Escolar Documentos
Profissional Documentos
Cultura Documentos
Vol 27 / 1
January 2008
An American Fire Sprinkler
Association Publication
SprinklerAge
Vol 27 / 09
September 2008
An American Fire Sprinkler
Association Publication
Reliables
Reliables
NewEvolution of
NewEvolution of
RFC49
RFC49 F1 RES 76
F1 RES 76
Residential Flat Plate Concealed sprinkler
K Factor of 4.9
Combines attractive appearance with (13mm)
of cover adjustment for ease of installation
Refer to Technical Bulletin 006
Largest K Factor on the market today
K Factor of 7.6
For design densities of .05 and .10
Available as pendent, recessed pendent and CCP
Refer to Technical Bulletins 135 and 176
1.800.431.1588
www.reliablesprinkler.com
The Reliable Automatic Sprinkler Co., Inc.
Manufacturer & Distributor of Fire Protection Equipment
RELIABLE ONE SOURCE
For all your fire protection needs.
Residential
Residential
Sprinklers
Sprinklers
Weve expanded our Residential product line
with TWONEWSPRINKLERS!
Sprinkler Spacing
ft. (m)
Minimum Required Sprinkler
Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
13 (49)
13 (49)
13 (49)
17 (64.3)
20 (75.7)
7.0 (0.48)
7.0 (0.48)
7.0 (0.48)
12.0 (0.83)
16.7 (1.14)
With these two new sprinklers,
Reliable continues to have the
best combinations of K Factors
for NFPA-13, 13R & 13D
Residential Applications
Reliables
Reliables
NewEvolution of
NewEvolution of
RFC49
RFC49 F1 RES 76
F1 RES 76
Residential Flat Plate Concealed sprinkler
K Factor of 4.9
Combines attractive appearance with (13mm)
of cover adjustment for ease of installation
Refer to Technical Bulletin 006
Largest K Factor on the market today
K Factor of 7.6
For design densities of .05 and .10
Available as pendent, recessed pendent and CCP
Refer to Technical Bulletins 135 and 176
1.800.431.1588
www.reliablesprinkler.com
The Reliable Automatic Sprinkler Co., Inc.
Manufacturer & Distributor of Fire Protection Equipment
RELIABLE ONE SOURCE
For all your fire protection needs.
Residential
Residential
Sprinklers
Sprinklers
Weve expanded our Residential product line
with TWONEWSPRINKLERS!
Sprinkler Spacing
ft. (m)
Minimum Required Sprinkler
Discharge
Flow
gpm (Lpm)
Press.
psi (bar)
12 x 12 (3.6x3.6)
14 x 14 (4.3x4.3)
16 x 16 (4.9x4.9)
18 x 18 (5.5x5.5)
20 x 20 (6.0x6.0)
13 (49)
13 (49)
13 (49)
17 (64.3)
20 (75.7)
7.0 (0.48)
7.0 (0.48)
7.0 (0.48)
12.0 (0.83)
16.7 (1.14)
With these two new sprinklers,
Reliable continues to have the
best combinations of K Factors
for NFPA-13, 13R & 13D
Residential Applications
800.786.5266 www.tolco.com
FM approved it.
TOLCO makes it.
California OSHPD Approved
TOLCO brings you a superior seismic bracing system that is
FM approved as well as:
Expertise you can count on
Innovative designs that promote labor savings
Technology that exceeds the industrys highest standards
Discover the benets of advanced seismic protection when
you use TOLCO.
TOLCO
800.786.5266 www.tolco.com
FM approved it.
TOLCO makes it.
California OSHPD Approved
12 Sprinkler Age | September 2008
800-PUMP 13D
The D System
A complete pre-wired factory
assembled unit
Installs in 3 easy steps
Meets NFPA quality standards
Components UL approved
The D Cono Line
New super affordable systems
Tanks available to fit
through 29 doorway
Your Best Value In Residential
Water Delivery Systems
D System Patent #4366865
800. 786. 7133
800-PUMP 13D
www. t hedsyst em. com
HF_AD 12/15/05 1:07 PM Page 1
Reed Manufacturing Company
1425 West 8th Street, Erie, PA 16502 USA
Telephone: 800-666-3691 or 814-452-3691
Fax: 800-456-1697 or 814-455-1697
www.reedmfgco.com
Pipe Tools & Vises
Since 1896
Cutters & Cutter Wheels
Groovers, Power Drives, Threaders & Dies
Vises
Clean Room Tools
Water Services Tools & Machines
Plastic Pipe Tools
Large Diameter Pipe Tools
Wrenches
General Pipe Working Tools
C
h
e
c
k
o
u
t
R
e
e
d
's
N
e
w
5
3
0
1
P
D
P
o
w
e
r
D
r
iv
e
!
An often forgotten and overlooked
design requirement for foam systems
is the requirement of the least
remote calculation. The 2007
edition of NFPA 16, Standard for the
Installation of Foam-Water Sprinkler
and Foam-Water Spray Systems;
7.4.2.2 requires that two sets of
hydraulic calculations be provided;
(1) a most remote hydraulic calcula-
tion and (2) a least remote hydraulic
calculation (both balanced to the
available water supply). In the design
of all fire sprinkler system, we utilize
the most remote calculation to
examine pressure losses and deter-
mine pipe sizes.
In the event of a fire in the most
remote area of a foam system, you
would have adequate pressure and
foam to achieve the design criteria,
but what if there was a fire much
closer to the water source? You would
certainly expect to have enough
pressure, but will you have enough
foam to last for the required duration
of the fire?
Tis scenario underlines the importance
of the least remote calculation, which is
the proper way to determine the actual
amount of foam required for the system.
Since the least remote calculation may
discharge more than the most remote
calculation, you may run out of foam
before the desired duration (20 minutes
in our example) if you used the most
remote area to determine the amount of
foam for the system.
The following example shows a
standard tree system with 6-in. cross
Foam Systems
Least Remote Calculations
RANDY NELSON | VFS Fire & Security Services
13 Sprinkler Age | September 2008
Figure 1. A standard tree system with 6-in. cross mains and 2-in. branch lines with heads spaced at 80 ft
2
throughout the system.
mains and 2-in. branch lines with
heads spaced at 80 ft
2
throughout the
system. (See Figure 1 above.) Using
the criteria in Figure 2 (below), we
can see that the total discharge for
the most remote area is 1,975 gpm
which would require 1,185 gallons of
foam (three percent concentration) to
satisfy a duration of 20 minutes,
however the total discharge for the
least remote area is 2,150 gallons
which would require 1,290 gallons of
foam (three percent concentration)
for the same duration.
