INDEX
This document is intended for those having electrical knowledge and expertise, such as those using these products for manufacturing assemblies, carrying out electrical installation, maintenance and inspection, including the operators (end users) of these products.
Note This document describes the product specifications for selecting an appropriate low-voltage circuit breaker. A separate document Handling and Maintenance describing the operating instructions in detail. Please be sure to request a copy for using the selected product correctly.
4. Accessories ................................................................................................................................... 33
Internal Accessories ......................................................................................................................................................... 33
1. Accessories ............................................................................................................................................................................. 2. Switch Operation and Rating ................................................................................................................................................... 3. Maximum Number of Internally Mounted Accessories ............................................................................................................ 4. Shunt Trip (SHT) ...................................................................................................................................................................... 5. Undervoltage Trip (UVT) .......................................................................................................................................................... 6. Test Button Module (TBM) ....................................................................................................................................................... 7. Lead-wire Specifications .......................................................................................................................................................... 8. Vertical Lead-wire Terminal Block (SLT) .................................................................................................................................. 9. Cassette-type Accessories ...................................................................................................................................................... 10. Pre-alarm Module (PAL) .......................................................................................................................................................... 1. F-type Operating Handle ......................................................................................................................................................... 2. V-type Operating Handle ......................................................................................................................................................... 3. S-type Operating Handle ......................................................................................................................................................... 4. Terminal Cover ........................................................................................................................................................................ 5. Electrical Operation Device ..................................................................................................................................................... 6. Mechanical Interlocks (MI) ...................................................................................................................................................... 7. Handle Lock Devices and Card Holder ................................................................................................................................... 8. IEC 35mm Rail Mounting Adapters ......................................................................................................................................... 9. Insulating Barrier ..................................................................................................................................................................... 33 33 34 35 35 35 35 35 36 36 37 38 39 39 40 40 41 41 41
Higher Performance
The new circuit breaking technology Expanded ISTAC upgrades current limiting performance, leading to higher breaking capacity.
With higher breaking capacity, lower class models (e.g. NF-S General-purpose model to NF-C Economy model) can be used, thus leading to cost reduction of panels/machines.
NF250-HV
Reaction circuit
Current B
Fixed conductor
75kA/75kA
New model NF250-HV (at 400VAC)
Extending the conductor (reaction circuit for movable conductor) beneath the fixed conductor makes the movable conductor open faster than the conventional ISTAC mechanism. Significantly improves the current limiting performance.(Reduces the maximum peak current by 10%.)
Visualization
The new electronic circuit breakers (with display) and MDU breakers can display various measurement items. This will enable energy management through visualization, which leads to energy saving.
Electronic circuit breaker (with display)
MDU breakers
The display is on the circuit breaker body and shows circuit information. Detailed setting can be done on the display. The display turns red during alarms.
Display Current in each phase Alarm
Compact
The thermal adjustable circuit breakers and electronic circuit breakers are smaller.
These breakers contribute to the reduction of panel size.
Volume ratio
NF250-SGW
74%
NF250-SGV
250AF circuit breakers fixed types (NF250-CV, NF250-SV, NF250-HV, NV250-CV, NV250-SV, NV250-HV), thermal adjustable types (NF250-SGV, NF250-HGV, NF250RGV), and electronic types (NF250-SEV, NF250-HEV, NV250-SEV, NV250-HEV) are the same size, leading to the standardization of panel design.
Standardization
Types of internal accessories are reduced from 3 types to 1 type.
Standardization of internal accessories contributes to the reduction of stock and delivery time.
Conventional models
Three types
New models
One type
For 32 to 250AF
Applicable accessories AL AX AL+AX SHT UVT
32AF and 63AF circuit breakers can now be used in both AC and DC circuits without specifying when ordering. This will lead to prevention of ordering mistakes. The earth-leakage circuit breakers can now be equipped with a voltage shunt trip device (SHT).
Environment
Nonuse of Hazardous Substances
Eco-friendly design is used for all circuit breakers, and they do not use hazardous substances.The circuit breakers comply with RoHS regulation.
Product Line-up
Molded-case circuit breakers
NF-C economy type NF-S standard type NF-H high-performance type NF-U ultra current-limiting type
Motor protection
Motor circuit breaker
MDU breakers
NF-S, NF-H types
30 32
50 60 63
NF63-CV
100 125
NF125-CV NF125-SV NF125-SGV NF125-SEV
160
225 250
NF250-CV NF250-SV
400
NF400-CW NF400-SW NF400-SEW
600 630
NF630-CW NF630-SW NF630-SEW
800
NF800-CEW NF800-SDW
1000
1250
1600
NF63-SV
NF160-SGV
NF63-HV
NF160-LGV NF160-HGV
NF400-HEW
NF630-HEW
NF800-HEW
NF400-REW NF400-UEW
NF400-REW
NF800-REW NF800-UEW
30 32
50 60 63
NV63-CV
100 125
NV125-CV NV125-SV NV125-SEV
160
225 250
NV250-CV NV250-SV NV250-SEV NV250-HV NV250-HEV
400
NV400-CW NV400-SW NV400-SEW
600 630
NV630-CW
800
NV800-SEW
NV63-SV
NV630-SW
NV63-HV
Motor Protection
Types Frame(A)
30 32
NF32-SV
50 60 63
NF63-CV NF63-SV
100 125
NF125-SV
160
225 250
NF250-SV
400
600 630
800
MDU Breakers
Types Frame(A)
30 32
50 60 63
100 125
160
225 250
NF250-SEV NF250-HEV
400
NF400-SEP NF400-HEP
600 630
NF600-SEP NF600-HEP
800
NF800-SEP NF800-HEP
New models
10
11
Ordering Information
Molded-case Circuit Breakers
Type name
NF C S H U DSN Economy type Standard type High-performance type Ultra current-limiting type DSN-type switches
NF250-SV
Number of poles
NV250-SV
Number of poles
2P, 3P, 4P
2P 3P 4P
NV NV NV
3P
Rated current
3P
Rated current
200A
Motor protection
Please specify the rated current even for rated current adjustable types
200A
Motor protection
Please specify the rated current even for rated current adjustable types
MB
Rated voltage
MB
Rated voltage
AC
AC
Standard
Please specify applicable marine standard
100-440V 200-440V
Connection method
F SL B PM
B
Built-in accessories
B
Type of residual current protection
PAL
Blank Specify
PAL
Internal accessories
AL AX SHT UVT SLT MD F/S/V Alarm switch Auxiliary switch Shunt trip (specify rated coil voltage) Under voltage trip (specify rated coil voltage) Lead-wire terminal block Electrical operation device Operating handle Enclosure box Mechanical interlock Terminal cover (TC-L, TC-S, TTC, BTC) Handle lock device Card holder Mag Only (specify AC or DC and rated current) DC-use (specify 400, 440, 500, 550 or 600VDC) 400Hz use Low-inst (specify AC or DC and Inst. %)
Built-in accessories
Insulation switch Earth-leakage circuit alarm switch Test button module Pre-alarm module
MG
Internal accessories
AL AX UVT SLT
Alarm switch Auxiliary switch Under voltage trip (specify rated coil voltage) Lead-wire terminal block
External accessories
MD F/S/V MI Electrical operation device Operating handle Mechanical interlock Terminal cover (TC-L, TC-S, TTC, BTC) Handle lock device Card holder
Quantity
Quantity
TC LC / HL HL-S CH
10
Mag Only
10
12
1. Detailed Specifications
Molded-case Circuit Breakers
NF-C (Economy type)
Frame (A) Type name 63 NF63-CV 125 NF125-CV 250 NF250-CV
Image
Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V
AC
DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 40 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.5 0.7 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped
50 (60) 63 (75) 80 100 125 3 40 600 7.5/4 10/5 10/5 10/5 10/5 30/15 7.5/4 (*2) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 60 90 130 68 90 0.6 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 2
(100) 125 150 175 200 225 250 2 3 40 600 10/8 15/12 25/19 25/19 25/19 36/27 15/12 (*2) 8 AC/DC compatible Compatible Possible 8,000 4,000 A 3 N/A 105 165 68 92 1.3 1.5 (*3) (*3) (*3) (*3) TV approval Recognized Thermal-magnetic Equipped
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *6 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively.
Line
Line
3-pole
Load
Load 4-pole
13
3 4 (5) 6 10 (15) 16 20 25 (30) 32 3 40 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.45 0.65 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 2
3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 4 40 600 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped
(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 2 3 4 40 690 8/8 18/18 25/25 30/30 30/30 30/30 50/50 40/40 (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 60 90 120 130 68 90 0.7 0.95 1.3 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped
16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*6) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
14
1. Detailed Specifications
Molded-case Circuit Breakers
NF-S (Standard type)
Frame (A) Type name 125 NF125-SEV 160 NF160-SGV 250 NF250-SV
Image
Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V 16-32 32-63 63-125 3 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 2 125-160 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped (100) 125 150 160 175 200 225 250 2 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) TV approval Self-declaration Recognized Thermal-magnetic Equipped
AC
DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible.
Line
Line
3-pole
Load
Load 4-pole
15
NF-L
250 NF250-SGV 250 NF250-SEV 125 NF125-LGV 160 NF160-LGV 250 NF250-LGV
Available soon 125-160 140-200 175-250 3 4 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2 80-160 125-250 3 40 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 125-160 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2 125-160 140-200 175-250 3 4 40 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
16
1. Detailed Specifications
Molded-case Circuit Breakers
NF-H (High-performance type)
Frame (A) Type name 63 NF63-HV 125 NF125-HV 125 NF125-HGV
Image
Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V
AC
DC Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*4) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*4) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
10 (15) 16 20 25 (30) 32 40 50 (60) 63 2 3 4 40 690 2.5/2.5 7.5/7.5 10/8 10/8 10/8 10/8 25/19 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped
(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 2 3 4 40 690 10/8 30/23 50/38 50/38 50/38 50/38 100/75 8 AC Compatible Possible 25,000 10,000 A 3 N/A 90 120 130 68 90 0.6 1.0 1.2 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped
16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *4 Not isolation-compatible. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right.
Line
Line
3-pole
Load
Load 4-pole
17
125 NF125-HEV
160 NF160-HGV
250 NF250-HV
250 NF250-HGV
250 NF250-HEV
Available soon 16-32 32-63 63-125 3 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4 2 125-160 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 40,000 15,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 125 150 160 175 200 225 250 2 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognized Thermal-magnetic Equipped 125-160 140-200 175-250 3 4 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 25,000 10,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 (*3) (*3) (*3) (*3) Self-declaration Recognition in process Thermal-magnetic Equipped 2
Available soon 80-160 125-250 3 40 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 8 AC Compatible Possible 25,000 10,000 A 3 A 105 165 68 92 1.7 2.2 140 4
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify P-LT when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
18
1. Detailed Specifications
Molded-case Circuit Breakers
NF-U (Current-limiting type ultra breaker)
Frame (A) Type name 125 NF125-RGV 250 NF250-RGV
Image
Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) 690V 500V 440V 415V 400V 380V 230V 250V 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 2 3 40 690 125/125 150/150 150/150 150/150 150/150 8 AC Compatible Possible 50,000 30,000 A 3 N/A 105 165 68 92 1.5 1.8 (*1) (*1) (*1) (*1) Self-declaration Recognition in process Thermal-magnetic Equipped
Available soon 125-160 160-200 200-250 2 40 690 125/125 150/150 150/150 150/150 150/150 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 165 68 92 1.5 1.8 (*1) (*1) (*1) (*1) Self-declaration Recognition in process Thermal-magnetic Equipped 3
AC
DC Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch Cassette-type Shunt trip (SHT) accessories (UVT) Undervoltage trip (SLT) With lead-wire terminal block (PAL) Pre-alarm Closed (S) Enclosure Dustproof (I) (W) Waterproof Electrical operation device (NFM) Mechanical interlock (MI) (*2) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*2) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
Notes: *1 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT, NF125-RGV, NF250-RGV). *2 Not isolation-compatible.
