Type: ADR233B

ASHIDA Numerical Differential Protection Relay

( ADITY AV2 Series) ( AM-220-06-01-08-03-01-04) ( AM-230-06-03-08-0x-01-03) ( AM-320-06-01-08-03-01-04)

Protection Features: Transformer Differential + Over Current + Restricted Earth Fault. Can be use as Motor Differential 3 Element (3 Phase + 3Io) Over current IDMT/DMT with instant Trip. Instantaneous Over-Current Protection with adjustable Timer. Internal calculation of zero seq. EF current (3Io). Negative Sequence Over Current (46). Selection of Curve: All major IDMT curve selection. Programmable starting current and dual bias setting. Programmable 2nd HRM restrain 5% - 100% 5th Harmonics Restrain 5% - 100% Programmable Internal ICT (Interposing CT) ratio to match different transformer having different vector groups.

In-built CB Trip Circuit Supervision function during pre closing and post closing of CB. Breaker Failure Detection. Disturbance Recorder. Up to 3 sec of actual waveform of current along with logical and physical status are captured and saved in the built-in memory, with date time stamping for analyzing fault condition & fault location.

Fully communicable with IEC standard open protocol. IEC 60870-5-103 & IEC 61850. Continuously monitors the modules internal hardware and alarm is generated in case of failure of any critical components.

Relay Design Features: Large 20x4 LCD display for Parameter and setting display. On site CT Secondary selection 1A or 5A. Very low burden on CT (less than 0.5VA) Operation based on fundamental frequency value.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 1 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Latching of fault current value. 11 Digital Output contacts for local Alarm as well as Tele-signalling. 10 Optically isolated digital status input for monitoring of status and to avoid use of external relay logic

controller samples these current signals through an A/D converter. The Digital Signal performs powerful Numerical Algorithms to find out RMS of fundamental & harmonic contents of the current. All measurement is tuned to fundamental frequency i.e. 50Hz, thus relay remains stable during distorted waveform by various industrial load. All these measured values are then used for different protection function such IDMT Over Current protection, Instantaneous Restricted Transformer Over Differential Current Protection, and These Earth Fault Protection Protection.

Programmable (Non- Volatile) settings by local keys as well as remote setting by communication port.

Facility to synchronised Relay Time from SCADA Separate Communication Port for SCADA (RS485) as well as Local Testing (RS232C)

100 nos of event memory, event such as CB close, Trip, digital status change, relay pkp etc. All these events are with date and time stamped up to 1ms. 10 nos of Fault data stored with keypad interface and time stamping. Description: ADR233B is second generation Numerical Transformer Differential + Over Current Protection Relay. It consists of all the necessary protection and monitoring functions required for transformer, i.e. 1. High Speed Digital DSP Controller 2. Analog Measuring Module 3. Power supply Module 4. Digital Input output module. The High speed Digital Signal Controller continuously monitors Line Phase current, HV and LV current, REF current, along with different status input through CTs and optical isolated status connections. The high-speed micro-

measured values are also displayed on large 20 x 4 LCD display for metering purpose. The DSC also monitor different digital input through optical isolator and perform some monitoring function such as Trip circuit supervision & control potential free contact for control CB and generate ALARM and Tele-signalling. The power supply module is basically DC DC converter designed using modern PWM based Switching mode technique to convert 110Vdc station battery supply to the 12V and 24Vdc low voltage supply for relay electronics and control circuit. It also provides necessary isolation from station battery. There are two types of power supply modules available 1) having range of 77Vdc 250Vdc covering requirement of 110Vdc and 220Vdc station battery system 2) having range of 18Vdc to 250Vdc covering 24Vdc, 40Vdc, 110Vdc, 220Vdc station battery requirement.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 2 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

The relay is having total 8 nos of dual LEDs of high intensity for easy identification of type of fault for easy user interface. The following features of the Relay are fully programmable via key pad interface i.e. LEDs L2 to L8 and Relays R1 to RB are digital output (DO), S1 to SA digital input (DI) Main Functions The ADR233B Relay Protection functions. Transformer Differential Protection. 1. Dual slope percentage restraint. 2. 3. 4. 5. Second harmonic blocking for magnetizing inrush. CT and Transformer connection compensation. Fifth-harmonic over excitation Unrestrained Differential Protection. blocking for transformer

