STRUCTURAL CALCULATIONS
FOR

job title
City, State

www.StruWare.com

Company
Address This is a demonstration program. Do not use for actual building City, State calculations, sincePhone some items have been deactivated or changed and can result in incorrect results. other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

Code Search
I. II. Code: Occupancy: Occupancy Group = III. Type of Construction: Fire Rating: Roof = Floor = IV. 0.0 hr 0.0 hr 0.0 deg B Business International Building Code 2000

Live Loads: Roof angle (q) 0.00 / 12 Roof 0 to 200 sf: 20 psf 200 to 600 sf: 24 - 0.02Area over 600 sf: 12 psf Floor 100 psf Stairs & Exitways 100 psf Balcony 100 psf Mechanical N/A Partitions 20 psf

V.

Wind Loads :

ASCE 7 - 98 1.00 120 mph 0.85 157.0 ft 160.0 ft B Enclosed Building +/-0.18 200.0 ft 100.0 ft 1.124 1.124

Importance Factor Wind speed Directionality (Kd) Mean Roof Ht (h) Parapet ht above grd Exposure Enclosure Classif. Internal pressure Building length (L) Least width (B) Kh case 1 Kh case 2

Topographic Factor (Kzt) Topography Hill Height (H) Half Hill Length (Lh) Actual H/Lh = Use H/Lh = Modified Lh = From top of crest: x= Bldg up/down wind?

Flat 80.0 ft 100.0 ft 0.80 0.50 160.0 ft 50.0 ft downwind 0.000 0.792 1.000 1.00 www.StruWare.com

H/Lh= 0.50 K1 = x/Lh = 0.31 K2 = z/Lh = 0.98 K3 = At Mean Roof Ht: Kzt = (1+K1K2K3)^2 =

Company
Address This is a demonstration program. Do not use for actual building City, State calculations, since some items have been deactivated or changed Phone results. and can result in incorrect other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

V.

Wind Loads - cont.:

Gust Effect Factor


Flexible structure if natural frequency < 1 Hz. However, rule of thumb is if h/B < 4 then rigid structure. h/B= 1.57 Therefore, probably rigid structure

G=
Rigid Structure /e = 0.33 l= 320 ft zmin = 30 ft c= 0.30 gQ, gv = 3.4 Calculated /z = 94.2 ft Use this /z : 94.2 ft Lz = 453.9 ft Q= 0.83 Iz = 0.25 G= 0.83

0.83
Flexible or Dynamically Sensitive Structure Building Natural Frequency (n1) = 0.0 Hz Damping ratio (b) = 0 /b = 0.45 /a = 0.25 Vz = 102.9 N1 = 0.00 Rn = 0.000 h= Rh = 28.282 h= RB = 28.282 h= RL = 28.282 gR = 0.000 R = 0.000 G = 0.000

0.000 0.000 0.000

Enclosure Classification
Test for Enclosed Building: A building that does not qualify as open or partially enclosed.

Test for Open Building:

All walls are at least 80% open. Ao 0.8Ag

Test for Partially Enclosed Building: Input Ao 0.0 sf Ag 0.0 sf Aoi 0.0 sf Agi 0.0 sf

Ao 1.1Aoi Ao > 4' / 0.01Ag Aoi / Agi 0.20

Test YES NO NO

Building is NOT Partially Enclosed.

Conditions to qualify as Partially Enclosed Building. Must satisfy all of the following: Ao >= 1.1Aoi Ao > smaller of 4' or 0.01 Ag Aoi / Agi <= 0.20 Where: Ao = the total area of openings in a wall that receives positive external pressure. Ag = the gross area of that wall in which Ao is identified. Aoi = the sum of the areas of openings in the building envelope (walls and roof) not including Ao. Agi = the sum of the gross surface areas of the building envelope (walls and roof) not including Ag.

Reduction Factor for large volume partially enclosed buildings (Ri):


If the partially enclosed building contains a single room that is unpartitioned , the internal pressure coefficient may be multiplied by the reduction factor Ri. Total area of all wall & roof openings (Aog): Unpartitioned internal volume (Vi) : Ri = 0 sf 0 cf 1.00

Actual program includes wind speed maps

Company
Address City, State Phone other V.

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

Wind Loads - MWFRS h60' (Low-rise Buildings) Enclosed/partially enclosed only See code for Case B diagram.

