Air Handling Unit

Structure and features of the air handling unit


Standard specification
Model of the air handling unit and air volume selection table
Table of external dimensions
Horizontal type
Horizontal type - built-in return fan
Combination type
Combination type - built-in return fan
Vertical type
Additional dimensions in longitudinal direction when applying optional items

Model selection and calculation of pressure drop inside the unit


Method and process of the air handling unit model selection
Internal static pressure drop
Calculation of static pressure drop resulting from coil
Calculation of the internal static pressure drop of the air handling unit
Calculation of pressure drop inside the cold and hot water coil

Outline drawing and dimensions of the coil


Outline drawing of the coil
Standard table of the face area of the coil
Dimension of the coil width
Diameter of the tube

Performance of the coil and selection method


Calculation of the chilled water coil performance
Calculation of hot water coil performance
Calculation of steam coil performance
Chilled water coil performance table
Hot water coil performance table
Steam coil performance table
Selection of the hot water coil
Selection of the steam coil

Weight table by model


Order specification sheet for the heat exchanger (Coil)
Cold hot water coil
Steam coil

Order specification sheet for the air handling unit

Air Handling Unit

Standard specification
Model
Category

AA0045 AA0065 AA0085 AA0120 AA0160 AA0200 AA0240 AA0300 AA0370 AA0450 AA0500 AA0600

m3/min

45

65

85

120

160

m3/h

2,700

3,900

5,100

7,200

9,600

m3/min 35~49 46~79

80~
100

101~
139

140~
199

200

240

300

370

450

500

600

12,000 14,400 18,000 22,200 27,000

30,000

36,000

180~
249

481~
556

557~
679

Standard air volume

200~
283

284~
339

340~
432

411~
529

Air volume range


m3/h
#DS

1 3/4

2 1/2

3 1/2

4 1/2

5 1/2

Motor

kW

1.5

2.2

2.2

3.7

3.7

5.5

7.5

7.5

11

15

15

18.5

Static
pressure

mmAq

60

75

75

80

80

80

85

85

85

90

90

90

Sirocco

#DS

1 3/4

1 3/4

2 1/2

2 1/2

3 1/2

4 1/2

Motor

kW

0.75

1.5

1.5

2.2

2.2

3.7

3.7

5.5

5.5

7.5

7.5

11

Static
pressure
Cooling Cold
capacity water

mmAq

35

35

40

40

40

45

45

45

45

45

45

45

kcal/h

19,000 29,000 38,000 54,000 71,000 90,000 105,000 135,000 165,000 200,000 225,000 270,000

Steam

kcal/h

27,000 39,000 51,000 73,000 97,000 121,000 145,000 181,000 224,000 272,000 302,000 363,000

Hot
water

kcal/h

22,000 32,000 42,000 60,000 80,000 100,000 120,000 150,000 185,000 225,000 250,000 300,000

Return Air

Fan

Supply Air

Air-Foil

Coil

Heating
capacity

Filter

Dimensions

PASS(H)
18(689) 18(689) 20(765) 22(842) 22(842) 26(994) 30(1146) 30(1146) 34(1299) 38(1451) 40(1527) 46(1756)
xLx
x
Quantity 440 x 1 x 640 x1 x 740 x1 x 940 x1 x 1240 x1 x 1340 x1 x 1440 x1 x 1740 x1 x 1840 x1 x 2140 x1 x 2140 x1 x 2340 x1

Face area

m2

Arrangement
610 x 610

Row x
Column
EA

305 x 610

EA

Face area

Standard humidity CAPA.


Connection diameter
of the pipes

2,100~ 2,760~ 4,800~ 6,060~ 8,400~ 10,800~ 12,000~ 17,040~ 20,400~ 24,660~ 28,860~ 33,420~
2,940 4,740 6,000 8,340 11,940 14,940 16,980 20,340 25,920 31,740 33,360 40,740

Inlet and outlet of the


cold and hot water
Steam inlet
Steam outlet

Kg/h

0.303

0.441

0.566

1.044

1.332

1.651

1.995

2.390

3.106

3.269

4.109

1x1

1 x 1.5

1 x 1.5 1.5 x 2 1.5 x 2

2x2

2 x 2.5

2x3

2 x 3.5 2.5 x 4

2.5 x 4

3x4

12

0.37

0.56

0.56

1.12

1.12

1.49

1.86

2.23

2.60

3.72

3.72

4.47

10

15

20

30

35

40

55

65

75

85

100

32 x 1 40 x 1

50 x 1

50 x 1

65 x 1

65 x 1

80 x 1

80 x 1

100 x 1

100 x 1

40 x 1 40 x 1

50 x 1

50 x 1

50 x 1

65 x 1

80 x 1

80 x 1

80 x 1

80 x 1

25 x 1 25 x 1 32 x 1 32 x 1 32 x 1 40 x 1

40 x 1

40 x 1

40 x 1

40 x 1

32 x 1 32 x 1
A
x
32 x 1 32 x 1
Quantity
25 x 1 25 x 1

0.791

[table 1-1]
Note
1. For specifications other than the standard air volume range, contact our sales department.
2. Operating conditions
Cooling coil inlet air temperature : 27 DB, 21 WB
Cold water inlet temperature: 7 , cold water temperature difference at the inlet and outlet: 5 , 6Row basis
Steam coil inlet air temperature: 15 DB, steam pressure: 0.35 kg/ , 2Row basis
Hot water coil inlet air temperature: 15 , hot water inlet temperature: 60 , hot water temperature difference at the inlet and outlet: 5 , 4Row basis
3. The standard and specification may change without prior notice for improvement of the product.

ACE R & A

08

www.aceind.co.kr

Model AA0700 AA0780 AA0870 AA0950 AA1050 AA1200 AA1300 AA1450 AA1600 AA1750 AA1850
700

780

870

950

1,050

1,200

1,300

1,450

1,600

1,750

1,850

2,000

Standard air volume

950~

1,124~ 1,246~ 1,403~ 1,500~ 1,699~

755

844

982

1,043

1,123

1,245

1,402

1,584

1,698

1,924

1,800~

1,900~

2,045

2,105

Air volume range


m3/h

58,920 62,580

67,380

74,700

84,120

95,040 101,880 115,440

122,700

129,000

7x2

7x2

5 1/2

Motor

kW

22

30

30

30

30

37

45

30 x 2

30 x 2

37 x 2

37 x 2

37 x 2

Static
pressure

mmAq

90

90

100

100

105

105

110

110

110

110

110

110

Sirocco

#DS

5 1/2

5 1/2

5x2

5 x 2 5 1/2 x 2

6x2

6x2

Motor

kW

11

15

15

15

18.5

18.5

22

15 x 2 18.5 x 2 15 x 2

15 x 2

18.5 x 2

Static
pressure
Cooling Cold
capacity water

mmAq

45

50

50

50

50

50

50

50

50

kcal/h

310,000 350,000 390,000 425,000 470,000 535,000 580,000 645,000 715,000 780,000

825,000

895,000

Steam

kcal/h

423,000 472,000 526,000 575,000 635,000 726,000 786,000 877,000 968,000 1,058,000 1,119,000 1,210,000

Hot
water

kcal/h

350,000 390,000 435,000 475,000 525,000 600,000 645,000 720,000 795,000 870,000

Supply Air

5 1/2

Return Air

Fan
Coil

50,640

#DS

Heating
capacity

Face area
Arrangement
Filter

45,300

Air-Foil

Dimensions

610 x 610

m2

50

920,000

995,000

5.580

6.441

6.935

7.922

8.656

9.882

10.539 11.884

12.633

13.473

Row x 3 x 4.5
Column
EA
12

3x5

3.5 x 5 3.5 x 5

4x5

4 x 5.5

4x6

4x7

4 x 7.5

4x8

4 x 8.5

4x9

15

15

15

20

20

24

28

28

32

32

36

5.02

5.58

6.51

6.51

7.44

8.19

8.93

10.42

11.16

11.91

12.65

13.40

Kg/h

120

130

150

160

180

210

225

251

277

303

320

346

Face area

Steam outlet

50

5.213

Steam inlet

50

4.662

EA

Inlet and outlet of the


cold and hot water

5 1/2 x 2 5 1/2 x 2 6 x 2

PASS(H)
24(918) 24(918) 24(918) 26(994) 28(1070) 32(1223) 32(1223) 30(1146) 32(1223) 32(1223) 30(1146) 32(1223)
xLx
x
Quantity 2540 x 2 x 2840 x 2 x 3040 x 2 x 3240 x 2 x 3240 x 2 x 3240 x 2 x 3540 x 2 x 2155 x 4 x 2155 x 4 x 2430 x 4 x 2755 x 4 x 2755 x 4

305 x 610

Standard humidity CAPA.


Connection diameter
of the pipes

39,000~ 43,800~ 50,700~ 54,000~ 57,000~ 67,440~ 74,760~ 84,180~ 90,000~ 101,940~ 108,000~ 114,000~

65 x 2
A
x
65 x 2
Quantity
40 x 2

80 x 2

80 x 2 100 x 2 100 x 2 100 x 2 100 x 2 80 x 4

80 x 4

80 x 4

80 x 4

100 x 4

80 x 2

80 x 2 80 x 2

80 x 2

80 x 2

80 x 2

80 x 4

80 x 4

80 x 4

80 x 4

80 x 4

40 x 2

40 x 2 40 x 2

40 x 2

40 x 2

40 x 2

40 x 4

40 x 4

40 x 4

40 x 4

40 x 4
[table 1-2]

Note
1. For specifications other than the standard air volume range, contact our sales department.
2. Operating conditions
Cooling coil inlet air temperature : 27 DB, 21 WB
Cold water inlet temperature: 7 , cold water temperature difference at the inlet and outlet: 5 , 6Row basis
Steam coil inlet air temperature: 15 DB, steam pressure: 0.35 kg/ , 2Row basis
Hot water coil inlet air temperature: 15 , hot water inlet temperature: 60 , hot water temperature difference at the inlet and outlet: 5 , 4Row basis
3. The standard and specification may change without prior notice for improvement of the product.