4. Breaker Failure Detection. Each of these functions is independently programmable disabled by requirement. Differential Protection (87): The ADR233B relay monitors HV and LV current of power transformer through respective CTs. and user can be enabled upon or the depending

is

having

following

The sample current values are processed by powerful DSP controller. It converts these current samples into equivalent vectors and numbers of parameter such as RMS values of IHV and ILV and phases. IHV represent HV current and ILV represent LV current. Normally to match HV and LV CT ratio, phase shift between two winding due to transformer vector group, ICTs (Interposing CTs) are needed. In ADR233B relay ICTs are software selectable. There are two separate ICT ratio and vector groups provided, one for HV value and another for LV value. After applying this corrective factor, relay calculates operating and restraining signal from IHx and ILx (IH1 and IL1 is HV and LV current after applying ICT correction factor. x denote phase, 1 for R, 2 for Y and 3 for B). Based on these settings the relay decides to operate or restrain. Operating Current Iox = IHx ILx Restraining Current Ibx = (|IHx| +| ILx| ) / 2 Relay operate when Io is greater than pick-up current setting and Iox > = S Ibx Where S = set bias. (Slope 1)

Over Current + REF protection. 1. 3 Stages of Phase Over Current element. (Ip>, Ip>> and Ip>>>) for both HV & LV side independently. 2. 3 stages of 3Io (Internally derived EF) (3Io>, 3Io>> and 3Io>>>) for both HV & LV side independently. 3. Negative Phase Sequence for both HV & LV side independently. 4. One Restricted Earth Fault. Others 1. Monitoring Functions. 2. Relay / Led configuration. 3. Trip Circuit Supervision.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 3 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

The relay support dual bias characteristic. The bias (slop 1) is settable from 10% to 50% this is a normal bias characteristic. The relay follows this characteristic up to Ibx become equal to 2nd Bias I setting. During heavy through fault due to CT saturation large difference current might generate, which leads to mal operation of relay. To prevent mal operation during such heavy through fault the relay is provided with dual bias characteristic. In which after 2nd Bias I setting the relay changes it bias setting from set Bias slope I value to set Bias slope 2 automatically.
SLOP 1 SLOP 2

set value then restrain its operation. Most of the relays are multifunction and having large numbers of setting. The ADR series relay is having big 4 line 20 character back lit LCD display and very strong user interface, this make very easy to manage the relay setting. All setting are arranged in menus for easy understanding of parameter

Maximum settings in one display

The relay shows all the parameters such current before ICT current after ICT, Primary current, Bias and difference current.

The relay is provided with differential highest protection where |IHx-ILx| is greater than a preset value relay will provided high-set protection. High-set setting can be bypassed when it is not required. The relay detect transformer charging condition from 2nd harmonics contents. The 2nd harmonics limits settable in between 5% to 100%. Similarly relay detects over excitation condition from 5th harmonics and if it more than

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 4 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Restricted Earth Fault: The relay is equipped special REF protection section for transformer winding. The setting for REF protection is 5% to 100% of rated. The relay gives instant Trip command as soon as it detects EF in restricted zone. Over Current / Earth Fault Element: Apart from Differential protection transformer required Over current / Earth fault protection for HV and LV winding to protect transformer from outside faults. The ADR233B relay is having 3 stages OC/EF protection for HV and LV. For HV phase IHP>, IHP>>, & IHP>>> for LV phase ILP>, ILP>>, & ILP>>> for HV; 3IoH>, 3IoH>>, & 3IoH>>> and for 3Io LV 3IoL>, 3IoL>>, &

3IoL>>>.

