5.9
6.2
6.5
6.9
7.3
Power
(kW)
9.1
9.6
10.2
10.8
11.4
12.1
Power
(kW)
11.9
12.6
13.3
14.0
14.8
15.7
Power
(kW)
15.1
15.9
16.8
17.7
18.7
19.8

35F
Cool
(Tons)
5.6
5.4
5.3
5.1
5.0
4.8
35F
Cool
(Tons)
8.2
7.9
7.7
7.4
7.1
6.8
35F
Cool
(Tons)
10.0
9.7
9.4
9.0
8.7
8.3
35F
Cool
(Tons)
14.3
13.8
13.4
12.9
12.4
11.8

LEAVING CHILLED WATER

Cool
(EER)
11.9
11.1
10.2
9.4
8.6
7.9
Cool
(EER)
10.8
9.9
9.0
8.2
7.5
6.8
Cool
(EER)
10.1
9.3
8.5
7.7
7.0
6.4
Cool
(EER)
11.4
10.4
9.6
8.7
7.9
7.2

40F
Power Cool
(kW) (Tons)
5.7
6.3
6.0
6.1
6.3
5.9
6.6
5.8
7.0
5.6
7.4
5.4
40F
Power Cool
(kW) (Tons)
9.1
9.0
9.6
8.8
10.2
8.5
10.8
8.2
11.4
7.9
12.1
7.6
40F
Power Cool
(kW) (Tons)
12.0
11.3
12.7
10.9
13.4
10.5
14.2
10.2
15.0
9.8
15.8
9.4
40F
Power Cool
(kW) (Tons)
15.2
15.8
16.0
15.4
16.8
14.9
17.8
14.4
18.8
13.9
19.9
13.3

Cool
(EER)
13.2
12.2
11.3
10.4
9.6
8.8
Cool
(EER)
11.9
10.9
10.0
9.1
8.3
7.5
Cool
(EER)
11.2
10.3
9.4
8.6
7.8
7.1
Cool
(EER)
12.5
11.6
10.6
9.7
8.9
8.1

45F
Power Cool
(kW) (Tons)
5.8
7.0
6.1
6.8
6.4
6.6
6.7
6.5
7.1
6.3
7.5
6.1
45F
Power Cool
(kW) (Tons)
9.2
10.0
9.7
9.7
10.2
9.4
10.8
9.0
11.4
8.7
12.1
8.4
45F
Power Cool
(kW) (Tons)
12.2
12.6
12.8
12.2
13.6
11.8
14.3
11.4
15.1
11.0
15.9
10.5
45F
Power Cool
(kW) (Tons)
15.3
17.5
16.1
17.0
16.9
16.5
17.9
16.0
18.8
15.5
19.9
14.9

Cool
(EER)
14.5
13.5
12.5
11.5
10.6
9.7
Cool
(EER)
13.1
12.0
11.0
10.1
9.2
8.3
Cool
(EER)
12.4
11.4
10.4
9.5
8.7
7.9
Cool
(EER)
13.7
12.7
11.7
10.8
9.9
9.0

50F
Power Cool
(kW) (Tons)
5.9
7.9
6.2
7.6
6.5
7.4
6.8
7.2
7.2
7.0
7.6
6.8
50F
Power Cool
(kW) (Tons)
9.2
11.0
9.7
10.7
10.2
10.3
10.8
10.0
11.4
9.6
12.1
9.2
50F
Power Cool
(kW) (Tons)
12.3
14.0
13.0
13.6
13.7
13.1
14.4
12.7
15.2
12.2
16.0
11.8
50F
Power Cool
(kW) (Tons)
15.5
19.3
16.2
18.8
17.1
18.3
18.0
17.7
18.9
17.2
20.0
16.6

Cool
(EER)
16.0
14.8
13.7
12.7
11.7
10.7
Cool
(EER)
14.4
13.2
12.1
11.1
10.1
9.2
Cool
(EER)
13.6
12.6
11.5
10.6
9.7
8.8
Cool
(EER)
15.0
13.9
12.9
11.8
10.9
10.0

