Application Note

Extending existing PTL Items for Distance Protection with Power Swing Blocking and Tripping Tests
Author Oliver Janke | oliver.janke@omicron.at Date Apr 19, 2011 Related OMICRON Product CMC Test Set, Test Universe Application Area Line Protection with Distance Protection Keywords Power Swing, NetSim, PTL Version v1.0 Document ID ANS_11007_ENU Abstract This document shows how to extend existing PTL items. The OMICRON Test Module NetSim will be used for testing the power swing blocking function during stable power swings and the tripping function during unstable swings.

OMICRON

Page 1 of 17

Content
1 2 3 Introduction ..................................................................................................................................... 3 The Emergence of Power Swings and their Detection .................................................................. 3 The OMICRON Protection Testing Library (PTL) ........................................................................... 5 3.1 The Structure of the XRIO Converter ........................................................................................ 5 3.2 Using the Import Filter............................................................................................................... 6 Adding a NetSim Module for Power Swing Blocking..................................................................... 6 Adding a NetSim Module for Power Swing Tripping ....................................................................11 Tips for Defining a Good Test Case ..............................................................................................13 Testing Power Swing Detection of ABB REL670 and Siemens 7SA631 ......................................14 7.1 Testing Power Swing Blocking of ABB REL670 ........................................................................14 7.2 Testing Power Swing Blocking and Tripping of Siemens 7SA631 .............................................15

4 5 6 7

Please use this note only in combination with the related product manual which contains several important safety instructions. The user is responsible for every application that makes use of an OMICRON product. OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON. OMICRON 2011. All rights reserved. This application note is a publication of OMICRON. All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted. The product information, specifications, and technical data embodied in this application note represent the technical status at the time of writing and are subject to change without prior notice. We have done our best to ensure that the information given in this application note is useful, accurate and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present. OMICRON translates this application note from the source language English into a number of other languages. Any translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern.
OMICRON 2011 Page 2 of 17

Introduction
The OMICRON Protection Testing Library (PTL) provides predefined test plans (Protection Testing Templates, PTTs) for testing a number of relays including distance protection devices. The respective PTL item supports the test person in developing a high quality test for the main protection functions in a short time. But for different reasons power swing detection is not implemented in the PTL. The aim of this application note is to demonstrate how the OMICRON Test Module NetSim can be added to an existing PTT to test this function. This is shown for the following three distance protection relays: > AREVA P442 > ABB REL670 > SIEMENS 7SA631 NetSim will be used to simulate the transient processes in a power network during a power swing to analyze the protection devices reaction. The whole protection system and not setting parameters is tested thereby. This kind of testing is called system testing. It proofs whether the IED (Intelligent Electronic Device) will protect the electrical equipment in the specific case, or not. Also other test modules like the OMICRON State Sequencer Module or the OMICRON Ramping module can be used for this purpose, however this is not content of this document. You can find other application notes about this topic on the OMICRON website.

The Emergence of Power Swings and their Detection


During the normal operation of the electrical power network the actual load always equals the generation. But caused by sudden load changes, switching operations or faults this balance can be disturbed. Because of the inertia of all connected electrical machines and the slow control of the generation of active power these events result in oscillations of voltages and currents. There are two possible scenarios:
1. 2.

The control devices are able to dampen the oscillations and the power system is equilibrated again. We call that a stable power swing. One or more generators fall out of step and loose synchronism to the remaining network. This is called an unstable power swing.

During this process the installed distance protection relays measure impedances that can be similar to those during three phase faults (see Figure 1). If the impedance is within a tripping zone for a long enough time, the protection device will trip the circuit breaker to disconnect the electrical equipment. During the first case tripping is not needed as no fault exists on the network and the disturbance will disappear by itself. To solve the disturbance in the second case a few predefined connections within the network should break before the whole network splits in separate subnetworks. To define these locations several considerations have to be made. An activated power swing detection can prevent these non selective trips and thus possible blackouts like the Northeast Blackout of 2003 in North America.