Stage 1 (>) stage 2 (>>) can be

programmed as IDMT or Definite Time. It has C1 to C5 selectable IDMT curves as per IEC standard, C7- C13 as per IEEE/ANSI. The C6 is definite time. t = T*{[K/ ((I/Is) -1)] + L} where t = operation time K = constant I = Measured current Is = Current threshold setting = Constant L = ANSI/IEEE constant (zero for IEC curve) T = Time multiplier setting or Time dial Setting

Curve Type C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13

Description Standard Inverse_1 Standard Inverse_2 Very Inverse Extremely inverse Long Time Inverse Define Time Moderate Inverse Very Inverse Extremely Inverse Inverse Short Time Inverse RI RXIDG

Standard IEC IEC IEC IEC IEC IEEE IEEE IEEE IEEE IEEE -

K 0.14 0.06 13.5 80 120 0.0515 19.61 28.2 5.95 0.0239 -

0.02 0.02 1 2 1 0.02 2 2 2 0.02 -

L 0 0 0 0 0 0 0.114 0.491 0.1217 0.18 0.0169 -

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 5 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 6 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 7 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Overexciting/Over fluxing Protection.(V/f 24): Transformer over fluxing can be a result of Overvoltage Low system frequency A transformer is designed to operate at or below a maximum magnetic flux density in the transformer core. Above this design limit the eddy currents in the core and nearby conductive components cause overheating which within a very short time may cause severe damage. The magnetic flux in the core is proportional to the voltage applied to the winding divided by the frequency of the winding. The flux in the core increases with either increasing voltage or decreasing frequency. During startup or shutdown of generator-connected transformers, or following a load rejection, the transformer may experience an excessive ratio of volts to hertz, that is, become overexcited. When a transformer core is overexcited, the core is operating in a nonlinear magnetic region, and creates harmonic components in the exciting current. A significant amount of current at the 5th harmonic is characteristic of over excitation Over excitation results from excessive applied voltage, possibly in combination with below-

normal frequency. Such condition may occur when a unit is on load, but are more likely to arise when it is on open circuit, or at a loss of load occurrence. Over excitation will result in: overheating of the non-laminated metal parts, a large increase in magnetizing currents, an increase in core and winding temperature, an increase in transformer vibration and noise. Over excitation protection detects impermissible high magnetic flux densitiy in the iron core of power transformers which can occur in case of increase in voltage and/or decrease in frequency. Flux density above the rated value saturates the iron core which may result in power transformer overheating due to large iron losses. Overexcitation protection processes the voltage to frequency ratio (V/f) in relation to their nominal values. In addition a definite-time alarm stage and IEEE time delay is available. The IEEE time delay is calculated as:

IEEE : t = (0.18*K)/(M - 1)2 M = (V/f measure)/(V/f Setting)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 8 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

Breaker Failure Detection : Normally after tripping the current should become Zero within 100 200ms time depending upon type of fault and breaker mechanism. After Fault ADR233B relay triggers internal timer (settable from 0.1s to 1.0s) if fault is not cleared during this time then relay declare as Breaker fail (LBB function) and change another contacts. This contact is marked as Breaker Fail can be used to TRIP back up breaker or can be used to generate ALARM signal. Programmable DI/DO and LED : The ADR233B has 11 digital outputs, 10 optoisolated input and 7 general purpose Dual LEDs. These can be programmed by local key board. Any logical of physical status can be assigned to any relay contact The logic of digital status input as well as logical status can be formed and assigned to any of the relay output. The

disturbance record can be trigger from external logical input.

Monitoring Functions (Event, Disturbance Record) : Apart from basic protection functions. Relay continuously monitors all substation operations through status, it internal functions, internal hardware etc. if any changed is observed it is marked as event. Such type of events are stored in internal non-volatile memory along with time stamped. Following are some of the events. Relay PKP, Relay Reset, CB Trip, CB close, changed of any digital status input, Relay setting changed etc. Up to 100 such event can be stored and can be download for detailed analysis. Apart from Event record Relay also record actual waveform of current along with all digital and logical status during fault condition. Up to 10 such waveforms can be recorded; the duration of disturbance record is 3 sec. The disturbance record can

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 9 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series)

be trigger from physical status input as well as from pick, trip operation of relay. This waveform can be downloaded through communication port for further analysis. Relay Talk Software : The general communication software is provided to communicate with relay, known as Relay

Talk. By using this software data such as event log, disturbance records etc can be down loaded and can be further analysis. The disturbance record data can be saved in standard COMTRADE Format which is understandable by numbers of relay testing units for play back.