CASE A - perpendicular Kz = Kh = Base pressure (qh) = GCpi =

CASE A - parallel Edge Strip (a) End Zone (2a) Zone 2 length = CASE B All Directions
w/-Gcpi

1.12 (case 1) 0.0 psf h>60 - can't use low-rise method +/-0.18 CASE A Parallel q = 0deg
w/-GCpi

10.0 ft 20.0 ft 50.0 ft

Perpendicular q = 0.0 deg

Surface 1 2 3 4 5 6 1E 2E 3E 4E 5E 6E 1 2 3 4 5 6 1E 2E 3E 4E 5E 6E

GCpf w/+Gcpi -0.45 -0.27 -0.69 -0.51 -0.37 -0.19 -0.45 -0.27 0.40 0.58 -0.29 -0.11 0.61 0.79 0.43 0.61 0.79 0.43 -0.48 -0.30 -1.07 -0.89 -1.25 -1.07 -0.89 -1.25 -1.07 -0.89 -0.53 -0.35 -0.71 -0.53 -0.35 -0.71 -0.53 -0.35 -0.43 -0.25 -0.61 -0.43 -0.25 -0.61 -0.48 -0.30 0.61 0.79 -0.43 -0.25 Wind Surface pressures (psf) - use 10 psf minimum for zones 1 plus 4 and 5 plus 6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
w/-GCpi

GCpf w/+GCpi 0.40 0.58 -0.69 -0.51 -0.37 -0.19 -0.29 -0.11

0.22 -0.87 -0.55 -0.47

GCpf w/+GCpi 0.40 0.58 -0.69 -0.51 -0.37 -0.19 -0.29 -0.11

0.22 -0.87 -0.55 -0.47

-0.63 -0.87 -0.55 -0.63 0.22 -0.47 -0.66 -1.25 -0.71 -0.66 0.43 -0.61 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

MWFRS Simple Diaphram Pressures (psf) Transverse direction (normal to L) Interior Zone: Wall 0.0 psf Roof 0.0 psf End Zone: Wall 0.0 psf Roof 0.0 psf Longitudinal direction (parallel to L) Interior Zone: Wall 10.0 psf End Zone: Wall 10.0 psf Windward roof overhangs: Parapet Windward parapet: Leeward parapet: 0.0 psf (upward) add to windward roof pressure 0.0 psf (GCpn = +1.8) 0.0 psf (GCpn = -1.1)

Company
Address This is a demonstration program. Do not use for actual building City, State calculations, since some items have been deactivated or changed Phone and can result in incorrect results. other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

V. Wind Loads - Components & Cladding: Low-rise Buildings (h60') & Alternate design 60'<h<90' Kz = Kh (case 1) = 1.12 GCpi = +/-0.18 NOTE: If tributary area is greater than Base pressure (qh) = 0.0 psf a= 10.0 ft 700sf, MWFRS pressure may be used. Minimum parapet height at building parimeter = 0.0 ft h>=90' - can't use low-rise method Roof Angle = 0.0 deg Check box if roof slopes in only one direction: Roof Area Negative Zone 1 Negative Zone 2 Negative Zone 3 Positive All Zones Overhang Zone 2 Overhang Zone 3 10 sf -1.18 -1.98 -2.98 0.48 -1.88 -2.98 GCp +/- GCpi 50 sf -1.11 -1.49 -1.79 0.41 -1.81 -1.58

Monosloped ?

100 sf -1.08 -1.28 -1.28 0.38 -1.78 -0.98

Surface Pressure (psf) 10 sf 50 sf 100 sf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf 0 psf

User input 70 sf -1.10 0 psf -1.39 0 psf -1.54 0 psf 0.40 0 psf -1.80 0 psf -1.29 0 psf

Walls Area Negative Zone 4 Negative Zone 5 Positive Zone 4 & 5 Parapet qp =

GCp +/- GCpi Surface Pressure (psf) 10 sf 100 sf 500 sf 10 sf 100 sf 500 sf -1.17 -1.01 -0.90 0.0 psf 0.0 psf 0.0 psf -1.44 -1.12 -0.90 0.0 psf 0.0 psf 0.0 psf 1.08 0.92 0.81 0.0 psf 0.0 psf 0.0 psf Note: GCp reduced by 10% due to roof angle <= 10 deg. 35.4 psf Solid Parapet Pressure CASE A : Interior zone : Corner zone : CASE B : Interior zone : Corner zone : 10 sf 0.0 psf 0.0 psf 0.0 psf 0.0 psf

User input 300 sf -0.94 0.0 psf -0.97 0.0 psf 0.85 0.0 psf

CASE A = pressure towards building CASE B = pressure away from building

100 sf 0.0 psf 0.0 psf 0.0 psf 0.0 psf

500 sf 0.0 psf 0.0 psf 0.0 psf 0.0 psf

q 10 degrees and Monoslope 3 degrees

Monoslope roofs 3 < q

Monoslope roofs 10 < q 30

q > 10 degrees

q > 10 degrees

Company
Address This is a demonstration Do not use for actual building City, program. State calculations, since some items have been deactivated or changed Phone and can result in incorrect results. other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

V.

