GENERATOR CONSTRUCTION DETAILS (210 MW)

1. Introduction : An electrical generator is a machine, which converts mechanical energy (or power) into electrical energy (or power). Energy conversion is based on the principal of the production of dynamically (or motionally) induced emf. Whenever conductor cuts magnetic flux, dynamically induced emf is produced in it according to Faradays Laws of electromagnetic induction. This emf causes a current to flow if the conductor circuit is closed. Hence two basic essential parts of an electrical generator are 1) A Magnetic field & 2) A Conductor or Conductors (armature) which can so move as to cut the flux. Generators are A.C. or D.C. the device in which electricity is generated by keeping the magnetic field stationary and armature rotating is called D.C. generator and the device in which electricity is generated by keeping the armature (conductor) stationary and magnetic field rotating is called A.C. generator. In the case of A.C. generators standard construction consists of armature winding mounted on stationary element called stator and field windings on a rotating element called rotor. The details of construction are as elaborated ahead. 1) Stator : consists of Body/Frame, Core, Winding, Distillate Header, Terminal Bushing, End shield, gas coolers etc. 2) Rotor : consists of shaft, winding, wedges, retaining ring, fans, field leads, slip ring & bush gear. 2. STATOR 2.1 STATOR BODY : The stator body with core and stator winding form the heaviest component of the entire Turbogenerator. The active parts to be accommodated and the forces and torque arising during operation call for a rigid and strong stator shell. Moreover, it is designed to withstand high internal pressure, which may arise due to unlikely event of explosion of hydrogen air mixture without any residual deformations. Stator body is a totally enclosed gas tight fabricated structure made up of high quality mild steel and austenitic steel. It is suitably ribbed with annular rings called inner walls to ensure high rigidity and strength. The arrangement, location and shape of inner walls is determined by the cooling circuit for the flow of gas and the required mechanical strength and stiffness and side walls are suitably blanked to house four longitudinal hydrogen gas coolers inside the stator body. PIPE CONNECTIONS : The water connection to gas coolers is done by routing stainless steel pipes inside the stator body which emanate from bottom and emerge out at side walls. These stainless steel pipes serve as inlet and outlet for gas coolers. From side wall these are connected to gas coolers by means of eight U-Tubes outside the stator body. For filling the generator with H2, a perforated manifold is provided at the top inside the stator body. The feed and vent terminating flanges for Hydrogen, carbon dioxide and air are provided at the bottom of stator body. Manhole is provided at the bottom to inspect inside of the generator if required.
279

TERMINAL BOX : The beginnings and ends of three phases of stator winding are brought out to the slip ring end of the stator body and brought out through 9 terminal bushings in the terminal box. The terminal box is a welded construction of (non-magnetic) austenitic steel plates. The material eliminates stray losses due to eddy currents. Which may result in excessive heating. The terminal box is a welded construction of (non-magnetic) austenitic steel plates. This material eliminates stray losses due to eddy currents, which may result in excessive heating. JACKING & DRAGGING PROVISION : Suitable jacking points are provided on stator body. Provision is also made for dragging the completely wound stator. The dragging provision is optional and achieved by welding a cradle plate on the sole of stator body. TESTING OF STATOR BODY : On completion of manufacture of stator body, it is subjected to a hydraulic pressure of 8 kg/cm2 for 30 minutes for ensuring its withstanding capability to all explosion pressure that might arise on account of hydrogen air mixture explosion. Complete stator body is then subjected to gas tightness test by filling in compressed air. 2.2 STATOR CORE : A rotating magnetic flux threads with the core. In order to minimize the magnetizing and eddy current losses in the active portion of the stator, the entire core is built up of thin laminations. Each lamination layer is made up of a number of individual segments. The segments are stamped out from sheets of cold rolled high quality silicon steel. Before insulating with varnish each segment is carefully deburred. The core is stacked with lamination segments in individual layers. The segments are assembled in an interleaved manner from layer to layer so that a monolithic core of high mechanical strength and uniform permeability to magnetic flux is obtained. The stampings are held in position by twenty core bars having dovetail section. Insulating paper pressboards are also put between the layer of stampings to provide additional insulation and to localize short circuit that may occur due to failure of varnish insulation of sheet stamping. To ensure tight monolithic core the stampings are hydraulically compressed during the stacking procedure at different stages when a certain heights of stack are reached forming different pockets. Between two packets one layer of ventilation segments is provided. The steel spacers are spot welded on stamping. These spacers form ventilating ducts from where the cold hydrogen from gas coolers enters the core radially inwards there-by taking away the heat. The pressed core is held in pressed condition by means of two massive nonmagnetic steel castings of press ring. The pressure of press ring is transmitted to stator core stampings through press fingers of non-magnetic steel and duralumin placed adjacent to press rings. The non magnetic steel press fingers extend up to the tip of stamping teeth so as to ensure the firm compression of the teeth part of the core portion too. The stepped arrangement of the stampings towards the bore at the two ends provides an efficient support of tooth Portion and contributes to a reduction of eddy current losses and local heating in this range in addition to the provision of more area of cross section for gas flow. To avoid heating of press
280

rings due to end leakage flux two rings made of copper sheet are used as flux shield. To monitor the formation of hot spots, resistance temperature detectors are placed along the bottom of slots. CORE SUSPENSION : The revolving magnetic field exerts pull on core, resulting in a revolving and nearly elliptical deformation of the core, which sets up a stator vibration at twice the system frequency known as double frequency vibrations. Generator core, is spring mounted in the stator frame to dampen the transmission of double frequency vibrations to the foundation. The elastic suspension of core consists of, longitudinal bar type springs called core bars. Twenty core bars are welded to inner walls of stator body with the help of brackets. These core bars provide radial and tangential isolation from magnetic vibrations of stator core. These are made up of spring steel having a rectangular cross section and dove tail cut at top. Similar type of dovetail is also stamped on to stampings and fit into that of core bar dovetail, thus offering a hold point for stampings. Core bars have longitudinal slits that act as inertial slots and help in damping the vibrations. Apart from this uniform distribution of forces is also achieved by putting a spring steel tape all around the core bars. 2.3 STATOR WINDING : GENERAL : The stator has a three phase, double layer, short pitched and bar type of windings having two parallel paths. Each slot accommodates two bars. The slot lower bars and the slot upper bars are displaced from each other by one winding pitch and connected at their ends so as to form coil groups. CONDUCTOR CONSTRUCTION : Each bar consist of solid as well as hollow conductors with cooling water passing through the latter. An alternate arrangement of hollow and solid conductors ensures an optimum solution for increasing current and to reduce losses. The conductors of small rectangular cross section are provided with glass lapped strand insulation. These are arranged side by side in two layers. The individual layers are insulated from each other by a separator in the straight slot portion the strands are transposed by 3600 to reduce the eddy losses. The transposition provides for a mutual neutralization of voltages induced in the individual strands due to the slot cross field and end winding field and ensures that no circulating currents will arise. To ensure that strands are firmly bonded together and to give dimensional stability in slot portion, a layer of glass tape is wrapped over the complete stack. After that the stack is pressed and cured in steam heated hydraulic press. Prior to applying the bar insulation, overhang on both ends of bar is formed as an involute in hydraulic press. Coil lugs for electrical and water connections are brazed at both ends. Bar insulation is done with epoxy mica thermosetting insulation. This insulation is void free and possesses better mechanical properties. The bar insulation is cured in a electrically heated press and thus epoxy resin fill all
281

