_______________________________________________________________________________________ Project No. R.050134.002 PLANS AND SPECIFICATIONS INDEX Page 1 of 2 SPECIFICATIONS: SECTION # SECTION TITLE NO.

OF PAGES

DIVISION 1 GENERAL REQUIREMENTS 01 00 10 General Instructions 01 14 00 Work Restrictions 01 14 25 Designated Substances Report 01 32 16.07 Construction Progress Schedule Bar (GANTT) Chart 01 33 00 Submittal Procedures 01 35 29.06 Health and Safety Requirements 01 61 00 Common Product Requirements 01 74 21 Construction/Demolition Waste Management and Disposal 01 78 00 Closeout Submittals DIVISION 7 THERMAL AND MOISTURE PROTECTION 07 21 16 Blanket Insulation 07 92 00 Joint Sealants DIVISION 8 DOORS AND WINDOWS 08 11 00 Metal Doors and Frames 08 14 16 Flush Wood Doors 08 71 00 Door Hardware DIVISION 09 FINISHES 09 21 16 Gypsum Board Assemblies 09 22 16 Non-Structural Metal Framing 09 69 00 Access Flooring 09 91 23 Interior Painting DIVISION 10 SPECIALTIES 10 22 13 Wire Mesh Partitions DIVISION 21 - FIRE SUPPRESSION 21 05 01 Common Work Results for Mechanical 21 13 13 Wet Pipe Sprinkler Systems 21 24 00 Dry Chemical Fire Extinguishing DIVISION 23 - HEATING, VENTILATING AND AIR-CONDITIONING (HVAC) 23 05 01 Use of HVAC Systems During Construction 23 05 93 Testing, Adjusting and Balancing for HVAC 23 31 13.01 Metal Ducts Low Pressure to 500 PA 23 33 00 Air Duct Accessories 23 34 00 HVAC Fans DIVISION 26 - ELECTRICAL 26 05 00 Common Work Results For Electrical 26 05 20 Wire and Box Connectors (0-1000 V) 26 05 21 Wires and Cables (0-1000 V) 26 05 28 Grounding - Secondary 26 05 29 Hangers and Supports for Electrical Systems 26 05 31 Splitters, Junction, Pull Boxes and Cabinets 26 05 32 Outlet Boxes, Conduit Boxes and Fittings 26 05 34 Conduits, Conduit Fastenings and Conduit Fittings 26 27 26 Wiring Devices

7 3 10 3 5 4 5 9 8

2 5

6 3 6

7 3 5 13

4 7 2

2 6 6 4 4

10 3 3 4 2 2 3 4 5

_______________________________________________________________________________________ Project No. R.050134.002 PLANS AND SPECIFICATIONS INDEX Page 2 of 2 26 28 16.02 Moulded Case Circuit Breakers 26 28 23 Disconnect Switches Fused and Non-fused 26 50 00 Lighting 26 52 00 Emergency Lighting 26 53 00 Exit Signs DIVISION 27 - COMMUNICATIONS 27 05 28 Pathways for Communications Systems DIVISION 28 ELECTRONIC SAFETY AND SECURITY 28 31 00 Fire Detection and Alarm Annex B: Pathway Infrastructure Specifications PLANS: ID01A ID01B ID02 ID03 ID04 ID05 ID06 ID07 ID08 ID09 ID10 ID11 ED-1 ED-2 E-1 E-2 E-3 E-4 E-5 E-6 E-7 E-8 M-1 M-2 M-3 S01 Project Phasing and Temporary Hoarding Plan A Project Phasing and Temporary Hoarding Plan B Furniture Plan Furniture Screen Plan Demolition Plan Partition Plan Reflected Ceiling Plan Power/Voice/Data Plan Floor and Wall Finish Plan Door Schedule and Elevations Door Elevations, Sections and Architectural Elevation and Section Partition Sections Electrical Demolition Electrical - Demolition Electrical - Legend and Drawing List Electrical - Lighting and Fire Alarm Electrical - Power and Systems Electrical - Black Cable Tray Electrical - Red Cable Tray Electrical - Schedules and Details Electrical - Details Electrical - Details Mechanical - Fire Protection Plan, Legends and Drawing List Mechanical - HVAC Ceiling Plan Mechanical - HVAC Raised Floor Plan Part Plan and Details 2 2 4 4 2

6 5

END OF SECTION

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 1

Part 1 1.1 .1

General TAXES Pay all taxes properly levied by law (including Federal, Provincial and Municipal). FEES, PERMITS and CERTIFICATES .1 Pay all fees and obtain all permits. Provide authorities with plans and information for acceptance certificates. Provide inspection certificates as evidence that work conforms to requirements of Authority having jurisdiction. CONSTRUCTION PROGRESS SCHEDULE .1 On award of contract submit bar chart construction schedule for work, indicating anticipated progress stages within time of completion. When the Departmental Representative has reviewed schedule, take necessary measures to complete work within scheduled time. Do not change schedule without notifying Departmental Representative. Carry out work during "regular hour", Monday to Friday from 07:00 to 18:00 hours. Carry out interior painting in occupied areas during "silent hours", Monday to Friday from 18:00 to 07:00 hours and on Saturdays, Sundays, and statutory holidays. Thoroughly ventilate areas painted during "silent hours". Give the Departmental Representative 48 hours notice for work to be carried out during "silent hours. REGULATORY REQUIREMENTS .1 References and Codes: .1 Materials shall be new and work shall conform to the minimum applicable standards of the References indicated in the specification sections, the National Building Code of Canada 2010 (NBC) and all applicable Provincial and Municipal codes. In the case of conflict or discrepancy the most stringent requirement shall apply.

1.2

1.3

.2 .3

.4

1.4

.2

Building Smoking Environment: .1 Smoking is not permitted in the Building. restrictions on building property. Obey smoking

.3

Hazardous Material Discovery: .1

Stop work immediately when material resembling spray or trowel-applied asbestos, Polychlorinated Biphenyl
(PCB), mould or other designated substance is encountered during demolition work. .1 Take preventative measure and promptly notify Departmental Representative. .2 Do not proceed until written instructions have been received from Departmental Representative.

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 2

1.5 .1

FIRE SAFETY REQUIREMENTS Comply with both the National Building Code of Canada 2010 and the National Fire Code of Canada 2010 for safety of persons in buildings in the event of a fire and the protection of buildings from the effects of fire, as follows; .1 The National Building Code (NBC): for fire safety and fire protection features that are required to be incorporated in a building during construction. The National Fire Code (NFC): .1 The on-going maintenance and use of the fire safety and fire protection features incorporated in buildings. .2 The conduct of activities that might cause fire hazards in and around buildings. .3 Limitations on hazardous contents in and around buildings. .4 The establishment of fire safety plans. .5 Fire safety at construction and demolition sites.

.2

.2

Where work requires interruption or cause activation of fire alarms or fire suppression, extinguishing or protection systems: .1 Provide Watchman Service as described in NFC 2010; In general, watchman service is defined as an individual conversant with Fire Emergency Procedures, performing fire picket duty within an unprotected and unoccupied (no workers) area once per hour. Retain services of manufacturer for fire protection systems on daily basis or as approved by Departmental Representative, to isolate and protect all devices relating to: .1 modification of fire alarms, fire suppression, extinguishing or protection systems; and/or .2 cutting, welding, soldering or other construction activities that might activate fire protection systems. Immediately upon completion of work, restore fire protection systems to normal operation and verify that all devices are fully operational.

.2

.3

.4

.5

.6

Inform fire alarm system monitoring agency and local Fire Department immediately prior to isolation and immediately upon restoration of normal operation. Designated contractor: shall hire the services of Chubb Edwards to do all the work related to the fire alarm system. Retain and pay all costs for services of company currently operating/servicing the building fire alarm system, to operate and protect all devices relating to: .1 Modification and/or temporary by-pass, shut down of fire alarms, fire suppression, extinguishing or protection systems; and/or, similar action

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 3

during cutting, welding, soldering or other construction activities which might activate fire protection systems. Contact: Leo Boucher Chubb Edwards 8 Hearst Way Kanata, ON K2L 2P4 Office: 613-591-0762 E-mail: leo.boucher@chubbedwards.com
1.6 .1 QUALITY CONTROL Testing Laboratory Services: .1 Departmental Representative will appoint and pay for costs of inspection and testing services, unless indicated otherwise. Provide safe working areas and assist with testing procedures, including provisions for materials or services and co-ordination, as required by testing agency and as authorized by Departmental Representative. Where tests indicate non-compliance with specifications, contractor to pay for initial test and all subsequent testing of work to verify acceptability of corrected work.

.2

.3

.2

Field Quality Control: 1. Carry out Work using qualified licensed workers or apprentices in accordance with Provincial Act respecting manpower vocational training and qualification. 2: Permit employees registered in Provincial apprenticeship program to perform specific tasks only if under direct supervision of qualified licensed workers. 3: Determine permitted activities and tasks by apprentices, based on level of training attended and demonstration of ability to perform specific duties.

1.7 .1

HAZARDOUS MATERIALS Hazardous Materials: product, substance, or organism that may cause adverse impact to environment or adversely affect health of persons, animals, or plant life when released into the environment. Comply with the requirements of the Workplace Hazardous Materials Information System (WHMIS) regarding use, handling, storage, and disposal of hazardous materials; and regarding labelling and the provision of Material Safety Data Sheets (MSDS). For work in occupied buildings, give the Department Representative 48 hours notice for work involving designated substances (Ontario Bill 208), hazardous substances, and before painting, caulking, installing carpet or using adhesives and other materials, that cause off gassing.

.2

.3

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 4

1.8 .1

TEMPORARY UTILITIES Existing services required for work, excluding power required for space temporary heating, may be used by the Contractor without charge. Ensure capacity is adequate prior to imposing additional loads. Connect and disconnect at own expense and responsibility. Notify the Departmental Representative and utility companies of intended interruption of services and obtain requisite permission. Give the Departmental Representative 1 week (5 working days) notice related to each necessary interruption of any mechanical or electrical service throughout the course of the work. Keep duration of these interruptions to a minimum. Carry out all interruptions after normal working hours of the occupants, preferably on weekends. CONSTRUCTION FACILITIES .1 Site Storage: .1 .2 .3 The Departmental Representative will assign storage space that shall be equipped and maintained by the Contractor. Do not unreasonably encumber site with materials or equipment. Move stored products or equipment that interfere with operations of Departmental Representative or other contractors. Obtain and pay for use of additional storage or work areas needed for operations. Do not load or permit to load any part of work with weight or force that will endanger work.

.2

.3

1.9

.4 .5 .2 .3 .4

Where security is reduced by work provide temporary means to maintain security. Sanitary facilities: will be assigned for Contractor's personnel. Others shall not be used. Keep facilities clean. Signage: .1 Provide common-use signs related to traffic control, information, instruction, use of equipment, public safety devices, etcetera, in both official languages or by the use of commonly understood graphic symbols and to approval of the Departmental Representative. No advertising will be permitted on this project. Maintain approved signs and notices in good condition for duration of project and dispose of off site, on completion of project or earlier, as directed by Departmental Representative.

.2 .3

1.10 .1 .2

TEMPORARY BARRIERS AND ENCLOSURES Maintain existing services to building and provide for personnel and vehicle access. Hoarding:

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 5

.1 .3

Design, erect and maintain temporary site enclosures as indicated.

Dust Control: .1 Provide dust tight screens or partitions to localize dustgenerating activities, and for protection of workers, finished areas of work and public. Dust filtering system required to prevent dust from being dispersed inside the HVAC system including filters installed on ventilation returns. Maintain and relocate protection until such work is complete. Protect all furnishings within work area with 0.102mm thick polyethylene film during construction. Remove film during non-construction hours and leave premises in clean, unencumbered and safe manner for normal daytime function.

.2

.3 .4

.4

Design, construct and maintain temporary "access to" and "egress from" work areas, including stairs, runways, ramps or ladders and scaffolding, independent of finished surfaces and in accordance with relevant municipal, provincial and other regulations. Protection: .1 .2 .3 Protect work against damage until take-over. Protect adjacent work against the spread of dust and dirt beyond the work areas. Protect operatives and other users of site from all hazards.

.5

1.11 .1 .2

EXAMINATION and PREPARATION Examine site and conditions likely to affect work and be familiar and conversant with existing conditions. Before commencing work, establish location and extent of services lines in area of work and notify Departmental Representative of findings. EXECUTION .1 Cut, Patch and Make Good: .1 .2 .3 Cut existing surfaces as required to accommodate new work. Remove all items so shown or specified. Patch and make good surfaces cut, damaged or disturbed, to Departmental Representatives approval. Match existing material, colour, finish and texture.

1.12

.2

Firestop and smoke seal systems: in accordance with CAN-ULC-S11505 Standard Method of Fire Test of Firestop Systems. Install around pipe, ductwork, cables, and other objects penetrating fire separations to provide fire resistance not less than the fire resistance rating of surrounding floor, ceiling, and wall assembly. Sleeves, Hangers and Inserts: co-ordinate setting and packing of sleeves and supply and installation of hangers and inserts.

.3

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 6

Obtain Departmental Representatives approval before cutting into structure. .4 Unless otherwise specified, materials for removal become the Contractor's property and shall be taken from site. CLEANING .1 Clean up as work progresses. At the end of each work period, and more often if ordered by the Departmental Representative, remove debris from site, neatly stack material for use, and clean up generally. Upon completion remove scaffolding, temporary protection and surplus materials. Make good defects noted at this stage. Clean and polish glass, mirrors, ceramic tile, aluminum, chrome, stainless steel, baked or porcelain enamel, plastic laminate and other plastic surfaces, floors, hardware and washroom fixtures. Clean manufactured articles in accordance with manufacturer's written instructions. Clean areas under contract to a condition equal to what previously existed and to approval of Departmental Representative. SECURITY CHECK .1 All personnel employed on this project will be subject to security check. Obtain requisite clearance, as instructed, for each individual required to enter the premises. Personnel will be checked daily at start of work shift and given a pass, which must be worn at all times. Pass must be returned at end of work shift and personnel checked out. COST BREAKDOWN .1 Before submitting first progress claim, submit breakdown of Contract Amount in detail as directed by Departmental Representative and aggregating the Contract Amount. After approval by Departmental Representative cost breakdown will be used as the basis of progress payments. PRECEDENCE .1 For Federal Government projects, Division 01 Sections take precedence over technical specification sections in other Divisions of this Project Manual

1.13

.2 .3

.4

1.14

.2

1.15

1.16

Part 2 2.1 .1

PRODUCTS NOT USED Not used.

Project No. R.050134.002

GENERAL INSTRUCTIONS

Section 01 00 10 Page 7

Part 3 3.1 .1

EXECUTION NOT USED Not used.

END OF SECTION

Project No. R.050134.002

WORK RESTRICTIONS

Section 01 14 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 01 00 10 - General Instructions.

1.2 ACCESS AND EGRESS

.1

Design, construct and maintain temporary "access to" and "egress from" work areas, including stairs, runways, ramps or ladders and scaffolding, independent of finished surfaces and in accordance with relevant municipal, provincial and other regulations. Execute work with least possible interference or disturbance to normal use of premises. Make arrangements with Departmental Representative to facilitate work as stated. Maintain existing services to building and provide for personnel and vehicle access. Where security is reduced by work provide temporary means to maintain security. Departmental Representative will assign sanitary facilities for use by Contractor's personnel. Keep facilities clean. Closures: protect work temporarily until permanent enclosures are completed. Execute work with least possible interference or disturbance to building operations and occupants, and normal use of premises. Arrange with Departmental Representative to facilitate execution of work.

1.3 USE OF SITE AND FACILITIES

.1

.2

.3

.4

.5

1.4 ALTERATIONS, ADDITIONS OR REPAIRS TO EXISTING BUILDING

.1

1.5 EXISTING SERVICES

.1

Notify, Departmental Representative and utility companies of intended interruption of services and obtain required permission. Where Work involves breaking into or connecting to existing services, give Departmental Representative 1 week (5 working days) of notice for necessary interruption of mechanical or electrical service throughout course of work. Keep duration of interruptions minimum. Carry out interruptions after normal working hours of occupants, preferably on weekends. Paint occupied areas Monday to Friday from 18:00 to

.2

1.6 SPECIAL

.1

Project No. R.050134.002

WORK RESTRICTIONS

Section 01 14 00 Page 2

REQUIREMENTS
.2

07:00 hours only and on Saturdays, Sundays, and statutory holidays. Carry out noise generating Work Monday to Friday from 18:00 to 07:00 hours and on Saturdays, Sundays, and statutory holidays. Submit schedule in accordance with Section 01 00 10 - General Instructions. Ensure Contractor's personnel employed on site become familiar with and obey regulations including safety, fire, traffic and security regulations. Keep within limits of work and avenues of ingress and egress. Deliver materials outside of peak traffic hours 7:00 to 15:00 unless otherwise approved by Departmental Representative. Provide 72 hours advance notice to the Departmental Representative for coordination of deliveries. Where security has been reduced by Work of Contract, provide temporary means to maintain security. Security clearances: .1 Personnel employed on this project will be subject to security check. Obtain clearance, as instructed, for each individual who will require to enter premises. .2 Obtain requisite clearance, as instructed, for each individual required to enter premises. .3 Personnel will be checked daily at start of work shift and provided with pass which must be worn at all times. Pass must be returned at end of work shift and personnel checked out. Security escort: .1 Personnel employed on this project must be escorted when executing work in non-public areas during normal working hours. Personnel must be escorted in all areas after normal working hours. .2 Submit an escort request to Departmental Representative at least 14 days before service is needed. For requests submitted within time noted above, costs of security escort will be paid for by Departmental Representative. Cost incurred by late request will be Contractor's responsibility. .3 Any escort request may be cancelled free of charge if notification of cancellation is given at least 4 hours before scheduled time of escort. Cost incurred by late request will be Contractor's responsibility. .4 Calculation of costs will be based on average hourly rate of security officer for minimum of 8 hours

.3

.4

.5

.6

1.7 SECURITY

.1

.2

.3

Project No. R.050134.002

WORK RESTRICTIONS

Section 01 14 00 Page 3

per day for late service request and of 4 hours for late cancellations.

1.8 BUILDING SMOKING ENVIRONMENT PART 2 - PRODUCTS

.1

Comply with smoking restrictions. Smoking is not permitted.

2.1 NOT USED

.1

Not Used.

PART 3 - EXECUTION 3.1 NOT USED


.1 Not Used.

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 1

PART 1 GENERAL 1.1 REGULATORY REQUIREMENTS .1 An investigation into the presence of designated substances for the Dismantling of the Current Partition in OPS Room Project at 3545 Leitrim Road, Ottawa, Ontario was performed in order to meet the requirements of the Canada Labour Code under Part II, section 124 which stipulates that every employer shall ensure that the health and safety at work of every person employed by the employer is protected and those employees are made aware of every known or foreseeable health or safety hazard in the work environment. Also, it was performed to meet the requirements of Section 30 of the Ontario Occupational Health and Safety Act, Revised Statutes of Ontario, 1990, Chapter 0.1. By having a Designated Substances Report (DSR) conducted, the Departmental Representative will be able to inform his or her employees, contractors, and tenants of any designated substances that may be present and possibly disturbed throughout the duration of the project. The informed Departmental Representative will then be able to impose appropriate health and safety precautions for all applicable personnel as required. .2 The designated substances identified in the Occupational Health and Safety Act and its corresponding regulations are: .1 Acrylonitrile: Designated Substance Acrylonitrile O.Reg 835 (as amended by O.Reg 490/09) Arsenic: Designated Substance Arsenic O.Reg 836 (as amended by O.Reg 490/09) Asbestos .1 The Regulation Respecting Asbestos O.Reg 837 (as amended by O.Reg 490/09) .2 General Waste Management O.Reg 347 (as amended by O.Reg 337/09) .3 Designated Substance Asbestos on Construction Projects and in Buildings and Repair Operations O.Reg 278/05 (as amended by O.Reg 493/09)

.2

.3

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 2

.4

PWGSC Departmental Policy DP 057 Asbestos Management

.4

Benzene: Designated Substance Benzene O.Reg 839 (as amended by O.Reg 490/09) Coke Oven Emissions: Designated Substance Coke Oven Emissions O.Reg 840 (as amended by O.Reg 490/09) Ethylene Oxide: Designated Substance Ethylene Oxide O.Reg 841 (as amended by O.Reg 490/09) Isocyanates: Designated Substance Isocyanates O.Reg 842 (as amended by O.Reg 490/09) Lead: .1 Designated Substance Lead O.Reg 843 (as amended by O.Reg 490/09) General Waste Management O.Reg 347 (as amended by O.Reg 337/09) Hazardous Products Acts Regulations Amending the Surface Coating Materials Regulations SOR/2010-224

.5

.6

.7

.8

.2

.3

.9

Mercury: .1 Designated Substance Mercury O.Reg 844 (as amended by O.Reg 490/09) General Waste Management O.Reg 347 (as amended by O.Reg 337/09)

.2

.10

Silica: Designated Substance Silica O.Reg 845 (as amended by O.Reg 490/09) Vinyl Chloride: Designated Substance Vinyl Chloride O.Reg 846 (as amended by O.Reg 490/09)

.11

.3

All contractors requesting tenders from subcontractors shall furnish this report to subcontractors.

