To become a leader in the competitive global market, LG has been divided


into three groups, electronics and chemicals for LG, energy and
distribution for GS, Industrial electricelectronics and material for LS
based on their business specialties.
LS' main companies, such as LS cable, LS industrial systems, LS-Nikko
copper, Gaon cable, E1 and Yesco, are ranked as No.1 in their
respective industry. However, LS won't just sit back, satisfied with being
the best in Korea. We will pave the way for becoming the world's best in
industrial electricelectronics and material industry with the new CI, LS.

Your good partner LG Cable is making a


fresh start as LS Cable
LS Cable is No. 1 cable maker in Korea and its business fields are
telecommunication, electric power, components & materials and
machinery. Also, LS Cable is creating new businesses particularly in
component and materials industry. LS Cable makes its best to accomplish
the vision, 'Your No.1 Creative Partner' and be one of the world leaders
with high technology and best level of service.

Leading Solution
LG Cable, LG Industrial Systems and LG-Nikko Copper,
Gaon Cable, E1 and Yesco are starting with
a new name, Leading Solution, LS.

2.00 Manufacturing Process & VCV Line

The system adopted for insulation of the XLPE Cable is VCV and N2 gas is used for cross linking, and the line is extruded in a vertical type.
The outstanding characteristics of the XLPE Cable manufactured in application of this system are :
1. The insulation has no eccentricity.
2. The cross-linking by use of N2 gas guarantees excellent electrical characteristics of the insulation.
3. The simultaneous extrusion of the inner and outer semi-conducting layers and the insulation prevents treeing and other irregularities.
4. Uniformity of quality is maintained of all products as the manufacturing processes are controlled by computer.

Extrusion
The conductor screen, the insulation and the insulation
screen are simultaneously extruded with the
compounds supplied from the clean room.

Conductor

Drawing
Stranding
Compact
Circular

Cross-Linking and Cooling


The corss-linking takes place in curing zone of A by
circulating N2 gas and the insulation is formed into core
through precooling zone of B and cooling zone of C.

Segmental
Compact

Segment
Stranding

A
B
C

Semi Conducting Tape

Taping

Pay Off

Compound

Insulation
Degassing

Take Up

Semi Conducting Tape

Taping

The conductor wound up


around the drum is set at
pay off to run to metering
capstan.

The cable comes to be wound up again around the


drum to go into the next process.
Corrugated
Al Sheath

Wire
Shield

Lead
Sheath

Outer
Sheath

Testing

Shipping

10

Manufacturing Process & VCV Line

Manufacturing Process & VCV Line

11

3.00 Cable Construction & Continuous Current Ratings

The continuous current capacity is calculated in accordance with IEC 60287.

4.00 XLPE Insulated Cables

4.01 36/66 (72.5) kV with Aluminum Sheath


4.02 36/66 (72.5) kV with Lead Sheath

Laying Conditions
4.03 36/66 (72.5) kV with Copper Wire Shield
1) Ground Temperature : 25
2) Depth of Laying : 1.5m

4.04 64/110 (123) kV with Aluminum Sheath

3) Soil Thermal Resistivity : 1.0m/W


4) Ambient Temperature : 40

4.05 64/110 (123) kV with Lead Sheath

5) Max. Conductor Temperature : 90

4.06 64/110 (123) kV with Copper Wire Shield

6) Cable Formation : Flat (S=2D)


S : Distance between cables / D : Cable diameter
7) Frequency : 50Hz

4.07 76/132 (145) kV with Aluminum Sheath

8) Load factor : 100%

4.08 76/132 (145) kV with Lead Sheath


4.09 76/132 (145) kV with Copper Wire Shield

Maximum Permissible Conductor Temperature


Normal Operation

90

Emergency Operation

130

Short Circuit

250

4.10 87/161 (170) kV with Aluminum Sheath


4.11 87/161 (170) kV with Lead Sheath
4.12 87/161 (170) kV with Copper Wire Shield

1) Normal Operation
Normal operation is meant to be maintained through out a given period of time everyday
or continuously, without affecting the operation.

4.13 127/230 (245) kV with Aluminum Sheath

2) Emergency Load
Emergency load is meant to be maintained for a short time under the condition of
system breakdown or under the state of excessively loaded operation, without causing
a defect.

4.14 127/230 (245) kV with Lead Sheath

3) Short Circuit
Short circuit is meant to cause no defect of the cable when an irregular current, flows for
short time due to shorting or earthing.

