ROTOTERM MR-TR
ROTOTERM MR-TR
ROTOTERM MR-TR Code 21128 21131 Description ROTOTERM MR-TR plus ROTOTERM MR-TR (Heating controller MR-TR, Room unit AS 2000-E, sensors AF, BSVF, BF, mounting kit) (Heating controller MR-TR, sensors AF, BSVF, BF, mounting kit)
ROTOTERM MR-TR plus is weather compensating central heating controller. It is designed to regulate the radiator or underfloor heating. The controller is 3-point (PID) temperature controller of heating water, which works as a function of external temperature, and in conjunction with the room correction unit, allows remote room temperature adjustment. The controller is built in microprocessor technology and meets the latest quality standards. It offers a wide variety of programming options, allowing optimal controller settings for the selected object. Features: LEDs indicate control output status Output for controlling motor actuator for mixing valves (UNI 3P, MV120) and circulation pump Pump and valve exercise (every 72h for 30s) which helps prevent sticking during long periods of inactivity Service switch to assist installer on start-up and technician during service Sensors fault status on digital display Factory set default parameters Digital setting of all parameters Temperature enquiry (outer, boiler, underfloor, mixed flow) on digital display
Characteristics: Supply voltage: 230VAC, 50Hz Power consumption: max.4VA Power supply of users: 1(1)A, 230VAC, 50Hz Room temperature setting range: 5 - 25C Heat curve ratio adjustment: 0,1 - 2C Heat curve parallel shift adjustment: +/- 10C Room unit influence (AS/VF): 1 - 15 Max. mixed flow temperature setting range: 30-85C Boiler condensation limit adjustment: 30-75C (radiator heating) Underfloor temperature limit adjustment: 15-35C (underfloor heating) Circulation pump switching-off adjustment: 20-45C Sensors type: KTY 81-210 Programmable Room unit AS 2000-E Room unit AS 2000-E is designed for daily and weekly mode of operation and for setting two temperature levels (day - night). The possibility of correction room temperature or mixed flow temperature (function is chosen on the right side of the unit ) Control of actual hour, day and heating status Room temperature display Kit weight: ROTOTERM MR-TR plus 1,1kg ROTOTERM MR-TR 0,9kg
1
www.first.si
ROTOTERM MR-TR
TECHNICAL DATA
Supply voltage............................................................................................................................................................230V , 50Hz Power consumption.............................................................................................................................................................max. 4VA Relay outputs...................................................................................................................................................1(1)A, 230V , 50Hz Power consumption .....................................................................................................................................................................4VA Humidity:. ............................................................................................................................................. 5% - 70% (without condense) Storage temperature: .........................................................................................................................................................0C-70C Mounting: . ........................................................................................................................................................................on the wall Recommended cable use:. ..............................................................................................................sensor cable: J-Y (St) 1X 2X0,6 .............................................................................................................................................Pump, actuator cable: H03VV-F 3x0,75 Sensor type.................................................................................................................................................................PTC KTY 10-6 Temperature measuring range.....................................................................................................................................-40C...160C Room temperature setting................................................................................................................................................. 5C...25C Program settings: Heating curve ratio setting. ....................................................................................................................................................... 0,1...2 Parallel shift...........................................................................................................................................................................+/- 10C Room unit influence. ................................................................................................................................................................. 1...15 Controller type.............................................................................................................................................................................. PID Floor temperature limit.................................................................................................................................................... 15C...35C Summer periodic run of pump and mixing valve............................................................................................ every 72 hours for 30s Connection mode...........................................................................................................................................................terminal pins Parameters selection mode . ......................................................................................................................................................keys Parameters....................................................................................................................................................... factory built-in values
Dimension of sensors:
l
l=1,5m sensor BSF1, PVC (grey cable) l=2m sensor KF, silicon (red cable)
www.first.si
ROTOTERM MR-TR
TEMPLATE FOR HOLES FOR EASIER INSTALLATION OF THE MR-TR CONTROLLER TO THE WALL.