This example shows that if you used
only the most remote area to dictate
the amount of foam for the system
you would be short 105 gallons of
foam or about nine percent.
Therefore, considering the valuable
assets that are typically protected by
foam systems, it doesnt make sense
to take on any additional risk or
liability because you are short one
more calculation and you didnt
supply a few more gallons of foam. n
ABOUT THE AUTHOR: Randy Nelson is
president of VFS Fire & Security Ser-
vices in Anaheim, Calif. He is a princi-
pal member of the NFPA 16 Technical
Committee for Foam-Water Sprinkler
and Foam-Water Spray Systems.
Figure 2. Foam systems comparative calculation at base of riser.
RESIDENTIAL FIRE SPRINKLER SYSTEM
INSTALLATION GUIDE RELEASED!
If you are thinking about getting into the residential
sprinkler market - or you already are but want to
become more effective, AFSA has a new fre sprinkler
ftter correspondence training program for you and your
employees Residential Fire Sprinkler System Installation.
Member price: $250
Non-Member price: $500
(Price includes online testing. Add $50 for paper testing option)
For more information, call (214) 349-5965 or
to order, visit AFSA online at www.fresprinkler.org
14 Sprinkler Age | September 2008
Complete fabricating services, including threading, grooving, welding, and end of pipe preparation for black or galvanized material.
Available with Viking SupplyNets complete line of fire protection products for a complete, single-source solution for any project.
Accurate, on-time delivery to virtually any location through Viking SupplyNets fleet of delivery vehicles.
Fabricated pipe is clearly and systematically marked, then bundled for easy installation at the job site.
From the smallest project to the largest endeavor,
its the one contact that gets the job done.
Nine Locations Serving the United States
East
147 Lincoln Drive
Hometown, PA 18252
Phone: (570) 668-4686
Fax: (570) 668-4688
vfshometown@supplynet.com
4593 Carolina Avenue
Richmond, VA 23222
Phone: (804) 228-1107
Fax: (804) 228-1556
vfsrichmond@supplynet.com
South
100 Piedmont Court, Suite A
Doraville, GA 30340
Phone: (770) 446-3068
Fax: (770) 446-3713
vfsatlanta@supplynet.com
West
6480 Box Springs Boulevard
Riverside, CA 92507
Phone: (951) 656-3111
Fax: (951) 656-2606
vfsriverside@supplynet.com
625 E. Watkins Street
Phoenix, AZ 85004
Phone: (602) 252-0400
Fax: (602) 252-2134
vfsphoenix@supplynet.com
12360 E. 46th Avenue #400
Denver, CO 80239
Phone: (303) 576-0665
Fax: (303) 576-0611
vfsdenver@supplynet.com
5081 Kelton Way, Suite 100
Sacramento, CA 95838
Phone: (916) 923-1080
Fax: (916) 923-1748
vfssacramento@supplynet.com
Midwest
640 Center Avenue
Carol Stream, IL 60188
Phone: (630) 462-5860
Fax: (630) 871-1898
vfschicago@supplynet.com
2353 International Street
Columbus, OH 43228
Phone: (614) 527-5800
Fax: (614) 527-5818
vfschicago@supplynet.com
Viking Fabrication Services
www.vikinggroupinc.com
Trusted above all.
TM
AFSAs informal interpretations are provided by AFSA Vice
President of Engineering & Technical Services Roland
Huggins, a P.E. registered in fre protection engineering; Phill
Brown, a NICET IV certifed automatic sprinkler technician
and NFPA Certifed Fire Protection Specialist (CFPS); and
Tom Wellen, a degreed fre protection engineering technolo-
gist. Tese opinions are provided for the beneft of the
requesting party, and are provided with the understanding
that AFSA assumes no liability for the opinions or actions
taken on them.
Subject: Water Velocity in Water Spray Systems
QUESTION: Even though NFPA has no specifc require-
ments for maximum water velocity in fre sprinkler systems,
some AHJs impose seemingly arbitrary maximum water
velocity limits, sometimes as low as 15 feet per second. What is
the impact of water velocity on sprinkler systems?
ANSWER: We have reviewed the 2007 editions of NFPA 13 and
NFPA 15 as the applicable standards. Our informal interpretation is
that except for water-spray systems, NFPA standards do not restrict
the water velocity for sprinklers and the impact of velocity does not
warrant any restriction. Tere are two aspects of hydraulics afected
by water velocity; one is the accuracy of the Hazen-Williams
equation for hydraulic calculations and the other is the impact on
water fow from a sprinkler (or branch line). Te accuracy of
Hazen-Williams was thought to break down at high-water velocities
(such as 32 ft/s). Te Hazen-Williams and Darcy-Weisbach formula
calculations were compared and the fndings were presented in an
article in Sprinkler Age, Pressure Velocity Part I: Defnition
Special Hazard
Situation?
Informal Interpretations Can Help
Complete fabricating services, including threading, grooving, welding, and end of pipe preparation for black or galvanized material.
Available with Viking SupplyNets complete line of fire protection products for a complete, single-source solution for any project.
Accurate, on-time delivery to virtually any location through Viking SupplyNets fleet of delivery vehicles.
Fabricated pipe is clearly and systematically marked, then bundled for easy installation at the job site.
From the smallest project to the largest endeavor,
its the one contact that gets the job done.
Nine Locations Serving the United States
East
147 Lincoln Drive
Hometown, PA 18252
Phone: (570) 668-4686
Fax: (570) 668-4688
vfshometown@supplynet.com
4593 Carolina Avenue
Richmond, VA 23222
Phone: (804) 228-1107
Fax: (804) 228-1556
vfsrichmond@supplynet.com
South
100 Piedmont Court, Suite A
Doraville, GA 30340
Phone: (770) 446-3068
Fax: (770) 446-3713
vfsatlanta@supplynet.com
West
6480 Box Springs Boulevard
Riverside, CA 92507
Phone: (951) 656-3111
Fax: (951) 656-2606
vfsriverside@supplynet.com
625 E. Watkins Street
Phoenix, AZ 85004
Phone: (602) 252-0400
Fax: (602) 252-2134
vfsphoenix@supplynet.com
12360 E. 46th Avenue #400
Denver, CO 80239
Phone: (303) 576-0665
Fax: (303) 576-0611
vfsdenver@supplynet.com
5081 Kelton Way, Suite 100
Sacramento, CA 95838
Phone: (916) 923-1080
Fax: (916) 923-1748
vfssacramento@supplynet.com
Midwest
640 Center Avenue
Carol Stream, IL 60188
Phone: (630) 462-5860
Fax: (630) 871-1898
vfschicago@supplynet.com
2353 International Street
Columbus, OH 43228
Phone: (614) 527-5800
Fax: (614) 527-5818
vfschicago@supplynet.com
Viking Fabrication Services
www.vikinggroupinc.com
Trusted above all.
