Você está na página 1de 10

Users Guide to IEC Type 1 and Type 2 Coordination

Application Note

April 2007 Supersedes February 2007

What is it?
The International Electrotechnical Commission (IEC) developed short circuit performance criteria for contactors and starters called Type 1 coordination and Type 2 coordination. This denes motor controller protection levels following a short circuit fault. In order to achieve this performance, the combination of a motor controller (contactor or starter) and short circuit protective device (manual motor protector, circuit breaker or fuse) must meet the following criteria as specied by IEC 60947-4-1 Low voltage switchgear and controlgear Part 4-1: Contactors and motor-starters Electromechanical contactors and motor-starters: Type 1 Coordination requires that under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts.

Manual Motor Controller

In this case, signicant damage is allowed to the contactor/ starter (e.g. contact welding, burning, or disintegration) and the overload relay (e.g. component harm or heater element burn-out). Type 2 Coordination requires that under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards to the maintenance of the equipment. In this case, the contactor/starter is able to continue use after the occurrence of a short circuit fault. Light contact burning or tack welding may occur provided the contacts are easily separable.

Who benets and why?


Series G Molded Case Circuit Breaker

Achieving an acceptable level of short circuit coordination requires knowledge about the application, product standards, installation codes and the attributes of the many short circuit protective devices (SCPDs) that are available. Extensive testing must be completed and certied in order to achieve a Type 1 or 2 rating. IEC 60947-4-1 offers precise denitions of allowable damage in order to guide users to the right product with the right protection. Generally speaking, most users expect Type 2 protection in their applications. With certifying agencies varying from country-to-country and continent-to-continent, users will sometimes mistakenly assume that Type 2 coordination has been achieved if their motor branch circuit components are CE marked, UL Listed Type E or F and/or CSA Certied. This is not necessarily true.

XT Starter

AP03407001E

For more information visit: www.eaton.com

Application Note
Page 2 Effective: April 2007

Users Guide to IEC Type 1 and Type 2 Coordination

At the forefront of Type 2 benets comes the assurance that the device poses no threat of danger to the person or installation. Furthermore, with increased emphasis placed on reducing downtime to increase productivity, proper application and selection of motor branch circuit devices is more important than ever. By selecting the proper type of protection, the working environment and employees can be protected against hazardous fault conditions and the performance of contactors and overload relays in the branch circuit can be maximized. Type 2 protection provides condence that motor control components will be operable following a short circuit fault. This reusability translates into hundreds or even thousands of dollars in savings due to reduced downtime and replacement costs. TYPE 2 Coordination = Safety + Less Downtime = Dollars and Cents

Standard Fault Short Circuit Current Rating (Derived from UL 508): The minimum short circuit current, based on horsepower rating, that a starter must be capable of withstanding in accordance with the applicable pass/fail criteria. Denoted as Ir by IEC 60947-4-1 and Icr by IEC 60947-6-2. Manufacturers may also specify short circuit ratings exceeding the minimum ratings required by standards. UL and CSA refer to these as the High-Available Fault Short Circuit Current Rating. IEC 60947-4-1 and 60947-6-2 refer to these ratings as Iq and Ics respectively. High-Available Fault Short Circuit Current Rating (Derived from UL 508): The short circuit current rating specied by the manufacturer of a motor controller, which is greater than the standard short circuit current rating. The motor controller is capable of withstanding the high-available short circuit current in accordance with the applicable pass/fail criteria. Denoted as Iq by IEC 60947-4-1 and I cs by IEC 60947-6-2. Following is a summary of short circuit testing pass/fail criteria applicable to magnetically operated direct-on-line contactors and starters. Standards should be referenced for exact wording and all specic pass/fail criteria. UL and IEC criteria are summarized for standard and high-available short circuit currents. CSA criteria are summarized for highavailable short circuit currents.

How does Eaton comply?


It is important to understand the short circuit testing pass/ fail criteria of the applicable product standards (UL 508, CSA C22.2 No. 14 and IEC 60947) when specifying products for each application. Each standard requires that devices are capable of withstanding minimum short circuit currents (based on the starters rating). UL and CSA refer to the minimum rating as the Standard Fault Short Circuit Current Rating. IEC 60947-4-1 and 60947-6-2 refer to these ratings as Ir and Icr respectively.