Following as some of software clips All The data can view at time

Event list with real time

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 10 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

The waveform and logical and physical status latched by relay can be view and analysed Data can be viewed as raw sine wave

or RMS value

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 11 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

Harmonics Analysis of fault

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 12 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

W h i le Or der in g S pec i fy t h e fo ll ow ing I n for m a t ion f or ADR233B Relay

Definition of Model No of Aditya Series of Relays AM XXXXX XX XX XX XXXX


Communication protocol 03 = IEC 60870-5-103 04 = IEC 61850 PT Secondary 1 = 63.5 VAC 2 = 110 VAC

Sub Type 220 = 3 PHASE Transformer Differential Relay With DDPT Connector. 230 = 3 PHASE Transformer Differential Relay, With Fix CT. 320 = Numerical Differential Relay With DDPT Connector, CT Selectable

CT Secondary 01 = 1Amp Fix 02 = 5Amp Fix 03 = 1 Amp. / 5 Amp. Selectable Auxiliary Supply 08 = 18 250 V dc

C a b in et Size 06=CSE (240 X 120MM)


C a b i n e t Type 01 = Non-drawout 02 = Plug In

O rd er ing in fo rmat ion : A D R 2 3 3 B A M 2 2 0 0 6 0 1 0 8 0 3 0 1 0 4

For Numerical Differential


ADR2 33B A M2 20 06 01 08 03 01 04 T ype Ca bine t Size Ca bine t T yp e CT s ec PT sec : ADR233B w i th IEC 61850 C om mun ica t io n Pro t oco l : C S E ( 2 40 x 1 20 M M) : N on-d rawo u t : 1 Amp. / 5 Amp selectable : 63.5 VAC

Auxiliar y Su pply : 1 8- 2 50 Vdc

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 13 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

ADR2 33B A M2 30 06 03 08 01 01 03 Type Ca bine t Size Ca bine t T yp e CT s ec PT sec : ADR233B with IEC 60870-5-103 Communication Protocol : C S E ( 2 40 x 1 20 M M) : Plug in : 1 Amp. Fix : 63.5 VAC

Auxiliar y Su pply : 1 8- 2 50 Vdc

ADR2 33B A M2 30 06 03 08 02 01 03 Type Ca bine t Size Ca bine t T yp e CT Sec PT Sec : ADR233B with IEC 60870-5-103 Communication Protocol : C S E ( 2 40 x 1 20 M M) : Plug in : 5 Amp. Fix : 63.5 VAC

Auxiliar y Su pply : 1 8- 2 50 Vdc

ADR2 33B A M3 20 06 01 08 03 01 04 T ype Ca bine t Size Ca bine t T yp e CT Sec PT Sec : ADR233B with IEC 61850 Co mmun ica tio n Pro toco l : C SE (2 40 x 120 MM) : N on- draw o u t : 1 Amp. / 5 Amp selectable : 63.5 VAC

Auxiliar y Su pply : 1 8- 2 50 Vdc

Technical Specifications: General specifications Sr. No. I. Specification Current Input Particulars : Suitable for CT secondary 5 Amp. or 1 Amp site selectable Model No. AM220 06 01 08 03 01 04 & AM320 06 01 08 03 01 04 : F i x C T Seco nda r y as p er re qu ire me n t Mo de l No. AM230 06 03 08 02 01 03 & AM230 06 03 08 01 01 03

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 14 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

II. III. IV. V. VI. VII. VIII. IX. X.

Aux. Supply VA burden on CT VA burden on Aux. Operating Temp. range Continuous Current carrying capacity Pick up Reset Value Output Contact Contact Rating

: 18V 250VDC : Less than 0.2VA : Less than 10 Watts : -10 deg. To + 65 deg. : 2 x of rated : Within 1.1 times of set : 95% to 90% of pick up. : 11 for General Programmable : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make & carry for 3 sec : 15A : 2 + common Input : 8 -ve common : Diff < 40ms at 2 times : REF < 25ms at 5 times : 20 x of rated for 3.0 sec.