TM
16 Sprinkler Age | September 2008
A 2250 gallon tank will t through a standard doorway
and assemble to full size capacity inside.
More information on all products is available
on our newly designed website: www.rewatersystemsinc.com
INDOOR & OUTDOOR MODULAR & STANDARD FIBERGLASS WATER TANKS
Phone: 800-381-0801 Fax: 717-234-3474
Complete systems of pumps, tanks and components available separately
Tanks come in all different congurations and are rated for potable water
Call for more information on our complete line of site water systems
Lowest Prices in the Industry
All individual pump components are listed and/or approved
Modular Tanks to Fit Through Small Spaces
Aboveground tanks : 108 to 12,000 gallons
Underground tanks: 900 to 24,000 gallons
Hydraulic Calculations for NFPA 15, Water Spray Fixed Systems
by Roland J. Huggins, P.E., November 1996. In summary, the
results varied signifcantly by pipe size and material, so no pattern
was detected. Te largest deviation took place with 1-in. Schedule
40 steel pipes, which had a 22 percent variance at 40 ft/s, but in real
numbers presented a diference of only 0.6 psi. In comparison,
4-inch schedule 40 varied only 0.08 psi at 40 ft/s. Te most
important aspect about this is that a fow of 108 gpm is required to
obtain 40 ft/s in 1-in. pipe. Tis is an immense amount of water for
such small pipe, resulting in a friction loss of 2.2 psi/ft. Very few
water supplies can tolerate a 22 psi friction loss in only 10 ft of pipe.
Te bottom line is that in regards to the accuracy of hydraulic
calculations, friction loss alone provides sufcient control on water
velocity. Te second aspect is the impact of velocity on fow from a
sprinkler. Typically, hydraulic calculations use total pressure (P
t
) for
determining fow from a sprinkler. Technically, the fow is a result of
normal pressure (P
n
) that is the total pressure minus velocity
pressure (P
v
). Recently, NFPA 15 changed such that hydraulic
calculations for water spray systems must account for velocity
pressure. Tere is an exception to this requirement; if P
v
does not
exceed fve percent of P
t
, it can be ignored. Te concern is if P
v
is
high, the actual fow from the sprinkler may be inadequate. Tere
have been cases, in water spray systems, where sprinklers near the
riser had virtually no fow. Tis is an issue for some water spray
systems because diferent nozzles and/or orifce sizes are allowed
across a system to balance the fow. Since this practice is not allowed
in NFPA 13 systems, the impact of water velocity is greatly reduced.
It comes down to a balancing act between friction loss (F
L
) and
velocity pressure. Its not uncommon, though, for P
v
to slightly
exceed F
L
for the second head up from the end of a branch line. At
frst glance, this could be perceived as a problem, but it is ofset by
the fact that the overall system demand (for both pressure and fow
rate) based on the P
t
method is higher than that for the P
v
method.
For example, I ran the calculations using both methods for the same
system and found the demands to be: P
t
- 283.8 gpm at 51.0 psi P
v
- 267.5 gpm at 48.2 psi. Te higher overall demand of the P
t
method is generally sufcient to cause the sprinklers identifed as
defcient by the P
v
method to actually exceed the minimum
required density. In closing, there is not a technical reason for
imposing a restriction on velocity so NFPA 13 does not restrict
water velocity.
Subject: Differing Orice Sizes on a Water-Spray
System
QUESTION: Te installation plans were rejected since K-4.2
orifce heads were used along with K-5.6 orifce heads. Is it the
intent to have all the fre sprinkler orifces the same size for a
open head foam system?
ANSWER: In response to your question, we have reviewed the 2007
edition of NFPA 16, Standard for the Installation of Foam-Water
Sprinkler and Foam-Water Spray Systems, as the applicable standard.
Our informal interpretation is that not all sprinkler orifce sizes have
to be constant for this application. Te hydraulic design for
foam-water deluge system refers to NFPA 15, Standard for Water
Spray Fixed Systems for Fire Protection. Section 8.1.1 states Hydrau-
lic calculations shall be conducted as part of the design of the piping
system to determine that the required pressure and fow is available
at each nozzle. Since this application is an open head foam-water
deluge system, all the sprinklers operate. Te system has to be
designed to provide a reasonably uniform foam and water distribu-
tion over the coverage area. When water fows through a piping
network, pressure changes result throughout the system due to
friction, turbulence, and elevation changes. Terefore, the pressures
acting at each sprinkler in the design area can vary, resulting in
diferent fows at each sprinkler. Te uniform foam application is
accomplished by sizing pipes and sprinkler orifces to accomplish
the hydraulic design. Te comment concerning the difering orifce
sizes may have originated from NFPA 13 that generally prohibits
the use of fre sprinklers with difering orifce sizes. Te concern was
that if sprinklers with various orifce sizes are used and if some of
those sprinklers have to be replaced at a future date, a sprinkler with
a difering orifce size might be installed. An example where
difering orifces can be used is if a room is protected with extended
coverage sprinklers that have a nominal K-factor of 8.0. However,
the space under a 3-ft wide soft also needs to be protected. Because
the areas under the softs are so small, the use of a smaller orifce
sprinkler can be used. In summary, the design of the system should
be according to NFPA 16 and 15 standards that permit the use of
difering orifce sizes. n
EDITORS NOTE: As noted in at the beginning of this article, these
interpretations were prepared by AFSAs Technical Services De-
partment in answer to specific questions from contractors and/
or AHJs. These opinions are provided for the benefit of the request-
ing party, and are provided with the understanding that AFSA as-
sumes no liability for the opinions or actions taken on them.
This program is available in all states, except Delaware. Some restrictive
coverage and limits may apply in certain states for residential exposures.
2005 Copyright Construction Insurance Solutions. All Rights Reserved
Are you having difficulty insuring your residential or
commercial operations? Facing coverage reductions?
At RISC, Inc. we have the tools of the trade to protect
your business. Backed by an insurance carrier with
excellent financial strength, we can cover your general
liability and umbrella needs providing you with the
peace of mind you deserve. This program is available
through your local agent we can even contact them
on your behalf. You get a comprehensive national
program with the convenience of local service.
For more information
call RISC, Inc. at 1-800-725-7472
or visit our Web site at www.gorisc.com
We have answers.
Have Questions?
Have Concerns?
We have solutions.