Table 1. Dening Pass/Fail Criteria: UL 508/CSA C22.2 No. 14 and IEC 60947-4-1
UL and CSA IEC 60947-4-1 Type 1 Fault Current Enclosure Terminals and Conductors Contactor/Starter Housing Short Circuit Protective Device (SCPD) Contactor/Starter Contacts Overload Relay Type 2

Fault current is successfully interrupted and no arcing to enclosure or proximity barrier is indicated by an open ground wire or fuselink. No substantial damage to the enclosure. It may be deformed but it must be possible to open the door. Live parts shall not be accessible. No damage to conductors or terminals. Conductors must not be separated from the terminals. No cracking or breaking of the contactor/starter housing that impairs the integrity of the mounting of live parts. The circuit breaker or switch must be capable of being operated manually. SCPD is not separated from its mounting means. Fuses must not rupture. Welding and complete disintegration acceptable. Electronic overload relays must be operable; tripping characteristics must be veried (UL). Mechanical overload relays may be damaged, if so, device must include markings indicating that (UL). May be inoperable. No discharge of parts from enclosure. No risk of re. Welding acceptable. Damage acceptable. Welding acceptable provided contacts can be easily separated. No damage, tripping characteristics must be veried.

Contactor/Starter Operation Other

May be inoperable. No discharge of parts from enclosure. Must pass 2X rated voltage, 1000V minimum dielectric test.

Must be operable, veried by 10 operations after short circuit test. No discharge of parts from enclosure. Must pass 2X rated voltage, 1000V minimum dielectric test.

For more information visit: www.eaton.com

AP03407001E

Users Guide to IEC Type 1 and Type 2 Coordination

Application Note
Effective: April 2007 Page 3

What branch circuit devices do you need for Type 2?


Achieving Type 2 is straightforward when using the following selection tables. Follow these steps to ensure that Type 2 coordination is in place: Step 1: Determine the motor Horsepower or kW (single or three phase) or full load motor current from the motor nameplate. Step 2: Verify the motor full load amps are less than or equal to the operational current (Ie) listed next to the hp or kW in the table. Step 3: Manual Motor Controllers (MMC): Read across the tables horizontally for catalog numbers of the Manual Motor Protector (MMP) and contactor (customer assembly) or pre-assembled Manual Motor Controller.
Note: For certain horsepowers at 480V and 600V, a current limiter must be used to achieve the maximum Type 2 rating (shown in the following tables). Customers can either order the MMP and Current Limit Contactors or an assembled MMC and current limiter.

Circuit breaker combination controllers: Read across the tables horizontally to determine the catalog numbers of the circuit breaker to be used in conjunction with the contactor and overload relay listed (customer assembly) or the pre-assembled motor starter. Fused combination controllers: Read across the tables horizontally to determine what amperage size fuse (customer to specify brand) and the catalog numbers of the contactor and overload relay or the pre-assembled motor starter.

Manual Motor Controller Combinations


Table 2. 400, 415V Type 2 Coordination MMC
P (kW) 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 5.50 7.50 11.0 15.0 18.5 22.0 30.0 34.0

Ie (A) 0.21 0.31 0.41 0.60 0.80 1.10 1.50 1.90 2.60 3.60 5.00 6.60 8.50 11.3 16.0 21.7 29.3 11.3 16.0 21.7 29.3 36.0 41.0 55.0 63.0

Iq (kA) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 (150) 50 50 50 50 50 50 50 50 50 50 50 50

MMP Catalog Number XTPRP25BC1 XTPRP40BC1 XTPRP63BC1 XTPRP63BC1 XTPR001BC1 XTPR1P6BC1 XTPR1P6BC1 XTPR2P5BC1 XTPR004BC1 XTPR004BC1 XTPR6P3BC1 XTPR010BC1 XTPR010BC1 XTPR012BC1 XTPR016BC1 XTPR025BC1 XTPR032BC1 XTPR016DC1 XTPR016DC1 XTPR025DC1 XTPR032DC1 XTPR040DC1 XTPR050DC1 XTPR058DC1 XTPR063DC1

