DCP-CZM CONVENTIONAL ZONE MODULE

SPECIFICATIONS
Supply Voltage (S-SC) Auxiliary Supply Voltage Average Current Consumption (On S-SC Line) 2-Wire Detector Loop Current Standby Detector Load From Auxiliary Supply EOL Device Max. Quantity Per Loop Alarm Threshold Level Wiring Threshold Level Open Circuit Threshold Level Max. 2-Wire Conventional Detector (Loop Resistance) Dimensions Operating Temperature Mounting Relative Humidity 25.3 ~ 39 VDC 18.8 ~ 27.2 VDC 670A 1mA Max. 60mA Max. 4.7K ohms Resistor 127 <1.5K ohms >2.5K ohms & <6K ohms >10K ohms 50 ohms (total wire length) 4.2W x 4.7H x 1.4D 32F (0C) ~ 120F (49C) 4 square electrical box 90% RH Non-Condensing

STANDARD FEATURES
Provides an address point for a zone of up to 25 conventional smoke detectors Blinks green when polled. Latched on red (controlled by panel) when activated Device address can be programmed with a handheld programmer. Device address- ranges from 1 to 127 Compatible with Class B and Class A wiring Auxiliary power source provides power for the zone of detectors Compatible with conventional detectors, SLR, SIJ, SLK, SLV, DCD, DFE and SIH series

DESCRIPTION
The Hochiki Conventional Zone Module (DCP-CZM) is designed for use on an analog addressable Fire Alarm system. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module allows the panel to interface and monitor two-wire conventional detectors or pull stations. Each DCP-CZM transmits the status on one zone of devices (25 maximum per zone) back to the panel. It supervises the power supply as well as the entire zone of devices. Status conditions are reported as normal, open or alarm. All 2-wire smoke detectors must be UL listed as compatible to be interfaced with the DCP-CZM. The interrupt driven Digital Communication Protocol (DCP) combines maximum communication reliability and fast response to emergency conditions. The module has a single bicolored LED to indicate device status. It fits into a standard 4" square or double gang electrical back box.
Continued on back. Find latest revision at www.hochiki.com

PRODUCT LISTINGS
California State Fire Marshal 3033215 7300-0410:150

S5694

Specifications subject to change without notice.

Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 Phone: 714/522-2246 Fax: 714/522-2268 Technical Support: 800/845-6692 or technicalsupport@hochiki.com

F0004

05/2010

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Conventional Zone Module (DCP-CZM). The modules shall be UL listed and compatible with the Hochiki America Analog Control Panel Protocol. The device address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status. The DCP-CZM shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang electrical back box. The DCP-CZM shall provide a monitor LED that is visible from outside the cover plate. LIST OF COMPATIBLE DEVICES
Detector Model SLK-24F SIH-24F SLR-24H SLR-24V SLR-835/-835W SLR-835H/-835HW SLR-835B-2/-2W SLR-835BH-2/-2W SIJ-24 DCD-135/-190 DFE-135/-190 SLV-24/-24N/-24V Detector Identifier HD-3 HD-3 HD-3 HD-3 HD-3 HD-5 HD-6 HD-6 HD-3 HD-3 N/A HD-3 Detector Type Photoelectric Ionization Photoelectric w/heat Photoelectric Photoelectric (8-35V) Photoelectric (8-35V) w/thermal Photoelectric (8-35V) (baseless) Photoelectric (8-35V) w/thermal (baseless) Ionization Heat Fixed Temp/Rate of Rise Heat Fixed Temp Photoelectric Base Model HSB-224 HSB-224 NS4-224, NS6-224 NS4-224, NS6-224 NS4-224, NS6-224 NS4-224W, NS6-224W NS4-224, NS6-224 NS4-224W, NS6-224W N/A N/A NS4-224, NS6-224 NS4-224, NS6-224 HSC-224L NS4-224, NS6-224 NS4-224W, NS6-224W Max Base Indetifier Detectors HB-53 HB-53 HB-5 HB-5 HB-5 HB-5 N/A N/A HB-5 HB-5 HB-62 HB-5 25 25 25 25 18 18 18 18 25 25 25 25

Back side of a CZM


NFPA CLASS A WIRING DIAGRAM
EXPLODED VIEW

3-4: CLASS A
OPTIONAL BRANCH CIRCUIT TO NEXT INTERFACE MODULE. MODULE SUPERVISES SUPPLY VOLTAGE AND DETECTOR LOOP.
S SC

Hochiki America Corporation


TB1

JP2
CLASS A

Conventional Zone Module


SER. NO. XXXXXXXXX
INOUT+ OUTSC S 24V24V+ IN+

DCP-CZM

U.L. LISTED COMPATIBLE SC FIRE CONTROL S PANEL UL LISTED + 1481 24VDC REGULATED POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
-

TB2

NOTE: ENSURE JUMPER IS IN CORRECT POSITION FOR WIRING CONFIGURATION. (POSITION 3-4)

For Dry Indoor Use Only For Proper Installation, see HA-06-101 Rev 03/10

MAX. 25 CONVENTIONAL DETECTORS

24-

24V+

NEXT DEVICE

CONVENTIONAL ZONE MODULE


EB

ALL WIRING IS SUPERVISED AND POWER LIMITED. DO NOT MIX FIRE ALARM INITIATING AND SUPERVISORY INITIATING DEVICES ON THE SAME MODULE.

Note: SLC circuit is in reference to S, and SC

NFPA CLASS B WIRING DIAGRAM

EXPLODED VIEW

1-2: CLASS B

OPTIONAL BRANCH CIRCUIT TO NEXT INTERFACE MODULE. MODULE SUPERVISES SUPPLY VOLTAGE AND DETECTOR LOOP.
S SC

Hochiki America Corporation


TB1

JP2 TB2

Conventional Zone Module


SER. NO. XXXXXXXXX
INOUT+ OUTSC S 24V24V+ IN+

DCP-CZM

CLASS B

U.L. LISTED COMPATIBLE SC FIRE CONTROL S PANEL


UL LISTED + 1481 24VDC REGULATED POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
-

NOTE: ENSURE JUMPER IS IN CORRECT POSITION FOR WIRING CONFIGURATION. (POSITION 1-2)

E.O.L. DEVICE 4.7K PART NUMBER 0400-01820

For Dry Indoor Use Only For Proper Installation, see HA-06-101 Rev 03/10

MAX. 25 CONVENTIONAL DETECTORS

HOCHIKI AMERICA CORP. E.O.L. DEVICE 4.7K PART NUMBER 0400-01820

24-

24V+

NEXT DEVICE

CONVENTIONAL ZONE MODULE


EB

ALL WIRING IS SUPERVISED AND POWER LIMITED. DO NOT MIX FIRE ALARM INITIATING AND SUPERVISORY INITIATING DEVICES ON THE SAME MODULE.

Hochiki America Corporation CZM

Specifications subject to change without notice.