4.16 190/345 (362) kV with Aluminum Sheath

4.15 127/230 (245) kV with Copper Wire Shield

4.17 190/345 (362) kV with Lead Sheath

4.18 220/400 (420) kV with Aluminum Sheath


4.19 220/400 (420) kV with Lead Sheath

12

Cable Construction & Continuous Current Ratings

4.01 36/66 (72.5) kV with Aluminum Sheath

4.02 36/66 (72.5) kV with Lead Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

524

592

671

762

878

965

1119

1198

1352

1468

Direct Buried

535

606

691

787

898

1008

1184

1282

1469

1626

Pipe Duct

491

556

631

714

808

928

1075

1146

1357

1475

Pipe Duct

502

567

646

733

833

958

1121

1208

1434

1585

598

682

781

894

1023

1150

1361

1460

1654

1800

Trefoil

621

710

822

951

1096

1243

1505

1648

1906

2130

Flat (S=2D)

706

810

942

1098

1274

1462

1759

1938

2282

2597

Trefoil
In Air

In Air
671

Flat (S=2D)

770

888

1025

1187

1355

1615

1745

2030

2273

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

240

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Conductor Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Insulation (mm)

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

Thickness of Insulation (mm)

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Aluminum Sheath (mm)

1.6

1.6

1.7

1.8

1.8

1.9

2.0

2.1

2.2

2.4

Thickness of Lead Sheath (mm)

2.1

2.2

2.3

2.4

2.4

2.6

2.7

2.8

3.0

3.2

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Outer Diameter of Cable (mm)

69

72

75

79

83

87

92

98

105

112

Outer Diameter of Cable (mm)

62

64

67

72

76

80

85

91

97

104

Weight of Cable (kg /m )

5.5

6.3

7.2

8.6

10.1

12.0

14.4

16.7

20.9

25.4

Weight of Cable (kg/m)

8.1

9.1

10.5

12.5

14.2

16.9

19.9

23.0

28.0

33.4

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

0.40

0.44

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

0.40

0.44

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

14

240

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

15

4.03 36/66 (72.5) kV with Copper Wire Shield

4.04 64/110 (123) kV with Aluminum Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Copper Wire Shield / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

530

599

683

780

886

997

1173

1270

1465

1627

Direct Buried

520

587

667

758

860

961

1109

1187

1338

1458

Pipe Duct

483

544

616

729

828

929

1087

1173

1375

1530

Pipe Duct

491

550

639

725

821

915

1057

1180

1332

1447

606

693

802

929

1066

1210

1473

1611

1883

2111

Trefoil

592

677

775

889

1020

1147

1346

1451

1635

1787

Flat (S=2D)

657

755

873

1006

1169

1333

1581

1717

1995

2236

Trefoil
In Air

In Air
692

Flat (S=2D)

795

925

1075

1247

1432

1728

1894

2245

2556

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

240

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Conductor Screen Approx.mm

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

Thickness of Insulation (mm)

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

Thickness of Insulation (mm)

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

Thickness of Aluminum Sheath (mm)

1.7

1.8

1.8

1.9

2.0

2.0

2.1

2.2

2.4

2.5

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Outer Diameter of Cable (mm)

58

60

63

66

71

75

80

85

91

97

Outer Diameter of Cable (mm)

76

78

81

86

90

94

99

104

111

118

Weight of Cable (kg /m )

4.4

5.1

5.9

7.2

8.6

10.4

12.7

14.7

18.7

22.7

Weight of Cable (kg/m)

6.3

7.0

8.0

9.3

11.0

12.9

15.4

17.7

22.1

26.5

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

0.40

0.44

0.17

0.18

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

Diameter & Number of Copper Wires (mm x No.)

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

16

240

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

17

4.05 64/110 (123) kV with Lead Sheath

4.06 64/110 (123) kV with Copper Wire Shield

Construction

Construction

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Copper Wire Shield / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

533

602

687

782

891

1001

1176

1269

1455

1609

Direct Buried

528

597

681

775

884

994

1169

1264

1456

1618

Pipe Duct

498

563

654

744

846

949

1108

1235

1415

1562

Pipe Duct

495

559

650

739

841

945

1106

1231

1415

1570

617

705

816

939

1083

1229

1486

1612

1870

2087

Trefoil

605

692

800

922

1065

1208

1465

1595

1860

2089

Flat (S=2D)

682

783

909

1053

1226

1406

1695

1849

2185

2487

Trefoil
In Air

In Air
692

Flat (S=2D)

794

923

1068

1243

1425

1718

1871

2206

2505

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

240

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

Thickness of Conductor Screen Approx.mm

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

Thickness of Insulation (mm)

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

Thickness of Insulation (mm)

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

14.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Lead Sheath (mm)

2.3

2.4

2.5

2.5

2.6

2.7

2.9

3.0

3.2

3.4

Diameter & Number of Copper Wires (mm x No.)