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE025C10_ XTCE032C10_ XTCE018C10_ XTCE018C10_ XTCE025C10_ XTCE032C10_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE065D00_

MMC Catalog Number XTSCP25BB_ XTSCP40BB_ XTSCP63BB_ XTSCP63BB_ XTSC001BB_ XTSC1P6BB_ XTSC1P6BB_ XTSC2P5BB_ XTSC004BB_ XTSC004BB_ XTSC6P3BB_ XTSC010BC_ XTSC010BC_ XTSC012BC_ XTSC016BC_ XTSC025BC_ XTSC032BC_ XTSC016DC_ XTSC016DC_ XTSC025DC_ XTSC032DC_ XTSC040DD_ XTSC050DD_ XTSC058DD_ XTSC063DD_

Values in parentheses ( ) are for Type 1 Coordination. Underscore (_) indicates magnet coil sufx required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

AP03407001E

For more information visit: www.eaton.com

Application Note
Page 4 Effective: April 2007

Users Guide to IEC Type 1 and Type 2 Coordination

Table 3. 480V Type 2 Coordination MMC


P (hp) 1/2 1/2 1/2 1/2 1/2 3/4 1 2 2 3 3 7-1/2 7-1/2 10 10 20 25 25 30 40 40 40

Ie (A) 0.24 0.32 0.51 0.74 0.94 1.32 1.72 2.55 3.10 4.55 6.15 8.40 11.0 14.5 20.0 20.0 27.0 32.0 37.5 40.5 50.5 64.0

Iq (kA) 65 65 65 65 65 65 65 65 65 65 (50) 65 (50) 65 (50) 65 (50) 65 (50) 65 (50) 65 65 65 65 65 65 65

MMP Catalog Number XTPRP25BC1 XTPRP40BC1 XTPRP63BC1 XTPR001BC1 XTPR001BC1 XTPR1P6BC1 XTPR2P5BC1 XTPR004BC1 XTPR004BC1 XTPR6P3BC1 XTPR6P3BC1 XTPR010BC1 XTPR012BC1 XTPR016BC1 XTPR020BC1 XTPR025DC1 XTPR032DC1 XTPR032DC1 XTPR040DC1 XTPR050DC1 XTPR058DC1 XTPR063DC1

Current Limiter Catalog Number

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE025C10_ XTCE040D00_ XTCE040D00_ XTCE040D00_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE065D00_

MMC Catalog Number XTSCP25BB_ XTSCP40BB_ XTSCP63BB_ XTSC001BB_ XTSC001BB_ XTSC1P6BB_ XTSC2P5BC_ XTSC004BC_ XTSC004BC_ XTSC6P3BC_ XTSC6P3BC_ XTSC010BC_ XTSC012BC_ XTSC016BC_ XTSC020BC_ XTSC025DD_ XTSC032DD_ XTSC032DD_ XTSC040DD_ XTSC050DD_ XTSC058DD_ XTSC063DD_

XTPAXCL XTPAXCL XTPAXCL XTPAXCL XTPAXCL XTPAXCL

Values in parentheses ( ) are achieved without the current limiter. Underscore (_) indicates magnet coil sufx required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

Table 4. 600V Type 2 Coordination MMC


P (hp) 1/2 1/2 1/2 1/2 1/2 1 1 1-1/2 1-1/2 3 5 10 10 10 10 25 30 30 30 40 40 50

Ie (A) 0.19 0.26 0.41 0.59 0.75 1.06 1.38 2.04 2.48 3.64 4.92 6.72 8.60 11.5 16.0 21.5 25.5 30.0 37.5 40.5 51.0 61.0

Iq (kA) 50 50 50 50 50 50 50 50 50 50 50 (18) 50 (18) 50 (18) 50 (18) 50 (18) 50 50 50 50 50 42 42

