The FIOD series products add digital capability to your PLC / SCADA. FIOD 0808 model has 8 digital inputs and 8 relay / transistor (PNP/NPN) outputs. The digital inputs and outputs are isolated from the host device. It has one (2 Wire RS485) communication port. The COM port is used to connect any modbus master device (PLC / SCADA / Operator Interface device). This module supports Modbus RTU (Slave) protocol.
support@renuelectronics.com
Website:
www.renuelectronics.com
70.
00
35
.00
100.00
support@renuelectronics.com
Website:
www.renuelectronics.com
4. 5. 6. 7. 8. 9. 10.
Communication Port I/O Terminals Operating Temperature Storage Temperature Humidity Mounting Dimensions (DIN rail)
: : : : : : :
Communication Parameters And Modbus Tag Definition Unit supports MODBUS driver for communication with Master device. COM Port Setting:
1 2 3 4 5 6 7 8 9 10
support@renuelectronics.com
Website:
www.renuelectronics.com
UNIT ID 1 2 . . . . 64
ADDR6 0 0
ADDR5 0 0
ADDR4 0 0
ADDR3 0 0
ADDR2 0 0
ADDR1 0 1
BAUD2 0 0 1 1
BAUD1 0 1 0 1
PARITY2 0 0 1
PARITY1 0 1 0
The following dedicated modbus registers are assigned to digital inputs and digital outputs. Digital I/P MODBUS Tag. Input Register I/P1 (X0) I/P2 (X1) I/P3 (X2) I/P4 (X3) I/P5 (X4) I/P6 (X5) I/P7 (X6) I/P8 (X7) 40001_0 40001_1 40001_2 40001_3 40001_4 40001_5 40001_6 40001_7 (Bit 0) (Bit 1) (Bit 2) (Bit 3) (Bit 4) (Bit 5) (Bit 6) (Bit 7) Input Coil 00001 00002 00003 00004 00005 00006 00007 00008
support@renuelectronics.com
Website:
www.renuelectronics.com
Type
Default
Valid Range
Description
40070
Communication Timeout for own frame Communication timeout for ideal communication line
Retentive 0
40071
Retentive 0
Retentive 0
1 or 0
Holds the communication timeout value. If unit doesnt reveive its own frame within this timeout period, it declares communication break. Holds the communication timeout value. If communication line is completely ideal (No frame from master for other slaves also) within this timeout period, unit declares communication break. If 1, timeout value from 40070 is selected If 0, timeout value from 40071 is selected
Note: The default timeout is 10sec. In case of communication break with the host all the outputs are switched OFF after the timeout period is over.
support@renuelectronics.com
Website:
www.renuelectronics.com
GND GND B A
TERM TERM REST REST
GND B A
M A S T E R
NC DC+ DCDC-
support@renuelectronics.com
Website:
www.renuelectronics.com
FIOD Unit 1
B A
FIOD Unit 2
FIOD Unit n
support@renuelectronics.com
Website:
www.renuelectronics.com
GND GND B A
TERM TERM REST REST
EARTH
SW1 SW2
X0 X1
SW8 24VDC
X7
+ IP COM
support@renuelectronics.com
Website:
www.renuelectronics.com
For FIOD-0808-R-B
Coil supply (+) Coil supply (-) RLY POLE 1 Y0 (NO) Y1 (NO) Y2 (NO) Y3 (NO)
L1
L2
L3
L4
N 230 VAC
L5
L6
L7
L8
support@renuelectronics.com
Website:
www.renuelectronics.com
For FIOD-0808-C-B
FIOD-0808-C-B
24 VDC Y0 INTERNAL CIRCUIT
LOAD
Max 500mA
+ 24 VDC -
OP COM
For FIOD-0808-P-B
FIOD-0808-P-B
24 VDC
+ 24 VDC -
LOAD
Max 500mA
support@renuelectronics.com
Website:
www.renuelectronics.com
10
MANUAL REVISION If you contact us in reference to this manual, please include the following document number Name : User Manual For FIOD0808 Part Number : URML403 Document : UMAN\FIOD-0808 10WAY\1106 Revision : 3
Revision Number Rev 1 Rev 2 Rev 3 Document Number Date Description Panel dimensions and port details are added. Power supply, multidropping wiring added. Communication timeout register is added.
support@renuelectronics.com
Website:
www.renuelectronics.com
11