Endorsed By
TM
18 Sprinkler Age | September 2008
Te 27th Annual Convention & Exhibi-
tion of the American Fire Sprinkler
Association (AFSA), AFSA in D.C.: A
Capitol Experience, is almost upon us! Tis
years event will be held October 15-19,
2008, at the Marriott Wardman Park Hotel
in Washington, D.C. Tis annual trade-
show boasts the worlds largest gathering of
fre sprinkler professionals, drawing some
1,400 participants from around the globe.
Tis years event features over 30
diferent sessions and countless network
opportunities including an exclusive
private event at the renowned Smithso-
nian Air and Space Museum. Its not too
late to attend North Americas largest
industry show exclusively tailored to the
needs of fre sprinkler contractors of
every size. Registration for the conven-
tion will be available onsite.
D.C. is a vibrant, accessible and world-
class city with everything from inspiring
monuments to monumental arts and
culture, and together with AFSAs
industry-leading show, it promises to be
one trip you wont want to miss! For
details, visit www.fresprinkler.org or call
(214) 349-5965. n
Dont Miss This
Capitol Experience
AFSAs 27th Annual Convention & Exhibition
Opens Soon
Always a great show, this years exhibition is bigger than ever, with a sold-out hall featuring 165 booths.
19 Sprinkler Age | September 2008
NCCER has partnered with construct-
Net International (cNI), Phoenix, Ariz.,
to provide online instructional language
resources for the construction industry
to help bridge the language barrier
between employers and employees.
Te frst series titled, Construction
English for the Spanish Speaker, contains
fve courses. Tese courses will cover
basic terminology related to employ-
ment, employability skills, construction,
and safety. Te frst course in this series,
Introduction to Construction English I,
will be available in September. Other
courses in this series are Introduction to
Construction English II, Intermediate
Construction English I and II, and
Advanced Construction English. Tese
courses are expected to be released
throughout 2008 and 2009.
Tis program is designed to improve
communication at work sites between
Spanish-speaking and English-speaking
employees. Whether asking for tools or
clarifying instructions, employees will learn
key phrases and increase vocabulary in an
easy-to-learn online format. Participants can
log in anytime and anywhere there is access
to a computer and the Internet. An
orientation on how to use the computer
and the Internet is also included.
A second series titled, Construction Spanish
for the English Speaker, consists of one
course aimed at foremen, supervisors, crew
leaders, and administration and is
estimated to be available in fall 2008. Te
primary purpose of this course is to ensure
clear communication between all parties
involved to ensure safety at the job site.
Safety and productivity are a priority for
contractors, and the language barrier is a
large factor contributing to construction-
related injuries and
fatalities, says Don
Whyte, NCCER presi-
dent. With the increas-
ing number of Hispanics
entering the industry, we
must do everything we
can to create a safe
working environment on
our job sites.
NCCER has also devel-
oped other Spanish-based
curricula and assessment
resources. Visit www.
nccer.org. n
Online Courses Bridge
Language Barrier
NCCER Partners With cNI
A screenshot from NCCER/cNIs online Construction English for the Spanish
Speaker series.
20 Sprinkler Age | September 2008
Tere are a variety of fre protection
systems available today, from traditional
sprinkler and high-pressure water mist
systems to chemical and inert gas clean
agent systems. Inherent in these systems
are particular advantages and limita-
tions, depending upon the hazard
application.
In June of this year, Victaulic launched
the worlds frst hybrid water-based inert
gas system: the Victaulic Vortex Fire
Suppression System. Trough a propri-
etary patented technology, this total
fooding solution combines nitrogen gas
and water to extinguish fres without
damaging property or using toxic agents.
Applications for the system include data
centers, automotive manufacturing,
industrial and power generation facilities.
Less Water, Smaller Droplets Te
engineering team at Victaulic spent
more than four years creating a product
that would conquer the limitations of
fre suppression systems currently on
the market. One objective was to
reduce the required water volume,
while simultaneously maximizing heat
absorption efciency. To achieve this
objective, a new high-velocity atomiza-
tion method was developed, producing
a homogeneous mixture of miniscule
water droplets and nitrogen gas,
propelled with enough energy to
overcome the drag efect which limits
the efectiveness of traditional water
mist systems. Te hybrid water and
nitrogen gas mixture travels at high
velocity to reach the fuel source and
overcome any fre plume resistance.
Figure 1. Victaulic Vortex emitter piping for water and nitrogen.
Victaulic Vortex is First Hybrid
Water-Based Inert Gas System
New Fire Suppression System Unveiled
ANTHONY GEE | Victaulic
21 Sprinkler Age | September 2008
Te small droplet size, velocity of the
hybrid mixture and minimal amount of
water dispersed diferentiate the Victau-
lic Vortex system from other technolo-
gies. Traditional sprinklers typically
release greater than 25 gallons of water
per minute per sprinkler, depending on
system design, with droplets generally
greater than 1,000 microns in size.
Te average Victaulic Vortex droplet size
is dramatically smaller at around 10
microns and the amount of water
released per emitter is also much less: as
little as one gallon per minute. Tis
virtually eliminates noticeable wetting of
the protected space, a critical beneft to
minimize property damage.
Supersonic Aerodynamics For the
Victaulic Vortex system piping, the
delivery of water and nitrogen requires
minimal pressure at the Victaulic Vortex
patented emitter. Te emitter has been
developed based upon the aerodynamics
of supersonic aircraft wing design.
Within the emitter, supersonic nitrogen
fow is transformed to subsonic velocity.
Tis produces a series of shock waves which
atomize water injected through the emitter.
Once the water is atomized in the nitrogen
stream, the blended (homogeneous)
mixture is projected from the emitter at
high velocity and at great distances. Each
emitter can cover 2,500ft
3
/70m
3
.
Te nitrogen and water mist function as
complementary extinguishing agents. Te
nitrogen serves as the primary extinguish-
ing agent in small, smoldering fres by
reducing the oxygen level in the enclosure
to where the air remains breathable but
combustion cannot be sustained. In larger
fres, the water mist is more efective as the
extinguishing media, cooling the fre by
Figure 2.Typical single-zone system design. Fully compatible with building detection and security systems.
Figure 3. Typical multi-zone system design. System scalability provides design flexibility and accommodates
changes in hazard protection needs.
What is YOUR Business
Doing To Be As Competitive
As It Can Be?
Fire protection contractors
may not realize the impact that
changes in regulations and
technology have on
their bottomline.
INCREASE REVENUE
Contractors who have trained
their employees on the latest
technology can often leverage
that skill to be more competitive
in the bid process.
DECREASE COSTS
Those contractors often see a
jump in accurate designed and
quality of work, resulting in
fewer change orders or rework.
Tyco now offers 2 & 3 day fire
protection training seminars
with CEU credit in Cranston, RI.