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 3

1.2

VALIDITY DATE .1 Cyprien Amani, Environmental Analyst of the Environmental Services Directorate of the Real Property Branch, PWGSC, conducted the on-site survey for this report on 2013/04/12. The work area is located at the 3545 Leitrim Road, in OPS Room, Ottawa, Ontario. The scope of the work proposed consists of : dismantling the current partition to have an open space . .1 The scope of work for this report involved a visual inspection of building materials and contents for the presence of suspected designated substances in the project area on 2013/04/12. From the visual inspection suspect materials were sampled and analyzed, where appropriate, for the above substances. On the basis of this inspection, a total of fifteen (15) bulk samples of suspected asbestoscontaining materials (ACMs), and three (3) bulk samples of suspected lead-containing paint were collected. Bulk ACM samples were collected in order to satisfy the requirements of O. Reg. 278/05, as amended. The samples were then submitted for analysis to the EXOVA Laboratory (an accredited CAEAL lab) located at 146 Colonnade Road, Nepean, Ontario, K2E 7Y1. The bulk asbestos samples were analyzed using Polarized Light Microscopy (PLM). This analytical method complies with the United States Environmental Protection Agency (U.S. EPA) Method 600/R-93/116. The lead analysis of the paint samples was completed using Inductively Coupled Plasma Mass Spectrometry (ICP-MS) in accordance with U.S. EPA Method 6010-C.

.2

.2

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 4

.3

The visual inspection and sampling was limited to readily accessible areas. Destructive testing was not included in the investigation, but is recommended prior to any major demolition. Due to the nature of building construction, some inherent limitations exist as to the possible thoroughness of the designated substance survey. The survey did not include the demolition of floors, floor finishes, plaster ceilings or walls or other areas to examine concealed conditions. No confined space was accessed for the purpose of this report. It is possible that the designated substances aforementioned are present in non-accessible areas and concealed spaces (i.e., wall and ceiling cavities), or confined spaces. No other areas outside the defined work boundaries have been assessed. Prior to beginning work, it must be confirmed with the Departmental Representative that no additional designated substances have been brought to the project area. In addition, the survey refers to PCBs and halocarbons; however, it does not refer to other substances that may be present in the day-to-day usage for specialized equipment or areas in buildings (i.e. lead shields, fume hoods, etc.). There is a possibility that materials which could not be reasonably identified within the scope of this assessment or which were not apparent during previous site visits may exist. Should any designated substance be encountered in the course of demolition, work must be stopped, preventative measures taken, and the Departmental

.4

.5

.6

.7

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 5

Representative must be notified immediately. Do not proceed until written instructions have been received. PART 2 - DESIGNATED SUBSTANCES 2.1 SURVEY RESULTS .1 .2 .3 ACRYLONITRILE: ARSENIC: Not Identified

Not Identified

ASBESTOS: Not Identified Asbestos is a naturally occurring material. In general, it has historically been intentionally added to many building materials in the construction industry to increase thermal or chemical resistance properties. More common uses are thermal insulation for pipes and boilers, structural steelwork fireproofing, floor tiles and in-wall and ceiling plasters. There are two classes of asbestos- containing materials: friable and non-friable. Friable asbestos-containing materials are loose in composition or can be easily crumbled using hand pressure. Non-friable asbestos-containing materials are more durable and are held together by a binder such as cement, vinyl or asphalt. Representative bulk samples, collected on 2013/04/12 from materials located within the project area have been analyzed for asbestos .Analytical results indicate that no asbestos has been detected in all drywall joint compounds, plaster, ceiling tile, partition wall material samples collected from the project area and submitted. The results are shown in Table 1 below.

Table 1: Asbestos Sample Results

Sample number LEITRIMROAD-AS-1A LEITRIMROAD-AS-1B Plaster Plaster

Material

Location From Room 1039 , OPS From Room 1039 , OPS

Asbestos Type n/a n/a

Asbestos content (%) n/d n/d

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 6

LEITRIMROAD-AS-1C LEITRIMROAD-AS-2A LEITRIMROAD-AS-2B LEITRIMROAD-AS-2C LEITRIMROAD-AS-3A LEITRIMROAD-AS-3B LEITRIMROAD-AS-3C LEITRIMROAD-AS-4A LEITRIMROAD-AS-4B LEITRIMROAD-AS-4C LEITRIMROAD-AS-5A LEITRIMROAD-AS-5B LEITRIMROAD-AS-5C

Plaster Drywall joint compounds Drywall joint compounds Drywall joint compounds Ceiling Tile Ceiling Tile Ceiling Tile Drywall joint compounds Drywall joint compounds Drywall joint compounds Partition wall material Partition wall material Partition wall material

From Room 1039 , OPS From Room 1036, OPS From Room 1036, OPS From Room 1036, OPS From Room 1039, OPS From Room 1039, OPS From Room 1039, OPS From Room 1037, OPS From Room 1037, OPS From Room 1037, OPS From Room 1037, OPS From Room 1037, OPS From Room 1037, OPS

n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d n/d

n/d = none detected, n/a = not applicable .4 .5 .6 .7 .8 BENZENE: Not Identified COKE OVEN EMISSIONS: ETHYLENE OXIDE: ISOCYANATES: LEAD: Not Identified

Not Identified

Not Identified

Trace amounts identified

Lead is a naturally occurring metal. It was used primarily in paint prior to the 1980's to increase the drying process. Lead in paint becomes a danger when it is old or damaged, as it creates lead dust and chips. Lead can also be found in soldered joints installed on piping up to the mid 1990s and in older cast iron bell and spigot joints. .1 According to the Hazard Products Acts Regulations Amending the Surface Coating Materials Regulations SOR/2010-224 allowable concentration of lead in surface coatings is 0.009 percent by weight (weight of lead to weight of paint), which is equivalent to 90 parts per million (ppm). .2 The laboratory analysis results indicate that trace amounts of lead were detected in the beige paint sample collected from the wall in

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 7

Rooms 1036, 1037 and 1039, OPS (Leitrimroad-Pb-1, Leitrimroad-Pb2, Leitrimroad-Pb-3). The results are shown in Table 2 below.

Table 2: Lead Sample Results

Sample Number LEITRIMROAD-Pb-1 LEITRIMROAD-Pb-2 LEITRIMROAD-Pb-3

Description Beige paint Beige paint Beige paint


.9 .10

Location From Room 1039 , OPS From Room 1036 , OPS From Room 1037, OPS
MERCURY: SILICA: Not Identified Identified

Lead Content (ppm) <10 <50 <10

Free crystalline silica is present in concrete within the project area. .11 .12 .13 2.2 RECOMMENDATIONS 1. LEAD If lead-containing materials are disturbed (i.e. during dry sanding, grinding, polishing and sawing operations), then proper precautions, as outlined under Designated Substances O.Reg 490/09, as amended, of the Occupational Health and Safety Act, must be followed. Under Ontario Regulation 490/09, as amended of the Occupational Health and Safety Act, regulatory limits have been established for occupational exposure limits to airborne lead that may be present in a workplace. The Time Weighted Average Exposure Values to airborne lead dust or fumes should not exceed the Ministry of Labours 0.05 milligram per cubic metre (mg/m3) limit during the removal of paints and products containing any concentration of lead. The TWAEV represents the VINYL CHLORIDE MONOMER: Identified Not

POLYCHLORINATED BIPHENYLS (PCBs): Not Identified HALOCARBONS: Not Identified

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 8

time-weighted average concentration for a conventional 8-hour workday and a 40-hour workweek, to which it is believed that nearly all workers may be repeatedly exposed, day after day, without adverse health effects. Contractors performing work that requires disturbance of leadcontaining materials are responsible to ensure that the workers are not exposed to airborne lead dust levels in excess of the time-weighted average and Maximum Exposure Concentration for lead-containing paints. It should be noted that the use of mechanicallypowered tools or torches on leadcontaining materials increases the concentration of airborne lead dust or fumes and thereby requiring more stringent respiratory protection and controlled work procedures. .1 Ontario Ministry of Labour (MoL) has published the document entitled Guideline: Lead on Construction Projects. This document classifies all disturbances of lead-containing materials as Type 1, Type 2a, Type 2b, Type 3a or Type 3b work, based on presumed airborne concentrations of lead generated during the work each of which will have defined work practices. Although this document is not a regulation, Ministry of Labour Inspectors use it as guidance during site inspections. .2 The disposal of construction waste containing lead is controlled by General Waste Management O.Reg 347/09, as amended, under the Ontario Environmental Protection Act. The classification of the waste is dependent upon the result(s) of leachate test(s). The waste can be classified as "hazardous", "nonhazardous" or "registerable solid waste", depending on the results of the leachate test. Prior to disposal, the concentration of leachable lead must be determined for waste materials with elevated lead contents following the Toxicity

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 9

Characteristic Leaching Procedure (TCLP). 2. SILICA . 1 Silica occurs as crystalline material in cement. Crystalline silica is regulated under Designated Substance Silica O.Reg 845 (as amended by O.Reg 490/09) of the Occupational Health and Safety Act as a Designated Substance. .2 Silica dust can be generated through such processes as blasting, grinding, crushing, and sandblasting silica-containing material. Since silica is present in the drywall within the project area, appropriate respiratory protection and ventilation must be donned during the demolition and modifications of these structures. .3 The Occupational Health and Safety Branch of the MoL has published the document entitled Guideline: Silica on Construction Projects. This document classifies the disturbance of materials containing silica as Type 1, Type 2 or Type 3 work, and assigns different levels of respiratory protection and work procedures for each classification. These work procedures should be followed when performing work involving the disturbance of silica-containing materials. CONTRACTORS DUTIES The contractor must review the designated substance report and take the necessary precautions to protect the health and safety of the workers and the environment. As per Section 30(4) of the Ontario Occupational Health and Safety Act, the party hiring the contractor (i.e. Departmental Representative) shall ensure that the contractor and subcontractor (if any) for the project has received a copy of the designated substance report prior to entering a binding contract for the supply of work on the project. As per Section 27(2) (a, b, and c) of the Ontario

Project No. R.050134.002

DESIGNATED SUBSTANCES REPORT

Section 01 14 25 Page 10

Occupational Health and Safety Act, while onsite, the contractor supervisor shall exercise every reasonable precaution for the protection of a worker. If you have any questions about the designated substance report, please contact the Departmental Representative. END OF SECTION

Project No. R.050134.002

CONSTRUCTION PROGRESS Sect 01 32 16.07 SCHEDULE - BAR (GANTT) CHART Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS 1.2 DEFINITIONS

.1

Section 01 00 10 - General Instructions.

.1

Activity: element of Work performed during course of Project. Activity normally has expected duration, and expected cost and expected resource requirements. Activities can be subdivided into tasks. Bar Chart (GANTT Chart): graphic display of schedule-related information. In typical bar chart, activities or other Project elements are listed down left side of chart, dates are shown across top, and activity durations are shown as date-placed horizontal bars. Generally Bar Chart should be derived from commercially available computerized project management system. Baseline: original approved plan (for project, work package, or activity), plus or minus approved scope changes. Construction Work Week: Monday to Friday, inclusive, will provide five day work week and define schedule calendar working days as part of Bar (GANTT) Chart submission. Duration: number of work periods (not including holidays or other nonworking periods) required to complete activity or other project element. Usually expressed as workdays or workweeks. Master Plan: summary-level schedule that identifies major activities and key milestones. Milestone: significant event in project, usually completion of major deliverable. Project Schedule: planned dates for performing activities and the planned dates for meeting milestones. Dynamic, detailed record of tasks or activities that must be accomplished to satisfy Project objectives. Monitoring and control process involves using Project Schedule in executing and controlling activities and is used as basis for decision making throughout project life cycle. Project Planning, Monitoring and Control System: overall system operated by Departmental Representative DCC Representative Consultant to enable monitoring of project work in relation to established milestones.

.2

.3

.4

.5

.6

.7

.8

.9

Project No. R.050134.002

CONSTRUCTION PROGRESS Sect 01 32 16.07 SCHEDULE - BAR (GANTT) CHART Page 2


Ensure Master Plan and Detail Schedules are practical and remain within specified Contract duration. Plan to complete Work in accordance with prescribed milestones and time frame. Limit activity durations to maximum of approximately 10 working days, to allow for progress reporting. Ensure that it is understood that Award of Contract or time of beginning, rate of progress, Interim Certificate and Final Certificate as defined times of completion are of essence of this contract. Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Submit to Departmental Representative within five (5) working days of Award of Contract Bar (GANTT) Chart as Master Plan for planning, monitoring and reporting of project progress. Submit Project Schedule to Departmental Representative within five (5) working days of receipt of acceptance of Master Plan. Project milestones form interim targets for Project Schedule. . .1 Phase 1 Mobilization onsite 2 weeks after contract award .2 Phase 1 Construction completed within 6 weeks of mobilization. .3 Demobilize and allow for 8 weeks of stoppage. .4 Remobilize as per Departmental Representative instructions. .5 Phase 2 Construction completed within 4 weeks of remobilization. .6 Commissioning and final certificate within 20 weeks of Contract award. Structure schedule to allow orderly planning, organizing and execution of Work as Bar Chart (GANTT). Departmental Representative will review and return revised schedules within five (5) working days. Revise impractical schedule and resubmit within five (5) working days. Accepted revised schedule will become Master Plan and be used as baseline for updates. Develop detailed Project Schedule derived from Master Plan.

1.3 REQUIREMENTS

.1

.2

.3

.4

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

.3

1.5 PROJECT MILESTONES

.1

1.6 MASTER PLAN

.1

.2

.3

.4

1.7 PROJECT SCHEDULE

.1

Project No. R.050134.002

CONSTRUCTION PROGRESS Sect 01 32 16.07 SCHEDULE - BAR (GANTT) CHART Page 3


Ensure detailed Project Schedule includes as minimum milestone and activity types as follows: .1 Award. .2 Shop Drawings, Samples. .3 Permits. .4 Mobilization. .5 Interior Architecture (Walls, Floors and Ceiling). .6 Plumbing. .7 Lighting. .8 Electrical. .9 Piping. .10 Controls. .11 Heating, Ventilating, and Air Conditioning. .12 Fire Systems. .13 Testing and Commissioning. .14 Supplied equipment long delivery items.

.2

1.8 PROJECT SCHEDULE REPORTING

.1

Update Project Schedule on weekly basis reflecting activity changes and completions, as well as activities in progress. Include as part of Project Schedule, narrative report identifying Work status to date, comparing current progress to baseline, presenting current forecasts, defining problem areas, anticipated delays and impact with possible mitigation. Discuss Project Schedule at regular site meetings, identify activities that are behind schedule and provide measures to regain slippage. Activities considered behind schedule are those with projected start or completion dates later than current approved dates shown on baseline schedule. Weather related delays with their remedial measures will be discussed and negotiated.

.2

1.9 PROJECT MEETINGS

.1

.2

PART 2 - PRODUCTS 2.1 NOT USED


.1 Not used.

PART 3 - EXECUTION

3.1 NOT USED

.1

Not used.

Project No. R.050134.002

SUBMITTAL PROCEDURES

Section 01 33 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 01 10 10 - General Instructions.

1.2 ADMINISTRATIVE

.1

Submit to Departmental Representative submittals listed for review. Submit promptly and in orderly sequence to not cause delay in Work. Failure to submit in ample time is not considered sufficient reason for extension of Contract Time and no claim for extension by reason of such default will be allowed. Do not proceed with Work affected by submittal until review is complete. Present shop drawings, product data, samples and mock-ups in SI Metric units. Where items or information is not produced in SI Metric units converted values are acceptable. Review submittals prior to submission to Departmental Representative . This review represents that necessary requirements have been determined and verified, or will be, and that each submittal has been checked and co-ordinated with requirements of Work and Contract Documents. Submittals not stamped, signed, dated and identified as to specific project will be returned without being examined and considered rejected. Notify Departmental Representative , in writing at time of submission, identifying deviations from requirements of Contract Documents stating reasons for deviations. Verify field measurements and affected adjacent Work are co-ordinated. Contractor's responsibility for errors and omissions in submission is not relieved by Departmental Representative's review of submittals. Contractor's responsibility for deviations in submission from requirements of Contract Documents is not relieved by Departmental Representative review. Keep one reviewed copy of each submission on site.

.2

.3

.4

.5

.6

.7

.8

.9

.10

Project No. R.050134.002

SUBMITTAL PROCEDURES

Section 01 33 00 Page 2

1.3 SHOP DRAWINGS

AND PRODUCT DATA

.1

The term "shop drawings" means drawings, diagrams, illustrations, schedules, performance charts, brochures and other data which are to be provided by Contractor to illustrate details of a portion of Work. Submit drawings stamped and signed by professional engineer registered or licensed in Province of Ontario. Indicate materials, methods of construction and attachment or anchorage, erection diagrams, connections, explanatory notes and other information necessary for completion of Work. Where articles or equipment attach or connect to other articles or equipment, indicate that such items have been co-ordinated, regardless of Section under which adjacent items will be supplied and installed. Indicate cross references to design drawings and specifications. Allow 2 days for Departmental Representative's review of each submission. Adjustments made on shop drawings by Departmental Representative are not intended to change Contract Price. If adjustments affect value of Work, state such in writing to Departmental Representative prior to proceeding with Work. Make changes in shop drawings as Departmental Representative may require, consistent with Contract Documents. When resubmitting, notify Departmental Representative Consultant in writing of revisions other than those requested. Accompany submissions with transmittal letter, containing: .1 Date. .2 Project title and number. .3 Contractor's name and address. .4 Identification and quantity of each shop drawing, product data and sample. .5 Other pertinent data. Submissions include: .1 Date and revision dates. .2 Project title and number. .3 Name and address of: .1 Subcontractor. .2 Supplier. .3 Manufacturer. .4 Contractor's stamp, signed by Contractor's authorized representative certifying approval of submissions, verification of field measurements and

.2

.3

.4

.5

.6

.7

.8

Project No. R.050134.002

SUBMITTAL PROCEDURES

Section 01 33 00 Page 3

compliance with Contract Documents. .5 Details of appropriate portions of Work as applicable: .1 Fabrication. .2 Layout, showing dimensions, including identified field dimensions, and clearances. .3 Setting or erection details. .4 Capacities. .5 Performance characteristics. .6 Standards. .7 Operating weight. .8 Wiring diagrams. .9 Single line and schematic diagrams. .10 Relationship to adjacent work. .9 After Departmental Representative's review, distribute copies. Submit electronic copy of shop drawings for each requirement requested in specification Sections and as Departmental Representative may reasonably request. Submit electronic copies of product data sheets or brochures for requirements requested in specification Sections and as requested by Departmental Representative where shop drawings will not be prepared due to standardized manufacture of product. Submit electronic copies of test reports for requirements requested in specification Sections and as requested by Departmental Representative. .1 Report signed by authorized official of testing laboratory that material, product or system identical to material, product or system to be provided has been tested in accord with specified requirements. .2 Testing must have been within 3 years of date of contract award for project. Submit electronic copies of certificates for requirements requested in specification Sections and as requested by Departmental Representative. .1 Statements printed on manufacturer's letterhead and signed by responsible officials of manufacturer of product, system or material attesting that product, system or material meets specification requirements. .2 Certificates must be dated after award of project contract complete with project name. Submit electronic copies of manufacturers instructions for requirements requested in specification Sections and as requested by Departmental Representative. .1 Pre-printed material describing installation of product, system or material, including special notices and Material Safety Data Sheets concerning impedances, hazards and safety precautions.

.10

.11

.12

.13

.14

Project No. R.050134.002

SUBMITTAL PROCEDURES

Section 01 33 00 Page 4

.15

Submit electronic copies of Manufacturer's Field Reports for requirements requested in specification Sections and as requested by Departmental Representative. Documentation of the testing and verification actions taken by manufacturer's representative to confirm compliance with manufacturer's standards or instructions. Submit electronic copies of Operation and Maintenance Data for requirements requested in specification Sections and as requested by Departmental Representative. Delete information not applicable to project. Supplement standard information to provide details applicable to project. If upon review by Departmental Representative, no errors or omissions are discovered or if only minor corrections are made, copies will be returned and fabrication and installation of Work may proceed. If shop drawings are rejected, noted copy will be returned and resubmission of corrected shop drawings, through same procedure indicated above, must be performed before fabrication and installation of Work may proceed. The review of shop drawings by Public Works and Government Services Canada (PWGSC) is for sole purpose of ascertaining conformance with general concept. .1 This review shall not mean that PWGSC approves detail design inherent in shop drawings, responsibility for which shall remain with Contractor submitting same, and such review shall not relieve Contractor of responsibility for errors or omissions in shop drawings or of responsibility for meeting requirements of construction and Contract Documents. .2 Without restricting generality of foregoing, Contractor is responsible for dimensions to be confirmed and correlated at job site, for information that pertains solely to fabrication processes or to techniques of construction and installation and for co-ordination of Work of sub-trades. Submit for review samples in duplicate as requested in respective specification Sections. Label samples with origin and intended use. Deliver samples prepaid to Departmental Representative's business address. Notify Departmental Representative in writing, at time of submission of deviations in samples from

.16

.17

.18 .19

.20

.21

1.4 SAMPLES

.1

.2

.3

Project No. R.050134.002

SUBMITTAL PROCEDURES

Section 01 33 00 Page 5

requirements of Contract Documents. .4 Where colour, pattern or texture is criterion, submit full range of samples. Adjustments made on samples by Departmental Representative are not intended to change Contract Price. If adjustments affect value of Work, state such in writing to Departmental Representative prior to proceeding with Work. Make changes in samples which Departmental Representative may require, consistent with Contract Documents. Reviewed and accepted samples will become standard of workmanship and material against which installed Work will be verified.

.5

.6

.7

1.5 CERTIFICATES AND TRANSCRIPTS

.1

Immediately after award of Contract, submit Workers' Compensation Board status. Submit transcription of insurance immediately after award of Contract.

.2

PART 2 - PRODUCTS

2.1 NOT USED

.1

Not Used.

PART 3 - EXECUTION

3.1 NOT USED

.1

Not Used.

Project No. R.050134.002

HEALTH AND SAFETY REQUIREMENTS

Sect 01 35 29.06 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 01 00 10 - General Instructions.