ACE R & A

09

www.aceind.co.kr

Thermo Hygrostat

900~

Heat Recovery
System

845~

Slim Type Air


Handling Unit

730~

Direct Expansion Type


Air Handling Unit

650~

Ceiling Type Air


Handling Unit

m3/min

42,000 46,800 52,200 57,000 63,000 72,000 78,000 87,000 96,000 105,000 111,000 120,000

Fan

m3/h

Built-Up Unit

m3/min

AA2000

Fan Dry Coil Unit

Category

Air Handling Unit

ACE Air Conditioning System

Air Handling Unit

Air handling unit


Model name display method

A
X

A
X

H
X
Type
H : Horizontal Type
HR : Horizontal Type, Built-in return fan
C : Combination Type
CR : Combination Type, Built-in return fan
V : Vertical Type

Process air volume (CMM)


Air handling unit
ACE R&A Co., Ltd.

Simple model selection table by air volume


Model
AA0045 AA0065 AA0085 AA0120 AA0160 AA0200 AA0240 AA0300 AA0370 AA0450 AA0500 AA0600
Supply Air #1 3/4
#2
#2 1/2
#3
#3
#3
#3 1/2
#4
#4
#4 1/2
#5
#5 1/2
Fan
Return Air #1 3/4 #1 3/4
#2
#2
#2 1/2 #2 1/2
#3
#3 1/2
#4
#4
#4
#4 1/2
Coil area(m2)
0.303 0.441 0.566 0.791 1.044 1.332 1.651 1.995 2.390 3.106 3.269
4.109
2,000
5,000
8,000
11,000
14,000
Air volume(CMH)

17,000
20,000
23,000
26,000
29,000
31,000
34,000
37,000
40,000
[table 2-1]

ACE R & A

10

www.aceind.co.kr

Model
AA0700 AA0780 AA0870 AA0950 AA1050 AA1200 AA1300 AA1450
Supply Air #5 1/2 #5 1/2
#6
#7
#7
#7
#8 #5 1/2X2
Fan
Return Air
#5
#5 1/2 #5 1/2
#6
#6
#6
#7
#5X2
Coil area(m2)
4.662 5.213 5.580 6.441 6.935 7.922 8.656 9.882

AA1600 AA1750
#5 1/2X2 #6X2
#5X2 #5 1/2x2
10.539 11.884

AA1850 AA2000
#7X2
#7X2
#6X2
#6X2
12.633 13.473

32,000

Air Handling Unit

ACE Air Conditioning System

Thermo Hygrostat

38,000
44,000
50,000
Heat Recovery
System

56,000
62,000
68,000

Slim Type Air


Handling Unit

74,000
80,000

Direct Expansion Type


Air Handling Unit

92,000
98,000
104,000
110,000

Ceiling Type Air


Handling Unit

116,000
122,000
128,000
134,000

Fan

140,000
146,000

158,000
[table 2-2]

Built-Up Unit

152,000

Fan Dry Coil Unit

Air volume(CMH)

86,000

ACE R & A

11

www.aceind.co.kr

Air Handling Unit

External dimensions chart


Horizontal Type

AA

[figure 1]
(mm)

Dimension
Size

PH

BH

AA0045H

500

750

1,100

2,350

940

1,020

850

100

270

385

170

790

AA0065H

600

750

1,150

2,500

1,140

1,120

950

100

315

440

170

990

AA0085H

600

750

1,300

2,650

1,240

1,170

1,000

100

397

550

300

1,090

AA0120H

600

750

1,450

2,800

1,440

1,270

1,100

100

480

660

300

1,290

AA0160H

600

750

1,450

2,800

1,740

1,370

1,200

100

480

660

300

1,590

AA0200H

600

750

1,450

2,800

1,840

1,470

1,300

100

480

660

300

1,690

AA0240H

600

750

1,600

2,950

1,940

1,570

1,400

100

560

745

320

1,790

AA0300H

600

750

1,450

2,800

2,240

1,670

1,500

100

642

865

320

2,090

AA0370H

750

750

1,450

2,950

2,340

1,770

1,600

100

642

865

430

2,190

AA0450H

750

750

1,600

3,100

2,640

1,870

1,700

100

723

970

430

2,490

AA0500H

750

750

1,650

3,150

2,640

1,970

1,800

100

745

1,070

450

2,490

AA0600H

900

750

1,900

3,550

2,840

2,170

2,000

100

886

1,185

560

2,690

AA0700H

900

750

1,900

3,550

3,040

2,270

2,100

100

886

1,185

600

2,890

AA0780H

900

750

1,900

3,550

3,340

2,270

2,100

100

886

1,185

600

3,190

Model

AA0870H

900

750

2,000

3,650

3,540

2,420

2,250

100

967

1,290

620

3,390

AA0950H

1,050

750

2,350

4,150

3,740

2,420

2,250

100

1,130

1,500

620

3,590

AA1050H

1,050

750

2,350

4,150

3,740

2,670

2,500

100

1,130

1,500

700

3,590

AA1200H

1,150

750

2,350

4,250

3,740

2,870

2,700

100

1,130

1,500

830

3,590

AA1300H

1,150

750

2,600

4,500

4,040

2,870

2,700

100

1,293

1,715

830

3,890

AA1450H

1,200

1,200

2,200

4,600

4,840

2,795

2,600

125

886 x 2 1,185 x 2 830 x 2 2,145x 2

AA1600H

1,350

1,200

2,200

4,750

4,840

2,895

2,700

125

886 x 2 1,185 x 2 890 x 2 2,145 x 2

AA1750H

1,350

1,200

2,450

5,000

5,390

2,895

2,700

125

967 x 2 1,290 x 2 890 x 2 2,420 x 2

AA1850H

1,350

1,200

2,800

5,350

6,040

2,795

2,600

125

1,130 x 2 1,500 x 2 770 x 2 2,745 x 2

AA2000H

1,500

1,200

2,800

5,500

6,040

2,895

2,700

125

1,130 x 2 1,500 x 2 830 x 2 2,745 x 2

Note
1. The dimensions B above are based on the setup cold water coil + steam coil + humidifier . For models AA1450H
and above, the dimensions are taken with the coil piping on one side.
2. When equipped with coil for both cold and hot water, the dimensions B of the model AA0045HR~AA1300HR can
be manufactured in 600mm, and AA1450H and above, in 750mm.
3. When coil piping is done for both directions in models AA1450HR and above, dimensions B can be manufactured in 750mm.
ACE R & A

12

www.aceind.co.kr

[table 3]

Horizontal type - built-in return fan

HR

PH

BH

1,100

1,150

500

4,000

940

1,020

850

100

270

385

170

790

AA0065HR

600

750

1,150

1,150

600

4,250

1,140

1,120

950

100

315

440

170

990

AA0085HR

600

750

1,300

1,250

600

4.500

1,240

1,170

1000

100

397

550

300

1,090

AA0120HR

600

750

1,450

1,250

600

4,650

1,440

1,270

1,100

100

480

660

300

1,290

AA0160HR

600

750

1,450

1,050

600

4,450

1,740

1,370

1,200

100

480

660

300

1,590

AA0200HR

600

750

1,450

1,050

600

4,450

1,840

1,470

1,300

100

480

660

300

1,690

AA0240HR

600

750

1,600

1,200

600

4,750

1,940

1,570

1,400

100

560

745

320

1,790

AA0300HR

600

750

1,450

1,300

600

4,700

2,240

1,670

1,500

100

642

865

320

2,090

AA0370HR

750

750

1,450

1,400

750

5,100

2,340

1,770

1,600

100

642

865

430

2,190

AA0450HR

750

750

1,600

1,400

750

5,250

2,640

1,870

1,700

100

723

970

430

2,490

AA0500HR

750

750

1,650

1,400

750

5,300

2,640

1,970

1,800

100

745

1070

450

2,490

AA0600HR

900

750

1,900

1,500

900

5,950

2,840

2,170

2,000

100

886

1,185

560

2,690

AA0700HR

900

750

1,900

1,600

900

6,050

3,040

2,270

2,100

100

886

1,185

600

2,890

AA0780HR

900

750

1,900

1,800

900

6,250

3,340

2,270

2,100

100

886

1,185

600

3,190

AA0870HR

900

750

2,000

1,800

900

6,350

3,540

2,420

2,250

100

967

1,290

620

3,390

AA0950HR

1,050

750

2,350

2,000

1,050

7,200

3,740

2,420

2,250

100

1,130

1,500

620

3,590

AA1050HR

1,050

750

2,350

2,000

1,050

7,200

3,740

2,670

2,500

100

1,130

1,500

700

3,590

AA1200HR

1,150

750

2,350

2,000

1,150

7,400

3,740

2,870

2,700

100

1,130

1,500

830

3,590

AA1300HR

1,150

750

2,600

2,300

1,150

7,950

4,040

2,870

2,700

100

1,293

1,715

830

3,890

AA1450HR

1,200

1,200

2,200

2,000

1,200

7,800

4,840

2,795

2,600

125

886 x 2 1,185 x 2 830 x 2 2,145 x 2

AA1600HR

1,350

1,200

2,200

2,000

1,350

8,100

4,840

2,895

2,700

125

886 x 2 1,185 x 2 890 x 2 2,145 x 2

AA1750HR

1,350

1,200

2,450

2,300

1,350

8,650

5,390

2,895

2,700

125

967 x 2 1,290 x 2 890 x 2 2,420 x 2

AA1850HR

1,350

1,200

2,800

2,000

1,350

8,700

6,040

2,795

2,600

125

1,130 x 2 1,500 x 2 770 x 2 2,745 x 2

AA2000HR

1,500

1,200

2,800

2,000

1,500

9,000

6,040

2,895

2,700

125

1,130 x 2 1,500 x 2 830 x 2 2,745 x 2

Note
1. The dimensions B above are based on the setup cold water coil + steam coil + humidifier. For models AA1450HR
and above, the dimensions are taken with the piping on one side.
2. When equipped with coil for both cold and hot water, the dimensions B of the model AA0045HR~AA1300HR can
be manufactured in 600mm, and AA1450HR and above, in 750mm.
3. When coil piping is done for both directions in models AA1450HR and above, dimensions B can be manufactured in 750mm.
ACE R & A