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

1.2 x 40

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

3.5

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Outer Diameter of Cable (mm)

68

71

74

78

82

86

92

97

103

110

Outer Diameter of Cable (mm)

64

66

69

73

77

81

86

91

97

103

Weight of Cable (kg /m )

9.6

10.9

12.3

13.8

16.0

18.5

21.9

24.7

30.1

35.7

Weight of Cable (kg/m)

5.0

5.7

6.6

7.9

9.4

11.2

13.6

15.6

19.6

23.7

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.17

0.18

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

0.17

0.18

0.20

0.21

0.23

0.25

0.28

0.30

0.33

0.36

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

18

240

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

19

4.07 76/132 (145) kV with Aluminum Sheath

4.08 76/132 (145) kV with Lead Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

519

585

665

755

856

956

1103

1185

1333

1452

Direct Buried

530

600

684

780

889

997

1170

1264

1449

1600

Pipe Duct

486

547

635

716

814

942

1093

1170

1324

1435

Pipe Duct

495

559

636

727

840

941

1100

1226

1404

1548

589

671

770

883

1011

1137

1333

1439

1627

1777

Trefoil

612

702

808

934

1077

1222

1469

1599

1853

2064

Flat (S=2D)

679

781

904

1050

1222

1400

1681

1842

2168

2460

Trefoil
In Air

In Air
649

Flat (S=2D)

742

858

992

1151

1313

1555

1695

1972

2211

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

240

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Insulation (mm)

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

Thickness of Insulation (mm)

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Aluminum Sheath (mm)

1.8

1.8

1.9

2.0

2.1

2.2

2.2

2.3

2.4

2.6

Thickness of Lead Sheath (mm)

2.4

2.5

2.6

2.7

2.7

2.9

3.0

3.1

3.3

3.5

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Outer Diameter of Cable (mm)

83

86

89

92

97

101

106

110

116

124

Outer Diameter of Cable (mm)

76

78

81

85

88

93

98

102

108

115

Weight of Cable (kg /m )

7.1

7.9

8.9

10.2

11.9

14.0

16.6

18.6

22.9

27.4

Weight of Cable (kg/m)

11.2

12.3

13.8

15.6

17.5

20.4

23.6

26.5

31.7

37.7

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.16

0.17

0.18

0.20

0.21

0.23

0.25

0.27

0.30

0.32

0.16

0.17

0.18

0.20

0.21

0.23

0.25

0.27

0.30

0.32

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

20

240

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

21

4.09 76/132 (145) kV with Copper Wire Shield

4.10 87/161 (170) kV with Aluminum Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Copper Wire Shield / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

240

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

525

593

675

767

872

979

1145

1233

1414

1569

Direct Buried

584

664

754

853

953

1100

1179

1331

1447

Pipe Duct

492

555

632

716

811

932

1087

1212

1388

1532

Pipe Duct

558

634

718

811

938

1087

1163

1311

1485

601

688

792

908

1045

1182

1420

1539

1784

2003

Trefoil

669

768

879

1009

1134

1328

1429

1627

1774

Flat (S=2D)

740

855

988

1146

1307

1548

1684

1967

2199

Trefoil
In Air

In Air
673

Flat (S=2D)

774

896

1033

1200

1374

1649

1801

2125

2418

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

300

Shape

400

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

300

400

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

18.1

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Insulation (mm)

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

16.0

Thickness of Insulation (mm)

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

Thickness of Aluminum Sheath (mm)

1.9

1.9

2.0

2.1

2.2

2.3

2.3

2.5

2.6

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Outer Diameter of Cable (mm)

70

72

75

80

84

88

93

96

102

110

Outer Diameter of Cable (mm)

87

91

94

98

102

108

111

119

125

Weight of Cable (kg /m )

6.5

7.1

8.1

9.5

11.0

12.9

15.3

17.1

21.2

25.8

Weight of Cable (kg/m)

8.4

9.4

10.7

12.3

14.4

17.0

19.0

23.5

28.0

0.0754

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.16

0.17

0.18

0.20

0.21

0.23

0.25

0.27

0.30

0.32

0.16

0.18

0.19

0.21

0.22

0.24

0.26

0.28

0.31

Diameter & Number of Copper Wires (mm x No.)