voids and eliminate air inclusions. The insulation is highly resistant to high temperatures and temperature changes. The composition of the insulation and synthetic resin permits the machine to be operated continuously under conditions corresponding to these for insulation class B. CORONA PREVENTION : To prevent corona discharges between insulation and the wall of the slot, the insulation in slot portion is coated with semiconducting varnish. At the transition from slot to over hang winding a stress grading varnish is coated to ensure a uniform control of the electric field and to prevent the formation of creepage sparks during operation & during high voltage test. In the course of manufacture the bar is subjected to a number of tests to ensure proper quality. The various test which are performed are a) Inter turn insulation test on stack after consolidations to ensure absence of interturn short. b) Each bar is subjected to hydraulic test to ensure the strength of all joints. c) Flow test is performed on each bar to ensure that there is no reduction in cross section area of the ducts of the hollow conductor. d) Leakage test by means of air pressure is performed to ensure gas tightness of all joints. e) High voltage test to prove soundness of insulation. f) Dielectric loss factor measurement to establish void free insulation. LAYING OF STATOR WINDING : The stator winding is placed in open rectangular slots of the stator core which are uniformly distributed on the circumference. After laying top bar, slot wedges are inserted. Below slot wedges, high strength glass textolite spacers are put to have proper tightness. In between top and bottom bars, spacers are also put. These measures prevent vibrations that may be set up by the bar currents. 2.4 END WINDING : In the end winding, the bars are arranged close to each other. Lower layers of bars are braced with terelyne cord with binding ring as well as with adjacent bars. Upper layer is also braced in a similar manner. These are fixed with epoxy glass ring made in segment and flexible spacer put in between the two layers. After laying, varnish is added on terelyne cord. After that varnish is cured to have solid bracing. Bus bars are connected to bring out the three phases & six neutrals. These bus bars are connected with terminal bushings. Both are water cooled, connection is made by brazing the two lugs properly. 2.5 ELECTRICAL & WATER CONNECTION : Putting copper ferrule over the two limbs of coil lug makes electrical connection between top and bottom bar. In between, copper wedges are inserted and then soldering is done. After that joint is subjected to ultrasonic testing. Water connection on Exciter side is done by simply connecting copper tube in two lugs. On turbine side, each lug is connected through a teflon hose to inlet/outlet header. Bus bars and the terminal bushings are also provided with water connections by copper tubes.
282

2.6 DISTILLATE HEADER : Ring type water headers, made of copper are provided separately for distillate inlet and outlet in the stator on turbine side. The headers are supported on insulators and isolated from stator body. The end connection of top and bottom bar is done by putting copper ferrule over the two coil lugs and then soldered to have solid joint. Connecting a copper tube to the two opening of lugs at exciter ends does the water connection. At turbine side, each individual bar is connected with inlet/outlet headers by P.T.F.E. hoses. Fibermoulded covers filled with putty insulate the bar heads. The complete water path is subjected to rigorous hydraulic and pneumatic tests at various stages to ensure water tightness and to detect blocking of the flow paths. The vent pipe connections are provided at the top of both inlet and outlet header to expel air during filling these headers with distillate. These vent pipes can be connected to gas trap device if provided, to measure the extent of hydrogen leaking into water circuit. 2.7 TERMINAL BUSHING : Three phases and six neutral terminals are brought out from the stator frame through bushings, which are capable of withstanding high voltage, and provided with gastight joints. The bushings are bolted to the bottom plate of the terminal box, with their mounting flanges. The terminal box that is welded underneath the stator frame at exciter end is made of nonmagnetic steel to avoid admissible temperature rise. The conductor of the bushing is made of high conductivity copper tube on which silver plated terminal plates are brazed at both ends. A copper pipe is connected to circulate water for cooling. The terminal bar conductor is housed in porcelain insulator which can be mounted on the terminal box by means of ring. The bushing is connected to terminal bus bar by means of flexible copper leads for making the electrical connections conveniently. 2.8 END SHIELD : To make the stator body gas tight at the two ends, two end shields are fitted with the help of bolts. Gas tightness is achieved by putting a rubber sealing cord. The end shields are made up in two halves for convenience during erection and inspection. To avoid leakage of gas through the split surface rubber sealing is put between two halves of end shields. A chamber is provided near the internal diameter to collect oil which might enter from shaft seal. This chamber is connected to liquid leakage Detector which gives an alarm for presence of any liquid. Aluminum alloy casting of fan shield is supported on end shields to direct the gas flow from the propeller fan. Shaft seal and oil catcher are also mounted on end shields.All end shields of Turbogenerators are tested hydraulically for checking the strength of weld seams. 3. 1. 2. ROTOR : The rotor comprises of following components Rotor shaft Rotor winding
283

3. 4. 5. 6.

Rotor wedges & other locating parts for winding Retaining ring Fans Field lead connections

3.1 ROTOR SHAFT The rotor shaft is long forging measuring more than 9 meters in length and slightly more than one meter in diameter. The main constituents of the steel are chromium, molybdenum. nickel, and vanadium. The shaft and body are forged integral to each other by drop forging process. Following tests warrant adherence to the specified mechanical and magnetic properties as well as a homogeneous forging. 1) Mechanical tests 2) Chemical Analysis 3) Magnetic permeability test 4) Micro structure analysis 5) Ultrasonic Examination 6) Boroscopic Examination On 2/3 of its circumference approximately, the rotor body is provided with longitudinal slots to accommodate field windings. The slots pitch is selected in such a way that two solid poles displaced by 180 are obtained. The rotor with all its sub assemblies mounted over it is dynamically balanced to a high degree of accuracy and subjected to 20% over speeding for two minutes. 3.2 ROTOR WINDING : The field winding consists of several coils inserted into the longitudinal slots of the rotor body. The coils are wound around the poles so that one north magnetic pole and one south magnetic pole are obtained on shaft. COPPER CONDUCTOR : The conductors are made of hard drawn silver bearing copper. Apart from low electrical resistance this grade exhibits high creep resistance so that coil deformations due to thermal cycling due to start and stop operation are minimum. INSULATION : Layer of glass laminates insulates the Individual turns from each other. This laminate is built by glass prepeg strips on the turn of copper and baked under pressure and temperature to give a monolithic interturn insulation. The coils are insulated from rotor body by U- shaped glass laminate moulded slot troughs made from glass cloth impregnated with epoxy varnish. At the bottom of slot D Shaped liners are put to provide a plane seating surface for conductors and to facilitate easy flow of gas from one side to another. The overhang windings are insulated from retaining ring by two layers of retaining ring segments having L shape and made of glass cloth impregnated by epoxy resin.