www.first.si
ROTOTERM MR-TR
CONNECTION Put side air sensor AF 2000 Mixed flow sensor VF2000 (grey colour) Room unit AS2000 (5-9, 6-9) Floor sensor (BF2000) or boiler sensor (KF2000) - red colour N - Neutral conduit L - Phase for switching on the pump 1(1)A, 230V , 50Hz N -Neutral conduit for pump L - Closing the valve 1(1)A, 230V , 50Hz N -Neutral conduit L - Opening the valve 1(1)A, 230V , 50Hz L - Phase connection to power supply network 230V , 50Hz N - Neutral conduit, connection to power supply network 230V , 50Hz
When connecting the wires in the terminal make sure that the insulated part of wire is in the housing part of the terminal!
To completely switch off the operation of the controller you need to disconnect it from the power supply network !
www.first.si
ROTOTERM MR-TR
grey
black
grey
black
MV 120/09E
MV 120/210 MV 120/360
MV 120..540 (EUROMIX)
SENSOR MOUNTING
All the connecting cables of temperature sensors and indoor units can be extended, but you have to some basic rules to consider: 1. Sensors cables do not lead in parallel with the mains voltage cables (220V/50Hz). There can appears current stroke, which cause voltage induction and it can damage the controller or sensors. If there is no other way then parallel minimum distance is 10cm between them. It is allowed to guide the sensors cable perpendicular crossing voltage cables. 2. If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V. It is installed by soldering at the point where the original sensors wire extended to the other cable wire (see Figure 2). 3. Extending the sensor cable is recommended by shielded telephone, shielded data or any other for that purpose cable cross section 0.5 mm or more (for example JY (St) 1X 2X0,6). These cables prevent the transmission of interference or noise from the environment that would cause improper operation or to reset the controller. Most often is a shield of aluminium foil and extra noninsulated - shield wire. Connection should be undertaken in a manner described below (see Figure 1 and the recommendation of experts). 4. By installation is necessary to provide mechanical protection of sensors and wires, and protection against atmospheric influences.
Recommendation of experts:
During the laying of cables is needed to decide the path-line, which is not near the Protection wire high voltage or high frequency electrical Signal wires Thermo sources (power cables, cables to various VDR resistor shrinkable tube appliances: pump, motor actuators, boiler,...). Common ground at one point is first condition to operate without interference. It is Signal wires Sensors recommended earthing of protective shield Extending cable to the power connection, which is in cable cable Protection wire turn the controller (the ground terminal) or in the back to cable shield and control, distribution cabinet. The other end of insulate them both Insulated band the cable connected to the sensor should be Figure: 1 Figure: 2 equipped in accordance with the procedure in Figure 1 and these instructions. On the side where is extended the original sensor, removable part of the insulation in the shielded wire turn back to connect cable shield. All together squeeze good, and by wrapping the insulating tape, taking care of protection shield wires do not extend the scope of the connection of two signal wires. Each protruding wire can become a source of new interference, that why it is necessary to make this connection especially with care. In this way it is assured the best possible protection of sensors, and save yourself a bunch of nerves and the spend time in case of any errors due to disturbances.
www.first.si
ROTOTERM MR-TR
MOUNTING OF SENSORS
MOUNTING OF OUTSIDE AIR SENSOR AF 2000
Fix the sensor to the north side wall (or shady side) of the building at least 1.5 m from the un der floor and from all possible heat sources (win dow, door, ventilating channels, stacks, direct sunlight, above the win dows) Connect the sensor cable to the terminal pins 1 and 2 in the au to matics connection box.
ASSEMBLY OF ROOM UNIT AS 2000-E (ROTOTERM MR-TR plus only) Use the enclosed bolts and mount the room unit to the wall. The unit shall be fixed at least 1.5 m above the floor and at least 1m away from all heating sources (radiator, sun influences, fire places, ...). If the room unit AS 2000-E is used as remote temperature corrector (correction of heating curve) is installation is not important because the unit operates independently of the ambient temperature. This happens in cases where in the existing space are used additional sources of heating - fireplace. In this case Heating source side switch for selecting operation (see description of the room unit AS2000-E) shifted to the OFF position (factory set to ON). This will enable heating of other room in the building by heating curve. Some examples of incorrect installation
WARNING! In this position, a switch (5) in position does not provide protection against frost (room temperature 8-10C), but the function of full-OFF operation - unconditionally closes the mixing valve.