TRAINING
TRAINING
www.tyco-fire.com
401-781-8220 ext. 500
Training@TycoFP.com
TOPICS INCLUDE:
Changes in Technology
Hands On Experience
Live Demos
Industry Direction
22 Sprinkler Age | September 2008
heat absorption and reducing available
oxygen at the fre by generating steam as
the droplets evaporate.
Agency fre testing was conducted in large
rooms (up to 125,000 ft
3
) with 8 ft x 8 ft
doors open allowing airfow and leakage of
agent from the room. Te results demon-
strated successful fre extinguishment
scalability to enclosures larger than any tests
previously conducted at Factory Mutual.
Additionally, the Victaulic Vortex Fire
Suppression System has demonstrated
the capability of extinguishing all fre
scenarios of NFPA 750 and NFPA 2001
even though this hybrid fre suppression
system is neither a pure water mist
system nor a clean agent system.
Sustainable and 90 Times More
Effective Since the Victaulic Vortex
system only deploys water and non-toxic
Nitrogen, system activation is immediate
upon detection of a fre hazard without
concern for exposing human occupants of
the space to any health danger from the
fre suppression system. Te system is
designed to make sure there is always
sufcient breathable oxygen in the
protected space while reducing it to a level
where the fre will extinguish. Addition-
ally, the large number of small droplets
produced by the Victaulic Vortex system
creates a heat-absorbing water droplet
surface area 90 times that of a standard
sprinkler system, providing signifcantly
higher heat absorption efciency.
Te Victaulic Vortex system has been
recognized by the EPA as a non-toxic
replacement for Halon 1301 in total
fooding applications.
Simple Design and Maintenance
Victaulic Vortex system design is modular
and straight-forward, based upon the
calculation of cubic feet/cubic meters per
hazard. Actual placement of emitters and
piping is fexible and single or multi-zone
layouts are possible.
Te system operates on a potable or
distilled water supply, as well as local
sources of Nitrogen. In environments
where electrical hazards are present,
de-ionized water may be used. System
maintenance is less than other technologies
currently available as the system can be
tested without water discharge, minimizing
the disturbance of the protected environ-
ment. Savings is also seen in the rapid reset
of the system after discharge, minimizing
facility downtime. Te low impact of
installation and system features make the
Victaulic Vortex an extremely cost-efective
fre suppression system option for new
construction and retroftting.
Minimal Wetting, Reduced Water
Damage Minimal wetting of the
protected space is an important beneft,
particularly in spaces housing electronic
equipment, such as data centers or
irreplaceable works like museums or
libraries. After system discharge, residual
moisture is barely detectible. Te reduced
amount of water discharged in such fne
particles creates a dew-like residue, as
compared to the hundreds of gallons of
water typically dispersed by sprinklers or
high-pressure mist systems.
Scalability Te Victaulic Vortex system
ofers scalable design, allowing for single or
multiple zones of hazard coverage and
integration with other facility systems such
as hazard detection and security. Tis
minimizes retroft impact and allows the
system to adapt to changes in space layout
and coverage requirements.
Te Victaulic Vortex Fire Suppression
System, built upon more than 80 years of
Victaulic innovation and product
development, provides the best capabili-
ties of both water mist and inert gas
systems. Te ease of design, minimal
wetting, and fre suppression features give
the Victaulic Vortex system numerous
advantages over existing systems. Visit
www.victaulicvortex.com. n
ABOUT THE AUTHOR: Anthony Gee is product
manager, Vortex for Victaulic. He has 24 years
experience in special hazards fire protection
system design, engineering, project manage-
ment, business development and marketing.
Gee has a Bachelors degree in mechanical en-
gineering. He has a diverse project background
in various vertical markets, including projects
such as the Canadian Hibernia Production
Platform, European Eurotunnel Channel Tunnel
Shuttle Trains and Locomotive Fire & Gas De-
tection and Suppression Systems, and the U.S.
Navy Arleighe Burke Guided Missile Destroyer
Program Fire Alarm Systems.
Wheeler Manufacturing
Division of Rex International U.S.A., Inc.
US Toll Free: 800-321-7950 Fax: 440-992-2925
e-mail: wheeler@wheelerrex.com www.wheelerrex.com
Grooves 1" 6" pipe
Mounts fast, no need to remove carriage
Short lengths stay on pipe without help
Fast, easy T-handle feed
Fits Wheeler-Rex models 6090, 7090 & 6790
Fits Ridgid
and
Rothenberger
Patented
U
L
LISTED
AQT 1.5 hp-15 hp
Inquire at your local distributor today!
Toll-Free (800) 327-3552
Phone: (630) 377-1750 Fax: (630) 377-0274
4N944 Old LaFox Road, Box 359,Wasco, IL 60183
Email: sales@pace-asp.com Web: www.pace-asp.com
2003 Pace Machinery Group. Ridgid is a registered trademark of the Ridge Tool Co.
Specifications
Weight.................. Just 19 pounds
Capacity............... 1-14 " 6" Schedule 40 or
thin-wall steel pipe
Tools Required.... Included multi-function
Ratchet Action Hand Crank is
all you need.
Hex Drives........... All 15 16"
Construction....... Heavy duty
Compatibility ...... Chucks in a Ridgid 300
The rugged self-contained
portable roll-groover that
is two tools in one!
Face it. Time is money. Especially when youre up in the
air. Now Pace, the industry leader has got a tool that
can eliminate hassles in the air and save you lots of
time and money.
The NEW PACE 1039 Mini-Mite Roll Groover service
tool goes from in-place grooving to machine grooving in
one motion without the need of spending valuable time
looking for tools. The PACE 1039 Mini-Mite is
self-contained, it can be entirely operated with
its own multi-function Ratchet Action Hand
Crank so there are no other tools needed!
The PACE 1039 Mini-Mite is totally portable. It features
rugged construction with a larger top roller bearing,
heavier top slide, and more material in the housing to
make for more durability.
And all hex drives on the PACE
1039 Mini-Mite are 15 16"
so one wrench ts
everything!
The PACE 1039 Mini-
Mite is simple to
operate. It rolls grooves
in 1-1 4" to 6" Schedule 40 or thin wall steel pipe on the
scaffold or anywhere power is unavailable. It also has the
ability to chuck in a Ridgid 300 in just seconds. (No
gearbox removal.)
In a Ridgid 300 In a ceiling application
Two Tools In One!
N
E
W
&
I
M
P
R
O
V
E
D
!
32 Sprinkler Age | September 2008
Tere was once a beer commercial that
used to talk about a mysterious group
of little people called the Artesians. Te
name was a take of on the beer
companys use of Artesian wells that
supposedly consisted of the purest of
well waters. As I recall the commercial,
the location was in Tumwater, Wash.
and the commercial always talked
about the fact that no one ever saw the
Artesians but that their work was
embedded in the quality of their brew.