284

COOLING OF WINDING The rotor winding are cooled by means of direct cooling method of gap pickup method. In this machine there are zones which result in multijet flow of hydrogen exposing large amount of rotor winding copper to the cooling medium thus creating very effective cooling and enabling a very low ratio of maximum to average copper temperature. The overhang portion of the winding is cooled by axial two-flow system and sectionalized into small parallel paths to minimize the temperature rise. Cold gas enters the overhang from under the retaining rings through special chamber in the end shields and ducts under the fan hub and gets released into the air gap at the rotor barrel ends. 3.3 ROTOR WEDGES The slot wedges are made from duralumin an alloy of copper Magnesium and Aluminum having high good electrical conductivity and high mechanical strength. The slot wedges behave as damper winding bars also under unbalanced operation of generator. The end wedges are made from an alloy of chromium and copper having high electrical conductivity. These wedges are connected with damper segments under the retaining ring for short circuiting induced shaft current. The end wedges are insulated from retaining rings by glass textolite liner. The field lead wedges are used to protect the field lead bar against centrifugal forces. Ventilation slot wedges are used to cover the ventilation canals in the rotor so that hydrogen for over hang portion flows in a closed channel. 3.4 RETAINING RING The overhang portion of field winding is held by retaining ring against centrifugal forces. They are shrink fitted to the ends of the rotor body barrel at one end, while the other side of the retaining ring does not make contact with the shaft thus ensuring an unobstructed shaft deflection at the end winding and eliminating the chances of fretling corrosion. The centering rings are shrinks fitted at the free end of the retaining ring that serves to rein-force the retaining ring, securing end winding in axial direction at the same time. A spring ring is used to prevent any relative movement between the retaining ring and centering ring. The nut for retaining ring is screwed on the retaining ring at fixed end. To reduce stray losses, the retaining rings are made of non magnetic, austenitic steel and cold worked, resulting in high mechanical strength. 3.5 FANS Two single stage axial flow propeller type fans circulate the generator cooling gas. Fitted on either sides of rotor body. Fan hubs are made of alloy steel forging with three peripheral grooves milled on it. Fan blades which are a precision casting with special alloy are machine in the tail portion so that they fit into the groove of fan hub. To check the fan blades from coming out of hub, ground tapered pins are used by reaming the two components together. Split pins are used alongwith slotted nuts to prevent the pins coming out during operation.

285

3.6 FIELD LEAD CONNECTIONS Slip Rings The slip rings consist of helically grooved alloy steel rings shrunk on the rotor body shaft and insulated from it. For convenience in assembly both the rings are mounted on a single common steel bush which has an insulating jacket pre moulded on it. The complete bush with slip rings is shrunk on the rotor shaft. The slip rings are provided with inclined holes for self-ventilation. The helical grooves cut on the outer surface of the slip rings improve brush performance. Field Lead The slip rings are connected to the field winding through semiflexible copper leads and current carrying bolts placed radially in the shaft. Leads are made up insulated by glass cloth impregnated with epoxy resin for low resistance and ease of assembly. Two semi-circular hard copper bars insulated from each other and from rotor shaft are placed in central bore of rotor joining two sets of current carrying bolts with special profiled precision conical threads. The radial holes with current carrying bolts in the rotor shaft are effectively sealed to prevent the escape of hydrogen. A field lead bar does the connection between current carrying bolt and field winding. 3.7 BEARING : The rotor shaft is supported on pedestal type of bearings which has spherical seating to allow self alignment. On the top of bearings pedestal a vent pipe emerges connecting bearing chamber to the atmosphere for venting out oil vapour or traces of Hydrogen. A current collector located just above the rotor shaft and touching it is also mounted on the bearing body to give, shaft voltage for rotor earth fault protection. To prevent the flow of shaft currents slip ring and bearing and connecting pipes are insulated from earth. For visual checking of oil flow check windows are provided in the drain oil pipe. The oil is supplied through inlet pipe and flow is adjusted by means of proper selection of diaphragm orifice. The generator bearings are provided with a hydraulic shaft lifting device to reduce bearing friction during start up and barring gear operation of the turboset. For this purpose, oil at high pressure is forced between the bearing surface and the shaft journal, lifting the rotor shaft to allow the formation of a lubricating oil film. 3.8 BRUSH GEAR The rotor winding is solidly connected to the slip rings by means of field lead bars, current carrying bolts, field lead core bar and flexible leads. The field current to the rotor winding is provided through the Brush gear. The current carrying brush gear assembly is rigidly fixed on the extended part of the bearing pedestal on the exciter side. There are two brush gear stands, each made up of two symmetrical silicon brass casting half rings. Which are bolted at the top to make one stand assembly, kept vertically. These ring stands are designed as helical from one end to the other to achieve uniform wear of slip rings as well as carbon brushes and smooth removal of carbon dusts all along the width of slip rings. Provision is made on these ring stands for connecting cables.
286

Three insulated straight pipes are rigidly placed horizontally in between the stand at three different positions to avoid any axial displacements to increase vibration rigidity of ring under normal running conditions. Brush holders are fixed on both sides of the brass rings and provides regular staggering of carbon brushes along the width of slip rings. The brushes are spring loaded to maintain required contact pressure of 0.2 kg/cm2 and the brush pressure can be adjusted individually. The design of brush gear permits replacement of the brushes during normal operating condition. This complete brush gear stand assembly is rigidly fitted in position on brush gear support, which as a whole unit is to be fixed on to the bearing pedestal. A glass textolite packing is provided in between the brush gear support and stand to insulate the latter. 3.9 BRUSHES AND BRUSH HOLDERS : Brushes have a low co-efficient of friction and are self lubricating. The brushes are provided with double flexible copper leads. Before filling the brushes are rubbed with medium or fine sand paper in the direction of rotation. This is to obtain the most favorable condition for equal current distribution. Moving the spring fulcrum either up or down on the brush holder adjusts the brush pressure. Excessive pressure tends to induce chattering or bouncing of the brushes, insufficient pressure tends to cause sparking. 3.10 SHAFT SEAL (RING TYPE) The locations where the rotor shaft passes through the stator casing, are provided with radial seal rings. The seal ring is guided in the seal body, which is bolted on to the end shield and insulated to prevent the flow of shaft currents. The seal ring is lined with babbit on the shaft journal side. The gap between the seal ring and the shaft is sealed with seal oil. The seal oil is supplied to the sealing gap from the seal body via radial holes and an annular groove in the seal ring. To ensure effective sealing, the seal oil pressure in the annular gap is maintained at a higher level than the gas pressure within the generator casing. The oil drained on the hydrogen and air sides of the seal rings is returned to the seal oil system through drains in the seal body and seal cover respectively. In the seal oil system, the oil is regenerated by a vacuum treatment and then returned to the shaft seals. On the air side, pressure oil also called ring relief oil is supplied laterally to the seal ring via an annular groove. This ensues free movement of the seal ring in radial direction. Gas coolers consist of cooling tubes made out of admiralty brass with coiled copper wire wound on them to increase the surface area of cooling. Cooling water flows through the tubes while hydrogen flowing across the cooler comes into contact with the external surface of the cooling tubes. Water chambers are bolted to the tube plates on either end through rubber gaskets. The out side flange of water chamber on slipring side is elastically fixed to the stator body with the help of moulded rubber gasket to allow free expansion of cooler where as on the Turbine side it is fixed rigidly to the stator. End covers of water chambers are removable without purging the hydrogen from the generator. This enables cleaning of the tubes of coolers while the generator is running at partial load. Four gas coolers mounted longitudinally inside the generator stator body cool hot hydrogen.
287