Chimney Gas boiler
When an additional heating source is no longer active, switch (14) moves back to ON, which provides us with a constant temperature in the room.
www.first.si
ROTOTERM MR-TR
ELECTRICAL CONNECTION
Connection between the room unit and the controller is of low voltage type (two-wire 2 x 0.5 mm2). When longer wires are required or where stronger interference is to be expected, we recommend use of shielded cable. DO NOT CONNECT ROOM UNIT AS 2000-E TO POWER SUPPLY NETWORK OR ANY OTHER VOLTAGE SOURCE! Room unit is supplied with its own power supply source (battery cells 2x 1.5V LR06), which need to be replaced every two years! Sensor cables shall not be placed parallel to live power supply cables, as in case of electric shock there is danger of induced current which can damage the controller or room unit. In case that power supply cable and sensor cable are parallel, the minimum distance between them shall be 10 cm. It is allowed however the sensor cable to trans versely cross the supply cable.
bimetal thermostat
Recommendation: For under floor heating we recommend in stallation of an extra safety bimetal thermostat on the mixed flow line. The ther mo stat shall be set to some 50C and shall switch off the cir cu lation pump after the tem pera ture in the heating wa ter line ex ceeds 50C. The use of ther mo stat is rec ommended as precaution in order to prevent hot wa ter to breaking into under floor heating system.
www.first.si
ROTOTERM MR-TR
Data display
During complete operating period the display shows temperature of VF mixed flow.
When value AS" is negative it indicates that the temperature in the room is too high and controller decreases the temperature of heating water line. When value "AS" is positive it indicates that the temperature in the room is too low and controller increases the temperature of heating water line. The parameter E, selected from displayed value AS, can be used for calculation of the difference (Troom ) between actual room temperature and required room temperature.
www.first.si
ROTOTERM MR-TR
Controller parameters
ROTOTERM MR-TR microprocessor controller of radiator and under floor type heating provides for setting of the following parameters:
1. CONTROLLER TYPE: [rAd] or [tAL] [rAd] - radiator heating system [tAL] - under floor heating system
range selection:
or
Select the type of controller in order to define the type of heating system and sensor function (BF/KF). You define whether BF/KF sensor, connected to terminal pins 7 and 8, is used as boiler or under floor type sensor. If under floor type heating is selected the BF/KF sensor functions as floor sensor and if radiator heating is selected it functions as boiler sensor.
range selection:
or
The ratio of heating curve defines the temperature of mixed flow at certain out side temperature. Considering the type of heating, the controller has the following limits: Under floor heating: from 0,1 to 1 (factory setting (0,5). Radiator heating: from 0,1 to 2 (factory setting1,0).
range selection:
or
Parallel shift of a curve enables dis placement of heating curve for +/- 10C (factory setting 0). When heating curve ratio is adequate (in case deviation of required tem pera ture is the same in cold and transition periods), it can be modified by means of heating curve ascent or descent.
1st example
Room temperature in transition period corresponds but is too low in cold periods. In this case the slope of heating curve [n] should be set to higher value.
www.first.si
ROTOTERM MR-TR
2nd example
Room temperature in transition period corresponds but is too high in cold periods. In this case the slope of heating curve [n] should be set to lower value.
transition period
cold period
3rd example
Room temperature in transition period too low but in cold period corresponds. 1st step Increase parallel shift of curve [P] to higher value. 2nd step Set ratio of heating curve [n] to lower value.
transition period
cold period
transition period
cold period
4th example
Room temperature in transition period too high but in cold period it corresponds. 1st step Increase parallel shift of curve [P] to lower value. 2nd step Set ratio of heating curve [n] to higher value.