Wind Loads - MWFRS all h (Enclosed/partially enclosed only) Kh (case 2) = 1.12 h= 157.0 ft Base pressure (qh) = 35.2 psf L= 200.0 ft Roof Angle = 0.0 deg B= 100.0 ft Roof tributary area - (h/2)L: 15700 sf (h/2)B: 7850 sf Surface Pressures (psf) Surface Windward Wall (WW) Leeward Wall (LW) Side Wall (SW) Leeward Roof (LR) Windward Roof: 0 to h/2* > h/2* Wind Normal to Ridge (psf) B/L = 0.50 h/L = 1.57 qhGCp w/+qiGCpi w/-qhGCpi Cp 0.80 23.5 see table below -0.50 -14.7 -8.3 -21.0 -0.70 -20.6 -14.2 -26.9 -1.04 -0.70 ** -30.5 -20.6 -24.2 -14.2 -36.9 -26.9

GCpi = G= qi = qh

+/-0.18 0.83

Dist.*

Wind Parallel to Ridge (psf) L/B = 2.00 h/L = 0.79 qhGCp w/ +qiGCpi w/ -qhGCpi Cp 0.80 -0.30 -0.70 23.5 -8.8 -20.6 see table below -2.5 -15.1 -14.2 -26.9 -35.1 -29.4 -24.4 -21.8

*Horizontal distance from windward edge

Included in windward roof 0 to h/2* -0.98 -28.8 -22.4 h/2 to h* -0.79 -23.1 -16.7 h to 2h* -0.61 -18.0 -11.7 > 2h* -0.53 -15.5 -9.2 **Roof angle < 10 degrees. Therefore, leeward roof is included in windward roof pressure zones.

Windward Wall Pressures at "z" (psf) z 0 to 15' 20 ft 25 ft 30 ft 40 ft 50 ft 60 ft 70 ft 80 ft 90 ft 100 ft 120 ft 140 ft 157 ft Kz 0.57 0.62 0.67 0.70 0.76 0.81 0.85 0.89 0.93 0.96 0.99 1.04 1.09 1.12 Kzt 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 qzGCp Windward Wall Combined WW + LW w/+qiGCpi w/-qhGCpi Normal to L Parallel 12.0 psf 18.3 psf 5.7 psf 26.7 psf 20.8 psf 13.0 19.4 6.7 27.7 21.8 13.9 20.2 7.6 28.6 22.7 14.6 21.0 8.3 29.3 23.4 15.9 22.2 9.6 30.6 24.7 16.9 23.3 10.6 31.6 25.7 17.8 24.2 11.5 32.5 26.7 18.6 25.0 12.3 33.3 27.5 19.4 25.7 13.0 34.1 28.2 20.0 26.4 13.7 34.7 28.8 20.6 27.0 14.3 35.3 29.5 21.8 28.1 15.4 36.4 30.6 22.7 29.1 16.4 37.4 31.5 23.5 29.8 17.1 38.2 32.3

NOTE: See figure 6-9 of ASCE7 for the application of full and partial loading of the above wind pressures. There are 4 different loading cases. Parapet z 160.0 ft

Kz 1.13

Kzt 1.00 63.7 psf -39.0 psf

qp (psf) 35.4 (GCpn = +1.8) (GCpn = -1.1)

Windward parapet: Leeward parapet:

Company
Address This is a demonstration program. Do not use for actual building City, State calculations, since some items have been deactivated or changed Phone and can result in incorrect results. other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

V. Wind Loads - Components & Cladding : h > 60' Kh (case 1) = 1.12 h= Base pressure (qh) = 35.2 psf a= Roof Angle = 0.0 deg GCpi = Minimum parapet height at building perimeter =

157.0 ft 10.0 ft +/-0.18 0.0 ft

NOTE: If tributary area is greater than 700sf, MWFRS pressure may be used.

Roof Area Zone 1 Zone 2 Zone 3 10 sf -1.58 -2.48 -3.38

GCp - GCpi 100 sf -1.29 -2.07 -2.85

500 sf -1.08 -1.78 -2.48

Surface Pressure (psf) 10 sf 100 sf 500 sf -56 psf -45 psf -38 psf -87 psf -73 psf -63 psf -119 psf -100 psf -87 psf

User input 300 sf -1.15 -40 psf -1.87 -66 psf -2.60 -91 psf

Walls

GCp +/- GCpi Surface Pressure at "h" User input Area 20 sf 100 sf 500 sf 20 sf 100 sf 500 sf 300 sf Negative Zone 4 -1.08 -0.98 -0.88 -38.0 psf -34.5 psf -31.0 psf -0.91 -32.1 psf Negative Zone 5 -1.98 -1.58 -1.18 -69.7 psf -55.7 psf -41.6 psf -1.31 -46.0 psf Positive Zone 4 & 5 1.08 0.93 0.78 38.0 psf 32.8 psf 27.5 psf 0.83 29.2 psf NOTE: Negative zones 4 & 5 pressures apply to all heights. Positive pressures vary with height, see below.