In order to remove air from gas coolers while filling them with water, vent pipes are provided on slip ring side. For alignment of the coolers in the stator while insertion, the bolts are provided at each end. The rollers in gas cooler facilitate easy insertion of cooler into the stator frame. 3.11 VENTILATION CIRCUIT : Two axial fans mounted on the rotor on both sides circulate the gas in two independent and symmetrical closed circuits with respect to center line of the generator. The schemes of stator core cooling divide itself into 3 paths. FLOW PATH 1 The cold gas after gas cooler enters chamber at the back of core and enters radially the ventilation ducts and flows to air gap after removing heat of the core. To remove higher losses in the end part, some of the cold gas is diverted towards press ring and press fingers. FLOW PATH 2 The direct cooling of rotor winding is accomplished by Gap Pick up method. The barrel portion is divided into a number of inlet and outlet zones. The gas picked up by the wedge scoops in the inlet zones due to the pressure created under the scoops by rotation, passes inwards, pass the lateral ducts on one side of the rotor coil stack and joins the corresponding duct on the other side and flows outwards and thrown into the gap in the outlet zones. Such a multi jet flow of hydrogen exposes large amount of rotor winding copper to the cooling medium thus creating very effective cooling and enabling a very low ratio of maximum to average copper temperature. FLOW PATH 3 The overhang portion of the winding is cooled by axial flow system and sectionalised into small parallel paths to minimize the temperature rise. Cold gas enters the overhang from under the retaining rings, through special chamber in the stator end shields and ducts under the fan hub and gets released into the air gap at the rotor barrel ends. 4. TEMPERATURE MONITORING : Temperature of various active parts of the generator are monitored and continuously recorded. For this purpose, resistance temperature detectors are embedded inside the stator slots for measurement of core iron and winding copper temperatures. Apart from RTD, mercury in steel dial type thermometers are also locally mounted to indicate hot and cold hydrogen, lub oil outlet from bearings, inlet and outlet water to generator gas cooler temperatures. Types of Resistance Temperature Detectors : Depending upon the medium where temperature is to be measured the following types are used: CRT-01-Suitable for temperature measurement of air & Hydrogen. CRT-02&04- Suitable for Temperature measurement of Liquid media.
288

CRT-03- Suitable for temperature measurement of bearing and seal babbit metals. CRT-05- For stator winding /core temperature. For temperature measurement of various active parts in the generator, copper element resistance thermometers are used. The basic principle is the change in electrical resistance of a conductor due to temperature. The resistance (Rt) at any temperature T is found by applying the equation. Rt = Ro (1 + !T)

Where Ro = Reference resistance at 00C. !""= Temperature coefficient in Ohms per 0C. T = Temperature in 0C. The standard resistance of the copper resistance elements used is 53 Ohms at 00C. The temperature coefficient amount to alfa (!) equal to 0.00426 Ohms/0C. Resistance characteristic for copper resistance thermometer with 53 ohms at 00C.

289

HYDRGEN COOLING OF GENERATOR & D. M. WATER COOLING OF STATOR


In all A.C. machines heat is generated due to windage cu-loss and core-loss. The rise in temperature must be controlled to protect the insulating material. The insulating materials can withstand temperatures from 900C to 1300C depending upon their grade. In earlier, smaller machines, air-cooling was sufficient. As the machine sizes increased, it was necessary to develop better ways of cooling to restrict the maximum temperature. In principle, Generators and motors are similar machines we are already familiar with various methods adopted for motor cooling i.e. direct cooled, T.E.F.C. T.E.W.C. etc. HYDROGEN COOLING : The turbo generator runs at 3000 rpm. With available material, the rotor diameter is limited to about 1.2 M. and length between bearings is restricted to 5 to 7 times diameter. As the air gap must also be limited, the size of stator gets limited. Thus the size of a Generator can not be increased in proportion to its size. Using higher current densities can only increase capacity. As the heat generated goes up, superior cooling methods are necessary to restrict the temperature rise. For a 60 MW, AIR COOLED Generator the break up of losses is as below : Total losses 1320 KW Windage loss 40% i.e. 528.0 KW Rotor loss 12% i.e. 158.0 KW Stator I2 R loss 12% i.e. 158.0 KW Stator iron loss 26% i.e. 344.0 KW Stray losses 10% i.e. 132.0 KW The quantity of cooling air required is 133 tons/hr. the total weight of stator and rotor is about 140 Tons. It can be seen that windage loss is the biggest loss. With hydrogen at only 5 lb/in2 this loss came down to 1/10th i.e.only 52.8 KW. This illustrates very dramatically, the advantages of Hydrogen cooling. TABLE RELATIVE QUALITIES HYDROGEN AIR 0.5 1 1 1 0.07 6.7 1.55 Pressure in Psi. 30 0.14 6.7 2.7 45 0.22 6.7 3.6

Density Thermal Conductivity Heat transfer co-eff.


290

Above table shows the superiority of Hydrogen over air. Further, hydrogen is non-toxic, and does not support combustion. In case of any internal fault (electrical), Hydrogen will not react in any way. However, with Hydrogen, a reliable sealing system is necessary. Monitoring of H2 purity is also essential as more than 20% oxygen can form an explosive mixture. Purity is generally maintained above 98.5% to derive full benefit of Hydrogen cooling. As the loss is reduced, generator loading and hence capacity is increased. It should be noted that heat is produced in 1) Rotor slots 2) Stator slots 3) Stator core Cu-loss Cu-loss Iron loss.

Hence, to effectively carry away this heat special construction features are adopted. Ventilation ducts and passages are provided in stator core the hot gas is cooled by D.M. water coolers, housed in the stator. Fans on the rotor circulate the gas to coolers and then stator core to the air gap where it cools the rotor and travels towards the fans. As generator capacities increased, may novel ways were developed to cool the conductors directly by providing gas passes along and below the slots. Even hollow conductors are used through which cooling gas is circulated. However Hydrogen cooling also reached its limit and for 210 MW generators, it became necessary to introduce cooling of stator conductors by water D.M. water has high resistivity and it is a very good cooling medium. Hydrogen cooling reduced windage loss to 1/10th and water cooling needs only 1/8th pumping power compared to fan power necessary for hydrogen circulation for stator cooling. Resistivity of D.M. water should be around 200 Kn/cm. Equipment for Hydrogen cooling : 1) H2 and CO2 cylinders. 2) H2 and CO2 manifolds and suitable piping, valves for filling and purfing out CO2. 3) H2 gas drier. 4) Purity meter for continuous monitoring of purity. 5) Shaft sealing arranement. Shaft sealing arrangement : To prevent escape of H2 from generator casing, two types of Hydrogen oil seals are used 1) Radial 2) Axial thrust type. Generally in both cases, the oil used is same as turbine lub. Oil. In some cases, a separate circuit is provided for seal oil and normally it does not mix with turbine oil. The axial thrust type seal is found more reliable and is used on existing 210 MW BHEL machines.

291

Stator water cooling : The stator conductors are made up of small cross section conductors to minimize eddy current losses. In a typical hollow bar construction, there are 14 hollow conductors sandwitched between solid conductors. The hollow cross-section is very small and hence good filters are provided in the circuit to avoid choking. D.M. Cooling water is admitted to upper bar and it returns through lower bar of next slot. The hot water then goes to expansion tank which is maintained under a vacuum of about 300 mm of Hg. This helps to remove gases from the water and thus corrosion is minimsed. From expansion tank, water is pumped by primary stator water pumps through DM/DM Coolers, filters back to stator conductors. Flow meters, purity meters (conductivity) and magnetic filters are included in the circuit. Water pressure must be kept below the hydrogen gas pressure in the casing. Cooling water flow of 27 M3/Hr is necessary for 210 MW unit. 1) Stator Water : Highest Water temp. - 60-700C Cold water temp. 400C 2) Gas Vs. Water cooling of hollow conductors.