1.2 REFERENCES

.1

Province of Ontario .1 Occupational Health and Safety Act and Regulations for Construction Projects, R.S.O. 1990, c. 0.1, as amended and O. Reg. 213/91, as amended. Make submittals in accordance with Section 01 33 00 - Submittal Procedures. Submit site-specific Health and Safety Plan: Within 7 days after date of Notice to Proceed and prior to commencement of Work. Health and Safety Plan must include: .1 Results of site specific safety hazard assessment. .2 Results of safety and health risk or hazard analysis for site tasks and operation found in work plan. Submit two copies of Contractor's authorized representative's work site health and safety inspection reports to Departmental Representative and authority having jurisdiction, daily weekly. Submit copies of reports or directions issued by Federal, Provincial and Territorial health and safety inspectors. Submit copies of incident and accident reports. Submit WHMIS MSDS - Material Safety Data Sheets in accordance with Section 01 47 15 - Sustainable Requirements: Construction and Section 02 81 01 Hazardous Materials. Departmental Representative will review Contractor's site-specific Health and Safety Plan and provide comments to Contractor within 7 days after receipt of plan. Revise plan as appropriate and resubmit plan to Departmental Representative within 7 day s after receipt of comments from Departmental Representative. Departmental Representative's review of Contractor's final Health and Safety plan should not be construed as approval and does not reduce the Contractor's overall responsibility for construction Health and

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

.3

.4

.5 .6

.7

.8

Project No. R.050134.002

HEALTH AND SAFETY REQUIREMENTS


Safety.

Sect 01 35 29.06 Page 2

.9

Medical Surveillance: where prescribed by legislation, regulation or safety program, submit certification of medical surveillance for site personnel prior to commencement of Work, and submit additional certifications for any new site personnel to Departmental Representative.

1.4 FILING OF NOTICE

.1

File Notice of Project with Provincial authorities prior to beginning of Work.

1.5 SAFETY ASSESSMENT

.1

Perform site specific safety hazard assessment related to project.

1.6 MEETINGS

.1

Schedule and administer Health and Safety meeting with Departmental Representative prior to commencement of Work.

1.7 PROJECT/SITE CONDITIONS

.1

Work at site will involve contact with: .1 Not used

1.8 GENERAL REQUIREMENTS

.1

Develop written site-specific Health and Safety Plan based on hazard assessment prior to beginning site Work and continue to implement, maintain, and enforce plan until final demobilization from site. Health and Safety Plan must address project specifications. Departmental Representative may respond in writing, where deficiencies or concerns are noted and may request re-submission with correction of deficiencies or concerns.

.2

1.9 RESPONSIBILITY

.1

Be responsible for health and safety of persons on site, safety of property on site and for protection of persons adjacent to site and environment to extent that they may be affected by conduct of Work. Comply with and enforce compliance by employees with safety requirements of Contract Documents, applicable federal, provincial, territorial and local statutes, regulations, and ordinances, and with site-specific Health and Safety Plan.

.2

Project No. R.050134.002

HEALTH AND SAFETY REQUIREMENTS

Sect 01 35 29.06 Page 3

1.10 COMPLIANCE REQUIREMENTS

.1

Comply with Ontario Health and Safety Act, R.S.O.

.2

Comply with Canada Labour Code, Canada Occupational Safety and Health Regulations.

1.11 UNFORSEEN HAZARDS

.1

When unforeseen or peculiar safety-related factor, hazard, or condition occur during performance of Work, follow procedures in place for Employee's Right to Refuse Work in accordance with Acts and Regulations of Province having jurisdiction and advise Departmental Representative verbally and in writing.

1.12 HEALTH AND SAFETY CO-ORDINATOR

.1

Employ and assign to Work, competent and authorized representative as Health and Safety Co-ordinator. Health and Safety Co-ordinator must: .1 Be responsible for completing Contractor's Health and Safety Training Sessions and ensuring that personnel not successfully completing required training are not permitted to enter site to perform Work. .2 Be responsible for implementing, enforcing daily and monitoring site-specific Contractor's Health and Safety Plan. .3 Be on site during execution of Work and report directly to and be under direction of site supervisor.

1.13 POSTING OF DOCUMENTS

.1

Ensure applicable items, articles, notices and orders are posted in conspicuous location on site in accordance with Acts and Regulations of Province having jurisdiction, and in consultation with Departmental Representative. Immediately address health and safety non-compliance issues identified by authority having jurisdiction or by Departmental Representative. Provide Departmental Representative with written report of action taken to correct non-compliance of health and safety issues identified. Departmental Representative may stop Work if non-compliance of health and safety regulations is not corrected. Use powder actuated devices only after receipt of written permission from Departmental Representative DCC Representative Consultant.

1.14 CORRECTION OF NON-COMPLIANCE

.1

.2

.3

1.15 POWDER ACTUATED DEVICES

.1

Project No. R.050134.002

HEALTH AND SAFETY REQUIREMENTS

Sect 01 35 29.06 Page 4

1.16 WORK STOPPAGE

.1

Give precedence to safety and health of public and site personnel and protection of environment over cost and schedule considerations for Work.

PART 2 - PRODUCTS 2.1 NOT USED


.1 Not used.

PART 3 - EXECUTION 3.1 NOT USED


.1 Not used.

Project No. R.050134.002

COMMON PRODUCT REQUIREMENTS

Section 01 61 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 01 00 10 - General Instructions.

1.2 REFERENCES

.1

Within text of each specifications section, reference may be made to reference standards. Conform to these reference standards, in whole or in part as specifically requested in specifications. If there is question as to whether products or systems are in conformance with applicable standards, Departmental Representative reserves right to have such products or systems tested to prove or disprove conformance. Cost for such testing will be born by Departmental Representative in event of conformance with Contract Documents or by Contractor in event of non-conformance. Products, materials, equipment and articles incorporated in Work shall be new, not damaged or defective, and of best quality for purpose intended. If requested, furnish evidence as to type, source and quality of products provided. Procurement policy is to acquire, in cost effective manner, items containing highest percentage of recycled and recovered materials practicable consistent with maintaining satisfactory levels of competition. Make reasonable efforts to use recycled and recovered materials and in otherwise utilizing recycled and recovered materials in execution of work. Defective products, whenever identified prior to completion of Work, will be rejected, regardless of previous inspections. Inspection does not relieve responsibility, but is precaution against oversight or error. Remove and replace defective products at own expense and be responsible for delays and expenses caused by rejection. Should disputes arise as to quality or fitness of products, decision rests strictly with Departmental Representative based upon requirements of Contract Documents. Unless otherwise indicated in specifications, maintain

.2

.3

.4

1.3 QUALITY

.1

.2

.3

.4

.5

Project No. R.050134.002

COMMON PRODUCT REQUIREMENTS

Section 01 61 00 Page 2

uniformity of manufacture for any particular or like item throughout building. .6 Permanent labels, trademarks and nameplates on products are not acceptable in prominent locations, except where required for operating instructions, or when located in mechanical or electrical rooms. Handle and store products in manner to prevent damage, adulteration, deterioration and soiling and in accordance with manufacturer's instructions when applicable. Store packaged or bundled products in original and undamaged condition with manufacturer's seal and labels intact. Do not remove from packaging or bundling until required in Work. Store products subject to damage from weather in weatherproof enclosures. Store cementitious products clear of earth or concrete floors, and away from walls. Keep sand, when used for grout or mortar materials, clean and dry. Store sand on wooden platforms and cover with waterproof tarpaulins during inclement weather. Store sheet materials and lumber on flat, solid supports and keep clear of ground. Store and mix paints in heated and ventilated room. Remove oily rags and other combustible debris from site daily. Take every precaution necessary to prevent spontaneous combustion. Remove and replace damaged products at own expense and to satisfaction of Departmental Representative. Touch-up damaged factory finished surfaces to Departmental Representative's satisfaction. Use touch-up materials to match original. Do not paint over name plates. Pay costs of transportation of products required in performance of Work. Transportation cost of products supplied by Owner will be paid for by Departmental Representative. Unload, handle and store such products. Unless otherwise indicated in specifications, install or erect products in accordance with manufacturer's instructions. Do not rely on labels or enclosures provided with products. Obtain written instructions

1.4 STORAGE, HANDLING AND PROTECTION

.1

.2

.3

.4

.5

.6

.7

.8

.9

1.5 TRANSPORTATION

.1

.2

1.6 MANUFACTURER'S INSTRUCTIONS

.1

Project No. R.050134.002

COMMON PRODUCT REQUIREMENTS

Section 01 61 00 Page 3

directly from manufacturers. .2 Notify Departmental Representative in writing, of conflicts between specifications and manufacturer's instructions, so that Departmental Representative will establish course of action. Improper installation or erection of products, due to failure in complying with these requirements, authorizes Departmental Representative to require removal and re-installation at no increase in Contract Price or Contract Time. Ensure Quality of Work is of highest standard, executed by workers experienced and skilled in respective duties for which they are employed. Immediately notify Departmental Representative if required Work is such as to make it impractical to produce required results. Do not employ anyone unskilled in their required duties. Departmental Representative reserves right to require dismissal from site, workers deemed incompetent or careless. Decisions as to standard or fitness of Quality of Work in cases of dispute rest solely with Departmental Representative, whose decision is final. Ensure co-operation of workers in laying out Work. Maintain efficient and continuous supervision. Be responsible for coordination and placement of openings, sleeves and accessories. In finished areas conceal pipes, ducts and wiring in floors, walls and ceilings, except where indicated otherwise. Before installation inform Departmental Representative if there is interference. Install as directed by Departmental Representative.

.3

1.7 QUALITY OF WORK

.1

.2

.3

1.8 CO-ORDINATION

.1

.2

1.9 CONCEALMENT

.1

.2

1.10 REMEDIAL WORK .1 Perform remedial work required to repair or replace parts or portions of Work identified as defective or unacceptable. Co-ordinate adjacent affected Work as required. Perform remedial work by specialists familiar with materials affected. Perform in a manner to neither damage nor put at risk any portion of Work. Consider location of fixtures, outlets, and mechanical and electrical items indicated as approximate.

.2

1.11 LOCATION OF FIXTURES

.1

Project No. R.050134.002

COMMON PRODUCT REQUIREMENTS

Section 01 61 00 Page 4

.2

Inform Departmental Representative of conflicting installation. Install as directed. Provide metal fastenings and accessories in same texture, colour and finish as adjacent materials, unless indicated otherwise. Prevent electrolytic action between dissimilar metals and materials. Use non-corrosive hot dip galvanized steel fasteners and anchors for securing exterior work, unless stainless steel or other material is specifically requested in affected specification Section. Space anchors within individual load limit or shear capacity and ensure they provide positive permanent anchorage. Wood, or any other organic material plugs are not acceptable. Keep exposed fastenings to a minimum, space evenly and install neatly. Fastenings which cause spalling or cracking of material to which anchorage is made are not acceptable. Use fastenings of standard commercial sizes and patterns with material and finish suitable for service. Use heavy hexagon heads, semi-finished unless otherwise specified. Use No. 304 stainless steel for exterior areas. Bolts may not project more than one diameter beyond nuts. Use plain type washers on equipment, sheet metal and soft gasket lock type washers where vibrations occur. Use resilient washers with stainless steel. Prevent overloading of parts of building. Do not cut, drill or sleeve load bearing structural member, unless specifically indicated without written approval of Departmental Representative. When breaking into or connecting to existing services or utilities, execute Work at times directed by local governing authorities, with minimum of disturbance to Work, and/or building occupants. Protect, relocate or maintain existing active services. When services are encountered, cap off in manner approved by authority having jurisdiction. Stake and record location of capped service.

1.12 FASTENINGS

.1

.2

.3

.4

.5

.6

1.13 FASTENINGS EQUIPMENT

.1

.2

.3

.4

1.14 PROTECTION OF WORK IN PROGRESS

.1

1.15 EXISTING UTILITIES

.1

.2

Project No. R.050134.002

COMMON PRODUCT REQUIREMENTS

Section 01 61 00 Page 5

PART 2 - PRODUCTS 2.1 NOT USED PART 3 - EXECUTION 3.1 NOT USED
.1 Not Used. .1 Not Used.

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 1

PART 1 - GENERAL

1.1 WASTE MANAGEMENT GOALS

.1

Prior to start of Work conduct meeting with Departmental Representative to review and discuss PWGSC's Waste Management Plan and Goals. PWGSC's Waste Management Goal 75 percent of total Project Waste to be diverted from landfill sites. Provide Departmental Representative documentation certifying that waste management, recycling, reuse of recyclable and reusable materials have been extensively practiced. Accomplish maximum control of solid construction waste. Preserve environment and prevent pollution and environment damage.

.2

.3

.4

1.2 RELATED REQUIREMENTS 1.3 REFERENCES

.1

Section 01 00 10 - General Instructions.

.1

LEED Canadian Green Building Council (CGBC), Green Building Rating System, For New Construction and Major Renovations LEED Canada-NC, Version 1.0 December 2004. Class III: non-hazardous waste - construction renovation and demolition waste. Cost/Revenue Analysis Workplan (CRAW): based on information from WRW, and intended as financial tracking tool for determining economic status of waste management practices. Demolition Waste Audit (DWA): relates to actual waste generated from project. Inert Fill: inert waste - exclusively asphalt and concrete. Materials Source Separation Program (MSSP): consists of series of ongoing activities to separate reusable and recyclable waste material into material categories from other types of waste at point of generation. Recyclable: ability of product or material to be recovered at end of its life cycle and re-manufactured into new product for reuse.

1.4 DEFINITIONS

.1

.2

.3

.4

.5

.6

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 2

.7

Recycle: process by which waste and recyclable materials are transformed or collected for purpose of being transferred into new products. Recycling: process of sorting, cleansing, treating and reconstituting solid waste and other discarded materials for purpose of using in altered form. Recycling does not include burning, incinerating, or thermally destroying waste. Reuse: repeated use of product in same form but not necessarily for same purpose. Reuse includes: .1 Salvaging reusable materials from re-modelling projects, before demolition stage, for resale, reuse on current project or for storage for use on future projects. .2 Returning reusable items including pallets or unused products to vendors. Salvage: removal of structural and non-structural materials from deconstruction/disassembly projects for purpose of reuse or recycling. Separate Condition: refers to waste sorted into individual types. Source Separation: acts of keeping different types of waste materials separate beginning from first time they became waste. Waste Audit (WA): detailed inventory of materials in building. Involves quantifying by volume/weight amounts of materials and wastes generated during construction, demolition, deconstruction, or renovation project. Indicates quantities of reuse, recycling and landfill. Refer to Schedule A. Waste Management Co-ordinator (WMC) : contractor representative responsible for supervising waste management activities as well as coordinating related, required submittal and reporting requirements. Waste Reduction Workplan (WRW): written report which addresses opportunities for reduction, reuse, or recycling of materials. Refer to Schedule B. WRW is based on information acquired from WA (Schedule A).

.8

.9

.10

.11

.12

.13

.14

.15

1.5 DOCUMENTS

.1

Maintain at job site, one copy of following documents: .1 Waste Audit. .2 Waste Reduction Workplan. .3 Material Source Separation Plan. .4 Schedules A, B and C completed for project.

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 3

1.6 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submittals in accordance with Section 01 33 00 Submittal Procedures. Prepare and submit following prior to project start-up: .1 Submit 2 copies of completed Waste Audit (WA): Schedule A. .2 Submit 2 copies of completed Waste Reduction Workplan (WRW): Schedule B. .3 Submit 2 copies of completed Demolition Waste Audit (DWA): Schedule C. Submit before final payment summary of waste materials salvaged for reuse, recycling or disposal by project using deconstruction/disassembly material audit form. .1 Failure to submit could result in hold back of final payment. .2 Provide receipts, scale tickets, waybills, and show quantities and types of materials reused, recycled or disposed of. .3 For each material reused, sold or recycled from project, include amount quantities by number, type and size of items and the destination. .4 For each material land filled or incinerated from project, include amount of material and identity of landfill, incinerator or transfer station. Conduct WA prior to project start-up. Prepare WA: Schedule A. Record, on WA - Schedule A, extent to which materials or products used consist of recycled or reused materials or products. Prepare WRW prior to project start-up. WRW should include but not limited to: .1 Destination of materials listed. .2 Deconstruction/disassembly techniques and sequencing. .3 Schedule for deconstruction/disassembly. .4 Location. .5 Security. .6 Protection. .7 Clear labelling of storage areas. .8 Details on materials handling and removal procedures. .9 Quantities for materials to be salvaged for reuse or recycled and materials sent to landfill. Structure WRW to prioritize actions and follow 3R's hierarchy, with Reduction as first priority, followed by Reuse, then Recycle. Describe management of waste.

.2

.3

1.7 WASTE AUDIT (WA)

.1 .2 .3

1.8 WASTE REDUCTION WORKPLAN (WRW)

.1 .2

.3

.4

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 4

.5

Identify opportunities for reduction, reuse, and recycling of materials. Based on information acquired from WA. Post WRW or summary where workers at site are able to review content. Set realistic goals for waste reduction, recognize existing barriers and develop strategies to overcome these barriers. Monitor and report on waste reduction by documenting total volume and cost of actual waste removed from project. Prepare DWA prior to project start-up. Complete DWA: Schedule C. Provide inventory of quantities of materials to be salvaged for reuse, recycling, or disposal. Store, materials to be reused, recycled and salvaged in locations as directed by Departmental Representative . Unless specified otherwise, materials for removal become Contractor's property. Protect, stockpile, store and catalogue salvaged items. Separate non-salvageable materials from salvaged items. Transport and deliver non-salvageable items to licensed disposal facility. Protect structural components not removed for demolition from movement or damage. Support affected structures. If safety of building is endangered, cease operations and immediately notify Departmental Representative. Protect surface drainage, mechanical and electrical from damage and blockage. Separate and store materials produced during dismantling of structures in designated areas. Prevent contamination of materials to be salvaged and recycled and handle materials in accordance with requirements for acceptance by designated facilities. .1 On-site source separation is recommended. .2 Remove co-mingled materials to off-site processing facility for separation. .3 Provide waybills for separated materials.

.6

.7

.8

1.9 DEMOLITION WASTE AUDIT (DWA)

.1 .2 .3

1.10 STORAGE, HANDLING AND PROTECTION

.1

.2

.3

.4

.5

.6

.7

.8

.9

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 5

1.11 DISPOSAL OF WASTES

.1 .2

Do not bury rubbish or waste materials. Do not dispose of waste, volatile materials, mineral spirits, oil, paint thinner into waterways, storm, or sanitary sewers. Keep records of construction waste including: .1 Number and size of bins. .2 Waste type of each bin. .3 Total tonnage generated. .4 Tonnage reused or recycled. .5 Reused or recycled waste destination. Remove materials from deconstruction as deconstruction/disassembly Work progresses. Prepare project summary to verify destination and quantities on a material-by-material basis as identified in pre-demolition material audit. Execute work with least possible interference or disturbance to normal use of premises.

.3

.4

.5

1.12 USE OF SITE AND FACILITIES

.1

1.13 SCHEDULING

.1

Co-ordinate Work with other activities at site to ensure timely and orderly progress of Work.

PART 2 - PRODUCTS

2.1 NOT USED

.1

Not Used.

PART 3 - EXECUTION

3.1 APPLICATION

.1 .2

Do Work in compliance with WRW. Handle waste materials not reused, salvaged, or recycled in accordance with appropriate regulations and codes. Remove tools and waste materials on completion of Work, and leave work area in clean and orderly condition. Clean-up work area as work progresses. Source separate materials to be reused/recycled into specified sort areas.

3.2 CLEANING

.1

.2 .3

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 6

3.3 DIVERSION OF MATERIALS

.1

From following list, separate materials from general waste stream and stockpile in separate piles or containers, as reviewed by Departmental Representative , and consistent with applicable fire regulations. .1 Mark containers or stockpile areas. .2 Provide instruction on disposal practices. On-site sale of salvaged, recovered, reusable, recyclable materials is not permitted. Demolition Waste: Recommended Diversion % 50 100 100 80 100 80 100 100 100 100 Actual Diversion %

.2

.3

Material Type Acoustic Tile Acoustical Insulation Carpet De-mountable Partitions Doors and Frames Electrical Equipment Furnishings Mechanical Equipment Metals Wood (uncontaminated) Other

.4

Construction Waste: Recommended Diversion % 100 100 100 100 100 Actual Diversion %

Material Type Cardboard Plastic Packaging Rubble Steel Wood (uncontaminated) Other

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 7

3.4 WASTE AUDIT (WA)

.1

Schedule A - Waste Audit (WA):

(1) Material Category Wood and Plastics Off-cuts Warpet Pallet Forms Plastic Packaging Cardboard Packaging Other Doors and Windows Painted Frames Glass Wood Metal Other

(2) Material Quantity

(3) Estimated Wasted

(4) Total Quantity (unit)

(5) Generation Point

(6) % Recycled

(7) % Resused

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL


Schedule B:

Section 01 74 21 Page 8

3.5 WASTE REDUCTION WORKPLAN (WRW)

.1

(1) Material Category

(2) Person(s) Responsible

(3) Total Quantity Waste (unit)

(4) Reused Amount (units) Projected

Actual

(5) Actual Recycled Amount (unit) Projected

Actual

(6) Material(s) Destination

Wood and Plastics Off-cuts Warpet Pallet Forms Plastic Packaging Cardboard Packaging Other Doors and Windows Painted Frames Glass Wood Metal Other

Project No. R.050134.002

CONSTRUCTION/DEMOLITION WASTE MANAGEMENT AND DISPOSAL

Section 01 74 21 Page 9

3.6 DEMOLITION WASTE AUDIT (DWA)


(1) Material Category Wood and Plastics Off-cuts Warpet Pallet Forms Plastic Packaging Cardboard Packaging Other Doors and Windows Painted Frames Glass Wood Metal Other

.1

Schedule C - Demolition Waste Audit (DWA):

(2) Quantity

(3) Total

(4) Volume (cum)

(5) Weight (cum)

(6) Remarks & Assumptions

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 01 00 10 - General Instructions.