13

www.aceind.co.kr

[table 4]

Slim Type Air


Handling Unit

750

Direct Expansion Type


Air Handling Unit

500

Ceiling Type Air


Handling Unit

AA0045HR

Model

Fan

Size

(mm)

Built-Up Unit

Dimension

Fan Dry Coil Unit

[figure 2]

Heat Recovery
System

Thermo Hygrostat

AA

Air Handling Unit

ACE Air Conditioning System

Air Handling Unit

Combination Type

AA

[figure 3]

Dimension
Model

(mm)

Size

PH1

PH2

BH

AA0045C

500

1,200

1,700

940

1,970

900

900

100

270

385

170

790

AA0065C

600

1,300

1,900

1,140

2,120

1,000

950

100

315

440

170

990

AA0085C

700

1,400

2,100

1,240

2,320

1,050

1,100

100

397

550

300

1,090

AA0120C

700

1,550

2,250

1,440

2,520

1,150

1,200

100

480

660

300

1,290

AA0160C

700

1,550

2,250

1,740

2,570

1,200

1,200

100

480

660

300

1,590

AA0200C

700

1,550

2,250

1,840

2,720

1,350

1,200

100

480

660

300

1,690

AA0240C

800

1,700

2,500

1,940

3,020

1,450

1,400

100

560

745

320

1,790

AA0300C

800

1,500

2,300

2,240

3,170

1,500

1,500

100

642

865

320

2,090

AA0370C

900

1,500

2,400

2,340

3,320

1,650

1,500

100

642

865

430

2,190

AA0450C

900

1,650

2,550

2,640

3,570

1,750

1,650

100

723

970

430

2,490

AA0500C

900

1,700

2,600

2,640

3,720

1,800

1,750

100

745

1,070

450

2,490

AA0600C

1000

1,900

2,900

2,840

4,220

2,050

2,000

100

886

1,185

560

2,690

AA0700C

1,050

1,900

2,950

3,040

4,320

2,150

2,000

100

886

1,185

600

2,890

AA0780C

1,050

1,900

2,950

3,340

4,320

2,150

2,000

100

886

1,185

600

3,190

AA0870C

1,050

2,050

3,100

3,540

4,570

2,300

2,100

100

967

1,290

620

3,390

AA0950C

1,050

2,400

3,450

3,740

4,870

2,300

2,400

100

1,130

1,500

620

3,590

AA1050C

1,150

2,400

3,550

3,740

5,170

2,600

2,400

100

1,130

1,500

700

3,590

AA1200C

1,300

2,400

3,700

3,740

5,320

2,750

2,400

100

1,130

1,500

830

3,590

AA1300C

1,300

2,700

4,000

4,040

5,620

2,750

2,700

100

1,293

1,715

830

3,890

AA1450C

1,300

2,300

3,600

4,840

4,795

2,600

2,000

125

ACE R & A

14

www.aceind.co.kr

886 x 2 1,185 x 2 830 x 2

2,145 x 2
[table 5]

Combination type - built-in return fan

CR

H1

H2

PH1

PH2

BH

940

2,110

970

1,040

900

900

100

270

385

170

790

AA0045CR

500

1,150 1,200 2,850

AA0065CR

600

1,150 1,300 3,050 1,140 2,210 1,070 1,040 1,000

900

100

315

440

170

990

AA0085CR

700

1,250 1,400 3,350 1,240 2,210 1,070 1,040 1,000

900

100

397

550

300

1,090

AA0120CR

700

1,250 1,550 3,500 1,440 2,310 1,170 1,040 1,100

900

100

480

660

300

1,290

AA0160CR

700

1,050 1,550 3,300 1,740 2,560 1,270 1,190 1,200

1,050

100

480

660

300

1,590

AA0200CR

700

1,050 1,550 3,300 1,840 2,660 1,370 1,190 1,300

1,050

100

480

660

300

1,690

AA0240CR

800

1,200 1,700 3,700 1,940 2,910 1,470 1,340 1,400

1,200

100

560

745

320

1,790

AA0300CR

800

1,300 1,500 3,600 2,240 3,110 1,570 1,440 1,500

1,300

100

642

865

320

2,090

AA0370CR

900

1,400 1,500 3,800 2,340 3,210 1,670 1,440 1,600

1,300

100

642

865

430

2,190

AA0450CR

900

1,400 1,650 3,950 2,640 3,510 1,770 1,640 1,700

1,500

100

723

970

430

2,490

AA0500CR

900

1,400 1,700 4,000 2,640 3,610 1,870 1,640 1,800

1,500

100

745

1,070

450

2,490

AA0600CR

1,000 1,500 1,900 4,400 2,840 3,910 2,070 1,740 2,000

1,600

100

886

1,185

560

2,690

AA0700CR

1,050 1,600 1,900 4,550 3,040 4,110 2,170 1,840 2,100

1,700

100

886

1,185

600

2,890

AA0780CR

1,050 1,800 1,900 4,750 3,340 4,310 2,170 2,040 2,100

1,900

100

886

1,185

600

3,190

AA0870CR

1,050 1,800 2,050 4,900 3,540 4,460 2,320 2,040 2,250

1,900

100

967

1,290

620

3,390

AA0950CR

1,050 2,000 2,400 5,450 3,740 4,610 2,320 2,190 2,250

2,050

100

1,130 1,500

620

3,590

AA1050CR

1,150 2,000 2,400 5,550 3,740 4,860 2,570 2,190 2,500

2,050

100

1,130 1,500

700

3,590

AA1200CR

1,300 2,000 2,400 5,700 3,740 5,060 2,770 2,190 2,700

2,050

100

1,130 1,500

830

3,590

AA1300CR

1,300 2,300 2,700 6,300 4,040 5,360 2,770 2,490 2,700

2,350

100

1,293 1,715

830

3,890

AA1450CR

1,300 2,000 2,300 5,600 4,840 4,585 2,670 1,790 2,600

1,650

125

886x2 1,185x2 830x2 2,145x2


[table 6]

ACE R & A

15

www.aceind.co.kr

Direct Expansion Type


Air Handling Unit

Ceiling Type Air


Handling Unit

Size

Fan

Model

(mm)

Built-Up Unit

Dimension

Fan Dry Coil Unit

[figure 4]

Slim Type Air


Handling Unit

Heat Recovery
System

Thermo Hygrostat

AA

Air Handling Unit

ACE Air Conditioning System

Air Handling Unit

Vertical Type

AA

[figure 5]

Dimension

(mm)

Size

PH1

PH2

PH3

BH

AA0045V

1,200

940

2,520

700

750

900

100

270

385

170

790

AA0065V

1,300

1,140

2,570

700

750

950

100

315

440

170

990

AA0085V

1,400

1,240

2,720

700

750

1,100

100

397

550

300

1,090

AA0120V

1,550

1,440

2,820

700

750

1,200

100

480

660

300

1,290

AA0160V

1,550

1,740

2,820

700

750

1,200

100

480

660

300

1,590

AA0200V

1,550

1,840

2,870

750

750

1,200

100

480

660

300

1,690

AA0240V

1,700

1,940

3,070

750

750

1,400

100

560

745

320

1,790

AA0300V

1,700

2,240

3,170

750

750

1,500

100

642

865

320

2,090

AA0370V

1,850

2,340

3,420

1,000

750

1,500

100

642

865

430

2,190

AA0450V

1,950

2,640

3,570

1,000

750

1,650

100

723

970

430

2,490

AA0500V

2,000

2,640

3,670

1,000

750

1,750

100

745

1,070

450

2,490

AA0600V

2,200

2,840

3,920

1,000

750

2,000

100

886

1,185

560

2,690

AA0700V

2,300

3,040

3,920

1,000

750

2,000

100

886

1,185

600

2,890

AA0780V

2,300

3,340

3,920

1,000

750

2,000

100

886

1,185

600

3,190

Model

Note
1. The dimensions PH2 above are based on the setup cold water coil + steam coil + humidifier .
2. When equipped with coil for both cold and hot water, the dimensions PH2 can be manufactured in 600mm
with humidifier, and 500mm without humidifier.

ACE R & A

16

www.aceind.co.kr

[table 7]

Additional dimensions in longitudinal direction when applying optional items

Charged corpuscle neutralization device

Self cleaning electric dust collector

Thermo Hygrostat

L1
450
650
850
900
1,000

Auto Filter

Slim Type Air


Handling Unit

Medium Filter L2
Mini Pleat 3
800
Cell Type 12 1,000

Fan

Water Spray +
Eliminator

Eliminator

Application type

Steam Grid
Steam Injection
Electrode type
Water evaporation
type

Humidifier

Ceiling Type Air


Handling Unit

Air filter assembly method


-Roll Filter + Service Door(430mm) + Medium Filter(Cell or Bag Type)
-Pre + Medium Filter( Mini Pleat 3 or Cell or Bag Type) + Service Door(430mm) +Charged corpuscle neutralization device

Application type

Heat Recovery
System

Standard
15
22
30
32
36

Air filter

Two-stage
electrostatic type

Bag Type

Cell Type

Direct Expansion Type


Air Handling Unit

Roll Type

(mm)

Air Handling Unit

ACE Air Conditioning System

C/C

C/C+H/C

H/C+C/C+H/C

C/C+S/D+H/C

H/C+S/D+C/C+H/C

/C : Cooling Coil
H/C : Heating Coil
S/D : Service Door
1. Additional dimensions are on the basis of C/C-6Rows and H/C-2Rows when the above coil option is added.
2. 33mm will be added for increment of each row of coil.