MMP Catalog Number XTPRP25BC1 XTPRP40BC1 XTPRP63BC1 XTPRP63BC1 XTPR001BC1 XTPR1P6BC1 XTPR1P6BC1 XTPR2P5BC1 XTPR2P5BC1 XTPR004BC1 XTPR6P3BC1 XTPR010BC1 XTPR010BC1 XTPR012BC1 XTPR016BC1 XTPR025DC1 XTPR032DC1 XTPR032DC1 XTPR040DC1 XTPR050DC1 XTPR058DC1 XTPR063DC1

Current Limiter Catalog Number

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE040D00_ XTCE040D00_ XTCE040D00_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE065D00_

MMC Catalog Number XTSCP25BB_ XTSCP40BB_ XTSCP63BB_ XTSCP63BB_ XTSC001BB_ XTSC1P6BB_ XTSC1P6BB_ XTSC2P5BC_ XTSC2P5BC_ XTSC004BC_ XTSC6P3BC_ XTSC010BC_ XTSC010BC_ XTSC012BC_ XTSC016BC_ XTSC025DD_ XTSC032DD_ XTSC032DD_ XTSC050DD_ XTSC050DD_ XTSC058DD_ XTSC063DD_

XTPAXCL XTPAXCL XTPAXCL XTPAXCL XTPAXCL

Values in parentheses ( ) are achieved without the current limiter. Underscore (_) indicates magnet coil sufx required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

For more information visit: www.eaton.com

AP03407001E

Users Guide to IEC Type 1 and Type 2 Coordination

Application Note
Effective: April 2007 Page 5

Contactor and Overload Relay (Motor Starter) with Fused Disconnect


Table 5. 400, 415V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Fused Disconnect
P (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160. 200. 250.

Ie (A) 0.41 0.60 0.80 1.10 1.50 1.90 2.60 3.60 5.00 6.60 8.50 11.3 16.0 21.7 29.3 36.0 41.0 55.0 68.0 81.0 99.0 134. 161. 196. 231. 279. 349. 437.

Iq (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Fuses Class gG/gL 2 2 4 4 4 6 6 6 10 16 20 25 32 40 63 63 80 100 125 160 200 200 250 315 400 400 500 630

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE009B10_ XTCE018C10_ XTCE018C10_ XTCE025C10_ XTCE032C10_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE080F00_ XTCE095F00_ XTCE115G00_ XTCE150G00_ XTCE185L22_ XTCE225L22_ XTCE250L22_ XTCE300M22_ XTCE400M22_ XTCE500M22_

Overload Relay Catalog Number XTOBP60BC1 XTOB001BC1 XTOB001BC1 XTOB1P6BC1 XTOB1P6BC1 XTOB2P4BC1 XTOB004BC1 XTOB004BC1 XTOB006BC1 XTOB010BC1 XTOB010BC1 XTOB016CC1 XTOB016CC1 XTOB024CC1 XTOB032CC1 XTOB040DC1 XTOB057DC1 XTOB057DC1 XTOB070GC1 XTOB100GC1 XTOB100GC1 XTOB150GC1 XTOB220LC1 XTOB220LC1 XTOB250LC1 XTOT290C35 XTOT400C35 XTOT540C35

Assembled Starter Catalog Number XTAE007B10_P60 XTAE007B10_001 XTAE007B10_001 XTAE007B10_1P6 XTAE007B10_1P6 XTAE007B10_2P4 XTAE007B10_004 XTAE007B10_004 XTAE007B10_006 XTAE007B10_010 XTAE009B10_010 XTAE018C10_016 XTAE018C10_016 XTAE032C10_024 XTAE032C10_032 XTAE040D00_040 XTAE065D00_057 XTAE065D00_057 XTAE080F00_070 XTAE095F00_100 XTAE115G00_100 XTAE150G00_150 XTAE185L22_220 XTAE225L22_220 XTAE250L22_250 XTAE300M22_290 XTAE400M22_400 XTAE500M22_540

Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

Table 6. 500V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Fused Disconnect
P (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160.

Ie (A) 0.33 0.48 0.70 0.90 1.20 1.50 2.10 2.90 4.00 5.30 6.80 9.00 12.1 17.4 23.4 28.9 33.0 44.0 54.0 65.0 79.0 107. 129. 157. 184. 224.