XI. XII. XIII.

Opto Isolated input general programmable Operating Time Thermal Withstand for CT

General Settings XIV. Communication Unit ID Baud Rate Com Port Set Parity Rated frequency Setting Group setting Breaker Fail Function Freq Select Grp Select BF Enable BF Int / Ext I_BF BF Delay Local Tripping Blocking Trip Circuit Supervision Reset Delay Protection & Metering Local Control Trip Circuit Test Reset Time delay CT Primary HV CT Primary LV

For TX diff : 001 250 in steps of 1 : Range 1200 57600 : RS232 / RS485 : None / Even / Odd : 50Hz 60Hz : Range G1 G2 : YES/NO : Int / Ext : 100 1000mSec in steps of 50 : Yes / No : Yes / No : (50-500) msec in steps of 50ms. : 5 2000 in steps 1 : 5 2000 in steps 1

For Motor Diff : 001 250 in steps of 1 : Range 1200 57600 : RS232 / RS485 : None / Even / Odd : 50Hz 60Hz : Range G1 G2 : YES/NO : Int / Ext : 100 1000mSec in steps of 50 : Yes / No : Yes / No : (50-500) msec in steps of 50ms. : 5 2000 in steps 1 : 5 2000 in steps 1

: 10 100% in steps of 1% : 10 100% in steps of 1%

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 15 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

CT Secondary HV CT Secondary LV Vector Compensation H.V. Vector Compensation L.V. Amp 1 Comp HV (ICT Amplitude Correction for HV) Amp 1 Comp LV (ICT Amplitude Correction for LV) CT Pri. REF CT Sec. REF PT Primary PT Secondary PT Connection CBSWI1 Cont

: 1Amp / 5Amp : 1Amp / 5Amp : Yy0, Yd1, Yy2, Yd3, Yy4, Yd5, Yy6, Yd7, Yy8, Yd9, Yy10, Yd11, Ydy0 &Ydy6 : Yy0, Yd1, Yy2, Yd3, Yy4, Yd5, Yy6, Yd7, Yy8, Yd9, Yy10, Yd11, Ydy0 &Ydy6 : 0.50 2.50 in steps of 0.01 : 0.5 2.5 in steps of 0.01

: 1Amp / 5Amp : 1Amp / 5Amp : Yy0 Fix

: Yy0 Fix

: 1.0 Fix

: 1.0 Fix

: 5 2000 in steps of 1 : 1Amp / 5Amp : 0.1 2000 in steps of 0.1 : 63.5 / 110VAC : PN, PP : None/ RL1 RL11

: 5 2000 in steps of 1 : 1Amp / 5Amp : 0.1 2000 in steps of 0.1 : 63.5 / 110VAC : PN, PP : None/ RL1 RL11

Winding Differential Protection (87) XV. Diff 87 Wdiff. Enable Io Alarm

For TX diff
: YES / NO

For Motor Diff


: YES / NO

: 10 100% in steps of 1%

: 10 100% in steps of 1% : 0.04 60 Sec in steps of 0.01S : 10 100% in steps of 1% : 10 100% in steps of 1% : 10 50% in steps of 1% : 400% Fix : 50 100% in steps of 1% : 500 2000% in steps of 10%

Alarm Delay Time : 0.04 60 Sec in steps of 0.01S Io Pickup (Ib1) Ib1 Bias Slope 1 Io pkp (Ib2) Bias Slop 2 HF (Restrain) : 10 100% in steps of 1% : 10 100% in steps of 1% : 10 50% in steps of 1% : 50 400% in steps of 1% : 50 100% in steps of 1%

: 00 2000% in steps of 10% : 00 2000% in steps of 10%

HF (Non-Restrain) : 500 2000% in steps of 10%

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 16 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

HF (Non Restrain) Delay 2 nd Harmonic 5 th Harmonic

: 0.04 1.00Sec in steps of 0.01S : 05 100% in steps of 5% : 05 100% in steps of 5%

: 0.04 1.00Sec in steps of 0.01S : NO : NO

REF Settings XVI. REF Settings REF Enable In Settings Oper Delay

For TX diff : YES / NO : 5% 100% in steps of 1% : 0.02 1.00 Sec in steps of 0.01Sec.