55F
Power Cool
(kW) (Tons)
6.0
8.7
6.3
8.5
6.6
8.3
6.9
8.0
7.3
7.8
7.7
7.6
55F
Power Cool
(kW) (Tons)
9.2
12.1
9.7
11.7
10.2
11.4
10.8
10.3
11.4
10.6
12.1
10.2
55F
Power Cool
(kW) (Tons)
12.4
15.5
13.0
15.0
13.7
14.6
14.5
14.1
15.3
13.6
16.1
13.1
55F
Power Cool
(kW) (Tons)
15.7
21.1
16.4
20.6
17.2
20.1
18.1
19.5
19.1
18.9
20.1
18.3

Cool
(EER)
17.6
16.3
15.1
13.9
12.9
11.8
Cool
(EER)
15.8
14.5
13.3
11.4
11.1
10.1
Cool
(EER)
15.0
13.8
12.7
11.7
10.7
9.8
Cool
(EER)
16.2
15.1
14.0
12.9
11.9
10.9

For non-published performance ranges, please contact Multistack.

16

Water-to-Water Heat Pump


COOLING PERFORMANCE: R134a REFRIGERANT

MS050AN
Leaving Source Power
Water F
(kW)
100F
27.1
105F
28.5
110F
30.0
115F
31.5
120F
33.2
125F
35.0
MS070AN
Leaving Source Power
Water F
(kW)
100F
34.5
105F
36.3
110F
38.1
115F
40.1
120F
42.2
125F
44.6
MS085AN
Leaving Source Power
Water F
(kW)
100F
105F
110F
115F
120F
125F

35F
Cool
(Tons)
25.4
24.7
24.0
23.3
22.6
21.9
35F
Cool
(Tons)
33.1
32.2
31.3
30.4
29.5
28.6
35F
Cool
(Tons)

LEAVING CHILLED WATER

Cool
(EER)
11.2
10.4
9.6
8.9
8.2
7.5
Cool
(EER)
11.5
10.6
9.8
9.1
8.4
7.7
Cool
(EER)

40F
Power Cool
(kW) (Tons)
27.4
28.4
28.9
27.7
30.8
29.1
32.0
26.1
33.6
25.4
35.4
24.6
40F
Power Cool
(kW) (Tons)
34.9
37.0
36.8
36.1
38.7
35.1
40.7
34.1
42.8
33.0
45.1
32.0
40F
Power Cool
(kW) (Tons)

Cool
(EER)
12.4
11.5
11.3
9.8
9.1
8.3
Cool
(EER)
12.7
11.8
10.9
10.0
9.3
8.5
Cool
(EER)

45F
Power Cool
(kW) (Tons)
27.7
31.8
29.2
30.9
30.8
30.1
32.4
29.2
34.0
28.4
35.8
27.5
45F
Power Cool
(kW) (Tons)
35.2
41.4
37.2
40.3
39.2
39.2
41.2
38.1
43.4
36.9
45.6
35.8
45F
Power Cool
(kW) (Tons)

Cool
(EER)
13.8
12.7
11.7
10.8
10.0
9.2
Cool
(EER)
14.1
13.0
12.0
11.1
10.2
9.4
Cool
(EER)

50F
Power Cool
(kW) (Tons)
27.8
35.4
29.4
34.4
31.1
33.5
32.8
32.6
34.5
31.6
36.3
30.7
50F
Power Cool
(kW) (Tons)
35.5
46.1
37.5
44.9
39.6
43.7
41.7
42.4
43.9
41.2
46.2
40.0
50F
Power Cool
(kW) (Tons)

Cool
(EER)
15.3
14.0
12.9
11.9
11.0
10.2
Cool
(EER)
15.7
14.4
13.2
12.2
11.3
10.4
Cool
(EER)

55F
Power Cool
(kW) (Tons)
27.7
39.3
29.6
38.3
31.3
37.2
33.1
36.2
34.8
35.2
36.7
34.1
55F
Power Cool
(kW) (Tons)
35.3
51.2
37.6
49.9
39.9
48.5
42.1
47.2
44.4
45.8
46.7
44.5
55F
Power Cool
(kW) (Tons)

Cool
(EER)
17.0
15.5
14.3
13.1
12.1
11.2
Cool
(EER)
17.4
15.9
14.6
13.4
12.4
11.4
Cool
(EER)

r
o
t
c
a
Call F

For non-published performance ranges, please contact Multistack.

