E10-331

Engineering
Data Book
3 compressors & 3 inverters Super Modular Multi System
< Digest version >

Notice: Toshiba is committed to continuously improving its products to ensure the highest
quality and reliability standard, and to meet local regulations and market requirements.

SMMS-i Data book

Contents

1
2
3
4

Foreword ........................................................................................ 1-1


Safety caution ................................................................................. 2-1
Introduction ..................................................................................... 3-1
System overview ............................................................................ 4-1
4.1.
4.2.
4.3.
4.4.
4.5.

OUTLINE OF TOSHIBA SMMS.......................................................................... 4-1


SUMMARY OF SYSTEM EQUIPMENTS........................................................... 4-2
List of product and combined model name......................................................... 4-3
Indoor unit........................................................................................................... 4-5
Remote controller ............................................................................................... 4-6

Basic system configuration ............................................................. 5-1


5.1. Basic systems..................................................................................................... 5-1
5.2. Fresh Air Intake Indoor Unit Type....................................................................... 5-3

Equipment selection procedure ...................................................... 6-1


6.1.
6.2.
6.3.
6.4.
6.5.

Refrigerant piping design .............................................................. 7-1


7.1.
7.2.
7.3.
7.4.
7.5.

Selection flow chart............................................................................................. 6-1


Operational temperature range........................................................................... 6-2
Combination conditions for indoor unit and outdoor unit .................................... 6-2
Cooling/heating capacity characteristics............................................................. 6-3
Selection procedure for fresh air intake indoor unit ............................................ 6-6
WARNINGS ON REFRIGERANT LEAKAGE ..................................................... 7-1
Free branching system ....................................................................................... 7-2
Allowable length/height difference of refrigerant piping ...................................... 7-3
Selection of refrigerant piping ............................................................................. 7-4
Charging requirement with additional refrigerant................................................ 7-5

Part Load performance ................................................................... 8-1


8.1. Single unit ........................................................................................................... 8-1
8.2. Combination........................................................................................................ 8-5

Wiring Design ................................................................................. 9-1


9.1.
9.2.
9.3.
9.4.
9.5.

General ............................................................................................................... 9-1


Summary of wiring design .................................................................................. 9-1
Electrical wiring design ....................................................................................... 9-1
Outdoor unit power supply.................................................................................. 9-1
Indoor unit power supply..................................................................................... 9-3

10 Controls ........................................................................................ 10-1


11 Sound characteristics (NC curve) ............................................... 11-1
11.1. Single unit ......................................................................................................... 11-1
11.2. Combination...................................................................................................... 11-3

12 Technical Specifications ............................................................. 12-1


12.1. Outdoor unit ...................................................................................................... 12-1
12.1.1
12.1.2
12.1.3
12.1.4
12.1.5

Specifications ........................................................................................................ 12-1


Dimensional drawing ............................................................................................. 12-9
Connecting diagram ............................................................................................ 12-10
Wiring diagram .................................................................................................... 12-11
Branch header / branch joint ............................................................................... 12-12

12.2. Indoor unit....................................................................................................... 12-13


12.2.1 Specifications ...................................................................................................... 12-13

SMMS-i Data book

Foreword

The engineering data book details all relevant data, charts


and drawings to enable you to get the best performance
from the Toshiba Super Modular Multi System i for the
various applications.
The information is aimed to assist you by providing greater
detail of the system and the wider applications that the
system will cover.

1 -1

SMMS-i Data book

Safety caution

Before use, read carefully through the Safety caution section to ensure correct operation.
The important contents concerned to the safety are described in the Safety Cautions.
Be sure to keep them. For Indications and their meanings, see the following description.

Explanation of indications

WARNING
Indicates possibilities that a death or serious injury of personnel is caused by an incorrect handling.

CAUTION
Indicates contents that an injury (*1) or property damage (*2) only may be caused when an incorrect work has been executed.

*1: Injury means a hurt, a burn, or an electric shock which does not require hospitalization or a long-term going to the hospital.
*2: Property damage means an enlarged damage concerned to property, or breakage of materials.
After installation work has finished, check there is no trouble by a test operation, and explain using method and
maintenance method to the customers based on the Owners Manual.
Please ask the customers to keep this Installation Manual together with the Owners Manual.

WARNING
Ask a shop or a professional dealer to install the air conditioner.
If you will install by yourself, a fire, an electric shock, or water leak is caused.
Take measures so that the refrigerant does not exceed the limit concentration even if it leaks when installing the air conditioner
in a small room.
For the measures not to exceed the limit of concentration, contact the dealer. If the refrigerant leaks and it exceeds the limit of
concentration, an accident of oxygen shortage is caused.
Install the air conditioner at a place which is satisfactorily bearable to weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work against a strong wind such as typhoon or earthquake.
If the air conditioner is imperfectly installed, an accident by falling or dropping may be caused.
If refrigerant gas leaks during installation work, ventilate the room.
If the leaked refrigerant gas approaches to fire, noxious gas may generate.
After installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks in the room, and approaches to fire such as fan heater, stove or kitchen range, generation of noxious gas may be
caused.
Never recover refrigerant in the outdoor unit.
Be sure to use a refrigerant recovery device to recover refrigerant in reinstallation or repair work.
Recovery of refrigerant in the outdoor unit is unavailable; otherwise a serious accident such as crack or human injury is caused.
A person qualified for the electric work should deal with the electric construction conforming to the regulations of the local
electric company and the Installation Manual. Be sure to use the exclusive circuit.
If there is capacity shortage of the power supply circuit or incomplete installation, a fire or an electric shock is caused.
For cabling, use the specified cables and connect them securely so that external force of cable does not transmit to the
terminal connecting section.
If connection or fixing is incomplete, a fire, etc. may be caused.
Be sure to connect earth wire.
Do not connect earth wire to gas pipe, water pipe, lightning rod, nor earth wire of telephone.
If grounding is incomplete, an electric shock is caused.

CAUTION
Do not install the air conditioner at a place where combustible gas may leak.
If gas leaks and is collected at surrounding the unit, the production of fire may be caused.
Be sure to attach an earth leakage breaker; otherwise an electric shock may be caused.
Using a torque wrench, tighten the flare nut in the specified method.
If the flare nut is exceedingly tightened, the flare nut is broken and a refrigerant leakage may be caused after a long time has passed.

2 -1

2 Safety caution
1. WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively.
Suffocation from leakage of R410A is almost
nonexistent. With the recent increase in the number of
high concentration buildings, however, the installation of
multi air conditioner systems is on the increase because
of the need for effective use of floor space, individual
control, energy conservation by curtailing heat and
carrying power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared
with conventional individual air conditioners. If a single
unit of the multi conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant
accidentally leaks out, its concentration does not reach
the limit (and in the event of an emergency, measures
can be made before injury can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.

NOTE 2:
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent


room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit

(3) If an indoor unit is installed in each partitioned room


and the refrigerant tubing is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
Refrigerant piping

Total amount of refrigerant (kg)


Min. volume of the indoor unit installed room (m3)
Concentration limit (kg/m3)

Outdoor unit
Very
small
room

The concentration limit of R410A which is used in multi


air conditioners is 0.3kg/m3.

e.g., charged
amount (10kg)

Room A Room B

Outdoor unit
e.g.,
charged amount (15kg)

Room C Room D Room E

Indoor unit
Small
room

Medium
room

Large room

Mechanical ventilation device - Gas leak detector

NOTE 3:
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 2.7m high)
40

Min. indoor floor area

NOTE 1:
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.

Important

Room F

Indoor unit

For the amount of charge in this example:


The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.

m 35
30
25

Range below the


density limit of
0.3 kg/m3
(countermeasur
es not needed)

20

Range above
the density limit
of 0.3 kg/m3
(countermeasur
es needed)

15
10
5
0

10

20

30
kg

Total amount of refrigerant

2 -2

SMMS-i Data book

Introduction

The next-generation -quality trio


Dedication to innovation and advanced intelligence fosters the imaginative
creativity with which we deliver total value in air conditioning systems.

innovation, intelligence and imagination


Industry-leading energy savings
(COP/EER)

Energy-efficient performance
for greater environmental
friendliness

6.38

COP

5.50

6.19

EER

5.60

7
6
5

4.42
Rated

4.06

3.44

50% load

3.21

8HP : MMY-MAP0804HT8-E
16HP : MMY-MAP1604HT8-E
(HP)

8HP

8HP

16HP

16HP

3
2

*European models

Industry-leading pipe length for greater flexibility


ry
Indust

No.1

Farthest equivalent length

* As of December 2009 (according to in-house studies)

Greater support for height differences between indoor units


ry
Indust

No.1
Single
system

Height between
indoor units

*Calculated at 3.5 meters per floor

3 -1

* As of December 2009 (according to in-house studies)

3 Introduction

The industry first!


Introducing high-performance outdoor units
with 3 compressors * 1 and 3 inverters
NEW

New DC twin-rotary compressor

Leading the world with Toshibas own new DC twin-rotary compressor


Improved motor
efficiency

Newly designed
compression path

Reduce 40%

Greater
parts precision

New DC twin-rotary compressor

(16HP Outdoor unit)

Compact and powerful magnetic rotor

Fast-calculating vector-controlled inverter

NEW

All-inverter control realizes finer control over operation to match the load
on the system

Smooth sine curve

Circuit board
(14HP, 16HP)

stry
The indu *2

Infinity variable control

1st!

Ultra-precise 0.1 Hz control over compressor


rotation speed
Current-SMMS

New-SMMSi

*1 14HP and 16HP models *2 As of December 2009 (according to in-house studies)

3 -2

SMMS-i Data book

System overview

1. OUTLINE OF TOSHIBA SUPER MMS


(Super Modular Multi System)
Shortest route design by free branching
The Combination of line and header branching is highly flexible.
Following the shortest design route possible, thereby saving
on installation time and cost. Line/header branching after the
header branching is only available with TOSHIBA Super MMS.

Line branching
Outdoor unit
Branching joint

8F

Indoor unit

Header branching
Outdoor unit
Branching
header

7F

Indoor unit

Line + Header branching

Header

Outdoor unit

Indoor
unit

Outdoor unit
Header

1F

Branching joint

TOSHIBA
Only

Indoor unit

Header branching after header branching


Outdoor unit
Header
TOSHIBA
Only

Outdoor
unit

Allowable pipe length:


235m equivalent length

1st branching
section

Height difference
between indoor
unit and indoor unit:
40m

Line branching after header branching

Height difference between


indoor
unit and outdoor unit: 70m (*1)

Branching joint

2F

From 1st branching to the furthest


indoor unit: 90m (*2)
*1: If the height different between(H2) indoor
units exceeds 3m, set below 50m.
*2 : If the height different between(H1) indoor
and outdoor units exceeds 3m, set below
65m.

Header
Indoor unit

4 -1

4 System overview

2. SUMMARY OF SYSTEM EQUIPMENTS


Equipment
Outdoor units
* SMMS outdoor unit
Inverter unit
10HP

Corresponding HP

Appearance

5HP*
6HP*
8HP
12HP
14HP
16HP
Heat
MMY- MAP0501HT8-E MAP0601HT8-E MAP0804HT8-E MAP1004HT8-E MAP1204HT8-E MAP1404HT8-E MAP1604HT8-E
Model pump
name Cooling
MMY- MAP0501T8-E MAP0601T8-E MAP0804T8-E MAP1004T8-E MAP1204T8-E MAP1404T8-E MAP1604T8-E
only
Cooling capacity (kW)
14.0
16.0
22.4
28.0
33.5
40.0
45.0
Heating capacity (kW)
16.0
18.0
25.0
31.5
37.5
45.0
50.0
No. of connectable
8
10
13
16
20
23
27
indoor units

Combination of outdoor units


Standard model
Corresponding HP
18HP
MMY- AP1814HT8-E
Combined
Model
MMY- AP1814T8-E
Cooling capacity (kW)
50.4
Heating capacity (kW)
56.5
10HP
8HP
Combined outdoor units

No. of connectable
30
indoor units

20HP
AP2014HT8-E
AP2014T8-E
56.0
63.0
10HP
10HP

Corresponding HP
34HP
MMY- AP3414HT8-E
Combined
Model
MMY- AP3414T8-E
Cooling capacity (kW)
96.0
Heating capacity (kW)
108.0
12HP
12HP
Combined outdoor units
10HP

No. of connectable
48
indoor units

36HP
AP3614HT8-E
AP3614HT8-E
101.0
113.0
12HP
12HP
12HP

22HP
AP2214HT8-E
AP2214T8-E
61.5
69.0
12HP
10HP

33

24HP
AP2414HT8-E
AP2414T8-E
68.0
76.5
12HP
12HP

37
38HP
AP3814HT8-E
AP3814T8-E
106.5
119.5
16HP
12HP
10HP

48

26HP
AP2614HT8-E
AP2614T8-E
73.0
81.5
16HP
10HP

40

43

40HP
AP4014HT8-E
AP4014T8-E
112.0
127.0
16HP
12HP
12HP

48

28HP
AP2814HT8-E
AP2814T8-E
78.5
88.0
16HP
12HP

47

42HP
AP4214HT8-E
AP4214T8-E
118.0
132.0
16HP
14HP
12HP

48

30HP
AP3014HT8-E
AP3014T8-E
85.0
95.0
16HP
14HP

44HP
AP4414HT8-E
AP4414T8-E
123.5
138.0
16HP
16HP
12HP

48

32HP
AP3214HT8-E
AP3214T8-E
90.0
100.0
16HP
16HP

48
46HP
AP4614HT8-E
AP4614T8-E
130.0
145.0
16HP
16HP
14HP

48

48
48HP
AP4814HT8-E
AP4814T8-E
135.0
150.0
16HP
16HP
16HP

48

48

High efficiency model


Corresponding HP
16HP
MMY- AP1624HT8-E
Combined
Model
MMY- AP1624T8-E
Cooling capacity (kW)
45.0
Heating capacity (kW)
50.0
8HP
8HP
Combined outdoor units

No. of connectable
27
indoor units

24HP
AP2424HT8-E
AP2424T8-E
68.0
76.5
8HP
8HP
8HP

Corresponding HP
38HP
MMY- AP3824HT8-E
Combined
Model
MMY- AP3824T8-E
Cooling capacity (kW)
106.5
Heating capacity (kW)
119.5
10HP
10HP
Combined outdoor units
10HP
8HP
No. of connectable
48
indoor units

40HP
AP4024HT8-E
AP4024T8-E
112.0
127.0
10HP
10HP
10HP
10HP

26HP
AP2624HT8-E
AP2624T8-E
73.0
81.5
10HP
8HP
8HP

40

28HP
AP2824HT8-E
AP2824T8-E
78.5
88.0
10HP
10HP
8HP

43
42HP
AP4224HT8-E
AP4224T8-E
118.0
132.0
12HP
10HP
10HP
10HP

48

30HP
AP3024HT8-E
AP3024T8-E
85.0
95.0
10HP
10HP
10HP

47

48

44HP
AP4424HT8-E
AP4424T8-E
123.5
138.0
12HP
12HP
10HP
10HP

48

32HP
AP3224HT8-E
AP3224T8-E
90.0
100.0
8HP
8HP
8HP
8HP
48

46HP
AP4624HT8-E
AP4624T8-E
130.0
145.0
12HP
12HP
12HP
10HP

48

34HP
AP3424HT8-E
AP3424T8-E
96.0
108.0
10HP
8HP
8HP
8HP

36HP
AP3624HT8-E
AP3624T8-E
101.0
113.0
10HP
10HP
8HP
8HP

48

48

48HP
AP4824HT8-E
AP4824T8-E
135.0
150.0
12HP
12HP
12HP
12HP

48

48

Branching joints and headers


Model name

Y-shape branching joint

(*3)

4-branching header

(*4)

8-branching header

(*4) (*5)

Branching joint for connection


of outdoor units
(1set of 1type of Y-shape joint
pipe and 2types of T-joint pipes
as described right.)