Iq (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Fuses Class gG/gL 2 2 2 2 4 4 6 6 10 16 16 20 25 32 50 50 63 80 100 125 160 200 200 250 250 315

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE009B10_ XTCE009B10_ XTCE012B10_ XTCE018C10_ XTCE025C10_ XTCE040D00_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE080F00_ XTCE095F00_ XTCE115G00_ XTCE185L22_ XTCE185L22_ XTCE185L22_ XTCE185L22_ XTCE225L22_

Overload Relay Catalog Number XTOBP40BC1 XTOBP60BC1 XTOB001BC1 XTOB001BC1 XTOB1P6BC1 XTOB1P6BC1 XTOB2P4BC1 XTOB004BC1 XTOB006BC1 XTOB006BC1 XTOB010BC1 XTOB010BC1 XTOB016CC1 XTOB024CC1 XTOB024DC1 XTOB040DC1 XTOB040DC1 XTOB057DC1 XTOB070GC1 XTOB070GC1 XTOB100GC1 XTOB125LC1 XTOB125LC1 XTOB160LC1 XTOB220LC1 XTOB250LC1

Assembled Starter Catalog Number XTAE007B10_P40 XTAE007B10_P60 XTAE007B10_001 XTAE007B10_001 XTAE007B10_1P6 XTAE007B10_1P6 XTAE007B10_2P4 XTAE007B10_004 XTAE007B10_006 XTAE009B10_006 XTAE009B10_010 XTAE012B10_010 XTAE018C10_016 XTAE025C10_024 XTAE040D00_024 XTAE040D00_040 XTAE050D00_040 XTAE065D00_057 XTAE080F00_070 XTAE095F00_070 XTAE115G00_100 XTAE185L22_125 XTAE185L22_125 XTAE185L22_160 XTAE185L22_220 XTAE225L22_250

Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

AP03407001E

For more information visit: www.eaton.com

Application Note
Page 6 Effective: April 2007

Users Guide to IEC Type 1 and Type 2 Coordination

Table 7. 690V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Fused Disconnect
P (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160.

Ie (A) 0.24 0.35 0.50 0.70 0.90 1.10 1.50 2.10 2.90 3.80 4.90 6.50 8.80 12.6 17.0 20.9 23.8 32.0 39.0 47.0 58.0 78.0 93.0 114. 134. 162.

Iq (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Fuses Class gG/gL 1 2 2 2 4 4 4 6 10 10 16 16 20 25 32 32 50 63 80 80 100 160 160 200 250 250

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE009B10_ XTCE012B10_ XTCE018C10_ XTCE025C10_ XTCE032C10_ XTCE040D00_ XTCE040D00_ XTCE065D00_ XTCE080F00_ XTCE080F00_ XTCE080F00_ XTCE095F00_ XTCE115G00_ XTCE185L22_ XTCE185L22_ XTCE185L22_

Overload Relay Catalog Number XTOBP40BC1 XTOBP40BC1 XTOBP60BC1 XTOB001BC1 XTOB001BC1 XTOB1P6BC1 XTOB1P6BC1 XTOB2P4BC1 XTOB004BC1 XTOB004BC1 XTOB006BC1 XTOB010BC1 XTOB010CC1 XTOB016CC1 XTOB024CC1 XTOB024DC1 XTOB040DC1 XTOB040DC1 XTOB050GC1 XTOB050GC1 XTOB070GC1 XTOB100GC1 XTOB100GC1 XTOB125LC1 XTOB160LC1 XTOB220LC1

Assembled Starter Catalog Number XTAE007B10_P40 XTAE007B10_P40 XTAE007B10_P60 XTAE007B10_001 XTAE007B10_001 XTAE007B10_1P6 XTAE007B10_1P6 XTAE007B10_2P4 XTAE007B10_004 XTAE007B10_004 XTAE009B10_006 XTAE012B10_010 XTAE018C10_010 XTAE025C10_016 XTAE032C10_024 XTAE040D00_024 XTAE040D00_040 XTAE065D00_040 XTAE080F00_050 XTAE080F00_050 XTAE080F00_070 XTAE095F00_100 XTAE115G00_100 XTAE185L22_125 XTAE185L22_160 XTAE185L22_220

Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

Table 8. 400, 415V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Fused Disconnect
P (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0

Ie (A) 0.41 0.60 0.80 1.10 1.50 1.90 2.60 3.60 5.00 6.60 8.50 11.3 16.0 21.7 29.3 36.0 41.0 55.0

Iq (kA) 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80

Fuses Class BS88 4 4 4 6 10 16 16 20 20 20 25 25 25 35 & 32M35 50 63 80 100

Contactor Catalog Number XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE007B10_ XTCE009B10_ XTCE018C10_ XTCE018C10_ XTCE025C10_ XTCE032C10_ XTCE040D00_ XTCE050D00_ XTCE065D00_

Overload Relay Catalog Number XTOBP60BC1 XTOBP60BC1 XTOB001BC1 XTOB1P6BC1 XTOB1P6BC1 XTOB2P4BC1 XTOB004BC1 XTOB004BC1 XTOB006BC1 XTOB010BC1 XTOB010BC1 XTOB016CC1 XTOB016CC1 XTOB024CC1 XTOB032CC1 XTOB040DC1 XTOB057DC1 XTOB065DC1

Assembled Starter Catalog Number XTAE007B10_P60 XTAE007B10_P60 XTAE007B10_001 XTAE007B10_1P6 XTAE007B10_1P6 XTAE007B10_2P4 XTAE007B10_004 XTAE007B10_004 XTAE007B10_006 XTAE007B10_010 XTAE009B10_010 XTAE018C10_016 XTAE018C10_016 XTAE032C10_024 XTAE032C10_032 XTAE040D00_040 XTAE065D00_057 XTAE065D00_065

GEC/Alstom Red Spot. Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

For more information visit: www.eaton.com

AP03407001E

Users Guide to IEC Type 1 and Type 2 Coordination

Application Note
Effective: April 2007 Page 7

Contactor and Overload Relay (Motor Starter) with Circuit Breaker


Table 9. 400, 415V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Circuit Breaker
P (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160. 200. 250.

Ie (A) 0.41 0.60 0.80 1.10 1.50 1.90 2.60 3.60 5.00 6.60 8.50 11.3 16.0 21.7 29.3 36.0 41.0 55.0 68.0 81.0 99.0 134. 161. 196. 231. 279. 349. 430.

Iq (kA) 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 50 50 50 80 80 80 80 80 70 70 70 70 70

Circuit Breaker

Contactor Catalog Number


Overload Relay Catalog Number


Assembled Starter Catalog Number


HMCPE015E0C HMCPE015E0C

XTCE018C10_ XTCE018C10_

XTOB010CC1 XTOB016CC1

XTAE018C10_010 XTAE018C10_016

HMCPE100R3C HMCPE100R3C HMCPJ250D5L HMCPJ250F5L HMCPJ250G5L HMCPJ250J5L HMCPJ250W5L HMCPJ250W5L HMCPL600R6G HMCPL600X6G HMCPL600P6G HMCPL600M

XTCE050D00_ XTCE065D00_ XTCE080F00_ XTCE095F00_ XTCE115G00_ XTCE150G00_ XTCE185L22_ XTCE225L22_ XTCE300M22_ XTCE300M22_ XTCE400M22_ XCE500M22_

XTOB057DC1 XTOB065DC1 XTOB070GC1 XTOB100GC1 XTOB125GC1 XTOB150GC1 XTOB220LC1 XTOB220LC1 XTOT240C3S XTOT400C3S XTOT400C3S XTOT540C3S

XTAE050D00_057 XTAE065D00_065 XTAE080F00_070 XTAE095F00_100 XTAE115G00_125 XTAE150G00_150 XTAE185L22_220 XTAE225L22_220 XTAE300M22_240 XTAE300M22_400 XTAE400M22_400 XTAE500M22_540

Underscore (_) indicates magnet coil code required. See Table 14, Page 9. Use MMP contactor combination. See Table 2, Page 3.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

Table 10. 525V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Circuit Breaker
P (kW) 0.37 0.55 0.75 1.10 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160. 200.