ACE R & A

17

www.aceind.co.kr

Fan Dry Coil Unit

Coil

Built-Up Unit

H/C

Air Handling Unit

Model selection and calculation of the pressure drop inside the unit
Method and process of the air handling unit model selection

ACE R & A

18

www.aceind.co.kr

Air Handling Unit

ACE Air Conditioning System

Internal static pressure drop


Static pressure drop = coil + air filter + eliminator +mixing box, casing + damper + other additional components
H = H1 + H2 + H3 + H4 + H5 + H6
H Internal static pressure drop
H1 Static pressure drop caused by the coil - [table8] [table9] [table15]
H2 Static pressure drop caused by the air filter - [table12]

Thermo Hygrostat

H3 Static pressure drop caused by the eliminator [If eliminator is installed] - [table13]
H4 Static pressure drop caused by the mixing box and casing - [table14]
H5 Static pressure drop caused by the damper - [table 16]

Heat Recovery
System

H6 Addition of other components

Static pressure drop curve caused


by the hot water(steam) coil

Static pressure drop correction


factor for coil fin pitch

Temperature correction factor for


pressure drop at the air side

Static pressure drop correction factor by fin pitch

Static pressure drop correction factor by temperature

Number of
fins(per inch) 14
Fin pitch
1.81
(mm)
Correction
1.95
factor

12

10

2.12

2.54

3.18

4.23

6.35

12.7

1.60

1.35

1.00

0.72

0.43

0.26

Built-Up Unit

[table 9]

[table 10]
[table 11]

ACE R & A

19

www.aceind.co.kr

Fan Dry Coil Unit

[table 8]

Fan

Ceiling Type Air


Handling Unit

Direct Expansion Type


Air Handling Unit

Slim Type Air


Handling Unit

Static pressure drop curve caused


by the chilled water coil

Air Handling Unit

Static pressure drop caused by the air filter

Static pressure drop caused by the mixing box and casing

Static pressure drop curve by air filter

Static pressure drop curve by mixing box & casing

[table12]

[table14]

Note 1. Air pressure drop by the air filter may be different by the actual media used.
2. Additional calculation for the pressure drop is required depending on the category, type and specification of the air filter.

Static pressure drop caused by the coil in


case of vertical air handling unit

Static pressure drop caused by the eliminator


Static pressure drop curve by eliminator

Static pressure drop curve by Vertical type coil

[table15]

Static pressure drop caused by the damper


Static pressure drop curve by air damper

[table13]

[table 16]

ACE R & A

20

www.aceind.co.kr

ACE Air Conditioning System

Method

Result

Air side static


pressure drop

Using the static pressure drop curve at the air side of the chilled water coil,
intersection between pass-through wind speed(2.5m/s) and number of coil 15.8 mmAq
rows (8Row) is taken

Fin pitch static pressure


drop correction factor

Check on the fin pitch static pressure drop correction factor table

1.35

Reference
table
table 8
table 10

Check on the temperature correction factor for the air side pressure drop
Correction factor on the
average dry bulb air
table 11
Average air temperature Coil inlet air temperature + Coil outlet air temperature
1.02
temperature at the coil inlet
=
23
at
the
inlet
and
outlet
=
and outlet
Air side static pressure drop x fin pitch static pressure drop correction factor
Through the above
x correction factor on the average dry bulb temperature of the coil inlet and 21.76 mmAq
process 1,2,3
outlet air =15.8mmAq x 1.35 x1.02

Calculation of internal static pressure drop of the air handling unit


Sample specification
- Chilled water coil: 8 Row, 10Fin/Inch - Air Filter: Glass Fiber material
- Pass-through wind speed: 2.5m/s
- Eliminator: Installed
Seque
nce

Item

Result

Method

7.6 mmAq

Air filter static pressure


drop

Eliminator, mixing box,


casing static pressure drop

Measured pressure drop at


the chilled water coil

According to the above calculation of static pressure drop


caused by the coil

21.76 mmAq

Through the above process


1,2,3

Summation of item 1,2,3


7.6 3.7 0.5 2.8 21.76

36.36 mmAq

Eliminator-3.7mmAq
Mixing box-0.5mmAq
Casing-2.8mmAq

table 13
table 14

Ceiling Type Air


Handling Unit

From each curve, read the value at the pass-through wind


speed 2.5m/s

Reference
table
table 12

Thermo Hygrostat

Item

Heat Recovery
System

Seque
nce

- Coil inlet air temperature(DB1) : 28


- Coil outlet air temperature(DB2) : 18

Slim Type Air


Handling Unit

- Coil : 8 Row, 10Fin/Inch


- Pass-through wind speed : 2.5m/s

Direct Expansion Type


Air Handling Unit

Sample specification - chilled water coil

Air Handling Unit

Calculation of static pressure drop caused by the coil

Calculation of pressure drop inside the


Cold and hot water coil
Basic specification

Fan

1. Model: AA0300H
2. Cooling caloric value : 135,000 kcal/h
3. Specification of coil : 6Row 30 Pass 1,740mm
4. Inlet and outlet temperature difference : 5

Calculation formula
and method
135,000 (60 5)

450 /min

450

30 (Single Circuit)

15 /min

Values

Water
pressure drop

As the length of the tube is


1,740mm, check the curve on
the right

0.76mAq

Through the
process 1,2,3

Total pressure drop = 0.76 6Row

4.56 mAq

Note Recommended water speed inside the coil is 0.5~2.3m/s.


[table 17]

ACE R & A

21

www.aceind.co.kr

Fan Dry Coil Unit

Seque
Item
nce
Flow rate
1
Flow rate per
2
tube

Built-Up Unit

When cold and hot water coil is used, the pressure drop on the
water side is calculated from the flow rate per tube Pass bundle
and the length (effective length) of tube.

Air Handling Unit

Outline drawing and dimensions of the coil


Outline drawing of the coil

[figure 6]

Standard face area table for the coil (Coil Face Area: m2)

Coil width dimension


Number of
rows

C(mm)

600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600

1-2

125

3-4

192

5-6

258

7-8

324

L(mm)

Height
H
Pass (mm) 400
10

384

0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.69 0.77 0.84 0.92 1.00 1.08 1.15 1.23 1.31 1.38

12

461

0.18 0.28 0.37 0.46 0.55 0.65 0.74 0.83 0.92 1.01 1.11 1.20 1.29 1.38 1.48 1.57 1.66

14

537

0.21 0.32 0.43 0.54 0.64 0.75 0.86 0.97 1.07 1.18 1.29 1.40 1.50 1.61 1.72 1.83 1.93

16

613

0.25 0.37 0.49 0.61 0.74 0.86 0.98 1.10 1.23 1.35 1.47 1.59 1.72 1.84 1.96 2.08 2.21

18

689

0.28 0.41 0.55 0.69 0.83 0.96 1.10 1.24 1.38 1.52 1.65 1.79 1.93 2.07 2.20 2.34 2.48

9-10

390

20

765

0.31 0.46 0.61 0.77 0.92 1.07 1.22 1.38 1.53 1.68 1.84 1.99 2.14 2.30 2.45 2.60 2.75

11-12

456

22

842

0.34 0.51 0.67 0.84 1.01 1.18 1.35 1.52 1.68 1.85 2.02 2.19 2.36 2.53 2.69 2.86 3.03

24

918

0.37 0.55 0.73 0.92 1.10 1.29 1.47 1.65 1.84 2.02 2.20 2.39 2.57 2.75 2.94 3.12 3.30

26

994

0.40 0.60 0.80 0.99 1.19 1.39 1.59 1.79 1.99 2.19 2.39 2.58 2.78 2.98 3.18 3.38 3.58

28

1070

0.43 0.64 0.86 1.07 1.28 1.50 1.71 1.93 2.14 2.35 2.57 2.78 3.00 3.21 3.42 3.64 3.85

30

1146

0.46 0.69 0.92 1.15 1.38 1.60 1.83 2.06 2.29 2.52 2.75 2.98 3.21 3.44 3.67 3.90 4.13

32

1223

0.49 0.73 0.98 1.22 1.47 1.71 1.96 2.20 2.45 2.69 2.94 3.18 3.42 3.67 3.91 4.16 4.40

34

1299

0.52 0.78 1.04 1.30 1.56 1.82 2.08 2.34 2.60 2.86 3.12 3.38 3.64 3.90 4.16 4.42 4.68

36

1375

38

[table 19]
1. Cu-Tube : OD5 / 8 (15.88mm)
2. Fin: 4~12 sheets / Inch

Tube diameter
Flow rate
( /min)

Tube diameter

0 ~ 150

32A

0.55 0.83 1.10 1.38 1.65 1.93 2.20 2.48 2.75 3.03 3.30 3.58 3.85 4.13 4.40 4.68 4.95

151 ~ 203

40A

1451

0.58 0.87 1.16 1.45 1.74 2.03 2.32 2.61 2.90 3.19 3.48 3.77 4.06 4.35 4.64 4.93 5.22

204 ~ 329

50A

40

1527

0.61 0.92 1.22 1.53 1.83 2.14 2.44 2.75 3.05 3.36 3.66 3.97 4.28 4.58 4.89 5.19 5.50

330 ~ 542

65A

42

1604

0.64 0.96 1.28 1.60 1.92 2.25 2.57 2.89 3.21 3.53 3.85 4.17 4.49 4.81 5.13 5.45 5.77

44

1680

0.67 1.01 1.34 1.68 2.02 2.35 2.69 3.02 3.36 3.70 4.03 4.37 4.70 5.04 5.38 5.71 6.05

543 ~ 767

80A

46

1756

0.70 1.05 1.40 1.76 2.11 2.46 2.81 3.16 3.51 3.86 4.21 4.57 4.92 5.27 5.62 5.97 6.32

768 ~ 1306

100A

[table 18]

ACE R & A

22

www.aceind.co.kr

[table 20]

ACE Air Conditioning System

The following coil performance tables (table25, table26, table27) are based on the standard operation condition, which
need to be corrected depending on the conditions of use.
In case the operation condition is the same with the standard operation condition: Refer to the chilled water coil
performance table, hot water coil performance table and the steam coil performance table
In case the operation condition is different from the standard operation condition: coil performance
= coil performance table (table25, table26, table27) X heat transfer correction factor of the fin (table21) X coil performance
correction factor (table22, table23, table24)

Thermo Hygrostat

Performance of the coil

Air Handling Unit

Performance of the coil and selection method

Number of fins / inch

14

12

10

Fin pitch(mm)

1.81

2.12

2.54

3.18

3.63

4.23

Correction factor

1.35

1.25

1.12

1.0

0.92

0.81
[table 21]

[table 22]