For Motor Diff : YES / NO : 5% 100% in steps of 1% : 0.02 1.00 Sec in steps of 0.01Sec.

HV Phase Section XVII. Phase (OC) Low set IHP> Enable IHP> Settings IHP> Time Multiplier (TMS) IHP> Curve (Operating Time) IHP> C6 Delay IHP>> Enable IHP>> Settings IHP>> Time Multiplier (TMS) IHP>> Curve

For TX diff
: YES / NO

For Motor Diff


NO

: 10% 250% in steps of 1%. : 10% 250% in steps of 1%. : 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 10% 250% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 10% 250% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
NO

IHP>> C6 Delay Phase (OC) High set IHP>>> Enable IHP>>> Settings IHP>>> Delay

: 50% 3000% in steps of 10% : 0 100.00 Sec in steps of 0.01Sec.

: 50% 3000% in steps of 10% : 0 100.00 Sec in steps of 0.01Sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 17 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

LV Phase Section XVIII. Phase (OC) Low set ILP> Enable ILP> Settings ILP> Time Multiplier (TMS) ILP> Curve (Operating Time) ILP> C6 Delay ILP>> Enable ILP>> Settings ILP>> Time Multiplier (TMS) ILP>> Curve

For TX diff
: YES / NO

For Motor Diff


: NO

: 10% 250% in steps of 1%. : 10% 250% in steps of 1%. : 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 10% 250% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 10% 250% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: NO

ILP>> C6 Delay Phase (OC) High ILP>>> Enable set ILP>>> Settings ILP>>> Delay

: 50% 3000% in steps of 10% : 0 100.00 Sec in steps of 0.01Sec.

: 50% 3000% in steps of 10% : 0 100.00 Sec in steps of 0.01Sec.

HV 3Io Section XIX. HV (3Io) Low set 3IoH> Enable 3IoH> Settings 3IoH> Time Multiplier (TMS) 3IoH> Curve (Operating Time) 3IoH> C6 Delay 3IoH>> Enable 3IoH>> Settings 3IoH>> Time Multiplier (TMS)

For TX diff
: YES / NO

For Motor Diff


: NO

: 10% 100% in steps of 1%. : 10% 100% in steps of 1%. : 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: NO

: 10% 100% in steps of 1% : 0.02 1.00 in step of 0.01

: 10% 100% in steps of 1% : 0.02 1.00 in step of 0.01

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 18 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

3IoH>> Curve

: C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: NO

3IoH>> C6 Delay HV (3Io) High set 3IoH>>> Enable 3IoH>>> Settings 3IoH>>> Delay

: 50% 1200% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

: 50% 1200% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

LV 3Io Section XX. LV (3Io) Low set 3IoL> Enable 3IoL> Settings 3IoL> Time Multiplier (TMS) 3IoL> Curve (Operating Time) 3IoL> C6 Delay 3IoL>> Enable 3IoL>> Settings 3IoL>> Time Multiplier (TMS) 3IoL>> Curve

For TX diff
: YES / NO

For Motor Diff


: NO

: 10% 100% in steps of 1%. : 10% 100% in steps of 1%. : 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 0.02 1.00 in steps of 0.01 : C1 C11 ( IDMT curve C1 C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec.
:NO

: 10% 100% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
: YES / NO

: 10% 100% in steps of 1% : 0.02 1.00 in step of 0.01 : C1 C11 (IDMT curve C1C11 for Define Time C6) : 0 99.9 Sec in steps of 0.1Sec.
:NO