1.2 REFERENCES

.1

Canadian Environmental Protection Act (CEPA) .1 SOR/2008-197, Storage Tank Systems for Petroleum Products and Allied Petroleum Products Regulations.

1.3 ADMINISTRATIVE REQUIREMENTS

.1

Pre-warranty Meeting: .1 Convene meeting one week prior to contract completion with Departmental Representative, in accordance with to: .1 Verify Project requirements. .2 Review manufacturer's installation instructions and warranty requirements. .2 Departmental Representative to establish communication procedures for: .1 Notifying construction warranty defects. .2 Determine priorities for type of defects. .3 Determine reasonable response time. .3 Contact information for bonded and licensed company for warranty work action: provide name, telephone number and address of company authorized for construction warranty work action. .4 Ensure contact is located within local service area of warranted construction, is continuously available, and is responsive to inquiries for warranty work action.

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Two weeks prior to Substantial Performance of the Work, submit to the Departmental Representative , four final copies of operating and maintenance manuals in English. Provide spare parts, maintenance materials and special tools of same quality and manufacture as products provided in Work. Provide evidence, if requested, for type, source and quality of products supplied. Organize data as instructional manual. Binders: vinyl, hard covered, 3 'D' ring, loose leaf

.2

.3

.4

1.5 FORMAT

.1 .2

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 2

219 x 279 mm with spine and face pockets. .3 When multiple binders are used correlate data into related consistent groupings. .1 Identify contents of each binder on spine. Cover: identify each binder with type or printed title 'Project Record Documents'; list title of project and identify subject matter of contents. Arrange content by systems, under Section numbers and sequence of Table of Contents. Provide tabbed fly leaf for each separate product and system, with typed description of product and major component parts of equipment. Text: manufacturer's printed data, or typewritten data. Drawings: provide with reinforced punched binder tab. .1 Bind in with text; fold larger drawings to size of text pages. Table of Contents for Each Volume: provide title of project; .1 Date of submission; names. .2 Addresses, and telephone numbers of Consultant and Contractor with name of responsible parties. .3 Schedule of products and systems, indexed to content of volume. .2 For each product or system: .1 List names, addresses and telephone numbers of subcontractors and suppliers, including local source of supplies and replacement parts. Product Data: mark each sheet to identify specific products and component parts, and data applicable to installation; delete inapplicable information. Drawings: supplement product data to illustrate relations of component parts of equipment and systems, to show control and flow diagrams. Maintain, at site for Departmental Representative one record copy of: .1 Contract Drawings. .2 Specifications. .3 Addenda. .4 Change Orders and other modifications to Contract. .5 Reviewed shop drawings, product data, and samples. .6 Field test records.

.4

.5

.6

.7

.8

1.6 CONTENTS PROJECT RECORD DOCUMENTS

.1

.3

.4

1.7 AS -BUILT DOCUMENTS AND SAMPLES

.1

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 3

.7 .8

Inspection certificates. Manufacturer's certificates.

.2

Store record documents and samples in field office apart from documents used for construction. .1 Provide files, racks, and secure storage. Label record documents and file in accordance with Section number listings in List of Contents of this Project Manual. .1 Label each document "PROJECT RECORD" in neat, large, printed letters. Maintain record documents in clean, dry and legible condition. .1 Do not use record documents for construction purposes. Keep record documents and samples available for inspection by Departmental Representative. Record information on set of black line opaque drawings, provided by Departmental Representative. Use felt tip marking pens, maintaining separate colours for each major system, for recording information. Record information concurrently with construction progress. .1 Do not conceal Work until required information is recorded. Contract Drawings and shop drawings: mark each item to record actual construction, including: .1 Measured depths of elements of foundation in relation to finish first floor datum. .2 Measured horizontal and vertical locations of underground utilities and appurtenances, referenced to permanent surface improvements. .3 Measured locations of internal utilities and appurtenances, referenced to visible and accessible features of construction. .4 Field changes of dimension and detail. .5 Changes made by change orders. .6 Details not on original Contract Drawings. .7 References to related shop drawings and modifications. Specifications: mark each item to record actual construction, including: .1 Manufacturer, trade name, and catalogue number of each product actually installed, particularly optional items and substitute items. .2 Changes made by Addenda and change orders.

.3

.4

.5

1.8 RECORDING INFORMATION ON PROJECT RECORD DOCUMENTS

.1

.2

.3

.4

.5

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 4

.6

Other Documents: maintain manufacturer's certifications, inspection certifications, field test records, required by individual specifications sections. Provide digital photos, if requested, for site records. For each item of equipment and each system include description of unit or system, and component parts. .1 Give function, normal operation characteristics and limiting conditions. .2 Include performance curves, with engineering data and tests, and complete nomenclature and commercial number of replaceable parts. Panel board circuit directories: provide electrical service characteristics, controls, and communications. Include installed colour coded wiring diagrams. Operating Procedures: include start-up, break-in, and routine normal operating instructions and sequences. .1 Include regulation, control, stopping, shut-down, and emergency instructions. .2 Include summer, winter, and any special operating instructions. Maintenance Requirements: include routine procedures and guide for trouble-shooting; disassembly, repair, and reassembly instructions; and alignment, adjusting, balancing, and checking instructions. Provide servicing and lubrication schedule, and list of lubricants required. Include manufacturer's printed operation and maintenance instructions. Include sequence of operation by controls manufacturer. Provide original manufacturer's parts list, illustrations, assembly drawings, and diagrams required for maintenance. Provide installed control diagrams by controls manufacturer. Provide Contractor's Design-Builder's co-ordination drawings, with installed colour coded piping diagrams. Provide charts of valve tag numbers, with location and function of each valve, keyed to flow and control diagrams.

.7

1.9 EQUIPMENT AND SYSTEMS

.1

.2

.3 .4

.5

.6

.7

.8

.9

.10

.11

.12

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 5

.13

Provide list of original manufacturer's spare parts, current prices, and recommended quantities to be maintained in storage. Include test and balancing reports as specified.

.14

.15

Additional requirements: as specified in individual specification sections. Building products, applied materials, and finishes: include product data, with catalogue number, size, composition, and colour and texture designations. .1 Provide information for re-ordering custom manufactured products. Instructions for cleaning agents and methods, precautions against detrimental agents and methods, and recommended schedule for cleaning and maintenance. Moisture-protection and weather-exposed products: include manufacturer's recommendations for cleaning agents and methods, precautions against detrimental agents and methods, and recommended schedule for cleaning and maintenance. Additional requirements: as specified in individual specifications sections. Spare Parts: .1 Provide spare parts, in quantities specified in individual specification sections. .2 Provide items of same manufacture and quality as items in Work. .3 Deliver to site; place and store. .4 Receive and catalogue items. .1 Submit inventory listing to Departmental Representative. .2 Include approved listings in Maintenance Manual. Obtain receipt for delivered products and submit .5 prior to final payment.

1.10 MATERIALS AND FINISHES

.1

.2

.3

.4

1.11 MAINTENANCE MATERIALS

.1

.2

Extra Stock Materials: .1 Provide maintenance and extra materials, in quantities specified in individual specification sections. .2 Provide items of same manufacture and quality as items in Work. .3 Deliver to site; place and store. .4 Receive and catalogue items. .1 Submit inventory listing to Departmental Representative. .2 Include approved listings in Maintenance Manual.

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 6

.5 Obtain receipt for delivered products and submit prior to final payment. .3 Special Tools: .1 Provide special tools, in quantities specified in individual specification section. .2 Provide items with tags identifying their associated function and equipment. .3 Deliver to site; place and store. .4 Receive and catalogue items. .1 Submit inventory listing to Departmental Representative. .2 Include approved listings in Maintenance Manual. Store spare parts, maintenance materials, and special tools in manner to prevent damage or deterioration. Store in original and undamaged condition with manufacturer's seal and labels intact. Store components subject to damage from weather in weatherproof enclosures. Store paints and freezable materials in a heated and ventilated room. Remove and replace damaged products at own expense and for review by Departmental Representative. Develop warranty management plan to contain information relevant to Warranties. Submit warranty management plan, 30 days before planned pre-warranty conference, to Departmental Representative approval. Warranty management plan to include required actions and documents to assure that Departmental Representative receives warranties to which it is entitled. Provide plan in narrative form and contain sufficient detail to make it suitable for use by future maintenance and repair personnel. Submit, warranty information made available during construction phase, to Departmental Representative for approval prior to each monthly pay estimate. Assemble approved information in binder, submit upon acceptance of work and organize binder as follows: .1 Separate each warranty or bond with index tab sheets keyed to Table of Contents listing. .2 List subcontractor, supplier, and manufacturer, with name, address, and telephone number of responsible

1.12 DELIVERY, STORAGE AND HANDLING

.1

.2

.3

.4

.5

1.13 WARRANTIES AND BONDS

.1

.2

.3

.4

.5

.6

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 7

principal. .3 Obtain warranties and bonds, executed in duplicate by subcontractors, suppliers, and manufacturers, within ten days after completion of applicable item of work. Verify that documents are in proper form, contain .4 full information, and are notarized. .5 Co-execute submittals when required. .6 Retain warranties and bonds until time specified for submittal. .7 Except for items put into use with Owner's permission, leave date of beginning of time of warranty until Date of Substantial Performance is determined. Conduct joint 4 month and 9 month warranty inspection, measured from time of acceptance, by Departmental Representative . Include information contained in warranty management plan as follows: .1 Roles and responsibilities of personnel associated with warranty process, including points of contact and telephone numbers within the organizations of Contractors, subcontractors, manufacturers or suppliers involved. .2 Listing and status of delivery of Certificates of Warranty for extended warranty items, to include HVAC balancing, pumps, motors, transformers, and commissioned systems such as fire protection, alarm systems, sprinkler systems, lightning protection systems,. .3 Provide list for each warranted equipment, item, feature of construction or system indicating: .1 Name of item. .2 Model and serial numbers. .3 Location where installed. .4 Name and phone numbers of manufacturers or suppliers. .5 Names, addresses and telephone numbers of sources of spare parts. .6 Warranties and terms of warranty: include one-year overall warranty of construction. Indicate items that have extended warranties and show separate warranty expiration dates. .7 Cross-reference to warranty certificates as applicable. .8 Starting point and duration of warranty period. .9 Summary of maintenance procedures required to continue warranty in force. .10 Cross-Reference to specific pertinent Operation and Maintenance manuals. Organization, names and phone numbers of .11 persons to call for warranty service. .12 Typical response time and repair time

.8

.9

Project No. R.050134.002

CLOSEOUT SUBMITTALS

Section 01 78 00 Page 8

expected for various warranted equipment. .4 Contractor's plans for attendance at 4 and 9 month post-construction warranty inspections. .5 Procedure and status of tagging of equipment covered by extended warranties. Post copies of instructions near selected pieces .6 of equipment where operation is critical for warranty and/or safety reasons. .10 Respond in timely manner to oral or written notification of required construction warranty repair work. Written verification to follow oral instructions. .1 Failure to respond will be cause for the Departmental Representative to proceed with action against Contractor. Tag, at time of installation, each warranted item. Provide durable, oil and water resistant tag approved by Departmental Representative. Attach tags with copper wire and spray with waterproof silicone coating. Leave date of acceptance until project is accepted for occupancy. Indicate following information on tag: .1 Type of product/material. .2 Model number. .3 Serial number. .4 Contract number. .5 Warranty period. .6 Inspector's signature. .7 Construction Contractor.

.11

1.14 WARRANTY TAGS

.1

.2

.3

.4

PART 2 - PRODUCTS

2.1 NOT USED

.1

Not Used.

PART 3 - EXECUTION

3.1 NOT USED

.1

Not Used.

Project No. R.050134.002

BLANKET INSULATION

Section 07 21 16 Page 1

PART 1 - GENERAL 1.1 RELATED REQUIREMENTS


.1 .2 Section 09 21 16 - Gypsum Board Assemblies. Section 09 22 16 - Non-structural Metal Framing.

1.2 REFERENCES

.1

American Society for Testing and Materials International (ASTM) .1 ASTM C 553-02, Specification for Mineral Fibre Blanket Thermal Insulation for Commercial and Industrial Applications. .2 ASTM C 1320-05, Standard Practice for Installation of Mineral Fiber Batt and Blanket Thermal Insulation for Light Frame Construction. Canadian Standards Association (CSA International) .1 CSA B111-1974(R2003), Wire Nails, Spikes and Staples. Underwriters Laboratories of Canada (ULC) .1 CAN/ULC-S702-1997, Standard for Mineral Fibre Insulation. Product Data: .1 Submit manufacturer's printed product literature, specifications and data sheet in accordance with Section 01 33 00 - Submittal Procedures. Manufacturer's Instructions: .1 Submit manufacturer's installation instructions. Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management And Disposal. Remove from site and dispose of packaging materials at appropriate recycling facilities. Collect and separate for disposal paper, plastic, polystyrene, corrugated cardboard packaging material in appropriate on-site for recycling in accordance with Waste Management Plan.

.2

.3

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

1.4 WASTE MANAGEMENT AND DISPOSAL

.1

.2

.3

PART 2 - PRODUCTS 2.1 INSULATION


.1 Batt and blanket mineral fibre: to ASTM C 553, ASTM C 665 and CAN/ULC S702. .1 Type: 1.

Project No. R.050134.002

BLANKET INSULATION

Section 07 21 16 Page 2

.2

Thickness: as indicated.

2.2 ACCESSORIES

.1

Insulation clips: Impale type, perforated 50 x 50 mm cold rolled .1 carbon steel 0.8 mm thick, adhesive back, spindle of 2.5 mm diameter annealed steel, length to suit insulation, 25 mm diameter washers of self locking type. Nails: galvanized steel, length to suit insulation plus 25 mm, to CSA B111. Staples: 12 mm minimum leg. Tape: as recommended by manufacturer.

.2

.3 .4

PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS


.1 Compliance: comply with manufacturer's written data, including product technical bulletins, product catalogue installation instructions, product carton installation instructions, and data sheets. Install insulation to maintain continuity of thermal protection to building elements and spaces and to ASTM C 1320. Fit insulation closely around electrical boxes, pipes, ducts, frames and other objects in or passing through insulation. Do not compress insulation to fit into spaces. Keep insulation minimum 75 mm from heat emitting devices such as recessed light fixtures. Do not enclose insulation until it has been inspected and approved by Departmental Representative. Upon completion of installation, remove surplus materials, rubbish, tools and equipment barriers.

3.2 INSULATION INSTALLATION

.1

.2

.3 .4

.5

3.3 CLEANING

.1

Project No. R.050134.002

JOINT SEALANTS

Section 07 92 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1

Section 09 21 16 - Gypsum Board Assemblies.

1.2 REFERENCES

.1

ASTM International .1 ASTM C 919-08, Standard Practice for Use of Sealants in Acoustical Applications. Canadian General Standards Board (CGSB) .1 CGSB 19-GP-5M-1984, Sealing Compound, One Component, Acrylic Base, Solvent Curing (Issue of 1976 reaffirmed, incorporating Amendment No. 1). .2 CAN/CGSB-19.13-M87, Sealing Compound, One-component, Elastomeric, Chemical Curing. .3 CGSB 19-GP-14M-1984, Sealing Compound, One Component, Butyl-Polyisobutylene Polymer Base, Solvent Curing (Reaffirmation of April 1976). .4 CAN/CGSB-19.17-M90, One-Component Acrylic Emulsion Base Sealing Compound. .5 CAN/CGSB-19.24-M90, Multi-component, Chemical Curing Sealing Compound. General Services Administration (GSA) - Federal Specifications (FS) .1 FS-SS-S-200-E(2)1993, Sealants, Joint, Two-Component, Jet-Blast-Resistant, Cold Applied, for Portland Cement Concrete Pavement. Health Canada/Workplace Hazardous Materials Information System (WHMIS) .1 Material Safety Data Sheets (MSDS). South Coast Air Quality Management District (SCAQMD), California State, Regulation XI. Source Specific Standards .1 SCAQMD Rule 1168-A2005, Adhesives and Sealants Applications. Submit in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for joint sealants and include product characteristics, performance criteria, physical size, finish and limitations. .2 Manufacturer's product to describe: .1 Caulking compound. .2 Primers.

.2

.3

.4

.5

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

Project No. R.050134.002

JOINT SEALANTS

Section 07 92 00 Page 2

.3 Sealing compound, each type, including compatibility when different sealants are in contact with each other. .3 Submit 2 copies of WHMIS MSDS in accordance with Section 01 35 29.06 - Health and Safety Requirements. .3 Samples: .1 Submit 2 samples of each type of material and colour. .2 Cured samples of exposed sealants for each colour where required to match adjacent material. Manufacturer's Instructions: .1 Submit instructions to include installation instructions for each product used. Submit in accordance with Section 01 78 00 - Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for incorporation into manual. Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Storage and Handling Requirements: .1 Store materials indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect joint sealants from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new.

.4

1.4 CLOSEOUT SUBMITTALS

.1

.2

1.5 DELIVERY, STORAGE AND HANDLING

.1

.2

.3

1.6 SITE CONDITIONS

.1

Ambient Conditions: .1 Proceed with installation of joint sealants only when: .1 Ambient and substrate temperature conditions are within limits permitted by joint sealant manufacturer or are above 4.4 degrees C. .2 Joint substrates are dry. .3 Conform to manufacturer's recommended temperatures, relative humidity, and substrate moisture content for application and curing of sealants including special conditions governing use. Joint-Width Conditions: .1 Proceed with installation of joint sealants only

.2

Project No. R.050134.002

JOINT SEALANTS

Section 07 92 00 Page 3

where joint widths are more than those allowed by joint sealant manufacturer for applications indicated. .3 Joint-Substrate Conditions: .1 Proceed with installation of joint sealants only after contaminants capable of interfering with adhesion are removed from joint substrates. Comply with requirements of Workplace Hazardous Materials Information System (WHMIS) regarding use, handling, storage, and disposal of hazardous materials; and regarding labelling and provision of Material Safety Data Sheets (MSDS) acceptable to Health Canada. Departmental Representative will arrange for ventilation system to be operated on maximum outdoor air and exhaust during installation of caulking and sealants. Ventilate area of work as directed by Departmental Representative by use of approved portable supply and exhaust fans.

1.7 ENVIRONMENTAL REQUIREMENTS

.1

.2

PART 2 - PRODUCTS 2.1 SEALANT MATERIALS


.1 Do not use caulking that emits strong odours, contains toxic chemicals or is not certified as mould resistant in air handling units. When low toxicity caulks are not possible, confine usage to areas which off gas to exterior, are contained behind air barriers, or are applied several months before occupancy to maximize off gas time. Where sealants are qualified with primers use only these primers.

.2

.3

2.2 SEALANT MATERIAL DESIGNATIONS

.1 .2

Acrylic latex one part: to CAN/CGSB-19.17. Acoustical sealant: to ASTM C 919.

2.3 SEALANT SELECTION

.1

Perimeters of interior frames, as detailed and itemized: sealant type: acrylic latex. Exposed interior control joints in drywall: sealant type: acoustical sealant. Non-corrosive and non-staining type, compatible with joint forming materials and sealant in accordance with sealant manufacturer's written recommendations.

.2

2.4 JOINT CLEANER

.1

Project No. R.050134.002

JOINT SEALANTS

Section 07 92 00 Page 4

.2

Primer: in accordance with sealant manufacturer's written recommendations.

PART 3 - EXECUTION 3.1 EXAMINATION


.1 Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for joint sealants installation in accordance with manufacturer's written instructions. .1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative. Examine joint sizes and conditions to establish correct depth to width relationship for installation of backup materials and sealants. Clean bonding joint surfaces of harmful matter substances including dust, rust, oil grease, and other matter which may impair Work. Do not apply sealants to joint surfaces treated with sealer, curing compound, water repellent, or other coatings unless tests have been performed to ensure compatibility of materials. Remove coatings as required. Ensure joint surfaces are dry and frost free. Prepare surfaces in accordance with manufacturer's directions. Where necessary to prevent staining, mask adjacent surfaces prior to priming and caulking. Prime sides of joints in accordance with sealant manufacturer's instructions immediately prior to caulking. Apply bond breaker tape where required to manufacturer's instructions. Install joint filler to achieve correct joint depth and shape, with approximately 30% compression. Mix materials in strict accordance with sealant manufacturer's instructions.

3.2 SURFACE PREPARATION

.1

.2

.3

.4 .5

3.3 PRIMING

.1

.2

3.4 BACKUP MATERIAL

.1

.2

3.5 MIXING

.1

Project No. R.050134.002

JOINT SEALANTS

Section 07 92 00 Page 5

3.6 APPLICATION

.1

Sealant: .1 Apply sealant in accordance with manufacturer's written instructions. .2 Mask edges of joint where irregular surface or sensitive joint border exists to provide neat joint. .3 Apply sealant in continuous beads. .4 Apply sealant using gun with proper size nozzle. .5 Use sufficient pressure to fill voids and joints solid. .6 Form surface of sealant with full bead, smooth, free from ridges, wrinkles, sags, air pockets, embedded impurities. .7 Tool exposed surfaces before skinning begins to give slightly concave shape. .8 Remove excess compound promptly as work progresses and upon completion. Curing: .1 Cure sealants in accordance with sealant manufacturer's instructions. .2 Do not cover up sealants until proper curing has taken place. Progress Cleaning: .1 Leave Work area clean at end of each day. .2 Clean adjacent surfaces immediately. .3 Remove excess and droppings, using recommended cleaners as work progresses. .4 Remove masking tape after initial set of sealant. Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment. Protect installed products and components from damage during construction. Repair damage to adjacent materials caused by joint sealants installation.