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

22

240

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

23

4.11 87/161 (170) kV with Lead Sheath

4.12 87/161 (170) kV with Copper Wire Shield

Construction

Construction

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Copper Wire Shield / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

300

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

300

400

500

630

800

1000

1200

1600

2000

Direct Buried

598

682

777

886

996

1168

1259

1445

1597

Direct Buried

591

673

766

871

977

1143

1232

1404

1554

Pipe Duct

557

648

736

836

939

1131

1221

1398

1541

Pipe Duct

553

629

713

829

928

1081

1208

1382

1523

698

805

928

1073

1218

1464

1589

1845

2060

Trefoil

684

789

907

1043

1181

1415

1535

1765

1973

Flat (S=2D)

765

887

1027

1193

1367

1639

1790

2100

2384

Trefoil
In Air

In Air
775

Flat (S=2D)

898

1042

1214

1391

1670

1825

2152

2445

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

400

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

300

400

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

20.4

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Insulation (mm)

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

Thickness of Insulation (mm)

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

17.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Thickness of Lead Sheath (mm)

2.5

2.6

2.7

2.8

2.9

3.0

3.2

3.4

3.6

Diameter & Number of Copper Wires (mm x No.)

1.6

1.7

1.8

1.8

1.9

2.0

2.1

2.2

2.4

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Thickness of Outer Sheath (mm)

3.5

3.5

4.0

4.0

4.0

4.0

4.5

4.5

4.5

Outer Diameter of Cable (mm)

80

83

86

90

94

100

103

110

116

Outer Diameter of Cable (mm)

72

75

79

83

87

92

98

105

112

12.5

14.0

15.7

18.0

20.5

23.8

26.7

32.2

37.9

Weight of Cable (kg/m)

6.3

7.2

8.6

10.1

12.0

14.4

16.7

20.9

25.4

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0601

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.16

0.18

0.19

0.21

0.22

0.24

0.26

0.28

0.31

0.21

0.23

0.25

0.28

0.30

0.33

0.36

0.40

0.44

Weight of Cable (kg /m )


Max. DC Conductor Resistance at 20 (/km)
Capacitance (/km)

24

300

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

25

4.13 127/230 (245) kV with Aluminum Sheath

4.14 127/230 (245) kV with Lead Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

400

500

630

800

1000

1200

1600

2000

Direct Buried

657

745

843

943

1090

1165

1316

1438

Direct Buried

676

770

876

986

1153

1243

1424

1571

Pipe Duct

641

725

822

916

1057

1131

1322

1440

Pipe Duct

638

745

847

950

1108

1194

1401

1545

757

866

989

1116

1310

1403

1596

1758

Trefoil

793

914

1054

1196

1429

1552

1797

2004

Flat (S=2D)

871

1010

1173

1343

1606

1757

2068

2342

Trefoil
In Air

In Air
Flat (S=2D)

836

962

1111

1268

1505

1631

1902

2143

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

400

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Insulation (mm)

23.0

23.0

23.0

23.0

23.0

23.0

23.0

23.0

Thickness of Insulation (mm)

23.0

23.0

23.0

23.0

23.0

23.0

23.0

23.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Aluminum Sheath (mm)

2.2

2.3

2.4

2.4

2.5

2.6

2.7

2.8

Thickness of Lead Sheath (mm)

3.2

3.3

3.4

3.5

3.6

3.9

4.1

4.2

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

5.0

5.0

5.0

5.0

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

5.0

5.0

5.0

5.0

Outer Diameter of Cable (mm)

104

108

112

116

122

126

133

139

Outer Diameter of Cable (mm)

96

100

104

108

114

118

124

130

Weight of Cable (kg /m )

11.0

12.1

14.2

15.8

19.4

21.5

26.0

30.7

Weight of Cable (kg/m)

17.9

19.7

22.1

24.8

28.8

32.3

38.2

43.8

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.14

0.15

0.17

0.18

0.20

0.21

0.23

0.24

0.14

0.15

0.17

0.18

0.20

0.21

0.23

0.24

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

26

400

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

27

4.15 127/230 (245) kV with Copper Wire Shield

4.16 190/345 (362) kV with Aluminum Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Copper Wire Shield / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