Wall surface pressure at "z" z Kz Kzt 0 to 15' 0.70 1.00 20 ft 0.70 1.00 25 ft 0.70 1.00 30 ft 0.70 1.00 40 ft 0.76 1.00 50 ft 0.81 1.00 60 ft 0.85 1.00 70 ft 0.89 1.00 80 ft 0.93 1.00 90 ft 0.96 1.00 100 ft 0.99 1.00 120 ft 1.04 1.00 140 ft 1.09 1.00 157 ft 1.12 1.00

qz (psf) 22.0 22.0 22.0 22.0 23.8 25.4 26.8 28.0 29.1 30.0 31.0 32.6 34.1 35.2

Positive zone 4 & 5 (psf) 20 sf 100 sf 500 sf 23.7 20.4 17.1 23.7 20.4 17.1 23.7 20.4 17.1 23.7 20.4 17.1 25.7 22.2 18.6 27.4 23.6 19.8 28.9 24.9 20.9 30.2 26.0 21.8 31.4 27.0 22.7 32.5 27.9 23.4 33.4 28.8 24.2 35.2 30.3 25.4 36.8 31.7 26.6 38.0 32.8 27.5

Parapet z 160.0 ft

Kz 1.13

Kzt 1.00

qp 35.4 psf Solid Parapet Pressure CASE A : Interior zone: Corner zone: CASE B : Interior zone: Corner zone: 10 sf 113.3 psf 145.2 psf 63.7 psf 95.6 psf 100 sf 93.4 psf 121.1 psf 54.9 psf 76.1 psf 500 sf 77.9 psf 102.7 psf 46.0 psf 56.7 psf

CASE A = pressure towards building CASE B = pressure away from building

Company
Address This is a demonstration program. Do not use for actual building City, State calculations, since some items have been deactivated or changed and can result in incorrect Phone results. other

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

V. Wind Loads - Other Structures: Importance Factor Height to evaluate pressure (z) Gust Effect Factor (G) Kz (case 2) 1.00 20.0 ft 0.83 0.624

Wind Speed 120 mph Exposure B Kzt 1.00 Base pressure (qz) = 23.00 Kd psf

A. Solid Freestanding Walls & Solid Signs (& open signs with less than 30% open) Height 8.0 ft M = 100.0 ft Width 100.0 ft N = 8.0 ft Dist above ground v = 0.080 to bottom edge 0.0 ft Cf = 1.20 Directionality (Kd) 1.00

F = q z G Cf Af = Af = F =

23.0 Af
10.0 sf 230 lbs

Horizontal design eccentricity for signs = 0 to 0.2 times sign width.

B. Open Signs & Lattice Frameworks (openings 30% or more of gross area) Height 15.0 ft Width (zero if round) 2.0 ft Either width or diameter must be zero Diameter (zero if rect) 2.0 ft D(qz)^.5 = 9.59 Percent of open area = 0.65 to gross area 35.0% Cf = 0 Directionality (Kd) 1.00

F = q z G Cf Af = Solid Area: Af = F =

0.0 Af
10.0 sf 0 lbs

C. Chimneys, Tanks & Similar Structures Cross-Section Square h/D = 15.00 Directionality (Kd) 0.95 Height (h) 15.0 ft Width (D) 1.0 ft Type of Surface N/A D = diameter or least horizontal dimension of square, hexagonal or octangular at elevation under consideration.

Square (wind along diagonal) Cf = 1.28 F = qz G Cf Af = 23.3 Af Af = 10.0 sf F= 233 lbs

Square (wind normal to face) Cf = 1.67 F = q z G Cf Af = 30.4 Af Af = 10.0 sf F = 304 lbs

D. Trussed Towers = 0.27 Tower Cross Section square Member Shape flat Directionality (Kd) 1.00 (Ratio of solid area to gross area of the tower face under consideration) Diagonal wind factor = Round member factor = 1.2 1.000

Square (wind along tower diagonal) Cf = 3.24 F = qz G Cf Af = 62.1 Af Solid Area: Af = 10.0 sf F= 621 lbs

Square (wind normal to face) Cf = 2.70 F = q z G Cf Af = 51.7 Af Solid Area: Af = 10.0 sf F = 517 lbs

Company
Address This is a demonstration City, program. Do not use for actual building State calculations, since some items have been deactivated or changed Phone and can result in incorrect results. other VI. Earthquake Loads: Seismic Use Group Importance Factor (Ie) Site Class Ss (0.2 sec) = S1 (1.0 sec) = Fa = Fv = 0.800 0.800 A Bearing Wall Systems Special reinforced concrete shear walls Height not limited 157.0 ft II 1.00 A 20.00 %g 5.00 %g Sms = Sm1 =

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

Demo =1.00 only

Zip Code Search for Ss & S1: http://eqint.cr.usgs.gov/eq/html/zipcode.shtml 0.160 0.040 Sds = Sd1 = 0.107 0.027 Design Category = Design Category = A A

Seismic Design Category = Building System: Seismic resisting system: System Building Height Limit: Building Height (hn) =

Response Modification Factor (R) = 5.5 System Over-Strength Factor (Wo) = 2.5 Deflection Amplification Factor (Cd) = 5 Code Reference Section for Detailing : 1910.2.4

may be reduced by 1/2 if flexible diaphram

Equivalent Lateral-Force Procedure - Permitted, but not required since Seismic Design Category A Building period coef. (CT) = 0.020 CThnx = Approx fundamental period (Ta) = 0.887 x= 0.75 Seismic response coef. (Cs) = SdsIe/R = 0.019 need not exceed Cs = Sd1Ie/RTa = 0.005 but not less than Cs = 0.044SdsIe = 0.005 USE Cs = 0.005 Design Base Shear V = 0.005W Simplified Procedure - Permitted, but not required, since Seismic Design Category A Design Base Shear V=1.2SdsW/R = 0.023W Design Requirements for Seismic Design Category A: Minimum lateral force Fx = 0.01Wx at each floor level