19
125 NF125-UGV
250 NF250-UGV
Available soon 16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 2 3 40 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 8 AC Compatible Possible 50,000 30,000 A 3 N/A 105 240 68 92 2.7 4 2
Available soon 125-160 160-200 175-225 3 40 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 240 68 92 2.7 4
140
140
2.5
3.7
2.5
3.7
20
1. Detailed Specifications
Earth-leakage Circuit Breakers
NV-C (Economy type) Harmonic surge ready
Frame (A) Type name 63 NV63-CV 125 NV125-CV 250 NV250-CV
Image
Rated current In (A) Number of poles Rated ambient temperature (C) Phase line (*1) Rated operational voltage Ue (V) High-speed type Max. operating time Rated current sensitivity Max. operating time Internal non-operating time Earth-leakage indication system Time-delay type Rated short-circuit breaking capacity (kA) (s)
(5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 2 40 (*2) (mA) at In at 5In AC 33W, 12W 100-440 30,100/200/500 30 selectable 0.1 0.04 Mechanical type (button) 2.5/2.5 2.5/2.5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 6 AC Compatible 10,000 6,000 A 2 A 75 130 68 90 0.7 0.75 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped 12W 100-240 3
(60) 63 (75) 80 100 125 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 10/5 10/5 10/5 30/15 30/15 30/15 6 AC Compatible 10,000 6,000 A 2 A 90 130 68 90 1.0 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped
125 150 175 200 225 250 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 15/12 25/19 25/19 36/27 36/27 36/27 6 AC Compatible 8,000 4,000 A 2 A 105 165 68 92 1.7 (*5) (*5) (*5) (*5) (*6) TV approval Recognized Thermal-magnetic Equipped
(mA) (s) (*4) (s) (or more) 440V 415V 400V 230V 200V 100V
AC
Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Number of operating Without current cycles With current Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch Cassette-type Shunt trip (SHT) accessories (UVT) Undervoltage trip (SLT) With lead-wire terminal block (TBM) Test button module Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*8) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*8) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
Notes: *1 For the 12W supply system, use the right and left pole terminals. Caution is required in this case as the center pole is a live part. *2 Rated operational voltage of time-delay type is for 200-440V. *3 Time-delayed types are produced for current specifications of 20A or more. *4 When operating times are 0.45s, 1.0s and 2.0s, the relay operates between 0.15s and 0.45s, 0.6s and 1.0s, and 1.2s and 2.0s, respectively.
*5 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *6 All models have a vertical lead terminal unit (SLT) as standard. *7 For other models, please order in conjunction with the circuit breaker. *8 Not isolation-compatible.
21
Available soon (5) 6 10 (15) 16 20 25 (30) 32 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 5/5 5/5 5/5 10/10 10/10 10/10 6 AC Compatible 10,000 6,000 A 2 A 75 130 68 90 0.75 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped (5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 6 AC Compatible 15,000 8,000 A 2 A 75 130 68 90 0.8 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped (15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 (*3) 3 40 33W, 12W 100-440 34W 200-440 4 3 40 33W, 12W 100-440 34W 63-125 4
30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 25/25 30/30 30/30 50/50 50/50 50/50 6 AC Compatible 25,000 10,000 A 2 A 90 130 68 90 1.1 1.4 120
(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breakers will be delivered with rated current sensitivity set to 500mA and operating time of time-delayed types to 2.0s unless otherwise specified. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block. 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
(5)
Applicable circuit voltage Available voltage range Rated operational voltage 100/110/200/220/230/240V 80~264V 100-240V 100/110/200/220/240/254/265/380/400/415/440V 80~484V 100-440V 200/220/240/254/265/380/400/415/440V 160~484V 200-440V 100/110/200/220/240/254/265/380/400/415/440V 80~484V 100-200-415V 200/220/240/254/265/380/400/415/440V 160~484V 200-415V
22
1. Detailed Specifications
Earth-leakage Circuit Breakers
NV-S (Standard type) Harmonic surge ready
Frame (A) Type name 250 NV250-SV 250 NV250-SEV
NV-H
63 NV63-HV
Image
Available soon Rated current In (A) Number of poles Rated ambient temperature (C) Phase line type (*1) Rated operational voltage Ue (V) High-speed type Max. operating time Rated current sensitivity Max. operating time Internal non-operating time Earth-leakage indication system Time-delay type Rated short-circuit breaking capacity (kA) (s) 125 150 175 200 225 250 3 40 (*2) (mA) at In at 5In AC 33W, 12W 100-440 34W 200-440 4 125-250 3 40 33W, 12W 100-440 (15) 16 20 (30) 32 40 50 (60) 63 3 40 33W, 12W 100-440 30, 100/200/500 selectable 0.1 0.04 Mechanical type (button) 10/8 10/8 10/8 25/19 25/19 25/19 6 AC Compatible 15,000 8,000 A 2 A 75 130 68 90 0.8 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped
(mA) (s) (*4) (s) (or more) 440V 415V 400V 230V 200V 100V
AC
Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Number of operating Without current cycles With current Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) (F) Front Installation (SL) Solderless (BOX) terminal and (B) Rear connections (PM) Plug-in (AL) Alarm switch (AX) Auxiliary switch (SHT) Cassette-type Shunt trip (UVT) accessories Undervoltage trip (SLT) With lead-wire terminal block (TBM) Test button module Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*8) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*8) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 165 68 92 1.9 (*5) (*5) (*5) (*5) (*6) TV approval Self-declaration Self-declaration Recognized Recognized Electronic (effective value detection) Thermal-magnetic Equipped Equipped (30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6)
Notes: *1 When wiring a three-pole earth-leakage circuit breaker to 12W, do not use the central pole but connect to the left and right poles. *2 Rated operational voltage of time-delay type is for 200-440V. *3 Time-delayed types are produced for current specifications of 20A or more. *4 When operating times are 0.45s, 1.0s and 2.0s, the relay operates between 0.15s and 0.45s, 0.6s and 1.0s, and 1.2s and 2.0s, respectively.
*5 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *6 All models have a vertical lead terminal unit (SLT) as standard. *7 For other models, please order in conjunction with the circuit breaker. *8 Not isolation-compatible.
23
surge ready
250 NV250-HV 250 NV250-HEV
125 NV125-HEV
Available soon (15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125 (*3) 3 40 33W, 12W 100-440 34W 200-440 4 3 40 33W, 12W 100-440 34W 33W, 12W 100-440 63-125 4 125 150 175 200 225 250 3 40 34W 200-440 4
Available soon 125-250 3 40 33W, 12W 100-440 (30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 165 68 92 1.9 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped
Applicable circuit voltage 100/110/200/220/230/240V 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V Available voltage range 80~264V 80~484V 160~484V 80~484V 160~484V
30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 50/38 50/38 50/38 100/75 100/75 100/75 6 AC Compatible 25,000 10,000 A 2 A 90 120 130 68 90 1.1 1.4 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped
(30) 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.9 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Electronic (effective value detection) Equipped
30, 100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible 25,000 10,000 A 2 A 105 140 165 68 92 1.8 2.5 (*5) (*5) (*5) (*5) (*6) Self-declaration Recognized Thermal-magnetic Equipped
(5)
Rated operational voltage 100-240V 100-440V 200-440V 100-200-415V 200-415V
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breakers will be delivered with rated current sensitivity set to 500mA and operating time of time-delayed types to 2.0s unless otherwise specified. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block (excluding 63A frame or smaller). 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells. 5. Please contact us for 4 pole of NV250-SEV, NV250-HEV.
24
1. Detailed Specifications
Motor-protection Breakers
NF - MB (Motor breakers)
Frame (A) Type name 32 NF32-SV 50 NF63-CV NF63-SV
A 32 25 16 12 10 8 7.1 5 4
200/220V 400/440V kW kW 7.5 15 11 5.5 7.5 3.7 5.5 2.2 3.7 1.5 2.2 1.5 0.75
A 45 40 32 25 16 12 10 8
200/220V 400/440V kW kW 22 11 18.5 15 7.5 11 5.5 7.5 3.7 5.5 2.2 3.7
A 7.1 5 4
Number of poles Rated ambient temperature (C) Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) 440V 415V 400V 380V 230V
AC
Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Number of operating Without current cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B)
a ca c b
a b c ca
Mass of front-face type (kg) Installation (F) Front and (B) Rear connections Plug-in (PM) (AL) Alarm switch (*1) (AX) Auxiliary switch (*1) Cassette-type (SHT) Shunt trip (*1) accessories (UVT) Undervoltage trip (*1) (SLT) With lead-wire terminal block Closed (S) Enclosure Dustproof (I) Waterproof (W) Electrical operation device (NFM) Mechanical interlock (MI) (*2) Panel mounting LC Handle lock device HL External HL-S accessories (F) External operating (V) handle (S) (*2) Terminal cover (TC-L, TC-S, TTC, BTC) (B-ST) Rear stud (PM) Plug-in IEC 35mm rail mounting adapters CE marking CCC recognition Automatic tripping device Trip button
3 40 500 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 8 AC Compatible Possible 10,000 6,000 A 3 N/A 75 130 68 90 0.65 Self-declaration Recognized Thermal-magnetic Equipped
3 40 500 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 8 AC Compatible Possible 10,000 6,000 A 3 N/A 75 130 68 90 0.65 Self-declaration Recognized Thermal-magnetic Equipped
3 500 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 8 AC Compatible Possible 15,000 8,000 A 3 N/A 75 130 68 90 0.7 Self-declaration Recognized Thermal-magnetic Equipped
Notes: *1 The cassette-type design makes it easy for customer to install. Available for installation on side (excluding UVT). *2 Not isolation-compatible.
25
100 NF125-SV
225 NF250-SV
200/220V 400/440V kW kW 100 55 90 22 45 71 18.5 37 63 15 30 45 11 22 (40) 19 32 7.5 15 (25) 5.5 11 (16) 3.7 7.5 (12.5) 5.5 A
3 40 500 25/25 30/30 30/30 30/30 50/50 8 AC Compatible Possible 25,000 10,000 A 3 N/A 90 130 68 90 0.95 Self-declaration Recognized Thermal-magnetic Equipped
3 40 500 36/36 36/36 36/36 36/36 85/85 8 AC Compatible Possible 25,000 10,000 A 3 N/A 105 165 68 92 1.6 TV approval Recognized Thermal-magnetic Equipped
Remarks: 1. The motor circuit breakers do not have an applicable rated motor capacity. Select a motor circuit breaker based on the total load current of the motor. 2. Products with rating parenthesized are produced when an order is placed. 3. Specify P-LT when using a plug-in product with a lead-wire terminal block. 4. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
26
2. Special-purpose Breakers
Mag Only, DC and DSN
Wiring diagram for DC use Remark: 1. The tripping characteristics will change if the wiring differs from that shown here.