Heat transfer is better in turbulent flow so velocity should be high and Reynolds number must be exceeded. For gases, R.N. is high, so high velocities are necessary. As ducts are small, pressure drop becomes high and too much fan power is needed. Water has high density and low R.N. Also, its heat transfer coeff. is 50 times more than hydrogen. Therefore, very low water velocities are needed for efficient cooling. Pumping power becomes only 1/8th of fan power necessary for gas circulation to obtain the same cooling effect. TYPICAL PROBLEMS : HYDROGEN COOLING SYSTEM : 1) Low H2 Purity : Even when all other things are normal, the purity meter shows a gradual drop in purity. This is due to reduced flow through purity meter. The drier contains calcium chloride which may block the flow after absorbing enough moisture. The CaCl2 should be replaced. 2) Excessive H2 leakage that is not tracable. The leakage may be at slip rings or through generator output leads. Shutdown is necessary for checking the leakage and attending the same. 3) Breaking of Cu-connectors and damage to brass nuts. This can be prevented by using flexible pipes suitably wirebraided. STATOR WATER SYSTEM : 1) Inadequate flow of cooling water even when filters are clean. This indicates blocking of stator conductors. The reason may be inadequate cleaning of stator water system initially

292

or after a maintenance job. Provision of back wash helps greatly. Cearing any debris stack up in stator bars is very difficult and so enough care must be taken for proper cleaning initially. 2) Drop in purity of D.M. Water : One important source is the injector which maintains vacuum in expansion tank. 3) If stator water pump has excessive gland leakage and a hose of raw-water is directed at the gland, D.M. water will get contaminated. This is a common practice and operators must be warned against this. Quantities of Gases for Puging CO2 : To remove air 90 M3 (To get 98% CO2 in Air) To remove H2 120 M3 (To get 98% CO2 in H2) Hydrogen : For initial filling 300 M3 (above 98% purity) Average make up (daily) 15 M3 When air is admitted to purge out CO2, the CO2 percentage should come down below 5% Temperature limits : Operational Limit due to Temperatures and Temperature Measurement : i) ii) iii) iv) v) vi) vii) viii) Stator winding copper Stator core iron Cold Hydrogen Hot Hydrogen 750C 950C 440C 750C 450C 850C 750C 1150C

Distillate at inlet of stator winding Distillate of outlet of stator winding Bearing & seal babbit Rotor winding temperature -

HEAT ABSORPTIN CAPACITY OF COOLANTS : COOLANT AIR HYDROGEN (0.5 PSIG) HYDROGEN (30 PSIG) OIL WATER VELOCITY FT/SEC 100 130 130 6.5 6.5

HEAT ABSORPTION CAPACITY W/0C/SEC 3.5 4.5 13 360 840

293

GENERATOR SEAL OIL SYSTEM FOR BHEL 210 MW UNITS (LMW Design)
In order to prevent the escape of Hydrogen from the generator casing along the rotor shaft, shaft seals with oil under pressure are used. The shaft seals are radial thrust type and are mounted between the end shield and the bearing at either end of the stator. The shaft seal consists of seal liner, lined with babbit surface that contacts a collar of the rotor shaft. The seal liner is enclosed in a sealed body. Sealing oil is fed through the seal body to form an oil film between babbit and the shaft collar. The liner is kept pressed to the shaft collar due to oil pressure in a chamber between the seal body and the liner and is free to move axially along with the shaft inside the seal body. Rubber sealing rings inserted between the seal body and the liner prevent oil leakage, from the high pressure oil zones. The oil catcher mounted on the shaft does not permit hydrogen side drain oil to go inside the machine. Drain oil in the air side is allowed to mix with the bearing oil but cannot leak due to the sealing ring assembly mounted on the sealing body fixed with the bearing. The seal oil supply system consists of an oil injector, two seal oil pumps, one cooler, two oil filters, differential pressure regulator, pressure oil regulator, damper tank, hydraulic seal, visual window, oil check pipe etc. The schematic diagram gives the complete details of the system. 1. SUPPLY OF OIL TO SHAFT SEAL : The oil to the shaft seal is supplied from two different sources. During the operating condition of the turbo-unit, the oil supply is taken from the governing system at 20 kg/cm2 and lubrication system at 1.5 kg/cm2. These two oils are diffused through the oil injector to get the supply of oil to the design pressure of oil in the supply pipe line. 2. OIL PUMPS : In case of failure of oil injector or during a standstill condition of the generator, the oil is supplied to the seals by means of two 100% oil pumps one as standby and the other as emergency. The standby pump is driven by 415 Volts A.C. motor and the emergency by 220 V. D.C. motor. The pumps are electrically interlocked. The standby oil pump automatically starts in case the pressure at the supply pipeline, detected by the electrical contact pressure gauge, drops by 1.5 kg/cm2 from the rated value. 3. OIL COOLER : In order to cool the seal oil, one oil cooler, vertical type, is used. The quantity of process water at 330C for cooling the seal oil is 95 M3/hr. at maximum 5 kg/cm2g. 4. OIL FILTERS : Two 50% oil filters are provided in the pipeline for filtering the seal oil.

294

5. DIFFERENTIAL PRESSURE REGULATOR : In order to maintain a constant pressure difference between oil and H2, a differential pressure regulator is adopted. This differential pressure maintains the oil at a pressure higher than the hydrogen pressure by 0.8 kg/cm2. 6. THRUST OIL REGULATOR : One thrust oil regulator in the circuit provides for holding the shaft sealing ring against a collar on the rotor. The outlet pressure of the regulator is regulated in the range 1 to 2.2 Kg/ cm2. 7. DAMPER TANK : The oil after the differential pressure regulator enters the damper tank and then to the shaft seals. The damper tank, provided in the system, supplies the oil to the shaft seal during transient conditions at changeover from injector supply to the pumps supply and vice-versa. The damper tank is situated at a height of 6 metres from the centre line of the generator, in order to keep the constant pressure difference between oil and hydrogen. To allow for constant checks on the level of oil in this tank, magnetic float indicators are installed which give the signals during low and emergency oil level in this tank. A greater part of the oil is drained towards the air side into oil of generation bearing. A small part of the oil is drained towards hydrogen side. To limit the zone of hydrogen dissipation throughout the turbine oil system pipeline, one 300 mm oil pipeline has a U-shaped oil seal at its end connected to turbine oil tank. 8. HYDRAULIC SEAL TANK : The oil discharged towards the hydrogen side is drained into the dydraulic seal. A 500 mm high loop in front of the hydraulic seal inlet is provided on the pipeline for oil discharge from the seal at the exciter end. This U-shaped pipeline prevents the gas circulation through the hydraulic seal, which is caused by the difference in the values of vacuum produced by the fans at both the generator rotor sides. The hydraulic seal ensures oil drainage from the hydrogen side of shaft seals and, at the same time, prevents escape of hydrogen from the generator casing through oil drain pipeline. The hydraulic seal has a level float regulator built into it for maintaining a set level of oil in the tank. The gas separated out assemblies at the top of the hydraulic seal and this is connected to the machine. Gas samples are also taken from the hydraulic seal for testing the purity of H2. Warning signals for high and low oil level in the hydraulic seal are provided by means of magnetic level indicator. 9. INSTRUMENTATION : The following pressure gauges are provided in the oil supply system for visual checks. Pressure gauges at the inlet and outlet of oil injector and centrifugal pump system. Pressure gauges at the outlet of cooler. Pressure gauges at the inlet and outlet of the differential pressure regulator.
295

Electrical contact pressure gauges at the oil supply header. Electrical contact pressure gauges at the inlet of seal oil to shaft seal. Electrical contact pressure gauges at the inlet of thrust oil to shaft seal. Pressure gauge at the outlet of thrust oil regulator.