OMICRON 2011

Page 3 of 17

power swing detection zone tripping zone line impedance stable power swing

unstable power swing

Figure 1: Impedance trajectory during power swings

But how does the IED distinguish between a stable power swing, an unstable one and a fault? While the impedance change during a power swing is rather slow the impedance vector jumps directly into the tripping zone at a fault occurrence. At a stable power swing the measured impedance enters the zones from one side, then turns around and leaves at the same side (see Figure 1). During an unstable power swing the impedance crosses the X axis completely and leaves the zones on the other side. The relay manufacturers developed different algorithms to decide which case is present. They all use one or more of the following criteria: > Power swing detection zone: As Figure 1 shows, a frame is drawn around the tripping zones or the starting zones. If the impedance is calculated within this area for a given number of measurement cycles, it is recognized as slowly changing and thus a power swing. Another possibility is to determine the time the trajectory needs to move through this area. Position and size of this frame are important parameters and can be set for some protection devices. > Monotony: The movement direction in R and X is determined. During a power swing only one direction is changing. > Continuity: The measured impedance must be changing with at least a minimum value to ensure, the trajectory is moving. Otherwise it cannot be a power swing. > Regularity: The ratio of two successive changes of the measured impedances is below a limit value. This ensures that the trajectory moves with constant or slowly changing speed, but not performing rapid changes. > Out of step detection: It is proved from which side the trajectory enters and leaves the out of step detection zone (which can be the power swing detection zone or a similar one). Another criterion is the direction of the impedance movement when crossing the line angle. Depending on the setting of the IED it trips immediately or after a given number of turns. Furthermore other criteria and exceptions to the listed ones are possible.

OMICRON 2011

Page 4 of 17

There are two different power swing functions in modern numerical relays: > Power swing blocking: The whole distance protection or only assigned zones are blocked when a power swing occurs. > Power swing tripping: The relay trips after detecting an unstable power swing.

The OMICRON Protection Testing Library (PTL)


There are different sources for the PTL: It can be installed from the DVD or CDs that are shipped with the CMC test set or it can be downloaded from the OMICRON customer area (www.omicron.at). In both cases it is free of charge. Each PTL item consists of several files: > An *.xrio-file: This is the XRIO converter. It can be used as test object for every test module. After entering the actual relay settings, the converter calculates the characteristics for the main protection functions automatically. > An *.occ-file: This is the PTT (Protection Test Template) and consists of several test modules to test the main functions of the corresponding protection device. A test for power swing blocking or tripping is always missing. The XRIO converter is already included as test object. Using the PTT is the fastest way of using the PTL as only the relay settings and little other information have to be entered in the test object. > One or two *.pdf-files: These are the manuals for the PTL item. They contain important information on how to use these files.

3.1

The Structure of the XRIO Converter


Each PTL XRIO converter is divided in five sections: > Relay Parameter Section: This is a copy of the relay settings software. The actual settings of the device have to be entered her either manually or with the help of an import filter (see chapter 0). Also the settings for the power swing detection are included, even if this function is not supported by the PTT. They can be used to build a customized test for this function. > Additional Information: This block contains few parameters which are needed to test the device but are not part of the relay settings. > RIOplus: This part is used for calculations to convert the relay specific parameters to values valid for the RIO block and OMICRON Test Universe test modules. It is only visible if the advanced view of the XRIO editor is active. > Template Controller: This block is needed for the PTT. Only visible in advanced view. > RIO: This block contains the resulting characteristics for most of the protection functions. Nothing must be changed here, as the formulas for the automatic calculation would be destroyed. In case of a distance protection the RIO function Distance contains the zones. They will be used for testing the power swing detection.

OMICRON 2011

Page 5 of 17

3.2

Using the Import Filter


With the help of one of the OMICRON import filters the manual entry of settings may be omitted. Different import filter for different manufacturers are available. With the import filter and the specific relay parameter software export file, it is possible to import the relay settings automatically into the XRIO converter. Even if the PTTs are normally not supporting power swing detection, the relay import filter will also work for these settings.

Adding a NetSim Module for Power Swing Blocking


In the following the PTT for AREVA P441, P442 and P444 is used as an example. After installing this PTL item the PTT is opened and the settings of the relay are entered in the converter. For testing the power swing blocking function a NetSim module is inserted after the last distance protection test, which is the SOTF (switch on to fault) test. At first the correct Test Case at the menu Parameters must be selected (see Figure 2). There are three different power swing cases: > Synchronous: A stable power swing is simulated. This one is selected here. > Asynchronous, Multiple Turns: An unstable power swing is simulated with multiple pole slips. > Asynchronous, With Fault: An unstable power swing is simulated with multiple pole slips. Additionally a fault occurs at a predefined time. The impedance view (Figure 3) shows, that the module is automatically using the impedance characteristic data of the converter. Also the three trajectories of the phase to phase impedances are drawn. With the default test settings entered in the test view (Figure 4) tabs the impedances will never reach the trip zones and thus no power swing blocking can be tested. Therefore the according settings have to be adapted first. Some further understanding of the data of the actual network and the physics behind the power swing is needed.

