Should the Medium Voltage switchgear being supplied without the CTs installed, the 3 CTs must be mounted the same side up to the busbar.
MV network management Phase to phase and/or phase to earth self powered fault passage indicators
Easergy range
+
11 12 13 14 15 16 1718 19 20
Flair 21D Flair 21DT with SCADA interface Flair 22D with SCADA interface and embedded battery Flair 23D with SCADA interface and external power supply
Users manual
CT connection card
+
BVP option Outdoor lamp with embedded battery
L1
L2
L3
1 2 3 4 5 6 7 8 9 10
21D Flair
x10
Phase CTs
Zero sequence CT: option for Flair 22D and 23D only Nota: do not connect a CT on L1 (3 and 4) when a zero sequence CT is connected
22D Flair
Publishing: Schneider Electric Production: Graphme Printing: Imprimerie des Deux-Ponts 01/2005
Raccordements
Si linterrupteur Moyenne Tension na pas t fourni avec les tores installs, monter les 3 tores dans le mme sens sur les 3 cbles MT.
Gestion des rseaux lectriques MT Indicateurs de passage de courant de dfaut phase-phase et/ou phase-terre autoaliment
Gamme Easergy Flair 21D Flair 21DT avec interface SCADA Flair 22D avec interface SCADA et pile intgre Flair 23D avec interface SCADA et alimentation extrieure
Manuel utilisateur
11 12 13 14 15 16 1718 19 20
+
Option BVP Botier Voyant extrieur Pile incorpore
L1
L2
L3
1 2 3 4 5 6 7 8 9 10
21D Flair
x10
Tores phase
Tore homopolaire (option pour Flair 22D et 23D) N.B. : ne pas raccorder de tore sur L1 (bornes 3 et 4) lors de lutilisation dun tore homopolaire
22D Flair
Publication : Schneider Electric Ralisation : Graphme Impression : Imprimerie des Deux-Ponts 01/2005
Operation
Indicators Flair 21D, 21DT, 22D and 23D are self-powered from the measurement. A minimum 3 A current is required in the MV cable to start up the Flair 21D and 21DT LCD display, an energy storage guarantees a 4 hours minimum autonomy. The indicators provide an output SCADA contact (except Flair 21D: transistor output). Flair 22D includes a lithium battery for a permanent display operation (in case of a load current less than 3 A during 4 hours) and for the outdoor lamp supply. Flair 23D has to be supplied from 12 Vdc to 48 Vdc (with a single zero sequence CT self powering is not possible.
DE55459 DE55458
Settings
Settings are performed using dip-switches (all version): press the (1) button to validate and front panel push buttons (Flair 22D and 23D only); these settings replacing those of the dip-switches.
21D Flair
x10
(2)
(3)
(1)
In order to display the settings (all version) or to modify the settings (Flair 22D and Flair 23D), enter the test/settings mode. The test mode is activated followed by the setting display mode, act as follow: b Flair 21D and Flair 21DT: press the (1) button. b Flair 22D and Flair 23D: press twice the (1) button (the first impulse activates the maximeter display mode). b The LED (3) blinks, up to the test completion. b The display shows successively: Flair 21D : then then (version) Flair 21DT : Flair 22D :
22D Flair
L1
8.0
080
(2)
If I < 3 A
Io
Flair 23D : (version) b The whole settings are scrolled and 10 s after the last one is displayed, the indicators returns to ammeter display mode. With a single press on the (1) button during the scrolling returns to the ammeter display mode.
21 d xx then then 21 db xx (version) then bESb 22d then Vxx bESb then 23d then Vxx
(version)
b Maxmeter function (Flair 22D and 23D only): Press once the (1) button to get access to the maxmeter function. For each phase, the maximum load current since the last reset is displayed. Example for a 500 A maximum in phase 1: then , then M2 and M3. The maximeter values are scrolled only once. The 3 maximeters are reset all together by pushing the (4) and (5) buttons during the scrolling. Should Flair 22D and Flair 23D fitted with zero sequence CT, M2 and M3 only are displayed.