I have a little surprise for you. You have
a group of people in your town who are
like those Artesians. You may not even
know where they are, but they are there
none the less. Tey are called Ucale-
gons. In the past you have met many
of them but didnt know what they
were called. You merely called them
fre victims. You might wonder, what
is the diference?
Te answer is found in the depths of
etymology. Etymology is the study of
the origins of words. Ucalegon was one
of the elders of Troy, whose house was
set on fre by the Achaeans when they
sacked the city. If you have read the
Iliad or the classic Aeneid, you will fnd
references to his name. He was a very
close friend to Priam, who was the
King of Troy. For many years, the word
Ucalegon was a noun that meant a
neighbor whose house was on fre or
had burned down. Apparently, it was
possible to be a fre victim over 2,000
years ago, and receive sympathy from
others. So it would appear that nothing
has really changed.
Or has it? Te prospect of a persons
home burning to the ground today is
far less than it ever has been in the
history of the human race. While
structure fres still occur, they tend to
be further between than they used to
be, and the average ignition does not
always result in the total destruction of
a building. Tere are many reasons for
this phenomenon. Among these is the
advance of modern building technol-
ogy, the widespread adoption of smoke
detection and residential sprinklers.
Lastly, there is the role of public
education and information that has
resulted in the average person being
more aware of the possibility of fre
than ever before.
We cannot rest on our laurels. For the
Ucalegons are still among us. I was
reminded of this over the last two
weeks while viewing television news
shows regarding the loss of homes to
urban wildland interface fres and by
reading newspaper accounts of multiple
alarm fres resulting in the deaths of
entire families in older non-conforming
multi-family residences. Today, the
person who is likely to sufer a major
fre loss is an interesting study in
contradiction. Te individuals who lost
their home to interface fre are more
likely to be very wealthy and/or at least
above average in income and personal
wealth. Te person who is most likely
to die in an apartment house fre is the
opposite end of the spectrum. Tey are
more likely to be lower income and
exist in living conditions that are highly
undesirable.
In reality, the middle class in America
is probably the safest from fre as
anyone. Tat doesnt mean they dont
experience fres, but the middle class, as
defned by economic factors, is sort of
like the center of a bell curve of
protection. A signifcant number of the
middle class lives in newer housing
stock and is a benefciary of the last 30
years of technological development.
I pose the question: Where are your
Ucalegons? Tis is to provoke your
consideration of how you are approach-
ing the process of both code enforce-
ment and public education and
information. If you are a fre chief or
fre marshal, your personal perspective
on that question is a lot more impor-
tant than it might seem. Te fre and
building codes that we have today are
on an order of magnitude more
sophisticated than they were 30 years
ago. I can recall when the fre code was
about the size of a small textbook. I
remember when the building code was
of a similar size. Today, both of these
documents have expanded to be about
the size of a notebook. Tese docu-
ments accompanied by appendices and
other supporting documents, create a
library of solutions to make the new
occupancy the safest that it can be.
So, I am not talking about code
enforcement per se. What I am in
reference to is how we use those codes
to improve the overall nature of our
community fre problem. What I am
talking about is dealing with the
non-compliant aspects of our commu-
nity and targeting specifc audiences to
reduce the possibility of fre loss.
How much time do you spend in
reviewing the NFIRS data for your
jurisdiction? Most everybody today is
experiencing a shift in demand upon
Where Are Your Ucalegons?
BY RONNY J. COLEMAN
AHJ PERSPECTIVE
C
M
Y
CM
MY
CY
CMY
K
topoftheline_Magenta.pdf 5/7/08 11:39:04 AM
C
M
Y
CM
MY
CY
CMY
K
topoftheline_Magenta.pdf 5/7/08 11:39:04 AM
34 Sprinkler Age | September 2008
their services that is primarily based
on emergency medical services. As I
look at different departments I see a
response rate ranging from 70 to as
high as 90 percent of the calls being
devoted to this type of service
demand. Fires can easily be lost in
the midst of that kind of statistical
static. The question I am posing to
you is whether or not you are actually
looking at your communitys fire
record, regardless of whether that
number is small or large. The empha-
sis here is on the process of examin-
ing fires to see if there are trends and
patterns that are likely to be repeated
in the following year. To give you
another visual image, you might
recall the admonition that lightning
never strikes in the same place twice.
But, it often strikes in the same
vicinity. One of the reasons that
might occur is that there could be
some specific factor that is attracting
the discharge of electricity from the
clouds to the ground. A tall tree or
some other attraction might result in
lightning strikes tattooing the area.
The same thing might be said about
structure fires. It is true that fire
seldom strikes the same place twice.
When it does occur, this is usually a
ground for suspicion.
The operations division often
intuitively knows what neighbor-
hoods are the most fire prone. Some
times the fire prevention bureaus are
not heeding the warnings coming
from this information.
Going back to the beginning of this
article, I mentioned that there are
demographic factors that tend to
repeat themselves in the fire world.
People who live in urban wildland
interface areas, whether they are rich
or poor, are likely to be victims of
wildland fire. People who live in
poverty or near poverty conditions
are much more likely to have a fire
and are more likely to suffer loss than
any other economic subgroup.
My interest in this topic came from
working with a fire department that
was paying attention to these factors.
At the end of one of their calendar
years, a review process was conducted
on structural fires and it was deter-
mined that a significant number had
occurred. Moreover, the structural
fires all tended to be kitchen fires and
the neighborhood had a specific
cultural background. This depart-
ment took action based on that
information and targeted the neigh-
borhood with a blitz attack that
resulted in the following years
statistics being drastically reduced.
As I read re protection publications, I
am often dismayed at the pride that we
seem to take about being the busiest
companies. Te reason I am dismayed
is that I actually understand the
phenomenon but I dont understand the
rationale. By understanding the phe-
nomenon, I will admit that when I was
an active reghter I loved going on
working calls like everyone else. When
is morale the highest in a rehouse?
When there is a lot of action. However,
we exist to save lives and property, not
to oer it up as a sacrice to our morale.
Tat is illogical.
Merely looking at the raw numbers of
our response workload is not managing
the problem. Fire marshals should be
focused on why things are occurring.
Tat level of analysis should be the
function of all re prevention bureaus. We
should be the leading experts on where
our structural re incidents are disturbed
and/or concentrated in the community. In
the GIS world, that term is called hot
spotting. Hot spotting is nothing more
than linking incidents up to other
incidents within a certain distance radius
and forming some conclusions about the
characteristics of that area that may be
causing the problems.