.2

3.7 CLEANING

.1

.2

3.8 PROTECTION

.1

.2

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2

Section 08 14 16 - Flush Wood Doors. Section 08 71 00 Door Hardware.

1.2 REFERENCES

.1

American Society for Testing and Materials International (ASTM) .1 ASTM A 653/A 653M-06a, Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process. .2 ASTM B 29-03, Standard Specification for Refined Lead. .3 ASTM B 749-03, Standard Specification for Lead and Lead Alloy Strip, Sheet and Plate Products. Canada Green Building Council (CaGBC) .1 LEED Canada-NC Version 1.0-2004, LEED (Leadership in Energy and Environmental Design): Green Building Rating System Reference Package For New Construction and Major Renovations (including Addendum 2007). .2 LEED Canada-CI Version 1.0-2007, LEED (Leadership in Energy and Environmental Design): Green Building Rating System Reference Guide For Commercial Interiors. Canadian General Standards Board (CGSB) .1 CAN/CGSB-1.181-99, Ready-Mixed Organic Zinc-Rich Coating. .2 CGSB 41-GP-19Ma-84, Rigid Vinyl Extrusions for Windows and Doors. Canadian Standards Association (CSA International) .1 CSA-G40.20-04/G40.21-04, General Requirements for Rolled or Welded Structural Quality Steel/Structural Quality Steel. .2 CSA W59-03, Welded Steel Construction (Metal Arc Welding). Canadian Steel Door Manufacturers' Association (CSDMA) .1 CSDMA, Recommended Specifications for Commercial Steel Doors and Frames, 2000. CSDMA, Selection and Usage Guide for Commercial .2 Steel Doors, 1990. National Fire Protection Association (NFPA) .1 NFPA 80-13, Standard for Fire Doors and Other Opening Protectives. .2 NFPA 252-12, Fire Tests of Door Assemblies.

.2

.3

.4

.5

.6

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 2

.7

South Coast Air Quality Management District (SCAQMD), California State .1 SCAQMD Rule 1113-04, Architectural Coatings. .2 SCAQMD Rule 1168-05, Adhesives and Sealants Applications. Underwriters' Laboratories of Canada (ULC) .1 CAN/ULC-S701-01, Standard for Thermal Insulation, Polystyrene, Boards and Pipe Covering. .2 CAN/ULC-S702-97, Standard for Thermal Insulation, Mineral Fibre, for Buildings. .3 CAN/ULC-S704-03, Standard for Thermal Insulation, Polyurethane and Polyisocyanurate Boards, Faced. .4 CAN4-S104-M80, Standard Method for Fire Tests of Door Assemblies. .5 CAN4-S105-M85, Standard Specification for Fire Door Frames Meeting the Performance Required by CAN4-S104. Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Provide product data: in accordance with Section 01 33 00 - Submittal Procedures. Provide shop drawings: in accordance with Section 01 33 00 - Submittal Procedures. .1 Indicate each type of door, material, steel core thicknesses, mortises, reinforcements, location of exposed fasteners, openings, glazed, arrangement of hardware and fire rating and finishes. .2 Indicate each type frame material, core thickness, reinforcements, glazing stops, location of anchors and exposed fastenings and fire rating finishes. .3 Include schedule identifying each unit, with door marks and numbers relating to numbering on drawings and door schedule. .4 Submit test and engineering data, and installation instructions.

.8

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

.3

.4

Provide samples in accordance with Section 01 33 00 - Submittal Procedures. Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements. Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

1.4 DELIVERY, STORAGE AND HANDLING

.1

.2

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 3

PART 2 - PRODUCTS 2.1 MATERIALS


.1 Hot dipped galvanized steel sheet: to ASTM A 653M, ZF75, minimum base steel thickness in accordance with CSDMA Table 1 - Thickness for Component Parts. Reinforcement plate: to CSA G40.20/G40.21, Type 44W, coating designation to ASTM A 653M, ZF75. Reinforcement frame size: 6.4 mm x 25 mm x 925 mm steel plate centred on door strike. Composites: balance of core materials used in conjunction with lead: in accordance with manufacturers' proprietary design. Hollow steel, vertically stiffened with 0.91 mm galvanized steel interlocking "z" or "top hat" shaped stiffeners welded at 150mm o.c. Weld front skin stiffeners offset to allow for 3mm clearance of bottom stiffeners. Weld shape stiffeners to back skin and mechanically interlock with top stiffeners. Form bottom stiffener in door core a minimum of 75 mm. Fill all voids with fibrous batt insulation. Honeycomb cores and steel components: heat resistant, spray grade, resin reinforced neoprene/rubber (polychloroprene) based, low viscosity, contact cement. .1 Adhesive: maximum VOC content 50 g/L to SCAQMD Rule 1168. Polystyrene and polyurethane cores: heat resistant, epoxy resin based, low viscosity, contact cement. Lock-seam doors: fire resistant, resin reinforced polychloroprene, high viscosity, sealant/adhesive. Touch-up prime CAN/CGSB-1.181. .1 Maximum VOC limit 50 g/L to GC-03. Field paint steel doors and frames in accordance with Sections 09 91 23 - Interior Painting. Protect weatherstrips from paint. Provide final finish free of scratches or other blemishes. .1 Maximum VOC emission level 50 g/L to GS-11 to SCAQMD Rule 1113. Door silencers: single stud rubber/neoprene type. Exterior and interior top and bottom caps: rigid polyvinylchloride extrusion conforming to CGSB 41-GP-19Ma steel.

.2

.3

2.2 DOOR CORE MATERIALS

.1

2.3 ADHESIVES

.1

.2

.3

2.4 PRIMER

.1

2.5 PAINT

.1

2.6 ACCESSORIES

.1 .2

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 4

.3

Fabricate glazing stops as formed channel, minimum 16 mm height, accurately fitted, butted at corners and fastened to frame sections with counter-sunk oval head sheet metal screws. Metallic paste filler: to manufacturer's standard. Fire labels: metal riveted. Fabricate frames in accordance with CSDMA specifications. Fabricate frames to profiles and maximum face sizes as indicated. Interior frames: 1.6 mm welded type construction. Fire rating as indicated. Blank, reinforce, drill and tap frames for mortised, templated hardware, and electronic hardware using templates provided by finish hardware supplier. Reinforce frames for surface mounted hardware. Protect mortised cutouts with steel guard boxes. Prepare frame for door silencers, 3 for single door, 2 at head for double door. Manufacturer's nameplates on frames and screens are not permitted. Conceal fastenings except where exposed fastenings are indicated. Provide factory-applied touch up primer at areas where zinc coating has been removed during fabrication. Provide appropriate anchorage to floor and wall construction. Locate each wall anchor immediately above or below each hinge reinforcement on hinge jamb and directly opposite on strike jamb. Provide 2 anchors for rebate opening heights up to 1520 mm and 1 additional anchor for each additional 760 mm of height or fraction thereof. Locate anchors for frames in existing openings not more than 150 mm from top and bottom of each jambs and intermediate at 660 mm on centre maximum. Welding in accordance with CSA W59. Accurately mitre or mechanically joint frame product

.4 .5

2.7 FRAMES FABRICATION GENERAL

.1

.2

.3

.4

.5 .6

.7

.8

.9

2.8 FRAME ANCHORAGE

.1

.2

.3

.4

2.9 FRAMES: WELDED TYPE

.1 .2

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 5

and securely weld on inside of profile. .3 Cope accurately and securely weld butt joints of mullions, transom bars, centre rails and sills. Grind welded joints and corners to a flat plane, fill with metallic paste and sand to uniform smooth finish. Securely attach floor anchors to inside of each jamb profile. Weld in 2 temporary jamb spreaders per frame to maintain proper alignment during shipment. Doors: swing type, flush, with provision for glass and/or louvre openings as indicated. Interior doors: hollow steel construction. Fabricate doors with longitudinal edges welded. Seams: grind welded joints to a flat plane, fill with metallic paste filler and sand to a uniform smooth finish. Blank, reinforce, drill doors and tap for mortised, templated hardware. Factory prepare holes 12.7 mm diameter and larger except mounting and through-bolt holes, on site, at time of hardware installation. Reinforce doors where required, for surface mounted hardware. Provide inverted, recessed, spot welded channels to top and bottom of interior doors. Provide factory-applied touch-up primer at areas where zinc coating has been removed during fabrication. Provide fire labelled doors for those openings requiring fire protection ratings, as scheduled. Test such products in conformance with CAN4-S104, ASTM E 152 and NFPA 252 and list by nationally recognized agency having factory inspection service and construct as detailed in Follow-Up Service Procedures/Factory Inspection Manuals issued by listing agency to individual manufacturers. Manufacturer's nameplates on doors are not permitted.

.4

.5

.6

2.10 DOOR FABRICATION GENERAL

.1

.2 .3

.4

.5

.6

.7

.8

.9

2.11 HOLLOW STEEL CONSTRUCTION

.1

Form face sheets for interior doors from 1.6 cold rolled sheet steel. Reinforce doors with vertical stiffeners, securely welded to face sheets at 150 mm on centre maximum.

.2

Project No. R.050134.002

METAL DOORS AND FRAMES

Section 08 11 00 Page 6

.3

Fill voids between stiffeners of interior doors with fibreglass core.

PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS


.1 Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheets. Install labelled steel fire rated doors and frames to NFPA 80 except where specified otherwise. Install doors and frames to CSDMA Installation Guide. Set frames plumb, square, level and at correct elevation. Secure anchorages and connections to adjacent construction. Brace frames rigidly in position while building-in. Install temporary horizontal wood spreader at third points of door opening to maintain frame width. Provide vertical support at centre of head for openings over 1200 mm wide. Remove temporary spreaders after frames are built-in. Make allowances for deflection of structure to ensure structural loads are not transmitted to frames. Caulk perimeter of frames between frame and adjacent material. Install doors and hardware in accordance with hardware templates and manufacturer's instructions and Section 08 71 00 - Door Hardware. Provide even margins between doors and jambs and doors and finished floorand thresholds as follows. .1 Hinge side: 1.0 mm. .2 Latchside and head: 1.5 mm. .3 Finished floor: 13 mm. Adjust operable parts for correct function. Touch up with primer finishes damaged during installation. Fill exposed frame anchors and surfaces with imperfections with metallic paste filler and sand to a uniform smooth finish.

3.2 INSTALLATION GENERAL

.1

.2

3.3 FRAME INSTALLATION

.1

.2

.3

.4

.5

3.4 DOOR INSTALLATION

.1

.2

.3

3.5 FINISH REPAIRS

.1

.2

Project No. R.050134.002

Flush Wood Doors

Section 08 14 16 Page 1

PART 1 - GENERAL 1.1 RELATED REQUIREMENTS


.1 .2 .1 Section 08 11 00 - Metal Doors and Frames. Section 08 71 00 - Door Hardware. Architectural Woodwork Manufacturers Association of Canada (AWMAC). .1 Quality Standards for Architectural Woodwork 1998. Canadian General Standards Board (CGSB). .1 CAN/CGSB-71.19-M88, Adhesive, Contact, Sprayable. .2 CAN/CGSB-71.20-M88, Adhesive, Contact, Brushable. Canadian Standards Association (CSA International). .1 CSA A440.2-98, Energy Performance of Windows and Other Fenestration Systems. .2 CSA O115-M1982(R2001), Hardwood and Decorative Plywood. .3 CAN/CSA O132.2 Series-90(R1998), Wood Flush Doors. .4 CAN/CSA-O132.5-M1992(R1998), Stile and Rail Wood Doors. .5 CAN/CSA-Z808-96, A Sustainable Forest Management System: Guidance Document. .6 CSA Certification Program for Windows and Doors 00. Environmental Choice Program (ECP). .1 CCD-045-92, Sealants and Caulking Compounds. .2 CCD-046-92, Adhesives. National Fire Protection Association (NFPA). .1 NFPA 80-1999, Standard for Fire Doors and Fire Windows. .2 NFPA 252-1999, Standard Method of Fire Tests of Door Assemblies. Underwriters' Laboratories of Canada (ULC). .1 CAN-4S104M-80(R1985), Fire Tests of Door Assemblies. .2 CAN4-S105M-85 (R1992), Fire Door Frames Meeting the Performance Required by CAN4-S104. Product Data: .1 Submit manufacturer's printed product literature, specifications and data sheet in accordance with Section 01 33 00 - Submittal Procedures. .2 Submit two copies of WHMIS MSDS - Material Safety Data Sheets in accordance with Section 01 33 00 -

1.2 REFERENCES

.2

.3

.4

.5

.6

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

Project No. R.050134.002

Flush Wood Doors

Section 08 14 16 Page 2

Submittal Procedures. Indicate VOC's: For caulking materials during application .1 and curing. .2 For door materials and adhesives. .2 Shop Drawings: .1 Submit shop drawings in accordance with Section 01 33 00 - Submittal Procedures. .2 Indicate door types and cutouts for lights and louvres, sizes, core construction, transom panel construction and cutouts. Submit samples in accordance with Section 01 33 00 Submittal Procedures. Submit one 300 x 300 mm corner sample of each type wood door. Show door construction, core, glazing detail and faces. Manufacturer's Instructions: .1 Submit manufacturer's installation instructions. Storage and Protection: .1 Protect doors from dampness. Arrange for delivery after work causing abnormal humidity has been completed. .2 Store doors in well ventilated room, off floor, in accordance with manufacturer's recommendations. .3 Protect doors from scratches, handling marks and other damage. .4 Store doors away from direct sunlight.

1.4 SAMPLES

.1

.2

.3 .4

1.5 DELIVERY, STORAGE, AND HANDLING

.1

1.6 WASTE MANAGEMENT AND DISPOSAL

.1

Remove from site and dispose of packaging materials at appropriate recycling facilities. Dispose of corrugated cardboard, polystyrene, plastic packaging material in appropriate on-site bin for recycling in accordance with site waste management program. Unused or damaged glazing materials are not recyclable and must not be diverted to municipal recycling programs. Divert unused adhesive material from landfill to official hazardous material collections site approved by Departmental Representative. Do not dispose of unused paint materials into sewer systems, into lakes, streams, onto ground or in locations where it will pose health or environmental hazard.

.2

.3

.4

.5

Project No. R.050134.002

Flush Wood Doors

Section 08 14 16 Page 3

PART 2 - PRODUCTS 2.1 WOOD FLUSH DOORS


.1 Solid core: to CAN/CSA-O132.2.1. .1 Construction: .1 Solid particleboard core: stile and rail frame bonded to particleboard core with wood lock blocks, 3-ply construction. .2 Solid wood core: .1 Glued block core with wood edge band. .2 Face Panels: .1 Hardboard: composition face moulded face. .3 Adhesive: Type II (water resistant) for interior doors. Vertical edge strips to match face veneer.

2.2 FABRICATION PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS

.1

.1

Compliance: comply with manufacturer's written data, including product technical bulletins, product catalogue installation instructions, product carton installation instructions, and data sheets. Unwrap and protect doors in accordance with CAN/CSA-O132.2 Series, Appendix A. Install labelled fire rated doors to NFPA 80. Install doors and hardware in accordance with manufacturer's printed instructions and CAN/CSA-O132.2 Series, Appendix A. Adjust hardware for correct function. Re-adjust doors and hardware just prior to completion of building to function freely and properly. Perform cleaning as soon as possible after installation to remove construction and accumulated environmental dirt. Remove traces of primer, caulking; clean doors and frames. On completion of installation, remove surplus materials, rubbish, tools and equipment barriers.

3.2 INSTALLATION

.1

.2 .3

.4

3.3 ADJUSTMENT

.1

3.4 CLEANING

.1

.2

.3

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2 .1

Section 08 11 00 - Metal Doors and Frames. Section 08 14 16 - Flush Wood Doors. American National Standards Institute (ANSI) / Builders Hardware Manufacturers Association (BHMA) .1 ANSI/BHMA A156.1-2000, American National Standard for Butts and Hinges. .2 ANSI/BHMA A156.2-2003, Bored and Preassembled Locks and Latches. .3 ANSI/BHMA A156.3-2001, Exit Devices. .4 ANSI/BHMA A156.4-2000, Door Controls - Closers. .5 ANSI/BHMA A156.5-2001, Auxiliary Locks and Associated Products. .6 ANSI/BHMA A156.6-2005, Architectural Door Trim. .7 ANSI/BHMA A156.8-2005, Door Controls - Overhead Stops and Holders. .8 ANSI/BHMA A156.10-1999, Power Operated Pedestrian Doors. .9 ANSI/BHMA A156.12-2005, Interconnected Locks and Latches. .10 ANSI/BHMA A156.13-2002, Mortise Locks and Latches Series 1000. .11 ANSI/BHMA A156.14-2002, Sliding and Folding Door Hardware. .12 ANSI/BHMA A156.15-2006, Release Devices Closer Holder, Electromagnetic and Electromechanical. .13 ANSI/BHMA A156.16-2002, Auxiliary Hardware. .14 ANSI/BHMA A156.17-2004, Self-closing Hinges and Pivots. .15 ANSI/BHMA A156.18-2006, Materials and Finishes. .16 ANSI/BHMA A156.19-2002, Power Assist and Low Energy Power - Operated Doors. .17 ANSI/BHMA A156.20-2006, Strap and Tee Hinges and Hasps. Canadian Steel Door and Frame Manufacturers' Association (CSDMA) .1 CSDMA Recommended Dimensional Standards for Commercial Steel Doors and Frames - 2009. Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for door hardware and include product characteristics, performance criteria, physical size, finish and limitations.

1.2 REFERENCES

.2

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 2

.3

Hardware List: .1 Submit contract hardware list. .2 Indicate specified hardware, including make, model, material, function, size, finish and other pertinent information. Test Reports: certified test reports showing compliance with specified performance characteristics and physical properties. Manufacturer's Instructions: submit manufacturer's installation instructions. Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for door hardware for incorporation into manual. Regulatory Requirements: .1 Hardware for doors in fire separations and exit doors certified by a Canadian Certification Organization accredited by Standards Council of Canada. Certificates: product certificates signed by manufacturer certifying materials comply with specified performance characteristics and criteria and physical requirements. Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Package items of hardware including fastenings, separately or in like groups of hardware, label each package as to item definition and location. Storage and Handling Requirements: .1 Store materials off ground, indoors, in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect door hardware from nicks, scratches, and blemishes. .3 Protect prefinished surfaces with wrapping or strippable coating. .4 Replace defective or damaged materials with new.

.4

.5

1.4 CLOSEOUT SUBMITTALS

.1

.2

1.5 QUALITY ASSURANCE

.1

.2

1.6 DELIVERY, STORAGE AND HANDLING

.1

.2

.3

.4

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 3

PART 2 - PRODUCTS

2.1 HARDWARE ITEMS

.1

Use one manufacturer's products only for similar items.

2.2 DOOR HARDWARE

.1

Locks and latches: .1 Bored and preassembled locks and latches: to ANSI/BHMA A156.2, series 2000 preassembled lock, grade 1 , designed for function and keyed as stated in Hardware Schedule. Interconnected locks and latches: to ANSI/BHMA .2 A156.12, series 5000 interconnected lock, grade 1, designed for function and keyed as stated in Hardware Schedule. .3 Mortise locks and latches: to ANSI/BHMA A156.13, series 1000 mortise lock, grade 1, designed for function and keyed as stated in Hardware Schedule. .4 Lever handles: plain design. .5 Roses: round. .6 Normal strikes: box type, lip projection not beyond jamb. .7 Cylinders: key into keying system as noted. .8 Finished to 626. Butts and hinges: .1 Butts and hinges: to ANSI/BHMA A156.1, designated by letter A and numeral identifiers, followed by size and finish, listed in Hardware Schedule. Exit devices: to ANSI/BHMA A156.3, type , function, grade 1 2, conventional modern modern-narrow stile special (describe) design, finished to. .1 Auxiliary items: door co-ordinator, type 21, for pairs of doors with overlapping astragals. Door Closers and Accessories: .1 Door controls (closers): to ANSI/BHMA A156.4, designated by letter C and numeral identifiers listed in Hardware Schedule, in accordance with ANSI/BHMA A156.4, table A1, finished to 626. .2 Door controls - magnetic overhead holders: to ANSI/BHMA A156.8, designated by letter C and numeral identifiers listed in Hardware Schedule, finished to 626. .3 Closer/holder release devices: to ANSI/BHMA A156.15, designated by letter C and numeral identifiers listed in hardware schedule, finished to 626. Auxiliary locks and associated products: to ANSI/BHMA A156.5, designated by letter E and numeral identifiers as listed below, finished to 626. .1 Abloy Model 1297 complete with CY415 hardened steel rim cylinder.

.2

.3

.4

.5

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 4

.6

Auxiliary hardware: to ANSI/BHMA A156.16, listed in Hardware Schedule and as listed below, finished to 626. .1 Mechanical access control heavy duty cylindrical lockset (mechanical push button combination lockset), lever trim, with key override, [finished to 626]. .2 Door silencer: type: clear. Door bottom seal: heavy duty, door seal of extruded aluminum frame and solid closed cell neoprene weather seal, surface mounted, closed ends, adjustable automatic retract mechanism when door is open, clear anodized finish. Thresholds: width of door frame x full width of door opening, extruded aluminum mill finish, serrated surface, with lip and vinyl door seal insert. Weatherstripping: .1 Head and jamb seal: .1 Extruded aluminum frame and solid closed cell neoprene insert, clear anodized finish. Use only fasteners provided by manufacturer. Failure to comply may void warranties and applicable licensed labels. Supply screws, bolts, expansion shields and other fastening devices required for satisfactory installation and operation of hardware. Exposed fastening devices to match finish of hardware. Where pull is scheduled on one side of door and push plate on other side, supply fastening devices, and install so pull can be secured through door from reverse side. Install push plate to cover fasteners. Use fasteners compatible with material through which they pass. Keying by others.