Ml
500
Setting scrolling
b CTs mounting (Flair 22D and Flair 23D only) , or , or (23D only) ( = phase CT and = zero sequence CT) b Network frequency (example 50 Hz) Flair 22D/23D: b I > threshold (example 600 A) Flair 21D/21DT: then , Flair 22D/23D: b I 0 > threshold (example 80 A) Flair 21D/21DT: then , Flair 22D/23D: If the dip-switches 3, 4 and 5 are on OFF position, no earth fault detection, display: Flair 21D/21DT: then , Flair 22D/23D: b Reset timer (example 2 hours) Flair 22D and Flair 23D only: b Automatic reset Flair 21D/21DT: then or , Flair 22D/23D: or
L l L2 L3
OC
L2
ooo
ooO OC EF EF Ar
--O o
Fr.5O
OC
6O 8 oF oF
I 600 80 o FF
Maintenance
b Detectors Flair 21D, 21DT and 23D require no maintenance (no periodic battery replacement). b Flair 22D lithium battery has to be changed once every 15 years approximatively. b Option BVP (external light indicator with battery): battery life time 15 years approximatively.
b.O2H
on
Ar.oF
Ar.on
Fonctionnement
Les indicateurs Flair 21D, 21DT, 22D et 23D sont autoaliments par les capteurs de mesure. Pour la mise en fonction de lafficheur des Flair 21D/21DT, un courant minimum de 3 A est ncessaire dans la ligne, une rserve dnergie assure une autonomie de 4 h. Le Flair 21DT possde un contact relais de sortie. Le Flair 22D intgre une pile au lithium pour assurer le fonctionnement permanent de lafficheur (si le courant de ligne est infrieur 3 A depuis plus de 4 h) et lalimentation du BVE. Le Flair 23D doit tre raccord une alimentation de 12 Vcc 48 Vcc pour assurer le fonctionnement permanent de lafficheur (si l < 3 A depuis plus de 4 h) et lalimentation du BVE (le montage type C, monotore, ne permet pas lautoalimentation).
DE55459 DE55458
Rglages
Sur tous les Flair, les rglages seffectuent grce aux microinterrupteurs : modifications prises en compte aprs appui sur le bouton (1). Sur les Flair 22D et 23D, on peut obtenir un rglage plus prcis, laide des boutons de face avant, ces rglages se substituant ceux des micro-interrupteurs.
21D Flair
x10
(2)
(3)
(1)
(2)
b Fonction ampremtre : en absence de dfaut, une indication du courant de charge est affiche (2). Lintensit de chaque phase dfile successivement prcde de son repre : L 1 - L 2 - L 3. Les valeurs de courant affiches doivent tre multiplies par 10 pour le Flair 21D et 21DT. Exemple pour un courant de charge de 80 A : puis (Flair 21D/21DT) ou (Flair 22D/23D), puis ensuite L2 et L3. Quand Flair 22D/23D sont quips dun tore homopolaire, le courant L1 est remplac par le courant de dsquilibre : Pour I >720A (Flair 21D/21DT), (Flair 22D/23D)
Pour visualiser les rglages (tous modles) et les modifier (Flair 22D et Flair 23D), passer en mode test/rglage. Le mode test suivi du dfilement des rglages est activ par : b Flair 21D et Flair 21DT : appuyer sur le bouton (1). b Flair 22D et Flair 23D : appuyer 2 fois sur le bouton (1) (la premire impulsion active le mode maximtre). b Le voyant (3) de lindicateur clignote, jusqu la fin du test. b Lafficheur indique successivement : Flair 21D : puis puis (version) Flair 21DT : Flair 22D :
DE55460
L1
8.0
080
Pour I < 3 A
Flair 23D : (version) b Puis, sur tous les Flair, lensemble des rglages dfilent et lindicateur repasse en mode ampremtre 10 s aprs laffichage du dernier rglage (un appui sur le bouton (1) permet de revenir immdiatement au mode ampremtre).
21 d xx puis puis 21 db xx (version) bESb puis 22d puis Vxx bESb puis 23d puis Vxx
(version)
b Fonction maximtre (sur Flair 22D et 23D uniquement) : Pour accder la fonction maximtre, appuyer une fois sur le bouton (1). Une indication des courants de charge maximum par phase depuis la dernire remise zro est affiche. Exemple pour un courant max. de 500 A dans la phase 1: puis , puis ensuite M2 et M3. Les maximtres ne dfilent quune seule fois. Toutes les valeurs des maximtres sont remises zro par action simultane sur les boutons (4) et (5) pendant le dfilement. Quand Flair 22D et Flair 23D sont quips dun tore homopolaire, affichage de M2 et M3 uniquement.
L l L2 L3
L2
OC
ooo
ooO OC EF EF Ar
--O o
Fr.5O
OC
6O 8 oF oF
I 600 80 o FF
Maintenance
b Les dtecteurs Flair 21D, 21DT et 23D ne ncessitent aucune maintenance (ni piles ou batteries changer priodiquement). b La pile au lithium du dtecteur Flair 22D est changer environ tous les 15 ans. b La pile au lithium de loption BVP (Botier Voyant extrieur Pile incorpore) est changer tous les 15 ans.
b.O2H
on
Ar.oF
Ar.on