Ie (A) 1.02 1.22 1.66 2.22 3.16 4.25 5.60 7.50 9.90 14.1 19.3 23.5 27.2 37.0 45.0 54.0 66.0 79.0 111. 130. 159. 185. 225. 270.

Iq (kA) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 42 50 50 25 25 50 50 25 25 50

Circuit Breaker

Contactor Catalog Number


Overload Relay Catalog Number


Assembled Starter Catalog Number


HMCP100R3C HMCPJ250D5L HMCPJ250F5L HMCPJ250J5L HMCPJ250K5L HMCPJ250W5L HMCPL600N6G HMCPL600R6G HMCPL600X6G

XTCE080F00_ XTCE080F00_ XTCE115G00_ XTCE115G00_ XTCE185L00_ XTCE185L00_ XTCE185L22_ XTCE225L22_ XTCE300M22_

XTOB070GC1 XTOB070GC1 XTOB100GC1 XTOB125GC1 XTOB160LC1 XTOB160LC1 XTOB220LC1 XTOB250LC1 XTOT290C3S

XTAE080F00_070 XTAE080F00_070 XTAE115G00_100 XTAE115G00_125 XTAE185L00_160 XTAE185L00_160 XTAE185L22_220 XTAE225L22_250 XTAE300M22_290

Underscore (_) indicates magnet coil code required. See Table 14, Page 9. Use MMP contactor combination. See Table 4, Page 4.

Note: See Page 9 for more information on Wye-Delta (Star-Delta) applications.

AP03407001E

For more information visit: www.eaton.com

Application Note
Page 8 Effective: April 2007

Users Guide to IEC Type 1 and Type 2 Coordination

Table 11. 480V Type 2 Coordination Contactor and Overload Relay (Motor Starter) with Circuit Breaker
P (hp) 50.0 60.0 75.0 100. 125. 150. 200. 250. 300. 350.

Ie (A) 65.0 77.0 96.0 124. 156. 180. 240. 290. 361. 414.

Iq (kA) 65 65 25 50 50 25 50 50 50 50

Circuit Breaker HMCPJ250D5L HMCPJ250G5L HMCPJ250J5L HMCPJ250K5L HMCPJ250W5L HMCPL600N6G HMCPL600N HMCPL600R HMCPL600Y HMCPL600M

Contactor Catalog Number XTCE080F00_ XTCE080F00_ XTCE115G00_ XTCE185L22_ XTCE185L22_ XTCE225L22_ XTCE300M22__ XTCE300M22_ XTCE400M22_ XTCE500M22_

Overload Relay Catalog Number XTOB070GC1 XTOB100GC1 XTOB125GC1 XTOB160LC1 XTOB160LC1 XTOB220LC1 XTOB240C3S XTOB290C3S XTOB400C3S XTOB540C3S

Assembled Starter Catalog Number XTAE080F00_070 XTAE080F00_100 XTAE115G00_125 XTAE185L22_160 XTAE185L22_160 XTAE225L22_220 XTAE300M22_240 XTAE300M22_290 XTAE400M22_400 XTAE500M22_540

Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Contactor with Circuit Breaker


Table 12. 400, 415V Type 2 Coordination Contactor with Circuit Breaker
P (kW) 1.50 2.20 3.00 4.00 5.50 7.50 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0 110. 132. 160. 200. 250.

Ie (A) 3.60 5.00 6.60 8.50 11.3 16.0 21.7 29.3 36.0 41.0 55.0 68.0 81.0 99.0 134. 161. 196. 231. 279. 350. 430.

Iq (kA) 50 50 50 50 50 50 50 50 50 50 50 80 80 80 80 80 80 70 70 70 70

Circuit Breaker MCP HMCPE015E0C HMCPE015E0C HMCPE015E0C HMCPE015E0C HMCPE015E0C HMCPE015E0C HMCPE100R3C HMCPE100R3C HMCPE100R3C HMCPE100R3C HMCPE100R3C HMCPJ250D5L HMCPJ250F5L HMCPJ250G5L HMCPJ250J5L HMCPJ250W5L HMCPJ250W5L HMCPL600R HMCPL600X HMCPL600P HMCPL600M

Contactor Catalog Number XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE018C10_ XTCE040D00_ XTCE040D00_ XTCE040D00_ XTCE050D00_ XTCE065D00_ XTCE080F00_ XTCE095F00_ XTCE115G00_ XTCE150G00_ XTCE185L22_ XTCE225L22_ XTCE300M22_ XTCE300M22_ XTCE400M22_ XTCE500M22_

For use with magnetic sensing means to monitor motor current. Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

Table 13. 480V Type 2 Coordination Contactor with Circuit Breaker


P (hp) 50.0 60.0 150. 200. 250. 300. 350.