17

Water-to-Water Heat Pump


ELECTRICAL DATA
External Input/Output Connections

18

Water-to-Water Heat Pump


ELECTRICAL DATA, Contd.
System Wire & Fuse Sizing Specifications
(Applicable codes may require different wire sizing)

1. Compressor Rated Load Amps (RLA) and Locked Rotor Amps (LRA)
Data: RLA/LRA
R410A

VOLTAGE

208

230

460

R134a

575

VOLTAGE

208

230

460

575

23.5/128

21/128

10.2/63

8.2/49

MS010XN

22.8/123

20.6/123

10.3/62

8.4/50

MS010AN

MS015XN

36.5/225

33/225

16.5/114

13/80

MS015AN

38.7/225

35/225

17.5/114

14/80

MS020XN

44/239

40/239

20/125

16/80

MS020AN

44/239

40/239

20/125

16/80

MS030XN

68/340

61/340

31/173

25/132

MS030AN

61/300

55/300

27/150

22/109

MS050XN

101/605

91/605

46/272

37/215

MS050AN

100/500

90/500

46/250

37/198

MS070XN

133/599

120/599

60/310

48/239

MS070AN

127/599

114/599

58/310

47/239

MS085XN

MS085XN

Call Factory

Note: RLA and LRA is per compressor. Two compressors per module.

2. Wiring Sizing: Minimum Circuit Ampacity (MCA)


MCA = (1.25 x RLA1*) + RLA2 + RLA3
MCA

50
65
85
100
115
130
150
175
200
230
255
285
300
350
400
460
500

6
3 CONDUCTORS CONDUCTORS
1 CONDUIT
2 CONDUIT

8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM
300 MCM

1/0
2/0
3/0
4/0
4/0
250 MCM

Call Factory

Note: RLA and LRA is per compressor. Two compressors per module.

3. Fuse Sizing: Maximum Fuse (MF), Type RK5 Fuse


MF= (2.25 x RLA1*) + RLA2 + RLA3
Where the MF does not equal a standard size fuse, the next larger size should be
used.
4. Standard modules short circuit current rating: SCCR=5kA
NOTES:
A.*RLA1 = RLA of the largest compressor in the system. RLA2 & RLA3 = RLA of the
other compressors in the system.
B. The total system Minimum Circuit Ampacity (aMCA) shall not exceed 500A.
C. Wire sizing is based on the Nat. Electr. Code (NEC) rating for 75C copper wire,
with 3 wires per conduit.
D. Wiring Distance from branch circuit shall not exceed 100ft.

19

Water-to-Water Heat Pump


CONTROLLER SCHEMATICS

Chiller Data
ENT. LOAD WATER TEMP.

LOAD WATER PUMP OPERATION

LVG. LOAD WATER TEMP

SOURCE/SINK WATER PUMP OPERATION

VERIFY LOAD WATER FLOW

FAULT NOTIFICATION

ENT. SOURCE/SINK WATER TEMP

FULL LOAD RELAY

LVG. SOURCE/SINK WATER TEMP

CHILLED WATER CONTROLS

VERIFY SOURCE/SINK WATER FLOW

HOT WATER CONTROLS

BUILDING AUTOMATION
SOLUTIONS
INTEROPERABILITY
PORTALS

CUSTOMER INTERLOCKS
LOAD WATER , OR LOAD LIMIT RESET INPUT

RS485 Serial Card

MASTER CONTROL
Can stage a maximum of 15 modules

PCO Net RS485 Interface Board

(30 compressors)

REMOTE DISPLAY

Module Data

(optional)

MODULE CONTROL PANEL


DATA FROM REFRIGERATION SYSTEM A
DATA FROM REFRIGERATION SYSTEM B
HP TRANSDUCER
HIGH PRESSURE SWITCH
LP TRANSDUCER
COMP. MOTOR PROTECTION

HP TRANSDUCER
HIGH PRESSURE SWITCH
LP TRANSDUCER
COMP. MOTOR PROTECTION

BACNET

MSTP
ETHERNET
TCP/IP

MODBUS (RTU)

SUCTION TEMPERATURE

SUCTION TEMPERATURE

LVG. LOAD WATER TEMP

LVG. LOAD WATER TEMP

SNMP PROTOCOL

CIRCUIT FAULT CONDITION

CIRCUIT FAULT CONDITION

LONMARK

LVG. SOURCE/SINK WATER TEMP

LVG. SOURCE/SINK WATER TEMP


HIGH VOLTAGE CONTROL PANEL
CIRCUIT A COMPRESSOR CONTACTOR
CIRCUIT B COMPRESSOR CONTACTOR

20

PCO Web Ethernet Interface Board

Water-to-Water Heat Pump


PIPING SCHEMATICS
Required Load Water Piping

PRESSURE TAPS

SUPPLIED AND INSTALLED BY MULTISTACK

1/2 SENSOR POCKETS SUPPLIED BY MULTISTACK

STRAINER ISOLATION VALVE

Installation of sensor pocket (weld-a let) is recommended


at 30 from end of chiller, supplied and installed by others.