Company
Address This is a demonstration program. Do not use for actual building City, State have been deactivated or changed calculations, since some items Phone and can result in incorrect results. other VII. Snow Loads - Flat, Gable & Hip Roofs Only : Roof slope = Horiz. eave to ridge dist (W) = Roof length parallel to ridge (L) = Type of Roof Ground Snow Load Importance Category Importance Factor Thermal Factor Exposure Factor Pf = 0.7*Ce*Ct*I*Pg Pf min Flat Roof Snow Load Pf Rain on Snow Surcharge Unobstructed Slippery Surface (per Section 7.4) Sloped-roof Factor Cs Design Roof Snow load = 0.0 deg 50.0 ft 200.0 ft Hip or gable 40.0 psf I 1.0 Demo = 1.0 1.00 1.0 28.0 psf 20.0 psf 28.0 psf 0.0 psf no 1.00

JOB TITLE JOB NO. CALCULATED BY CHECKED BY

job title
SHEET NO. DATE DATE

Pg = = I = Ct = Ce = = = = = = =

Terrain A B C D Above treeline Alaska-no trees

Exposure Factor, Ce Exposure of roof Fully Partially Sheltered n/a 1.1 1.3 0.9 1.0 1.2 0.9 1.0 1.1 0.8 0.9 1.0 0.7 0.8 n/a 0.7 0.8 n/a

28.0 psf ("balanced" snow load)

NOTE:Alternate spans of continuous beams and other areas shall be loaded with half the design roof snow load so as to produce the greatest possible effect - see code. Unbalanced Snow Loads - for Hip & Gable roofs only 70/W + 0.5 = 1.9 deg Unbalanced snow loads are not required Windward snow load = Demo - not available Leeward snow load = Demo - not available

Leeward Snow Drifts - from adjacent higher roof Upper roof length lu = 100.0 ft Projection height h = 5.0 ft Building separation s = 0.0 ft Adjacent structure factor 1.00 g = Snow density 19.2 pcf Balanced snow height hb = 1.46 ft hc = 3.54 ft hc/hb = 2.4 Therefore, design for drift Drift height Drift width Surcharge load: hd = w = pd = g*hd = 3.54 ft 16.37 ft

68.0 psf

Windward Snow Drifts - Against walls, parapets, etc more than 15' long Building roof length lu = 100.0 ft Demo - locked Projection height h = 5.0 ft Demo - locked g = Snow density 19.2 pcf Balanced snow height hb = 1.46 ft hc = 3.54 ft hc/hb = 2.4 Therefore, design for drift Drift height Drift width Surcharge load: hd = w = pd = g*hd = 2.86 ft 11.42 ft

54.8 psf

Company

JOB TITLE

job title
SHEET NO. DATE DATE

Address This is a demonstration program. Do not use for actual building City, State JOB NO. calculations, since some items have been deactivated or changed Phone CALCULATED BY and can result in incorrect results. other CHECKED BY

Roof Design Loads Items Roofing Deck Framing Insulation Ceiling Sprinklers Mech & Elec Misc. Description Multiple psf (max) 5.5 1.7 3.0 3.0 1.0 2.0 2.0 0.5 18.7 20.0 20.0 0.0 38.7 33.7 54.4 32.4 0.00 / 12 psf (min) 5.0 1.2 2.0 1.5 0.8 1.5 0.0 0.0 12.0 9.0 0.0 -72.8 -67.4 -108.5 0.0 deg

ASD Loading

3 ply felt & gravel Metal Roof deck, 1.5, 22 ga. Steel roof joists & girders Rigid insulation, per 1" x 2.0" Acoustical fiber x 1 ply(s) Sprinklers Mech. & Elec. Misc. 1 Actual Dead Load Use this DL instead Live Load Wind (zone 2 - 100sf) Dead + Live Load Dead + 0.75(Wind + Live) Load 0.6*Dead + Wind Load 1.2D + 1.6 Lr + 0.8W 1.2D + 1.6W + 0.5Lr 0.9D + 1.6W Roof angle

LRFD Loading

Roof Live Load Reduction 0 to 200 sf: 200 to 600 sf: over 600 sf: 20.0 psf 24 - 0.02Area 12.0 psf

User Input:

300.0 sf 400.0 sf 500.0 sf 450.0 sf

18.0 psf 16.0 psf 14.0 psf 15.0 psf

Company

JOB TITLE

job title
SHEET NO. DATE DATE

Address This is a demonstration program. Do not use for actual building City, State JOB NO. calculations, since some items have been deactivated or changed Phone CALCULATED BY and can result in incorrect results. other CHECKED BY