NF63-SV
3 400 2/2 4 550
NF125-SV
3 440 4 550
NF250-SV
3 500 4 600
10/10
20/20
DC side These breakers are designed as thyristor-Leonard system DC-side breakers. They protect the thyristor from short circuiting when there is a power or communication failure (Mag-only breakers can also be used for this purpose). Use these breakers in combination with fast fuses for even greater protection.
Type Number of poles Rated voltage (VDC) Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics) Instantaneous trip current (min.)
NF125-SV
2 250 40/40 3 440 10/10
NF250-SV
2 300 20/20 3 times rated current 3 500
DSN switches These are standard MCCBs without the automatic tripping element. The tripping capacity is approximately six times the rated current. The appearance, size, drilling plan and available accessories are all identical to similar standard S and C Series MCCBs.
Type Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC)
DSN63-CV
63 2 500/ 250 378/155 3
DSN125-CV
125 2 500/ 250 750/ 310 3
DSN250-CV
250 2 500/ 250 1500/ 625 3
Type Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC)
DSN32-SV
32 2 3
DSN63-SV
63 2 3
500/250 192/80
500/250 378/155
27
2. Special-purpose Breakers
400Hz, Instantaneous and Generator Protection
400Hz MCCBs
Standard MCCBs cannot be used in 400Hz circuits. When standard MCCBs are used in high-frequency circuits (eq. 400Hz), the instantaneous characteristics are shifted higher. The 400Hz MCCB is recommended for use in 400Hz circuits.
Type Rated current (A) Number of poles Rated insulation voltage (V) 690V 500V Rated breaking capacity (kA) 440V IEC 60947-2 (Icu / Ics) 400V 230V
Specifications The appearance, size, rated interrupting capacity, drilling plan, accessories, etc., are all identical to the standard S and H Series breakers of the same designation.
NF250-SV
125, 150 175, 200 2 690 3 8/8 30/30 36/36 36/36 85/85 4 2
NF125-SV
16, 20, 32, 40, 50, 63, 80, 100 2 3 8/8 18/18 25/25 30/30 50/50 4
NF125-HV
16, 20, 32, 40, 50, 63, 80, 100 2 3 10/8 30/23 50/38 50/38 100/75 4
NF250-HV
125, 150 175, 200 3 10/8 50/38 65/65 75/75 100/100 4
Low-instantaneous MCCBs
Low-Inst. MCCBs for Discrimination When a power fuse (PF) is used for high-voltage protection, make sure that the MCCB on the secondary side is compatible.
Type Number of poles Rated current (A) 600 400
Specifications
NF125-CV
2 3 2
NF125-SV
3 4
NF250-CV
2 3 2
NF250-SV
3 125, 150, 175 200, 225, 250 4
PF Time
Tr1
16, 20, 32, 40 125, 150, 175 50, 63, 80, 100,125 200, 225, 250
MCCB 1
Low-inst. MCCBs
MCCB 2
Current
Remarks: 1. Ensure compatibility with motor, etc., before use to prevent accidental tripping at start up. 2. Specify rated current and tripping characteristics. 3. There are no short time delay characteristics.
Fig. 4.12 Low-inst. MCCB characteristics The appearance, size, rated interrupting capacity, accessories, etc., are all identical to the standard instantaneous trip breakers of the same designation.
NF125-SEV
3 16-32 32-63 63-125 adjustable
NF125-HEV
3 16-32 32-63 63-125 adjustable
NF250-SEV
3 80-160 125-250 adjustable
NF250-HEV
3 80-160 125-250 adjustable
Instantaneous trip (% of rated current) Operating time at 150% of rated current (s) Rated insulation voltage (V) 690VAC 500VAC Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics) 440VAC 400VAC 230VAC 8/8 30/30 36/36 36/36 85/85 10/8 50/38 65/65 75/75 100/100
300 (*1) 18~28 (*1) 690 8/8 30/30 36/36 36/36 85/85 10/8 50/38 65/65 75/75 100/100
Note: *1 The MCCB operating characteristics must be adjusted as follows. STD 3 (Is setting) LTD: minimum setting (TL = 12s setting)
28
2. Special-purpose Breakers
MDU Breakers
Available soon
Circuit breakers and measurement display units are integrated. With built-in VT and CT, the circuit breaker requires less space and contributions are made to reduced work and energy savings.
A low-voltage circuit breaker combines an MDU for measuring, displaying, and transmitting information on cable ways, and closely monitors energy consumption by measuring current, voltage, power, electric energy, harmonic current, leakage current, power factor, etc., to assist in energy savings. Since the circuit breaker saves its tripping information (causes and current values), causes of accidents can be investigated and corrected sooner.
Type Frame (A) Number of poles Suitability for use Rated insulation voltage (V) Rated current (A) Rated short-circuit breaking capacities (kA) AC IEC60947-2 (Icu/Ics) 690V 500V 440V 415V 400V 380V 230V 200V Reverse connection Installation and connections Front connection (F) Rear connection (R) Cassette-type accessories External accessories (*1)
Note: *1 For models with DP, the accessories below are not applicable. Electrical operation device (NFM) Mechanical interlock (MI) External operating handle (F, V, S) Handle lock device (HL-S) Enclosure (S, I, W)
NF250-SEV with MDU 250 3 33W 690 125-250A (adjustable) 8/8 18/18 36/36 36/36 36/36 36/36 85/85 85/85 Refer to P.16 Refer to P.16 4 34W 3
NF250-HEV with MDU 250 4 34W 690 125-250A (adjustable) 10/8 30/23 50/50 70/70 75/75 75/75 100/100 100/100 Refer to P.18 Refer to P.18
33W
Panelboard mounting 4 1
3 NF250-SEV/HEV with DP NF250-SEV/HEV Module (power input) Module (power input + transmission) Module (pre-alarm) MDU-DP-N (display) MDU-DP-C (display + network) Measuring Load current Line voltage Power (active/reactive) Energy (active/reactive) Display 14 Harmonic current Power factor Frequency Alarm OVER Trip cause (LTD, STD, INST) & trip current Pre-alarm Transmission 2 CC-Link Pulse output (electric energy) 2-a 2-b 3 2-a 2-b 3 4-a 4-b 3 4-a 1-a 1-a 1-a 1-a 1-b 1-b 1-b
1-b
4-b
29
24
144 165
102 50
45 61 68 77 92
22 70 105
100
8.5
100
8.5
45 61 4 68 72 92
Neutral pole
22 70 105
35 105 140
Neutral pole
3-pole
4-pole
3-pole
4-pole
Breaker mounting
Panel mounting
Rear connection
Mtg plate t max.=3.2 Stud can be rotated 90 Insulation tube 4-pole 3-pole Mtg plate Stud can be t max.=3.2 rotated 90 Insulation 4-pole Breaker tube 3-pole 39.5 4-pole 3-pole Breaker
4-pole 3-pole
20
20
Connection allowance 22
R1
144
144
Connection allowance 22 15
88.5
M40.7 32.5 breaker 15 mtg screw 70 100 105 Insulation 9 1mm clearance tube M8 bolt on each side of handle Breaker mounting Front-plate cutout 6
6 15 9 M8 bolt 70 105
32.5 100
68 72
71 106
Insulation 1mm clearance tube on each side of handle Front-plate cutout Panel mounting
MDU Terminal
Breaker mounting
MDU terminal In the figure below the terminal cover is removed. Control power FG Control power P1 M3 screw Control power P2
Connector (removable)
1 2 3 4 5 6
3 4 5 114 DG DB
6 113 DA
52
4.5
30
2. Special-purpose Breakers
MDU Breakers
MDU panel mounting
Front connection
10 Insulation barrier (removable) 100 Mtg hole Trip Button M8 bolt (hex-socket)
8 .5
C 1
24
Breaker
100
8.5
45 61 4 68 72 92 25max. 35 35 M40.7 (Bus t max.=7) or 5 4-pole 3-pole Bus drilling for direct connection Drilling plan
22 70 105
35 105 140
Neutral pole
3-pole
4-pole
Panel mounting
Rear connection
Mtg plate Stud can be t max.=3.2 rotated 90 Insulation 4-pole tube 3-pole 4-pole 3-pole Breaker Breaker
144
20
Connection allowance 22 15
6 15 9 M8 bolt 70 105
32.5 100 35 70
24 M40.7 or 5
68 72
71 106
Insulation 1mm clearance tube on each side of handle Front-plate cutout Panel mounting
35 35 105
3-pole
MDU connector
90
Terminal block
R2
72
91 35
Front-panel cutout
126 144 6
31
72
52
126
1 C
3. Connection Method
1. Connection Types
Table 3-1: Connection types
Connection method (abbreviation) The front connection model will be delivered unless otherwise specified. Front connection models can be converted to other types using an appropriate connection component (separately available).
Plug-in (PM)
Image
2. Connection Accessories
Table 3-2: List of connection accessories
Type name NF32-SV, NF63-CV/SV/HV NV32-SV, NV63-HV NV63-CV/SV NF63-SV/HV NF125-CV/SV NF125-HV NF125-CV/SV, NV125-CV/SV NF125-HV, NV125-HV NF125-SV, NV125-SV, NF125-ZSV NF125-HV, NV125-HV, NF125-ZHV NF250-CV/SV NF250-HV NF250-CV/SV, NF125-SEV, NF250-SEV, NF125-SGV/LGV/HGV, NF160-SGV/LGV/HGV, NF250-SGV/LGV/HGV, NV250-CV/SV, NV125-SEV, NV250-SEV NF250-HV, NF250-HEV, NV250-HV, NV250-HEV, NF125-HEV, NV125-HEV NF125-SEV, NV125-SEV, NF250-SV, NF250-SEV, NV250-SV, NV250-SEV (*5) NF250-HV, NF250-HEV, NV250-HEV (*5), NF125-HEV, NV125-HEV 2P 3P 2P 4P 2P 3P 4P 2P SL-1SV4L (*1) SL-1SV4G (*2) SL-1SV3L (*1) SL-1SV3G (*2) SL-1SV4L (*1) SL-1SV4G (*2) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV3L (*3) SL-2SV3G (*4) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV4L (*3) SL-2SV4G (*4) SL-2SV3L (*3) SL-2SV3G (*4) SL-2UV4L (*3) SL-2UV4G (*4) SL-2UV3L (*3) SL-2UV3G (*4) SL-2UV4L (*3) SL-2UV4G (*4) Solderless terminal (SL) Rear studs (B-ST) (ST-05SV2) (ST-05SV3) (ST-05SV2) (ST-05SV4) (ST-1SV2) (ST-1HV2) (ST-1SV3) (ST-1SV4) (ST-2SV2) Plug-in (PM) (PM-05SV2) (PM-05SV3) (PM-NV05SV2) (PM-05SV4) (PM-1SV2) (PM-1HV2) (PM-1SV3) (PM-1SV4) (PM-2SV2)
3P
(ST-2SV3)
(PM-2SV3)
4P 2P
(ST-2SV4)
32
4. Accessories
Internal Accessories
1. Accessories
Table 4-1: Accessories
Internal accessories Alarm switch Auxiliary switch Function Electrically indicates the trip status of the circuit breaker. Electrically indicates the ON/OFF status of the circuit breaker. NF-C/S/H/U NV-C/S/H/U Applicable models Cassette-type accessories
Shunt trip
Electrically trips the circuit breaker from a remote distance. Permissible working voltages are 70 to 110% of the AC rated voltage or 70 to 125% of the DC rated voltage. Automatically trips the circuit breaker if the voltage is lowered. Working voltages are 70 to 35% of the UVT rated voltage. When the voltage recovers to 85% or higher, it is possible to reset the device and restart operation. Allows remote testing through application of a voltage. An external sequence common to SHT can be used. (The standard configuration requires the vertical lead-wire terminal unit (SLT).) Indicates that the load current exceeds the pre-alarm setting current.