SUPPLIED AND INSTALLED BY OTHERS

EVAPORATOR WATER PUMP

STANDARD Y STRAINER

SUPPLIED AND INSTALLED BY OTHERS

SUPPLIED AND INSTALLED BY OTHERS.


NOTE: SELECT STRAINER BASED ON
WATER QUALITY

SP

FROM BUILDING LOAD

SP

TO BUILDING LOAD
FS

MULTISTACK CHILLER
EVAPORATOR ISOLATION VALVES
SUPPLIED AND INSTALLED BY OTHERS

FLOW SWITCH

SUPPLIED AND INSTALLED BY OTHERS

Required Source/Sink Water Piping

PRESSURE TAPS

SUPPLIED AND INSTALLED BY MULTISTACK

1/2 SENSOR POCKETS SUPPLIED BY MULTISTACK

Installation of sensor pocket (weld-a-let) is recommended


at 30 from end of chiller, supplied and installed by others.

FLOW SWITCH

CONDENSER ISOLATION VALVES

SUPPLIED AND INSTALLED BY


OTHERS

SUPPLIED AND INSTALLED BY OTHERS

FS

SP

TO SOURCE/SINK LOAD

SP

FROM SOURCE/SINK LOAD

MULTISTACK CHILLER
STRAINER ISOLATION VALVE
SUPPLIED AND INSTALLED BY
OTHERS

STANDARD Y STRAINER

SUPPLIED AND INSTALLED BY OTHERS.


NOTE: SELECT STRAINER MESH BASED ON
WATER QUALITY

SOURCE/SINK WATER PUMP

SUPPLIED AND INSTALLED BY OTHERS

3-WAY SOURCE/SINK
BY-PASS VALVE

SUPPLIED AND INSTALLED IN


BUILDING BY OTHERS
* May be required if tying into
additional heat rejection equipment
like a ground source, cooling tower
or dry cooler.

21

Water-to-Water Heat Pump


MECHANICAL SPECIFICATIONS
PART 2 PRODUCTS
2.01 Operating Conditions
A. Provide water-to-water heat pump with the capacity as scheduled on drawings
at job site elevation listed in Section 15050.
B. Heat Pump shall be designed to operate using R-410A or R-134a Refrigerant.
C. Heat Pump shall be designed for parallel evaporator water flow.
D. The liquid to be heated and cooled will be water containing corrosion inhibitors.
E. Heat Pump shall be designed to operate using ____ volt, 3 phase, 60Hz
electrical power supply.
2.02 Water-to-Water Packaged Heat Pump
A. Approved manufacturer is MULTISTACK.
B. System Description: Heat Pump shall incorporate Scroll-type compressors and
consist of multiple refrigerant circuits. Each refrigerant circuit shall consist of
an individual compressor, condenser, evaporator circuit, thermal expansion
valve, reversing valve, and control system. Each circuit shall be constructed to
be independent of other circuits from a refrigeration and electrical stand-point.
The multi-circuit heat pump must be able to produce chilled water even in the
event of a failure of one or more refrigerant circuits. Circuits shall not contain
more than 20 lb. of R-410a refrigerant.
C. General
1. Heat Pump Modules shall be ETL listed in accordance with UL Standard
1995, CSA certified per Standard C22.2#236, and bear the ASME UM
stamp on all heat exchangers (not applicable for modules with R-410A
refrigerant).
2. Modules shall ship wired and charged with refrigerant. All modules shall be
factory run tested prior to shipment.
3. Compressors, heat exchangers, piping and controls shall be mounted on a
heavy gauge steel frame. Electrical controls, contactors, and relays for each
module shall be mounted within that module.
D. Water Mains: Each module shall include supply and return mains for both
load and source-sink water. Grooved end connections are provided for
interconnection to six inch standard (6.625 outside diameter) piping with
Victaulic type couplings.
E. Heat Exchangers: Each load and source-sink heat exchanger shall be brazed
plate heat exchangers constructed of 316 stainless steel; designed, tested,
and stamped in accordance with UL code 1995 for 650 psig working pressure
on load and source-sink heat exchangers. Heat exchangers shall be mounted
below the compressor, to eliminate the effect of migration of refrigerant to the
cold evaporator with consequent liquid slugging on start-up.
F. Compressor: Each module shall contain two hermetic scroll compressors
independently circuited and with internal spring isolation mounted to the
module with rubber-in-shear isolators. Each system also includes high discharge
pressure and low suction pressure manual reset safety cut-outs.
G. Central Control System.
1. Scheduling of the various compressors shall be performed by a
microprocessor based control system (Master Controller). A new lead
compressor is selected every 24 hours to assure even distribution of
compressor run time.