Ie (A) 65.0 77.0 180. 240. 300. 361. 414.

Iq (kA) 65 65 50 50 50 50 50

Circuit Breaker MCP HMCPJ250G5L HMCPJ250G5L HMCPL600N HMCPL600N HMCPL600R HMCPL600Y HMCPL600M

Contactor Catalog Number XTCE080F00_ XTCE080F00_ XTCE300M00_ XTCE300M22__ XTCE300M22_ XTCE400M00_ XTCE500M00_

For use with magnetic sensing means to monitor motor current. Underscore (_) indicates magnet coil code required. See Table 14, Page 9.

For more information visit: www.eaton.com

AP03407001E

Users Guide to IEC Type 1 and Type 2 Coordination

Application Note
Effective: April 2007 Page 9

Wye-Delta (Star-Delta) Applications


If Type 2 Coordination is required when using Wye-Delta starters, the full voltage (direct on-line) test data that is included in this document is valid. To ensure proper protection, the K1M (Main), K3M (Star) and K5M (Delta) contactors must all be the same size (amperage). For Wye-Delta starter kits, please see the XT. IEC Power Control section in Tab 34 of Eatons Control Products Catalog, CA08102001E.

Magnet Coil Sufx Reference


Table 14. Magnet Coil Sufx
Coil Voltage Sufx Code A B F T TD C D E G H L N P R U W Y AD BD RD WD Coil Voltage Sufx Code A B F T TD C D E G H L N P R U W Y AD BD RD WD Coil Voltage Sufx Code A B T TD C L W AD BD WD A C Y TD

Frame A B
110V 50 Hz, 120V 60 Hz 220V 50 Hz, 240V 60 Hz 230V 50 Hz 24V 50/60 Hz 24V DC 415V 50 Hz, 480V 60 Hz 550V 50 Hz, 600V 60 Hz 208V 60 Hz 190V 50 Hz, 220V 60 Hz 240V 50 Hz, 277V 60 Hz 380V 50 Hz, 440V 60 Hz 400V 50 Hz 380V 60 Hz 12V 50/60 Hz 24V 50 Hz 42V 50 Hz, 48V 60 Hz 48V 50 Hz 120V DC 220V DC 12V DC 48V DC

Frame C F
110V 50 Hz, 120V 60 Hz 220V 50 Hz, 240V 60 Hz 230V 50 Hz 24V 50/60 Hz 24 27V DC 415V 50 Hz, 480V 60 Hz 550V 50 Hz, 600V 60 Hz 208V 60 Hz 190V 50 Hz, 220V 60 Hz 240V 50 Hz, 277V 60 Hz 380V 50 Hz, 440V 60 Hz 400V 50 Hz 380V 60 Hz 12V 50/60 Hz 24V 50 Hz 42V 50 Hz, 48V 60 Hz 48V 50 Hz 110 130V DC 200 240V DC 12 14V DC 48 60V DC

Frame G
100 120V 50/60 Hz 190 240V 50/60 Hz 24V 50/60 Hz 24 27V DC 480 500V 50/60 Hz 380 440V 50/60 Hz 42 48V 50/60 Hz 110 130V DC 200 240V DC 48 60V DC

Frame L M
110 250V 40 60 Hz/DC 250 500V 40 60 Hz/DC 48 110V 40 60 Hz/DC 24 48V DC

With DC operation: Integrated diode-resistor combination, coil rating 2.6W.

AP03407001E

For more information visit: www.eaton.com

Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN CARE (877-386-2273) Eaton.com

2007 Eaton Corporation All Rights Reserved Printed in USA Publication No. AP03407001E/CPG April 2007

Você também pode gostar