3IoL>> C6 Delay LV (3Io) High set 3IoL>>> Enable 3IoL>>> Settings 3IoL>>> Delay

: 50% 1200% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

: 50% 1200% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

Over Exc Settings XXI. OverExc OEX En V/Hz> Settings

For TX diff : YES / NO : 100% 180% in steps of 0.1%

For Motor Diff : NO : 100% 180% in steps of 0.1%

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 19 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

V/Hz>> Settings v / f Char K IEEE Mult t Min t Max t Delay t Alarm

: 100% 200% in steps of 0.1% : IEEE / DT : 1 60 in steps of 1 : 0 60 sec in steps of 1 : 0 9000 sec in steps of 1 : 0.1 60.00Sec in steps of 0.1Sec. : 0.1 60.00Sec in steps of 0.1Sec.

: 100% 200% in steps of 0.1% : IEEE / DT : 1 60 in steps of 1 : 0 60 sec in steps of 1 : 0 9000 sec in steps of 1 : 0.1 60.00Sec in steps of 0.1Sec. : 0.1 60.00Sec in steps of 0.1Sec.

UV Settings XXII. UV V< Enable UV Settings UV Delay

For TX diff : YES / NO : 25% 100% in steps of 1% : 0.10 100.0 Sec in steps of 0.01Sec. For TX diff V> Enable OV Settings OV Delay : YES / NO : 100% 150% in steps of 1% : 0.10 100.00Sec in steps of 0.01Sec.

For Motor Diff : NO : 25% 100% in steps of 1% : 0.10 100.0 Sec in steps of 0.01Sec. For Motor Diff : NO : 100% 150% in steps of 1% : 0.10 100.00Sec in steps of 0.01Sec.

OV Settings XXIII. OV

HV Negative Phase sequence Element (46) Section XXIV. HV NPS


I2H>> Enable I2H>> Settings I2H>> Time Multiplier (TMS) I2H>> Curve (Operating Time) I2H>> C6 Delay I2H>>> Enable I2H>>> Settings I2H>>> Time

For TX diff
: YES / NO : 10% 150% in steps of 1% : 0.02 2.00 in step of 0.01. : C1 C11 ( IDMT curve C1C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec. : YES / NO : 50% 1500% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

For Motor Diff


: NO : 10% 150% in steps of 1% : 0.02 2.00 in step of 0.01. : C1 C11 ( IDMT curve C1C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec. : YES / NO : 50% 1500% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 20 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

`LV Negative Phase sequence Element (46) Section XXV. LV NPS I2L>> Enable I2L>> Settings

For TX diff : YES / NO : 10% 150% in steps of 1%

For Motor Diff NO : 10% 150% in steps of 1% : 0.02 2.00 in step of 0.01. : C1 C13 ( IDMT curve C1C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec. : YES / NO : 50% 1500% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

I2L>> Time Multiplier : 0.02 2.00 in step of 0.01. (TMS) I2L>> Curve (Operating Time) I2L>> C6 Delay I2L>>> Enable I2L>>> Settings I2L>>> Time : C1 C13 ( IDMT curve C1C11 for Define Time C6 ) : 0 99.9 Sec in steps of 0.1Sec. : YES / NO : 50% 1500% in steps of 10% : 0 3.00 Sec in steps of 0.01Sec.

Operational Indicators (Flags) XXVI. PROT.H /ERR : Green LED indicates Relay OK (Protection Healthy) : In case of following condition LED becomes Red 1. Problem in relay Hardware. : LEDs Programmable : For Cabinet Type : For Back Terminal Connections for Model no. A M- 22 0- 06- 01-0 8- 0 3-0 1- 0 4 & AM- 32 0-06- 01-0 8-0 3-0 1-0 4 : For Typical Electrical connection for Model no. AM-220-06-01-08-03-01-04 : For Typical Electrical connection for Model no. AM- 32 0-06- 01-0 8-0 3-0 1-0 4 : For Back Terminal Connection for Model no. A M- 23 0- 06- 03-0 8- 0 1-0 1- 0 3 & AM- 23 0-06- 03-0 8-0 2-0 1-0 3 : For Typical Electrical connection for Model no. A M- 23 0- 06- 03-0 8- 0 1-0 1- 0 3 & AM- 23 0-06- 03-0 8-0 2-0 1-0 3 - MAC01302 - ACD02204