NF-C/S/H/U NV-C/S/H/U
Undervoltage trip
NF-C/S/H/U NV-C/S/H/U
NV-C/S/H
Electronic type
OFF or ON
250 125
Trip
OFF or Trip
ON
33
Cassette-type accessories NV
NF63-CV, NF125-CV
S Type
NF32-SV, NF63-SV, NF125-SV NF125-SEV, NF125-SGV, NF160-SGV NF250-SV, NF250-SEV, NF250-SGV NF125-LGV, NF160-LGV, NF250-LGV
NF63-HV
AL
AX
AL + AX (*2) SHT or UVT (*1) AL + SHT or UVT (*1) AX + SHT or UVT (*1) (*1) (*3) (*1) (*2)
Remarks: 1. Circled numbers indicate the order of installation. 2. Accessories of EAL, and TBM can be installed independent of installations of AL, AX, and MG (two units among EAL and TBM cannot be installed at the same time).
34
4. Accessories
Internal Accessories
4. Shunt Trip
Table 4-10: Standard coil rating
Series Cut-off switch
(SHT)
Input power requirement (VA) (*1) Voltage 100V 240V AC 380V 550V DC 100V 100-125V Operating time (ms) (*2)
All models
Equipped
120
50
15 or less
Notes: *1 Secure a sufficient input power so that the voltage will not drop below the permissible lower working voltage (70% of the lowest rated voltage). *2 The operating time denotes the time from when the rated voltage is applied to SHT until when the main contact of the breaker starts to open.
5. Undervoltage Trip
Table 4-11: Standard coil rating
Series Voltage 100-130VAC/VDC (*1) All models 200-250VAC 380-480VAC (Compatible to 50 and 60Hz) 5 30 or less Input power VA (*1) (*2)
(UVT)
UVT Voltage Module
Circuit breaker D2
The UVT voltage module is normally installed on the vertical lead-wire terminal unit (SLT) (a separate-mount type can be produced on request).
Notes: *1 The operating time denotes the time from when no voltage is applied to UVT until when the main contact of the breaker starts to open. *2 Time-delayed types can be produced. Details are available on request.
(TBM)
Press the test button on the main body of the breaker while control voltage is applied to test the unit. The voltage must be applied to the main body of the breaker for more than two seconds when testing time-delayed NV models All models have a vertical lead terminal unit (SLT) as standard
18
TBM2 TBM1 87 (Terminal cover) 10.5 (10.5) 7 12.5 Ring-mark example 98/ALa , 96/ALb , 95/ALc C1/S1 , C2/S2
Note: *1 100-240VAC and 100-240VDC specifications are standard unless otherwise specified. Specifications for 24VDC are available on request.
7. Lead-wire Specifications
Table 4-13
Type Heatresistant wire Size Length (*1) 450mm Marking A ring-mark with the terminal symbol is attached to each lead wire 0.5mm2
Note: *1 400mm for models with four poles and right-pole installation.
Lead wires are normally extended laterally Grooves are provided on the side of the breaker for extending lead wires on the side of the breaker
18
(SLT)
86.5 M3.5 M3.5 terminal screw
35
9. Cassette-type Accessories
The cassette-type accessories can be attached to or removed from a circuit breaker by the customer. Table 4-14: Model names of cassette-type accessories
Applicable models Frame size AL AX AL + AX Type of accessories SHT UVTN or UVTS UVTNAD130-05SVR NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV NF125-SGV/LGV/HGV NF125-RGV/UGV NF125-SEV/HEV NF160-SGV/LGV/HGV NF250-CV/SV/HV NF250-SGV/LGV/HGV NF250-RGV/UGV NF250-SEV/HEV 05 AL-05SV AL-05SVLS AL-05SVRS AX-05SV AX-05SVLS AX-05SVRS ALAX-05SV ALAX-05SVLS ALAX-05SVRS SHTA240-05SVR SHTA550-05SVR SHTD125-05SVR SHTA240-05SVRS SHTA550-05SVRS SHTD125-05SVRS UVTNAD130-05SVL UVTNA250-05SVR UVTNA250-05SVL UVTNA480-05SVR UVTNA480-05SVL UVTNAD130-05SVRS UVTNAD130-05SVLS UVTNA250-05SVRS UVTNA250-05SVLS UVTNA480-05SVRS UVTNA480-05SVLS (*1)
UVTSAD130-05SVR UVTSAD130-05SVL UVTSA250-05SVR UVTSA250-05SVL UVTSA480-05SVR UVTSA480-05SVL UVTSAD130-05SVRS UVTSAD130-05SVLS UVTSA250-05SVRS UVTSA250-05SVLS UVTSA480-05SVRS UVTSA480-05SVLS
SHTA240-05SVL NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV NV125-SEV/HEV NV250-CV/SV/HV NV250-SEV/HEV (*3) SHTA550-05SVL SHTD125-05SVL SHTA240-05SVLS SHTA550-05SVLS SHTD125-05SVLS
Notes: *1
UVTN UVTS
SHT
Voltage SHT A240:100-240VAC A440:380-440VAC A550:380-550VAC D100:100VDC D125:100-125VDC
A240
UVTN, UVTS (*1)(*2)
05
SV R S
Installation R: Right-pole installation, 2-pole and 3-pole RF: Right-pole installation, 4-pole L: Left-pole installation Blank: Compatible with both left and right poles
The circuit breaker main body of UVTS can be reset even if not electrically energized. *2 The UVTN is not a cassette accessory. An order for the UVTN should be placed at the same time as an order of circuit breaker main body. *3 Please contact us for 4 pole of NV250-SEV, NV250-HEV. Remarks: 1. Refer to the list of combinations of accessories on page 44 for possible combinations and pole connections. 2. No cassette accessories are available for the corrosion-resistant models of AL and AX. 3. Cassette accessories cannot be mounted on circuit breakers with MG. 4. Cannot be mounted on a built-in circuit breaker with an SLT. 5. The four-pole circuit breakers with a right-pole SLT or UVT have different dimensions and model names. Please contact us for details.
(PAL)
Pre-alarm characteristics
Pre-alarm pick-up current I t =OFF
6
Notes: *1 Control power source of 100 to 200VAC is necessary. *2 In this case, no other accessory can be attached to the right pole.
Pre-alarm pickup current Ip Ir (0.7 0.75 0.8 0.85 0.9 0.95 1.0) 10% Pre-alarm operating time Tp Tp= 60 70 100 125
TL 2
(at 200%)
36
4. Accessories
External Accessories
ON
IP P
ED
Hinge (right)
O FF
R
ET N ES O P E
TR
H Trip button 35
Left hinge L X1 L
* The above drawing shows the layout of the hinge and the circuit breaker when viewed from the load side.
(a) (b) D D (b) (a) C Either M4 0.7 screw or 5 Either M4 0.7 screw or 5
78
78
4-12
(a)
(b)
(c)
Table 4-16
Type names F-05SV2 F-05SV F-05SVE F-1SV2 F-1SVE2 F-1SV F-1SVE
Summary of dimensions
Applicable models NFB Number of poles 2 3/4 2 3/4 2/3/4 NV32-SV NV63-CV, NV63-SV, NV63-HV NV125-CV, NV125-SV, NV125-HV NV Drilling plans Number of poles 2/3 3/4 (b) (a) (c) (a) 105 (b) (a) (c) (a) 104 15 Dimensions (mm) A (*1) B C 12.5 25 111 H D Trip button position H J (a): Breaker mounting screws (2 pcs) (b): Breaker - operating handle mounting screws (2 pcs) F-05SV2, NV125-SEV, NV125-HEV 2/3/4 NV250-CV, NV250-SV, NV250-HV NV250-SEV (*4), NV250-HEV (*4) 3/4 (c) (a) 107 35 126 K F-05SVE2, F-1SV2 and F-1SVE2 use (b) only. Mounting screws
NF32-SV NF32-SV NF63-CV, NF63-SV, NF63-HV NF125-CV, NF125-SV NF125-CV, NF125-SV NF63-HRV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV NF125-LGV, NF125-HGV, NF125-RGV
30
F-2SV F-2SVE
NF160-SGV, NF160-LGV, NF160-HGV NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV NF250-SEV, NF250-HEV, NF250-RGV
Notes: *1 Shows dimensions for front connection types. For rear connection and plug-in types, the reference surface changes. *2 Do not remove the sponge packing installed to ensure protection rating of IP54. Install the packing that comes with the operating handle. *3 Operating the trip button can trip the circuit breaker with the door open (the trip button position differs from one model to another). *4 Please contact us for 4 pole of NV250-SEV, NV250-HEV.
Remarks: 1. Products with E in the model numbers are for emergency stop devices. 2. The standard models have reset-open specifications that allow the door to be opened only when reset (open operation). Products with OFF-open specifications are made on request and allow the door to be opened in the OFF position. 3. Products with the same ON/OFF indication specifications as the standard models are made on request even if the circuit breaker is installed on its side.
37
OFF
TRI
PP
ED
Hinge (left)
R
ET ES
H Trip button
L 0 or more
* The above drawing shows the layout of the hinge and the circuit breaker when viewed from the load side.
Operating handle attached to the panel door and control settings attached to the breaker body
Provides a circuit-disconnecting (isolating) function in combination with the breaker body Conforms to EN safety standards (EN 60204-1) IP65 rating (IEC 60529) Can be locked with a commercial padlock (35mm and 40mm) in the OFF position The panel door can be opened in the OFF position In the ON and TRIP position, the panel door is locked so that it cannot be opened, but the panel door can still be opened in the ON and TRIP positions by pushing the release tab using a tool
(a)
(b)
(c)
(d)
Table 4-17
Type names V-05SV2
Summary of dimensions
Applicable models NFB Number of poles 2 2/3 3 4 2 3 4 2/3 4 2/3 NV32-SV NV63-CV, NV63-SV, NV63-HV NV Drilling plans Number of poles 2/3 3 4 (b) (a) (c) (a) (d) (a) (b) (a) (c) (a) (d) (a) (c) (a) (d) (a) (c) (a) 41 4 (d) (a) 162 300 35 126 K 125 90 30 J 39 15 111 H (b): Breaker operating handle mounting screws and nuts (2 pcs each) V-05SV2, V-05SVE2, V-1SV2 and V-1SVE2 use (b) only with no nuts attached. A B Dimensions (mm) Fixed type Adjustable type (*1) C (min.) C (max.) D E 12.5 Trip button F position H Mounting screws (a): Breaker mounting screws (2 pcs) (4 pcs for 4P)
162
300
25
NF125-CV, NF125-SV NF125-CV, NF125-SV NF63-HRV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV NF125-LGV, NF125-HGV, NF125-RGV
V-1SV V-1SVE
V-2SV V-2SVE
NF160-SGV, NF160-LGV, NF160-HGV NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV NF250-SEV, NF250-HEV, NF250-RGV 4
Notes: *1 For the adjustable type, the dimensions shown above are those when the adjustment unit V-AD3S (separately available) is mounted. *2 Please contact us for 4 pole of NV250-SEV, NV250-HEV.
Remarks: 1. Please contact us regarding applicable models other than those mentioned above. 2. IP65 rating (IEC 60529). 3. Operating the trip button can trip the circuit breaker with the door open (the trip button position differs from one model to another). 4. Products with E in the model numbers are for emergency stop devices.