400

500

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

630

800

1000

1200

1600

2000

Direct Buried

668

759

864

970

1131

1221

1397

1543

Direct Buried

832

928

1072

1149

1299

1419

Pipe Duct

634

719

842

944

1100

1185

1354

1489

Pipe Duct

822

917

1060

1136

1325

1446

779

895

1031

1167

1390

1512

1750

1950

Trefoil

976

1095

1284

1383

1577

1726

Flat (S=2D)

1092

1239

1467

1595

1859

2089

Trefoil
In Air

In Air
863

Flat (S=2D)

998

1159

1326

1583

1733

2040

2309

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

Shape

500

630

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

Shape

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

23.2

26.3

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Insulation (mm)

23.0

23.0

23.0

23.0

23.0

23.0

23.0

23.0

Thickness of Insulation (mm)

27.0

27.0

27.0

27.0

27.0

27.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

1.5 x 80

Thickness of Aluminum Sheath (mm)

2.5

2.6

2.7

2.8

2.9

3.0

Thickness of Outer Sheath (mm)

4.5

4.5

4.5

4.5

5.0

5.0

5.0

5.0

Thickness of Outer Sheath (mm)

6.0

6.0

6.0

6.0

6.0

6.0

Outer Diameter of Cable (mm)

91

94

98

102

107

110

116

123

Outer Diameter of Cable (mm)

124

128

134

137

144

150

10.0

11.2

12.8

14.8

17.2

19.2

23.3

27.6

Weight of Cable (kg/m)

16.5

18.7

21.6

23.8

28.4

33.1

0.0470

0.0366

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.14

0.15

0.17

0.18

0.20

0.21

0.23

0.24

0.15

0.16

0.18

0.19

0.20

0.22

Diameter & Number of Copper Wires (mm x No.)

Weight of Cable (kg /m )


Max. DC Conductor Resistance at 20 (/km)
Capacitance (/km)

28

400

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

29

4.17 190/345 (362) kV with Lead Sheath

4.18 220/400 (420) kV with Aluminum Sheath

Construction

Construction

Copper Conductor / XLPE Insulation / Lead Sheath / PE (or PVC) Outer Sheath

Copper Conductor / XLPE Insulation / Aluminum Sheath / PE (or PVC) Outer Sheath

Continuous Current Ratings for Single Circuit (A)

Continuous Current Ratings for Single Circuit (A)

Cross-Sectional Area (mm2)

630

800

1000

1200

1600

2000

Cross-Sectional Area (mm2)

630

800

1000

1200

1600

2000

Direct Buried

862

970

1133

1222

1400

1541

Direct Buried

825

920

1062

1139

1292

1410

Pipe Duct

828

936

1107

1193

1364

1540

Pipe Duct

812

907

1046

1120

1304

1422

1032

1173

1399

1520

1764

1961

Trefoil

967

1090

1279

1372

1569

1711

Flat (S=2D)

1081

1231

1458

1581

1842

2067

Trefoil
In Air

In Air
Flat (S=2D)

1141

1305

1561

1706

2009

2270

Constructional Data (Nominal Values)

Constructional Data (Nominal Values)


Cross-Sectional Area (mm2)
Conductor

Shape

800

1000

Compact Round Stranded

1200

1600

Cross-Sectional Area (mm2)

2000
Conductor

Segment Stranded (Miliken)

Shape

630

800

1000

Compact Round Stranded

1200

1600

2000

Segment Stranded (Miliken)

Diameter (mm)

30.2

34.0

38.7

41.8

48.1

54.3

Diameter (mm)

30.2

34.0

38.7

41.8

48.1

54.3

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Conductor Screen Approx.mm

1.5

1.5

1.5

1.5

1.5

1.5

Thickness of Insulation (mm)

27.0

27.0

27.0

27.0

27.0

27.0

Thickness of Insulation (mm)

29.0

29.0

29.0

29.0

30.0

30.0

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Insulation Screen Approx.mm

1.3

1.3

1.3

1.3

1.3

1.3

Thickness of Lead Sheath (mm)

3.4

3.5

3.6

3.8

4.0

4.2

Thickness of Aluminum Sheath (mm)

2.6

2.7

2.8

2.8

3.0

3.1

Thickness of Outer Sheath (mm)

6.0

6.0

6.0

6.0

6.0

6.0

Thickness of Outer Sheath (mm)

6.0

6.0

6.0

6.0

6.0

6.0

Outer Diameter of Cable (mm)