Figure 2: Selection of the Test Case

OMICRON 2011

Page 6 of 17

Figure 3: Impedance view

Most of the parameters which have to be entered in the Test View do not correspond to the settings of the protection function. Instead these are data about the network the IED is used on. By means of these data the module will simulate the transient signals which occur during a power swing on this network. Not the settings of the relay are tested, but its behavior under realistic conditions. Unfortunately some of the needed network data are often not available in practice. Furthermore most of the networks have a variety of switching states. This leads to many different combinations of test settings that have to be tested. But with some considerations a good test case can be found. If there is no claim laid to test with real network data, there is still the possibility to test the protection function with the standard values. So let's go through the test views tabs and see, which effect on the test the individual settings have. Fault In this tab a Prefault and a Postfault time can be set. 100 ms are enough for both. The next two settings are much more important for the test: The Slip angle specifies the maximum asynchronicity. 180 are the theoretical limits for a stable power swing. If the angle became even more, the machine would fall out of step, as its maximum torque was exceeded. Less slip angle means less power swing and results in higher impedances. By entering the maximum of -180 it is achieved that the relay measures impedances within the tripping zones. The negative limit is chosen as this will create a power swing coming from the right what looks like a big load to the IED. The protection device will thus be tested whether it is still working fine in such a difficult situation.

Figure 4: Test View with entered Fault settings

OMICRON 2011

Page 7 of 17

The Slip time defines the duration of the power swing. If this time is too short the trajectory might move to fast and leave the tripping zones before the distance protection tripped. 500ms are a good value but after all settings were entered it must be checked, that the trajectory stays within a tripping zone for a long enough time. Line Here the LinkToXRIO function is used to define the lines parameters (see Figure 5). For the selected mode Z and k the corresponding values are stored in the RIO block of the converter (see Figure 6). As they are secondary values, this option must be selected in the View menu before linking otherwise they are interpreted as primary values. The value for the grounding factor must be checked, as some PTL converters use a grounding factor of zero and recalculate all zones to loop impedances. In that case the link must be done to the corresponding parameter in the Relay Parameter Section. Changing the Mode might be needed.

Figure 5: Line settings

Figure 6: Linking the line settings

Sources These data are characterizing the network. A user defined block called "System Data" is added to the XRIO converter for some calculations (see Figure 8). The Voltage and Frequency in this tab (Figure 7) can be linked to the nominal values in the RIO Device block. Delta V and Delta phi are both zero for the moment. Chapter 6 explains how these values can be used to move the trajectory of the impedances.

OMICRON 2011

Page 8 of 17

For the impedance magnitudes and angles a user defined XRIO block shall be used. This block must be added to the XRIO converter like shown in Figure 8 and is used to calculate the source impedances , from the short circuit power , of the two connected sources. To calculate the parameters Z1 source 1 and 2 equation (1) is implemented as a formula in XRIO. , =
., ,

In this equation , is the primary nominal line to line voltage. The four variables above and below the right fraction line are the primary and secondary values of the installed current transformers or voltage transformers. They are needed to convert the impedance value to a secondary value. The results can be linked to the NetSim settings Zmag for source 1 and source 2. The angles can be entered either directly in NetSim or as seen in Figure 7 and Figure 8 also linked to XRIO. In the converter the angle is calculated from an R/X ratio of 10%, which is an approximation that can be made if the exact values are not known. For this example 5000 MVA are used for both sources. The grounding factor magnitudes and angles can normally be chosen as one and zero, if the exact values are unknown.

, ,

(1)

Figure 7: The sources definition

Figure 8: The user defined block System Data in XRIO

OMICRON 2011

Page 9 of 17

Outputs The primary and secondary values for the current transformers and voltage transformers can be linked to the corresponding values in the RIO Device block (see Figure 9). This has only to be done for the location (A or B) at which the relay is installed.