Calculation of the chilled water coil performance

Fan

Ceiling Type Air


Handling Unit

Direct Expansion Type


Air Handling Unit

Slim Type Air


Handling Unit

Chilled water coil performance correction factor

Heat Recovery
System

Heat transfer correction factor of the fin

Sequence
1
2
3
4

Item

4. Coil specification : 6 Row (8Fins/Inch)


5. Air volume : 45 CMM
6. Coil pass-through wind speed : 2.5m/s
Method

Chilled water coil performance Check on the chilled water coil performance table

Result

19,000Kcal/h
Heat transfer correction
Check on the heat transfer correction factor table of the fin
1.0
factor of the fin
Chilled water coil performance Check on the chilled water coil performance
1.0
correction factor chart
correction factor
Chilled
water
coil
performance
table
X
heat
transfer
correction
According to the items 1,2,3
19,000Kcal/h
factor of the fin X coil performance correction factor

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with the values of 2.0m/s and 2.5m/s.
ACE R & A

23

www.aceind.co.kr

Reference table
Table 25
Table 21
Table 22

Fan Dry Coil Unit

1. Chilled water inlet temperature : 7


2. Chilled water inlet and outlet temperature difference : 5
3. Chilled water coil inlet air temperature : 27 DB, 21 WB

Built-Up Unit

Operating condition

Air Handling Unit

Hot water coil performance correction factor

Calculation of the hot water coil performance


Operating condition
1. Hot water inlet temperature: 70
2. Hot water inlet and outlet temperature difference : 5
3. Hot water coil inlet air temperature : 15 DB
4. Coil specification : 4 Row (8Fins/Inch)
5. Air volume : 65CMM
6. Coil pass-through wind speed : 2.5m/s
Sequ
ence

Item

Method

Result

Reference
table

Hot water coil


performance

Check on the hot water coil


performance table

32,000Kcal/h table 26

Heat transfer
correction factor
of the fin

Check on the heat transfer


correction factor table of
the fin

1.0

table 21

Hot water coil


performance
correction factor

Check on the hot water coil


performance correction
factor chart

1.23

table 23

According to the
Heat transfer correction factor of the fin X 39,400Kcal/h
items 1,2,3

Hot water coil performance table X

Coil performance correction factor X

[[table 23]

Steam coil performance correction factor

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with the
values of 2.0m/s and 2.5m/s.

Calculation of the steam coil performance


Operating condition
1. Steam coil inlet air temperature : 11 DB
2. Steam pressure : 1Kg/cm2
3. Coil specification : 2 Row (8Fins/Inch)
4. Air volume : 65CMM
5. Coil pass-through wind speed : 2.5m/s
Sequ
ence

Item

Method

Result

Reference
table

Steam coil
performance

Check on the steam coil


performance table

39,000Kcal/h Table 27

Heat transfer
correction factor
of the fin

Check on the heat transfer


correction factor Table of
the fin

1.0

Table 21

Steam coil
performance
correction factor

Check on the performance


correction factor Chart of
the steam coil

1.179

Table 24

According to the
Heat transfer correction factor of the fin X 45,981Kcal/h
items 1,2,3

Steam coil performance table X

Coil performance correction factor

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with the
values of 2.0m/s and 2.5m/s.
[[table 24]

ACE R & A

24

www.aceind.co.kr

6 ROW
21.7
33.1
43.3
61.6
80.9
102.6
119.7
153.9
188.1
228.0
256.5
307.8
353.4
399.0
444.6
484.5
535.8
609.9
661.2
735.3
815.1
889.2
940.5
1,020.3
19.0
29.0
38.0
54.0
71.0
90.0
105.0
135.0
165.0
200.0
225.0
270.0
310.0
350.0
390.0
425.0
470.0
535.0
580.0
645.0
715.0
780.0
825.0
895.0

4 ROW
16.0
23.9
31.9
44.5
59.3
75.2
87.8
112.9
136.8
166.4
187.0
224.6
257.6
291.8
324.9
353.4
391.0
445.7
482.2
536.9
595.1
648.7
686.3
744.4
14.0
21.0
28.0
39.0
52.0
66.0
77.0
99.0
120.0
146.0
164.0
197.0
226.0
256.0
285.0
310.0
343.0
391.0
423.0
471.0
522.0
569.0
602.0
653.0

8 ROW
26.2
38.8
51.3
73.0
95.8
122.0
141.4
182.4
223.4
270.2
304.4
364.8
418.4
473.1
526.7
574.6
635.0
722.8
783.2
871.0
965.6
1,053.4
1,114.9
1,209.5
23.0
34.0
45.0
64.0
84.0
107.0
124.0
160.0
196.0
237.0
267.0
320.0
367.0
415.0
462.0
504.0
557.0
634.0
687.0
764.0
847.0
924.0
978.0
1,061.0

Note
1. Operating condition - Air temperature at the inlet of the coil: 27 DB, 21 WB
- Cold water temperature difference at the inlet and outlet: 5
2. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch 3. Same heat transfer area condition
ACE R & A

25

www.aceind.co.kr

4 ROW

18.2
27.4
36.5
50.2
67.3
85.5
100.3
128.8
156.2
190.4
213.2
256.5
294.1
332.9
370.5
403.6
445.7
508.4
549.5
612.2
678.3
739.9
783.2
849.3
16.0
24.0
32.0
44.0
59.0
75.0
88.0
113.0
137.0
167.0
187.0
225.0
258.0
292.0
325.0
354.0
391.0
446.0
482.0
537.0
595.0
649.0
687.0
745.0

6 ROW
25.1
37.6
49.0
70.7
92.3
117.4
136.8
175.6
214.3
259.9
293.0
351.1
403.6
454.9
507.3
552.9
611.0
695.4
753.5
839.0
929.1
1,014.6
1,072.7
1,163.9
22.0
33.0
43.0
62.0
81.0
103.0
120.0
154.0
188.0
228.0
257.0
308.0
354.0
399.0
445.0
485.0
536.0
610.0
661.0
736.0
815.0
890.0
941.0
1,021.0

8 ROW
29.6
44.5
58.1
83.2
109.4
139.1
160.7
207.5
255.4
307.8
347.7
416.1
477.7
539.2
600.8
655.5
723.9
824.2
892.6
992.9
1,101.2
1,201.6
1,271.1
1,379.4
26.0
39.0
51.0
73.0
96.0
122.0
141.0
182.0
224.0
270.0
305.0
365.0
419.0
473.0
527.0
575.0
635.0
723.0
783.0
871.0
966.0
1,054.0
1,115.0
1,210.0
[table 25]

Thermo Hygrostat

8 ROW
21.7
33.1
43.3
61.6
80.9
102.6
118.6
152.8
188.1
226.9
255.4
306.7
351.1
397.9
442.3
482.2
533.5
607.6
657.8
731.9
810.5
884.6
937.1
1,015.7
19.0
29.0
38.0
54.0
71.0
90.0
104.0
134.0
165.0
199.0
224.0
269.0
308.0
349.0
388.0
423.0
468.0
533.0
577.0
642.0
711.0
776.0
822.0
891.0

Heat Recovery
System

6 ROW
18.2
27.4
36.5
51.3
68.4
86.6
100.3
128.8
158.5
191.5
215.5
258.8
296.4
335.2
373.9
407.0
450.3
511.9
555.2
617.9
685.1
746.7
790.0
857.3
16.0
24.0
32.0
45.0
60.0
76.0
88.0
113.0
139.0
168.0
189.0
227.0
260.0
294.0
328.0
357.0
395.0
449.0
487.0
542.0
601.0
655.0
693.0
752.0

Slim Type Air


Handling Unit

4 ROW
13.7
20.5
27.4
37.6
50.2
62.7
74.1
94.6
115.1
140.2
157.3
188.1
216.6
245.1
272.5
296.4
328.3
373.9
404.7
451.4
499.3
544.9
576.8
625.9
12.0
18.0
24.0
33.0
44.0
55.0
65.0
83.0
101.0
123.0
138.0
165.0
190.0
215.0
239.0
260.0
288.0
328.0
355.0
396.0
438.0
478.0
506.0
549.0

Direct Expansion Type


Air Handling Unit

AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0300
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1300
AA1450
AA1600
AA1750
AA1850
AA2000
AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0300
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1300
AA1450
AA1600
AA1750
AA1850
AA2000

Air velocity through the coil Va = 2.0m/s Air velocity through the coil Va = 2.5m/s Air velocity through the coil Va = 3.0m/s

Ceiling Type Air


Handling Unit

Model

1,000 kcal/h)

Fan

Cooling performance (

Built-Up Unit

Inlet
water
temper
ature

Fan Dry Coil Unit

Performance table of cold water coil

Air Handling Unit

ACE Air Conditioning System

Air Handling Unit

Performance table of hot water coil


Inlet
water
temper
ature

60

70

Model
AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0300
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1300
AA1450
AA1600
AA1750
AA1850
AA2000
AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0300
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1300
AA1450
AA1600
AA1750
AA1850
AA2000

Heating performance ( 1,000 kcal/h)


Air velocity through the coil Va = 2.0m/s Air velocity through the coil Va = 2.5m/s Air velocity through the coil Va = 3.0m/s
2 ROW
11.0
14.1
18.5
26.4
35.2
44.0
52.8
66.0
81.4
99.0
110.0
132.0
188.8
210.4
234.6
256.2
283.2
323.6
347.9
388.4
428.8
469.3
496.2
536.7
13.0
17.6
23.2
33.1
44.1
55.1
66.2
82.7
102.0
124.0
137.8
165.4
236.9
264.0
294.5
321.6
355.4
406.2
436.7
487.4
538.2
589.0
622.8
673.6

4 ROW
19.0
26.6
34.9
49.8
66.4
83.0
99.6
124.5
153.6
186.8
207.5
249.0
304.5
339.3
378.5
413.3
456.8
522.0
561.2
626.4
691.7
756.9
800.4
865.7
23.8
32.7
42.9
61.3
81.7
102.1
122.5
153.1
188.9
229.7
255.2
306.3
370.2
412.5
460.1
502.5
555.3
634.7
682.3
761.6
841.0
920.3
973.2
1,052.5