Adjustable Type
Mounting the separately available adjustment unit V-AD3S to the built-in control settings, enables adjustment of the height between the breaker installation face and the panel door. Cut the shaft of the adjustment unit to fit the height.
Operating section Joint
Shaft
Warning mark
38
4. Accessories
External Accessories
114
Clasp (*1) Center of the circuit breaker operating handle (*3) 17 43.5 4 Clasp (*1) 80
The handle can be locked at either ON or OFF position (three padlocks (40mm) can be installed, OFF-position lock only specifications are also acceptable) Degrees of protection (IEC 60529) IP5X
Remark: 1. Trip action can be displayed when the circuit breaker trips even if ON-position lock is selected (only in the case of a single padlock (35 mm)).
Max. 115
Front plate deviation of 4mm or less 100 or more (210 or more when the hinge is on the left) Front plate thickness 1.23.2
45 34 40 110
Table 4-18
Type names S-05SV
Summary of dimensions
Applicable models NFB NF32-SV, NF63-CV, NF63-SV, NF63-HV, NF50-HRV, NF125-CV, NF125-SV, NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NV NV32-SV, NV63-CV, NV63-SV, NV63-HV, NV125-CV, NV125-SV, NV125-HV Delivery category A (*4) 87
S-2SV
NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV
95
110
112.5
Notes: *1 The clasps are not supplied as standard, and should be prepared by users. Other details such as dimensions are available on request. *2 When the optional clasp is used. *3 The tolerance from the center of 62 is shown. *4 The dimensions of the front-face type are shown. Some of the back-face and plug-in types have a different reference plane for mounting the circuit breaker. *5 Please contact us for 4 pole of NV250-SEV, NV250-HEV.
4. Terminal Cover
Table 4-19
Large terminal cover (TC-L) Small terminal cover (TC-S) Transparent terminal cover (TTC) Rear terminal cover (BTC) Plug-in terminal cover (PTC)
Breaker type
A
B
A
B
A
C
B
A
B
A
C
B
C
(*1) (*2) (*1) (*2)
C
(*1) (*2) (*1) (*2) (*2) (*3) BTC-05SV2 (5065.55) BTC-05SV3 (7565.55) BTC-1SV2 (6065.56.5) BTC-1SV3 (9065.56.5) PTC-05SV2 (5065.55) PTC-05SV3 (7565.55) PTC-1SV2 (6065.56.5) PTC-1SV3 (9065.56.5)
NF32-SV, NF63-CV/SV/HV NF32-SV, NF63-CV/SV/HV, NV32-SV, NV63-HV NV63-CV/SV NF125-CV/SV NF125-CV/SV, NV125-CV/SV/HV NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV, NV250-HEV
2P 3P 2P, 3P 2P 3P 2P, 3P
BTC-2SV3 (10565.56.5)
PTC-2SV3 (10565.56.5)
Notes: *1 Attach the letter F to the end of model names for models with F-type operating handle (Those are F-type operating-handle dedicated models which use screws for fixing). *2 Can be combined with the F-type or V-type operating handle as a standard feature. *3 Available for 200A rating or smaller (maximum wire size of 100mm2). *4 Available for 250A rating or smaller (maximum wire size of 150mm2). Remarks: 1. External dimensions shown in parentheses are in mm and correspond to the figure labels A, B and C in the format (ABC). 2. The wire sizes mentioned in notes (*3) through (*6) refer to 600V polyvinyl chloride wire. 3. Cover the exposed live conductors of crimp terminals with insulation tape.
39
Notes: *1 For other models, please order in conjunction with the circuit breaker. *2 Please contact us for 4 pole of NV250-SEV, NV250-HEV.
24VDC 0.050.1
Compatible with 100-240VAC/100-250VDC 0.6 or less (self-holding) 1.2 or less (self-holding) 150
Panel mounting
MI-05SVFP3
MI-05SVFB3 MI-1SVFB2
MI-05SVFP4
MI-1SVFP3
MI-1SVFB3 MI-2SVFB3
44
70 13 15 33
22
Stroke 1.5
Notes: *1 When the panel plate thickness is 2.3 or more, prepare four holes (5.5 and 9.5 countersunk (rear)). *2 These are standard dimensions for two- and three-pole models, but can be altered on request. *3 The U Series have different dimensions. Please contact us for details. Remarks: 1. Please contact us for external dimensions of other models of different specifications. 2. Not isolation-compatible.
40
4. Accessories
External Accessories
NF32-SV, NF63-CV/SV/HV NV63-CV NF32-SV, NF63-CV/SV/HV, NV32-SV, NV63-SV/HV NF125-CV/SV NF125-CV/SV, NV125-CV/SV/HV NF125-HV NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV, NV125-SEV, NV125-HEV, NV250-CV, NV250-SV, NV250-HV, NV250-SEV (*3), NV250-HEV (*3)
(*1)
HLS-05SV2
CH-P No.5
2P 3P 4P LC-05SV
Notes: *1 HLF types are used for OFF-lock, and HLN types for ON-lock. *2 HL-S types are used for OFF-lock. *3 Please contact us for 4 pole of NV250-SEV, NV250-HEV. Remark: 1. Users are requested to prepare padlocks for HL and HL-S types (25mm padlock for HL, and 35mm padlock for HL-S).
9. Insulating Barrier
The insulating barrier enhances the insulation between the phases of circuit breaker terminals. It also prevents accidents due to conductive foreign matter and dust, and secondary accidents when isolating a fault current.
(1) The insulating barrier is available for the models listed in the table below.
Table 4-25
Applicable models NFB
NF32-SV, NF63-CV, NF125-CV NF63-SV/HV, NF125-SV/HV NF125-SEV/HEV NF125-RV, NF250-CV/SV/HV/SEV/HEV NV32-SV, NV63-CV, NV125-CV NV63-SV/HV NV125-SV/HV NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV
(
NV
denotes optional)
Plug-in
Connection method Front connection Rear connection Standard attachment Standard attachment
Standard attachment
Remark: 1. Always mount the insulating barrier when it comes with the circuit breaker.
41
Summary of dimensions
Applicable models NFB
NF32-SV, NF63-CV, NF125-CV NV32-SV NV63-CV NV125-CV 50 NF63-SV/HV, NF125-SV/HV NV63-SV/HV NV125-SV/HV 59.5 1 (*1) 2 3
B
NV
Reference diagram
BAF-05SV
Standard attachment
BAF-2SV
NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NV125-SEV/HEV Standard NF160-SGV, NF160-LGV, NV250-CV/SV/HV/SEV/HEV attachment NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV
100
59.5
Summary of dimensions
Applicable models NFB NV Delivery Dimensions (mm) Quantity per breaker category A B 2P 3P 4P Reference diagram
NF125-SEV, NF125-HEV, NF125-SGV, NF125-LGV, NF125-HGV, NF125-RGV, NF160-SGV, NF160-LGV, BAP-2SV NF160-HGV, NF250-CV, NF250-SV, NF250-HV, NF250-SGV, NF250-LGV, NF250-HGV, NF250-SEV, NF250-HEV, NF250-RGV
B
NV125-SEV/HEV
172
74.5
42
690V 500V Rated 440V short-circuit IEC 60947-2 415V AC breaking (Icu/Ics) 400V capacity 380V (kA) 230V DC 250V (*1) Standard attached parts (front connection)
NF32-SV 3 4 (5) 6 10 (15) 16 20 25 (30) 32 2 3 600 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 2.5/2.5
NF63-CV NF63-SV NF63-HV 3 4 (5) 6 10 (15) 3 4 (5) 6 10 (15) 10 (15) 16 20 25 16 20 25 (30) 32 16 20 25 (30) 32 (30) 32 40 50 40 50 (60) 63 40 50 (60) 63 (60) 63 2 3 2 3 4 2 3 4 600 600 690 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 2.5/2.5 7.5/7.5 10/8 2.5/2.5 7.5/7.5 10/8 5/5 7.5/7.5 10/8 5/5 7.5/7.5 10/8 7.5/7.5 15/15 25/19 2.5/2.5 7.5/7.5 7.5/7.5 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) (*2)
Notes: *1 Use two poles for three- and four-pole products. Not available for use with connection as shown at the bottom of page 13. *2 Supplied with NF63-SV and NF63-HV.
NF63-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s AC 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip DC Min. Max. Operating characteristics NF32-SV 3A~6A NF63-CV 3A~6A NF63-SV 3A~6A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s DC 0.02s Time-delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 Instantaneous trip 30 40 50 60 70 100 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip AC Min. Max. Instantaneous trip current is fixed to AC600A120A and DC850A170A. Operating time Operating characteristics NF32-SV 10A~32A NF63-CV 10A~32A NF63-SV 10A~32A NF63-HV 10A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s AC 0.2s 0.1s 0.05s DC Operating characteristics NF63-CV 40A~63A NF63-SV 40A~63A NF63-HV 40A~63A
Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT
Right-side mounting
2-pole
3, 4-pole
10
20
30
40
130
60
External Accessories
Accessories Type name Reference page Accessories Mechanical interlock
2P 3, 4P 2P 3, 4P
HL HL-S
37 38 39 41
MI TC-S
Small
2, 3P 4P 2P 3P 2P
Large
Terminal cover
TC-L
3P
Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.
4P 2P 3P 2P BTC Rear 3P 2P PTC Plug-in 3P IEC 35mm rail mounting adapters Skeleton TTC
Type name MI-05SV3 MI-05SV4 TCS-05SV2 TCS-05SV3 TCL-05SV2 TCL-05SV2L TCL-05SV3 TCL-05SV3L TCL-05SV4 TTC-05SV2 TTC-05SV3 BTC-05SV2 BTC-05SV3 PTC-05SV2 PTC-05SV3 DIN-05SV
Reference page
40
39
41
43
Front connection
Insulation barrier (removable) Mounting hole 50 24 Applicable wire size: 2 1.6 to 22mm (for M50.8 screw) 4.5 111 5.5 (8.5 for 60A and 63A) 8 25 12.5 max. (16 max. for 60A and 63A) (Conductor thickness t = 5 max.) 25 84 50 M50.8 screw (M8 for 60A and 63A) M40.7 taps or 5 Breaker
112
130
2-pole
3-pole
4-pole
2-pole
3-pole
4-pole
Drilling plan
Rear connection
2-pole Mounting plate t = 3.2 max. Insulation tube 42 (44 for 60A and 63A) 27 min. (29 min. for 60A and 63A) 112 8 M40.7 taps or 5 Breaker 4-pole 3-pole Breaker
111
112
R1
M6 screw 27 min. 68 72 42 (46 for 60A and 63A) (31 min. for 60A and 63A)
50
25 25 75 50 70
22.5
2-pole
3-pole
Drilling plan
Plug-in
3-pole
Mounting plate Plug-in terminal block M50.8 Terminal block mounting screw 80 50
4-pole
105 Breaker (plug-in terminal block) 75 25 54
83.5
170
116
11 5.5
85
M6 screw 21
Details of terminal
89
30
2-pole
Conductor drilling
2-pole
3-pole
4-pole
Drilling plan
Remark: 1. Only two- and three-pole models are available for NF32-SV and NF63-CV.