Figure 9: The output configuration

After all settings have been entered the impedance view shows the resulting power swing (see Figure 10). As a next step, the trajectories are proved to remain in a tripping zone long enough to evoke a trip. As the trajectories move into Z1 (TZ1 = 0 s) this zone will probably cause the trip. Depending on the movement speed theoretically every other zone could trip first. To test the power swing blocking function at least one zone must be found that would surely trip, if the function did not work probably. Therefore the cursors are moved on the time axis to find the points where the trajectories enter and leave the zone. It is even more exact not to take the borders of the zone but to use the tolerance lines. Now the time deviation can be read, which is 110 ms what is enough for the relay to trip. The proper operation of the power swing blocking function can be tested with this power swing. If the time was too short the Slip Time (Fault settings) can be increased.

cursor 2

cursor 1

Figure 10: Measuring the time the trajectory of the resulting power swing is within zone 1

OMICRON 2011

Page 10 of 17

After configuring the trip signal in the local hardware configuration three measurements for the phase selective trip times can be defined. These time measurements start with the beginning of the power swing and end with the trip signal for phase A, B or C. When testing the power swing blocking function, no trip is expected at all, that's why no nominal values are entered. Therefore the assessment must be done manually. The test was OK if no trip occurred. The Measurement View after a successful test is shown in Figure 11.

Figure 11: Measurement View

Adding a NetSim Module for Power Swing Tripping


To test the power swing tripping function of the relay another NetSim module must be added, where Power Swing / Asynchronous / Multiple Turns is selected as test case. The settings are very similar to those from the power swing blocking test: Power Swing A Slip frequency (see Figure 12) of 1 Hz causes a slow enough movement through the impedance plane, to possible cause a trip. The duration of each turn will be is 1 s and the trajectory will again move from right to left through the impedance plane. As the example relay is configured to block during the first turn and trip if a second one occurs, the Number of turns should at least be two.

Figure 12: The Power Swing settings

Line, Sources and Outputs These settings are exactly the same as for the power swing blocking test and can be seen in Figure 5, Figure 7 and Figure 9. The resulting impedance trajectory is shown in Figure 13. The time within zone 1 can be determined as about 110 ms, what is long enough.

OMICRON 2011

Page 11 of 17

Figure 13: The resulting out of step power swing

Again measurements for the trip times are defined. Unlike during the power swing blocking test trips are now expected in all three phases. Defining a nominal time is not possible, as it depends on the moment the relay recognizes, that the power swing is an unstable one, which in turn depends on the algorithm of the IED. This task is something completely different to measuring the trip time of a zone. The assessment again has to be done manually. Figure 14 shows the result of this measurement: A trip time above 1 s signifies that the relay tripped as supposed during the second turn. This can be verified with help of the signal view. Figure 15 clearly shows that all three trip signals occur during the second power swing. This is exactly how the IED was meant to react. Thus the power swing tripping function could successfully be tested that way.

Figure 14: Measurement for the trip time

Figure 15: Signal view of an unstable power swing

OMICRON 2011

Page 12 of 17

Tips for Defining a Good Test Case


A good test case for a stable power swing is one with the turning point of the trajectory inside of zone 1. This will ensure that the relay will trip if the power swing blocking function did not work probably. If the real network data (i.e. the source impedances) are unknown, default values have to be used or assumptions must be done. If the resulting turning point is outside of all tripping zones there is a possibility to move it within the impedance plane: By changing the value for Delta V (see Figure 7) the transfer of reactive power on the line can be modeled. With Delta phi the active power transfer can be changed. This results in a movement of the turning point like shown in Figure 16. A change of reactive power results in a movement in direction of the line angle, a change of active power in a movement in 90 turned to it. These two parameters can now be used to move the turning point from outside of the tripping characteristic to the inside. Of course only realistic values should be used, that correspond to a power transfer that can happen in reality. Nevertheless this function can still be tested by using unrealistic test values that do not represent the connected network. X line impedance -Delta V -Delta phi +Delta phi +Delta V

line angle R
Figure 16: Movement of the turning point depending on the power transport

OMICRON 2011

Page 13 of 17

Testing Power Swing Detection of ABB REL670 and Siemens 7SA631


Up to this point this application note describes how to test the power swing blocking and tripping of the AREVA P442 relay. This chapter is therefore devoted to using the existing OMICRON NetSim modules to test the same protection function in other relay types. This will be done with very few changes as no parameter test but a system test was performed. Even if the line parameters and zone reaches will be the same for these examples the distance characteristics will differ from relay to relay.

