Extending existing PTL Items for Distance Protection with Power Swing Blocking and Tripping Tests
Author Oliver Janke | oliver.janke@omicron.at Date Apr 19, 2011 Related OMICRON Product CMC Test Set, Test Universe Application Area Line Protection with Distance Protection Keywords Power Swing, NetSim, PTL Version v1.0 Document ID ANS_11007_ENU Abstract This document shows how to extend existing PTL items. The OMICRON Test Module NetSim will be used for testing the power swing blocking function during stable power swings and the tripping function during unstable swings.
OMICRON
Page 1 of 17
Content
1 2 3 Introduction ..................................................................................................................................... 3 The Emergence of Power Swings and their Detection .................................................................. 3 The OMICRON Protection Testing Library (PTL) ........................................................................... 5 3.1 The Structure of the XRIO Converter ........................................................................................ 5 3.2 Using the Import Filter............................................................................................................... 6 Adding a NetSim Module for Power Swing Blocking..................................................................... 6 Adding a NetSim Module for Power Swing Tripping ....................................................................11 Tips for Defining a Good Test Case ..............................................................................................13 Testing Power Swing Detection of ABB REL670 and Siemens 7SA631 ......................................14 7.1 Testing Power Swing Blocking of ABB REL670 ........................................................................14 7.2 Testing Power Swing Blocking and Tripping of Siemens 7SA631 .............................................15
4 5 6 7
Please use this note only in combination with the related product manual which contains several important safety instructions. The user is responsible for every application that makes use of an OMICRON product. OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON. OMICRON 2011. All rights reserved. This application note is a publication of OMICRON. All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted. The product information, specifications, and technical data embodied in this application note represent the technical status at the time of writing and are subject to change without prior notice. We have done our best to ensure that the information given in this application note is useful, accurate and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present. OMICRON translates this application note from the source language English into a number of other languages. Any translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern.
OMICRON 2011 Page 2 of 17
Introduction
The OMICRON Protection Testing Library (PTL) provides predefined test plans (Protection Testing Templates, PTTs) for testing a number of relays including distance protection devices. The respective PTL item supports the test person in developing a high quality test for the main protection functions in a short time. But for different reasons power swing detection is not implemented in the PTL. The aim of this application note is to demonstrate how the OMICRON Test Module NetSim can be added to an existing PTT to test this function. This is shown for the following three distance protection relays: > AREVA P442 > ABB REL670 > SIEMENS 7SA631 NetSim will be used to simulate the transient processes in a power network during a power swing to analyze the protection devices reaction. The whole protection system and not setting parameters is tested thereby. This kind of testing is called system testing. It proofs whether the IED (Intelligent Electronic Device) will protect the electrical equipment in the specific case, or not. Also other test modules like the OMICRON State Sequencer Module or the OMICRON Ramping module can be used for this purpose, however this is not content of this document. You can find other application notes about this topic on the OMICRON website.
The control devices are able to dampen the oscillations and the power system is equilibrated again. We call that a stable power swing. One or more generators fall out of step and loose synchronism to the remaining network. This is called an unstable power swing.
During this process the installed distance protection relays measure impedances that can be similar to those during three phase faults (see Figure 1). If the impedance is within a tripping zone for a long enough time, the protection device will trip the circuit breaker to disconnect the electrical equipment. During the first case tripping is not needed as no fault exists on the network and the disturbance will disappear by itself. To solve the disturbance in the second case a few predefined connections within the network should break before the whole network splits in separate subnetworks. To define these locations several considerations have to be made. An activated power swing detection can prevent these non selective trips and thus possible blackouts like the Northeast Blackout of 2003 in North America.
OMICRON 2011
Page 3 of 17
power swing detection zone tripping zone line impedance stable power swing
But how does the IED distinguish between a stable power swing, an unstable one and a fault? While the impedance change during a power swing is rather slow the impedance vector jumps directly into the tripping zone at a fault occurrence. At a stable power swing the measured impedance enters the zones from one side, then turns around and leaves at the same side (see Figure 1). During an unstable power swing the impedance crosses the X axis completely and leaves the zones on the other side. The relay manufacturers developed different algorithms to decide which case is present. They all use one or more of the following criteria: > Power swing detection zone: As Figure 1 shows, a frame is drawn around the tripping zones or the starting zones. If the impedance is calculated within this area for a given number of measurement cycles, it is recognized as slowly changing and thus a power swing. Another possibility is to determine the time the trajectory needs to move through this area. Position and size of this frame are important parameters and can be set for some protection devices. > Monotony: The movement direction in R and X is determined. During a power swing only one direction is changing. > Continuity: The measured impedance must be changing with at least a minimum value to ensure, the trajectory is moving. Otherwise it cannot be a power swing. > Regularity: The ratio of two successive changes of the measured impedances is below a limit value. This ensures that the trajectory moves with constant or slowly changing speed, but not performing rapid changes. > Out of step detection: It is proved from which side the trajectory enters and leaves the out of step detection zone (which can be the power swing detection zone or a similar one). Another criterion is the direction of the impedance movement when crossing the line angle. Depending on the setting of the IED it trips immediately or after a given number of turns. Furthermore other criteria and exceptions to the listed ones are possible.