54
80
52
44
690V 500V Rated 440V short-circuit IEC 60947-2 AC 415V breaking (Icu/Ics) 400V capacity 380V (kA) 230V DC 250V (*1) Standard attached parts (front connection)
NF125-SV NF125-HV (15) 16 20 (30) 32 (15) 16 20 (30) 32 50 (60) 63 (75) 80 40 50 (60) 63 (75) 40 50 (60) 63 (75) 100 125 80 100 125 80 100 125 2 3 2 3 4 2 3 4 600 690 690 8/8 10/8 7.5/4 18/18 30/23 10/5 25/25 50/38 10/5 30/30 50/38 10/5 30/30 50/38 10/5 30/30 50/38 30/15 50/50 100/75 7.5/4 40/40 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) (*2) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs)
NF125-CV
Notes: *1 Use two poles for three- and four-pole products. If wired as shown at the bottom on page 13, three and four poles can be used for up to 400 and 500VDC, respectively. *2 Supplied with NF125-SV and NF125-HV.
NF125-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 6070 Time-delay trip AC DC Instantaneous trip Min. Max. Operating characteristics NF125-SV 15A~32A NF125-HV 15A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to AC600A120A and DC850A170A. Operating time 2min 1min Operating time 30s 20s 10s 5s Min. 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 DC 0.2s 0.1s 0.05s 0.02s Time-delay trip Instantaneous trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time-delay trip Instantaneous trip 2s 1s 0.5s AC DC Operating characteristics NF125-CV 50A~100A NF125-SV 40A~100A NF125-HV 40A~100A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. Operating characteristics NF125-CV 125A NF125-SV 125A NF125-HV 125A
Max.
Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT
Right-side mounting
2-pole
3, 4-pole
10
20
30
40
130
60
External Accessories
Accessories Type name Reference page Accessories Mechanical interlock Type name Reference page
2P 3, 4P 2P 3, 4P
HL HL-S
37 38 39
Small Large
41
Terminal cover
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF125-CV/SV.
2, 3P 4P 2P 3P 2P 3P 4P 2P 3P 2P 3P 2P 3P
MI-05SV3 MI-05SV4 TCS-1SV2 TCS-1SV3 TCL-1SV2 TCL-1SV3 TCL-1SV4 TTC-1SV2 TTC-1SV3 BTC-1SV2 BTC-1SV3 PTC-1SV2 PTC-1SV3 (*2)
40
39
40
45
Front connection
Insulation barrier (removable) M8 screw 50 24
Mounting hole
Breaker
112
130
84
50
4.5
Wire connection
8.5 8
8.5
Trip button 30 60 22 60 90
30
30 M40.7 taps or 5
72 90
2-pole
3-pole
4-pole
2-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole Insulation tube Mounting plate t = 3.2 max. 102 52 Stud can be rotated 90 3-pole 2-pole Breaker 2-pole 4-pole 3-pole Breaker
111
112
R1
R1
16
15 connection allowance
112
30 30 8.5 2.5 15 68 72 54.5 104.5 M8 bolt 2.5 15 Insulation tube 5 60 90 M40.7 breaker mounting screw 30 60 M40.7 taps or 5 18 30 90 57 86
28
2-pole
3-pole
4-pole
Drilling plan
Front-panel cutout
Plug-in
3-pole
Mounting plate Plug-in terminal block M50.8 Terminal block mounting nut or screw mounted directly 95 60
4-pole
125 90 30 56 Breaker (plug-in terminal block)
83.5
170
116
54
12
5.5
85
20 max. 56 67 97 127
21 89 30
M8 screw
3-pole
4-pole
Details of terminal
2-pole
Drilling plan
Remarks: 1. The two-pole models of NF125-HV are three-pole models with the central pole removed. 2. Only two- and three-pole models are available for NF125-CV.
80
11
52
111
46
DC (*1)
Standard attached parts (front connection)
NF250-SV NF250-HV NF250-CV (*1) (100) (*1) (100) 125 150 160 175 125 150 160 175 125 150 175 200 200 225 250 200 225 250 225 250 2 3 4 2 3 4 2 3 690 690 600 8/8 10/8 30/30 50/38 10/8 36/36 65/65 15/12 36/36 70/70 25/19 36/36 75/75 25/19 36/36 75/75 25/19 85/85 100/100 36/27 20/20 (300V) 40/40 (300V) 15/12 Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Note: *1 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown at the bottom of page 13, three-pole NF250-CV can be used for up to 400VDC, three-pole NF250-SV and NF250-HV up to 500VD and four-pole products up to 600VDC.
NF250-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 AC DC Min. Operating time Operating characteristics NF250-CV 100A~225A NF250-SV 100A~225A NF250-HV 125A~225A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 15 Instantaneous trip 20 30 40 AC DC Min. Operating characteristics NF250-CV 250A NF250-SV 250A NF250-HV 250A
Max.
Max.
Internal Accessories
Lead-wire direction
AL
AX
SHT or UVT
130
Right-side mounting
10
20
30
40
60
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
2, 3P 4P 2, 3P 2, 3P 4P 2, 3P 2, 3P 2, 3P
41
Terminal cover
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF250-CV/SV.
MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)
40
39
40
47
Front connection
M8 bolt (hex-socket) 100
30
Mounting hole
24
Breaker
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
144
165
102
4.5
C 1
8.5
100
Trip button
22 70 105 35
25 max.
45 61
Or
8
10
35
.5
35
Neutral pole
105 140 4
68 72 92
M40.7 taps or 5
25 max.
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
Insulation tube Mounting plate t = 3.2 max. Stud can be rotated 90
4-pole 3-pole 4-pole 3-pole
Breaker
Breaker
144
126
144
20
22
Connection allowance
35 35 105 100
32.5
Insulation tube
70
M40.7 taps or 5
4-pole
Front-panel cutout
Plug-in
4-pole 145
Mounting plate
34.5
3-pole 110
190
165
24
144
70
11
151
54
28
15
20 9 M8 bolt 3-pole 70 70 107 Stud attachable in this direction only 105 142
21 31 89 112 30
Insulation barrier
4-pole
Remarks: 1. two-pole models are three-pole models with the central pole removed. 2. Only two- and three-pole models are available for NF250-CV.
56.5
80
56.5
Connection allowance
52
126
50
8 .
5
1 C
48
AC
DC (*1)
Standard attached parts (front connection)
Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs) NF125-HGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 56-80, 70-100, 90-125 2 690V 500V 440V 415V 400V 380V 230V 200V 300V 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF160-HGV 125-160 2 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF250-HGV 125-160 140-200 175-250 2 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 4 NF125-RGV 16-20, 20-25, 25-32 32-40, 40-50, 50-63 63-80, 80-100, 100-125 2 3 690 125/125 150/150 150/150 150/150 150/150 150/150 NF250-RGV 125-160 160-200 200-250 2 3 690 125/125 150/150 150/150 150/150 150/150 150/150
Type name Rated current In (A) Number of poles Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF250-SGV
AC
DC (*1)
Standard attached parts (front connection)
Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Note: *1 When wired as shown at the bottom of page 13, three-pole models can be used for up to 500VDC, and 4-pole models for up to 600VDC.
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 15 20 Current( 100% of Ir) Instantaneous tripping current( 100% of In) Instantaneous trip 30 40 50 6070 AC DC Max. Max. total breaking time
Operating Characteristics Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV NF125-RGV Current setting Ir = 16-20A(Rated current In=20A) Current setting Ir = 20-25A(Rated current In=25A) Current setting Ir = 25-32A(Rated current In=32A)
lnstantaneous trip current AC DC 600A 120A 850A 170A
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Current( 100% of Ir) Instantaneous tripping current( 100% of In) Instantaneous trip 15 20 30 40 DC Min. Max. total breaking time Max.
Operating Characteristics Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 35-50A(Rated current In=50A) NF125-RGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 40-50A(Rated current In=50A)
lnstantaneous trip current AC DC 600A 120A 850A 170A
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 DC Max. total breaking time Min.
Operating Characteristic Curves Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 45- 63A(Rated current In= 63A) Current setting Ir = 56- 80A(Rated current In= 80A) NF125-RGV Current setting Ir = 50- 63A(Rated current In= 63A) Current setting Ir = 63- 80A(Rated current In= 80A)
lnstantaneous trip current ratio AC DC xln(%) xln(%) 1000 200 1300 260
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s Min.
Max.
Operating Characteristic Curves Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 70-100A(Rated current In=100A) Current setting Ir = 90-125A(Rated current In=125A) NF160-SGV NF160-LGV NF160-HGV Current setting Ir = 125-160A(Rated current In=160A) NF250-SGV NF250-LGV NF250-HGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 140-200A(Rated current In=200A) Current setting Ir = 175-250A(Rated current In=250A) NF125-RGV Current setting Ir = 80-100A(Rated current In=100A) Current setting Ir = 100-125A(Rated current In=125A) NF250-RGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 160-200A(Rated current In=200A) Current setting Ir = 200-250A(Rated current In=250A)
Max.
lnstantaneous trip current ratio AC DC xln(%) xln(%) 1000 200 1300 260
Instantaneous trip 15 20 30 40
Internal Accessories
Right-side mounting Operating handle Left-side mounting
AL
AX
SHT or UVT
Lead-wire direction
40
50
60
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
2, 3P 4P 2, 3P 2, 3P 4P 2, 3P 2, 3P 2, 3P
41
Terminal cover
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name. *3 Available for NF250-CV/SV.
MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)
40
39
40
49
Front connection
Insulating barrier (removable) 100 Mounting hole
30
M8 bolt (hex-socket)
24 Breaker
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
144
165
102
4.5
8.5
100
Trip button
25 max.
45
Or
10
35
35
22 70 105
61
68 72 92
8.5
M40.7 taps or 5
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole
Insulating tube
4-pole 3-pole
3-pole
Breaker
Breaker
144
126
144
20
22
Connection allowance
24
70 105
35 35 105 100
32.5
9 M8 bolt
Insulating tube
35 70
M40.7 taps or 5
3-pole
4-pole
Drilling plan
Front-panel cutout
Plug-in
24 connection allowance 4-pole 145 3-pole 110
Breaker (plug-in terminal block)
Mounting plate
34.5
190
165
144
70
11
151
54
28
15
20
21 31 89 112 30
70 107
105 142
3-pole
4-pole
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
56.5
80
56.5
52
126
C 1
50
.5
50
NF125-SEV 16-32 32-63 63-125 3 690V 500V 440V 415V 400V 380V 230V 250V 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85
NF125-HEV 16-32 32-63 63-125 3 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100
NF250-SEV 80-160 125-250 3 690 8/8 30/30 36/36 36/36 36/36 36/36 85/85
DC
Standard attached parts (front connection)
Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
NF125-SEV
Operating Characteristics
10h 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 0.6 0.7 1 1.25 2 I t OFF
2
10h Operating characteristics NF125-SEV NF125-HEV Current setting Ir 16-32 32-63 63-125 Rated current In 32A 63A 125A 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min I t ON I t OFF STD pickup current Is Ir (22.533.54 567810) 15%
6 6
Operating characteristics NF250-SEV NF250-HEV Current setting Ir 80-160 125-250 Rated current In 160A 250A
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
I t ON I t OFF
6
STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In 2~14 15%, Ir 14 15% 3 4 5 6 7 10
2
STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In 2~14 15%, Ir 14 15% 2 3 4 5 6 7 10
2
0.10.03s
0.10.03s
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
Internal Accessories
AL
AX
SHT or UVT
Lead-wire direction
Right-side mounting
PAL
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40 C.
(Note)
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
3P 4P 3P 3P 4P 3P 3P 3P
41
Terminal cover
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)
40
39
40
51
Front connection
30
M8 bolt (hex-socket)
24
Mounting hole
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
Breaker
Trip button
8 .5
144
165
102
10
4.5
25 max.