22

2. The Master Controller shall monitor and report the following on each
refrigeration system:
a. Discharge Pressure Fault
b. Suction Pressure Fault
c. Compressor Winding Temperature
d. Suction Temperature
e. Load Leaving Water Temp.
f. Source-Sink Leaving Water Temp.
3. The Master Controller shall monitor and report the following system
parameters:
a. Load Water Entering and Leaving Temperature
b. Source-Sink Water Entering and Leaving Temperature
c. Load Water and Source-Sink Water Flow
4. An out of tolerance indication from these controls or sensors shall cause a
fault indication at the Master Controller and shutdown of that compressor
with the transfer of load requirements to the next available compressor. In
the case of a System Fault the entire heat pump will be shut down. When
a fault occurs, the Master Controller shall record conditions at the time of
the fault and store the data for recall. This information shall be capable of
being recalled through the keypad of the Master Controller and displayed
on the Master Controllers semigraphical display. A history of faults shall be
maintained including date and time of day of each fault (up to the last 20
occurrences).
5. Individual monitoring of leaving water temperatures from each
refrigeration system shall be programmed to protect against heat
exchanger freeze-up.
6. The control system shall monitor entering and leaving water temperatures
to determine system load and select the number of compressor circuits
required to operate. Response times and set points shall be adjustable. The
system shall provide for variable time between compressor sequencing and
temperature sensing, so as to fine tune the heat pump to different existing
building conditions.
7. Optionally, the Heat pump shall be capable of interfacing with the Building
Automation System via an Interoperability Web Portal.
8. The heat pump mode (heating or cooling) shall be selected by an external
dry contact interlock to the Master Controller. If no interlock is present, or
in the event of a reversing valve solenoid failure, the system shall revert to
heating mode.
H. Heat pump shall have a single point power connection and external inputs
and outputs to be compatible with the building management system. Inputs/
Outputs include:
1. Remote Start/Stop
2. Cooling Alarm
I. Each inlet water header shall incorporate a built in 30-mesh in-line strainer
system to prevent heat exchanger fouling.

Water-to-Water Heat Pump


MECHANICAL SPECIFICATIONS, contd
2.03 SAFETIES, CONTROLS AND OPERATION
A. Heat pump safety controls system shall be provided with the unit
(minimum) as follows:
1. Low refrigerant pressure
2. Loss of flow through the source/sink heat exchanger
3. Loss of flow through the load heat exchanger
4. High refrigerant pressure
5. High compressor motor temperature
6. Low suction gas temperature
7. Low leaving water temperature
B. Failure of heat pump to start or heat pump shutdown due to any of the above
safety cutouts shall be enunciated by display of the appropriate diagnostic
description at the unit control panel. This annunciation will be in plain English.
Alphanumeric codes shall be unacceptable.
C. The heat pump shall be furnished with a Master Controller as an integral portion
of the heat pump control circuitry to provide the following functions:
1. Provide automatic heat pump shutdown during periods when the load level
decreases below the normal operating requirements of the heat pump. Upon an
increase in load, the heat pump shall automatically restart.
2. Provisions for connection to automatically enable the heat pump from a
remote energy management system.
3. The control panel shall provide alphanumeric display showing all system
parameters in the English language with numeric data in English units.
D. Normal Heat Pump Operation
1. When heat pump is enabled, the factory supplied Master Controller
modulates the heat pump capacity from minimum to maximum as required
by building load.
2. The heat pump control system shall respond to Entering Water Temperature
and will have an integral reset based on entering water temperature to
provide for efficient operation at part-load conditions.
3. The operating mode (heating or cooling) shall be determined by a customer
provided dry contact interlock.
E. Power Phase Monitor
1. Provide a Power Phase Monitor on the incoming power supply to the heat
pump. This device shall prevent the heat pump from operating during
periods when the incoming power is unsuitable for proper operation.
2. The Power Phase Monitor shall provide protection against
the following conditions:
a. Low Voltage (Brown-Out)
b. Phase Rotation
c. Loss of Phase
d. Phase Imbalance