*1
*2
*3
*4
*5

Appearance

Usage (Classification according to indoor unit capacity code (*1))

RBM-BY55E

Total below 6.4

RBM-BY105E

Total 6.4 or more and below 14.2

(*2)

RBM-BY205E

Total 14.2 or more and below 25.2

(*2)

RBM-BY305E

Total 25.2 or more

(*2)

RBM-HY1043E Total below 14.2

Max.4 branches

RBM-HY2043E Total 14.2 or more and below 25.2


RBM-HY1083E Total below 14.2

Max.8 branches

RBM-HY2083E Total 14.2 or more and below 25.2


Usage
Piping at gas side (Y-shape)
RBM-BT14E

RBM-BT24E

Total below 26

Total 26 or more

31.8

38.1

28.6
25.4

Piping at liquid side (T-shape) Balance pipe (T-shape)


19.1
9.5

38.1
28.6

19.1

19.1

9.5

22.2
22.2

9.5
9.5

22.2

9.5

Capacity code can be obtained by the lists on next page and after the next page.(Capacity code is not actual capacity.)
If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
When using Y-shape branching joint for 1st branching, select according to the capacity code of the outdoor unit.
Max. capacity code of 6.0 in total can be connected.
If capacity code of outdoor unit is 26 or more, it is not used for 1st branching.

4 -2

9.5

4 System overview

3. List of product and combined model name


Heat Pump model
HP
No. of
Model name
Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used Inverter 14HP Used Inverter 16HP Used
(Capacity
combined
MMYMMYQty
MMYQty
MMYQty
MMYQty
MMYQty
MMYQty
MMYQty
code)
units
Standard model
5HP(5)*
MAP0501HT8-E
1
MAP0501HT8-E
1
6HP(6)*
MAP0601HT8-E
1
MAP0601HT8-E
1
8HP(8)
MAP0804HT8-E
1
MAP0804HT8-E
1
10HP(10)
MAP1004HT8-E
1
MAP1004HT8-E
1
12HP(12)
MAP1204HT8-E
1
MAP1204HT8-E
1
14HP(14)
MAP1404HT8-E
1
MAP1404HT8-E
1
16HP(16)
MAP1604HT8-E
1
MAP1604HT8-E
1
18HP(18)
AP1814HT8-E
2
MAP0804HT8-E
1
MAP1004HT8-E
1
20HP(20)
AP2014HT8-E
2
MAP1004HT8-E
2
22HP(22)
AP2214HT8-E
2
MAP1004HT8-E
1
MAP1204HT8-E
1
24HP(24)
AP2414HT8-E
2
MAP1204HT8-E
2
26HP(26)
AP2614HT8-E
2
MAP1004HT8-E
1
MAP1604HT8-E
1
28HP(28)
AP2814HT8-E
2
MAP1204HT8-E
1
MAP1604HT8-E
1
30HP(30)
AP3014HT8-E
2
MAP1404HT8-E
1
MAP1604HT8-E
1
32HP(32)
AP3214HT8-E
2
MAP1604HT8-E
2
34HP(34)
AP3414HT8-E
3
MAP1004HT8-E
1
MAP1204HT8-E
2
36HP(36)
AP3614HT8-E
3
MAP1204HT8-E
3
38HP(38)
AP3814HT8-E
3
MAP1004HT8-E
1
MAP1204HT8-E
1
MAP1604HT8-E
1
40HP(40)
AP4014HT8-E
3
MAP1204HT8-E
2
MAP1604HT8-E
1
42HP(42)
AP4214HT8-E
3
MAP1204HT8-E
1
MAP1404HT8-E
1
MAP1604HT8-E
1
44HP(44)
AP4414HT8-E
3
MAP1204HT8-E
1
MAP1604HT8-E
2
46HP(46)
AP4614HT8-E
3
MAP1404HT8-E
1
MAP1604HT8-E
2
48HP(48)
AP4814HT8-E
3
MAP1604HT8-E
3
High efficiency model
16HP(16)
AP1624HT8-E
2
MAP0804HT8-E
2
24HP(24)
AP2424HT8-E
3
MAP0804HT8-E
3
26HP(26)
AP2624HT8-E
3
MAP0804HT8-E
2
MAP1004HT8-E
1
28HP(28)
AP2824HT8-E
3
MAP0804HT8-E
1
MAP1004HT8-E
2
30HP(30)
AP3024HT8-E
3
MAP1004HT8-E
3
32HP(32)
AP3224HT8-E
4
MAP0804HT8-E
4
34HP(34)
AP3424HT8-E
4
MAP0804HT8-E
3
MAP1004HT8-E
1
36HP(36)
AP3624HT8-E
4
MAP0804HT8-E
2
MAP1004HT8-E
2
38HP(38)
AP3824HT8-E
4
MAP0804HT8-E
1
MAP1004HT8-E
3
40HP(40)
AP4024HT8-E
4
MAP1004HT8-E
4
42HP(42)
AP4224HT8-E
4
MAP1004HT8-E
3
MAP1204HT8-E
1
44HP(44)
AP4424HT8-E
4
MAP1004HT8-E
2
MAP1204HT8-E
2
46HP(46)
AP4624HT8-E
4
MAP1004HT8-E
1
MAP1204HT8-E
3
48HP(48)
AP4824HT8-E
4
MAP1204HT8-E
4

* : SMMS outdoor unit

1. Allocation standard of model name


MMY_ M

AP

_E
Power supply specifications, 3 380-400-415V, 50Hz ....... 8
T: Capacity variable unit
H: Heat pump
Development series No.
0 : Single model, 1: Standard model, 2 : High efficiency model
Capacity rank HP
Refrigerant R410A
M: Single module unit, No mark: Combined Model name
Modular Multi

2. Rang of combined capacity


No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)

3. Rated conditions
Cooling: Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating: Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

4 -3

4 System overview

Cooling Only model


HP(Capacity Model name
code)
MMYStandard model
5HP(5)*
MAP0501T8-E
6HP(6)*
MAP0601T8-E
8HP(8)
MAP0804T8-E
10HP(10)
MAP1004T8-E
12HP(12)
MAP1204T8-E
14HP(14)
MAP1404T8-E
16HP(16)
MAP1604T8-E
18HP(18)
AP1814T8-E
20HP(20)
AP2014T8-E
22HP(22)
AP2214T8-E
24HP(24)
AP2414T8-E
26HP(26)
AP2614T8-E
28HP(28)
AP2814T8-E
30HP(30)
AP3014T8-E
32HP(32)
AP3214T8-E
34HP(34)
AP3414T8-E
36HP(36)
AP3614T8-E
38HP(38)
AP3814T8-E
40HP(40)
AP4014T8-E
42HP(42)
AP4214T8-E
44HP(44)
AP4414T8-E
46HP(46)
AP4614T8-E
48HP(48)
AP4814T8-E
High efficiency model
16HP(16)
AP1624T8-E
24HP(24)
AP2424T8-E
26HP(26)
AP2624T8-E
28HP(28)
AP2824T8-E
30HP(30)
AP3024T8-E
32HP(32)
AP3224T8-E
34HP(34)
AP3424T8-E
36HP(36)
AP3624T8-E
38HP(38)
AP3824T8-E
40HP(40)
AP4024T8-E
42HP(42)
AP4224T8-E
44HP(44)
AP4424T8-E
46HP(46)
AP4624T8-E
48HP(48)
AP4824T8-E

No. of
combined
units
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3

Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used Inverter 14HP Used Inverter 16HP Used
MMYQty
MMYQty
MMYQty
MMYQty
MMYQty
MMYQty
MMYQty
MAP0501T8-E

1
MAP0601T8-E

1
MAP0804T8-E

1
MAP1004T8-E

1
MAP1204T8-E

1
MAP1404T8-E

MAP0804T8-E

2
3
3
3
3
4
4
4
4
4
4
4
4
4

MAP0804T8-E
MAP0804T8-E
MAP0804T8-E
MAP0804T8-E

2
3
2
1

MAP0804T8-E
MAP0804T8-E
MAP0804T8-E
MAP0804T8-E

4
3
2
1

MAP1004T8-E
MAP1004T8-E
MAP1004T8-E

1
2
1

MAP1004T8-E

MAP1004T8-E

MAP1004T8-E

MAP1004T8-E
MAP1004T8-E
MAP1004T8-E

1
2
3

MAP1004T8-E
MAP1004T8-E
MAP1004T8-E
MAP1004T8-E
MAP1004T8-E
MAP1004T8-E
MAP1004T8-E

1
2
3
4
3
2
1

MAP1204T8-E
MAP1204T8-E

1
2

MAP1204T8-E

MAP1204T8-E
MAP1204T8-E
MAP1204T8-E
MAP1204T8-E
MAP1204T8-E
MAP1204T8-E

2
3
1
2
1
1

MAP1204T8-E
MAP1204T8-E
MAP1204T8-E
MAP1204T8-E

MAP1404T8-E

MAP1404T8-E

MAP1404T8-E

1
2
3
4

* : SMMS outdoor unit

1. Allocation standard of model name


MMY_ M

AP

_E
Power supply specifications, 3 380-400-415V, 50Hz ....... 8
T: Capacity variable unit
Development series No.
0 : Single model, 1: Standard model, 2 : High efficiency model
Capacity rank HP
Refrigerant R410A
M: Single module unit, No mark: Combined Model name
Modular Multi

2. Rang of combined capacity


No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)

3. Rated conditions
Cooling: Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB

4 -4

MAP1604T8-E

MAP1604T8-E
MAP1604T8-E
MAP1604T8-E
MAP1604T8-E

1
1
1
2

MAP1604T8-E
MAP1604T8-E
MAP1604T8-E
MAP1604T8-E
MAP1604T8-E
MAP1604T8-E

1
1
1
2
2
3

4 System overview
4. Indoor unit
Type

4-way Air Discharge


Cassette Type

Compact 4-way
Cassette (600 600)
Type

2-way Air Discharge


Cassette Type

1-way Air Discharge


Cassette Type

Concealed Duct
Standard Type

Concealed Duct
High Static
Pressure Type

Slim Duct Type

Under Ceiling Type

High-wall Type
1 series

High-wall Type
2 series

High-wall Type
3 series

Floor Standing
Concealed Type

Floor Standing
Cabinet Type

Floor Standing Type

Fresh Air Intake


Indoor Unit Type

Appearance

Model name
MMU-AP0092H
MMU-AP0122H
MMU-AP0152H
MMU-AP0182H
MMU-AP0242H
MMU-AP0272H
MMU-AP0302H
MMU-AP0362H
MMU-AP0482H
MMU-AP0562H
MMU-AP0071MH
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
MMU-AP0181MH
MMU-AP0071WH
MMU-AP0091WH
MMU-AP0121WH
MMU-AP0151WH
MMU-AP0181WH
MMU-AP0241WH
MMU-AP0271WH
MMU-AP0301WH
MMU-AP0071YH
MMU-AP0091YH
MMU-AP0121YH
MMU-AP0152SH
MMU-AP0182SH
MMU-AP0242SH
MMD-AP0071BH
MMD-AP0091BH
MMD-AP0121BH
MMD-AP0151BH
MMD-AP0181BH
MMD-AP0241BH
MMD-AP0271BH
MMD-AP0301BH
MMD-AP0361BH
MMD-AP0481BH
MMD-AP0561BH
MMD-AP0181H
MMD-AP0241H
MMD-AP0271H
MMD-AP0361H
MMD-AP0481H
MMD-AP0721H
MMD-AP0961H
MMD-AP0071SPH
MMD-AP0091SPH
MMD-AP0121SPH
MMD-AP0151SPH
MMD-AP0181SPH
MMC-AP0151H
MMC-AP0181H
MMC-AP0241H
MMC-AP0271H
MMC-AP0361H
MMC-AP0481H
MMK-AP0071H
MMK-AP0091H
MMK-AP0121H
MMK-AP0151H
MMK-AP0181H
MMK-AP0241H

Capacity rank

Capacity code

009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
056 type
007 type
009 type
012 type
015 type
018 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
056 type
018 type
024 type
027 type
036 type
048 type
072 type
096 type
007 type
009 type
012 type
015 type
018 type
015 type
018 type
024 type
027 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
024 type

1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
6.00
2.00
2.50
3.00
4.00
5.00
8.00
10.00
0.80
1.00
1.25
1.70
2.00
1.70
2.00
2.50
3.00
4.00
5.00
0.80
1.00
1.25
1.70
2.00
2.50

Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
16.0
5.6
7.1
8.0
11.2
14.0
22.4
28.0
2.2
2.8
3.6
4.5
5.6
4.5
5.6
7.1
8.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
7.1

Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
6.3
8.0
9.0
10.0
16.0
25.0
31.5
2.5
3.2
4.0
5.0
6.3
5.0
6.3
8.0
9.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
8.0

MMK-AP0072H

007 type

0.80

2.2

2.5

MMK-AP0092H

009 type

1.00

2.8

3.2

MMK-AP0122H

012 type

1.25

3.6

4.0

MMK-AP0073H
MMK-AP0093H
MMK-AP0123H
MMK-AP0153H
MMK-AP0183H
MMK-AP0243H
MML-AP0071BH
MML-AP0091BH
MML-AP0121BH
MML-AP0151BH
MML-AP0181BH
MML-AP0241BH
MML-AP0071H
MML-AP0091H
MML-AP0121H
MML-AP0151H
MML-AP0181H
MML-AP0241H
MMF-AP0151H
MMF-AP0181H
MMF-AP0241H
MMF-AP0271H
MMF-AP0361H
MMF-AP0481H
MMF-AP0561H
MMD-AP0481HFE
MMD-AP0721HFE
MMD-AP0961HFE

007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
015 type
018 type
024 type
027 type
036 type
048 type
056 type
048 type
072 type
096 type

0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
6.00
5.00
8.00
10.00

2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
16.0
14.0
22.4
28.0

2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
18.0
8.9
13.9
17.4

4 -5

4 System overview

5. Remote controller
Name

Model
name

Appearance

Application

Function

RBC-AMT32E/RBC-AMT31E

Wired remote controller

Connected to indoor unit

TIMER SET

SET

Start/Stop
Temperature setting
Change of air flow
Check code display

Start/Stop
Mode change
Temperature setting
Change of air flow
Timer function
Control by 2 remote controllers is available.
Check code display

CL

Wired remote
controller

Wired remote controller


(In case of control by 2
remote controllers)

RBC-AS21E2
RBC-AX22CE2

RBC-AX31U(W)-E
RBC-AX31U(WS)-E

Simple remote controller

Connected to indoor unit

RBC-AX31U(W)-E
RBC-AX31U(WS)-E
(For 4-way Air Discharge Cassette)
RBC-AX22CE2
(For Under Ceiling, 1-way Air Discharge
Cassette SH)

TCB-AX21E2

Simple wired remote controller

Start/Stop
Mode change
Temperature setting
Change of air flow
Timer function
Filter sign
Self-diagnosis function
Control by 2 remote controllers is available.