Floor Design Loads


Items Flooring Topping Deck/Sub-floor Framing Other Ceiling Sprinklers Mech & Elec Partitions Misc. Description Acoustical fiber Concrete regular per 1" Metal Floor deck - 2", 20ga Steel floor bms/joists & girders Deflection Concrete Acoustical fiber Sprinklers Mech. & Elec. Wood 2x @24" Misc. Multiple x 4.25"
psf (max) psf (min)

x 0.75 x 1 ply(s)

Actual Dead Load Use this DL instead Live Load Total Load FLOOR LIVE LOAD REDUCTION Not allowed for assembly occupancy or LL>100psf or passenger car garages, except may reduce columns 20% if 2 or more floors & non-assembly IBC & ASCE 7 L=Lo(0.25+15/KLLAT) Unreduced design live load: Lo = Floor member KLL = Tributary Area AT = Reduced live load: L = Columns (2 or more floors) KLL = Tributary Area AT = Reduced live load: L =

1.0 53.1 2.0 8.0 9.4 1.0 2.0 2.0 1.5 0.5 80.5 100.0 100.0 200.0

0.8 51.0 1.5 5.0 1.5 0.8 0.0 0.0 1.5 0.0 62.1 50.0 50.0

100 psf 2 300 sf 86.2 psf 4 500 sf 58.5 psf

IBC alternate procedure Smallest of: R= .08%(SF - 150) R= 23.1(1+D/L) = R= 40% beams; 60% columns R= Reduced live load: L =

46.2%

12.0% 88.0 psf

R= Reduced live load: L =

28.0% 72.0 psf

Software License Agreement

SOFTWARE LICENSE AGREEMENT IMPORTANT, READ BEFORE USING: THIS DOCUMENT IS A LEGAL AGREEMENT BETWEEN YOU AS THE LICENSEE, AND STRUWARE. USING THE SOFTWARE PRODUCT CONSTITUTES ACCEPTANCE OF THE TERMS OF THIS AGREEMENT. IF YOU DO NOT AGREE TO THE TERMS OF THIS AGREEMENT, PROMPTLY RETURN ALL MATERIALS TO STRUWARE FOR A FULL REFUND.

1 CONFIDENTIALITY. This computer program is a proprietary trade secret of STRUWARE. Possession and use of this program shall be strictly in accordance with this license agreement and receipt or possession does not convey any rights to divulge, reproduce, or allow others to use this program without specific written authorization of STRUWARE. 2 GRANT OF LICENSE. In consideration of payment of the license fee, which is part of the price paid for this product, STRUWARE grants to the LICENSEE a nonexclusive, nontransferable license, without right to sublicense, to use this copy of the enclosed software on a single computer at a single location. If a site license was purchased, the software may be used on multiple computers at a single location. STRUWARE reserves all rights not expressly granted to LICENSEE. 3 OWNERSHIP OF SOFTWARE. Title to, ownership of, and all rights and interests in the software and software documentation, and all copies thereof, remain at all times vested in STRUWARE. The license granted by this Agreement, and your payment of the license fee, gives you the right to use the software in accordance with the terms of this Agreement. This license is not a sale of the original software or any copy. 4 COPY RESTRICTIONS. This software product and the accompanying written materials are protected by law. Unauthorized copying of the software product, including software that has been modified, merged, or included with other software, or other written materials is expressly forbidden. You may be held legally responsible for any copyright infringement that is caused or incurred by your failure and/or the failure of your employees to abide by the terms of this license. Subject to these restrictions, you may make one (1) archival copy of the software product solely for backup purposes as permitted by 17 U.S.C. 117. You must reproduce and include this with the copy. This clause does not provide any rights beyond those provided by 17 U.S.C. 117. 5 USE RESTRICTIONS. As the LICENSEE, you may physically transfer the software from one computer to another, provided that the software is used on only one computer at a time. You may not disclose, publish, translate, release, or distribute copies of the software or accompanying written materials to others. You may not modify, adapt, translate, reverse engineer, decompile, disassemble, or create derivative works based on the software. You may not modify, adapt, translate, or create derivative works based on the written materials without the prior written consent of STRUWARE. 6 TRANSFER RESTRICTIONS. This software is licensed to you, the LICENSEE, and may not be transferred to anyone without the prior written consent of STRUWARE. In no event may you transfer, assign, rent, lease, sell, or otherwise dispose of the software on a temporary basis except as expressly provided herein. 7 TERMINATION. This license is effective until terminated. This license will terminate automatically without notice from STRUWARE if you fail to comply with any provisions of this license. Upon termination you shall destroy all copies of the software, including modified copies, if any. 8 UPDATE POLICY. STRUWARE may create, from time to time, updated versions of the software product. STRUWARE will make available to LICENSEE all such updates, which are released within 90 days of LICENSEE's purchase of this license. 9 LIMITED WARRANTY. STRUWARE warrants to the original licensee that the disk(s) or electronic transfer on which the software is recorded is (are) free from defects and materials and workmanship under normal use and service for a period of 180 days from the date of delivery, as evidenced by a