8.5
100
45 61
Or 8.5
35
35
Neutral pole
105 140 4
68 72 92
25 max.
M40.7 taps or 5
3-pole
(Conductor thickness t = 7 max.)
4-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole
Insulation tube
4-pole
3-pole
Breaker
3-pole
Breaker
144
126
144
20
22 connection allowance
15 15 68 72 71 106 9 M8 bolt
6 70 105
24
35 35 105 100
32.5
Insulation tube
70
M40.7 taps or 5
3-pole
4-pole
Drilling plan
Front-panel cutout
Plug-in
24 connection allowance 4-pole 145 3-pole 110
Mounting plate
34.5
190
165
54
70
11
144
151
28
15
20 9 M8 bolt 70 107
Stud attachable in this direction only
21 31 89 112 30
105 142
3-pole 70
Insulation barrier
3-pole
4-pole
Drilling plan
Remark: 1. Products with data parenthesized come with PAL; built-in models with PAL have different external dimensions from the standard models.
56.5
80
56.5
52
126
50
C 1
52
AC
Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs) M40.773 (2 and 3P: 2pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
NF250-UGV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 100% of rated current Instantaneous trip current 600A 120A(AC) 850A 170A(DC) Instantaneous trip 15 20 30 40 50 6070 AC Max. total breaking time Max. Operating time
Operating characteristics Thermal-adjustable types NF125-UGV 16A-20A(rated current In= 20A) 20A-25A(rated current In= 25A) 25A-32A(rated current In= 32A)
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Min. Max. total breaking time Max. Operating time
Operating characteristics Thermal-adjustable types NF125-UGV 32A-40A(rated current In= 40A) 40A-50A(rated current In= 50A)
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Max. total breaking time Min. Max.
Operating characteristic curves Thermal-adjustable types NF125-UGV 50A-63A(rated current In= 63A) 63A-80A(rated current In= 80A)
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s AC 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 Time-delay trip 2 3 4 5 6 7 10 Instantaneous trip 15 20 30 40 Max. total breaking time Min. Max.
Operating characteristic curves Thermal-adjustable types NF125-UGV 80A-100A(rated current In=100A) 100A-125A(rated current In=125A) NF250-UGV 125A-160A(rated current In=160A) 160A-200A(rated current In=200A) 175A-225A(rated current In=225A)
100% of rated current Instantaneous trip current 600A 120A(AC) 850A 170A(DC)
Internal Accessories
Operating handle Right-side AL mounting
SHT or UVT
Left-side mounting
130
AX
40
50
60
53
Front connection
Mounting hole
100
M8 bolt (hex-socket)
24
Breaker
Solderless terminal for wire size 125~175A 14~95mm2 200~250A 70~125mm2 Wire connection
201
75
219
240
75
102
165
165
50
4.5
8.5 10
100
8.5
45 61
Trip button
22 70 105 35
35
35
Neutral pole
105 140 4 68 72 92
M40.7 taps or 5
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole
Insulation tube
3-pole
Breaker
Breaker
Connection allowance 22
219
20
R1
15 15 68 72 71 106 9 M8 bolt
6 70 105
24
35 35
32.5 100
Insulation tube
70
M40.7 taps or 5
105
4-pole
Front-panel cutout
Plug-in
Mounting plate
34.5
24 Connection allowance
110
219
265
70
11 6
151
129
15
20 70 9 M8 bolt
Stud attachable in this direction only
28
21 31 89 30
70 107
Insulation barrier
6 hole or M5 screw
105
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
56.5
155
52
54
NV63-CV
NV63-SV
NV63-HV
(5) (10) (15) 16 20 25 (5) (10) (15) 16 20 25 (15) 16 20 25 (30) (30) 32 40 50 (60) 63 (30) 32 40 50 (60) 63 32 40 50 (60) 63 2 12W 100-240 3 33W, 12W 2 12W 3 33W, 12W 3 33W, 12W
100-440 100-440 100-240 100-440 15 30 (15) 30 (15) 30 100/200/ 100/200/ (15) Rated current sensitivity (mA) 30 100/200/ 500 500 30 500 selectable High-speed type selectable selectable 0.1 0.1 0.1 0.1 at In Max operating time (s) 0.04 0.04 0.04 0.04 at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) 440V 5/5 2.5/2.5 7.5/7.5 10/8 Rated 415V 5/5 2.5/2.5 7.5/7.5 10/8 short-circuit 400V 5/5 5/5 7.5/7.5 10/8 IEC 60947-2 AC breaking 230V 10/10 7.5/7.5 15/15 25/19 (Icu/Ics) capacity (kA) 200V 10/10 7.5/7.5 15/15 25/19 100V 10/10 7.5/7.5 15/15 25/19 Mounting screw: M40.755 (2pcs) (*1) Insulation barrier: (2P: 1pc, 3P: 2pcs) Standard attached parts (front connection) (15) 30 100/200/ 500 selectable
NV63-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time delay trip Instantaneous trip Min. Max. Operating characteristics NV32-SV 6A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 Instantaneous trip 30 40 50 60 70 100 Min. Max. Instantaneous trip current is fixed to 600A120A. Operating time Operating characteristics NV32-SV 10A~32A NV63-CV 16A~32A NV63-SV 16A~32A NV63-HV 16A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Max. (60A~63A) Max. (40A~50A) Operating characteristics NV63-CV 40A~63A NV63-SV 40A~63A NV63-HV 40A~63A
Instantaneous trip
Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT
0.5s 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000
Line side
ZCT
10
20
30
40
50
60
Magnetic device
Senstivity selector
External Accessories
Operating handle
Accessories F V S LC
(*1)
Type name
HL HL-S
Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.
Reference page Accessories 37 Mechanical interlock MI 38 TC-S Small 39 Large TC-L Terminal Skeleton TTC cover 41 BTC Rear Plug-in PTC IEC 35mm rail mounting adapters
Type name MI-05SV3 TCS-05SV3 TCL-05SV3 TCL-05SV3L TTC-05SV3 BTC-05SV3 PTC-05SV3 DIN-05SV
Reference page 40
39
41
55
Front connection
Sensitivity current selector 130 112 4.5 Leakage indication button Test button Trip button 22 50 75 4 8.5 45 61 68 72 90 12.5 max. (16 max. for 60A and 63A) (Conductor thickness t = 5 max.) 25 111 5.5 (8.5 for 60 and 63A) 8 84 50
Drilling plan
Rear connection
Insulation tube
112
111
112
R1
50 27 min. 68 72 42 M6 screw
M40.7 breaker mounting screw 14 25 50 70 1.0mm clearance on each side of the handle frame
Drilling plan
Front-panel cutout
Plug-in
Mounting plate Plug-in terminal block M50.8 terminal block mounting screw 80 50 Breaker (plug-in terminal block)
83.5
170
116
11
5.5
85
21 89 30
M6 screw
Details of terminal
Conductor drilling
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
54
80
54
52
56
NV125-CV (60) 63 (75) 80 100 125 3 33W, 12W AC 100-440 (15) 30 100/200/ 500 selectable
NV125-SV (15) 16 20 30 32 40 50 (60) 63 (75) 80 100 125 3 33W, 12W 100-440 4 34W 200-440
NV125-HV (15) 16 20 (30) 32 40 50 (60) 63 75 80 100 125 3 33W, 12W 100-440 4 34W 200-440
Rated current sensitivity (mA) High-speed type at In at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system 440V Rated 415V short-circuit IEC 60947-2 400V AC breaking (Icu/Ics) 230V capacity (kA) 200V 100V Standard attached parts (front connection) Max operating time (s)
30 100/200/500 selectable
0.1 0.1 0.1 0.04 0.04 0.04 (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) Mechanical type (button) 50/38 10/5 25/25 50/38 10/5 30/30 50/38 10/5 30/30 100/75 30/15 50/50 100/75 30/15 50/50 100/75 30/15 50/50 Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) (*1) Insulation barrier: (3P: 2pcs, 4P: 3pcs)
NV125-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 60 70 Time delay trip Instantaneous trip Min. Max. Operating characteristics NV125-SV 15A~30A NV125-HV 15A~30A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to 600A120A. Operating time 2min 1min Operating time 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Instantaneous trip 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 Time delay trip Instantaneous trip Operating characteristics NV125-CV 60A~100A NV125-SV 40A~100A NV125-HV 40A~100A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Min. Operating characteristics NV125-CV 125A NV125-SV 125A NV125-HV 125A
Max.
Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT
1s Inertial operating time 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 Inertial operating time
0.5s
ZCT
10
20
30
40
50
60
Magnetic device
Senstivity selector
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
3P 4P 3P 4P
41
Terminal
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
Skeleton TTC cover Rear BTC Plug-in PTC Electrical operation device
40
39
40
57
Front connection
Solderless terminal for wire size
Mounting hole 50
Insulation barrier (removable) M8 screw Operating time selector (for time-delay type) Sensitivity current selector Leakage indication button Test button 50 24
14~2/0AWG CU/AL
Breaker
Wire connection
130
112
112
130
4.5
8.5 8
8.5
Trip button
22 60 90
30
30 M40.7 taps or 5
72 90
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole Insulation tube Mounting plate t = 3.2 max. 102 52 Stud can be rotated 90 111 112 3-pole Breaker
R1
16
15 connection allowance
112
30 M40.7 breaker mounting screw 60 2.5 15 Insulating tube 90 8.5 30 60 18 30 90 M40.7 taps or 5 86
28
M8 bolt 2.5 15
68 72
54.5 104.5
Plug-in
3-pole
Mounting plate Plug-in terminal block M50.8 terminal block mounting nut or screw mounted directly 95 60
4-pole
125 90 30 54 Breaker (plug-in terminal block)
83.5
170
116
54 20 max. 12
5.5
85
21 89 30
M8 screw
8.5
97
127
Details of terminal
Conductor drilling
3-pole
Note: *1 Products with data parenthesized come with EAL or TBM; built-in models with EAL or TBM have different external dimensions from the standard models. Remark: 1. Only three-pole models are available for NV125-CV.
54
80
11
52
111
84
50
58
NV250-CV 125 150 175 200 225 250 3 33W, 12W AC 100-440 30 100/200/500 selectable 3
Rated current sensitivity (mA) High-speed type at In at 5In Rated current sensitivity (mA) Time-delay type Max operating time (s) Inertial operating time (s) (or more) Earth-leakage indication system 440V Rated 415V short-circuit IEC 60947-2 400V AC breaking (Icu/Ics) 230V capacity (kA) 200V 100V Standard attached parts (front connection) Max operating time (s)
0.1 0.1 0.1 0.04 0.04 0.04 (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) Mechanical type (button) 65/65 15/12 36/36 70/70 25/19 36/36 75/75 25/19 36/36 100/100 36/27 85/85 100/100 36/27 85/85 85/85 100/100 36/27 Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
NV250-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Operating time Operating characteristics NV250-CV 125A~225A NV250-SV 125A~225A NV250-HV 125A~225A 4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating characteristics NV250-CV 250A NV250-SV 250A NV250-HV 250A
4h 2h 1h 30min High-speed type Time-delay type 0.45s (MAX) Time-delay type 1s (MAX) Time-delay type 2s (MAX)
Max.
Max.