TIME
FILTER
L
RESET TEST

Connected to indoor unit

Wireless remote controller kit

TCB-AX21E2
(For Compact 4-way Cassette, 2-way Air
Discharge Cassette, 1-way Air Discharge
Cassette YH, Concealed Duct Standard, Slim
Duct, Floor Standing Cabinet, Floor Standing)
Connected to outdoor unit,
indoor unit
Header

Follower

Individual control up to 16 indoor units.


Setting of simultaneous ON/OFF 3 times for
each day of the week when combined with
schedule timer.

TCB-CC163TLE2

ON-OFF controller

Connected to 2 remote controllers is available.

Outdoor unit

ON-OFF
controller
ON-OFF
controller

Indoor
remote controller

4 -6

4 System overview
Name

Model
name

Appearance

Application

TCB-SC642TLE2

ZONE
ALL
ZONE
GROUP

CODE
No.
1234
SET DATA
SETTING

R.C.

UNIT No.

TEST

Connected to outdoor unit,


indoor unit
Header

No.

Function

Follower

GROUP
SELECT

ZONE

CL

SET

Outdoor unit

Central remote controller

Central
remote controller

BMS-CM1280TLE

Individual control up to 64 indoor units.


Individual control for max. 64 indoor units
divided into 4 zones.
Up to 16 indoor units
for each zone
Up to 16 outdoor header units are connectable.
4 type central control setting to inhibit individual
operation by remote controller can be selected.

Central
remote
controller
Indoor
remote controller

4 -7

Setting for one of 1 to 4 zones is available.


Can be used with other central control devices
(Up to 10 central control devices with in one
control circuit)
Two selectable control modes
Central controller mode
Remote controller mode
Setting of simultaneous ON/OFF 3 times for
each day of the week combined with schedule
timer.
Individual control of up to (64 indoor units) 2
TCC-LINK buses
Individual control of up to (64 indoor units
divided 1 to 64 zone) 2 TCC-LINK buses (Up
to 64 indoor units for each zone)
Up to 16 outdoor header units are connectable
per 1 TCC-LINK bus
4 types of central control settings of inhibit
individual operation by remote controller can be
selected.
Setting for (one of 1 to 64 zones) 2ch is
available.
Setting for (one of 1 to 64 groups) 2ch is
available.
Usable with other central control devices
(Up to 10 central control devices in one TCCLINK bus).
Two control mode selectively
(contral controller mode)
(Remote controller mode) by SW01 bit6.
Combined with schedule timer.
Return back setting

4 System overview
Name

Model
name

Appearance

Application

Function

Schedule timer mode

Outdoor unit

TCB-EXS21TLE

Schedule timer

Indoor unit

Schedule timer mode


6 programmings per day
Enabling 8 groups to be programmed
A maximum of 64 indoor units can be controlled
A maximum of 100 hours back-up power supply
Weekly timer mode
7 types of weekly schedule and 3
programmings per day
Can set ON/OFF by one-minute interval
Wekly timer mode

TCC-LINK

Connected to central remote controller or


wired remote controller

Central
remote controller

Schedule
timer

Connected to indoor unit

RBC-AMS41E

Remote controller with weekly timer


(7-day timer function)

Wired
remote controller

Simple remote controller

4 -8

Schedule
timer

Clock display
Schedule timer:
Possible to program schedule timer (7-day
timer) function
Possible to program 8 functions for each day of
the week
* The following items can be set in program:
Operation time, Operation start/stop, Operation
mode, Temperature setting, Restriction on
button operation.

SMMS-i Data book

Basic system configuration

1. Basic systems
8 HP system

Capacity code

Max. indoor unit : 13 units


Capacity code of indoor unit :

Total 10.4

Min. : 4
Max. : 10.8

8HP
10.4

No. of total units

Capacity code
over the branch
(0.8 + 0.8 = 1.6)

Outdoor unit

13

Indoor unit
designation

4.8

4.0

007

007

(0.8)

5.6

(0.8)

(0.8)

3.2

007

2.4

007

(0.8)

Capacity
Code

007

(0.8)

4.0

(0.8)

1.6

007

(0.8)

007

(0.8)

2.4

007

4.8

Indoor unit 007


Remote
controller

3.2

(0.8)

1.6

007

(0.8)

007

(0.8)

0.8

007
(0.8)

20 HP system

007
(0.8)

Capacity code

Max. indoor unit : 33 units


Capacity code of indoor unit :

Total 26.75

Min. : 10
Max. : 27

No. of total units

Outdoor unit

19

10HP 10HP

26.75

10.25

10
8.25

018
(2.0)

16.5

8.25
018
(2.0)

8.25
Indoor unit 018
Remote
controller

(2.0)

6.25

018
(2.0)

6.25
012
(1.25)

6.25
012
(1.25)

5.0

012

012

(1.25)

5.0

3.75

(1.25)

3.75

012

012

(1.25)

5.0

(1.25)

3.75

012
(1.25)

5 -1

012
(1.25)

012
(1.25)

2.5
012
(1.25)

2.5
012
(1.25)

012
(1.25)

2.5
012
(1.25)

012
(1.25)

012
(1.25)

5 Basic system configuration


40 HP system (Standard model)
Max. indoor unit : 48 units
Capacity code of indoor unit :

Capacity code
Total 53.75

Min. : 20
Max. : 54

No. of total units


32

Outdoor unit

16HP 12HP 12HP

40
53.75

14.0

28

13.0

009

39.75

13.25

13.25

12.25

009
(1)

13.25
Indoor unit 009
Remote
controller

(1)

(1)

012

(1)

11.25

009

(1.25)

10.25

009

(1)

12.25

012

(1)

11.25

009

(1.25)

10.25

009

(1)

9.75

012

(1)

11.25

009

(1)

11.0

009

(1)

12.25

009

26.5

12.0

009

(1)

16

(1.25)

10.25

009
(1)

012
(1.25)

5 -2

8.5

012

018

(1.25)

9.0

7.75

012

012

(1.25)

9.0

(1.25)

7.75

012

012

(1.25)

9.0

(2.0)

(1.25)

7.75

012
(1.25)

012
(1.25)

6.5
024
(2.5)

036
(4)

6.5
024
(2.5)

036
(4)

6.5
024
(2.5)

036
(4)

6.5
024
(2.5)

036
(4)

5 Basic system configuration

2. Fresh Air Intake Indoor Unit Type


34 HP system

Capacity code

Connecting limitation
The total capacity of the fresh air intake units and the indoor units is restricted to 80
to 100% against the capacity of the outdoor units.
Up to two fresh air intake units can be connected on one line of the multi system.
The allowable total capacity of fresh air intake units shall be 30% or less against
the total capacity of the indoor units (including the fresh air intake units).
The fresh air intake units only cannot connected.

Total 34
No. of total units
8

12HP 12HP 10HP

Outdoor unit

34
24

20

036

16

036

(4)

(4)

12

036

036

(4)

(4)

036
(4)

Indoor unit

036
(4)

Remote
controller

10

024

Fresh Air Intake Indoor unit

024
(5)

(5)

Remote
controller

5 -3

SMMS-i Data book

Equipment selection procedure

1. Selection flow chart


1 Determination of indoor air-conditioning load at each room.

2 Preliminary selection of indoor units in the standard capacity no less


than air-conditioning load at each room.
3 Calculate corrected capacity A of each indoor unit by correcting of
indoor temperature for the standard capacity of each indoor unit.(Refer
to Chart [1])

4 Preliminary selection of outdoor unit in the standard capacity no less


than total values of corrected capacity A in indoor units. At the same time,
check both connectable indoor units number and the outdoor unit
diversity(Connected ratio of indoor units to outdoor units) for the
specifications.

2 Increase of indoor
unit capacity at object
room against airconditioning load

5 Calculate corrected capacity B of each indoor unit by following 2 steps.


Step1:Find the correction value of "Connecting pipe length and lift" by
both the longest length and the largest height with selected piping
condition at 4 or 4.(Refer to Chatrt [3])
Step2:Calculate by multiplying the value of step1 by corrected capacity A.

NG

6 Corrected capacity B of indoor


unit >= air-conditioning load (for All
rooms)

YES
OK
7 Find correction values of below items for the standard capacity of
outdoor unit selected at 4 or 4.
Then determination of total corrected capacity of the selected outdoor unit
by all multiplying.
-Correction of indoor temperature condition(Refer to Chart [1])
-Correction of outdoor temperature condition(Refer to Chart [2])
-Correction of connecting pipe length and lift between indoor and outdoor
units by both the longest length and the largest height (Refer to Chart [3])
-Correction of outdoor unit diversity in only over 100%(Refer to Chart [4])
-Correction of frost condition on outdoor heat exchanger when in heating
(Refer to Chart [5])

8 Calculate corrected capacity C of each indoor unit by multiplying the


total corrected capacity of outdoor unit at 7by proportional division of
each indoor unit standard capacity for total standard capacity of all indoor
units.

5 Increase of outdoor unit capacity.


At the same time, check both
connectable indoor units number
and the outdoor unit diversity

NG

9 Corrected capacity C of indoor


unit >= air-conditioning load (for All
rooms)

OK
end

6 -1

NO

5 <Only cooling>
The correction characteristic
of "connecting pipe length and
lift"(Graph [3]) between
increased outdoor unit at ?
and preliminary selected
outdoor unit at ? is different.
(The both graphs are
different.)

6 Equipment selection procedure


2. Operational temperature range
Heating

35
30
25

Continuously
operable
range

20
15
10
5
0
-5
-10
10

15

20

25

28

30

Indoor air wet bulb temp. (C)

20
15
10
5

Range for warming


up operation

Outdoor air wet bulb temp. (C)

40

Range for pull


down operation

Outdoor air dry bulb temp. (C)

Cooling
45

0
-5
-10

Continuously
operable
range

-15
-20

10

15

20

25

30

Indoor air dry bulb temp. (C)

The unit will operate down to an outdoor temperature of


-20C, however considerable performance decrease will be expected below -15C.
Therefore please consider installation location/surroundings and system design
when expected to operate between -15C and -20C.

3. Combination conditions for indoor unit and outdoor unit


1. For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank type

007

009

012

015

018

024

027

030

036

048

056

072

096

Capacity code

0.8

1.25

1.7

2.5

3.2

10

NOTE:
Capacity rank: Correspondence to Btu/h.

Capacity code: Correspondence to Horsepower.

2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
Outdoor unit (Heat pump)
Standard model
MMY-MAP0501HT8-E*
MMY-MAP0601HT8-E*
MMY-MAP0804HT8-E
MMY-MAP1004HT8-E
MMY-MAP1204HT8-E
MMY-MAP1404HT8-E
MMY-MAP1604HT8-E
MMY-AP1814HT8-E
MMY-AP2014HT8-E
MMY-AP2214HT8-E
MMY-AP2414HT8-E
MMY-AP2614HT8-E
MMY-AP2814HT8-E
MMY-AP3014HT8-E
MMY-AP3214HT8-E
MMY-AP3414HT8-E
MMY-AP3614HT8-E
MMY-AP3814HT8-E
MMY-AP4014HT8-E
MMY-AP4214HT8-E
MMY-AP4414HT8-E
MMY-AP4614HT8-E
MMY-AP4814HT8-E
High efficiency model
MMY-AP1624HT8-E
MMY-AP2424HT8-E
MMY-AP2624HT8-E
MMY-AP2824HT8-E
MMY-AP3024HT8-E
MMY-AP3224HT8-E
MMY-AP3424HT8-E
MMY-AP3624HT8-E
MMY-AP3824HT8-E
MMY-AP4024HT8-E
MMY-AP4224HT8-E
MMY-AP4424HT8-E
MMY-AP4624HT8-E
MMY-AP4824HT8-E

Outdoor unit (Cooling only)

Capacity code of outdoor unit

Max. No. of indoor units

Total capacity code of


indoor units

MMY-MAP0501T8-E*
MMY-MAP0601T8-E*
MMY-MAP0804T8-E
MMY-MAP1004T8-E
MMY-MAP1204T8-E
MMY-MAP1404T8-E
MMY-MAP1604T8-E
MMY-AP1814T8-E
MMY-AP2014T8-E
MMY-AP2214T8-E
MMY-AP2414T8-E
MMY-AP2614T8-E
MMY-AP2814T8-E
MMY-AP3014T8-E
MMY-AP3214T8-E
MMY-AP3414T8-E
MMY-AP3614T8-E
MMY-AP3814T8-E
MMY-AP4014T8-E
MMY-AP4214T8-E
MMY-AP4414T8-E
MMY-AP4614T8-E
MMY-AP4814T8-E