In order to check the differential pressure between seal oil and H2, a differential pressure recording and indicating instrument with two position contact devices, having scale 0-1 kg/cm2 is used. The differential pressure transducer is mounted near the pipe line and the indicating and the recording instrument is mounted on the unit control board. 9. ANNUNCIATIONS PROVIDED : The following annunciations are provided on the signalling panel. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 10. 1. 2. Pressure of seal oil Pressure of pressure oil Oil level in Damper tank Oil level in Damper tank Oil level in Hydraulic seal Oil level in Hydraulic seal Automatic switching on of AC standby oil pump Automatic switching on of DC Emergency oil pump. Differential pressure between oil and H2 Differential pressure between oil and H2 TECHNICAL DATA : Quantity of oil for both the shaft seals. Rated pressure of shaft seal oil ... 160 L/min. 4.1 to 4.5 kg/cm2 ... Low ... High ... Low ... Low ... Low ... Emergency ... Low ... High

296

Generator seal oil system for BHEL 210 MW Units (Russian Design)

297

298

CONSTRUCTION OF EXCITER
Introduction : An electrical generator is a machine, which converts mechanical energy (or power) into electrical energy (or power). Energy conversion is based on the principal of the production of dynamically induced emf. Whenever conductor cuts magnetic flux dynamically an induced emf is produced in it according to Faradays Laws of electromagnetic induction. This emf causes a current to flow if the conductor circuit is closed. Hence two basic essential parts of an electrical generator are 1) A Magnetic field & 2) A Conductor or Conductors (armature) which can so move as to cut the flux. Generators are A.C. or D.C. the device in which electricity is generated by keeping the magnetic field stationary and armature rotating is called D.C. generator and the device in which electricity is generated by keeping the armature (conductor) stationary and magnetic field rotating is called A.C. generator. In the case of A.C. generators standard construction consists of armature winding mounted on stationary element called stator and field windings on a rotating element called rotor. The stator has a balanced, distributed three phase windings. The rotor is a cylindrical one and excited by the D. C source. The rotor winding is so arranged on rotor periphery that the field excitation produce nearly sinusoidal distributed flux/ pole in the air gap. As the rotor rotates, three phase emfs are produced in stator windings. Natural choice for excitation source was a shaft driven D. C. Generator whose output was supplied to the generator field through brushes and slip rings. Large capacity generators require very high excitation currents limiting thereby use of directly coupled conventional D. C. machines due to commutation and brushgear problem. Therefore mainly two types of excitation systems are in service namely a) AC excitation system & b) Static excitation system Excitation to the Gen.

Prime mover

Generator

D.C. Generator as exciter

(A) AC excitation system : A typical AC excitation system contains shaft mounted main exciter and pilot exciter and there is another AC excitation system known as Brushless excitation system. Description of typical excitation system that contains shaft mounted main exciter and pilot exciter. Main Exciter : Directly coupled higher frequency generators working at 400-500 Hz frequency
299

are also utilized as main exciter. The main exciter output is rectified through static silicon rectifier unit and fed to the generator. The armature is designed for low voltage operation, with comparatively high current levels. A permanent magnet type generator also known as pilot exciter that provides the excitation required for the main exciter and is mounted on the same shaft.

Generator Field excitation to the Gen. Rectifier

Pilot Exciter PMG

For 210 MW TG set maximum continuous ratings of the three phase main exciter are as per the following : 1500/1350 KVA/KW, 360 volts, 2400 A, 500 Cycles/Second, 3000 RPM The stator core and windings are air cooled, the ventilation circuit being formed by the end cover and ducting in the stator casing. The main exciter has induction type generator in which rotor has only empty slots on the surface of rotor without any windings inserted in them. The main as well as excitation D. D. windings are mounted on stator. Pilot Exciter : Pilot exciter is a permanent magnet type A. C. Generator having 400Hz frequency which provides osurce of supply for the automatic voltage regulator (AVR) circuit of the T. G. set. Stator has a frame of three phase winding which is brought out to the terminals at the terminal box. Permanent magnets are mounted on the rotor supported on tow journal type bearings. Brushless Excitation : Brushless excitation system is alternative to the conventional slipring excitation system and this system eliminates the need for brushgear maintenance and reduces the overall unit size. This system is used in 5oo MW units of CSTPS. Revolving armature AC exciter is the main component of this system. Revolving armature AC exciter is connected to the rotating rectifier mounted on same shaft, which itself is directly coupled to the main generator shaft. Field windings are on the rotor of the generator and they are directly connected to the output of the rotating rectifier. Excitation to the main exciter is obtained from pilot exciter. The three phase pilot exciter has a revolving field with permanent magnet poles. The three phase ac generated by the permanent magnet pilot exciter is rectified and controlled by the AVR (Automatic Voltage Regulator) to provide a variable DC current for exciting the main exciter.
300

Generator Pilot Exciter Main Exciter

Diode Wheel AVR (B) Static Excitation : As the technology is advanced static excitation is used for controlling the AVR circuit. Static excitation system is used in most of the 210 MW units of the MSPGCL. With large alternators in the power system, excitation control plays a vital role. With ever growing size of alternators various characteristic parameters also change and the effect of these on system performance has to be taken care of to a certain extent by the excitation system. Today more stringent specifications are required than ever before. In order to maintain system stability it is necessary to have very fast response excitation systems for large synchronous machines operating with the grid. This means that the field current of a synchronous machine must be matched extremely fast to changing operational conditions. It is because of this reason that the static excitation system is preferred. A high control speed is achieved by using an inertia free control and power electronic system. Fully controlled thyristor bridges are used to feed the generator field for controlling the generator output parameters. Any deviation in the generator terminal voltage is sensed by an error detector and causes the firing angle of the thyristors, which in turn controls, the field supply of the alternator. For synchronous machines, normally only positive excitation current i.e. current in only one direction in the rotor is required for the purpose of voltage control. STATIC EXCITATION EQUIPMENT : The static excitation equipment consists of the following main components or assemblies. 1. Rectifier transformer : The power transformer gets input supply from the generator output terminals. The secondary is connected to the thyristor bridge which delivers a variable DC output to the generator field. The transformer is housed in a ventilated cubicle. Normally dry type transformer is provided with protective devices. 2. Thyristor bridges : The thyristor bridge is assembled in one or more number of cubicles depending on the number of thyristor bridges connected in parallel. The number of bridges is so designed that in case one bridge fails during operation, the remaining bridges will have adequate capacity to
301

feed the generator field for full load output.In such (n-1) operation, where n specifies the total number of thyristor bridges, the converter is capable of delivering full power for field forcing conditions. Fans mounted on the top of the cubicle cool the thyristor bridges. Adequate protection and monitoring is provided for the thyristors and cooling fans. 3. Control electronics : The control circuits contain various electronic sub-assemblies in modular form mounted in various racks in regulation cubicle. The racks are mounted in a swing frame in the cubicle. Other items pertaining to the control scheme like auxiliary transformer, relays, filters, MCBs contactors, etc., are mounted in the cubicle on channels. Various features and working of the control scheme is explained separately. 4. Field flashing unit : Since it is not possible to start the excitation system with the residual voltage at nominal speed, a field flashing circuit is provided to overcome this problem. Initially the station auxiliary supply of 415V AC is stepped down by a small transformer, then rectified in a rectifier bridge and supplied to the generator field through a breaker. As soon as the generator output builds upto about 30%, the excitation system starts working smoothly and the field flashing circuit is then cut off at 70% of the generator voltage. Field flashing can also be done by feeding the generator field from station battery supply. The battery will be required to deliver approximately 50% of the no load current for 30 secs. Blocking diodes are provided to prevent any back feed from the field to the battery when the generator voltage rises under excitation control by thyristors. Field flashing cubicle contains the field flashing contactor, diode bridge, dropping resistors, etc. 5. Field suppression : For rapid de-excitation of the synchronous machine and complete isolation of the field from the thyristor bridge a field breaker is provided. In case of severe internal faults or a three phase short circuit at the generator terminals or a short circuit on the slip rings, the field breaker provides protection by isolating the DC source from the field. The field energy is dissipated through a field discharge resistance, which gets connected across the field under such operation. Normally non-linear discharge resistance is provided for rapid action.