.7

.8

.9

2.3 FASTENINGS

.1

.2

.3 .4

.5

2.4 KEYING

.1

PART 3 - EXECUTION 3.1 INSTALLATION


.1 Manufacturer's Instructions: comply with manufacturer's written recommendations, including product technical bulletins, product catalogue installation instructions, product carton installation instructions, and data sheets. Supply metal door and frame manufacturers with complete instructions and templates for preparation of their work to receive hardware.

.2

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 5

.3

Supply manufacturers' instructions for proper installation of each hardware component. Install hardware to standard hardware location dimensions in accordance with CSDFMA Canadian Metric Guide for Steel Doors and Frames (Modular Construction). Where door stop contacts door pulls, mount stop to strike bottom of pull. Install key control cabinet. Use only manufacturer's supplied fasteners. .1 Use of "quick" type fasteners, unless specifically supplied by manufacturer, is unacceptable. Remove construction cores when directed by Departmental Representative. .1 Install permanent cores and ensure locks operate correctly. Adjust door hardware, operators, closures and controls for optimum, smooth operating condition, safety and for weather tight closure. Lubricate hardware, operating equipment and other moving parts. Adjust door hardware to ensure tight fit at contact points with frames. Progress Cleaning: .1 Leave Work area clean at end of each day. .2 Clean hardware with damp rag and approved non-abrasive cleaner, and polish hardware in accordance with manufacturer's instructions. .3 Remove protective material from hardware items where present. Final Cleaning: upon completion remove surplus .4 materials, rubbish, tools and equipment. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. .1 Remove recycling containers and bins from site and dispose of materials at appropriate facility. Demonstrate operation, operating components, adjustment features, and lubrication requirements.

.4

.5

.6 .7

.8

3.2 ADJUSTING

.1

.2

.3

3.3 CLEANING

.1

.2

3.4 DEMONSTRATION

.1

Project No. R.050134.002

DOOR HARDWARE

Section 08 71 00 Page 6

3.5 PROTECTION

.1

Protect installed products and components from damage during construction. Repair damage to adjacent materials caused by door hardware installation. Hardware Set H1: .1 1 Unican level lockset (active leaf only) reused. .2 1 pairs hinges reused. .3 1 ea. Top and bottom flush bolts (fixed leaf only) reused. .4 1 door closer (active leaf only) reused. .5 1 aluminum threshold reused. .6 1 automatic drop bottom, surface mounted reused. .7 1 floor mounted door stop new. .8 1 full height steel astragal reused. .9 Signage plate (active leaf only) reused. .10 Acoustic gasket new. Hardware Set H2: .1 1 Unican level lockset (active leaf only) reused. .2 1 pairs hinges reused. .3 1 door closer (active leaf only) reused. .4 1 aluminum threshold new. .5 1 automatic drop bottom, surface mounted new. .6 1 wall mounted door stop new. .7 1 metal kick-plate (corridor side) reused. .8 Signage plate (corridor side) reused. .9 Acoustic gasket new. Hardware Set H3: .1 1 mortise lock and latch set Schlage L9486, ANSI F15 function without indicator. .2 1 rim lock Abloy Model 1297 complete with CY415 hardened steel rim cylinder. .3 2 pairs hinges. .4 1 interlocking threshold. .5 1 door contact (by others). .6 1 magnetic hold open device. .7 1 heavy duty pneumatic door closer. .8 1 door sweep. Hardware Set H4: .1 1 mortise lever lockset. .2 1 pairs hinges. .3 2 floor mounted door stop. .4 1 acoustical gasket.

.2

3.6 SCHEDULE

.1

.2

.3

.4

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS 1.2 REFERENCES

.1

09 22 15 - Non-structural Metal Framing.

.1

Aluminum Association (AA) .1 AA DAF 45-03(R2009), Designation System for Aluminum Finishes. ASTM International .1 ASTM C 475-02(2007), Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board. .2 ASTM C 514-04(2009e1), Standard Specification for Nails for the Application of Gypsum Board. .3 ASTM C 557-03(2009)e1, Standard Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing. .4 ASTM C 840-08, Standard Specification for Application and Finishing of Gypsum Board. .5 ASTM C 954-07, Standard Specification for Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs From 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness. .6 ASTM C 1002-07, Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs. .7 ASTM C 1047-09, Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base. .8 ASTM C 1280-99, Standard Specification for Application of Gypsum Sheathing. .9 ASTM C 1177/C 1177M-08, Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing. .10 ASTM C 1178/C 1178M-08, Standard Specification for Glass Mat Water-Resistant Gypsum Backing Board. .11 ASTM C 1396/C 1396M-09a, Standard Specification for Gypsum Wallboard. Association of the Wall and Ceilings Industries International (AWCI) .1 AWCI Levels of Gypsum Board Finish-97. Canadian General Standards Board (CGSB) .1 CAN/CGSB-51.34-M86(R1988), Vapour Barrier, Polyethylene Sheet for Use in Building Construction. .2 CAN/CGSB-71.25-M88, Adhesive, for Bonding Drywall to Wood Framing and Metal Studs. South Coast Air Quality Management District (SCAQMD), California State, Regulation XI. Source Specific

.2

.3

.4

.5

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 2

Standards .1 SCAQMD Rule 1113-A2007, Architectural Coatings. .2 SCAQMD Rule 1168-A2005, Adhesives and Sealants Applications. .6 Underwriters' Laboratories of Canada (ULC) .1 CAN/ULC-S102-07, Standard Method of Test of Surface Burning Characteristics of Building Materials and Assemblies. Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for gypsum board assemblies and include product characteristics, performance criteria, physical size, finish and limitations. Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Storage and Handling Requirements: .1 Store gypsum board assemblies materials level off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect gypsum board assemblies from nicks, scratches, and blemishes. .3 Protect from weather, elements and damage from construction operations. .4 Handle gypsum boards to prevent damage to edges, ends or surfaces. .5 Protect prefinished aluminum surfaces with wrapping. Do not use adhesive papers or sprayed coatings which bond when exposed to sunlight or weather. .6 Replace defective or damaged materials with new. Maintain temperature 10 degrees C minimum, 21 degrees C maximum for 48 hours prior to and during application of gypsum boards and joint treatment, and for 48 hours minimum after completion of joint treatment. Apply board and joint treatment to dry, frost free surfaces. Ventilation: ventilate building spaces as required to remove excess moisture that would prevent drying of

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

1.4 DELIVERY, STORAGE AND HANDLING

.1

.2

.3

1.5 AMBIENT CONDITIONS

.1

.2

.3

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 3

joint treatment material immediately after its application.

PART 2 - PRODUCTS 2.1 MATERIALS


.1 Standard board: to ASTM C 1396/C 1396M regular, thickness as indicated, 1200 mm wide x maximum practical length, ends square cut, edges squared. Drywall furring channels: 0.5 mm core thickness galvanized steel channels for screw attachment of gypsum board. Resilient clips : 0.5 mm base steel thickness galvanized steel for resilient attachment of gypsum board. Nails: to ASTM C 514. Steel drill screws: to ASTM C 1002. Stud adhesive: to CAN/CGSB-71.25 ASTM C 557. Casing beads, corner beads, control joints and edge trim: to ASTM C 1047, PVC, 0.5 mm base thickness, perforated flanges, one piece length per location. Vinyl mouldings: mouldings for joint treatment of vinyl-faced gypsum board, as supplied by gypsum board manufacturer. Sealants: in accordance with Section 07 92 00 - Joint Sealants. .1 VOC limit 250 g/L maximum to SCAQMD Rule 1168. .2 Acoustic sealant: in accordance with Section 07 92 00 - Joint Sealants. Polyethylene: to CAN/CGSB-51.34, Type 2. Insulating strip: rubberized, moisture resistant, 3 mm thick closed cell neoprene strip, 12 mm wide, with self sticking permanent adhesive on one face, lengths as required. Joint compound: to ASTM C 475, asbestos-free.

.2

.3

.4 .5 .6 .7

.8

.9

.10 .11

.12

2.2 FINISHES

.1

Texture finish: asbestos-free standard white texture coating and primer-sealer, recommended by gypsum board manufacturer. .1 Primer: VOC limit 50, 100 or 200 g/L maximum to GS-11 SCAQMD Rule 1113.

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 4

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify conditions of substrates previously installed under other Sections or Contracts are acceptable for gypsum board assemblies installation in accordance with manufacturer's written instructions. .1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative. Do application and finishing of gypsum board to ASTM C 840 except where specified otherwise. Do application of gypsum sheathing to ASTM C 1280. Erect hangers and runner channels for suspended gypsum board ceilings to ASTM C 840 except where specified otherwise. Support light fixtures by providing additional ceiling suspension hangers within 150 mm of each corner and at maximum 600 mm around perimeter of fixture. Install work level to tolerance of 1:1200. Frame with furring channels, perimeter of openings for access panels, light fixtures, diffusers and grilles. Install 19 x 64 mm furring channels parallel to, and at exact locations of steel stud partition header track. Furr for gypsum board faced vertical bulkheads within and at termination of ceilings. Furr above suspended ceilings for gypsum board fire and sound stops and to form plenum areas as indicated. Install wall furring for gypsum board wall finishes to ASTM C 840, except where specified otherwise. Furr openings and around built-in equipment, cabinets, access panels, on four sides. Extend furring into reveals. Check clearances with equipment suppliers. Furr duct shafts, beams, columns, pipes and exposed services where indicated.

3.2 ERECTION

.1

.2 .3

.4

.5 .6

.7

.8

.9

.10

.11

.12

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 5

.13

Erect drywall resilient furring transversely across studs, spaced maximum 600 mm on centre and not more than 150 mm from ceiling/wall juncture. Secure to each support with 25 mm drywall screw. Install 150 mm continuous strip of 12.7 mm gypsum board along base of partitions where resilient furring installed. Apply gypsum board after bucks, anchors, blocking, sound attenuation, electrical and mechanical work have been approved. Apply gypsum board (number of layers as indicated) to metal furring or framing using screw fastenersfor first layer, screw fasteners for second layer. Maximum spacing of screws 300 mm on centre. .1 Single-Layer Application: .1 Apply gypsum board on ceilings prior to application of walls to ASTM C 840. .2 Apply gypsum board vertically or horizontally, providing sheet lengths that will minimize end joints. .2 Double-Layer Application: .1 Install gypsum board for base layer and exposed gypsum board for face layer. .2 Apply base layer to ceilings prior to base layer application on walls; apply face layers in same sequence. Offset joints between layers at least 250 mm. .3 Apply base layers at right angles to supports unless otherwise indicated. .4 Apply base layer on walls and face layers vertically with joints of base layer over supports and face layer joints offset at least 250 mm with base layer joints. Apply 12 mm diameter bead of acoustic sealant continuously around periphery of each face of partitioning to seal gypsum board/structure junction where partitions abut fixed building components. Seal full perimeter of cut-outs around electrical boxes, ducts, in partitions where perimeter sealed with acoustic sealant. Arrange vinyl-faced gypsum board symmetrical about openings and wall areas, with butt joints. Install gypsum board on walls vertically to avoid end-butt joints. At stairwells and similar high walls, install boards horizontally with end joints staggered over studs, except where local codes or fire-rated assemblies require vertical application. Install gypsum board with face side out.

.14

3.3 APPLICATION

.1

.2

.3

.4

.5

.6

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 6

.7 .8

Do not install damaged or damp boards. Locate edge or end joints over supports. Stagger vertical joints over different studs on opposite sides of wall. Erect accessories straight, plumb or level, rigid and at proper plane. Use full length pieces where practical. Make joints tight, accurately aligned and rigidly secured. Mitre and fit corners accurately, free from rough edges. Secure at 150 mm on centre using contact adhesive for full length. Install casing beads around perimeter of suspended ceilings. Install casing beads where gypsum board butts against surfaces having no trim concealing junction and where indicated. Seal joints with sealant. Install insulating strips continuously at edges of gypsum board and casing beads abutting metal window and exterior door frames, to provide thermal break. Install shadow mould at gypsum board/ceiling juncture as indicated. Minimize joints; use corner pieces and splicers. Install cornice cap where gypsum board partitions do not extend to ceiling. Fit cornice cap over partition, secure to partition track with two rows of sheet metal screws staggered at 300 mm on centre. Splice corners and intersections together and secure to each member with 3 screws. Install access doors to electrical and mechanical fixtures specified in respective sections. .1 Rigidly secure frames to furring or framing systems. Finish face panel joints and internal angles with joint system consisting of joint compound, joint tape and taping compound installed according to manufacturer's directions and feathered out onto panel faces. Finish corner beads, control joints and trim as required with two coats of joint compound and one coat of taping compound, feathered out onto panel faces. Fill screw head depressions with joint and taping compounds to bring flush with adjacent surface of gypsum board so as to be invisible after surface finish is completed.

3.4 INSTALLATION

.1

.2

.3

.4

.5

.6

.7

.8

.9

.10

.11

.12

Project No. R.050134.002

GYPSUM BOARD ASSEMBLIES

Section 09 21 16 Page 7

.13

Sand lightly to remove burred edges and other imperfections. Avoid sanding adjacent surface of board. Completed installation to be smooth, level or plumb, free from waves and other defects and ready for surface finish. Apply one coat of white primer sealer over surface to be textured. When dry apply textured finish in accordance with manufacturer's instructions. Mix joint compound slightly thinner than for joint taping. Apply thin coat to entire surface using trowel or drywall broad knife to fill surface texture differences, variations or tool marks. Allow skim coat to dry completely. Remove ridges by light sanding or wiping with damp cloth. Progress Cleaning: .1 Leave Work area clean at end of each day. .2 Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment. Protect installed products and components from damage during construction. Repair damage to adjacent materials caused by gypsum board assemblies installation. As indicated.

.14

.15

.16

.17

.18 .19

3.5 CLEANING

.1

3.6 PROTECTION

.1

.2

3.7 SCHEDULES

.1

Project No. R.050134.002

Non-structural Metal Framing Section 09 22 16 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2 .3

Section 05 50 00 - Metal Fabrications. Section 09 21 16 - Gypsum Board Assemblies. Section 10 22 13 - Wire Mesh Partitions. American Society for Testing and Materials International, (ASTM). .1 ASTM C 645-00, Specification for Nonstructural Steel Framing Members. .2 ASTM C 754-00, Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products. Canadian General Standards Board (CGSB). .1 CAN/CGSB-1.40-97, Primer, Structural Steel, Oil Alkyd Type. Environmental Choice Program (ECP). .1 CCD-047a -98, Paints - Surface Coatings. .2 CCD-048-98, Surface Coatings - Recycled Water-borne. Separate and recycle waste materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management And Disposal. Remove from site and dispose of packaging materials at appropriate recycling facilities. Collect and separate for disposal paper, plastic, polystyrene, corrugated cardboard packaging material in appropriate on-site for recycling in accordance with Waste Management Plan. Divert unused metal materials from landfill to metal recycling facility approved by Departmental Representative. Divert unused gypsum materials from landfill to recycling facility approved by Departmental Representative.

1.2 REFERENCES

.1

.2

.3

1.3 WASTE MANAGEMENT AND DISPOSAL

.1

.2

.3

.4

.5

PART 2 - PRODUCTS 2.1 MATERIALS


.1 Non-load bearing channel stud framing: to ASTM C 645, stud size as indicated, roll formed, thickness as indicated, hot dipped galvanized steel sheet, for screw attachment of gypsum board . Knock-out service holes

Project No. R.050134.002

Non-structural Metal Framing Section 09 22 16 Page 2


at 460 mm centres.

.2

Floor and ceiling tracks: to ASTM C 645, in widths to suit stud sizes, 32 mm flange height. Acoustical sealant: to ASTM C 919. Insulating strip: rubberized, moisture resistant 3 mm thick foam strip, 12 mm wide, with self sticking adhesive on one face, lengths as required.

.3 .4

PART 3 - EXECUTION 3.1 ERECTION


.1 Align partition tracks at floor and ceiling and secure at 600 mm on centre maximum. Install damp proof course under stud shoe tracks of partitions on slabs on grade. Place studs vertically at 400 mm on centre and not more than 50 mm from abutting walls, and at each side of openings and corners. Position studs in tracks at floor and ceiling. Cross brace steel studs as required to provide rigid installation to manufacturer's instructions. Erect metal studding to tolerance of 1:1000. Attach studs to bottom and ceiling tracks using screws. Co-ordinate simultaneous erection of studs with installation of service lines. When erecting studs ensure web openings are aligned. Co-ordinate erection of studs with installation of door/window frames and special supports or anchorage for work specified in other Sections. Provide two studs extending from floor to ceiling at each side of openings wider than stud centres specified. Secure studs together, 50 mm apart using column clips or other approved means of fastening placed alongside frame anchor clips. Install heavy gauge single jamb studs at openings. Erect track at head of door/window openings and sills of sidelight/window openings to accommodate intermediate studs. Secure track to studs at each end, in accordance with manufacturer's instructions. Install intermediate studs above and below openings in same manner and spacing as wall studs. Frame openings and around built-in equipment, cabinets, access panels, on four sides. Extend framing

.2

.3

.4 .5 .6

.7

.8

.9 .10

.11

Project No. R.050134.002

Non-structural Metal Framing Section 09 22 16 Page 3


into reveals. Check clearances with equipment suppliers.

.12

Provide 40 mm stud or furring channel secured between studs for attachment of fixtures behind lavatory basins, toilet and bathroom accessories, and other fixtures including grab bars and towel rails, attached to steel stud partitions. Install steel studs or furring channel between studs for attaching electrical and other boxes. Extend partitions to ceiling height except where noted otherwise on drawings. Maintain clearance under beams and structural slabs to avoid transmission of structural loads to studs. Use 50 mm leg ceiling tracks. Use double track slip joint as indicated. Install continuous insulating strips to isolate studs from uninsulated surfaces. Install two continuous beads of acoustical sealant under studs and tracks around perimeter of sound control partitions. Upon completion of installation, remove surplus materials, rubbish, tools and equipment barriers.

.13

.14

.15

.16

.17

3.2 CLEANING

.1

Project No. R.050134.002

ACCESS FLOORING

Section 09 69 00 Page 1

PART 1 - GENERAL 1.1 RELATED REQUIREMENTS 1.2 REFERENCES


.1 Reserved.

.1

Aluminum Association (AA). .1 DAF 45-03, Designation System for Aluminum Finishes. Canadian General Standards Board (CGSB). .1 CAN/CGSB-1.81-M90, Air Drying and Baking Alkyd Primer for Vehicles and Equipment. .2 CAN/CGSB-1.88-92, Gloss Alkyd Enamel Air Drying and Baking. .3 CAN/CGSB-1.104-M91, Semigloss Alkyd Air Drying and Baking Enamel. .4 CAN/CGSB-51.34-M86, Vapour Barrier, Polyethylene Sheet, for Use in Building Construction.

.2

1.3 SYSTEM DESCRIPTION

.1

Design Requirements: .1 Pedestals: .1 Existing to remain. .2 Stringers: .1 Existing to remain. .3 Floor Panels: .1 Uniformly distributed load of 12 kPa: Maximum deflection of 1 mm. .2 Concentrated load of 4.4kN applied over area of 25 x 25 mm at any location: maximum deflection of 2.54 mm. .3 Rolling load of 2.2 kN on 76 mm diameter caster with bearing area of 1.27 mm anywhere on panel without damage maximum deflection of 2.54 mm. .4 Permanent deflection: maximum 0.5 mm at design load. .5 Ultimate strength of the panel: provide safety factor of 3.0 times its design load without failure. .4 Allowable Tolerances: .1 Flatness of floor panels: plus or minus 0.5 mm in any direction. .2 Surface Dimension: plus or minus 0.5 mm of all panels. Finished floor level tolerance: plus or .3 minus 3 mm for overall floor, and plus or minus 1 mm in 2000 mm in any direction. .4 Squareness: plus or minus 0.5 mm in surface dimension and 0.25 mm measured diagonally. .5 Fire Resistance: .1 Floor panels, less finished flooring: flame spread rating of 5; fuel contribution of

Project No. R.050134.002

ACCESS FLOORING

Section 09 69 00 Page 2

10 and smoke development of 15.