5
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48

8
10
13
16
20
23
27
30
33
37
40
43
47
48
48
48
48
48
48
48
48
48
48

2.5 to 6.75
3 to 8.1
4 to 10.8
5 to 13.5
6 to 16.2
7 to 18.9
8 to 21.6
9 to 24.3
10 to 27
11 to 29.7
12 to 32.4
13 to 35.1
14 to 37.8
15 to 40.5
16 to 43.2
17 to 45.9
18 to 48.6
19 to 51.3
20 to 54
21 to 56.7
22 to 59.4
23 to 62.1
24 to 64.8

MMY-AP1624T8-E
MMY-AP2424T8-E
MMY-AP2624T8-E
MMY-AP2824T8-E
MMY-AP3024T8-E
MMY-AP3224T8-E
MMY-AP3424T8-E
MMY-AP3624T8-E
MMY-AP3824T8-E
MMY-AP4024T8-E
MMY-AP4224T8-E
MMY-AP4424T8-E
MMY-AP4624T8-E
MMY-AP4824T8-E

16
24
26
28
30
32
34
36
38
40
42
44
46
48

27
40
43
47
48
48
48
48
48
48
48
48
48
48

8 to 21.6
12 to 32.4
13 to 35.1
14 to 37.8
15 to 40.5
16 to 43.2
17 to 45.9
18 to 48.6
19 to 51.3
20 to 54
21 to 56.7
22 to 59.4
23 to 62.1
24 to 64.8

* : SMMS

50 to 135% of outdoor unit capacity

6 -2

6 Equipment selection procedure


4. Cooling/heating capacity characteristics
1. Correction charts for cooling capacity calculation
[1] Indoor air wet bulb temperature vs. capacity
correction value

[2] Outdoor air dry bulb temperature vs.capacity


correction value

Capacity correction value

1.1

1.0

0.9

1.0

0.9
-10

24

-5

Indoor air wet bulb temp. (C)


HP
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48

0 10 20 30 40 50 60 70 80 90100 110 120130 140 150160 170 180190 200 210

-40

40 43

235
235
235
235
235
235
235
235
235
235
235
185
185

A3
B3
B3
B3
B3
B3
A3
B3
B3
B3
B3
C1
C1

72.5%

75%

77.5%

70%

-40

0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220

0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230

Pipe length (Equivalent length) L (m)

67.5%

0 10 20 30 40 50 60 70 80 90100 110 120130 140 150160 170 180190 200 210

Pipe length (Equivalent length) L (m)

6 -3

70%

72.5%

75%

77.5%

80%

Outdoor unit (B1)


70
60
50
40
30
20
10
0
-10
-20
-30
-40

100%
97.5%
95%

Height of outdoor unit H (m)

70%

72.5%

75%

77.5%

80%

82.5%

85%

87.5%

92.5%

90%

95%

35

Pipe length (Equivalent length) L (m)

Outdoor unit (A3)

100%
97.5%

Height of outdoor unit H (m)

30

Outdoor unit (A2)


70
60
50
40
30
20
10
0
-10
-20
-30

Pipe length (Equivalent length) L (m)

70
60
50
40
30
20
10
0
-10
-20
-30

A2

80%

72.5%

75%

77.5%

80%

82.5%

85%

87.5%

90%

92.5%

97.5%
95%

100%

Height of outdoor unit H (m)

Outdoor unit (A1)


70
60
50
40
30
20
10
0
-10
-20
-30
-40

25

220

82.5%

B Indoor unit

l'c

20

High efficiency model


Pipe length
Graph

85%

l'b

15

82.5%

l'a

92.5%

hc

ha

90%

hb

H = ho +
(Largest one of ha, hb, and hc)

Height of outdoor unit H (m)

l'o

92.5%

L' is the longest one of


(l'o + l'a, l'o + l'b, l'o + l'c)

90%

Outdoor unit

Standard model
Pipe length
Graph
210
A1
210
B1
210
A1
210
A1
210
A1
220
B2
220
B2
220
A2
220
A2
220
B2
220
B2
220
B2
220
B2
235
B3
235
A3
235
B3
235
B3
235
B3
235
B3
185
C1
185
C1

100%
97.5%
95%

[3] Connecting pipe length and lift difference between


indoor and outdoor units vs. capacity correction value

ho

10

Outdoor air dry bulb temp. (C)

87.5%

20

1.1

85%

0.8
15

1.2

87.5%

Capacity correction value

1.2

0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220

65%

67.5%

70%

72.5%

75%

77.5%

80%

82.5%

85%

87.5%

92.5%

90%

-40
0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230

Pipe length (Equivalent length) L (m)

67.5%

70%

72.5%

75%

77.5%

80%

82.5%

85%

87.5%

90%

Outdoor unit (C)


70
60
50
40
30
20
10
0
-10
-20
-30
-40

100%
97.5%
95%
92.5%

Height of outdoor unit H (m)

Pipe length (Equivalent length) L (m)

Outdoor unit (B3)


70
60
50
40
30
20
10
0
-10
-20
-30

100%
97.5%
95%

67.5%

70%

72.5%

75%

77.5%

80%

85%

82.5%

87.5%

90%

Height of outdoor unit H (m)

-40

92.5%

Outdoor unit (B2)


70
60
50
40
30
20
10
0
-10
-20
-30

100%
97.5%
95%

Height of outdoor unit H (m)

6 Equipment selection procedure

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180

Pipe length (Equivalent length) L (m)

[4]* Correction of outdoor unit diversity


1.2

Correction

1.0
0.8
0.6
0.4
0.2

20

40

60

80

100

120

135

Standard capacity ratio


Indoor units total capacity ratio (%)

*:

Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the
outdoor unit capacity.

6 -4

6 Equipment selection procedure


2. Correction charts for heating capacity calculation
[1] Indoor air dry bulb temperature vs. capacity correction value

[2] Outdoor air wet bulb temperature vs. capacity correction value
Capacity correction value

Capacity correction value

1.2

1.1

1.0

0.9

0.8
15

20

24

1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-20

Indoor air dry bulb temp. (C)

-10

-15

-5

10

100

120

Outdoor air wet bulb temp. (C)

15

[3] Connecting pipe length and lift difference between indoor


and outdoor units vs. capacity correction value
Outdoor unit

ho

L' is the longest one of


(l'o + l'a, l'o + l'b, l'o + l'c)

l'o

H = ho +
(Largest one of ha, hb, and hc)

hc

hb

ha

l'a

l'b

B Indoor unit
C

[4]* Correction of outdoor unit diversity

Outdoor unit (8 to 48HP)

1.2
1.0

Correction

85%

86%

87%

89%

88%

90%

91%

92%

94%

93%

95%

97%

96%

98%

70
60
50
40
30
20
10
0
-10
-20
-30
-40

100%
99%

Height of outdoor unit H (m)

l'c

0.8
0.6
0.4
0.2

0 10 20 30 40 50 60 70 80 90 100 110 120130 140 150160 170 180190 200 210 220 230

Pipe length (Equivalent length) L (m)


0

20

40

60

80

135

Standard capacity ratio


Indoor units total capacity ratio (%)

*: Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the
outdoor unit capacity.

3. Capacity correction in case of frost on the outdoor heat exchanger when in heating

Capacity correction value

Correct the heating capacity when frost can be found on the outdoor heat exchanger.
Heating capacity = Capacity after correction of outdoor unit x Correction value of capacity resulted from frost
(Capacity after correction of outdoor unit: Heating capacity calculated in the above item 2.)
[5] Capacity correction in case of frost on the outdoor heat exchanger
1.0

0.9

0.8
-15

-10

-5

Outdoor air wet bulb temp. (C)

4. Rated conditions
Cooling: Indoor air temperature 27C DB/19C WB, Outdoor air temperature 35C DB
Heating: Indoor air temperature 20C DB, Outdoor air temperature 7C DB/6C WB

6 -5

6 Equipment selection procedure


5. Selection procedure for fresh air intake indoor unit
5.1 Selection flow chart
1. Decisions of both air volume for fresh air intake and static pressure of duct
It is necessary to calculate required ventilatory volume to decide the air volume.
Be sure to consider the balance of air supply and exhaust.

2. Decisions of fresh air intake indoor unit by necessary air volume and external
static pressure

3. Temporary grouping of outdoor units and normal indoor units + fresh air intake
indoor units
Grouping limitation
*1 : The system is SMMS, is not SHRM
SHRM(heat
(heatrecovery).
recovery).
*2 : Up to two fresh air intake indoor units on one line of the multi system.
*3 : The allowable total capacity of fresh air intake units shall be 30% or less against the total
capacity of the indoor units
units(including
(includingthe
thefresh
freshair
airintake
intakeunits).
units).
*4 : The total capacity of the fresh air intake units and the indoor units is restricted to 80 to
100% against the capacith
capacity of the outdoor units.
*5 : The fresh air intake units only cannot connected.

4. Check of piping length and the height difference for between outdoor units and
normal indoor units + fresh air intake indoor units.

5. Capacity correction with design indoor temperature and outdoor temperature

6. Check of temporary grouping


outdoor units and normal indoor
units + fresh air intake indoor units

No good

OK

7. Decision of combination between outdoor units and normal indoor units + fresh
air intake indoor units

end

6 -6

6 Equipment selection procedure


5.2 Operatable temperature range and discharge temperature set up
Operatable temperature range
Ts : Setup Temp.

Fresh air temp.C


10

10

20
Ts

COOL mode

30

40

Operable mode and sidecharge temp setup range

50

40

FAN

Operation mode
COOL
HEAT

At shipment from factory


18C
25C

Setup range
16 to 27C
16 to 27C

COOL
Ts + 3C

Ts

HEAT mode

HEAT

43

FAN
Ts 3C

In cooling operation, if the temperature is below 5C, the operation stops automatically. (FAN stop)
In heating operation, if the temperature is below 5C, the operation stops automatically. (FAN stop)
(To protect the refrigerant cycle)

5.3 Calculation of required ventilatory volume


The required ventilatory volume (air supply quantity) is calculated depending on the ventilation purpose or the
number of ventilation ducts.
Ex. Calculation method based on a general living room under Japanese Building Standard Law
Available amount of ventilation V [m3/h]
V = 20 Af/N
Af : Floor space of the living room m2
N : Occupation area per room m2
If N > 10, please set N to 10.
(In the case of a living room of the special building, please change 10m2 to 3m2 as N.)
Af/N means number of people in the living room.
So if X as number of people in the living room is settled, V is able to define by the below expression
V = 20 x X
This expression is based on Japanese Building Standard Law and the coefficient 20 (unit : m3/h) is based on
exhaust volume of carbon dioxide by breathing per person who is quietly sitting adult male.
Although the coefficient is not always enough ventilatory volume.
In fact in ASHRAE (American Society of Heating Refrigerating and Air-Conditioning Engineers),
it shows 30 m3/h per person as its guideline in consideration of smells of the cigarette and so on.
Please calculate the required ventilatory volume with meeting for local regulations, market requirements
and customers purpose.

6 -7

SMMS-i Data book

Refrigerant piping design

1. WARNINGS ON REFRIGERANT LEAKAGE


Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively.
Suffocation from leakage of R410A is almost
nonexistent. With the recent increase in the number of
high concentration buildings, however, the installation of
multi air conditioner systems is on the increase because
of the need for effective use of floor space, individual
control, energy conservation by curtailing heat and
carrying power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared
with conventional individual air conditioners. If a single
unit of the multi conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant
accidentally leaks out, its concentration does not reach
the limit (and in the event of an emergency, measures
can be made before injury can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.

NOTE 2:
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)

(2) When there is an effective opening with the adjacent


room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit

(3) If an indoor unit is installed in each partitioned room


and the refrigerant tubing is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
Refrigerant piping

Total amount of refrigerant (kg)


Min. volume of the indoor unit installed room (m3)
Concentration limit (kg/m3)

Outdoor unit
Very
small
room

The concentration limit of R410A which is used in multi


air conditioners is 0.3kg/m3.

e.g., charged
amount (10kg)

Room A Room B

Outdoor unit
e.g.,
charged amount (15kg)

Room C Room D Room E

Indoor unit
Small
room

Medium
room

Large room

Mechanical ventilation device - Gas leak detector

NOTE 3:
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 2.7m high)
40

Min. indoor floor area

NOTE 1:
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.

Important

Room F

Indoor unit

For the amount of charge in this example:


The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.

m 35
30
25

Range below the


density limit of
0.3 kg/m3
(countermeasur
es not needed)

20

Range above
the density limit
of 0.3 kg/m3
(countermeasur
es needed)

15
10
5
0

10

20

30
kg

Total amount of refrigerant

7 -1

7 Refrigerant piping design


2. Free branching system
[1] Line branching system
[2] Header branching system
[3] Header branching system after line branching
[4] Line branching system after header branching
[5] Header branching system after header branching
The above five branching systems enable to dramatically increase the flexibility of refrigerant piping design.
Outdoor unit
Branching joint

Line branching
system
Indoor unit
Remote
controller

Outdoor unit

Header
branching
system

Branching header

Indoor unit
Remote controller

Outdoor unit
Branching joint

Header
branching
system after line
branching
Indoor unit

Remote
controller

Line branching
system after
header
branching

Header
branching
system after
header
branching

Outdoor unit

Branching header

Branching
joint
Indoor
unit
Remote
controller

7 -2

7 Refrigerant piping design


3. Allowable length/height difference of refrigerant piping
D
Follower
unit 3

Height
difference
between
outdoor
units
H3 5m

A
Header
unit

B
Follower
unit 1

Y-shape branching joint for gas pipe

<Ex.1>

C
Follower
unit 2
Connecting
piping of
outdoor unit

Outdoor unit

OK

OK

<Ex.2>
La

Height
difference
between
outdoor
units
H1 70m

T-shape branching joint for liquid pipe

<Ex.1>

Main
piping

Lb

Lc

<Ex.2>

Ld

LA
LB
Main connecting piping between outdoor units
Y-shape branching
joint for gas pipe

L1

T-shape branching
joint for liquid pipe

NO GOOD
NOTE:
T-shape branching joint of <Ex.2> is prohibited.
Branching
header

Branching piping L2
Connecting piping of indoor unit

1st branching
section

OK

NOTE:
Incase of 5 & 6 HP SMMS, apply the piping rules for
length/height of SMMS.
L7

Indoor unit

L3

Equivalent length corresponded to farthest piping L

235 m

Equivalent length corresponded to farthest piping after 1st branching Li

L6

L5

L4

Y-joint

Height difference
between indoor
units
H2 40m

90 m

Indoor unit

System restrictions
Max. No. of combined outdoor units

4 units

Max. capacity of combined outdoor units

48 HP

Max. No. of connected indoor units


Max. capacity of combined
indoor units

H2

48 units
15

135%

H2 > 15

105%

Note 1) Combination of outdoor units: Header unit (1 unit) + Follower units (0 to 3 units).
Header unit is the outdoor unit nearest to the connected indoor units.
Note 2) Install the outdoor units in order of capacity.
(Header unit Follower unit 1 Follower unit 2 Follower unit 3)
Note 3) Use Y-shape branching joint in connecting of gas pipe for outdoor unit, and install horizontally.
Note 4) Piping to indoor units shall be perpendicular to piping to the header outdoor unit as <Ex.1>.
Do not connect piping to indoor units in the same direction of header outdoor unit as T-shape
branching joint for liquid pipe of <Ex.2>.