transition period
cold period
transition period
cold period
from:
to
Temperature limit of mixed flow is used in systems where smaller areas of under floor are heated with pipes of radiator heating (bathrooms, toilet rooms). To prevent damages of under floor systems or under floor linings (ceramic tiles) the temperature in pipes should be limited under certain temperature value (50C). Such limit value, used in radiator heating systems, prevents fast rise of temperature of heating units during very cold mornings; consequently the time required to reach the desired room temperature is extended. Therefore in this case it is recommended to pre-set the time for morning start up of heating WARNING: If the temperature of heating water line for radiator heating is limited to too low value it is possible that very low morning temperatures prevent reaching of required room temperature. Considering the type of heating the controller enables the following settings: Under floor heating: from 30C to 50C (factory setting 50). Radiator heating: from 30C to 85C (factory setting 80).
from:
to
This setting specifies the temperature at which the controller switches off the pump, when mixing valve is already closed. This function enables that all heating units are uniformly cooled down after termination of higher operating mode. Factory settings of deactivation: radiator heating: 30C, under floor heating: 25C.
from:
to
This setting specifies the degree of increase or decrease of the temperature of heating water line if room temperature changes for 1C. Higher is the inertia of the system, lower should be the influence of room unit and vice versa. Under floor heating: the influence of room temperature can be set between 0 and 5 (factory setting 3); radiator heating: between 0 and 15 (factory setting 8). When MR-TR controller is used solely as temperature controller of mixed flow with reference to out side temperature (without room unit), the terminal pins 5 and 6 remain free. IN THIS CASE THE INFLUENCE OF ROOM UNIT MUST BE SET TO 0!
www.first.si
10
ROTOTERM MR-TR
7. PARAMETER: [t]
Parameter [t] has two functions and depends on the type of selected controller (radiator of under floor type heating).
to
When boiler has more users (mixing valves with pumps) or the boiler is under-di men sioned, condense frequently appear during morning start-ups in boiler and flues due to too high consumption, especially at radiator heating. For this reason the controller is equipped with KF boiler sensor, which reads boiler temperature. If the temperature of the boiler decreases under the set value, the controller begins closing the mixing valve and enables the burner to quickly heat the boiler to set temperature. The temperature of condense point can be set between 30C and 75C (factory set to 65). The very same KF sensor protects the boiler against overheating. It opens the mixing valve and activates the pump, if the temperature of boiler exceeds 95C. In this way it prevents deactivation of thermal fuse in boiler regulation unit. If the sensor is not connected a resistance should be used instead of it - see chapter: Installation of boiler sensor!
from:
to
When MR-TR is used as under floor controller, maximum floor temperature can be set. Floor temperature is read by means of BF sensor installed in screed close to floor surface. This sensor has a function of protection. The temperature of condense point is set between 15C and 35C (factory set to 29). If the sensor is not connected a resistance should be used instead of it - see chapter Installation of boiler sensor!
4. Value [rAd] or [tAL] is displayed. Set controller type with ( ) and ( ) keys. [rAd] - radiator heating [tAL] - under floor heating
www.first.si
5. Keep pressing E key until P.r. disappears and save set values.
11
ROTOTERM MR-TR
www.first.si
12
ROTOTERM MR-TR
LEGEND : 1 - slide switch 1: working regime 1 ( - Non-stop working on higher (comfort) temperature AUTO - Automatic working according set program 0 ( ) - Non-stop working on lower (economic) temperature 2 - slide switch 2: time and program setting - time and day setting RUN - timer working - program setting 3 - LCD display for exact time and state of program 4 - LCD display for room temperature 5 - Slide switch for choosing way of op er ating - (Protection against freezing (8C) - Automatic working according set program
6 - Knob for setting higher (comfort) temperature 7 - Knob for setting lower (economic) temperature 8 - key for the tem po rarily manual override of program till next program step 9 - key for setting minutes 10 - key for setting hours 11 - key for setting the day of the week 12 - key for input the program 13 - key RESET (deletes time and program) 14 - Slide switch for unit operation ON - temperature control of mixed flow dependents on exterior and internal room temperature (normal operation) OFF - temperature control of mixed flow dependents on exterior temperature (based on heating curve)
NOTE: LCD display room temperature does not affect the operation of automation. It is intended only to indicate the temperature of the room in which it is installed!