6 ROW
23.5
32.7
42.9
61.3
81.7
102.1
122.5
153.1
188.9
229.7
255.2
306.3
386.7
430.9
480.6
524.8
580.1
662.9
712.7
795.5
878.4
961.3
1,016.5
1,099.4
29.0
39.5
51.9
74.1
98.8
123.5
148.2
185.3
228.5
277.9
308.8
370.6
451.7
503.3
561.4
613.0
677.5
774.3
832.4
929.2
1,026.0
1,122.7
1,187.3
1,284.1

2 ROW
12.0
16.6
21.8
31.2
41.6
52.0
62.4
78.0
96.2
117.0
130.0
156.0
220.5
245.7
274.1
299.3
330.8
378.0
406.4
453.6
500.9
548.1
579.6
626.9
15.0
20.9
27.4
39.1
52.2
65.2
78.2
97.8
120.6
146.7
163.0
195.6
258.3
287.8
321.0
350.6
387.5
442.8
476.0
531.4
586.7
642.1
679.0
734.3

4 ROW
22.0
32.0
42.0
60.0
80.0
100.0
120.0
150.0
185.0
225.0
250.0
300.0
350.0
390.0
435.0
475.0
525.0
600.0
645.0
720.0
795.0
870.0
920.0
995.0
28.0
39.4
51.7
73.8
98.4
123.0
147.6
184.5
227.6
276.8
307.5
369.0
430.5
479.7
535.1
584.3
645.8
738.0
793.4
885.6
977.9
1,070.1
1,131.6
1,223.9

6 ROW
28.0
39.4
51.7
73.8
98.4
123.0
147.6
184.5
227.6
276.8
307.5
369.0
444.5
495.3
552.5
603.3
666.8
762.0
819.2
914.4
1,009.7
1,104.9
1,168.4
1,263.7
35.0
48.0
63.0
90.0
120.0
150.1
180.1
225.1
277.6
337.6
375.2
450.2
538.1
599.6
668.8
730.3
807.2
922.5
991.7
1,107.0
1,222.3
1,337.6
1,414.5
1,529.8

Note
1. Operating condition - Air temperature at the inlet of the coil: 15 DB,
- Hot water temperature difference at the inlet and outlet: 5
2. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch
3. Same heat transfer area condition
ACE R & A

26

www.aceind.co.kr

2 ROW
13.5
19.3
25.4
36.3
48.3
60.4
72.5
90.6
111.8
135.9
151.1
181.3
245.2
273.2
304.8
332.8
367.8
420.4
451.9
504.4
557.0
609.5
644.6
697.1
17.0
23.3
30.6
43.7
58.3
72.9
87.5
109.4
134.9
164.1
182.3
218.7
296.7
330.7
368.8
402.7
445.1
508.7
546.9
610.4
674.0
737.6
780.0
843.6

4 ROW
25.0
36.5
47.9
68.4
91.2
114.0
136.8
171.0
210.9
256.5
285.0
342.0
395.5
440.7
491.6
536.8
593.3
678.0
728.9
813.6
898.4
983.1
1,039.6
1,124.4
32.0
44.9
58.9
84.1
112.2
140.2
168.3
210.3
259.4
315.5
350.6
420.7
486.5
542.1
604.6
660.2
729.7
833.9
896.5
1,000.7
1,105.0
1,209.2
1,278.7
1,383.0

6 ROW
32.5
46.0
60.3
86.2
114.9
143.6
172.4
215.5
265.7
323.2
359.1
430.9
502.3
559.7
624.3
681.7
753.4
861.1
925.6
1,033.3
1,140.9
1,248.5
1,320.3
1,427.9
40.5
55.2
72.4
103.5
138.0
172.5
207.0
258.7
319.1
388.1
431.2
517.4
622.7
693.8
773.9
845.1
934.0
1,067.4
1,147.5
1,280.9
1,414.4
1,547.8
1,636.7
1,770.2
[table 26]

2.0

Va=3.0m/s
32.4
46.8
61.2
87.6
116.4
145.2
174.0
217.2
268.8
326.4
362.4
435.6
507.6
566.4
631.2
690.0
762.0
871.2
943.2
1,052.4
1,161.6
1,269.6
1,342.8
1,452.0
42.0
60.0
79.2
112.8
150.0
186.0
223.2
279.6
345.6
420.0
465.6
559.2
652.8
728.4
811.2
886.8
979.2
1,119.6
1,212.0
1,352.4
1,492.8
1,632.0
1,725.6
1,866.0

Va=3.5m/s
38.9
56.2
73.4
105.1
139.7
174.2
208.8
260.6
322.6
391.7
434.9
522.7
609.1
679.7
757.4
828.0
914.4
1,045.4
1,131.8
1,262.9
1,393.9
1,523.5
1,611.4
1,742.4
50.4
72.0
95.0
135.4
180.0
223.2
267.8
335.5
414.7
504.0
558.7
671.0
783.4
874.1
973.4
1,064.2
1,175.0
1,343.5
1,454.4
1,622.9
1,791.4
1,958.4
2,070.7
2,239.2

Note
1. Operating condition - Steam pressure: 0.35kg/ G - Air temperature at the inlet of the coil: 15 DB
- Steam pressure: 2.0kg/ G - Air temperature at the inlet of the coil: 11 DB
2. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch
3. Same heat transfer area condition and two row basis.
ACE R & A

27

www.aceind.co.kr

Va=4.0m/s
46.7
67.4
88.1
126.1
167.6
209.1
250.6
312.8
387.1
470.0
521.9
627.3
730.9
815.6
908.9
993.6
1,097.3
1,254.5
1,358.2
1,515.5
1,672.7
1,828.2
1,933.6
2,090.9
60.5
86.4
114.0
162.4
216.0
267.8
321.4
402.6
497.7
604.8
670.5
805.2
940.0
1,048.9
1,168.1
1,277.0
1,410.0
1,612.2
1,745.3
1,947.5
2,149.6
2,350.1
2,484.9
2,687.0
[table 27]

Thermo Hygrostat

Va=2.5m/s
27.0
39.0
51.0
73.0
97.0
121.0
145.0
181.0
224.0
272.0
302.0
363.0
423.0
472.0
526.0
575.0
635.0
726.0
786.0
877.0
968.0
1,058.0
1,119.0
1,210.0
35.0
50.0
66.0
94.0
125.0
155.0
186.0
233.0
288.0
350.0
388.0
466.0
544.0
607.0
676.0
739.0
816.0
933.0
1,010.0
1,127.0
1,244.0
1,360.0
1,438.0
1,555.0

Heat Recovery
System

Va=2.0m/s
22.5
32.5
42.5
60.8
80.8
100.8
120.8
150.8
186.7
226.7
251.7
302.5
352.5
393.3
438.3
479.2
529.2
605.0
655.0
730.8
806.7
881.7
932.5
1,008.3
29.2
41.7
55.0
78.3
104.2
129.2
155.0
194.2
240.0
291.7
323.3
388.3
453.3
505.8
563.3
615.8
680.0
777.5
841.7
939.2
1,036.7
1,133.3
1,198.3
1,295.8

Slim Type Air


Handling Unit

Va=1.5m/s
18.8
27.1
35.4
50.7
67.4
84.0
100.7
125.7
155.6
188.9
209.7
252.1
293.8
327.8
365.3
399.3
441.0
504.2
545.8
609.0
672.2
734.7
777.1
840.3
24.3
34.7
45.8
65.3
86.8
107.6
129.2
161.8
200.0
243.1
269.4
323.6
377.8
421.5
469.4
513.2
566.7
647.9
701.4
782.6
863.9
944.4
998.6
1,079.9

Direct Expansion Type


Air Handling Unit

AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0300
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1350
AA1450
AA1600
AA1750
AA1850
AA2000
AA0045
AA0065
AA0085
AA0120
AA0160
AA0200
AA0240
AA0350
AA0370
AA0450
AA0500
AA0600
AA0700
AA0780
AA0870
AA0950
AA1050
AA1200
AA1300
AA1450
AA1600
AA1750
AA1850
AA2000

Ceiling Type Air


Handling Unit

Air velocity through the coil

Model

Fan

0.35

Heating performance ( 1,000 kcal/h)

Built-Up Unit

Steam
pressure
(kg/cm2 G)

Fan Dry Coil Unit

Performance table of steam coil

Air Handling Unit

ACE Air Conditioning System

Air Handling Unit

Selection of the chilled flow rate


Basic specification
1. Model : AA0300
2. Air volume : Qa = 18,000m3/h
3. Cooling capacity : Ht = 135,000Kcal/hr
4. Flow rate : Qw = 450 /min
5. Inflow water temperature : tw1 = 7
Sequ
ence

Item

Sym
bol

Tf l
l
Circulation air wet bulb temperature Tr
Dry bulb temperature
DB1
Wet bulb temperature
WB1
Dew point temperature
DP
Inlet air heat transfer quantity
h1

Coil inlet

Coil outlet

Fresh air wet bulb temperature

Outlet air heat transfer quantity

6. Fresh air dry bulb temperature : Tf = 32


7. Fresh air relative humidity : RHf = 65%
8. Circulation air dry bulb temperature : Tr = 26
9. Circulation air relative humidity : RHr = 50%
10. Ratio between fresh air quantity and the circulation air quantity : ( 30% , 70% )

h2

Wet bulb temperature

WB2

Coil surface temperature

tc

Sensible heat ratio

Coil outlet dry bulb


temperature

DB2

Coil face area

FA l
FA

Calculation formula
When Tf = 32 , RHf = 65%
When Tr = 26 , RHr = 50%
Tf 0.3 + Tr 0.7
Tf l 0.3 + Tr l 0.7
When DB1 = 27.8 , WB1 = 21.
When WB1 = 21
Ht
h1 Qa 1.2
When h2 = 8.3kcal/kg
1/2 (tw1 + WB2)

26.5
18.7
Psychrometric
32 0.3 + 26 0.7 = 27.8
chart
26.5 0.3 + 18.7 0.7 = 21
17.7
14.7kcal/kg
135,000
14.5 = 8.3kcal/kg
18,000 1.2
12.2
1/2 (7+12.2) = 9.6
hc = 6.8kcal/kg
0.24(27.8-9.6)
= 0.57
14.5-6.8
(14.5-8.3) 0.57
= 13.1
27.8 0.24
18,000 (2.5 3,600)=2.0m2
1.995m2
Table 18
30 Pass 1740L
18,000 (1.995 3,600) = 2.51m/s
Coil Circuit
H.C.= 0.5
450 (30 1)=15 /min
S.C.= 1
O.H.C.= 1.5
D.C.= 2
135,000
7+
= 12
450 60 1