Allowable length and height difference of refrigerant piping


Total extension of pipe
(Liquid pipe, real length)
Farthest piping Length L (*1)

Allowable value
300m
500m
190m
235m

Below 34HP
34HP or more
Actual pipe length
Equivalent length

Equivalent length of farthest piping


from 1st branching Li (*1)
Piping length Equivalent length of farthest piping
between outdoor units LO (*1)

90m (*2)
25m

Actual pipe length


Max. equivalent length of main piping
Equivalent length
Max. equivalent length of outdoor unit connecting piping
Max. real length of indoor unit connecting piping
Max. equivalent length between branches
Upper outdoor unit
Height between indoor and outdoor units H1
Difference in
Lower outdoor unit
height
Height between indoor units H2
Height between outdoor units H3

(*1) :
(*2) :
(*3) :
(*4) :
(*5) :

100m (*3)
120m (*3)
10m
30m
50m
70m (*4)
40m (*5)
40m
5m

Piping section
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+ L5 +
L6 + L7 + a + b + c + d + e + f + g + h + i + j
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
L3 + L4 + L5
LA + LB + Ld
(LA + Lb, LA + LB + Ld)
L1
Ld(La, Lb, Lc)
a, b, c, d, e, f, g, h, i, j
L2, L3, L4, L5, L6, L7

(D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch.
If the height difference (H1) between indoor and outdoor unit exceeds 3m, set 65m or less.
If the max. combined outdoor unit capacity is 46HP or more, then max. equivalent length is 70m or less (real length is 50m or less).
If the height difference (H2) between indoor units exceeds 3m, set 50m or less.
If the height difference (H2) between indoor units exceeds 3m, set 30m or less.

7 -3

7 Refrigerant piping design


4. Selection of refrigerant piping
Branching piping
Follower
unit 3

Follower
unit 2

Follower
unit 1 Header unit

1 Outdoor unit
connecting
piping

Balance pipe
9.5
1st branching
1
section

Indoor unit connecting piping

Outdoor
unit

6 Header branching pipe

7 Branching joint for

Indoor unit

6 Y-shape

3 Main piping

branching
joint
4

outdoor unit

Main connecting
piping between
outdoor units

Indoor unit
connecting piping
Indoor unit

Pipe size of outdoor unit (Table 1)


Model name MMYMAP0804*
MAP1004*
MAP1204*
MAP1404*
MAP1604*

Liquid side
12.7
12.7
12.7
15.9
15.9

Gas side
28.6
34.9
34.9
41.3

Liquid
side
15.9
15.9
19.1
22.2

Branching header
*2 *3 *6

Balance
pipe
7

Total
capacity
code of
outdoor unit

Size of main pipe (Table 3)

Pipe size between branching sections (Table 4)*5

Branching Below 26
joint for
outdoor
unit
26 or more

*7

Joints
Gas
(Y-shape)
31.8

28.6

Liquid
(T-shape)

Balance
(T-shape)

19.1

9.5

25.4 19.1 19.1


38.1

38.1

22.2

28.6 22.2 22.2

9.5

9.5

Model
name
RBMBT14E

9.5
9.5

9.5

RBMBT24E

OK
OK
OK
OK
NG*4
NG*4
NG*4
NG*4
NG*4

Half hard or hard OD (Inch) OD (mm)


OK
OK
OK
OK
OK
OK
OK
OK
OK

1/4''
3/8''
1/2''
5/8''
3/4''
7/8''
1.1/8''
1.3/8''
1.5/8''

6.35
9.52
12.70
15.88
19.05
22.20
28.58
34.92
41.28

Minimum wall
thickness (mm)
0.80
0.80
0.80
1.00
1.00
1.00
1.00
1.10
1.25

Piping of indoor unit (Table 5)

Capacity rank
Actual length 15m or less
007 type to
012 type
Actual length exceeds 15m
015 type to 018 type
024 type to 056 type
072 type to 096 type

*1
*2
*3
*4
*5
*6

Model name
RBM-BY55E
RBM-BY105E
RBM-BY205E
RBM-BY305E
RBM-HY1043E
RBM-HY2043E
RBM-HY1083E
RBM-HY2083E

Minimum wall thickness for R410A application (Table 8)


Soft

Total capacity code of indoor


Gas side
Liquid side
units at downstream side *1
2.4 or less
12.7
9.5
2.4 to below 6.4
15.9
9.5
6.4 to below 12.2
22.2
12.7
12.2 to below 20.2
28.6
15.9
20.2 to below 35.2
34.9
19.1
35.2 or more
41.3
22.2
If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of outdoor units.
5

Total capacity code of indoor unit *1


Below 6.4
6.4 to below 14.2
14.2 to below 25.2
25.2 or more
For 4
Below 14.2
14.2 to below 25.2
branching
For 8
Below 14.2
14.2 to below 25.2
branching

Selection of branching joint for outdoor unit (Table 7)

9.5

Total capacity code of all


Gas side
Liquid side
outdoor units *1
8 to below 12
22.2
12.7
12 to below 14
28.6
12.7
14 to below 22
28.6
15.9
22 to below 36
34.9
19.1
36 to below 46
41.3
22.2
7
46 or more *
41.3
22.2
Determine thickness of the main pipe according to capacity of the outdoor units.
4

Selection of branching section (Table 6)

Y-shape branching
joint *2 *3

Connecting pipe size between outdoor units (Table 2)

Total capacity code of outdoor units at


downstream side *1
16 to below 22
22 to below 26
26 to below 36
36 or more
3

Gas side
22.2
22.2
28.6
28.6
28.6

Gas side
9.5
12.7
12.7
15.9
22.2

Liquid side
6.4
6.4
6.4
9.5
12.7

NOTE:
In case of 5 & 6 HP SMMS, apply the piping selection rules for SMMS.

Code is determined according to the capacity rank.


When using a Y-shape branching joint for the 1st branch, select according to capacity code of the outdoor unit.
For 1 line after branching header indoor units with a maximum capacity code of 6.0 in total can be connected.
If the pipe size is 19.0 or more, use a suitable material as detailed in the installation manual.
If the piping size becomes over main piping size, select the size same as main piping.
When the first branch is a header with the outdoor total capacity codes of 12 to 26, apply the model RBM- HY2043E(4-branch) or RBMHY2083E(8-branch) regardless of the total capacity codes of the down-stream indoor units.
The maximum equivalent length of main pipe should be 70m or shorter.

7 -4

7 Refrigerant piping design


5. Charging requirement with additional refrigerant
After the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and system with
additional refrigerant.

Calculating the amount of additional refrigerant required


R410A

Refrigerant in the system when shipped from the factory

*SMMS
Refrigerant amount
charged in factory

Heat pump model


Cooling only model

5HP*
8.5kg
8.0kg

6HP*
8.5kg
8.0kg

8HP
11.5kg
10.5kg

10HP
11.5kg
10.5kg

12HP
11.5kg
11.5kg

14HP
11.5kg
11.5kg

16HP
11.5kg
11.5kg

When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site
is not included. Therefore, calculate the additional amount needed and add the required amount to the system.

(Calculation)
Additional refrigerant charge amount is calculated based on the size of liquid pipe at site and its real length.
Additional refrigerant charge amount at site =
Additional refrigerant charge amount
Real length of liquid pipe per liquid pipe 1m (Table 1)
+ Compensation by system HP (Table 2)
Example : Additional charge amount R (kg) = (L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m) + (3.0kg)
L1 : Real total length of liquid pipe 6.4 (m)
L2 : Real total length of liquid pipe 9.5 (m)
L3 : Real total length of liquid pipe 12.7 (m)

Table 1
Pipe dia. at liquid side
Additional refrigerant amount/1m

6.4
0.025kg

9.5
0.055kg

12.7
0.105kg

15.9
0.160kg

19.0
0.250kg

22.2
0.350kg

Table 2
Standard model
Combined
Outdoor
horse power
combination(HP)
(HP)
5*
5
6*
6
8
8
10
10
12
12
14
14
16
16
18
10
8
20
10
10
22
12
10
24
12
12
26
16
10
28
16
12
30
16
14
32
16
16
34
12
12
10
36
12
12
12
38
16
12
10
40
16
12
12
42
16
14
12
44
16
16
12
46
16
16
14
48
16
16
16

High efficiency model


Combined
Outdoor
horse power
combination(HP)
(HP)
16
8
8
24
8
8
8
26
10
8
8
28
10
10
8
30
10
10
10
32
8
8
8
8
34
10
8
8
8
36
10
10
8
8
38
10
10
10
8
40
10
10
10
10
42
12
10
10
10
44
12
12
10
10
46
12
12
12
10
48
12
12
12
12

Compensation
by System HP
(kg)
0.0
0.0
1.5
2.5
3.5
8.5
10.5
0.0
3.0
5.0
7.5
8.5
9.5
11.5
12.5
3.0
4.0
6.0
7.0
8.0
10.0
12.0
14.0
*SMMS

7 -5

Compensation
by System HP
(kg)
0.0
-4.0
-4.0
-2.0
0.0
-6.0
-6.0
-6.0
-6.0
-5.0
-4.0
-2.0
0.0
2.0

SMMS-i Data book

Part Load performance

Part Load performance


1. Single unit
MMY-MAP0501* (5HP, 14kW system)

<SMMS>

Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

13.0

3.86

3.16

2.54

2.02

1.59

1.24

1.03

0.88

35 C

14.0

3.65

2.98

2.40

1.90

1.49

1.16

0.96

0.82

30 C

14.0

3.02

2.48

2.00

1.60

1.27

1.00

0.84

0.73

25 C

14.0

2.71

2.22

1.80

1.45

1.15

0.92

0.78

0.68

20 C

14.0

2.52

2.07

1.68

1.35

1.08

0.87

0.74

0.65

15 C

14.0

2.34

1.93

1.57

1.26

1.01

0.82

0.70

0.61

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
16.0

11

9.8

16.0

16.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

3.35

2.80

2.32

1.90

1.53

1.23

0.99

0.80

3.61

3.01

2.48

2.01

1.61

1.28

1.01

0.81

3.84

3.19

2.62

2.12

1.69

1.32

1.03

0.81

-0.7

14.1

3.74

3.11

2.55

2.06

1.64

1.28

1.00

0.78

-5

-5.6

12.8

3.63

3.02

2.47

1.99

1.58

1.24

0.96

0.75

-10

-10.5

10.9

3.26

2.72

2.23

1.81

1.44

1.14

0.89

0.71

-14.5

-15

8.0

2.56

2.15

1.78

1.46

1.18

0.95

0.77

0.63

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-MAP0601* (6HP, 16kW system)

<SMMS>

Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

14.9

4.91

4.01

3.23

2.57

2.02

1.58

1.26

1.05

35 C

16.0

4.64

3.79

3.05

2.42

1.90

1.48

1.17

0.97

30 C

16.0

3.84

3.15

2.55

2.03

1.61

1.28

1.03

0.87

25 C

16.0

3.44

2.83

2.29

1.84

1.46

1.17

0.95

0.82

20 C

16.0

3.20

2.63

2.14

1.72

1.37

1.10

0.90

0.78

15 C

16.0

2.97

2.45

1.99

1.61

1.29

1.04

0.86

0.74

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
18.0

11

9.8

18.0

18.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

3.97

3.30

2.76

2.25

1.82

1.46

1.17

0.96

4.28

3.57

2.94

2.39

1.92

1.52

1.20

0.96

4.56

3.79

3.11

2.52

2.00

1.57

1.23

0.97

-0.7

15.8

4.44

3.70

3.03

2.44

1.94

1.52

1.18

0.93

-5

-5.6

14.4

4.31

3.58

2.93

2.37

1.88

1.47

1.14

0.89

-10

-10.5

12.2

3.87

3.23

2.65

2.15

1.71

1.35

1.06

0.84

-14.5

-15

9.0

3.04

2.55

2.11

1.73

1.41

1.13

0.91

0.75

Indoor air temperature conditions : 20.0 C dry-bulb

8 -1

8 Part Load performance


MMY-MAP0804* (8HP, 22.4kW system)
Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

40 C

20.8

5.83

4.79

35 C

22.4

5.40

4.44

30 C

22.4

4.47

25 C

22.4

20 C
15 C

Outdoor Unit
Dry-Bulb
(C)

Power consumption (kW)

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

3.89

3.11

2.46

1.94

1.55

1.29

3.60

2.87

2.27

1.79

1.43

1.19

3.68

3.00

2.42

1.93

1.54

1.26

1.07

3.75

3.10

2.54

2.06

1.66

1.34

1.10

0.95

22.4

3.40

2.82

2.31

1.88

1.53

1.24

1.04

0.90

22.4

3.26

2.71

2.23

1.82

1.48

1.22

1.02

0.89

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
25.0

11

9.8

25.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

4.60

3.82

3.18

2.65

2.21

1.83

1.51

1.20

5.00

4.11

3.37

2.78

2.29

1.88

1.54

1.22

25.0

5.53

4.48

3.63

2.95

2.40

1.95

1.58

1.24

-0.7

21.9

5.23

4.24

3.43

2.79

2.27

1.85

1.49

1.17
1.13

-5

-5.6

19.6

5.02

4.06

3.29

2.67

2.17

1.77

1.43

-10

-10.5

17.1

4.80

3.89

3.15

2.56

2.08

1.69

1.37

1.08

-14.5

-15

14.7

4.60

3.73

3.02

2.45

1.99

1.62

1.31

1.03

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-MAP1004* (10HP, 28kW system)


Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

26.1

8.00

6.58

5.33

4.26

3.37

2.66

2.12

1.76

35 C

28.0

7.41

6.09

4.93

3.95

3.12

2.46

1.96

1.63

30 C

28.0

6.13

5.06

4.12

3.32

2.65

2.12

1.72

1.46

25 C

28.0

5.15

4.26

3.48

2.82

2.27

1.84

1.51

1.30

20 C

28.0

4.66

3.87

3.17

2.58

2.09

1.71

1.42

1.24

15 C

28.0

4.48

3.72

3.06

2.50

2.04

1.67

1.40

1.23

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
31.5

11

9.8

31.5

31.5

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

6.24

5.18

4.31

3.59

2.99

2.49

2.04

1.62

6.79

5.57

4.57

3.76

3.10

2.56

2.08

1.65

7.50

6.08

4.92

4.00

3.25

2.65

2.14

1.68

-0.7

27.6

7.10

5.75

4.66

3.78

3.08

2.50

2.02

1.59

-5

-5.6

24.6

6.80

5.51

4.47

3.62

2.95

2.40

1.94

1.53

-10

-10.5

21.5

6.51

5.27

4.27

3.47

2.82

2.30

1.86

1.46

-14.5

-15

18.5

6.24

5.05

4.10

3.32

2.70

2.20

1.78

1.40

Indoor air temperature conditions : 20.0 C dry-bulb

8 -2

8 Part Load performance


MMY-MAP1204* (12HP, 33.5kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

31.2

10.3

8.41

6.76

5.36

4.21

3.30

2.63

2.20

35 C

33.5

9.55

7.78

6.25

4.96

3.89

3.05

2.44

2.03

30 C

33.5

7.86

6.43

5.20

4.16

3.30

2.63

2.14

1.82

25 C

33.5

6.58

5.40

4.39

3.53

2.83

2.28

1.88

1.63

20 C

33.5

5.94

4.90

3.99

3.23

2.60

2.12

1.76

1.54

15 C

33.5

5.70

4.71

3.85

3.12

2.53

2.07

1.74

1.53

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
37.5

11

9.8

37.5

37.5

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

8.51

7.04

5.80

4.78

3.93

3.25

2.70

2.27

9.25

7.59

6.19

5.04

4.10

3.34

2.74

2.27

10.2

8.29

6.69

5.38

4.32

3.47

2.80

2.28

-0.7

32.9

9.65

7.84

6.33

5.09

4.08

3.28

2.65

2.16

-5

-5.6

29.3

9.25

7.52

6.07

4.88

3.91

3.15

2.54

2.07

-10

-10.5

25.6

8.85

7.19

5.81

4.67

3.75

3.01

2.43

1.98

-14.5

-15

22.0

8.49

6.89

5.57

4.47

3.59

2.89

2.33

1.90

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-MAP1404* (14HP, 40kW system)


Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

40 C

37.2

12.4

10.1

35 C

40.0

11.5

9.39

30 C

40.0

9.48

7.76

25 C

40.0

7.94

20 C

40.0

7.18

15 C

40.0

6.88

Outdoor Unit
Dry-Bulb
(C)

90%
Capacity

80%
Capacity

Power consumption (kW)

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

8.14

6.40

4.95

3.82

3.02

2.57

7.53

5.92

4.58

3.54

2.80

2.38

6.24

4.94

3.87

3.03

2.46

2.15

6.51

5.25

4.18

3.30

2.63

2.17

1.93

5.89

4.77

3.81

3.03

2.43

2.04

1.84

5.66

4.59

3.68

2.94

2.38

2.01

1.84

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
45.0

11

9.8

45.0

45.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

9.32

7.74

6.43

5.36

4.47

3.71

3.05

2.42

10.1

8.31

6.83

5.62

4.64

3.82

3.11

2.46

11.2

9.07

7.35

5.97

4.85

3.95

3.19

2.51

-0.7

39.5

10.6

8.59

6.96

5.65

4.59

3.74

3.02

2.38

-5

-5.6

35.2

10.2

8.23

6.67

5.41

4.40

3.58

2.90

2.28

-10

-10.5

30.7

9.72

7.88

6.38

5.18

4.21

3.43

2.77

2.18

-14.5

-15

26.5

9.32

7.55

6.12

4.96

4.04

3.29

2.66

2.09

Indoor air temperature conditions : 20.0 C dry-bulb

8 -3

8 Part Load performance


MMY-MAP1604* (16HP, 45kW system)
Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

40 C

41.9

14.8

12.1

35 C

45.0

13.7

11.2

30 C

40.0

11.3

9.27

25 C

45.0

9.49

20 C

40.0

15 C

45.0

Outdoor Unit
Dry-Bulb
(C)

80%
Capacity

Power consumption (kW)

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

9.69

7.54

5.74

4.34

3.40

2.97

8.97

6.98

5.31

4.02

3.14

2.74

7.41

5.79

4.45

3.43

2.76

2.50

7.77

6.22

4.88

3.78

2.96

2.44

2.26

8.58

7.02

5.63

4.43

3.46

2.74

2.30

2.17

8.22

6.73

5.40

4.27

3.35

2.68

2.28

2.17

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
50.0

11

9.8

50.0

50.0

14.2

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

11.9

9.74

7.92

6.40

5.18

4.25

3.63

3.30

12.9

10.5

8.51

6.81

5.43

4.37

3.64

3.24

11.5

9.26

7.33

5.76

4.54

3.69

3.19

-0.7

43.9

13.4

10.9

8.76

6.94

5.45

4.30

3.49

3.02

-5

-5.6

39.1

12.9

10.5

8.40

6.65

5.22

4.12

3.35

2.90

-10

-10.5

34.1

12.3

10.0

8.04

6.36

5.00

3.94

3.20

2.77

-14.5

-15

29.4

11.8

9.61

7.70

6.10

4.79

3.78

3.07

2.66

Indoor air temperature conditions : 20.0 C dry-bulb

8 -4

8 Part Load performance


2. Combination
2.1 Standard model
MMY-AP2014* (20HP, 56kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

52.1

15.8

13.0

10.5

8.40

6.64

5.24

4.18

3.48

35 C

56.0

14.8

12.2

9.87

7.89

6.24

4.92

3.93

3.26

30 C

56.0

12.3

10.1

8.24

6.63

5.30

4.24

3.45

2.92

25 C

56.0

10.3

8.52

6.97

5.65

4.55

3.68

3.03

2.61

20 C

56.0

9.32

7.73

6.35

5.17

4.19

3.41

2.84

2.47

15 C

56.0

8.96

7.44

6.13

5.00

4.08

3.34

2.80

2.46

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
63.0

11

9.8

63.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

12.5

10.4

8.62

7.18

5.98

4.97

4.08

3.25

13.6

11.1

9.15

7.53

6.21

5.11

4.17

3.30

63.0

15.0

12.2

9.84

7.99

6.50

5.29

4.28

3.36

-0.7

55.3

14.2

11.5

9.32

7.56

6.15

5.01

4.05

3.18
3.05

-5

-5.6

49.3

13.6

11.0

8.93

7.25

5.90

4.80

3.88

-10

-10.5

43.0

13.0

10.5

8.54

6.93

5.64

4.59

3.71

2.92

-14.5

-15

37.0

12.5

10.1

8.19

6.65

5.41

4.40

3.56

2.80

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP2614* (26HP, 73kW system)


Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

67.9

22.8

18.7

15.1

11.9

9.23

7.13

5.64

4.80

35 C

73.0

21.1

17.3

13.9

11.0

8.54

6.60

5.22

4.44

30 C

73.0

17.5

14.3

11.6

9.19

7.20

5.66

4.58

4.01

25 C

73.0

14.6

12.0

9.75

7.78

6.15

4.90

4.04

3.60

20 C

73.0

13.2

10.9

8.86

7.09

5.65

4.54

3.80

3.43

15 C

73.0

12.7

10.5

8.52

6.85

5.48

4.44

3.75

3.42

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
81.5

11

9.8

81.5

81.5

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

18.1

14.9

12.3

10.1

8.29

6.85

5.72

4.87

19.7

16.1

13.1

10.6

8.64

7.04

5.80

4.86

21.7

17.6

14.2

11.4

9.10

7.30

5.91

4.88

-0.7

71.5

20.5

16.7

13.4

10.8

8.61

6.91

5.59

4.61

-5

-5.6

63.8

19.7

16.0

12.9

10.3

8.26

6.62

5.36

4.42

-10

-10.5

55.7

18.8

15.3

12.3

9.88

7.90

6.34

5.13

4.23

-14.5

-15

47.9

18.1

14.7

11.8

9.47

7.57

6.07

4.92

4.06

Indoor air temperature conditions : 20.0 C dry-bulb

8 -5

8 Part Load performance


MMY-AP3014* (30HP, 85kW system)
Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

Outdoor Unit
Dry-Bulb
(C)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

Power consumption (kW)

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

79.1

27.2

22.3

17.8

13.9

10.7

8.18

6.44

5.55

35 C

85.0

25.2

20.6

16.5

12.9

9.91

7.57

5.95

5.13

30 C

85.0

20.8

17.0

13.7

10.7

8.33

6.48

5.23

4.65

25 C

85.0

17.4

14.3

11.5

9.07

7.09

5.60

4.62

4.20

20 C

85.0

15.8

12.9

10.4

8.25

6.50

5.19

4.35

4.01

15 C

85.0

15.1

12.4

9.99

7.95

6.30

5.07

4.30

4.01

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
95.0

11

9.8

95.0

95.0

Outdoor Unit

100%
Capacity

90%
Capacity

80%
Capacity

21.2

17.5

23.0

18.9

25.4

20.6

Power consumption (kW)

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

14.4

11.8

9.70

8.02

6.70

5.70

15.4

12.5

10.1

8.24

6.78

5.69

16.6

13.3

10.7

8.54

6.92

5.71

-0.7

83.3

24.0

19.5

15.7

12.6

10.1

8.09

6.55

5.40

-5

-5.6

74.3

23.0

18.7

15.1

12.1

9.66

7.75

6.28

5.18

-10

-10.5

64.9

22.0

17.9

14.4

11.6

9.25

7.42

6.01

4.95

-14.5

-15

55.8

21.1

17.2

13.8

11.1

8.86

7.11

5.76

4.75

40%
Capacity

30%
Capacity

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP3414* (34HP, 96kW system)


Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

40 C

89.3

29.2

23.9

19.3

15.3

12.1

9.46

7.53

6.28

35 C

96.0

27.1

22.1

17.8

14.2

11.2

8.75

6.97

5.81

30 C

96.0

22.3

18.3

14.9

11.9

9.46

7.53

6.12

5.21

25 C

96.0

18.7

15.4

12.6

10.1

8.11

6.53

5.38

4.66

20 C

96.0

16.9

14.0

11.4

9.25

7.46

6.06

5.05

4.42

96.0

16.2

13.4

11.0

8.95

7.26

5.93

4.98

4.39

30%
Capacity

Outdoor Unit
Dry-Bulb
(C)

15 C

50%
Capacity

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Power consumption (kW)

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
108.0

11

9.8

108.0

-0.7

-5

-5.6

-10

-10.5

73.8

24.8

20.1

16.3

13.1

10.6

8.55

6.90

5.56

-14.5

-15

63.5

23.8

19.3

15.6

12.6

10.1

8.19

6.62

5.33

Outdoor Unit

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

23.8

19.7

16.3

13.5

11.2

9.24

7.65

6.30

25.9

21.3

17.4

14.2

11.6

9.50

7.77

6.34

108.0

28.6

23.2

18.8

15.1

12.2

9.85

7.96

6.41

94.7

27.1

22.0

17.8

14.3

11.5

9.32

7.53

6.07

84.5

25.9

21.1

17.0

13.7

11.1

8.93

7.22

5.81

Indoor air temperature conditions : 20.0 C dry-bulb

8 -6

8 Part Load performance


MMY-AP4014* (40HP, 112kW system)
Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

Outdoor Unit
Dry-Bulb
(C)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

Power consumption (kW)

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

104.2

35.4

28.9

23.2

18.3

14.2

11.0

8.74

7.39

35 C

112.0

32.8

26.8

21.5

16.9

13.2

10.2

8.08

6.84

30 C

112.0

27.0

22.1

17.8

14.1

11.1

8.76

7.10

6.16

25 C

112.0

22.6

18.6

15.0

12.0

9.49

7.58

6.25

5.53

20 C

112.0

20.5

16.8

13.6

10.9

8.72

7.03

5.87

5.26

15 C

112.0

19.6

16.1

13.1

10.6

8.47

6.88

5.80

5.24

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
127.0

11

9.8

127.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

29.5

24.3

20.0

16.3

13.4

11.0

9.24

7.96

32.0

26.2

21.3

17.3

13.9

11.3

9.34

7.92

127.0

35.3

28.7

23.1

18.5

14.7

11.8

9.52

7.92

-0.7

111.4

33.4

27.1

21.9

17.5

13.9

11.1

9.01

7.49

-5

-5.6

99.4

32.0

26.0

21.0

16.8

13.4

10.7

8.64

7.18

-10

-10.5

86.7

30.6

24.9

20.1

16.0

12.8

10.2

8.26

6.87

-14.5

-15

74.6

29.4

23.9

19.2

15.4

12.2

9.79

7.92

6.59

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP4414* (44HP, 123.5kW system)


Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

114.9

39.3

32.2

25.8

20.2

15.5

11.9

9.36

8.04

35 C

123.5

37.0

30.2

24.2

18.9

14.6

11.2

8.79

7.55

30 C

123.5

30.5

25.0

20.0

15.8

12.3

9.55

7.73

6.84

25 C

123.5

25.6

20.9

16.8

13.3

10.4

8.26

6.81

6.17

20 C

123.5

23.1

18.9

15.3

12.1

9.58

7.65

6.41

5.89

123.5

22.1

18.2

14.7

11.7

9.29

7.48

6.33

5.88

50%
Capacity

40%
Capacity

30%
Capacity
8.89

Outdoor Unit
Dry-Bulb
(C)

