Você está na página 1de 4

Contact

Export sales Phone: +49(0)2166 27 2468 Export-Sales.ND@nexans.com

NHXMH-O / -J 300/500V
Halogen Free light weight cable

Description Applications
For xed installation on ships and offshore-units in all locations below the upper metallic deck, especially in chambers for secondary circuits. A more specic design (e.g. screening) is necessary for installations in radio stations or above the upper metallic deck. The cables meet the ame test requirements for bunched cables acc. to IEC 60332-3-22 and IEEE 45-18.13 and perform to the SOLAS requirements. All cable materials are free of halogens.This design ensures that non corrosive and low toxic gases are emitted in case of re. Therefore, these cables are especially suitable for the installation on passenger ships.

Design
1. 2. 3. 4. Conductor: solid bare copper class 1 Insulation: XLPE (cross linked polyethylene) Common covering Outer sheath: cross-linked polyolen, light grey

Standards
International IEC 60228; IEC 60332-3-22; IEC 60754-1; IEC 60754-2; IEC 61034 National DIN VDE 0250 part 214

Marking
e.g.: l NEXANS l VDENHXMH 3 x 1,5 300/500 V IEC 60332-3 CAT. A

Core Identikation
According with DIN VDE 0293-308 1 core: black 2 cores: blue/brown 3 cores: brown/black/grey 4 cores: blue/brown/black/grey 5 cores: blue/brown/black/grey/black Cables with 3 cores and more also with green-yellow core (has to be stated in order

Conductor exibility Solid class 1

Halogen free IEC 60754-1

Rated Voltage Uo/U (Um) 300 / 500 V

Max.conductor temp.in service 60 C

Minimum installation temperature -10 C

Minimum operating temperature -35 C

Flame retardant IEC 60332-3 Cat. A

Smoke density IEC 61034

Version 00.01.00 Generated 10/8/13 - http://www.nexans.de

Page 1 / 4

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Export sales Phone: +49(0)2166 27 2468 Export-Sales.ND@nexans.com

NHXMH-O / -J 300/500V
Characteristics
Construction characteristics Conductor material Conductor exibility Halogen free Insulation Outer sheath Sheath colour Electrical characteristics Rated Voltage Uo/U (Um) Operating voltage Usage characteristics Max. conductor temperature in service Short-circuit max. conductor temperature Minimum installation temperature Minimum operating temperature Flame retardant Smoke density Gases corrosivity Gases toxicity Standard 60 C 160 C -10 C -35 C IEC 60332-3 Cat. A IEC 61034 IEC 60754-2 No toxicity to IEC 60754-1 DIN VDE and IEC 300 / 500 V 250 V Bare copper Solid class 1 IEC 60754-1 XLPE (chemical) Cross-linked polyolen Light grey

Product List Nexans ref. Name 61640024 61640025 61640001 61640005 61640006 61640002 61640046 61640003 61640004 61640000 61640009 61640034 NHXMH-J 10x1,5 RE NHXMH-J 12x1,5 RE NHXMH-J 1x1,5 RE NHXMH-J 1x10 RE NHXMH-J 1x16 RM NHXMH-J 1x2,5 RE NHXMH-J 1x2,5 RE NHXMH-J 1x4 RE NHXMH-J 1x6 RE NHXMH-J 3x1,5 RE NHXMH-J 3x1,5 RE NHXMH-J 3x1,5 RE

=Make to order,

=In stock

Construction type Nb. of cores Cross section (mm) Approx. weight (kg/km) 10 12 1 1 1 1 1 1 1 3 3 3 1.5 1.5 1.5 10 16 2.5 2.5 4 6 1.5 1.5 1.5 316 343 41 136 210 52 52 73 92 107 125 125 = Make to order, = In stock

Conductor exibility Solid class 1

Halogen free IEC 60754-1

Rated Voltage Uo/U (Um) 300 / 500 V

Max.conductor temp.in service 60 C

Minimum installation temperature -10 C

Minimum operating temperature -35 C

Flame retardant IEC 60332-3 Cat. A

Smoke density IEC 61034

Version 00.01.00 Generated 10/8/13 - http://www.nexans.de

Page 2 / 4

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Export sales Phone: +49(0)2166 27 2468 Export-Sales.ND@nexans.com

NHXMH-O / -J 300/500V
Nexans ref. Name 61640013 61640010 61640035 61640011 61640012 61640014 61640026 61640039 61640028 61640041 61640015 61640030 61640031 61640032 61640033 61640016 61640017 61640018 61640036 61640027 61640040 61640044 61640029 61640042 61640019 61640037 61640020 61640021 61640043 61640022 61640045 61640023 61640007 61640008 NHXMH-J 3x10 RE NHXMH-J 3x2,5 RE NHXMH-J 3x2,5 RE NHXMH-J 3x4 RE NHXMH-J 3x6 RE NHXMH-J 4x1,5 RE NHXMH-J 4x10 RE NHXMH-J 4x10 RE NHXMH-J 4x16 RM NHXMH-J 4x16 RM NHXMH-J 4x2,5 RE NHXMH-J 4x25 RM NHXMH-J 4x25 RM NHXMH-J 4x35 RM NHXMH-J 4x35 RM NHXMH-J 4x4 RE NHXMH-J 4x6 RE NHXMH-J 5x1,5 RE NHXMH-J 5x1,5 RE NHXMH-J 5x10 RE NHXMH-J 5x10 RE NHXMH-J 5x10 RE NHXMH-J 5x16 RM NHXMH-J 5x16 RM NHXMH-J 5x2,5 RE NHXMH-J 5x2,5 RE NHXMH-J 5x4 RE NHXMH-J 5x6 RE NHXMH-J 5x6 RE NHXMH-J 7x1,5 RE NHXMH-J 7x1,5 RE NHXMH-J 7x2,5 RE NHXMH-O 2x1,5 RE NHXMH-O 2x2,5 RE Construction type Nb. of cores Cross section (mm) Approx. weight (kg/km) 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 7 7 7 2 2 10 2.5 2.5 4 6 1.5 10 10 16 16 2.5 25 25 35 35 4 6 1.5 1.5 10 10 10 16 16 2.5 2.5 4 6 6 1.5 1.5 2.5 1.5 2.5 470 163 163 236 319 150 576 576 900 900 197 1413 1390 1861 1811 295 385 172 172 685 685 685 1122 1122 228 228 347 455 455 209 209 290 105 134 = Make to order, = In stock

Conductor exibility Solid class 1

Halogen free IEC 60754-1

Rated Voltage Uo/U (Um) 300 / 500 V

Max.conductor temp.in service 60 C

Minimum installation temperature -10 C

Minimum operating temperature -35 C

Flame retardant IEC 60332-3 Cat. A

Smoke density IEC 61034

Version 00.01.00 Generated 10/8/13 - http://www.nexans.de

Page 3 / 4

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Export sales Phone: +49(0)2166 27 2468 Export-Sales.ND@nexans.com

NHXMH-O / -J 300/500V
Cable Characteristics
Minimum internal bending radius Current ratings for continuous operation and further hints for cable installation are according to DIN VDE 0298-4 and DIN VDE 0250-214 4 x cable diameter

Conductor exibility Solid class 1

Halogen free IEC 60754-1

Rated Voltage Uo/U (Um) 300 / 500 V

Max.conductor temp.in service 60 C

Minimum installation temperature -10 C

Minimum operating temperature -35 C

Flame retardant IEC 60332-3 Cat. A

Smoke density IEC 61034

Version 00.01.00 Generated 10/8/13 - http://www.nexans.de

Page 4 / 4

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.