Capacitor Division Ref : CAP/QND/H/13-14/0161/RKM PARTICULARS 1. Nominal System Voltage 2. Maximum operational Voltage 3. Frequency 4. Rating of APFC in KVAr 5. Step Configuration CAPACITOR SUB -BANK RATING 1. Rated Voltage KV 2. Rated Output, KVAr 3. Rated Current , Amps 4. No. of phases 5. Insulation Level ( KV rms / KV peak ) 6. No. of Banks / Units 1. 2. 3. 4. 5. 6. 7. 8. 1. 2. 3. 4. 5. Type of Banks Connection Terminal Arrangement Series Group per phase Units in parallel per Series group per phase Finish Busbar Material Overall Dimensions Dielectric and Impregnant No. of Bushings Discharge device to Discharge to 50 Volts in less than 600 Sec. Unit Protection Allowable Overloads

ANNEXURE- I
TECHNICAL PARTICULARS OF HT - APFC SYSTEM SPECIFICATION 11KV 12.65KV 50Hz 18000 KVAr

1800kVArX2 Fixed step + 1800 kVAr X 8 variable step


BANK RATING UNIT RATING 12.65 7.3 1800 200 82.15 27.39 03 01 28/75 28/75 10 10 X 09 BANK DETAILS : (i)Outdoor (ii) Sheet Steel Enclosure(IP-55) : Single Star : Detachable Cable Gland Plate Provided : One : : Three

RAL-7032 : Aluminium : To be furnished in the event of order. UNIT DETAILS : All Polypropylene Impregnated with non PCB oil : Two : Discharge Resistors provided. : :

External HRC Fuses. 110% of rated voltage or 130% of rated current or 130% of rated output 6. Losses : 0.2 Watts / KVAr 7. Creepage distance : 25 mm/KV 8. Dimensions : To be furnished in the event of order ASSCIATED EQUIPMENTS 1. Switching Device : Vacuum Contactor 2. Incomer : Off load Isolator 3. Series Reactor : 0.2% Air Cored, Dry Type, Single Phase 4. RVT : 11 KV, Dry Type, PROTECTION 1. Over Current & Earth Fault X Recommended as marked X to be provided by customer. 2. Over Voltage X 3. Under / No Voltage with 600 Sec Timer X 4. Unbalance RVT Provided Capacitors confirm to IS-13925/1998 (superseding the old IS: 2834-1986) having upper limit of temperature category of 50 C and for use up to 1000M above the sea level and suitable for 50 HZ.
For UNIVERSAL CABLES LIMITED
UNIVERSAL CABLES LTD
P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31 Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688 Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Ref : CAP/QND/H/13-14/0161/RKM

Annexure II

GENERAL TECHNICAL PARTICULARS OF VACUUM CONTACTOR Sr. No. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Applicable standard Make Type Number of poles, nos. of break/pole Rated Voltage Rated maximum voltage Rated normal current Rated single capacitor banks current Frequency Impulse with stand voltage Main circuit to earth & between poles Across terminals in open position 11. One minute power frequency withstand voltage Main circuit to earth & between poles Across terminals in open position 12. 28 kV 28 kV 75 kV 75 kV IS:9920:85 EPCOS/CGL/ABB/Jyoti Indoor, Vacuum Three, One 11 KV 12 KV 400 Amp 50 Amp 50 Hz Particulars Specifications

One minute power frequency withstand voltage on auxiliary circuit 2.5 KV to earth

13. 14. 15. 16.

Operating Mechanism Release Coil Voltage Qty. (Nos.)

Solenoid type Spring Solenoid 220 V AC -1-Phase 03 Nos./Step

For Universal Cables Ltd

UNIVERSAL CABLES LTD


P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31

Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688

Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Ref : CAP/QND/H/13-14/0161/RKM

Annexure III

General Technical Particulars of Series Reactors


Reactor shall be suitable to be connected in series with capacitor bank on the Neutral side for suppressing switching inrush currents. The reactor shall be dry type and shall be suitable for Indoor installation and shall have other particulars as mentioned below. A B C D Reference standard Type of Reactor Rated Voltage & Frequency No. Of phase : IS : 5553 : Air Cored, Dry Type : 11 KV, 50Hz : Single : : : : : 1800KVAr 0.177 14.54 1.2 82.15 :130 % of rated current : 70 Deg. C by resistance method : 28 KV rms./ 75 KV Peak : Terminal Pads provided : Base Insulators : All routine test, except intern/impulse test carried out as per IS:5533 : Class F

Capacitor Sub-Bank rating E F G H I J K L M N O Per phase reactance, Ohms Per phase voltage drop, volts Rated output, KVAr Rated current, Amp Max. Continuous current Temperature rise Basic insulation Level Terminal arrangement Accessories for Reactors Testing Other details i) Class of insulation

ii) Rated short time symmetrical RMS Current: 16.66 times the rated current for 2 Sec. iii) Winding materials P Quantities (Nos.) : : Aluminium 03Nos./Step

For Universal Cables Ltd


UNIVERSAL CABLES LTD
P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31 Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688 Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Ref : CAP/QND/H/13-14/0161/RKM

Annexure IV

GENERAL TECHNICAL PARTICULARS FOR RESIDUAL VOLTAGE TRANSFORMER Sr. No. 1. 2. Reference Standard Type Particulars IS: 3156 Indoor & Dry Type, Resin Cast 5 Limb Construction 3. 4. 5. 6. 7. Rated primary voltage Frequency No. of secondary windings Ratio Rated burden per phase & Accuracy class a) Metering Winding ( Star) b) Protection Winding ( Open Delta) 8. 9. Method of connection Insulation level a) One minute power frequency withstand voltage b) Impulse with stand voltage (1.2x50 micro sec. wave, crest) 75 KV (Peak) 28 KV (RMS) 100 VA 0.5 100 VA 3P Star / Star - Open Delta 11KV 50 Hz Two 11000V /110-190 V Specifications

10. 11.