113

118

123

127

133

140

Outer Diameter of Cable (mm)

128

132

138

141

150

157

Weight of Cable (kg /m )

23.5

27.3

30.7

33.8

40.3

46.7

Weight of Cable (kg/m)

17.5

19.6

22.5

24.6

29.9

34.7

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.0283

0.0221

0.0176

0.0151

0.0113

0.0090

0.15

0.16

0.18

0.19

0.20

0.22

0.14

0.15

0.17

0.18

0.19

0.20

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

30

630

XLPE Insulated Cables

Max. DC Conductor Resistance at 20 (/km)


Capacitance (/km)

XLPE Insulated Cables

31

6.00 Permissible Short Circuit Currents

The permissible short circuit current of a cable is determined by the maximum permissible
conductor temperature and by the duration of the short circuit current. At high peak
currents, the dynamic forces between the conductors must be taken into account.
The short circuit capacity of the conductor and metallic shield of a cable are related
principally to their heat capacities and are limited by the maximum temperature permitted
under short circuit XLPE power are as follow.
From the two graphs, the short circuit capacity of copper or aluminum conductors (based
on a temperature rise from 90 to 250) can be determined.
Logarithmic interpolation between the curves will give estimated values for the various
duration.
The curves may be used also to determine the amount of conducting material required to
carry a known short circuit current for a given duration.

Cu

Copper Conductor
According to IEC 60949 curves based on formula

7.00 Accessories for EHV Cable Systems

LS Cable has developed and manufactured a wide


range of terminations and joints for Extra High
Voltage(EHV) cable system since 1983.
Prefabricated terminations and tape molded joints
are installed for 154kV cable system in domestic
market. A new advanced accessories, which is
called prefabricated and premolded joints, were
developed and supplied to many countries in the
world. Cable systems from 132kV up to 400kV
has been certified through the type test by many
international independent institutes
(KEMA, CESI, KERI).
Pre-qualification tests for 345kV and 400kV cable
systems in accordance with latest IEC standard
were carried out successfully by the KEMA and
KERI.

7.01 Outdoor Terminations for 66kV ~ 230kV


7.02 Outdoor Terminations for 345kV ~ 400kV

where,
Is = Permissible Short Circuit Current (A)
= Factor to allow for heat loss into the Adjacent Components
S = Cross-Sectional Area of Conductor (mm2)
t = Duration of Short Circuit (s)

f = Final Temperature (250)

i = Initial Temperature (90)

Aluminum Conductor

7.03 SF6Gas-Immersed Terminations


7.04 Oil-Immersed Terminations

7.05 Pre-Molded Joints (PMJ)


7.06 Pre-Fabricated Joint (PJ)
7.07 Transition Joint

Al
According to IEC 60949 curves based on formula

where,
Is = Permissible Short Circuit Current (A)
= Factor to allow for heat loss into the Adjacent Components
S = Cross-Sectional Area of Conductor (mm2)
t = Duration of Short Circuit (s)

f = Final Temperature (250)

i = Initial Temperature (90)

34

Permissible Short Circuit Currents

7.08 Link Box

7.01 Outdoor Terminations for 66kV ~ 230kV

7.02 Outdoor Terminations for 345kV ~ 400kV

The outdoor terminations for 66kV~230kV are available


for both the EPR-based rubber stress relief cone with an
epoxy housing (so called pre-fabricated type) and the
silicone rubber sleeve (so called pre-molded type).

The construction of outdoor terminations for 345~400kV is


somewhat different from the lower voltage group.
Based on the EPR-based stress relief cone and the epoxy
housing, an oil-impregnated cylindrical capacitor cone is
added to secure the uniform longitudinal voltage
distribution all along the termination.

The former uses mechanical devices to maintain the


interface pressure and the latter uses elastic retention of
silicone material itself.

The main insulation components are fully examined and


tested in the factory.
The maximum allowable cable conductor size is 2500mm2.

In both cases, the main insulation components are fully


examined and tested in the factory. The maximum
allowable cable conductor size is 2500mm2.
Porcelain (Polymer)
Insulator
Porcelain (Polymer)
Insulator

Epoxy Housing

Porcelain (Polymer) Insulator


Cylindrical Capacitor Cone

Upon request of the customer, either porcelain or


composite hollow insulator can be supplied.