Coil pass-through wind speed

Va

0.24(DB1-tc)
0.24(DB1-DB2)
=
h1-hc
h1-h2
(h1-h2)R
(h1-h2)
DB1= DB1(DB1-tc)
0.24
(h1-hC)
Qa (2.5 3,600)
Modified by the Coil, Table
Coil Pass X effective length
Qa (FA 3,600)

Flow rate per tube

Vq

Qw

Outlet water temperature

tw2

10

Heat transfer coefficient

K
tc1

DB1 - tw1

27.8 - 7 = 20.8

11

Air inlet dry bulb temperature


- inlet water temperature
Air inlet dew point temperature
- inlet water temperature
Coefficient on the surface of the coil

tc2

DP - tw1

17.7 - 7 = 10.7

6
Coil dimension

12

13

Cws

t1
Large temperature difference
Small temperature difference
t2
Logarithmic Mean Temperature Mtd
Number of rows

(Pass

Circuit)

Ht
Qw 60 Cw
Vq = 15 /min
When Va = 2.51 m/s
tw1 +

tc1 = 20.8

K = 885kcal/h

When tc2 = 10.7

DB1 - tw2

FA K

Table 29

13.1 - 7 = 6.1
When t2 = 6.1

1.995 885 1.38 10.2


N = 6Row

28

Table 30

10.2
135,000

Cws MTD

ACE R & A

Table 31

Cws = 1.38

Ht
N

m2 Row

27.8 - 12 = 15.8

DB2 - tw1
t1 = 15.8

Reference
table

Calculation

www.aceind.co.kr

= 5.4Row
Table 28

Basic specification

Coil outlet dry bulb temperature DB2


FA l
FA

Coil face area


3
Coil dimension
4

Coil pass-through wind speed

Va

Flow rate per tube

Vq

Outlet water temperature

tw2

Heat transfer coefficient

t1
Large temperature difference
t2
Small temperature difference
Logarithmic Mean Temperature Mtd

Number of rows

Tf

0.2 + Tr 0.8
Ht
DB1 +
a Cp Qa
Qa (2.5 3600)
Modified by the Coil, Table
Coil Pass X effective length
Qa (FA 3,600)

0.2 + 21 0.8 = 14.6


150,000
14.6+
= 43.54
1.2 0.24 18,000
18,000 (2.5 3,600) = 2.0m2
1.995m2
30 Pass 1,740L
18,000 (1.995 3,600) = 2.51m/s

(-11)

(number of pass X
Circuit X number of stack)

Qw

Ht
Qw 60 Cw
Vq = 16.67 /min
Va = 2.51 m/s
tw2 - DB1
tw1 - DB2
t1 = 40.2
When t2 = 16.5
tw1 -

FA

Reference
table

Ht
K MTD

500

(30 1

1) = 16.67 /min

150,000
= 55
500 60 1
K = 910kcal/h .m2.Row

Table 18

COIL Circuit
H.C. = 0.5
S.C. = 1
O.H.C. = 1.5
D.C. = 2

60 -

55 - 14.6 = 40.4
60 - 43.5 = 16.5
26.69
150,000
= 3.1Row
1.995 910 26.69
N=4Row

Table 31

Table 30

Table 28

0~2.00

2.01~4.00

4.01~6.00

6.01~8.00

8.01~10.00

10.01~12.00

10

12
<table 28>

Fan Dry Coil Unit

Calculated number
of rows
Number of
rows that are
actually used(Row)

Fan

Conversion table for number of rows that are actually used

Heat Recovery
System

Coil inlet dry bulb temperature DB1

Calculation

Slim Type Air


Handling Unit

Calculation formula

Direct Expansion Type


Air Handling Unit

Sym
bol

Item

Ceiling Type Air


Handling Unit

Sequ
ence

5. Fresh air dry bulb temperature : Tf = -11


6. Circulation air dry bulb temperature : Tr = 21
7. Inlet water temperature : Tw1= 60
8. Ratio between fresh air quantity and the circulation air quantity : ( 20% , 80% )

Built-Up Unit

1. Model: AA0300
2. Air volume : Qa = 18,000m3/h
3. Heating capacity : Ht = 150,000Kcal/h
4. Flow rate : Qw = 500 /min

Thermo Hygrostat

Selection of the hot flow rate

Air Handling Unit

ACE Air Conditioning System

ACE R & A

29

www.aceind.co.kr

Air Handling Unit

Logarithmic Mean Temperature


difference Mtd

Wet coil coefficient of the coil surface (Cws)

1t(

40 37.5
35.0
32.5
30.0
27.5
25.0
22.5
20.0
17.5
15.0
12.5
10.0
7.5
5.0

30
25
20
15
10
5

Inlet air dry bulb temperature


- Inlet water temperature( )

Inlet air dew point temperature


-Inlet water temperature( )

45 42.5
35

1.1

1.2

1.3

1.4

1.5

1.6

1.7

(Wet coil coefficient of the coil surface)

Mtd(

t2( )

30

30

30

25

25

25

20

20

20

15

15

15

10
9
8
7
6(60)
5(50)
4(40)
3(30)
2(20)
1(10)

10
9
8
7
6(60)
5(50)
4(40)
3(30)
2(20)
1(10)

[table 29]

MTD=

(Exam
water ple of chille
d
coil se
lection
)

(Example of hot water


coil selection)

10
9
8
7
6(60)
5(50)
4(40)
3(30)
2(20)
1(10)

t1- t2
2.3log ( t1/ t2)

[table 30]

Chilled water, hot flow rate heat transfer coefficient

N=

5.0

Ht
K

Cws FA MTD

4.5

4.0
3.5

Heat transfer coefficient k


(kcal/h m2Row)

3.0

2.5

2.0

Wind speed
1.5m/s

Flow rate per tube ( /min)


[table 31]

ACE R & A

30

www.aceind.co.kr

ACE Air Conditioning System

Coil inlet dry bulb temperature

DB1

Coil outlet dry bulb temperature DB2

Required temperature difference


Coil face area

t
FA l
FA

Coil dimension
5
6
7

Coil pass-through wind speed


Saturated steam temperature
Coil correction factor

Va
ts
f

Final outlet temperature

td

(Actual coil air temperature difference)(Theoretical coil air temperature difference)

tl

Calculation formula
Tf 0.33+Tr 0.67
Ht
DB1 +
a Cp Qa
DB2 - DB1
Qa (2.5 3,600)
Modified by the Coil, Table
Coil Pass X effective length
Qa (FA 3,600)
When Ps = 2kg/cm2 G
When Ps = 2kg/cm2 G, ta1 = 11
When N = 2, Va = 2.51
DTB f + ta1

(-11.3)

(td-DB1)- t

(67.9-11)-34.92=21.98

Ht1 =
10

Number of rows

a Cp

Reference
table

Calculation
0.33+22 0.67 = 11
181,000
11+
= 45.92
1.2 0.24 18,000
45.92 - 11 = 34.92
18,000 (2.5 3,6000) = 2.0m2
1.995m2
30 Pass 1,740L
18,000 (1.995 3,600) = 2.51m/s
133
1.285
DTB = 44.3
44.3 1.285+11= 67.9

Qa (td - DB1)

Compare Ht and Ht1,


and then decide if they appropriate

1.2 0.24 18,000


= 294,970kcal/h
181,000 < 294,970
N = 2Row

(67.9-11)

100
104
107
113
116
120
127
133
143
151
158
164
170
175
183

Latent heat
( kcal/kg )
539
536
534
531
528
526
521
517
510
504
499
494
490
486
479

Fan

0
0.2
0.35
0.6
0.8
1.0
1.5
2
3
4
5
6
7
8
10

Table 33

Built-Up Unit

Temperature
( )

Table 32
Table 24

tl >0

Steam saturation temperature by pressure Temperature increase of the steam coil (


and table of vaporization latent heat
Gage pressure
(kg/ G)

Table 18

Heat Recovery
System

Sym
bol

Direct Expansion Type


Air Handling Unit

Item

Ceiling Type Air


Handling Unit

Sequ
ence

5. Latent heat of vaporization : rs = 517Kcal/Kg


6. Fresh air dry bulb temperature : Tf = -11.3
7. Circulation air dry bulb temperature : Tr = 22
8. Ratio between fresh air quantity and the circulation air quantity : ( 33% , 67% )

[table 32]

ACE R & A

[table 33]

31

www.aceind.co.kr

Fan Dry Coil Unit

1. Model : AA0300
2. Air volume : Qa = 18,000m3/h
3. Heating capacity : Ht =181,000 Kcal/h
4. Steam pressure : Ps = 2Kg/cm2G

Slim Type Air


Handling Unit

Basic specification

Thermo Hygrostat

Air Handling Unit

Selection of the steam coil

Air Handling Unit

Weight table by model


H Type

HR Type

[figure 7]

Basis of the weight calculation


1. Glass Wool insulation, AL Model Frame basis
2. Weight below is machine weight
Type/
Part
Model
AA0045

Air
volume
(CMH)
2,700

AA0065

(kg)

HR Type

H Type
Mixing &
Filter Part

Coil Part

Fan Part

Return Fan Mixing(EA) Mixing(OA)