LCD display
Day of the week 1-monday, 2-tuesday, ..., 7-sunday High, comfort temperature Time: hours and minutes
Temperature correction
Room unit has the option of setting the two temperature levels, namely higher comfort level - ( level - ( ). Setting the higher and lower temperatures are independent of each other. If you set the heating curve between 0.5 and 1 and you have average heating system, will control knob to the higher temperature in the middle position provides room temperature between 20C and 21C. Setting the lower temperature in the middle position provides room temperature between 17 and 18C. Rotate buttons to the left or right allows you to set the room temperature within about 4C (from the starting position of the middle button - depends of parameter E). ) and lower economical
www.first.si
13
ROTOTERM MR-TR
BATTERY REPLACEMENT
It is recommended to replace the battery cell at the beginning of heating period in order to attain reliable operation of room unit! Use screwdriver to separate AS 2000-E from wall console: press the screwdriver in the notch on bottom part, lift it with hand and remove it. AS 2000-E uses alkaline battery cell 2x LR06 1.5V. In the unit are inserted two LR06 alkaline battery LR06 1,5 V. Pull out the spent cartridges and replace them immediately with new ones (you have a few seconds for replacement to maintain set program). AS 2000-E operates regardless the network conditions (during eventual current break downs programme is not deleted) due to supply from batteries. Life time of batteries cell is about 2 years from the date of in stallation of new one and it becomes worn out when the display becomes pale. Use exclusively alkaline battery cells type LR 06 in order to pre vent leakage and damages to electronic circuit. Do not put used batteries in your regular household rubbish. Take them to your local batterydisposal point. Do not throw this device away with your regular household waste. You must take electronic equipment to a local tip to be disposed of in line with current regulations. Never try to recharge standard batteries as they may explode. Do not take batteries apart or throw them into a fire. Do not short circuit batteries.
www.first.si
14
ROTOTERM MR-TR
TIME SETTINGS
NOTE: When you first set the time and program of room unit, we recommend that you delete all previous settings. To do so, press the button <RESET>. 1. After <RESET> is pressed, the display flashes - it is ready for setting.
2. Setting time To do so, to move the switch to position 2 ( ). Adjust time by pressing key <h> (hour) and <m> (minutes). If you hold the button longer, the value (hours or minutes) changing faster and faster. 3. Setting the day of the week To set the day of the week, press key <1 ... 7> until the indicator is placed on the exact day (1 = Monday 2 = Tuesday 3 = Wednesday, ...). Each time the key is pressed the indicator moves forward by one day. To complete time setting move slide switch 2 in RUN position.
Program setting
1. Move the slide switch 2 in position for setting program . There is 16 switch cycles available - 8 switch cycle to a higher and 8 switch cycle to lower temperature. Switch cycles are in order from 1 to 16. All odd switch cycles (1, 3, 5, 7, 9, 11, 13 and 15) are for switching to a higher temperature, all the even switch cycles (2, 4, 6, 8, 10, 12, 14 and 16) are for switching to a lower temperature. On the display appears symbol which indicates switching to higher temperature. 2. First switching cycle for switching to higher temperature On display appears symbol for first setting. 3. Setting the time (hours and minutes) of the switching cycle Set it with keys <h> (hour) in <m> (minute). 4. Setting the day of the week You can set the day of switch cycle or group of days with key <1..7>.
The day of the week is obligatory to set for each cycle, otherwise the switching cycle is not implemented! 5. First switching cycle for switching to lower temperature By pressing key < > it saves switching cycle 1 and moves to next switching cycle (2) - lower temperature 6. Setting the day of the week or group of days Setting the day MUST be the same as previous switch cycle to a higher temperature. Set the day to switch to a lower temperature, time (hours and minutes) and press < > to move to the next switch cycle. 7. Settings for all next switch cycles Repeats the process - points 3, 4, 5 and 6) 8. END OF PROGRAM SETTINGS Move slide switch 2 in RUN position, the slide switch 1 in the AUTO position. Room unit operates after the set program. NOTE: In case you do not need all the switch cycles, which allows the timer, leave the value effective entries (first on , first off, the second on , second off, ...). . Pay attention to sequence of
www.first.si
15
ROTOTERM MR-TR
Program setting
Room unit AS2000-E does not have factory-installed the program and must be set initially or after RESET. We recommend you to easily program settings, you enter your program into a table at the back of the manual. There is 16 switch cycles which are set by pairs: the switch cycle to a higher level and switch cycle to the lower level.