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

Product Data: .1 Submit manufacturer's printed product literature, specifications and data sheet in accordance with Section 01 33 00 - Submittal Procedures. .2 Submit two copies of WHMIS MSDS - Material Safety Data Sheets in accordance with Section 01 33 00 Submittal Procedures. Indicate VOC's: .1 For caulking materials during application and curing. .2 For adhesives. Shop Drawings: .1 Submit shop drawings in accordance with Section 01 33 00 - Submittal Procedures. .2 Take measurements from finished area at site. Indicate where applicable following information: .1 Layout of work. .2 Sizes and details of components. .3 Anchorage methods. .4 Edge and fascia details. .5 Elevation differences. .6 Stair, handrail and ramp framing and details. .7 Lateral bracing. .8 Typical cutout details. .9 Gasketting, return air details, supply air registers and perforated panels. Include air transfer capacity of grilles, registers and panels. .10 Floor finishes. .11 Location of connection to building grounding electrode. Samples: .1 Submit samples in accordance with Section 01 33 00 - Submittal Procedures. .2 Submit one full size sample consisting of 4 panels of complete access flooring system, including finishes. .3 Submit one of each of following components. .1 Full size floor panel. .2 High pressure laminate. .3 Fasteners. .4 Accessories. .4 Submit duplicate samples of each type floor covering. Colour chips from manufacturer's standard .1 range of colours for specified floor covering material. .5 Incorporate approved samples into finished installation. Identify and note locations. Manufacturer's Instructions: .1 Submit manufacturer's installation

.2

.3

.4

Project No. R.050134.002

ACCESS FLOORING

Section 09 69 00 Page 3

.5 .6

instructions. Manufacturers' Field Reports: submit copies of manufacturers field reports. Closeout Submittals: .1 Provide operation and maintenance data for access flooring system for incorporation into manual specified in Sections 01 78 00 - Closeout Submittals. Certificates: .1 Submit certification, to demonstrate compliance of the access flooring system to specification and specified standards by submitting: .1 CSA or ULC certification. Government or independent testing agency .2 test reports certifying that the product meets the standard. .3 Letter of certification from a responsible official of the manufacturer. .4 Method for testing access flooring in accordance with Ceilings and Interior Systems Construction Association (CISCA) standard test procedures. Have tests performed by an independent testing laboratory regularly engaged in testing of access floor components. .2 Test Reports: certified test reports showing compliance with specified performance characteristics and physical properties. .3 Certificates: product certificates signed by manufacturer certifying materials comply with specified performance characteristics and criteria and physical requirements.

1.5 QUALITY ASSURANCE

.1

1.6 WASTE MANAGEMENT AND DISPOSAL

.1

Separate and recycle waste materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. Remove from site and dispose of packaging materials at appropriate recycling facilities. Collect and separate for disposal paper plastic, polystyrene, corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan. Extra Materials: .1 Provide maintenance materials special tools and spare parts in accordance with Section 01 78 00 Closeout Submittals. .2 Provide 5 spare solid floor panels and 5 spare perforated floor panels complete with specified floor covering. Store where directed. Identify each box. .3 Provide 1 floor panel lifting device , standard with access floor manufacturer.

.2

.3

1.7 MAINTENANCE

.1

Project No. R.050134.002

ACCESS FLOORING

Section 09 69 00 Page 4

PART 2 - PRODUCTS

2.1 MATERIALS

.1 .2

Access flooring. Pedestals: steel assembly with minimum 10,000 mm base plate. Pedestal head formed steel. Threaded supporting rod and vibration-proof lock nut to permit 38 mm adjustment. Manufacturer's standard finish. Panels: .1 Steel floor panels: die formed, reinforced steel bottom plate welded to flat steel top plate and die cut to 610 x mm 610 mm size, bonderized and baked enamel finish, integral edge trim for plastic laminate finish.

.3

2.2 ACCESSORIES

.1

Panel lifting device: one per enclosed area, manufacturer's standard equipment, type recommended for each panel type. Include wall mounting bracket for panel lifter. Perforated floor panels: same size, materials, and construction as floor panels with 25% free area, quantity as indicated. Adhesives: moisture resistant type as recommended by manufacturer of material to be bonded. Cable cutout protection: extruded polyvinyl chloride or neoprene edging. Access grommets: textured plastic, sized to suit power and communication outlets colour black. Aluminum finishes: .1 Finish exposed surfaces of aluminum components in accordance with Aluminum Association Designation System for Aluminum Finishes. .1 As fabricated or mill finish. .2 Appearance and properties of anodized finishes designated by the Aluminum Association as Architectural Class 1, Architectural Class 2, and Protective and Decorative. Metal finishes: .1 Steel components: .1 Exposed steel components: thoroughly clean surfaces, spray apply 1 coat CAN/CGSB-1.81 primer and two coats CAN/CGSB-1.104 type 2 semi-gloss paint, colour selected by Departmental Representative. Individually bake each coat.

.2

.3

.4

.5

2.3 FINISHES

.1

.2

Project No. R.050134.002

ACCESS FLOORING

Section 09 69 00 Page 5

PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS


.1 Compliance: comply with manufacturer's written data, including product technical bulletins, product catalogue installation instructions, product carton installation instructions, and data sheets. Install components to system manufacturer's instructions. Pedestals and stringers: .1 Arrange pedestal assemblies to meet grid spacing required. .2 Bond pedestals base plate to structural floor with adhesive. Secure base plate to concrete floor with power activated fasteners after adhesive has cured. .3 When adhesive is cured no bond impairment acceptable when 178 N horizontal force is applied to 300 mm high pedestals. Install additional pedestal assemblies where grid pattern is disturbed by columns, walls, ramps, openings, and steps, and at cut-outs that impair floor load capacity. .4 Install stringers rigidly brace floor pedestals four ways. .3 Floor panels: .1 Install floor panels and floor finish solidly on pedestals, level to maximum variation over entire floor of 1:2000. .2 Install perforated panels where indicated. .3 Seal field cuts with plastic angles or channels. No exposed cut edges permitted. Adhere base to wall at intersection of walls and access floor panels. Adjust floor panel system for smooth, quiet operation. Perform cleaning after installation to remove construction and accumulated environmental dirt. Clean surfaces after installation using manufacturer's recommended cleaning procedures. Clean aluminum with damp rag and approved non-abrasive cleaner. Upon completion of installation, remove surplus materials, rubbish, tools and equipment barriers. Protect finished access floor with 0.15 mm thick polyethylene film kraft paper, sealed at edges to prevent tearing.

3.2 INSTALLATION

.1

.2

.4

.5

3.4 CLEANING

.1

.2

.3

.4

3.5 PROTECTION

.1

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 1

PART 1 - GENERAL 1.1 SUMMARY


.1 Related Requirements .1 Section 08 11 00 - Metal Doors and Frames. .2 .3 Section 08 14 16 - Flush Wood Doors. Section 09 21 16 - Gypsum Board Assemblies.

1.2 REFERENCES

.1

Department of Justice Canada (Jus) .1 Canadian Environmental Protection Act (CEPA), 1999, c. 33. Environmental Protection Agency (EPA) .1 EPA Test Method for Measuring Total Volatile Organic Compound Content of Consumer Products, Method 24 - 1995, (for Surface Coatings). Health Canada / Workplace Hazardous Materials Information System (WHMIS) .1 Material Safety Data Sheets (MSDS). Master Painters Institute (MPI) .1 MPI Architectural Painting Specifications Manual, 2004. National Fire Code of Canada - 1995 Society for Protective Coatings (SSPC) SSPC Painting Manual, Volume Two, 8th Edition, .1 Systems and Specifications Manual. Transport Canada (TC) .1 Transportation of Dangerous Goods Act (TDGA), 1992, c. 34. Submit work schedule for various stages of painting to Departmental Representative for review. Submit schedule minimum of 48 hours in advance of proposed operations. Obtain written authorization from Departmental Representative for changes in work schedule. Schedule painting operations to prevent disruption of occupants. Submittals in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit product data and instructions for each paint and coating product to be used. .2 Submit product data for the use and application

.2

.3

.4

.5 .6

.7

1.3 SCHEDULING

.1

.2

.3

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 2

of paint thinner. .3 Submit two copies of Workplace Hazardous Materials Information System (WHMIS) Material Safety Data Sheets (MSDS) in accordance with Section 01 33 00 - Submittal Procedures. Indicate VOCs during application and curing. .3 Samples: .1 Submit full range colour sample chips to indicate where colour availability is restricted. .2 Submit duplicate 200 x 300 mm sample panels of each paint with specified paint or coating in colours, gloss/sheen and textures required to MPI Architectural Painting Specification Manual standards submitted on following substrate materials: .1 3 mm plate steel for finishes over metal surfaces. .2 13 mm birch plywood for finishes over wood surfaces. .3 50 mm concrete block for finishes over concrete or concrete masonry surfaces. .4 13 mm gypsum board for finishes over gypsum board and other smooth surfaces. .5 10 mm hardboard for finishes over wood surfaces. .3 Retain reviewed samples on-site to demonstrate acceptable standard of quality for appropriate on-site surface. .4 Test reports: submit certified test reports for paint from approved independent testing laboratories, indicating compliance with specifications for specified performance characteristics and physical properties. .1 Lead, cadmium and chromium: presence of and amounts. .2 Mercury: presence of and amounts. Organochlorines and PCBs: presence of and .3 amounts. .5 Certificates: submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties. .6 Manufacturer's Instructions: .1 Submit manufacturer's installation and application instructions. .7 Closeout Submittals: submit maintenance data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals include following: .1 Product name, type and use. .2 Manufacturer's product number. .3 Colour numbers. .4 MPI Environmentally Friendly classification system rating. Extra Materials: .1 Deliver to extra materials from same production run as products installed. Package products with

1.5 MAINTENANCE

.1

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 3

protective covering and identify with descriptive labels. Comply with Section 01 78 00 - Closeout Submittals. .2 Quantity: provide one - one litre can of each type and colour of finish coating. Identify colour and paint type in relation to established colour schedule and finish system. .3 Delivery, storage and protection: comply with Departmental Representative requirements for delivery and storage of extra materials.

1.6 DELIVERY, STORAGE AND HANDLING

.1

Packing, Shipping, Handling and Unloading: .1 Pack, ship, handle and unload materials in accordance with Section 01 61 00 - Common Product Requirements and manufacturer's written instructions. Acceptance at Site: .1 Identify products and materials with labels indicating: .1 Manufacturer's name and address. .2 Type of paint or coating. .3 Compliance with applicable standard. .4 Colour number in accordance with established colour schedule. Remove damaged, opened and rejected materials from site. Storage and Protection: .1 Provide and maintain dry, temperature controlled, secure storage. .2 Store materials and supplies away from heat generating devices. Store materials and equipment in well ventilated .3 area with temperature range 7 degrees C to 30 degrees C. Store temperature sensitive products above minimum temperature as recommended by manufacturer. Keep areas used for storage, cleaning and preparation clean and orderly. After completion of operations, return areas to clean condition. Remove paint materials from storage only in quantities required for same day use. Fire Safety Requirements: .1 Provide one 9 kg Type ABC dry chemical fire extinguisher adjacent to storage area. .2 Store oily rags, waste products, empty containers and materials subject to spontaneous combustion in ULC approved, sealed containers and remove from site on a daily basis. .3 Handle, store, use and dispose of flammable and combustible materials in accordance with National Fire

.2

.3

.4

.5

.6

.7

.8

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 4

Code of Canada requirements. .9 Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. .2 Remove from site and dispose of packaging materials at appropriate recycling facilities. .3 Collect and separate for disposal paper, plastic, polystyrene, corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan (WMP). Separate for reuse and recycling and place in .4 designated containers Steel, Metal, Plastic waste in accordance with Waste Management Plan (WMP). .5 Place materials defined as hazardous or toxic in designated containers. .6 Handle and dispose of hazardous materials in accordance with CEPA, TDGA, Regional and Municipal, regulations. .7 Ensure emptied containers are sealed and stored safely. .8 Unused paint materials must be disposed of at official hazardous material collections site as approved by Departmental Representative. .9 Paint, stain and wood preservative finishes and related materials (thinners, and solvents) are regarded as hazardous products and are subject to regulations for disposal. Information on these controls can be obtained from Provincial Ministries of Environment and Regional levels of Government. .10 Material which cannot be reused must be treated as hazardous waste and disposed of in an appropriate manner. .11 Place materials defined as hazardous or toxic waste, including used sealant and adhesive tubes and containers, in containers or areas designated for hazardous waste. To reduce the amount of contaminants entering .12 waterways, sanitary/storm drain systems or into ground follow these procedures: .1 Retain cleaning water for water-based materials to allow sediments to be filtered out. .2 Retain cleaners, thinners, solvents and excess paint and place in designated containers and ensure proper disposal. .3 Return solvent and oil soaked rags used during painting operations for contaminant recovery, proper disposal, or appropriate cleaning and laundering. .4 Dispose of contaminants in approved legal manner in accordance with hazardous waste regulations. .5 Empty paint cans are to be dry prior to disposal or recycling (where available).

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 5

.13 Where paint recycling is available, collect waste paint by type and provide for delivery to recycling or collection facility.

1.7 SITE CONDITIONS

.1

Heating, Ventilation and Lighting: .1 Ventilate enclosed spaces. .2 Provide continuous ventilation for seven days after completion of application of paint. .3 Coordinate use of existing ventilation system with Departmental Representative and ensure its operation during and after application of paint as required. .4 Provide temporary ventilating and heating equipment where permanent facilities are not available or supplemental ventilating and heating equipment if ventilation and heating from existing system is inadequate to meet minimum requirements. .5 Provide minimum lighting level of 323 Lux on surfaces to be painted. Temperature, Humidity and Substrate Moisture Content Levels: .1 Unless pre-approved written approval by Paint Inspection Agency Authority and product manufacturer, perform no painting when: .1 Ambient air and substrate temperatures are below 10 degrees C. .2 Substrate temperature is above 32 degrees C unless paint is specifically formulated for application at high temperatures. .3 Substrate and ambient air temperatures are not expected to fall within MPI or paint manufacturer's prescribed limits. .4 The relative humidity is under 85% or when the dew point is more than 3 degrees C variance between the air/surface temperature. Paint should not be applied if the dew point is less than 3 degrees C below the ambient or surface temperature. Use sling psychrometer to establish the relative humidity before beginning paint work. .5 Ensure that conditions are within specified limits during drying or curing process, until newly applied coating can itself withstand 'normal' adverse environmental factors. .2 Perform painting work when maximum moisture content of the substrate is below: .1 Allow new concrete and masonry to cure minimum of 28 days. .2 15% for wood. .3 12% for plaster and gypsum board. .3 Test for moisture using calibrated electronic Moisture Meter. Test concrete floors for moisture using "cover patch test".

.2

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 6

.4 Test concrete, masonry and plaster surfaces for alkalinity as required. .3 Surface and Environmental Conditions: .1 Apply paint finish in areas where dust is no longer being generated by related construction operations or when wind or ventilation conditions are such that airborne particles will not affect quality of finished surface. .2 Apply paint to adequately prepared surfaces and to surfaces within moisture limits. .3 Apply paint when previous coat of paint is dry or adequately cured. Additional interior application requirements: .1 Apply paint finishes when temperature at location of installation can be satisfactorily maintained within manufacturer's recommendations. Apply paint in occupied facilities during silent .2 hours only. Schedule operations to approval of Departmental Representative such that painted surfaces will have dried and cured sufficiently before occupants are affected.

.4

PART 2 - PRODUCTS 2.1 MATERIALS


.1 Paint materials listed in the MPI Approved Products List (APL) are acceptable for use on this project. Provide paint materials for paint systems from single manufacturer. Only qualified products with E2 "Environmentally Friendly" rating are acceptable for use on this project. Conform to latest MPI requirements for interior painting work including preparation and priming. Materials (primers, paints, coatings, varnishes, stains, lacquers, fillers, thinners, solvents, etc.) in accordance with MPI Architectural Painting Specification Manual "Approved Product" listing. Linseed oil, shellac, and turpentine: highest quality product from approved manufacturer listed in MPI Architectural Painting Specification Manual, compatible with other coating materials as required. Provide paint products meeting MPI "Environmentally Friendly" , E2 ratings based on VOC (EPA Method 24) content levels.

.2

.3

.4

.5

.6

.7

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 7

.8

Use MPI listed materials having minimum E2 rating where indoor air quality (odour) requirements exist. Paints, coatings, adhesives, solvents, cleaners, lubricants, and other fluids: .1 Water-based. .2 Manufactured without compounds which contribute to ozone depletion in the upper atmosphere. .3 Manufactured without compounds which contribute to smog in the lower atmosphere. .4 Do not contain methylene chloride, chlorinated hydrocarbons, toxic metal pigments. Formulate and manufacture water-borne surface coatings with no aromatic solvents, formaldehyde, halogenated solvents, mercury, lead, cadmium, hexavalent chromium or their compounds. Flash point: 61.0 degrees C or greater for water-borne surface coatings and recycled water-borne surface coatings. Ensure manufacture and process of both water-borne surface coatings and recycled water-borne surface coatings does not release: .1 Matter in undiluted production plant effluent generating 'Biochemical Oxygen Demand' (BOD) in excess of 15 mg/L to natural watercourse or sewage treatment facility lacking secondary treatment. .2 Total Suspended Solids (TSS) in undiluted production plant effluent in excess of 15 mg/L to natural watercourse or a sewage treatment facility lacking secondary treatment. Water-borne paints and stains, recycled water-borne surface coatings and water borne varnishes to meet minimum "Environmentally Friendly" E2 rating. Recycled water-borne surface coatings must not contain: .1 Lead in excess of 600.0 ppm weight/weight total solids. .2 Mercury in excess of 50.0 ppm weight/weight total product. .3 Cadmium in excess of 1.0 ppm weight/weight total product. .4 Hexavelant chromium in excess of 3.0 ppm weight/weight total product. .5 Organochlorines or polychlorinated biphenyls (PCBS) in excess of 1.0 ppm weight/weight total product. Submit proposed Colour Schedule to Departmental Representative for review. Colour schedule will be based upon selection of three

.9

.10

.11

.12

.13

.14

2.2 COLOURS

.1

.2

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 8

base colours and two accent colours. No more than five colours will be selected for entire project and no more than three colours will be selected in each area. .3 Selection of colours from manufacturers full range of colours. Where specific products are available in restricted range of colours, selection based on limited range. Second coat in three coat system to be tinted slightly lighter colour than top coat to show visible difference between coats. Perform colour tinting operations prior to delivery of paint to site. Obtain written approval from Departmental Representative for tinting of painting materials. Mix paste, powder or catalyzed paint mixes inaccordance with manufacturer's written instructions. Use and add thinner in accordance with paint manufacturer's recommendations. Do not use kerosene or similar organic solvents to thin water-based paints. Thin paint for spraying in accordance with paint manufacturer's instructions. Re-mix paint in containers prior to and during application to ensure break-up of lumps, complete dispersion of settled pigment, and colour and gloss uniformity. Paint gloss is defined as sheen rating of applied paint, in accordance with following values: Gloss @ 60 degrees Max. 5 Sheen @ 85 degrees Max. 10

.4

.5

2.3 MIXING AND TINTING

.1

.2

.3

.4

.5

2.4 GLOSS/SHEEN RATINGS

.1

Gloss Level 1 - Matte Finish (flat) Gloss Level 2 - Velvet-Like Finish Gloss Level 3 - Eggshell Finish Gloss Level 4 - Satin-Like Finish Gloss Level 5 - Traditional Semi-Gloss Finish

Max.10

10 to 35

10 to 25

10 to 35

20 to 35

min. 35

35 to 70

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 9

Gloss Level 6 - Traditional Gloss Gloss Level 7 - High Gloss Finish .2

70 to 85

More than 85

Gloss level ratings of painted surfaces as indicated. Plaster and gypsum board: gypsum wallboard, drywall, "sheet rock type material", and textured finishes: .1 INT 9.2B - High performance architectural latex finish as indicated.

2.5 INTERIOR PAINTING SYSTEMS

.1

PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS


.1 Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and data sheet. Perform preparation and operations for interior painting in accordance with MPI Architectural Painting Specifications Manual except where specified otherwise. Apply paint materials in accordance with paint manufacturer's written application instructions. Investigate existing substrates for problems related to proper and complete preparation of surfaces to be painted. Report to Departmental Representative damages, defects, unsatisfactory or unfavourable conditions before proceeding with work. Conduct moisture testing of surfaces to be painted using properly calibrated electronic moisture meter, except test concrete floors for moisture using simple "cover patch test". Do not proceed with work until conditions fall within acceptable range as recommended by manufacturer. Maximum moisture content as follows: .1 Stucco, plaster and gypsum board: 12%. .2 Concrete: 12%. .3 Clay and Concrete Block/Brick: 12%. .4 Wood: 15%. Protection: .1 Protect existing building surfaces and adjacent structures from paint spatters, markings and other damage by suitable non-staining covers or masking. If damaged, clean and restore surfaces as directed by Departmental Representative. .2 Protect items that are permanently attached such

3.2 GENERAL

.1

.2

3.3 EXAMINATION

.1

.2

.3

3.4 PREPARATION

.1

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 10

as Fire Labels on doors and frames. Protect factory finished products and equipment. .3 .4 Protect building occupants in and about the building. .2 Surface Preparation: .1 Remove electrical cover plates, light fixtures, surface hardware on doors, bath accessories and other surface mounted equipment, fittings and fastenings prior to undertaking painting operations. Identify and store items in secure location and re-installed after painting is completed. .2 Move and cover furniture and portable equipment as necessary to carry out painting operations. Replace as painting operations progress. .3 Place "WET PAINT" signs in occupied areas as painting operations progress. Signs to approval of Departmental Representative . Clean and prepare surfaces in accordance with MPI Architectural Painting Specification Manual requirements. Refer to MPI Manual in regard to specific requirements and as follows: .1 Remove dust, dirt, and other surface debris by vacuuming, wiping with dry, clean cloths or compressed air. .2 Wash surfaces with a biodegradable detergent and bleach where applicable and clean warm water using a stiff bristle brush to remove dirt, oil and other surface contaminants. .3 Rinse scrubbed surfaces with clean water until foreign matter is flushed from surface. .4 Allow surfaces to drain completely and allow to dry thoroughly. .5 Prepare surfaces for water-based painting, water-based cleaners should be used in place of organic solvents. .6 Use trigger operated spray nozzles for water hoses. .7 Many water-based paints cannot be removed with water once dried. Minimize use of mineral spirits or organic solvents to clean up water-based paints. Prevent contamination of cleaned surfaces by salts, acids, alkalis, other corrosive chemicals, grease, oil and solvents before prime coat is applied and between applications of remaining coats. Apply primer, paint, or pretreatment as soon as possible after cleaning and before deterioration occurs. Where possible, prime non-exposed surfaces of new wood surfaces before installation. Use same primers as specified for exposed surfaces. Apply vinyl sealer to MPI #36 over knots, pitch, .1 sap and resinous areas. .2 Apply wood filler to nail holes and cracks.

