Switchgear outdoor ground device erection

Form coding FormDLT5161.62.0.1-1 Outdoor grounding device erection for switchgear Process Check item
Material

Check status Quality Standard


as per design 1m

Inspection result

Vertical grounding Conductor laying Chemical ground electrode installation Grounding Device Connection of high pressure backfill soil

Buried depth (from top) Distance between each other Check item Hole preparation for earth pit Weld part inspect point connected with other ground device quality of backfill soil density smooth soil compaction by layer as per design 6 not less or equal 6m As per design 4m Depth 4m fasten

earth resistance

0.5 no more than 0.5

Quality inspection organization NEPCConstruction team Signed confirmation NEPC Site Technician Signed confirmation NEPC() Professional engineer Signed confirmation CNEEC()Professional engineer Signed confirmation HPC/OE()Professional engineer Signed confirmation

Comments

Signature

inspection signature for resistance of outdoor grounding devices for switch yard
Form coding Form DLT5161.6 4.0.3-1 Check item As per design Bare annealed soft conductor HV HV Equipment Grounding stranded copper conductor 240mm2 Weld per 1 m along steel Exothermic welding along steel support structure Connect to ground Connection to equipment terminal Connect to operator platform measure range date of measure column and structure result

measurement methods, technical parameter and wiring sketch (measurement reports attached ) of grounding resistance: ZC29B-1 G 110HZ I1 T r I2 K r P I1 Rg I2 r r0 Ir*Rg=I2*r0grounding megohm meter measuring method: ZC29B-1 type grounding resistance meter is bridge type, its principle grounding diagram is followed. Hand generator G generating 110HZ current I1, through transformer T primary side current goes to the measured grounding network, from current electrode, back to electrical source. When the current of slide resistance r is I2, when galvanometer P shows zero by adjusting K and r, the voltage reduction of I1 at grounding resistance Rg is equal to the voltage reduction of I2 at a certain resistance r0 within resistance r, that is Ir*Rg=I2*r0 K1- K1-transformer ratio K2- K K2-shunt coefficient at multiplying power switch K K1K2 n=0.1110 Rg r r0 by adjusting K1, K2 make n=0.1110, the measured grounding resistance Rg can be calculated out by multiplying r0 on the dial and integer multiplying power.

Grounding net to electric tension pole about 20m., grounding net to electric current pole about 40m. Terminal C1 and P1 will be connected to grounding conductor at grounding pit 185mm2 from ground grid of equipment

picture 6-2-18 ZC type grounding resistance principle grounding diagram 5 any rainly days or snowing within 5 days before measurement type, series number, specification and expiry date of the meter used designed grounding resistance Quality inspection organization NEPC Construction team Signed confirmation NEPC Site Technician Signed confirmation NEPC() Professional engineer Signed confirmation CNEEC() Professional engineer Signed confirmation HPC/OE() Professional engineer Signed confirmation measured grounding resistance Comments Signature ambient temperature during measurement