15 C

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
138.0

11

9.8

138.0

138.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

32.4

26.7

21.8

17.7

14.4

11.9

10.0

35.3

28.9

23.4

18.8

15.1

12.2

10.1

8.79

38.9

31.6

25.4

20.2

16.0

12.7

10.3

8.73

-0.7

121.1

36.8

29.9

24.0

19.1

15.1

12.0

9.74

8.26

-5

-5.6

108.0

35.2

28.7

23.0

18.3

14.5

11.5

9.33

7.92

-10

-10.5

94.2

33.7

27.4

22.0

17.5

13.9

11.0

8.93

7.58

-14.5

-15

81.1

32.3

26.3

21.1

16.8

13.3

10.6

8.56

7.26

Indoor air temperature conditions : 20.0 C dry-bulb

8 -7

8 Part Load performance


MMY-AP4814* (48HP, 135kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

125.6

44.4

36.4

29.1

22.7

17.4

13.2

10.4

9.06

35 C

135.0

41.1

33.6

26.9

21.0

16.1

12.2

9.63

8.38

30 C

135.0

34.0

27.8

22.3

17.5

13.5

10.5

8.48

7.62

25 C

135.0

28.5

23.3

18.7

14.7

11.5

9.05

7.49

6.89

20 C

135.0

25.7

21.1

16.9

13.4

10.5

8.38

7.05

6.59

15 C

135.0

24.6

20.2

16.3

12.9

10.2

8.20

6.97

6.59

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
150.0

11

9.8

150.0

150.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

35.6

29.2

23.8

19.2

15.5

12.8

10.9

9.90

38.7

31.6

25.5

20.4

16.3

13.1

10.9

9.71

42.6

34.6

27.8

22.0

17.3

13.6

11.1

9.58

-0.7

131.6

40.3

32.8

26.3

20.8

16.3

12.9

10.5

9.07

-5

-5.6

117.4

38.6

31.4

25.2

19.9

15.7

12.4

10.0

8.70

-10

-10.5

102.4

37.0

30.1

24.1

19.1

15.0

11.8

9.61

8.32

-14.5

-15

88.2

35.4

28.8

23.1

18.3

14.4

11.3

9.21

7.97

Indoor air temperature conditions : 20.0 C dry-bulb

8 -8

8 Part Load performance


2.2 High efficiency model
MMY-AP2624* (26HP, 73kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

67.9

19.8

16.3

13.2

10.5

8.33

6.57

5.24

4.36

35 C

73.0

18.3

15.0

12.2

9.75

7.71

6.08

4.85

4.03

30 C

73.0

15.1

12.5

10.2

8.20

6.55

5.24

4.26

3.61

25 C

73.0

12.7

10.5

8.61

6.97

5.62

4.54

3.74

3.22

20 C

73.0

11.5

9.55

7.84

6.38

5.17

4.22

3.51

3.06

15 C

73.0

11.1

9.20

7.57

6.18

5.03

4.13

3.46

3.03

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
81.5

11

9.8

81.5

-0.7

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

15.4

12.8

10.7

8.88

7.41

6.16

5.05

4.02

16.8

13.8

11.3

9.31

7.68

6.33

5.16

4.08

81.5

18.6

15.0

12.2

9.89

8.04

6.55

5.29

4.16

71.5

17.6

14.2

11.5

9.36

7.61

6.20

5.01

3.94

-5

-5.6

63.8

16.8

13.6

11.1

8.97

7.30

5.94

4.80

3.78

-10

-10.5

55.7

16.1

13.1

10.6

8.58

6.98

5.68

4.59

3.61

-14.5

-15

47.9

15.4

12.5

10.1

8.23

6.69

5.45

4.40

3.46

40%
Capacity

30%
Capacity

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP3024* (30HP, 85kW system)


Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

Outdoor Unit
Dry-Bulb
(C)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

Power consumption (kW)

60%
Capacity

50%
Capacity

40 C

79.1

24.6

20.2

16.4

13.1

10.4

8.16

6.52

5.42

35 C

85.0

22.8

18.7

15.1

12.1

9.58

7.55

6.03

5.01

30 C

85.0

18.8

15.5

12.6

10.2

8.14

6.51

5.29

4.49

25 C

85.0

15.8

13.1

10.7

8.67

6.98

5.64

4.65

4.00

20 C

85.0

14.3

11.9

9.74

7.93

6.43

5.24

4.36

3.80

15 C

85.0

13.7

11.4

9.40

7.68

6.26

5.13

4.30

3.77

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
95.0

11

9.8

95.0

95.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

18.9

15.7

13.0

10.9

9.06

7.53

6.18

4.91

20.5

16.9

13.8

11.4

9.40

7.74

6.31

4.99

22.7

18.4

14.9

12.1

9.84

8.01

6.47

5.09

-0.7

83.3

21.5

17.4

14.1

11.4

9.31

7.58

6.13

4.82

-5

-5.6

74.3

20.6

16.7

13.5

11.0

8.93

7.27

5.87

4.62

-10

-10.5

64.9

19.7

16.0

12.9

10.5

8.54

6.95

5.62

4.42

-14.5

-15

55.8

18.9

15.3

12.4

10.1

8.19

6.67

5.38

4.24

Indoor air temperature conditions : 20.0 C dry-bulb

8 -9

8 Part Load performance


MMY-AP3424* (34HP, 96kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

89.3

25.9

21.3

17.3

13.8

10.9

8.61

6.87

5.71

35 C

96.0

24.0

19.7

16.0

12.8

10.1

7.97

6.36

5.29

30 C

96.0

19.8

16.4

13.3

10.7

8.58

6.86

5.58

4.73

25 C

96.0

16.7

13.8

11.3

9.14

7.36

5.95

4.91

4.22

20 C

96.0

15.1

12.5

10.3

8.37

6.78

5.53

4.60

4.00

15 C

96.0

14.5

12.1

9.92

8.10

6.60

5.41

4.54

3.98

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
108.0

11

9.8

108.0

Outdoor Unit

70%
Capacity

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

20.6

17.1

14.2

22.3

18.3

15.1

11.8

9.86

8.19

6.72

5.34

12.4

10.2

8.42

6.86

108.0

24.7

20.0

16.2

5.43

13.2

10.7

8.71

7.04

-0.7

94.7

23.4

18.9

5.54

15.3

12.5

10.1

8.25

6.66

-5

-5.6

84.5

22.4

18.2

5.24

14.7

11.9

9.71

7.90

6.39

5.03

-10

-10.5

73.8

21.4

17.4

14.1

11.4

9.29

7.56

6.11

4.81

-14.5

-15

63.5

20.5

16.6

13.5

10.9

8.91

7.25

5.86

4.61

40%
Capacity

30%
Capacity

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP4024* (40HP, 112kW system)


Cooling

Compressor + Oudoor Fan


Outdoor Unit
100%
Cooling
Capacity
(kW)

Outdoor Unit
Dry-Bulb
(C)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

Power consumption (kW)

60%
Capacity

50%
Capacity

40 C

104.2

32.0

26.3

21.3

17.1

13.5

10.6

8.49

7.06

35 C

112.0

29.6

24.4

19.7

15.8

12.5

9.84

7.86

6.53

30 C

112.0

24.5

20.2

16.5

13.3

10.6

8.48

6.89

5.85

25 C

112.0

20.6

17.0

13.9

11.3

9.10

7.35

6.06

5.22

20 C

112.0

18.6

15.5

12.7

10.3

8.38

6.83

5.68

4.95

15 C

112.0

17.9

14.9

12.3

10.0

8.15

6.68

5.60

4.91

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
127.0

11

9.8

127.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

25.3

21.0

17.5

14.6

12.1

10.1

8.28

6.58

27.5

22.6

18.5

15.3

12.6

10.4

8.45

6.69

127.0

30.4

24.6

20.0

16.2

13.2

10.7

8.67

6.82

-0.7

111.4

28.8

23.3

18.9

15.3

12.5

10.2

8.20

6.46

-5

-5.6

99.4

27.6

22.4

18.1

14.7

12.0

9.74

7.87

6.19

-10

-10.5

86.7

26.4

21.4

17.3

14.1

11.4

9.31

7.53

5.92

-14.5

-15

74.6

25.3

20.5

16.6

13.5

11.0

8.93

7.21

5.68

Indoor air temperature conditions : 20.0 C dry-bulb

8 -10

8 Part Load performance


MMY-AP4424* (44HP, 123.5kW system)
Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

114.9

36.9

30.2

24.4

19.5

15.3

12.0

9.59

7.99

35 C

123.5

34.2

28.0

22.6

18.0

14.2

11.1

8.87

7.39

30 C

123.5

28.2

23.2

18.8

15.1

12.0

9.58

7.78

6.63

25 C

123.5

23.7

19.5

15.9

12.8

10.3

8.31

6.85

5.92

20 C

123.5

21.4

17.7

14.5

11.7

9.49

7.71

6.42

5.61

123.5

20.6

17.0

14.0

11.4

9.23

7.55

6.33

5.58

Outdoor Unit
Dry-Bulb
(C)

15 C

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
138.0

11

9.8

138.0

Outdoor Unit

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

29.5

24.4

20.2

16.8

13.9

11.5

9.51

7.76

32.1

26.3

21.5

17.6

14.4

11.8

9.68

7.83

138.0

35.4

28.7

23.2

18.8

15.2

12.3

9.91

7.94

-0.7

121.1

33.5

27.2

22.0

17.8

14.3

11.6

9.38

7.51
7.20

-5

-5.6

108.0

32.1

26.1

21.1

17.0

13.8

11.1

8.99

-10

-10.5

94.2

30.7

24.9

20.2

16.3

13.2

10.6

8.60

6.89

-14.5

-15

81.1

29.4

23.9

19.3

15.6

12.6

10.2

8.24

6.60

Indoor air temperature conditions : 20.0 C dry-bulb

MMY-AP4824* (48HP, 135kW system)


Cooling

Compressor + Oudoor Fan

Power consumption (kW)

Outdoor Unit
100%
Cooling
Capacity
(kW)

100%
Capacity

90%
Capacity

80%
Capacity

70%
Capacity

60%
Capacity

50%
Capacity

40%
Capacity

30%
Capacity

40 C

125.6

41.9

34.1

27.4

21.7

17.1

13.4

10.7

8.91

35 C

135.0

38.8

31.6

25.4

20.1

15.8

12.4

9.88

8.24

30 C

135.0

31.9

26.1

21.1

16.9

13.4

10.7

8.67

7.39

25 C

135.0

26.7

21.9

17.8

14.3

11.5

9.25

7.63

6.60

20 C

135.0

24.1

19.9

16.2

13.1

10.6

8.59

7.16

6.26

15 C

135.0

23.1

19.1

15.6

12.7

10.3

8.41

7.06

6.22

50%
Capacity

40%
Capacity

30%
Capacity

Outdoor Unit
Dry-Bulb
(C)

Indoor air temperature conditions : 27.0 C dry-bulb / 19.0 C wet bulb

Heating

Compressor + Oudoor Fan

Dry-Bulb
( C)

Wet-Bulb
( C)

15

13.7

Outdoor
Unit 100%
Heating
Capacity
(kW)
150.0

11

9.8

150.0

-0.7

Outdoor Unit

70%
Capacity

Power consumption (kW)

100%
Capacity

90%
Capacity

80%
Capacity

60%
Capacity

34.0

28.2

23.2

19.1

15.7

13.0

10.8

9.06

37.0

30.3

24.8

20.2

16.4

13.4

11.0

9.08

150.0

40.8

33.1

26.8

21.5

17.3

13.9

11.2

9.14

131.6

38.6

31.4

25.3

20.4

16.3

13.1

10.6

8.65
8.29

-5

-5.6

117.4

37.0

30.1

24.3

19.5

15.7

12.6

10.2

-10

-10.5

102.4

35.4

28.8

23.2

18.7

15.0

12.0

9.73

7.93

-14.5

-15

88.2

33.9

27.6

22.3

17.9

14.4

11.5

9.33

7.60

Indoor air temperature conditions : 20.0 C dry-bulb

8 -11

SMMS-i Data book

Wiring Design

1. General
Perform wiring of the power supply in conformance with the regulations of the local electric company.
For cabling of the power supply of the indoor unit and the inter-unit cabling between indoor and outdoor units,
refer to the Installation Manual of indoor unit.
Never connect power supply to the terminal block (U1, U2, U3, U4, U5, U6) for control wiring.
(The equipment breaks down.)
Arrange the cables so that the electric wires do not come to contact with high-temperature part of the pipe;
otherwise coating melts and an accident may be caused.
After connecting cable to the terminal block, take off the trap and then fix the cable with cable clamp.
Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.

2. Summary of wiring design


Design of outdoor unit power supply

Select the wiring depending on MCA.


Be sure to set the earth leakage breaker from the viewpoint of safety.

Design of indoor unit power supply

Select the wiring depending on total current of indoor units.


Determine the wire size for the length rules.
Be sure to set the earth leakage breaker from the viewpoint of safety.

Design of control wiring

Design each control wiring.


Between outdoor and indoor units,
Between indoor units/outdoor units
Between indoor unit and remote controller, central control, BMS
Select the wire size and type depending on the length rules.

3. Electrical wiring design

3-phase
380-415V, 50Hz
or 380V, 60Hz
Earth leakage breaker
hand switch

Earth

Outdoor
power source
Pull box

Indoor
power source

Model
MMY-MAP/AP XXXX HT8,
HT8-E, T8, T8-E
MMY-MAP/AP XXXX HT7

Outdoor power supply

Single phase
220-240V 50Hz
or 220V 60Hz
Earth leakage breaker
power switch

3phese, 380-415V, 50Hz


3phese, 380V, 60Hz

Wiring size must comply with the applicable local and national code.
Determine the wire size for the indoor unit according to the number of connected indoor units downstream.

4. Outdoor unit power supply


Select the power supply cabling and fuse of each
outdoor unit from the following specifications:
cable 4-core, in conformance with Design 60245
IEC 66
Do not connect the outdoor units by crossing
outside of them, but connect them via the terminal
block (L1, L2, L3, N).