Epoxy Housing
Stress Relief Cone

Stress Relief
Cone

Pre-Fabricated Type

Rubber Sleeve

Pre-Molded Type

Rating & Dimension

36

Rated Voltage (kV)

400

Max. Voltage (kV)

420

BIL (kV)

1425

Nominal Creepage Distance (mm)

11500

Approx. Height (mm)

4500

Dimension of Base Plate (mm)

650

Approx. Weight (kg)

1000

Selection of Insulators with Respect to Polluted Conditions (Based on IEC60815)

Max. Voltage (kV)

72.5

123

170

245

Pollution Level

BIL (kV)

325

550

750

1050

Min. Nominal Specific Creepage Distance

Nominal Creepage Distance (mm)

2000

3200

4500

6400

Approx. Height (mm)

1000

1500

2100

2700

Dimension of Base Plate (mm)

400

550

550

600

Approx. Weight (kg)

100

200

300

500

Accessories for EHV Cable Systems

Rating & Dimension

I (Light)

II (Medium)

III (Heavy)

IV (Very Heavy)

16 mm/kV

20 mm/kV

25 mm/kV

31 mm/kV

Accessories for EHV Cable Systems

37

7.03 SF6Gas-Immersed Terminations

7.04 Oil-Immersed Terminations

The construction of SF6 gas immersed terminations is


based on the EPR-based stress relief cone and the epoxy
housing.

The construction of oil immersed terminations is based on


the EPR-based stress relief cone and the epoxy housing.
The main insulation components are fully examined and
tested in the factory.

The main insulation components are fully examined and


tested in the factory.
Design and scope of delivery are fully complying with IEC
60859 and possibly adjusted to various needs of
customers.

Dimensions of base plate are complying with IEC 60859


and possibly adjusted to various needs of customers.
They are currently available at the voltage range up to
400kV and the maximum allowable cable conductor size
is 2500mm2.

They are currently available at the voltage range up to


400kV and the maximum allowable cable conductor size
is 2500mm2.

Epoxy Insulator

Epoxy Insulator

Stress Relief Cone

Stress Relief Cone

Casing

Casing

Water-Proof Layer

Water-Proof Layer

Rating & Dimension

38

Rating & Dimension

Max. Voltage (kV)

72.5

123

145

170

245

420

Max. Voltage (kV)

72.5

123

145

170

245

420

BIL (kV)

325

550

650

750

1050

1425

BIL (kV)

325

550

650

750

1050

1425

Approx. Height (mm)

583

757

757

757

960

1400

Approx. Height (mm)

655

835

835

835

1035

1475

Dimension of Base Plate (mm)

270

320

320

320

582

640

Dimension of Base Plate (mm)

270

320

320

320

582

640

Approx. Weight (kg)

70

90

90

90

170

300

Approx. Weight (kg)

90

110

110

110

220

350

Accessories for EHV Cable Systems

Accessories for EHV Cable Systems

39

7.05 Pre-Molded Joint (PMJ)

7.06 Pre-Fabricated Joint (PJ)

The single piece pre-molded type rubber joint is based on


silicone insulation embedded with two semi-conductive stress
relief cones and one high voltage electrode. Without any
mechanical devices, the interface pressure is safely
maintained with elastic retention of material itself. The main
insulation components are factory-made and fully tested before
delivering to the site.

The pre-fabricated type joint, so called PJ, is based on the


epoxy insulating unit and the EPR-based rubber stress relief
cones. Using mechanical devices, the interface pressure is
safely maintained all through the operation period.
The main insulation components are factory-made and fully
tested before delivering to the site. They are currently
available at the voltage range up to 400kV. The maximum
allowable cable conductor size is 2500mm2.

The cost-efficient and simplified design along with easy and


fast installation meets the various needs of customers.
Installation tools can be provided if requested by customers.
The maximum allowable cable conductor size is 2500mm2.

Water-Proof Layer

Water-Proof Layer

Joint Sleeve

Sheath Sectionalized Unit

Ferrule

Sheath Sectionalized Unit

Metal Casing

Rating & Dimension

40

Ferrule

Stress Relief Cone

Metal Casing

Rating & Dimension

Max. Voltage (kV)

72.5

123

145 ~ 170

245 ~ 300

362 ~ 420

Approx. Length (mm)

1000

1400

1500

1700

Approx. Max. Outer Dia. (mm)

200

230

250

Approx. Weight (kg)

90

120

150

Accessories for EHV Cable Systems

Epoxy Insulating Unit

Max. Voltage (kV)

145

170

245

420

1800

Approx. Length (mm)

1800

1800

2000

2200

270

310

Approx. Max. Outer Dia. (mm)

290

320

360

400

200

250

Approx. Weight (kg)

220

250

300

350

Accessories for EHV Cable Systems

41

Global Network

LSIC (Beijing Office) : LS International


[Shanghai] Ltd.