10min Rated non-operating current Rated non-operating current Rated non-operating current Rated non-operating current Rated current sensitivity Rated current sensitivity Rated current sensitivity 4min 2min Rated current sensitivity Inertial operating time 0.2s Inertial operating time 0.1s 0.05s 0.04s 0.02s 0.01s 500 1000
Operating time
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
25 50 100
Internal Accessories
Operating handle Left-side mounting Right-side mounting AL AX
SHT or UVT
TBM
ZCT
Magnetic device
0 10 20 30 40 50 60
Senstivity selector
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
3P 4P 3P 3P 4P 3P 3P 3P
41
Terminal cover
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
40
39
40
59
Front connection
Insulation barrier (removable) Mounting hole Operating time selector (for time-delay type) Sensitivity current selector 144 165 165 144 Leakage indication button Test button 100 8.5 45 61 Neutral pole 4 140 68 72 92
25 max. (Conductor thickness t = 7 max.)
30
M8 bolt (hex-socket)
24
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
8 .5
Breaker
100
100
102
10
4.5
25 max. Or
8 .5
Trip button
35 M40.7 taps or 5
35
22 70 105
35 105
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
Insulation tube Mounting plate t = 3.2 max. Stud can be rotated 90 4-pole Breaker 3-pole 4-pole 3-pole Breaker
144
126
144
22 connection allowance
20
24 M40.7 taps or 5
35 35 105 100
32.5
Plug-in
24 connection allowance
34.5
Mounting plate
190
165
144
54
70
11
151
28
15
21 31 89 112 30
105 142
Insulation barrier
4-pole
Note: *1 Products with data parenthesized come with EAL or TBM. Built-in models with EAL or TBM have different external dimensions from the standard models. Remark: 1. Only three-pole models are available for the model of NV250-CV and NV250-HV.
56.5
80
56.5
52
126
50
C 1
60
440 100-440
440 100-440
Rated current sensitivity (mA) High-speed type Max operating time (s)
(30) (30) (30) (30) 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable
0.1 0.1 0.1 0.1 at In 0.04 0.04 0.04 0.04 at 5In Rated current sensitivity (mA) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) (0.45/1.0/2.0 selectable) Time-delay type Max operating time (s) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) (0.1/0.5/1.0) Inertial operating time (s) (or more) Earth-leakage indication system Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button) 36/36 65/65 36/36 65/65 440V Rated 36/36 70/70 36/36 70/70 415V short-circuit IEC 60947-2 36/36 75/75 36/36 75/75 400V AC breaking (Icu/Ics) 85/85 100/100 85/85 100/100 230V capacity (kA) 85/85 100/100 85/85 100/100 200V 85/85 100/100 85/85 100/100 100V Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs) Standard attached parts (front connection)
NV250-SEV
Operating Characteristics
10h 5h 2h 1h 30min 20min 14min 10min 6min 4min 2min Operating time Operating time 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 0.6 0.7 1 1.25 2 3 4 5 6 7 10 I t OFF
2
Operating characteristics NV125-SEV NV125-HEV Current setting Ir Rated current In 63-125 125A LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set) LTD operating time TL 126080100s 20% (at 200%)
6
Operating characteristics NV250-SEV NV250-HEV Current setting Ir Rated current In 250A 125-250
4h 2h 1h 30min 10min Rated non-operating current Rated non-operating current Rated non-operating current Rated non-operating current Rated current sensitivity Rated current sensitivity Rated current sensitivity 4min 2min 1min Operating time 30s 10s 5s 2s 1s 0.5s Inertial operating time 0.2s 0.1s 0.05s 0.04s 0.02s 0.01s 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 25 50 100 500 1000 Inertial operating time Rated current sensitivity High-speed type Time-delay type 0.45s (MAX) Time-delay type 1s (MAX) Time-delay type 2s (MAX)
I t ON I t OFF
6
I t ON I t OFF
6
STD operating time Ts 0.30.06s 0.20.04s I t ON INST pickup current Ii In2~14 15%, Ir14 15%
2
STD operating time Ts 0.3 0.06s 0.2 0.04s I t ON INST pickup current Ii In2~14 15%, Ir14 15% 2 3 4 5 6 7 10
2
0.10.03s
0.1 0.03s
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
Internal Accessories
AL
AX
SHT or UVT
Lead-wire direction
130
Test button
Rated ambient temperature
Characteristic setting part
TBM
PAL
Current rating (%)
120 110 100 90 80
Magnetic device
CT CT CT Senstivity selector
(Note *1)
(Note *2)
70 10
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40C.
0 10 20 30 40 50 60
Notes: *1 For the 24VDC TBM only instruct us of a control voltage. (The standard shared voltage is 100-240VAC/100-240VDC.) *2 SLT equipped is standard. Control voltage (100-200VAC) is necessary.
Magnetic device
External Accessories
Accessories F Operating handle V S LC Type name
(*1)
HL HL-S
Type name
Reference page
3P 4P 3P 3P 4P 3P 3P 3P
41
Terminal cover
Large
TC-L
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
40
39
40
61
Load side
Line side
ZCT
Front connection
Solderless terminal for wire size 125 175A 14 95mm2 200 250A 70 125mm2 Wire connection
30
Insulation barrier (removable) Mounting hole Operating time selector (for time-delay type) Sensitivity current selector Leakage indication button Test button Trip characteristics selector Trip button
22 70 105 35 105 140 100 100
M8 bolt (hex-socket)
24
Breaker
8 .
C 1
5
10
165
144
144
165
102
4.5
25 max. Or
100
8.5
45 61
.5
35
35
Neutral pole
4
68 72 92
M40.7 taps or 5
3-pole
4-pole
3-pole
4-pole
Drilling plan
Rear connection
4-pole
Insulation tube
4-pole
3-pole
Breaker
3-pole
Breaker
144
126
144
20
22 connection allowance
15 15 68 72 71 106 9 M8 bolt
6 70 105
24
35 35 105 100
32.5
Insulation tube
70
M40.7 taps or 5
3-pole
4-pole
Drilling plan
Front-panel cutout
Plug-in
24 connection allowance 4-pole 145 3-pole 110
Mounting plate
34.5
190
165
144
54
70
11
151
28
15
21 31 89 112 30
105 142
3-pole
4-pole
Drilling plan
Note: *1 Products with data parenthesized come with PAL, EAL or TBM. Built-in models with PAL, EAL or TBM have different external dimensions from the standard models.
56.5
80
56.5
52
126
50
1 C
62
Specify MB
NF63-SV 4 5 7.1 8 10 12 16 25 32 40 45
3 3 3 600 600 600 2.5/2.5 2.5/2.5 7.5/7.5 2.5/2.5 2.5/2.5 7.5/7.5 5/5 5/5 7.5/7.5 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 2.5/2.5 2.5/2.5 7.5/7.5 5/5 5/5 7.5/7.5 5/5 5/5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 2.5/2.5 2.5/2.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 Mounting screw: M40.755 (3P: 2pcs) (*2) Insulation barrier: (3P: 2pcs)
Notes: *1 Refer to page 64 for the external dimensions. *2 Supplied with NF63-SV.
NF63-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 Time-delay trip 3 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Max.(4A~5A) Operating time Max.(7.1A~8A) Operating characteristics NF32-SV 4A~8A NF63-CV 4A~8A NF63-SV 4A~8A
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s Instantaneous trip Instantaneous trip current is fixed to 600A120A. Operating time Operating characteristics NF32-SV 10A~32A NF63-CV 10A~32A NF63-SV 10A~32A
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min 30s 20s 10s 5s Operating characteristics NF63-CV 40A~45A NF63-SV 40A~45A
Max.(40A~45A)
Max.
Min.
Min.
2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s 100 1 1.25 Instantaneous trip
1 1.25
5 6 7
10
15
20
30
40 50 60 70
5 6 7
10
15
20
30
40
Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT
130
Right-side mounting
60
External Accessories
Accessories Type name Reference page Accessories Mechanical interlock
2P 3, 4P 2P 3, 4P
HL HL-S
37 38 39 41
MI TC-S
Small
2, 3P 4P 2P 3P 2P
Large
Terminal cover
TC-L
3P
Note: *1 HLF types are used for OFF-lock and HLN types for ON-lock.
4P 2P 3P 2P BTC Rear 3P 2P PTC Plug-in 3P IEC 35mm rail mounting adapters Skeleton TTC
Type name MI-05SV3 MI-05SV4 TCS-05SV2 TCS-05SV3 TCL-05SV2 TCL-05SV2L TCL-05SV3 TCL-05SV3L TCL-05SV4 TTC-05SV2 TTC-05SV3 BTC-05SV2 BTC-05SV3 PTC-05SV2 PTC-05SV3 DIN-05SV
Reference page
40
39
41
63
NF125-SV
Rated short-circuit breaking capacity (kA)
Type name Rated current In (Amp.) Number of poles Rated insulation voltage Ui (V) Rated operational voltage Ue (V) AC JIS C 8201-2-1 Ann.1 440V JIS C 8201-2-1 Ann.2 415V IEC 60947-2 AC 400V EN 60947-2 380V (Icu/Ics) 230V 415V GB 14048.2 400V AC (Icu/Ics) 380V 230V NK 450V AC (Icu/Ics) 240V Standard attached parts (front connection)
NF125-SV (12.5) (16) (25) 32 (40) 45 63 71 90 100 3 690 230, 380/440 25/25 30/30 30/30 30/30 50/50 30/30 30/30 30/30 50/50 25/25 50/50 Mounting screw: M40.755 (3P: 2pcs) Insulation barrier: (3P: 2pcs)
NF125-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 50 60 70 100% of rated current Time-delay trip Instantaneous trip Min. Max. Operating characteristics NF125-SV 12.5A~32A 4h 2h 1h 30min 20min 14min 10min 6min 4min Instantaneous trip current is fixed to 600A120A. Operating time 2min 1min 30s 20s 10s 5s Min. 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s Time-delay trip 0.01s 1 1.25 2 3 4 5 6 7 10 15 20 30 40 100% of rated current Instantaneous trip Operating characteristics NF125-SV 40A~100A
Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT
Right-side mounting
10
20
30
40
Lead-wire direction
60
External Accessories
Accessories F Operating handle V S LC Handle lock device
(*1)
HL HL-S
Reference page Accessories Mechanical interlock MI 37 TC-S 38 Small TC-L 39 Large Terminal Skeleton TTC cover BTC Rear 41 PTC Plug-in Electrical operation device
Reference page
40
39 40
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
64
NF250-SV
Operating Characteristics
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min 1min Operating time 30s 20s 10s 5s 2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s 1 1.25 2 3 Time-delay trip 4 5 6 7 10 15 Instantaneous trip 20 30 40 Min. Operating characteristics NF250-SV 125A~225A
Max.
Internal Accessories
Operating handle Left-side mounting AL AX
SHT or UVT
Right-side mounting
10
20
30
40
Lead-wire direction
60
External Accessories
Accessories F Operating handle V S LC Handle lock device
(*1)
Reference page Accessories Mechanical interlock MI 37 Small TC-S 38 39 Large TC-L Terminal
Reference page 40
HL HL-S
41
Notes: *1 HLF types are used for OFF-lock and HLN types for ON-lock. *2 Specify the working voltage. Refer to the reference page for type name.
39
40
65
MEMO
66
6 . L O W- V O LTA G E S W I T C H G E A R T E C H N I C A L
67
I N F O R M AT I O N S E RV I C E V I A T H E I N T E R N E T
68
For Safety : Please read the instruction manual carefully before using the products in this catalog.
Wiring and connection must be done by the person have a specialized knowledge of electric construction and wiring.
Revised publication, effective Aug. 2011. Specifications are subject to change without notice. This pamphlet is made from recycled paper.