) set in to position
with key <P> switch to next switch cycle. 4. To end program setting move slide switch 2 ( )in position RUN.
Program overview
The program can be reviewed at any time to move slide switch 2 into the position . The program initially displays the first switch cycle. By pressing the key < > moving to the next switch cycle, etc..
Program changing
Move slide switch 2 into the position . Press < > to put it on the program position and with keys <1 .. 7>, <h> and <m> can change existing settings. Press < > to move to the next switch cycle. Once you have changed the program, move the slide switch 2 back to position AUTO - automatic mode.
Frost protection
Move slide switch 2 to position AUTO. Both buttons 5 and 6 turn to the left end position, the position of 5C.
www.first.si
16
ROTOTERM MR-TR
ROTOTERM MR-TR
STATUS POSSIBLE FAULT REMEDY Set the curve to higher value. At outside temp. +10C the room is warm Heating curve set too low. enough, at temp. -10 it is too cold. In room should be higher (day) temperature - Timer settings. but is too cold. - Digital timer - overlapping of switch cycles
- No supply from controller - Faulty motor - Too hard (blocked) mixing valve. - Broken safety forks (only by MV120/09E,...) - Broken lever on handle. - Valve handle displaced. Interrupted - outside sensor AF, - mixed flow sensor VF, - AS 2000 room unit .
- Check terminal pins 17, 18 and 19, - Check mixing valve and its rigidity.
Regulation motor rotates, mixing valve does not respond. Regulation motor does not stop in final positions. LED for valve opening ( ) is ON on controller, mixing valve is fully open, hot in the room
- Replace safety forks on handle, - replace handle. - check handle end positions - Check final positions of the handle. Check - resistance of AF, - resistance of VF, - room unit.
Check - resistance of AF, VF and BF - supply from AF, VF, BF and room unit - set selector switch 5 to position .
LED for valve closing ( )is ON on controller, Short circuited mixing valve is closed, too cold in the room - outside air sensor AF
- AS 2000 room unit - sensor VF - under floor sensor BF - slide switch in position.
www.first.si
17
ROTOTERM MR-TR
STATUS
POSSIBLE FAULT
REMEDY
LED for valve closing ( ) is ON on - Motor MV 120/ rotation direction is Check motor rotation direction left and right. controller, mixing valve is opened, heating inverted regarding mixing valve. water line is hot Temperature in the room is always the same regardless of program Too cold in the room. Slide switch 1 is in position
1( ) or 0 ( )
position AUTO
- set selector switch 5 to position . - Terminal pins 9 and 10 on room unit is - check connection of room unit inverted AS2000-E - Knobs for temperature setting are set to - set knobs (5 and 6) to higher level low
At timer status is cold in the room, at status is warmer. If T2 or T3 key is pressed, Er1 is displayed. If T2 or T3 key is pressed, Er2 is displayed.
The controller operating normally. In the system appears strong Sometimes it happens that the controller electromagnetic interference. Controller repeatedly reset (off and on again). activates the built-in protection against electromagnetic pulses.
YOURS PROGRAM
Write down your's program
switch cycle temp. level day time 1 higher 2 lower 3 higher 4 lower 5 higher 6 lower 7 higher 8 lower
9 higher
10 lower
11 higher
12 lower
13 higher
14 lower
15 higher
16 lower
Radegunda 54, 3330 Mozirje, Slovenia Koroka cesta 56a, 3320 VELENJE, Slovenija tel. +386 3 898 35 00, fax. +386 3 898 35 35 e-mail:info@first.si, www.first.si