LSCT : LS Cable [Tianjin] Ltd.


East of Jing-Jin, Express Yixingbu Toll Gate Beichen, Tianjin, China
Tel. +86-22-2699-7618 Fax. +86-22-2699-7617

#05 B-17th Fl. Global Trade Center, 36 Beisanhuan-Dong Rd


Dongcheng Dt. Beijing, China
Tel. +86-10-5825-6011
Fax. +86-10-5825-6015

LSAS : LS Air-Conditioning [Shandong] Ltd.

Russia Office

Yu-Huangling Industrial Area, Xiazhuang, Chengyang District, Qingdao, China.


Tel. +86-532-8096-8888
Fax. +86-532-8096-5688

Park Place Moscow 113/1 Leninsky Prospect E-711, Moscow 117198 Russia
Tel. +7-495-956-5814
Fax. +7-495-956-5811

Jordan Office
#307 4th Fl. Mid Town Plaza, Sweifieh-Subhi Al-Omari St.
P.O. Box 851885 Amman 11185 Jordan
Tel. +962-6-583-3357 Fax. +962- 6-583-3359

India Office

Japan Office

C-1, 3rd Fl. Community Centre (Opp. I.I.T Gate)


Safdarjung Development Area, New Delhi 110016 India
Tel. +91-11-4602-1657,1658
Fax. +91-11-4602-1659

E 16th Fl. Akasaka Twin Tower 17-22, 2-Chome Akasaka, Minato-Ku, Tokyo, Japan
Tel. +81-3-3582-9129
Fax. +81-3-3582-7363

Seoul

920 Sylvan Avenue, Englewood Cliffs, NJ 07632, USA


Tel. +1-201-816-2253
Fax. +1-201-816-2984

LSCW : LS Cable [Wuxi] Ltd.


LS-VINA

LS Industrial Park, Xin Mei Rd., New Dt. Wuxi 214028, China
Tel. +86-510-8811-9000
Fax. +86-510-8534-5341

So Dau Precint, Hong Bang Dt., Hai Phong, Vietnam


Tel. +84-31-540750
Fax. +84-31-540241

LSMW : LS Machinery [Wuxi] Ltd.


LS Industrial Park, Xin Mei Rd., New Dt. Wuxi 214028, China
Tel. +86-510-8299-3888
Fax. +86-510-8299-3889

UAE Office
#502 Capricorn Tower, Sheikh Zayed Rd., Dubai, UAE, PO Box 113798
Tel. +971-4-332-9445
Fax. +971-4-332-9446

LS Cable America, Inc.

VINA-LSC
1 Nui Truc Lane, Giang Van St., Ba Dinh, Hanoi, Vietnam
Tel. +84-4-722-3838, 3535
Fax. +84-4-722-3030

LSIC : LS International [Shanghai] Ltd.


12th Fl. Huamin Empire Plaza, 726 West Yan'an Rd., Shanghai 200050 China
Tel. +86-21-5237-3399, 8997
Fax. +86-21-5237-8996

Singapore Office
300 Beach Road #25-07 The Concourse
Singapore 199555
Tel. +65-6342-9162~3 Fax. +65-6342-9164

LLSMW
Suite 7A, Menara Northam, 55 Jalan Sultan
Ahmad Shah, Penang 10050 Malaysia
Tel. +60-4-588-9609(34)
Fax. +60-4-588-9607

Branches
Subsidiaries
Head Office

Anyang Plant

Gumi Plant

Indong Plant

Jeongeup Plant

Jeonju Plant

R&D Center

21st Fl. ASEM Tower, 159


Samsung-dong, Gangnam-gu
Seoul 135-798 Korea
Tel. +82-2-2189-9114

555 Hogye-dong, Dongan-gu


Anyang, Gyeonggi-do 431-831 Korea
Tel. +82-31-428-4114

190 Gongdan-dong, Gumi


Gyeongsangbuk-do 730-708 Korea
Tel. +82-54-469-7114

643 Jinpyeong-dong, Gumi


Gyeongsangbuk-do 730-735 Korea
Tel. +82-54-469-7050

938 Jeongeup 3 Industrial Complex