302

GENERATOR EXCITATION SYSTEM


I THEORY : The synchronous machine is the most important element of a power system. The synchronous generator converts mechanical power into electrical form and feeds into the power network. Normally, a synchronous generator operates in parallel with other generator connected to an infinite bus. An infinite bus means a large system whose voltage and frequency remain constant independent of the power exchange between the synchronous generator and the bus, and independent of the excitation of the synchronous generator. The generator excitation which is controllable determines the flow of VARs into or out of the generator. The stator has a balanced, distributed three phase windings. The rotor is a cylindrical one and excited by the D. C source. The rotor winding is so arranged on rotor periphery that the field excitation produces nearly sinusoidal distributed flux/ pole (fr) in the air gap. As the rotor rotates, three phase emfs are produced in stator windings. On no load the voltage Ef induced in the reference phase a lags 900 behind fr which produces it and is proportional to %f. %f

Ef =Vf Obviously the terminal voltage Vt = Ef. As balanced steady load is drawn from the generator the stator currents produce synchronously rotating flux fa/pole. This flux, called armature reaction flux, is stationary with respect to field flux ff because the direction of armature flux is the direction of rotation of the rotor. &"% r = %"f + %"a

# = power factor angle $ = angle by which Ef leads vt called as load angle or torque angle. Magnitude of Ef determines the VARs delivered by the generator. Because of the assumed linearity of the magnetic circuit, voltage phasors Ef, Ea and Vt are proportional to flux
303

phasors f f, f a and f r respectively; further the voltage phasors lag 900 behind flux phasors. Vt = Ef j Ia x a Xa is the synchronous reactance of the generator. Ef = voltage induced by field flux f f alone. = no load voltage. The field induced emf Ef leads the terminal voltage by the torque angle d. This, in fact, is the condition for active power to flow out of the generatro. The magnitude of power delivered depends upon sin d. The flow of reactive power and terminal voltage of a synchronous generator is mainly controlled by means of its excitation. AVR [Auto Voltage Regulator] of the generator controls the terminal voltage and reactive power flow of the generator.

From the above phasor diagram we can conclude. ' Ef ' Sin (90+#) &'Ia' Cos # = 'Ia' Xs Sin$

'Ef' Sin $ Xs &P = 'Ef''Vt' Sin $ Xs i.e for Sin d = 900 maximum power can be drawn from the generator. =

The power factor or flow of reactive power can be changed by the excitation system by keeping active power constant. From the above equation we can device that Ef sin $ = Ia Xs cos % = PXs___ 'V+' = constant for constant delivery of power to the system.
304

Figure shows the phasor diagram for a generator delivering constant power to infinite bus but with varying excitation. As |Ef | sin $ remains constant f the tip of phasor Ef moves along a line parallel to V+ as excitation is varied. AVR does the job of controlling the excitation. Objectives of excitation control : Besides maintaining the field current and steady state operating point, the excitation system is required to improve the natural damping behavior and to extend the stability limits. The operating conditions to be taken into consideration are : Good response in Voltage and reactive power control. Satisfactory steady state stability i.e. sufficient damping of electromagnetic and electromechanical transients. Transient stability for all stated conditions. Quick voltage recovery after fault clearance.

In steady state operation, voltage response is of secondary importance. It is stability, i.e. damping behaviour of small oscillations which is more important. Under fault conditions the transient stability i.e., ability to return to the normal operating point is the main objective and voltage response again plays a secondary role. Natural choice for excitation source was a shaft driven D. C. Generator whose output was supplied to the generator field through brushes and slip rings. Large capacity generators require very high excitation currents limiting thereby use of directly coupled conventional D. C. machines due to commutation and brushgear problem. Therefore mainly two types of excitation systems are in service namely a) AC excitation system & b) Static excitation system (A) AC excitation system : A typical AC excitation system contains shaft mounted main exciter and pilot exciter and there is another AC excitation system known as Brushless excitation system. The details of this type of excitation system are covered in construction of exciter. (B) Static excitation system : With large alternators in the power system, excitation control plays a vital role. With ever growing size of alternators various characteristic parameters also change and the effect of these on system performance has to be taken care of to a certain extent y the excitation system. Today it is required to meet more stringent specifications than ever before. In order to maintain system stability it is necessary to have very fast response excitation
305

systems for large synchronous machines operating with the grid. This means that the field current of a synchronous machine must be matched extremely fast to changing operational conditions. It is because of this reason that the static excitation system is preferred. A high control speed is achieved by using an inertia free control and power electronic system. Fully controlled thyristor bridges are used to feed the generator field for controlling the generator output parameters. Any deviation in the generator terminal voltage is sensed by an error detector and causes the firing angle of the thyristors, which in turn controls the field supply of the alternator. For synchronous machines, normally only positive excitation current i.e. current in only one direction in the rotor is required for the purpose of voltage control. I. STATIC EXCITATION EQUIPMENT : The static excitation equipment consists of the following main components or assemblies. 1. Rectifier transformer : The power transformer gets input supply from the generator output terminals. The secondary is connected to the thyristor bridge which delivers a variable DC output to the generator field. The transformer is housed in a ventilated cubicle. Normally dry type transformer is provided with protective devices. 2. Thyristor bridges : The thyristor bridge is assembled in one or more number of cubicles depending on the number of thyristor bridges connected in parallel. The number of bridges is so designed that in case one bridge falls during operation, the remaining bridges will have adequate capacity to feed the generator field for full load output, under such (n-1) operation, where n specifies the total number of thyristor bridges, the converter is capable of delivering full power for field forcing conditions. The thyristor bridges are cooled by fans mounted on the top of the cubicle. Adequate protection and monitoring is provided for the thyristors and cooling fans. 3. Control electronics : The control circuits contain various electronic sub-assemblies in modular form mounted in various racks in regulation cubicle. The racks are mounted in a swing frame in the cubicle. Other items pertaining to the control scheme like auxiliary transformer, relays, filters, MCBs contactors, etc., are mounted in the cubicle on channels. Various features and working of the control scheme is explained separately. 4. Field flashing unit : Since it is not possible to start the excitation system with the residual voltage at nominal speed, a field flashing circuit is provided to overcome this problem. Initially the station auxiliary supply of 415V AC is stepped down by a small transformer, then rectified in a rectifier bridge and supplied to the generator field through a breaker. As soon as the generator output builds upto about 30%, the excitation system starts working smoothly and the field flashing circuit is then cut off at 70% of the generator voltage. Field flashing can also be done by feeding the generator field from station battery
306