7.1

Testing Power Swing Blocking of ABB REL670


In the example settings of this IED only power swing blocking is included. A test for power swing tripping is not needed. The first step is to prepare the XRIO converter. As some settings of the NetSim module are linked to the System Data block, this block must be copied to the REL670 converter. Therefore the Organize function (XRIO editor advanced view) is used: The P442 converter is imported in the right window. Then the System Data block is marked and moved to the appropriate place in the REL670 converter. Now the NetSim module for power swing blocking is copied to the REL670 PTT. It will automatically use the already imported System Data block of the converter. Depending on the wiring the local hardware configuration might have to be adapted. Also the measurements are changed as only one general trip signal exists in this example. As the parameters for the line are different to those in the P442 converter they have to be adapted as seen in Figure 17. In the REL670 settings no grounding factor k is defined. That's why a different Mode is chosen and the values are now linked to the R and X values of the positive and negative sequence parameters of the line. These values are found in the settings for the fault locator. Please note, that they are primary values and therefore the module must be configured to view primary values while linking.

Figure 17: Defining the line for testing ABB REL670

The resulting impedance trajectory is shown in Figure 18. After checking its residence time in zone 1 the module is ready for testing.

OMICRON 2011

Page 14 of 17

Figure 18: Power swing blocking test for ABB REL670

7.2

Testing Power Swing Blocking and Tripping of Siemens 7SA631


In the example settings for this relay power swing blocking and tripping are activated. It is configured to have phase selective trip signals. Therefore both NetSim modules from the Areva P442 test can be copied to the Siemens 7SA631 PTT. But before that the System Data block must be added to the converter like in the previous chapter. The modules will now automatically use these values and also the distance characteristic of the RIO block. Again the links for the line settings must be adapted to the new settings: Like in Figure 19 a different mode must be selected. The R and X values can be taken from the RIOplus block under ProtectedObject. The two ratios RE/R and XE/X are linked to the RIO distance function. For testing power swing tripping the number of turns is changed, as the IED is meant to trip during the first pole slip. Figure 20 shows the resulting trajectory. After checking its residence time within zone 1 the test can be started.

Figure 19: Line settings for Siemens 7SA631

OMICRON 2011

Page 15 of 17

Figure 20: Testing of power swing tripping of Siemens 7SA631

List of Literature [1] Michael Albert, Eugenio Carvalheira, Oliver Janke: PTL: A solid basis for building customized line protection test standards, OMICRON IPTS 2009 (www.omicron.at) [2] Dr. Peter Meinhardt, OMICRON electronics GmbH: Testing approaches for power swing blocking function, OMICRON IPTS 2009 (www.omicron.at) [3] Dr. Fred Steinhauser, OMICRON electronics GmbH: Testing of the Power Swing Blocking in Distance Relays [4] Dr. Yuchen Lu, Dr. Juergen Holbach, Laurie Martuscello, P.E., Edward Krizauskas, P.E.: Tests of Distance Relay Performance on Stable and Unstable Power Swings Using Simulated Data of the August 14th 2003 System Disturbance [5] Jrg Blumschein, Matthias Kereit, Yilmaz Yelgin, SIEMENS: Erhhung der Netzstabilitt durch zuverlssige Pendelerkennung, Tagungsbeitrag 4.1 OMICRON Anwendertagung 2009 (www.omicron.at) [6] MiCOM P441/P442/P444 Numerical Distance Protection, Technical Manual [7] Technical reference manual Line distance protection IED REL 670 [8] SIPROTEC DISTANZSCHUTZ 7SA6 MANUAL

OMICRON 2011

Page 16 of 17

OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products provides users with the highest level of confidence in the condition assessment of primary and secondary equipment on their systems. Services offered in the area of consulting, commissioning, testing, diagnosis, and training make the product range complete. Customers in more than 140 countries rely on the company's ability to supply leading edge technology of excellent quality. Broad application knowledge and extraordinary customer support provided by offices in North America, Europe, South and East Asia, and the Middle East, together with a worldwide network of distributors and representatives, make the company a market leader in its sector.

Americas OMICRON electronics Corp. USA 12 Greenway Plaza, Suite 1510 Houston, TX 77046, USA Phone: +1 713 830-4660 +1 800-OMICRON Fax: +1 713 830-4661 info@omicronusa.com

Asia-Pacific OMICRON electronics Asia Limited Suite 2006, 20/F, Tower 2 The Gateway, Harbour City Kowloon, Hong Kong S.A.R. Phone: +852 2634 0377 Fax: +852 2634 0390 info@asia.omicron.at

Europe, Middle East, Africa OMICRON electronics GmbH Oberes Ried 1 6833 Klaus, Austria Phone: +43 5523 507-0 Fax: +43 5523 507-999 info@omicron.at

For addresses of OMICRON offices with customer service centers, regional sales offices or offices for training, consulting and commissioning please visit our web site.

www.omicron.at www.omicronusa.com

Você também pode gostar