Part of the management strategy of a
fire prevention bureau should be
looking at all structural fires on an
annual basis. The more uniform the
distribution of structural fires, the
more likely that there is a degree of
randomness of the events. But, if the
experience demonstrates that some
demand zones have more fires than
others, it is time to drill down.
35 Sprinkler Age | September 2008
It is interesting to me that many
operations divisions have already
accomplished this when viewing EMS
calls. For example, the location of
residential care facilities for the
elderly, often results in a tremendous
amount of concentration of EMS
calls. Depending upon the nature of
the working relationship with that
business and with the ambulance
authority, that may or may not be a
problem. Some departments have
coined the term frequent flyers.
This is a pejorative term for locations
where demand is on the verge of
being unreasonable.
Trend analysis is a very important
part of risk mitigation. Because we
are paying so much attention to the
EMS problem, we may be missing the
point with our fire problem. If there
is a particular area in which a particu-
lar type of call occurs over and over
again it should be a targeted area. It
should be the target for such things
as public education programs,
targeted enforcement programs and
maybe even surveillance and one-on-
one contact.
When you look at fre problems, this
kind of trend analysis may be a part of
the overall strategy to introduce
mitigation practices. If there is a
particular area in which a particular
type of call occurs over and over again,
that should become the loci of future
consideration for mitigation strategy.
Tat would include but not necessarily
be limited to such things as public
education programs, targeted enforce-
ment programs even surveillance and
interviewing processes.
Over time this lightning strike
phenomenon can be either reduced or
at least more thoroughly understood.
If it cannot be reduced, there is a
possibility that the operations
division in the fire department needs
to be considering additional resourc-
es. This begins to play into such
things as unit utilization and the
need to have secondary equipment.
Or, it can be reduced if they require
the department enact memorandums
of agreement for other entities to
reduce reliance on the emergency
services division for events that are
essentially non-emergency.
In essence what we are saying is that
if you have got lightning strikes that
start to concentrate you ought to be
putting up a lightning rod.
This metaphor applies to the fact that
you are unlikely to be able to prevent
lightning from being discharged but
you certainly can minimize its impact
on the ground. Workload analysis
that is based upon frequency, distri-
bution and concentration of levels of
activity is a logical extension of
understanding the risk assessment in
a community. This particular tech-
nique does not necessarily mean that
you give up the more structured
approach to inspecting occupancies
in accordance with other policies and
procedures. In other columns we have
talked about the fact that there is a
function of graceful degradation that
sits in place of almost all occupancies
that once you inspect the building
the minute you walk out the door it
begins to deteriorate.
I would carry that so far as to say that
once you have compliance that
graceful degradation begins to occur
shortly after that also. The reason for
using this particular technique in
conjunction with linear planning for
code enforcement is the very idea that
you may have some parts of your
town in which conditions have not
been brought into compliance and
they need to be targeted and reduced
to an absolute minimum if you wish
to keep the remainder of your
workload totally under control. n
ABOUT THE AUTHOR: Ronny J. Coleman
is president of the Fire and Emergency
Television Network (FETN). He is the
former California State Fire Marshal, past
president of IAFC, and currently serves as
chairman of Board of Trustees for the Com-
mission on Fire Accreditation, International
and the NFPA Committee on Fire Protec-
tion in the Motion Picture and Television
Industry. Coleman was honored as AFSAs
1989 Henry S. Parmelee Award recipient.
800-854-1015
www.argco.com
A Great Way to Advertise
Right on the Jobsite
Put your Company Name & Logo on
your ID signs, Service Decals,
InspectionTags, Bell signs, FDC
Wallplates, Gauges, even on your Ball
Valve handles!
ARGCOs art department can take your
personalized artwork and recreate it
on your signs - Custom to your specs.
The California
State Fire Marshal has changed the specs on
the California State Inspection Tags and Decals.
Get your updated versions now!
PERSONALIZED SIGNS
NEW!
36 Sprinkler Age | September 2008
Arizona The Arizona Chapter of AFSA gath-
ered at the Phoenix Fire Department Admin-
istration Building August 28 and 29, 2008
for Steven J. Scandaliatos designer train-
ing course.
The two-day training honed in on NFPA
13, 2007 edition. The course paid special at-
tention to Chapter 8 of NFPA 13, 2007 edi-
tion, which contains the majority of the rules
and requirements for providing proper cover-
age. The seminar focused in on these gray ar-
eas, spacing and obstruction sections as well
as other important sections of chapter 8. In
depth discussions including several real life
situations as well as actual designs and solu-
tions were also used. Class participation was
great. For more information, contact Becky
Grantham at BECKYGAFSA@aol.com.
Louisiana The AFSA Louisiana Chapter host-
ed a training class August 14 at the Caddo
Parish Fire District #1, Station #1 in Shreve-
port, La. Led by Rudy Blackburn and Armond
Lombas from licensing section of the State
Fire Marshals Office, the day-long course
was aimed at teaching the proper tagging
rules and regulations. For more information,
contact the chapters new Executive Director
Ronald Bayless at trainingmatters@gmail.com
or (225) 572-4909.
Mid-Atlantic Members of the AFSA Mid-At-
lantic Chapter were among the first to see Ty-
cos brand new FireXchange Trailer at their
monthly meeting held at Tycos Lansdale, Pa.
Headquarters August 14, 2008.
AFSA members joined together to tour
the trailer, which features both water-based
and chemical-based suppression systems
and includes Wet Pipe, Dry Pipe, Preaction,
and Deluge Systems. In addition, the FireX-
change trailer features Foam Systems, SAP-
PHIRE
TESTANDRAIN
allows the re sprinkler inspectors test to be
performed by a single operator from a single
location through a local switch, an auxiliary
panel, an addressable FAC panel, or even a LAN
system ultimately saving time, money, and
manpower while promoting regular inspections
and preserving system integrity. To learn more,
visit AGF online at www.testandrain.com.
40 Sprinkler Age | September 2008
V I C T A U L I C F I R E P R O T E C T I O N S Y S T E M S
International Press Production Ltd Tel: +44 (0) 1305 257 774
CLIENT:
Victaulic
COPY DATE:
9 July
PUBLICATION:
Sprinkler Age Magazine
SIZE:
Full page bleed
ISSUE:
The First CMSA Sprinkler
for 40 ft Ceilings to
Exceed the Design
Flexibility of ESFR
As much as 70% lower end-head pressure
Approved up to 40 ft ceilings and storage of
cartoned, unexpanded, group A commodities
As much as 20% savings on materials and labor
Reduce pipe size requirements for mains and
branches by as much as 25%
Less water demand can eliminate or reduce
pump size
12 head calculations for ease of design
www.victaulic.com
1.800.PICK-VIC
LESS WATER.
