Project
Subject
95MW CCPP
SL. NO.
1
DESCRIPTION
LOAD
(WATTS)
AMPS
TOTAL
NO.
Doc. No.
AMPS
2 - 119TH MINUTE
LOAD
QTY.
AMPS
Rev.
Sheet No.
00
REMARKS
AMPS
11 kV Generator Breakers
2 nos of 11 kV breakers
a.
Tripping coil
550
2.50
10.00
0.00
0.00
b.
Tripping relay
150
0.68
1.36
0.00
0.00
c.
Indicating lamps
0.03
0.25
0.25
0.25
d.
Auxiliary relay
20
0.09
0.73
0.73
0.73
e.
400
1.82
0.00
0.00
1.82
f.
Closing coil
500
2.27
0.00
0.00
2.27
g.
25
0.11
0.45
0.45
0.45
h.
Annunciator
30
0.14
0.14
0.14
0.14
2 coils/breaker
4 lamps / feeder
2 relays/feeder
6.6 kV Breakers
a.
Tripping coil
400
1.82
12.73
0.00
0.00
b.
Tripping relay
150
0.68
4.77
0.00
0.00
c.
Indicating lamps
0.03
60
60
1.91
60
1.91
60
1.91
4 lamps / feeder
d.
Auxiliary relay
25
0.11
30
30
3.41
30
3.41
30
3.41
e.
350
1.59
0.00
0.00
11.14
f.
Closing coil
350
1.59
0.00
0.00
11.14
g.
25
0.11
30
30
3.41
30
3.41
30
3.41
h.
Annunciator
50
0.23
0.23
0.23
0.23
2 relays/feeder
415 V Breakers
a.
Tripping coil
250
1.14
10
10
11.36
0.00
0.00
b.
Tripping relay
40
0.18
10
10
1.82
0.00
0.00
c.
Indicating lamps
0.03
80
80
2.55
80
2.55
80
2.55
F:\Elec\3679\bat-cal latest\212772751.xls.xls
1 coil/breaker
JJS / EL
1 coil/breaker
4 lamps / feeder
02/22/2014
FICHTNER India
Project
Subject
95MW CCPP
SL. NO.
DESCRIPTION
AMPS
TOTAL
NO.
2 - 119TH MINUTE
LOAD
Rev.
Sheet No.
00
QTY.
AMPS
QTY.
AMPS
QTY
AMPS
d.
Auxiliary relay
25
0.11
80
80
9.09
80
9.09
80
9.09
e.
350
1.59
10
0.00
0.00
10
15.91
f.
Closing coil
350
1.59
10
0.00
0.00
10
15.91
g.
25
0.11
40
40
4.55
40
4.55
40
4.55
h.
Annunciator
50
0.23
0.23
0.23
0.23
1000
4.55
4.55
4.55
4.55
ST Generator loads
1
LOAD
(WATTS)
Doc. No.