L2 to L8 XXVII. Drawing References

- ACD02304 - ACD02305 - ACD02205

- ACD02306

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 21 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

Type Test Details : Sr. No. I. Title High Frequency test Standard no. : IEC 60255-22-1, class III : Frequency : 1MHz Damped Oscillatory : Longitudinal :5 KV (peak) : Duration: sec duration 2 sec. : Between input current Terminal : IEC 60255-22-2 Class III and IEC 61000-4-2 class III. : Contact discharge: 6Kv, : Air discharge: 8KV : Polarity: both +ve and Ve polarities. : IEC-61000-4-2, Class-III : IEC 60255-22-4 and IEC 61000-4-4, class A : 1.2KV; 5/50ns; 5KHz burst duration = 15ms. : Repetition rate 300ms; Both polarities; Ri = 50; duration 1 min. : IEC 60255-22-5 / IEC 61000-4-6 class 4 : Differential Mode = 2kV : Common Mode = 4kV : 1.2/50uS , 5 surges of each polarity : IEC-60255-22-7, Class-A : IEC-61000-4-8, Class-V : IEC- 60255-22-3 : EN-61000-4-3 : Frequency 80MHz 1GHz : IEC 60255-22-6 / IEC 61000-4-6: 1996. : Freq. 150kHz 80MHz, Amplitude 10 V, Modulation 80% AM @ 1 KHz : IEC 60255-11 : IEC- 60255-25 : IEC 60255-5. class III : At 2.5kV 50Hz between all terminal connected together and earth for 1 minutes : IEC60255-5. class III : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec.

Electromagnetic Compatibility Type Test :

II.

Electrostatic discharge Direct application

III. IV.

Indirect application Fast transient disturbance

V.

Surge immunity test Power frequency immunity test Power frequency magnetic field test Radiated electromagnetic field disturbance
Conducted Disturbance induced by Radio Frequency field

VI. VII. VIII.

IX.

X. XI. XII.

AC Ripple in DC supply Test Radiated emission High Voltage Test

Insulation tests:

XIII.

Impulse Voltage Test

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 22 / 23

ASHIDA Numerical Differential Protection Relay

Type: ADR233B
( ADITY AV2 Series) (Preliminary)

Environmental tests: XIV. XV. XVI. XVII. XVIII. XIX. XX. Cold test Storage test Dry heat test Damp heat test, steady state Damp heat test, cyclic Immunity Emissive Test Low voltage directive : IEC-60068-2-1 : IEC-60068-2-2 : IEC-60068-2-3 : IEC-60068-2-30 : IEC-60255-26 : IEC- 60255-26 : EN-50178 : IEC 60255-21-1 class 1 : Frequency Range = 10Hz 150Hz , acceleration. = 1gn (9.8 m/s2) : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis. : IEC- 60255-21-2 : IEC-60255-21-3

CE compliance

Mechanical tests XXI. XXII. XXIII. Vibration Shock and bump Seismic

Revision Note: Revision 01 02 03 04 04A 05 06 Date 27.01.2008 10.11.2009 02.02.2010 23.03.2011 01.04.2011 07.05.2012 16.06.2012 Description Original specs Additional Specification of Over Current Photograph of the Relay updated. Back Terminal revised. One REF is removed and PT is added for compatibility with future model ICT Ratio for HV and LV Added Back Terminal Arrangement Modified. Name of relay change from ASHIDA Numerical 3 Phase Tx. Differential + Over Current Protection Relay to ASHIDA Numerical Differential Protection Relay New Model no. & back terminal drawings added.

07

14.07.2012

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above. ASHIDA ELECTRONICS PVT LTD.
ASHIDA HOUSE, Plot No. A-308, Road No. 21, Wagle Industrial Estate,Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR233B_V2 Issue: 07 14.07.2012 Page 23 / 23