PART 3 INSTALLATION
3.01 PIPING SYSTEM FLUSHING PROCEDURE
A. A. Prior to connecting the heat pump to the condenser and chilled water
loop, the piping loops shall be flushed with a detergent and hot water (110130 F) mixture to remove previously accumulated dirt and other organic .
In old piping systems with heavy encrustation of inorganic materials consult
a water treatment specialist for proper passivation and/or removal of these
contaminants.
B. During the flushing 30 mesh (max.) Y-strainers (or acceptable equivalent) shall
be in place in the system piping and examined periodically as necessary to
remove collected residue. The flushing process shall take no less than 6 hours or
until the strainers when examined after each flushing are clean. Old systems with
heavy encrustation shall be flushed for a minimum of 24 hours and may take as
long as 48 hours before the filters run clean. Detergent and acid concentrations
shall be used in strict accordance with the respective chemical manufacturers
instructions. After flushing with the detergent and/or dilute acid concentrations
the system loop shall be purged with clean water for at least one hour to ensure
that all residual cleaning chemicals have been flushed out.
C. Prior to supplying water to the heat pump the Water Treatment Specification
shall be consulted for requirements regarding the water quality during heat
pump operation. The appropriate heat pump manufacturers service literature
shall be available to the operator and/or service contractor and consulted for
guidelines concerning preventative maintenance and off-season shutdown
procedures.
3.02 Water Treatment Requirements
A. Supply water for both the chilled water and condenser water
circuits shall be analyzed and treated by a professional water
treatment specialist who is familiar with the operating conditions
and materials of construction specified for the heat pumps heat
exchangers, headers and associated piping. Cycles of
concentration shall be controlled such that recirculated water
quality for modular heat pumps using 316 stainless steel brazed
plate heat exchangers and carbon steel headers is maintained
within the following parameters:
1. pH Greater than 7 and less than 9
2. Total Dissolved Solids (TDS) Less than 1000 ppm
3. Hardness as CaCO3 30 to 500 ppm
4. Alkalinity as Ca CO3 30 to 500 ppm
5. Chlorides Less than 200 ppm
6. Sulfates Less than 200 ppm

23

Environmentally Friendly Refrigerants


R-410A and R-134a
Refrigerant R-410A and R-134a are widely available, safe, and environmentally friendly refrigerants. R-410A is available in virtually all Multistack systems making hot
water up to 140F and R-134a is available in machines making hot water up to 180F. Good environmental choices!
Environmental Focus
In addition to providing products to deliver reliable comfort and low operating cost, Multistacks products can also reduce your environmental footprint. We are
committed to developing and manufacturing cooling and heating products that can reduce fossil fuel consumption and operate on the refrigerants designed to
protect the environment. Dedicated heat recovery chillers, water-to-water heat pumps and efficiency improvements across our product line are the result of this focus.

Originators

Multistack invented the modular water chiller. It started with a radically simple idea: chiller modules that could be brought into the equipment room one at a time,
through standard doorways and down elevators, to form a fully integrated chiller system. The idea launched a revolution and transformed Multistack into a leader in
the commercial water-chiller industry.

Innovators

Multistack perfected the modular chiller and leads the industry in innovative and environmentally friendly modular solutions. Since founding in the late 1980s,
Multistack has engineered, manufactured, and distributed an impressive array of modular air conditioning firsts: the first on-board strainer, the first modular
automatic blow-down device, the first modular chiller for variable flow, the first modular chiller-heater (heat pump), the first modular heat-recovery chiller, the first
modular air-to-water heat pump, the first modular chiller to utilize MagLev compressor technology, and the first modular chiller to utilize R-410A.

Never the Imitators