OMICRON 2011
Page 4 of 17
There are two different power swing functions in modern numerical relays: > Power swing blocking: The whole distance protection or only assigned zones are blocked when a power swing occurs. > Power swing tripping: The relay trips after detecting an unstable power swing.
3.1
OMICRON 2011
Page 5 of 17
3.2
OMICRON 2011
Page 6 of 17
Most of the parameters which have to be entered in the Test View do not correspond to the settings of the protection function. Instead these are data about the network the IED is used on. By means of these data the module will simulate the transient signals which occur during a power swing on this network. Not the settings of the relay are tested, but its behavior under realistic conditions. Unfortunately some of the needed network data are often not available in practice. Furthermore most of the networks have a variety of switching states. This leads to many different combinations of test settings that have to be tested. But with some considerations a good test case can be found. If there is no claim laid to test with real network data, there is still the possibility to test the protection function with the standard values. So let's go through the test views tabs and see, which effect on the test the individual settings have. Fault In this tab a Prefault and a Postfault time can be set. 100 ms are enough for both. The next two settings are much more important for the test: The Slip angle specifies the maximum asynchronicity. 180 are the theoretical limits for a stable power swing. If the angle became even more, the machine would fall out of step, as its maximum torque was exceeded. Less slip angle means less power swing and results in higher impedances. By entering the maximum of -180 it is achieved that the relay measures impedances within the tripping zones. The negative limit is chosen as this will create a power swing coming from the right what looks like a big load to the IED. The protection device will thus be tested whether it is still working fine in such a difficult situation.
OMICRON 2011
Page 7 of 17
The Slip time defines the duration of the power swing. If this time is too short the trajectory might move to fast and leave the tripping zones before the distance protection tripped. 500ms are a good value but after all settings were entered it must be checked, that the trajectory stays within a tripping zone for a long enough time. Line Here the LinkToXRIO function is used to define the lines parameters (see Figure 5). For the selected mode Z and k the corresponding values are stored in the RIO block of the converter (see Figure 6). As they are secondary values, this option must be selected in the View menu before linking otherwise they are interpreted as primary values. The value for the grounding factor must be checked, as some PTL converters use a grounding factor of zero and recalculate all zones to loop impedances. In that case the link must be done to the corresponding parameter in the Relay Parameter Section. Changing the Mode might be needed.
Sources These data are characterizing the network. A user defined block called "System Data" is added to the XRIO converter for some calculations (see Figure 8). The Voltage and Frequency in this tab (Figure 7) can be linked to the nominal values in the RIO Device block. Delta V and Delta phi are both zero for the moment. Chapter 6 explains how these values can be used to move the trajectory of the impedances.
OMICRON 2011
Page 8 of 17
For the impedance magnitudes and angles a user defined XRIO block shall be used. This block must be added to the XRIO converter like shown in Figure 8 and is used to calculate the source impedances , from the short circuit power , of the two connected sources. To calculate the parameters Z1 source 1 and 2 equation (1) is implemented as a formula in XRIO. , =
., ,
In this equation , is the primary nominal line to line voltage. The four variables above and below the right fraction line are the primary and secondary values of the installed current transformers or voltage transformers. They are needed to convert the impedance value to a secondary value. The results can be linked to the NetSim settings Zmag for source 1 and source 2. The angles can be entered either directly in NetSim or as seen in Figure 7 and Figure 8 also linked to XRIO. In the converter the angle is calculated from an R/X ratio of 10%, which is an approximation that can be made if the exact values are not known. For this example 5000 MVA are used for both sources. The grounding factor magnitudes and angles can normally be chosen as one and zero, if the exact values are unknown.
, ,
(1)
OMICRON 2011
Page 9 of 17
Outputs The primary and secondary values for the current transformers and voltage transformers can be linked to the corresponding values in the RIO Device block (see Figure 9). This has only to be done for the location (A or B) at which the relay is installed.