Page 17

Software License Agreement

copy of the sales receipt. Further, STRUWARE hereby limits the duration of any implied warranty(ies) on the disk to the period stated above. Some states do not allow limitations on duration of an implied warranty, so the above limitation may not apply to you. 10 DISCLAIMER OF WARRANTY AND LIMITED WARRANTY. THE SOFTWARE AND ACCOMPANYING WRITTEN MATERIALS, INCLUDING INSTRUCTIONS FOR USE, ARE PROVIDED "AS IS," WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED. FURTHER, STRUWARE DOES NOT WARRANT, GUARANTEE, OR MAKE ANY REPRESENTATIONS REGARDING THE USE, OR THE RESULTS OF THE USE, OF THE SOFTWARE OR WRITTEN MATERIALS IN TERMS OF ACCURACY, RELIABILITY, CURRENTNESS, OR OTHERWISE. YOU ASSUME THE ENTIRE RISK AS TO THE RESULTS AND PERFORMANCE OF THE SOFTWARE. IF THE SOFTWARE OR WRITTEN MATERIALS ARE DEFECTIVE, YOU, AND NOT STRUWARE, ASSUMES THE ENTIRE COST OF ALL NECESSARY SERVICING, REPAIR, OR CORRECTION. STRUWARE'S ENTIRE LIABILITY AND YOUR EXCLUSIVE REMEDY AS TO THE DISK(S) WILL BE, AT STRUWARE'S OPTION, EITHER (A) RETURN OF THE PURCHASE PRICE OR (B) REPLACEMENT OF THE DISK THAT DOES NOT MEET STRUWARE'S LIMITED WARRANTY AND WHICH IS RETURNED TO STRUWARE WITH A COPY OF THE SALES RECEIPT. IF FAILURE OF THE DISK HAS RESULTED FROM ACCIDENT, ABUSE, OR MISAPPLICATION, STRUWARE SHALL HAVE NO RESPONSIBILITY TO REPLACE THE DISK OR REFUND THE PURCHASE PRICE. ANY REPLACEMENT DISK IS WARRANTED FOR THE REMAINDER OF THE ORIGINAL WARRANTY PERIOD OR THIRTY (30) DAYS, WHICHER IS LONGER. EXCEPT AS STATED ABOVE FOR THE DISK(S), THE SOFTWARE AND THE DOCUMENTATION ARE PROVIDED WITHOUT WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. NO ORAL OR WRITTEN INFORMATION OR ADVICE GIVEN BY STRUWARE SHALL CREATE A WARRANTY OR IN ANY WAY INCREASE THE SCOPE OF THIS WARRANTY, AND YOU MAY NOT RELY ON ANY SUCH INFORMATION OR ADVICE. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY HAVE OTHER RIGHTS, WHICH VARY FROM STATE TO STATE. NEITHER STRUWARE NOR ANYONE ELSE WHO HAS BEEN INVOLVED IN THE CREATION, PRODUCTION, OR DELIVERY OF THIS PRODUCT SHALL BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, OR INCIDENTAL DAMAGES, INCLUDING DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION, AND THE LIKE (ARISING OUT OF THE USE OF OR INABILITY TO USE SUCH PRODUCTS), EVEN IF STRUWARE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. BECAUSE SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. 11 MISCELLANEOUS. This Agreement expresses the entire agreement between Struware and the LICENSEE, and supersedes any prior communication, oral or written, relating to this software. The laws of the state of Florida govern this Agreement. RESTRICTED RIGHTS LEGEND The Software and documentation is commercial computer software as defined in DFARS 252.227.7014(a)(1). The Government shall have only those rights specified in this Agreement.

Page 18

Software License Agreement

MENT BETWEEN YOU ONSTITUTES EE TO THE TERMS E FOR A FULL REFUND.

et of STRUWARE. agreement and ers to use this

hich is part of the price paid able license, mputer at a single mputers at a single

interests in the software and WARE. The he right to use the of the original

written materials are protected been modified, dden. You may by your failure o these restrictions, oses as permitted e does not provide

he software from one ime. You may not nying written mpile, disassemble, slate, or create STRUWARE. ENSEE, and may not be may you transfer, except as expressly

will terminate automatically

versions of the software e released within

at the disk(s) or electronic and workmanship evidenced by a

Page 19

Software License Agreement

ations on duration

TWARE AND

OR IMPLIED.

HE RESULTS MATERIALS

PLACE THE

RMATION OR

etween Struware and the s software. The

efined in DFARS

Page 20

the 1997 Standard Building Code, except the wind loading is ASCE7-98 (there is no seismic or snow in the FBC). Therefore, this program can be used for the Florida Building Code. But you couldn't use this program for the 1997 Standard Building Code, since it references ASCE7-95 as the acceptable alternate. If you have more than one type of load such as dead loads or snow, you can add a second sheet. For example right click on the "snow" tab at the bottom of the page, select "move or copy", select the sheet you want to copy, check the box "Create a copy", then click on the OK button. You will have a new sheet titled "snow(2)".

First Issue 7/18/2003 - Code03 Revised entire Code00 program to accommodate ASCE 7 - 02 building code and 2003 IBC.