REMARKS
2 relays/feeder
GT Generator loads
1000
4.55
4.55
4.55
4.55
200
0.91
0.91
0.91
0.91
STG loads
1
11000
50.00
100.00
50.00
50.00
18500
84.09
168.18
84.09
84.09
Emergency DC lighting
10000
45.45
45.45
45.45
45.45
AC control panel
1000
4.55
4.55
4.55
4.55
Assumed
1000
4.55
4.55
4.55
4.55
Assumed
10
10.00
10.00
10.00
10.00
11
DAVR
10.00
10.00
10.00
10.00
12
DVR -1
15/40
40.00
15.00
15.00
13
DVR -2
50
50.00
0.00
0.00
14
100
0.45
0.45
0.45
0.45
TOTAL LOAD
F:\Elec\3679\bat-cal latest\212772751.xls.xls
512.16
JJS / EL
261.03
319.21
02/22/2014
FICHTNER India
F:\elec\3679\data\212772751.xls.xls
512.16
512.16
261.03
261.03
261.03
261.03
261.03
261.03
261.03
261.03
261.03
10
261.03
11
261.03
12
261.03
13
261.03
14
261.03
15
261.03
16
261.03
17
261.03
18
261.03
19
261.03
20
261.03
21
261.03
22
261.03
23
261.03
24
261.03
25
261.03
26
261.03
JJS / EL
22/12/1999
FICHTNER India
F:\elec\3679\data\212772751.xls.xls
27
261.03
28
261.03
29
261.03
30
261.03
31
261.03
32
261.03
33
261.03
34
261.03
35
261.03
36
261.03
37
261.03
38
261.03
39
261.03
40
261.03
41
261.03
42
261.03
43
261.03
44
261.03
45
261.03
46
261.03
47
261.03
48
261.03
49
261.03
50
261.03
51
261.03
52
261.03
53
261.03
54
261.03
55
261.03
JJS / EL
22/12/1999
FICHTNER India
F:\elec\3679\data\212772751.xls.xls
56
261.03
57
261.03
58
261.03
59
261.03
60
261.03
61
261.03
62
261.03
63
261.03
64
261.03
65
261.03
66
261.03
67
261.03
68
261.03
69
261.03
70
261.03
71
261.03
72
261.03
73
261.03
74
261.03
75
261.03
76
261.03
77
261.03
78
261.03
79
261.03
80
261.03
81
261.03
82
261.03
83
261.03
84
261.03
JJS / EL
22/12/1999
FICHTNER India
F:\elec\3679\data\212772751.xls.xls
85
261.03
86
261.03
87
261.03
88
261.03
89
261.03
90
261.03
91
261.03
92
261.03
93
261.03
94
261.03
95
261.03
96
261.03
97
261.03
98
261.03
99
261.03
100
261.03
101
261.03
102
261.03
103
261.03
104
261.03
105
261.03
106
261.03
107
261.03
108
261.03
109
261.03
110
261.03
111
261.03
112
261.03
113
261.03
JJS / EL
22/12/1999
FICHTNER India
F:\elec\3679\data\212772751.xls.xls
114
261.03
115
261.03
116
261.03
117
261.03
118
261.03
119
261.03
119
319.21
120
319.21
120
JJS / EL
22/12/1999
FICHTNER India
Project
Subject
Doc. No.
Rev.
Sheet No.
Voltage variation
220 + 10%
Max.voltage of system
(Max.cell voltage during float
charging)
220 x 1.1/2.25
107.6
108
Min.sys.voltage
No.of cells
198/108
1.83
1.85 volt/cell
System Voltage
220 Volts
18 0
Deg.
AH
F:\Elec\3679\bat-sum\212772751.xls.xls
JJS / EL
02/22/2014
FICHTNER India
Project
Subject
Doc. No.
Rev.
Sheet No.
95 MW CCPP
PEEC-1741
00
TNEB- VALUTHUR(PERUNGULAM)
Based on above design parameters the required battery size is calculated below as per IEEE-485 standard
PERIOD
LOAD(Amps)
CHANGE IN LOAD(Amps)
DURATION OF
PERIOD(min)
TIME TO END OF
SECTION(min)
CAPACITY FACTOR
REQUIRED
SIZE(AH)
512.16
512.16
1.03
527.53
NET VALUE
527.53
PERIOD - II
1
512.16
512.16
119
3.26
1669.65
261.03
-251.14
118
118
3.26
-818.70
NET VALUE
850.95
PERIOD - III
1
512.16
512.16
120
3.26
1669.65
261.03
-251.14
118
119
3.26
-818.70
319.21
58.18
1.03
59.93
NET VALUE
Uncorrected size
910.88
Corrected size
1179.31
1200 AH
F:\Elec\3679\bat-sum\212772751.xls.xls
910.88
AH
AH
JJS / EL
02/22/2014
FICHTNER India
F:\Elec\3679\bat-sum\212772751.xls.xls
JJS / EL
02/22/2014
DUTY CYCLE
600.00
500.00
CURRENT (AMPS)
400.00
200.00
100.00
0.00
0
20
40
60
TIME (MIN.)
80
100
120