Note: If an average rate per year is to be used, input the sum of 12 months in the spaces above.
C. Cooling Tower Fans (Determine the partial or average load operating condition in amps)
32.1 X 480 X 1.73 X 0.91 / 1,000 = 24.3
Amps Volts Sq. Root of Phase Power Factor KWH
F. Other
37 X 480 X 1.73 X 0.95 / 1,000 = 29.2
Amps Volts Sq. Root of Phase Power Factor KWH
Step 3 - Hourly Electrical Consumption - Heating
Electrical Strip Heat (Determine the average [%] run time for strip heat)
0 X 0 = 0
Total KW of Strip Heaters Percentage Operation KWH
(May be applicable for large tenant or whole floor type occupancy only.)
60 X 32 / 1,000 = 1.6
Light Fixture Quantity Watts per Fixture KWH
Step 6 - Hourly Water Consumption (Condenser Systems)(Tons = minimum or average load on chiller)
$35.00 $35.00
Hourly cost of labor (to include overtime rate, payroll taxes and insurance) Cost/Hour
Totals
Hourly Mechanical System Operating Cost $49.80
Hourly Cost - Heating (Gas or Fuel Oil) $13.18
Hourly Cost - Water Consumption (Condenser Systems) $24.77
Hourly Cost - Water Treatment (Condenser Systems) $3.65
Hourly Cost - Equipment Maintenance $9.38
Hourly Cost - Equipment Depreciation $16.03
Hourly Cost - Labor $35.00
Administative Fee $22.77
Total Cost per Hour $174.58