SMALLER PIPE.
NORTH AMERICA UNITED KINGDOM EUROPE
ASIA PACIFIC LATIN AMERICA MIDDLE EAST
LP-46 Low Pressure
Pendent Storage
Sprinkler
APPROVED
The Soffi-Steel System is
todays premier, custom-
fabricated enclosure system
that safely conceals any size or
type of exposed utility such as
Fire Sprinkler Systems, Plumbing,
HVAC, and Electrical Wiring
within an established facility.
In Memoriam: Congresswoman Stephanie
Tubbs Jones Congresswoman Stephanie Tubbs
Jones (OH-11) died August 20, 2008 of a brain
hemorrhage. Congresswoman Tubbs Jones
was a leading advocate of campus fire safety
and introduced a number of bills, including reso-
lutions designating September as Campus Fire
Safety Month, the College Fire Prevention Act
and the Collegiate Infrastructure Act. Congress-
woman Tubbs Jones was also this years Con-
gressional cosponsor of the launch of National
Campus Fire Safety Month on Capitol Hill. Her
leadership and advocacy will be missed.
Harvel Names Foose COO Patrick M. Foose
has been appointed chief operating officer by
Harvel
Plastics,
Inc., a leading U.S.
manufacturer of
high-quality PVC
and CPVC indus-
trial piping, duct
systems, and oth-
er thermoplastic
extrusions. Foose
had previously
served the company as vice president of sales
and marketing.
Foose is a member of the International As-
sociation of Plastics Distribution (IAPD) Board
of Directors since 2001. He currently serves
as the Boards vice president and will begin a
term as Board president in the fall, becoming
the first plastics manufacturer representative
to hold the position. In 2005, he received the
IAPDs annual Pacesetter Award.
Foose has served on the Harvel Plastics
Board of Directors since 1993. He is also a
member of the Childrens Home of Easton
Board of Directors. Foose joined Harvel Plas-
tics in 1981 and was promoted to vice presi-
dent of sales and marketing in 1989.
Reliable Welcomes Alan Larson Reliable is
pleased to welcome a new Technical Servic-
es Manager Alan Larson, to their team. Lar-
son brings the perfect background to Reliables
Technical Services Group with his technical,
contractor, and sales knowledge. He has more
than 20 years of experience in fire suppres-
sion systems and has worked in fire protec-
tion contracting, with various consulting engi-
neering firms, and as a technical representative
for a sprinkler manufacturer. Immediately pri-
or to joining Reliable, Larson was employed
as Aquasafe product manager with Uponor-
USA. Larson is a NICET (National Institute for
the Certification of Engineering Technicians)
certified fire sprin-
kler designer, a cer-
tified fire protection
specialist (CFPS), is
certified in plumb-
ing engineering by
the American Soci-
ety of Plumbing En-
gineers (ASPE) and
is a member of the
NFPA committee on residential fire sprinkler
systems (AUT-RSS). He will be based in Reli-
ables Liberty, S.C. facility.
Potter Names New Hires Potter Electric Sig-
nal Company, LLC announced several new em-
ployees. Doug Chartier has been named prod-
uct manager of the newly formed Corrosion
Solutions Division at Potter. Robbie Murray has
been hired as the new global product training
manager for the Fire and Security Division, and
Dave Kosciuk has been named vice president
of sales for the Fire and Security Division.
Chartier brings 25 years of corrosion moni-
toring experience to his new position. He will be
responsible for all Potters corrosion monitoring
efforts, including updates to preventative control
devices as well as testing and treatment.
Chartier was the principle of Martier Enterpris-
es LLC, before joining Potter. He is the co-author
of various patents, is a hands-on field chem-
ist, and has been involved with MIC for 25 years
plus. He is a member of NFPA, Society of Petro-
leum Engineers and the American Chemical Soci-
ety. His work on MIC is widely published.
Murray brings over 25 years of industry ex-
perience to Potter and will be responsible for
Potters training and educational efforts for fire
and security customers. Murray was the direc-
tor of global business development at his for-
mer company. He previously worked as the
application engineer involved with technical
support and training for a span of eleven years.
Murray has worked in the industry for over 25
years and has technical experience in both the
United States and internationally.
Kosciuk brings over 17 years of industry
experience to Potter and will be responsi-
ble for all Potters domestic sales efforts for
the fire and security marketplace. He was
responsible for key initiatives for the sales
and marketing of products and programs in
the security equipment distribution channel
as well as the engineering systems distribu-
tion channel. n
PEOPLE IN THE NEWS
V I C T A U L I C F I R E P R O T E C T I O N S Y S T E M S
International Press Production Ltd Tel: +44 (0) 1305 257 774
CLIENT:
Victaulic
COPY DATE:
9 July
PUBLICATION:
Sprinkler Age Magazine
SIZE:
Full page bleed
ISSUE:
The First CMSA Sprinkler
for 40 ft Ceilings to
Exceed the Design
Flexibility of ESFR
As much as 70% lower end-head pressure
Approved up to 40 ft ceilings and storage of
cartoned, unexpanded, group A commodities
As much as 20% savings on materials and labor
Reduce pipe size requirements for mains and
branches by as much as 25%
Less water demand can eliminate or reduce
pump size
12 head calculations for ease of design
www.victaulic.com
1.800.PICK-VIC
LESS WATER.
SMALLER PIPE.
NORTH AMERICA UNITED KINGDOM EUROPE
ASIA PACIFIC LATIN AMERICA MIDDLE EAST
LP-46 Low Pressure
Pendent Storage
Sprinkler
42 Sprinkler Age | September 2008
PRODUCT NEWS
RIDGID
FPPI.
Performance,
Dedication and Skill.
FPPI.
Performance,
Dedication and Skill.
FGG/BM/CZ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold
, BlazeMaster
and Corzan
pipe and
fittings. FlowGuard Gold
, Corzan
and BlazeMaster
are registered trademarks of The Lubrizol Corporation. FGG/BM/CZ is a trademark of The Lubrizol Corporation. FPPI
, PipeFit
, ThreadFit
, and LubeFit
are
registered trademarks of Fire Protection Products, Inc.
FPPI.
Performance,
Dedication and Skill.
FPPI.
Performance,
Dedication and Skill.
FGG/BM/CZ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold
, BlazeMaster
and Corzan
pipe and
fittings. FlowGuard Gold
, Corzan
and BlazeMaster
are registered trademarks of The Lubrizol Corporation. FGG/BM/CZ is a trademark of The Lubrizol Corporation. FPPI
, PipeFit
, ThreadFit
, and LubeFit
are
registered trademarks of Fire Protection Products, Inc.