After all settings have been entered the impedance view shows the resulting power swing (see Figure 10). As a next step, the trajectories are proved to remain in a tripping zone long enough to evoke a trip. As the trajectories move into Z1 (TZ1 = 0 s) this zone will probably cause the trip. Depending on the movement speed theoretically every other zone could trip first. To test the power swing blocking function at least one zone must be found that would surely trip, if the function did not work probably. Therefore the cursors are moved on the time axis to find the points where the trajectories enter and leave the zone. It is even more exact not to take the borders of the zone but to use the tolerance lines. Now the time deviation can be read, which is 110 ms what is enough for the relay to trip. The proper operation of the power swing blocking function can be tested with this power swing. If the time was too short the Slip Time (Fault settings) can be increased.
cursor 2
cursor 1
Figure 10: Measuring the time the trajectory of the resulting power swing is within zone 1
OMICRON 2011
Page 10 of 17
After configuring the trip signal in the local hardware configuration three measurements for the phase selective trip times can be defined. These time measurements start with the beginning of the power swing and end with the trip signal for phase A, B or C. When testing the power swing blocking function, no trip is expected at all, that's why no nominal values are entered. Therefore the assessment must be done manually. The test was OK if no trip occurred. The Measurement View after a successful test is shown in Figure 11.
Line, Sources and Outputs These settings are exactly the same as for the power swing blocking test and can be seen in Figure 5, Figure 7 and Figure 9. The resulting impedance trajectory is shown in Figure 13. The time within zone 1 can be determined as about 110 ms, what is long enough.
OMICRON 2011
Page 11 of 17
Again measurements for the trip times are defined. Unlike during the power swing blocking test trips are now expected in all three phases. Defining a nominal time is not possible, as it depends on the moment the relay recognizes, that the power swing is an unstable one, which in turn depends on the algorithm of the IED. This task is something completely different to measuring the trip time of a zone. The assessment again has to be done manually. Figure 14 shows the result of this measurement: A trip time above 1 s signifies that the relay tripped as supposed during the second turn. This can be verified with help of the signal view. Figure 15 clearly shows that all three trip signals occur during the second power swing. This is exactly how the IED was meant to react. Thus the power swing tripping function could successfully be tested that way.
OMICRON 2011
Page 12 of 17
line angle R
Figure 16: Movement of the turning point depending on the power transport
OMICRON 2011
Page 13 of 17
7.1
The resulting impedance trajectory is shown in Figure 18. After checking its residence time in zone 1 the module is ready for testing.
OMICRON 2011
Page 14 of 17
7.2
OMICRON 2011
Page 15 of 17
List of Literature [1] Michael Albert, Eugenio Carvalheira, Oliver Janke: PTL: A solid basis for building customized line protection test standards, OMICRON IPTS 2009 (www.omicron.at) [2] Dr. Peter Meinhardt, OMICRON electronics GmbH: Testing approaches for power swing blocking function, OMICRON IPTS 2009 (www.omicron.at) [3] Dr. Fred Steinhauser, OMICRON electronics GmbH: Testing of the Power Swing Blocking in Distance Relays [4] Dr. Yuchen Lu, Dr. Juergen Holbach, Laurie Martuscello, P.E., Edward Krizauskas, P.E.: Tests of Distance Relay Performance on Stable and Unstable Power Swings Using Simulated Data of the August 14th 2003 System Disturbance [5] Jrg Blumschein, Matthias Kereit, Yilmaz Yelgin, SIEMENS: Erhhung der Netzstabilitt durch zuverlssige Pendelerkennung, Tagungsbeitrag 4.1 OMICRON Anwendertagung 2009 (www.omicron.at) [6] MiCOM P441/P442/P444 Numerical Distance Protection, Technical Manual [7] Technical reference manual Line distance protection IED REL 670 [8] SIPROTEC DISTANZSCHUTZ 7SA6 MANUAL
OMICRON 2011
Page 16 of 17
OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products provides users with the highest level of confidence in the condition assessment of primary and secondary equipment on their systems. Services offered in the area of consulting, commissioning, testing, diagnosis, and training make the product range complete. Customers in more than 140 countries rely on the company's ability to supply leading edge technology of excellent quality. Broad application knowledge and extraordinary customer support provided by offices in North America, Europe, South and East Asia, and the Middle East, together with a worldwide network of distributors and representatives, make the company a market leader in its sector.
Americas OMICRON electronics Corp. USA 12 Greenway Plaza, Suite 1510 Houston, TX 77046, USA Phone: +1 713 830-4660 +1 800-OMICRON Fax: +1 713 830-4661 info@omicronusa.com
Asia-Pacific OMICRON electronics Asia Limited Suite 2006, 20/F, Tower 2 The Gateway, Harbour City Kowloon, Hong Kong S.A.R. Phone: +852 2634 0377 Fax: +852 2634 0390 info@asia.omicron.at
Europe, Middle East, Africa OMICRON electronics GmbH Oberes Ried 1 6833 Klaus, Austria Phone: +43 5523 507-0 Fax: +43 5523 507-999 info@omicron.at
For addresses of OMICRON offices with customer service centers, regional sales offices or offices for training, consulting and commissioning please visit our web site.
www.omicron.at www.omicronusa.com