supply. The battery will be required to deliver approximately 50% of the no load current for 30 secs. Blocking diodes are provided to prevent any back feed from the field to the battery when the generator voltage rises under excitation control by thyristors. Field flashing cubicle contains the field flashing contactor, diode bridge, dropping resistors, etc. 5. Field suppression : For rapid de-excitation of the synchronous machine and complete isolation of the field from the thyristor bridge a field breaker is provided. In case of severe internal faults or a three phase short circuit at the generator terminals or a short circuit on the slip rings, the field breaker provides protection by isolating the DC source from the field. The field energy is dissipated through a field discharge resistance, which gets connected across the field under such operation. Normally non-linear discharge resistance is provided for rapid action. Over voltage protection : An additional over voltage protection circuit is provided across the field so that during faults on the stator side, the induced over-voltages on rotor side are limited to remain below the insulation level of the field winding. Installation : The static excitation equipment should be normally mounted in dust free atmosphere on a floor free from vibration and heat source. The scheme can be understood easily by referring to the block diagram. II. DESCRIPTION : 1. Error detector and amplifier : The generator terminal voltage is stepped down by a three phase P.T. and fed to the Automatic Voltage Regulator (A.V.R.). The AC input thus obtained is rectified, filtered and compared against a highly stabilized reference value and any difference is amplified in different stages of amplification. The AVR is designed with highly stable elements so that variation in ambient temperature does not cause any drift or change in the output level. For parallel running of generators, compounding feature is provided. Three CTs sensing the current in the generator terminals feed proportional current across variable resistors in the AVR. The voltage thus obtained across the resistors can be added vectorially either for compounding purpose or for transformer drop compensation. The percentage of compensation can be adjusted as the resistors are of the variable type. The AVR also has a built-in frequency dependent circuit so that when the machine is running below the rated frequency fn the regulated voltage should be proportionally reduced with frequency. With the help of a potentiometer provided in the AVR the circuit can be made to respond proportionally to voltage above a certain frequency and proportionally to frequency below a certain frequency. The range of adjustment of this cut off frequency lies between 40 and 60 Hz. Various negative feed backs are provided to damp oscillations of the control variable and thus make the amplifier stable.

307

2.

Gate control unit : The output of the AVR is fed to a gate control unit. It gets its synchronous AC reference through a filter circuit and generates a row of pulses whose position depends on the DC input from the AVR i.e., the pulse position varies continuously as a function of the control voltage. The pulse limits for rectifier and inverter (de-excitation) operation can be adjusted independent of each other by potentiometers provided on the front side of the module. Six double pulses displaced by 600 from one another are generated at the output. Two relays are provided, by exciting which, the pulses can be either blocked completely or shifted to inverter mode of operation. Pulse amplifier : The pulse output of the gate control unit is amplified further at an intermediate stage of amplification. This is also known as pulse coupling stage. The unit besides pulse amplification of the preceding stage also enables direct parallel coupling of two fault independent pulse output channels to excitation system. It also has a DC power supply unit which operates from a three phase 380 V supply & delivers +15V, -15 V, +5V and a coarse stabilised voltage UL. A built-in relay is provided which can be used for blocking the 6 pulse channels. In a two channel system (like auto and hand) the changeover is effected by energizing/ deenergizing the relay. 4. Pulse final stage : This unit receives input pulses from the previous stage i.e. pulse amplifier (intermediate state) and transmits them through pulse transformers to the gates of the thyristors. The steep pulses at the output ensure simultaneous firing of several thyristors in parallel. A built-in power supply provides the required DC supply (15 V, + 5V &UL) to the final amplifiers. Each thyristor bridge has its own final pulse stage. Therefore, even if a thyristor bridge fails with its final pulse stage, the remaining thyristor bridges can continue to provide full load output and thereby ensure (n-1) operation. Pulses can be blocked with an internal relay provided in this unit. Pulses are blocked in case of : Failure of one or more thyristor fuses. Failure of the power supply of the final stage. Failure of the converter cooling fan. 5. Manual control channel : A separate manual control channel is provided where the controlling DC voltage through a motor operated potentiometer. The DC signal is fed to a separate grid control unit whose output pulses, after being amplified at an intermediate stage, can be fed to the final pulse stage. When one channel is working generating the required pulses, the other between Auto and Manual control is effected by blocking or releasing the pulses of the corresponding intermediate stage. A pulse supervision unit detects spurious pulses or loss of pulses on the pulses busbar and transfers control from Automatic channel to Manual channel. However during manual
308

3.

channel operation the pulse supervision is locked. Hence no supervision exists for the manual channel pulses. 6. Follow-up unit : To ensure a smooth changeover form Automatic to Manual control it is necessary that the position of the pulses in both channels should be identical. A pulse comparison unit detects any difference in the position of the pulses and with the help of a follow-up unit, actuates the motor operated potentiometer on the manual channel to turn in a direction so as to eliminate the difference. However, while transfering control from Manual to Auto mode, any difference in the two control levels can be visually checked on the balance meter provided on the swing frame in regulation cubicle. 7. Limit controllers in excitation system : When a generator is running in parallel with the power net-work, it is essential to maintain its synchronism without exceeding the max. permissible load on the machine and also without tripping by the protection system. The automatic voltage regulator alone cannot ensure this. It is necessary to influence the voltage regulator by suitable means to limit the over excitation and under excitation. This not only improves the security of parallel operation but makes operation of the system easier. However it must be made clear that the limiters do not replace the protection system but only prevent the protection system from tripping unnecessarily under extreme transient condition. Following limiters are normally used in the static excitation system : 1. Stator current limiter in over excited and under excited operation. 2. Rotor current limiter 3. Rotor angle limiter Rotor and stator current limiters reduce excitation in over excited operation while rotor angle and stator current limiters increase excitation in under excited operation. In the first case i.e., over-excited operation, the limiter intervenes only after a certain time i.e., over-excitation only for a short time is made available to facilitate field forcing to overcome short lived faults in the network. However, if the over-excitation persists, say, due to a remote three phase short circuit, the rotor current or stator current limiter after a time delay will be in action and protect the rotor current or stator current limiter after a time delay will be in action and protect the field winding & exciter equipment against over heating. In the second case i.e., under-excited operation, the rotor angle or stator current intervenes immediately, thereby, increasing the excitation and prevent a further increase in rotor angle which otherwise would cause the generator to fall out of step. The rotor angle limiter becomes operative as the load becomes increasingly capacitive. For instance, with long, lightly loaded high voltage lines capacitive load is found. Also due to failure of the voltage regulator or mal-operation of the system or tapchange in unit transformer the machine can become under excited.
309

7.1

Stator current limiter : This module functions in conjunction with an integrator which provides the necessary dead time and the gradient, that can be adjusted by potentiometers. The regulator consists essentially of a measuring converter, two comparators, two PID regulators and DC powe pack. A discriminator in the ckt. Differentiates between inductive & capacitive current. The positive & negative signals processed by two separate amplifiers are brought to the output stage & only that output which has to take care of the limitation is made effective. 7.2 Rotor current limiter : The unit basically comprises an actual value converter, a limiter with adjustable PID characteristics, a reference value, dv/dt sensor and a signalisation unit. The field current is measured on AC input side of the thyristor converter and is converted into a proportional DC voltage. The signal is compared with an adjustable reference value, amplified, and with necessary time lapse fed to the voltage regulator output. For operation DC power supply is given from a separate DC power supply unit. 7.3 Rotor angle limiter : This unit limits the angle between the voltages or it limits the angle between generator voltage and the rotor voltage. It comprises an actual value converter, a limiting amplifier with adjustable PID characteristics and a reference value unit. The limiting regulator operates as soon as the DC value exceeds the reference value. For its operation the unit is given separate power supply from a DC power pack.

310

311