NO GOOD

Outdoor power supply


3-phase 380-415V, 50Hz
380V
60Hz

9 -1

L1 L2 L3

L1 L2 L3

L1 L2 L3

L1 L2 L3

Heat Pump Model


MMY-

MAP0501HT8-E*
MAP0601HT8-E*
MAP0804HT8-E
MAP1004HT8-E
MAP1204HT8-E
MAP1404HT8-E
MAP1604HT8-E
MAP1814HT8-E
MAP2014HT8-E
MAP2214HT8-E
MAP2414HT8-E
MAP2614HT8-E
MAP2814HT8-E
MAP3014HT8-E
MAP3214HT8-E
MAP3414HT8-E
MAP3614HT8-E
MAP3814HT8-E
MAP4014HT8-E
MAP4214HT8-E
MAP4414HT8-E
MAP4614HT8-E
MAP4814HT8-E

HP

5*
6*
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48

MAP1624HT8-E
MAP2424HT8-E
MAP2624HT8-E
MAP2824HT8-E
MAP3024HT8-E
MAP3224HT8-E
MAP3424HT8-E
MAP3624HT8-E
MAP3824HT8-E
MAP4024HT8-E
MAP4224HT8-E
MAP4424HT8-E
MAP4624HT8-E
MAP4824HT8-E

16
24
26
28
30
32
34
36
38
40
42
44
46
48

MAP1624T8-E
MAP2424T8-E
MAP2624T8-E
MAP2824T8-E
MAP3024T8-E
MAP324T8-E
MAP3424T8-E
MAP3624T8-E
MAP3824T8-E
MAP4024T8-E
MAP4224T8-E
MAP4424T8-E
MAP4624T8-E
MAP4824T8-E

Cooling Only Model


MMY-

MAP0501T8-E*
MAP0601T8-E*
MAP0804T8-E
MAP1004T8-E
MAP1204T8-E
MAP1404T8-E
MAP1604T8-E
MAP1814T8-E
MAP2014T8-E
MAP2214T8-E
MAP2414T8-E
MAP2614T8-E
MAP2814T8-E
MAP3014T8-E
MAP3214T8-E
MAP3414T8-E
MAP3614T8-E
MAP3814T8-E
MAP4014T8-E
MAP4214T8-E
MAP4414T8-E
MAP4614T8-E
MAP4814T8-E

Cooling Only Model


MMY-

Power Supply
Phase and
Nominal
frequency
Voltage
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V

Power Supply
Phase and
Nominal Voltage
frequency
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V
3N~ 50Hz
380-400-415V

Notes MCA : Minimum Circuit Amps


MOCP : Maximum Overcurrent Protection (Amps)

Heat Pump Model


MMY-

HP

Type

Combination of outdoor unit

9 -2

High efficiency model

Combination of outdoor unit

Single unit

Type

Standard model

Outdoor unit data

Voltage Range
Min.
Max
(V)
(V)
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456

Voltage Range
Min.
Max
(V)
(V)
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456
342
456

Unit No.1
(kW)
2.3 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
4.2 x 2
4.2 x 2
4.2 x 2
4.2 x 2

Unit No.1
(kW)
1.1 x 2
1.4 x 2
2.3 x 2
3.1 x 2
4.2 x 2
3.0 x 3
3.6 x 3
3.1 x 2
3.1 x 2
4.2 x 2
4.2 x 2
3.6 x 3
3.6 x 3
3.6 x 3
3.6 x 3
4.2 x 2
4.2 x 2
3.6 x 3
3.6 x 3
3.6 x 3
3.6 x 3
3.6 x 3
3.6 x 3
3.1 x 2
4.2 x 2
3.1 x 2
4.2 x 2
4.2 x 2
4.2 x 2
3.0 x 3
3.6 x 3

Compressor
Unit No.2
Unit No.3
(kW)
(kW)
2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
3.1 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
4.2 x 2
3.1 x 2
4.2 x 2
4.2 x 2
4.2 x 2
4.2 x 2

2.3 x 2
3.1 x 2
3.1 x 2
4.2 x 2
3.1 x 2
4.2 x 2
3.0 x 3
3.6 x 3
4.2 x 2
4.2 x 2
4.2 x 2
4.2 x 2
3.0 x 3
3.6 x 3
3.6 x 3
3.6 x 3

Compressor
Unit No.2
Unit No.3
(kW)
(kW)

2.3 x 2
2.3 x 2
2.3 x 2
2.3 x 2
3.1 x 2
3.1 x 2
3.1 x 2
3.1 x 2
4.2 x 2

Unit No.4
(kW)

Unit No.4
(kW)

MCA
(A)
46.9
70.4
72.4
74.5
76.5
93.8
95.9
97.9
100.0
102.0
105.0
108.0
111.0
114.0

(kW)
1.0 x 2
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4
1.0 x 4

(A)
16.5
16.5
23.5
25.5
28.5
33.2
36.5
49.0
51.0
54.0
57.0
62.0
65.0
69.7
73.0
82.5
85.5
90.5
93.5
98.2
101.5
106.2
109.5

(kW)
0.6
0.6
1.0
1.0
1.0
1.0
1.0
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 2
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3
1.0 x 3

Fan Motor

MCA

Fan Motor

(A)
63
80
80
100
100
125
125
125
125
125
125
125
125
125

MOCP

(A)
20
20
32
32
40
40
50
63
63
63
63
80
80
80
100
100
100
100
125
125
125
125
125

MOCP

* : SMMS model

9 Wiring Design

9 Wiring Design
5. Indoor unit power supply
Electrical characteristics
Type

4-Way Air
Discharge
Cassette Type

Compact 4-way Cassette


(600 x 600) Type

2-Way Air
Discharge
Cassette Type

1-Way Air
Discharge
Cassette Type

Concealed Duct Type

Concealed Duct
High Static
Pressure Type

Slim Duct Type

Under Ceiling Type

High Wall Type


(1 series)

High Wall Type


(2 series)

High Wall Type


(3 series)

Floor Standing
Cabinet Type

Floor Standing
Concealed Type

Floor Standing Type

Fresh Air Intake Indoor Unit


Type

Model
MMU-AP0092H
MMU-AP0122H
MMU-AP0152H
MMU-AP0182H
MMU-AP0242H
MMU-AP0272H
MMU-AP0302H
MMU-AP0362H
MMU-AP0482H
MMU-AP0562H
MMU-AP0071MH
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
MMU-AP0181MH
MMU-AP 0071 WH
MMU-AP 0091 WH
MMU-AP 0121 WH
MMU-AP 0151 WH
MMU-AP 0181 WH
MMU-AP 0241 WH
MMU-AP 0271 WH
MMU-AP 0301 WH
MMU-AP 0481 WH
MMU-AP 0071 YH
MMU-AP 0091 YH
MMU-AP 0121 YH
MMU-AP0152SH
MMU-AP0182SH
MMU-AP0242SH
MMD-AP 0071 BH
MMD-AP 0091 BH
MMD-AP 0121 BH
MMD-AP 0151 BH
MMD-AP 0181 BH
MMD-AP 0241 BH
MMD-AP 0271 BH
MMD-AP 0301 BH
MMD-AP 0361 BH
MMD-AP 0481 BH
MMD-AP 0561 BH
MMD-AP 0181 H
MMD-AP 0241 H
MMD-AP 0271 H
MMD-AP 0361 H
MMD-AP 0481 H
MMD-AP 0721 H
MMD-AP 0961 H
MMD-AP0071SPH
MMD-AP0091SPH
MMD-AP0121SPH
MMD-AP0151SPH
MMD-AP0181SPH
MMC-AP 0151 H
MMC-AP 0181 H
MMC-AP 0241 H
MMC-AP 0271 H
MMC-AP 0361 H
MMC-AP 0481 H
MMK-AP 0071 H
MMK-AP 0091 H
MMK-AP 0121 H
MMK-AP 0151 H
MMK-AP 0181 H
MMK-AP 0241 H
MMK-AP0072H
MMK-AP0092H
MMK-AP0122H
MMK-AP0073H
MMK-AP0093H
MMK-AP0123H
MMK-AP0153H
MMK-AP0183H
MMK-AP0243H
MML-AP 0071 H
MML-AP 0091 H
MML-AP 0121 H
MML-AP 0151 H
MML-AP 0181 H
MML-AP 0241 H
MML-AP 0071 BH
MML-AP 0091 BH
MML-AP 0121 BH
MML-AP 0151 BH
MML-AP 0181 BH
MML-AP 0241 BH
MMF-AP 0151 H
MMF-AP 0181 H
MMF-AP 0241 H
MMF-AP 0271 H
MMF-AP 0361 H
MMF-AP 0481 H
MMF-AP 0561 H
MMD-AP0481HFE
MMD-AP0721HFE
MMD-AP0961HFE

Voltage Range
Min
Max
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264
198
264

Nominal Voltage
(V-Ph-Hz)
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50

9 -3

Fan Motor
kW
FLA
0.014
0.63
0.014
0.63
0.014
0.80
0.014
0.80
0.020
0.87
0.020
0.87
0.020
0.87
0.068
1.15
0.072
1.15
0.072
1.15
0.060
0.32
0.060
0.35
0.060
0.36
0.060
0.48
0.060
0.48
0.053
0.36
0.053
0.36
0.053
0.36
0.039
0.37
0.039
0.37
0.053
0.53
0.053
0.53
0.053
0.54
0.092
1.33
0.022
0.28
0.022
0.28
0.022
0.28
0.030
0.40
0.030
0.42
0.030
0.71
0.120
0.33
0.120
0.33
0.120
0.39
0.120
0.39
0.120
0.50
0.120
0.60
0.120
0.60
0.120
0.70
0.120
0.96
0.120
1.13
0.120
1.13
0.160
0.93
0.160
1.55
0.160
1.55
0.260
1.87
0.260
2.12
0.370 x 3
6.04
0.370 x 3
6.35
0.060
0.35
0.060
0.35
0.060
0.37
0.060
0.38
0.060
0.47
0.030
0.33
0.030
0.37
0.040
0.48
0.040
0.48
0.080
0.90
0.080
0.96
0.030
0.35
0.030
0.35
0.030
0.35
0.030
0.37
0.030
0.37
0.030
0.40
0.030
0.20
0.030
0.21
0.030
0.22
0.030
0.20
0.030
0.22
0.030
0.22
0.030
0.37
0.030
0.37
0.030
0.43
0.045
0.30
0.045
0.30
0.045
0.49
0.045
0.49
0.070
0.54
0.070
0.54
0.019
0.29
0.019
0.29
0.019
0.29
0.070
0.52
0.070
0.52
0.070
0.53
0.037
0.77
0.037
0.77
0.063
1.01
0.063
1.01
0.110
1.48
0.160
1.84
0.160
1.84
0.160
0.28
0.16 x 2
0.45
0.16 x 2
0.52

Power Supply
MCA
MOCP
0.79
15
0.79
15
1.00
15
1.00
15
1.09
15
1.09
15
1.09
15
1.44
15
1.44
15
1.44
15
0.40
15
0.44
15
0.45
15
0.60
15
0.60
15
0.45
15
0.45
15
0.45
15
0.46
15
0.46
15
0.66
15
0.66
15
0.68
15
1.67
15
0.35
15
0.35
15
0.35
15
0.49
15
0.53
15
0.88
15
0.41
15
0.41
15
0.49
15
0.49
15
0.62
15
0.75
15
0.75
15
0.88
15
1.20
15
1.41
15
1.41
15
1.16
15
1.94
15
1.94
15
2.34
15
2.65
15
7.55
15
7.94
15
0.44
15
0.44
15
0.47
15
0.48
15
0.59
15
0.41
15
0.46
15
0.60
15
0.60
15
1.13
15
1.20
15
0.44
15
0.44
15
0.44
15
0.46
15
0.46
15
0.50
15
0.24
15
0.26
15
0.27
15
0.22
15
0.24
15
0.24
15
0.40
15
0.40
15
0.47
15
0.37
15
0.37
15
0.62
15
0.62
15
0.68
15
0.68
15
0.36
15
0.36
15
0.36
15
0.65
15
0.65
15
0.66
15
0.96
15
0.96
15
1.27
15
1.27
15
1.85
15
2.30
15
2.30
15
0.35
15
0.56
15
0.65
15

9 Wiring Design
Wiring size
Must be independent from the outdoor unit power supply
Item

Model

All models of indoor units

2.0m2 (AWG#14)

Power supply wiring


Wire size
Max. 20m
3.5m2 (AWG#12)

Max. 50m

NOTE:
The above connecting lengths stated in the table, indicate the length from the isolator to the outdoor unit. When the
power supply of the indoor units are connected in parallel, it is assumed that no more than a 2% voltage drop will occur. If
the connecting length is to exceed the stated lengths, select a suitable wire in accordance with the local wiring standards.

6. Design of control wiring


Summary of control wiring
Header outdoor

Central control
device

Follower outdoor

U1 U2 U3 U4 U5 U6

U1 U2
U3 U4

U1 U2 U3 U4 U5 U6

Control wiring between outdoor units (Shield wire)


Control wiring between indoor and outdoor units (Shield wire)
Control wiring between indoor units (Shield wire)

U1 U2 A B

Indoor unit

U1 U2 A B

Indoor unit
A B

Remote controller

U1 U2 A B

Indoor unit

Indoor unit

A B

A B

Remote controller

Remote controller
(Group control)

9 -4

U1 U2 A B

9 Wiring Design
Restriction of control wiring
Be sure to keep the rule of below tables about size and length of control wiring.
Central control
device

Super modular multi system

U1 U2
U3 U4

Header
unit

Header
unit

Table-1

L4
Follower
unit

Follower
unit

Follower
unit

Header
unit

U3 U4

U3 U4

U3 U4

U3 U4

U3 U4

U3 U4

U3 U4

U1 U2 U5 U6

U1 U2 U5 U6

U1 U2 U5 U6

U1 U2 U5 U6

U1 U2 U5 U6

U1 U2 U5 U6

U1 U2 U5 U6

Outdoor unit

Table-1

L5

L1

Table-2

L2

Indoor unit

U1 U2

U1 U2

A B

A B

U1 U2

L3
U1 U2

A B

U1 U2

A B

U1 U2

A B

Table-3

U1 U2

A B

A B

L7

Remote
controller

L6

Remote controller
Remote controller

Table-1 Control wiring between indoor and outdoor units (L1, L2, L3),
Central control wiring (L4)
Wiring
Type
Size/Length

2-core, non-polarity
Shield wire
1.25 mm2: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)

Note (*1): Total length of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4)

Table-2 Control wiring between outdoor units (L5)


Wiring
Type
Size/Length

2-core, non-polarity
Shield wire
1.25 mm2 to 2.0 mm2/Up to 100 m (L5)

Table-3 Remote controller wiring (L6, L7)


Wire
Size
Length

Follower
unit

2-core
0.5 mm2 to 2.0 mm2
Up to 500 m (L6 + L7)
Up 400 m in case of wireless remote controller in group control.
Up to 200 m total length of control wiring between indoor units (L6)

Group Operation through a Remote Controller


Group operation of multiple indoor units (8 units) through a single remote controller switch
Indoor unit No.1

No.2

No.3

No.4

AB

AB

AB

AB

Remote
controller

(A.B)

9 -5

No.7
AB

No.8
AB

U1 U2
A B