Tables

GCp angle Area 01 2 3 all over 2 over 3 10.01-30 1 2 3 all over 2 over 3 30.01-45 1 2 3 all over 2 over 3 monoslope 3-10 1 2 3 all 2' 3' monoslope 10-30 1 2 3 all 2' 3' 10 sf -1.00 -1.80 -2.80 0.30 -1.70 -2.80 -0.90 -2.10 -2.10 0.50 -2.20 -3.70 -1.00 -1.20 -1.20 0.90 -2.00 -2.00 -1.10 -1.30 -1.80 0.30 -1.60 -2.60 -1.30 -1.60 -2.90 0.40 0.00 0.00 10 sf -1.40 -2.30 -3.20 50 sf -0.93 -1.31 -1.61 0.23 -1.63 -1.40 -0.83 -1.61 -1.61 0.36 -2.20 -2.86 -0.86 -1.06 -1.06 0.83 -1.86 -1.86 -1.10 -1.23 -1.38 0.23 -1.53 -1.90 -1.16 -1.32 -2.27 0.33 0.00 0.00 100 sf -1.11 -1.89 -2.67 100 sf -0.90 -1.10 -1.10 0.20 -1.60 -0.80 -0.80 -1.40 -1.40 0.30 -2.20 -2.50 -0.80 -1.00 -1.00 0.80 -1.80 -1.80 -1.10 -1.20 -1.20 0.2 -1.50 -1.60 -1.10 -1.20 -2.00 0.30 0.00 0.00 500 sf -0.90 -1.60 -2.30 70 -0.92 -1.21 -1.36 0.22 -1.62 -1.11 -0.82 -1.51 -1.51 0.33 -2.20 -2.69 -0.83 -1.03 -1.03 0.82 -1.83 -1.83 -1.10 -1.22 -1.29 0.22 -1.52 -1.75 -1.13 -1.26 -2.14 0.32 0.00 0.00 roof1

roof2

roof3

roof4

roof5

h>60, angle<10 1 2 3

300 -0.97 roof6 -1.69 -2.42

Page 22

Weights

Weights of Materials (psf) Roofing Materials: None Asphalt Shingles w/roll roofing Wood Shingles Clay Tile Clay Tile w/ mortar Slate (1/4" thk) Slate (3/8" thk) Concrete tile Spanish Tile Metal, copper, or tin sheets 5 ply felt & gravel 3 ply felt & gravel 5 ply composite, no gravel 3 ply composite, no gravel Single ply Zonolite roof, deck & concrete Insulation: None Rock Wool per 1" thk Glass Wool per 1" thk R-30 Fiberglass insul. R-19 Fiberglass insul. R-11 Fiberglass insul. Rigid insulation, per 1" Styrofoam, per 1" thk Zonolite insulation per 1" Decking Materials: None

min psf 0 3 3 14 19 10 15 16 19 1.5 6.5 5.5 2.5 1.5 1 7 0 2 2 8 16 9 13 14 16 1 6 5 2 1 1 5.7

8 1 7

0 0.2 0.3 0.9 0.6 0.35 1.5 0.2 0.15

0 0.2 0.3 0.9 0.6 0.35 0.7 0.2 0.01

0 Page 23

Weights

Metal Roof deck, 1.5, 22 ga. Metal Roof deck, 1.5, 20 ga. Metal Floor deck - 2", 20ga Metal Floor deck - 2", 18ga Metal Floor deck - 3", 20ga Metal Floor deck - 3", 18ga 7/16" plywood/OSB 1/2" plywood/OSB 5/8" plywood/OSB 3/4" plywood/OSB 1 1/8" plywood/OSB Topping/flooring: None Concrete regular per 1" Concrete lightwt per 1" Deflection Concrete Vermiculite concrete per 1" Poured gypsum per 1" Hardwood (Nominal 1") Sheet vinyl Carpet & pad Ceramic tile (3/4") Thin Set Tile Terrazo (1 1/2") Ceilings: None Acoustical fiber 1/2" gypsum board 5/8" gypsum Plaster per 1" 1" plaster on metal lathe 1" plaster on wood lathe FRAMING: None Steel roof joists & girders Steel roof beams & girders Steel floor bms/joists & girders Wood Trusses @ 24" Wood 2x @24" LVL @ 24" TJI @ 24" Other: None Sprinklers Mech. & Elec. Partitions Sprinklers

1.7 2.5 2 3 2.5 3 1.6 1.8 2.2 2.7 4.1

1.2 2 1.5 2 1.5 2.5 1.4 1.5 1.8 2.3 3.4

0 12.5 10 12.5 2.5 6.5 2 1.5 1 10 4 19

0 12 8.5 2 1.8 6 2 0.5 1 8 3 16

0 1 2.2 2.8 8 8.5 10

0 0.8 2 2.5 6 6 8

0 3 5 8 3 1.5 3 2

0 2 3 5 2.5 1.5 2 1

0 2 2 20 2 Page 24

0 1.5 0 0 0

Weights

Misc.

0.5

Page 25