Coil Part
Part
Part
& Filter Part

Total
Weight

Supply
Fan Part

Total
Weight

90

162

252

505

252

59

61

162

244

779

3,900

122

193

300

616

282

80

84

193

290

929

AA0085

5,100

138

218

361

717

320

90

93

218

347

1,068

AA0120

7,200

165

262

392

819

355

106

108

262

375

1,207

AA0160

9,600

207

319

504

1,030

392

126

132

319

479

1,448

AA0200

12,000

226

367

548

1,141

420

134

142

367

523

1,586

AA0240

14,400

253

430

645

1,328

515

149

157

430

616

1,867

AA0300

18,000

297

487

748

1,533

631

169

180

487

718

2,185

AA0370

22,200

357

554

802

1,713

761

214

220

554

772

2,521

AA0450

27,000

419

659

958

2,036

825

249

258

659

918

2,910

AA0500

30,000

442

707

973

2,123

843

262

270

707

935

3,018

AA0600

36,000

545

829

1,177

2,551

1,003

331

340

829

1,138

3,641

AA0700

42,000

604

1,101

1,386

3,091

1,187

364

372

1,101

1,333

4,537

AA0780

46,800

668

1,208

1,444

3,319

1,413

404

406

1,208

1,383

4,813

AA0870

52,200

728

1,276

1,666

3,670

1,471

429

438

1,276

1,599

5,213

AA0950

57,000

822

1,433

2,103

4,358

1,691

506

508

1,433

2,011

6,143

AA1050

63,000

897

1,506

2,153

4,555

1,779

548

554

1,506

2,069

6,454

AA1200

72,000

948

1,640

2,256

4,844

1,822

572

581

1,640

2,179

6,794

AA1300

78,000

1,045

1,751

2,798

5,595

2,284

639

640

1,751

2,696

8,010

AA1450

87,000

1,197

2,831

2,686

6,714

2,346

723

732

2,831

2,578

9,211

AA1600

96,000

1,291

2,939

2,707

6,938

2,445

801

807

2,939

2,604

9,596

AA1750

105,000

1,422

3,196

3,258

7,875

2,791

875

880

3,196

3,115

10,858

AA1850

111,000

1,527

3,373

4,107

9,006

3,010

935

942

3,373

3,903

12,163

AA2000

120,000

1,640

3,576

4,134

9,349

3,115

1,027

1,030

3,576

3,935

12,682
[table 34]

ACE R & A

32

www.aceind.co.kr

ACE Air Conditioning System

L
(mm)

Header
(A)

Inlet
(A)

Copper coated fin Number of coil fins:


Header material:
0.8th
Air Vent, Drain V/V

Circuit Direction Remark


of tube

8FPI
10FPI
Black tube
White tube
Copper tube(L)

12FPI
Copper tube(K)

Special considerations for ordering

Nominal Steel tube Copper tube


diameter (mm)
(mm)
25A
34.0
28.58
32A
42.7
34.92
40A
48.6
41.28
50A
60.5
53.98
65A
76.3
66.68
80A
89.1
79.38
100A
114.3
104.78

Stands for the standard specification of the company


Flow
rate

Row

Pass

FH
(mm)

L
(mm)

Header
(A)

Inlet
(A)

Outlet
(A)

H1 Direction
Remark
(mm) of tube

Ceiling Type Air


Handling Unit

Caloric
Air
Equipment
volume value
number
(CMM) (Kcal/h)

10FPI
12FPI
White tube Copper tube(K)
Including the pairing flange

Nominal Steel tube Copper tube


diameter
(mm)
(mm)
25A
34.0
28.58
32A
42.7
34.92
40A
48.6
41.28
50A
60.5
53.98
65A
76.3
66.68
80A
89.1
79.38
100A
114.3
104.78

Special consider
ations for ordering

Fill in the blanks (air volume, caloric value, etc. as many as possible). Check box for optional specifications must be marked with

ACE R & A

33

www.aceind.co.kr

Copper tube(L)
Air Vent,Drain V/V

for the corresponding item.

Fan

8FPI
Black tube
Flange

Built-Up Unit

Flat coil
Number of coil fins:
Copper coated fin Header material:
0.8th
Additional item:

Fan Dry Coil Unit

Gradient coil(Non-freezing Coil)


General AL Fin Coated fin Copper fin
0.7th
0.5th
0.6th

Reference drawing

Coil category:
Coil Fin material:
Copper tube thickness:

Reference dimension

Equipment order
and Quantity

Steam coil

Optional
specification

Outlet
(A)

Thermo Hygrostat

Coated fin
Copper fin
0.6th
0.7th
Including the pairing flange

FH
(mm)

Heat Recovery
System

Pass

Slim Type Air


Handling Unit

General AL Fin
0.5th
Flange

Row

Reference dimension

Coil Fin material:


Thickness of the copper tube:
Additional items:

Flow
rate

Direct Expansion Type


Air Handling Unit

Stands for the standard specification of the company

Air
Caloric
Equipment
volume
value
number
(CMM) (Kcal/h)

Reference drawing

Optional
specification

Equipment order
and Quantity

Cold and hot flow rate

Air Handling Unit

Order specification sheet for heat exchanger (Coil)

Air Handling Unit

Order specification sheet for air handling unit


* For ordering, the corresponding items must be marked with
Contact our sales department for questions.

Item

Insulator
External board

Return

Supply

Internal board

5. Fan

Optional specification

ACE standard

1. Type of AHU
2. Installation
3. Power source specification

4. Casing

or required specifications need to be written down.

Drain Pan
Air volume
Static pressure
Type
Model X Quantity
Air volume
Static pressure
Type
Model X Quantity
Motor location

Horizontal type(Al Mold)


Indoor
380V-60Hz
G/W-40K x 50T
Cold & painting (color :
SGCC 0.6T(perforation)

STS 1.5T+P.EF 15TH insulation


CMH / CMM
mmAQ
Air Foil(ACE Fan)
CMH /
CMM
mmAQ
Sirocco(ACE Fan)
Built-in AHU

Fan Option

7. Coil

Heating

Cooling

6. Isolator

Displacement
Type
Cooling capacity
Condition of air
Condition of cold water
Type
Heating capacity
Condition of air
Condition of hot water
Option
Direction of tube
COIL material
and standard
Pre

Medium
8. Filter
Special

Advanced
9. Humidifier

Type
Humidification
quantity

10. Damper

11. Option

Anti-freezing
heater
Lamp
Sight Glass
Heat exchanger
Etc.

1"(housing type)
Chilled water coil

Vertical type
Complex type
Other (Frame, artilon)
Outdoor
Pinch Roof required (cold & painting STS)
220V-60Hz
440V, 480V
50Hz
G/W-40KX25T
Artilon-50T
Polyurethane foam -50T
G/W-[
]K X [ ]T
Other-[
]
SGCC 1.6T
PCM color coated steel plate
STS
Galvalume
SGCC 0.6T(plain plate)
SGCC 0.8T(plain plate)
STS 0.6T(plain plate)
Other-[
]
SGCC 0.8T(perforation)
STS 0.6T(perforation)
STS 1.5T+G/W insulation Cold & painting +G/W artilon insulation Other-[
]

Specified domestic brand-[


Other model and quantity-[

Specified domestic brand-[


Other model and quantity-[
External AHU
Variable pulley (motor side)

2"
D.X Coil

3"
Relife Coil

Specified overseas brand-[


X EA]

Sirocco

Specified overseas brand-[ ]


Air Foil
X EA]
Including isolator base
Inlet Vane (Worm gear mounted not mounted)
Automatic grease injector (manual electronic)
Open type
Specified brand[
]

kcal/h
Inlet DB :
InletWB :
Inlet :
Outlet :
Common coil for cold and hot water Separate hot water Steam coil Electric coil Anti-freezing damper coil(hot water steam)
kcal/h
Inlet DB:
Inlet :
Outlet :
Steam pressure in case of steam coil 2kg/cm2 1kg/cm2
0.35kg/cm2 Other[ ]kg/cm2
Pre-heating coil (steam hot water) Pre-cooling coil Supply of tube flange
Eliminator-material SGCC+AL Eliminator-material STS
Supply of pairing flange
Left side
Right side
Both sides
CU Tube 0.5T
0.6T
0.7T
0.8T
STS
Al Fan 0.14T(Plate)
AL coated fin
Copper fin
Copper coated fin
STS Aero
Steel tube(black tube)
Copper Header Steel tube(white tube)Header
STS Header
AFI 82%(KPS-4000N,20TH)
AFI 85%(25TH) NBS 30%(50TH) Unpowered electrostatic type 1"(AFI 85%)
AFI 70%(DEMISTER)
Auto Roll Filter [AFI %]
Auto washing anti-fungus filter(AFI 80%)
Auto Clean Filter[AFI %]
NBS 85%(3")
NBS 60-65%
80-85%
90-95% (3" Mini Pleat thin type basis)
NBS 60-65%
80-85%
90-95% (12" Cell Type basis)
NBS 60-65%
80-85%
90-95% (12 18 22 30 36"Bag Type basis)
Brand not specified
Unpowered electrostatic type 2"(AFI 95%, NBS 40%)
[Maker :
]
Brand not specified
Auto washing electric dust collector (NBS 85~90%)
[Maker :
]
Brand not specified
Two-stage electrostatic type electric dust collector (NBS 85~90%) [Maker :
]
Brand not specified
Charged corpuscle neutralization device [Pre :
,Med :
] [Maker :
]
Brand not specified
Hepa[DOP %]
Ulpa[ %]
Bio-Clean
UV Lamp
Carbon(MAT TRAY)
Chemical Filter
Steam Injection
Steam Grid [Maker:
]
Including Control Valve
kg/h
Electrode type [Maker: ]
Evaporation type(thickness of filter media:50 100TH)
Water Spray Type
Pan Type(electric type)
Air Tight(AL+AL)
General damper (SGCC+SGCC)
Air Tight(AL+SGCC)
Other
Electric Heater [ ]Kw, (single phase or three phase), (voltage : 220V, 380V, V)
Control Panel(based on integrated heater type)
Control Panel(separate heater type)
Wiring for each section
Integrated wiring
Controlled by the Heater Control Box
Round shape double window ( 250)
Square (100 X 150TH)
Squared double window(100 X 150TH)
Sensible heat heat transfer exchanger [air volume: ]
30%
100%
Refer to other data selection required
Rotary heat transfer exchanger Plate type sensible heat exchanger Plate type heat transfer exchanger Heat pipe
Ladder installation
U-Trap installation
Common Base supply
Silencer installation
Air Mixer installation
Air Blender installation
Damper Actuator supply
Other additional comment:

* Inlet size : width [ ] X height [ ]

* When brand is specified, write down the brand of the component you request.

ACE R & A

34

www.aceind.co.kr