Voltage Factor Terminal Arrangement 1) HV Side 2) LV Side

1.2 Conti. & 1.9 For 30 Sec.

4 Nos. Terminal for R,Y,B&N Terminal Box. 01 No./Panel

12.

Quantity (Total)

FOR UNIVERSAL CABLES LIMITED


UNIVERSAL CABLES LTD
P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31 Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688 Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Ref : CAP/QND/H/13-14/0161/RKM

ANNEXURE- V

Technical Comments
Sl. No. 1. 2. 3. We have quoted for capacitor bank as per the specification and following are the point wise comments / deviations:Clause No. of Specification 4.0 11.0 18.0 Our Comments Please note that capacitors offered by us are suitable for temperature category of 50 Deg C. as against 60 Deg asked by in specification. As desired, we have included six nos. of spare HRC fuses in our scope and price of same has been considered in price of APFC panel. Ammeter with selector switch shall be provided in C&R panel of VCB which is not in our scope and therefore same has not been considered in ACU. APFC relay has a provision of showing ON/OFF status of capacitor banks and therefore separate indicating lamps are not considered. Control equipments and associate circuitry shall be suitable for ambient temperature range of 0 to 50 Deg. C. These clauses calls for use of outdoor type Capacitor switches with mechanical indicators, porcelain bushings etc to be used whereas clause No. 43 calls for use of Vacuum contactors. We note that asked APFC system is Pad mounted, we have therefore considered vacuum contactors for switch purpose and accordingly we are commenting relevant clauses. Clause No. 33.3 to 33.6 are not applicable for vacuum contactors. Offered vacuum contactors are suitable for switching of capacitive current of 400 A, Operating mechanism of Vacuum contactor shall be solenoid operated. Mechanical & Electrical endurance mentioned in specification shall be at 200 A capacitive current at low voltage. We have quoted for outdoor type 11KV,630 Amps, double break off load type , triple pole, gang operated, with earth switch Isolator & 9kV, 5 kA station class lightning arrestors a/w elevating frames . We have not quoted for VCBs, same shall be provided by you. We have offered for lightning arrestor as mentioned above sr no.9 We have not quoted for 11 kV HT XLPE cable, Cable jointing kits, control cables in our scope of supply.

4. 5.

21.0 24.0 to 36.2

6. 7. 8. 9.

28.0 34.0 35.0 38.0

10. 11 13.

39.0 41.0 46.0

UNIVERSAL CABLES LTD


P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31

Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688

Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

As per our understanding complete scheme is as shown below:-

APFC Relay CT ,PT signals


APFC Relay

V.C.B.
Off Load Isolator. RVT Vaccum contactor. Capacitor bank Series Reactor 8 X1800 KVAr Variable step 2X1800 kVAr fix step

LA

CRCA sheet steel thickness of Capacitor cubicle shall be of 2. 0 mm Necessary control signals of CT & PTs from load end and control voltage shall be provided by customer. All foundation bolts, civil work etc are not included in our scope of supply General technical details HV APFC Enclosure

The panel shall be Painted processed with seven tank, Outdoor type conforming to suitable grade protection. Gland plate will be provided at the bottom for cable entry of suitable size.. The protection class shall be IP 55.

Cooling Arrangement: Cross Air Flow fans shall be provided for effective cooling of the panels. Top shall be provided with suitable canopy for effective cooling. Dust Filtering:
UNIVERSAL CABLES LTD
P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31 Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688 Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Dust Filters are provided to avoid ingress of dust & vermin inside the Panel. Drawings : We shall provide three sets of GA and internal wiring diagrams. Test Certificates : We shall provide test certificates of the panel as well as the major components. Power Cable: Power Cable for connecting the APFC Panels to the electrical system ( HT Panel/ Transformer) shall be supplied by the Customer.

For UNIVERSAL CABLES LIMITED

UNIVERSAL CABLES LTD


P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31

Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688

Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

UNIVERSAL CABLES LIMITED


A COMPANY OF M P BIRLA GROUP

Ref : CAP/QND/H/13-14/0161/RKM General Construction Of MV Capcitor Panels

ANNEXURE- VI

Enclosure Cubicle, hinged type doors, fabricated by 14/16swg crca sheet. Painted & Powder Coated. Bus bar Electrical grade Copper of suitable sizes , bolted with spring Washers, bus bar supporters. Power termination above 63 amp shall be made by using bus bar of suitable rating. Instrument label Label for danger, bus bar, cableway, on/ off etc. Wiring Wiring by copper wire of suitable rating as per IS 8623-1977 with proper lugs & ferule as per requirement of the drawing. Main supply 415v, 3 phase 4 wire,50 HZ. Control supply 230v Ac single phase, 50 HZ. Testing Panel will undergo following testing prior dispatch Functional test. H.V.test at 5 K.V. Load run test (at rated load) Tripping & meter collaboration test if applicable.

For Universal Cables Ltd

UNIVERSAL CABLES LTD


P O: Birla Vikas Satna MP India 485005 Ph: +91 7672 257121 to 27 Fax: +91 7672 257136 / 31

Mumbai : +91 99701 53690 Chennai : +91 98407 54741 Delhi : +91 98100 70570 Kolkata : +91 94330 17753 Bangalore : +91 93422 79994 Raipur : +91 99262 22688

Baroda : +91 98258 15744 Bhopal : +91 97526 52001 Hyderabad : +91 98490 38799 GOA : +91 98221 02787 Allahabad : +91 94153 07784

AN ISO 9001 ORGANISATION

SERVING THE NATION SINCE 1962.

Você também pode gostar