.3

.4

.5

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 11

.3 .6

Tint filler to match stains for stained woodwork.

Sand and dust between coats as required to provide adequate adhesion for next coat and to remove defects visible from a distance up to 1000 mm. Clean metal surfaces to be painted by removing rust, loose mill scale, welding slag, dirt, oil, grease and other foreign substances in accordance with MPI requirements. Remove traces of blast products from surfaces, pockets and corners to be painted by brushing with clean brushes, blowing with clean dry compressed air or vacuum cleaning. Touch up of shop primers with primer as specified. Do not apply paint until prepared surfaces have been accepted by Departmental Representative. Method of application to be as approved by Departmental Representative . Apply paint by brush, roller or air sprayer. Conform to manufacturer's application instructions unless specified otherwise. Brush and Roller Application: .1 Apply paint in uniform layer using brush and/or roller type suitable for application. .2 Work paint into cracks, crevices and corners. .3 Paint surfaces and corners not accessible to brush using spray, daubers and/or sheepskins. Paint surfaces and corners not accessible to roller using brush, daubers or sheepskins. .4 Brush and/or roll out runs and sags, and over-lap marks. Rolled surfaces free of roller tracking and heavy stipple. .5 Remove runs, sags and brush marks from finished work and repaint. Spray application: .1 Provide and maintain equipment that is suitable for intended purpose, capable of atomizing paint to be applied, and equipped with suitable pressure regulators and gauges. .2 Keep paint ingredients properly mixed in containers during paint application either by continuous mechanical agitation or by intermittent agitation as frequently as necessary. .3 Apply paint in uniform layer, with overlapping at edges of spray pattern. Back roll first coat application. .4 Brush out immediately all runs and sags. .5 Use brushes and rollers to work paint into cracks, crevices and places which are not adequately painted by spray. Use dipping, sheepskins or daubers only when no other

.7

.8 .9

3.5 APPLICATION

.1

.2

.3

.4

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 12

method is practical in places of difficult access. .5 Apply coats of paint continuous film of uniform thickness. Repaint thin spots or bare areas before next coat of paint is applied. Allow surfaces to dry and properly cure after cleaning and between subsequent coats for minimum time period as recommended by manufacturer. Sand and dust between coats to remove visible defects. Finish surfaces both above and below sight lines as specified for surrounding surfaces, including such surfaces as tops of interior cupboards and cabinets and projecting ledges. Finish inside of cupboards and cabinets as specified for outside surfaces. Finish closets and alcoves as specified for adjoining rooms. Finish top, bottom, edges and cutouts of doors after fitting as specified for door surfaces. Paint finished area exposed conduits, piping, hangers, ductwork and other mechanical and electrical equipment with colour and finish to match adjacent surfaces, except as indicated. Boiler room, mechanical and electrical rooms: paint exposed conduits, piping, hangers, ductwork and other mechanical and electrical equipment. Other unfinished areas: leave exposed conduits, piping, hangers, ductwork and other mechanical and electrical equipment in original finish and touch up scratches and marks. Touch up scratches and marks on factory painted finishes and equipment with paint as supplied by manufacturer of equipment. Do not paint over nameplates. Keep sprinkler heads free of paint. Paint inside of ductwork where visible behind grilles, registers and diffusers with primer and one coat of matt black paint. Paint fire protection piping red. Paint disconnect switches for fire alarm system and exit light systems in red enamel.

.6

.7 .8

.9

.10

.11

3.6 MECHANICAL/ ELECTRICAL EQUIPMENT

.1

.2

.3

.4

.5 .6 .7

.8 .9

Project No. R.050134.002

INTERIOR PAINTING

Section 09 91 23 Page 13

.10 .11

Paint natural gas piping yellow. Paint both sides and edges of backboards for telephone and electrical equipment before installation. Leave equipment in original finish except for touch-up as required, and paint conduits, mounting accessories and other unfinished items. Do not paint interior transformers and substation equipment. Walls: no defects visible from a distance of 1000 mm at 90 degrees to surface. Ceilings: no defects visible from floor at 45 degrees to surface when viewed using final lighting source. Final coat to exhibit uniformity of colour and uniformity of sheen across full surface area. Field inspection of painting operations to be carried out be independent inspection firm as designated by Departmental Representative. Advise Departmental Representative when surfaces and applied coating is ready for inspection. Do not proceed with subsequent coats until previous coat has been approved. Cooperate with inspection firm and provide access to areas of work. Retain purchase orders, invoices and other documents to prove conformance with noted MPI requirements when requested by Departmental Representative. Clean and re-install hardware items removed before undertaken painting operations. Remove protective coverings and warning signs as soon as practical after operations cease. Remove paint splashings on exposed surfaces that were not painted. Remove smears and spatter immediately as operations progress, using compatible solvent. Protect freshly completed surfaces from paint droppings and dust to approval of Departmental Representative. Avoid scuffing newly applied paint. Restore areas used for storage, cleaning, mixing and handling of paint to clean condition as approved by Departmental Representative.

.12

3.7 SITE TOLERANCES

.1

.2

.3

3.8 FIELD QUALITY CONTROL

.1

.2

.3

.4

3.9 RESTORATION

.1

.2

.3

.4

.5

Project No. R.050134.002

WIRE MESH PARTITIONS

Section 10 22 13 Page 1

PART 1 - GENERAL 1.1 RELATED REQUIREMENTS 1.2 REFERENCES


.1 Section 09 22 16 - Non-structural Metal Framing.

.1

American Society for Testing and Materials International (ASTM) .1 ASTM A 653/A 653M-01a, Standard Specification for Steel Sheet, Zinc-Coated, (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process. Canadian General Standards Board (CGSB) .1 CAN/CGSB-1.81-M90, Air Drying and Baking Alkyd Primer for Vehicles and Equipment. .2 CAN/CGSB-1.88-92, Gloss Alkyd Enamel, Air Drying and Baking. .3 CAN/CGSB-1.104-M91, Semigloss Alkyd, Air Drying and Baking Enamel. Canadian Standards Association (CSA International) .1 CSA-G40.20-04/G40.21-02, General Requirements for Rolled or Welded Structural Quality Steel/Structural Quality Steel. .2 CAN/CSA-G164-M92(R2003), Hot Dip Galvanizing of Irregularly Shaped Articles. .3 CSA W59-03, Welded Steel Construction (Metal Arc Welding). Green Seal Environmental Standards .1 Standard GC-03-93, Anti-Corrosive Paints. .2 Standard GS-11-97, Architectural Paints. Health Canada/Workplace Hazardous Materials Information System (WHMIS) .1 Material Safety Data Sheets (MSDS). South Coast Air Quality Management District (SCAQMD), California State .1 SCAQMD Rule 1113-04, Architectural Coatings. The Master Painters Institute (MPI) .1 Architectural Painting Specification Manual February 2004. .1 MPI # 76, Quick Dry Alkyd Metal Primer. .2 MPI # 81, Machinery Enamel. .3 MPI # 96, Quick Dry Enamel Gloss. Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Submit manufacturer's printed product

.2

.3

.4

.5

.6

.7

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

.2

Project No. R.050134.002

WIRE MESH PARTITIONS

Section 10 22 13 Page 2

literature for wire mesh partitions or components, specifications and datasheet and include product characteristics, performance criteria, physical size, finish and limitations. .2 Submit two copies WHMIS MSDS - Material Safety Data Sheets in accordance with Section 02 81 01 Hazardous Materials. .3 Shop Drawings: .1 Indicate partition panel modules and types, materials, gauges, finishes, door and other openings, hardware, fastening methods to adjacent structure, ceiling details, and assembly methods. Samples: .1 Submit duplicate 300 x 300 mm samples of each type partition and colour and finish on actual base metal. .2 Sample to show basic construction and finishes. .3 Erect trial assembly of at least two modules of each type partition, on site where directed by Departmental Representative. Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements. Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

.4

1.4 DELIVERY, STORAGE AND HANDLING

.1

.2

PART 2 - PRODUCTS 2.1 MATERIALS


.1 Partition mesh: galvanized. .1 Expanded metal mesh: thickness MW 9.1, diamond size 20 mm x 40 mm, provide in flat sheets. Welding materials: to CSA W59. Bolts, fasteners and fastening hardware: manufacturer's standard to suit design and application.

.2 .3

2.2 FABRICATION

.1

Panels: .1 Fabricate panels 2400 x 1200 mm and special sizes or shapes as required consisting of wire mesh secured to metal studs as indicated.

PART 3 - EXECUTION 3.1 MANUFACTURER'S INSTRUCTIONS


.1 Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheets.

Project No. R.050134.002

WIRE MESH PARTITIONS

Section 10 22 13 Page 3

3.2 ERECTION

.1

Install mesh enclosures in accordance with manufacturer's printed instructions. Erect enclosures plumb, level, straight, rigidly supported, and securely fastened to abutting surfaces, free from superimposed loads. Fix to masonry and concrete using lag bolts and shields; to hollow walls using bolts and toggle type anchors; to steel supports with bolts in threaded holes or spot welds. .1 Locate fasteners on interior side where possible for maximum security. On completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment.

.2

.3

3.3 CLEANING

.1

Project No. R.050134.002

COMMON WORK RESULTS FOR MECHANICAL

Section 21 05 01 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2 .3

Section 01 33 00 - Submittal Procedures. Section 01 78 00 - Closeout Submittals. Section 23 05 93 - Testing, Adjusting and Balancing for HVAC. Section 01 35 29.06 - Health and Safety Requirements. Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.4

.5

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submittals: in accordance with Section 01 33 00 Submittal Procedures. Shop drawings to show: .1 Mounting arrangements. .2 Operating and maintenance clearances. Shop drawings and product data accompanied by: .1 Detailed drawings of bases, supports, and anchor bolts. .2 Acoustical sound power data, where applicable. .3 Points of operation on performance curves. .4 Manufacturer to certify current model production. .5 Certification of compliance to applicable codes. In addition to transmittal letter referred to in Section 01 33 00 - Submittal Procedures: use MCAC "Shop Drawing Submittal Title Sheet". Identify section and paragraph number. Closeout Submittals: .1 Provide operation and maintenance data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals. Operation and maintenance manual approved by, .2 and final copies deposited with, Departmental Representative before final inspection. .3 Operation data to include: .1 Control schematics for systems including environmental controls. .2 Description of systems and their controls. .3 Description of operation of systems at various loads together with reset schedules and seasonal variances.

.2

.3

.4

.5

Project No. R.050134.002

COMMON WORK RESULTS FOR MECHANICAL

Section 21 05 01 Page 2

.4

.5

.6

.7

.8

.9

.4 Operation instruction for systems and component. .5 Description of actions to be taken in event of equipment failure. Maintenance data to include: .1 Servicing, maintenance, operation and trouble-shooting instructions for each item of equipment. .2 Data to include schedules of tasks, frequency, tools required and task time. Performance data to include: .1 Equipment manufacturer's performance datasheets with point of operation as left after commissioning is complete. .2 Equipment performance verification test results. .3 Special performance data as specified. .4 Testing, adjusting and balancing reports as specified in Section 23 05 93 Testing, Adjusting and Balancing for HVAC. Approvals: .1 Submit 2 copies of draft Operation and Maintenance Manual to Departmental Representative for approval. Submission of individual data will not be accepted unless directed by Departmental Representative. .2 Make changes as required and re-submit as directed by Departmental Representative. Additional data: .1 Prepare and insert into operation and maintenance manual additional data when need for it becomes apparent during specified demonstrations and instructions. Site records: .1 Departmental Representative will provide 1 set of reproducible mechanical drawings. Provide sets of white prints as required for each phase of work. Mark changes as work progresses and as changes occur. Include changes to existing mechanical systems, control systems and low voltage control wiring. .2 Transfer information weekly to reproducibles, revising reproducibles to show work as actually installed. Use different colour waterproof ink for .3 each service. .4 Make available for reference purposes and inspection. As-built drawings: .1 Prior to start of Testing, Adjusting and Balancing for HVAC, finalize production of as-built drawings. .2 Identify each drawing in lower right hand corner in letters at least 12 mm high as follows: - "AS BUILT DRAWINGS: THIS DRAWING

Project No. R.050134.002

COMMON WORK RESULTS FOR MECHANICAL

Section 21 05 01 Page 3

HAS BEEN REVISED TO SHOW MECHANICAL SYSTEMS AS INSTALLED" (Signature of Contractor) (Date). .3 Submit to Departmental Representative for approval and make corrections as directed. .4 Perform testing, adjusting and balancing for HVAC using as-built drawings. .5 Submit completed reproducible as-built drawings with Operating and Maintenance Manuals. .10 Submit copies of as-built drawings for inclusion in final TAB report.

1.3 QUALITY ASSURANCE

.1

Health and Safety Requirements: do construction occupational health and safety in accordance with Section 01 35 29.06 - Health and Safety Requirements.

1.4 DELIVERY, STORAGE, AND HANDLING

.1

Waste Management and Disposal: .1 Construction/Demolition Waste Management and Disposal: separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

PART 2 - PRODUCTS

.1

Not used.

PART 3 - EXECUTION

3.1 PAINTING REPAIRS AND RESTORATION

.1

Prime and touch up marred finished paintwork to match original. Restore to new condition, finishes which have been damaged.

.2

3.2

CLEANING

.1

Clean interior and exterior of all systems including strainers. Vacuum interior of ductwork.

3.3

DEMONSTRATION

.1

Departmental Representative will use equipment and systems for test purposes prior to acceptance. Supply labour, material, and instruments required for testing.

Project No. R.050134.002

COMMON WORK RESULTS FOR MECHANICAL

Section 21 05 01 Page 4

.2

Supply tools, equipment and personnel to demonstrate and instruct operating and maintenance personnel in operating, controlling, adjusting, trouble-shooting and servicing of all systems and equipment during regular work hours, prior to acceptance. Use operation and maintenance manual, as-built drawings, and audio visual aids as part of instruction materials. Instruction duration time requirements as specified in appropriate sections.

.3

.4

3.4

PROTECTION

.1

Protect equipment and systems openings from dirt, dust, and other foreign materials with materials appropriate to system.

END OF SECTION

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2 .3 .4

Section 01 33 00 - Submittal Procedures. Section 01 78 00 - Closeout Submittals. Section 01 61 00 - Common Product Requirements. Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

1.2

REFERENCES

.1

National Fire Prevention Association (NFPA) .1 NFPA 13-2013, Standard for the Installation of Sprinkler Systems. .2 NFPA 25-2011, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Provide manufacturer's printed product literature and data sheets, and include product characteristics, performance criteria, physical size, finish and limitations. Shop Drawings: .1 Indicate: .1 Materials. .2 Finishes. .3 Method of anchorage .4 Number of anchors. .5 Supports. .6 Reinforcement. .7 Assembly details. .8 Accessories. Test reports: .1 Submit certified test reports for wet pipe fire protection sprinkler systems from approved independent testing laboratories, indicating compliance with specifications for specified performance characteristics and physical properties.

.2

.3

.4

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 2

.5

Certificates: .1 Submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties. Manufacturers' Instructions: .1 Provide manufacturer's installation instructions.

.6

1.4 CLOSEOUT SUBMITTALS

.1

Provide operation, maintenance and engineering data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals in accordance with ANSI/NFPA 20. Manufacturer's Catalog Data, including specific model, type, and size for: .1 Pipe and fittings. .2 Sprinkler heads. .3 Pipe hangers and supports. Drawings: .1 Sprinkler heads and piping system layout. .1 Prepare 760 mm by 1050 mm detail working drawings of system layout in accordance with NFPA 13, "Working Drawings (Plans)". .2 Show data essential for proper installation of each system. Design Data: .1 Calculations of sprinkler system design. .2 Indicate type and design of each system and certify that each system has performed satisfactorily in the manner intended for not less than 18 months. Field Test Reports: .1 Preliminary tests on piping system. Records: .1 As-built drawings of each system. .1 After completion, but before final acceptance, submit complete set of as-built drawings of each system for record purposes. .2 Submit 760 mm by 1050 mm drawings on reproducible Mylar film with title block similar to full size contract drawings.

.2

.3

.4

.5

.6

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 3

1.5 QUALITY ASSURANCE

.1

Qualifications: .1 Installer: company or person specializing in wet sprinkler systems with documented experience approved by manufacturer. Supply grooved joint couplings, fittings, valves, grooving tools and specialties from a single manufacturer. Use date stamped castings for coupling housings, fittings, valve bodies, for quality assurance and traceability.

.2

1.6 MAINTENANCE MATERIAL SUBMITTALS

.1

Extra Materials: .1 Provide maintenance materials in accordance with Section 01 78 00 - Closeout Submittals. .2 Provide spare sprinklers and tools in accordance with NFPA 13.

1.7 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: Deliver materials to site in original factory .1 packaging, labelled with manufacturer's name, address. Storage and Protection: .1 Store materials indoors in dry location. .2 Store and protect materials from exposure to harmful weather conditions and at temperature and humidity conditions recommended by manufacturer. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

.3

.4

PART 2 - PRODUCTS

2.1 DESIGN REQUIREMENTS

.1

Design automatic wet pipe fire suppression sprinkler systems in accordance with required and advisory provisions of NFPA 13 for uniform distribution of water over design area.

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 4

.2

Include with each system materials, accessories, and equipment inside and outside building to provide each system complete and ready for use. Design and provide each system to give full consideration to blind spaces, piping, electrical equipment, ducts, and other construction and equipment in accordance with detailed shop drawings. Locate sprinkler heads in consistent pattern with ceiling grid, lights, and air supply diffusers. Devices and equipment for fire protection service: ULC approved for use in wet pipe sprinkler systems. Design systems for earthquake protection for buildings in seismic zone 3. Location of Sprinkler Heads: .1 Locate heads in relation to ceiling and spacing of sprinkler heads not to exceed that permitted by NFPA 13. .2 Uniformly space sprinklers on branch. Water Distribution: Make distribution uniform throughout the area .1 in which sprinkler heads will open. .2 Discharge from individual heads in hydraulically most remote area to be 100 % of specified density. Density of Application of Water: .1 Size pipe to provide specified density when system is discharging specified total maximum required flow. Sprinkler Discharge Area: .1 Area: hydraulically most remote m area as defined in NFPA 13.

.3

.4

.5

.6

.7

.8

.9

.10

2.2 ABOVE GROUND PIPING SYSTEMS

.1

Provide fittings for changes in direction of piping and for connections. .1 Make changes in piping sizes through tapered reducing pipe fittings, bushings will not be permitted. Perform welding in shop; field welding will not be permitted. Conceal piping in areas with suspended ceiling and.

.2

.3

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 5

2.3 PIPE, FITTINGS AND VALVES

.1

Pipe: .1 Ferrous: to NFPA 13. .2 Copper tube: to NFPA 13. Fittings and joints to NFPA 13: .1 Ferrous: screwed, welded, flanged or roll grooved. .1 Grooved joints designed with two ductile iron housing segments, pressure responsive gasket, and zinc-electroplated steel bolts and nuts. Cast with offsetting angle-pattern bolt pads for rigidity and visual pad-to-pad offset contact. .2 Copper tube: screwed, soldered, brazed, grooved. .3 Provide welded, threaded, grooved-end type fittings into which sprinkler heads, sprinkler head riser nipples, or drop nipples are threaded. .4 Plain-end fittings with mechanical couplings and fittings which use steel gripping devices to bite into pipe when pressure is applied will not be permitted. .5 Rubber gasketted grooved-end pipe and fittings with mechanical couplings are permitted in pipe sizes 32 mm and larger. .6 Fittings: ULC approved for use in wet pipe sprinkler systems. .7 Ensure fittings, mechanical couplings, and rubber gaskets are supplied by same manufacturer. .8 Side outlet tees using rubber gasketted fittings are not permitted. .9 Sprinkler pipe and fittings: metal. Valves: .1 ULC listed for fire protection service. .2 Gate valves: open by counterclockwise rotation. Pipe hangers: .1 ULC listed for fire protection services in accordance with NFPA.

.2

.3

.4

2.4

SPRINKLER HEADS

.1

General: to NFPA 13 and ULC listed for fire services. Sprinkler Head Type: .1 Pendant chrome glass bulb type. Provide nominal 1.2 cm orifice sprinkler heads. .1 Release element of each head to be of intermediate temperature rating or higher as suitable for specific application. .2 Provide sprinkler heads as indicated.

.2

.3

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 6

.3 Deflector: not more than 75 mm below suspended ceilings.

2.5 ESCUTCHEON PLATES

.1

Provide one piece split hinge type metal plates for piping passing through walls, floors, and ceilings in exposed spaces.

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheet.

3.2

INSTALLATION

.1

Install, inspect and test to acceptance in accordance with NFPA 13 and NFPA 25.

3.3 PIPE INSTALLATION

.1

Install piping straight and true to bear evenly on hangers and supports. Do not hang piping from plaster ceilings. Keep interior and ends of new piping and existing piping thoroughly cleaned of water and foreign matter. Keep piping systems clean during installation by means of plugs or other approved methods. When work is not in progress, securely close open ends of piping to prevent entry of water and foreign matter. Inspect piping before placing into position.

.2

.3

.4

3.4

DISINFECTION

.1 .2

Disinfect new piping and existing piping. Fill piping systems with solution containing minimum of 50 parts per million of chlorine and allow solution to stand for minimum of 24 hours. Flush solution from systems with clean water until maximum residual chlorine content is not greater than 0.2 part per million or residual chlorine content of domestic water supply.

.3

Project No. R.050134.002

WET PIPE SPRINKLER SYSTEMS

Section 21 13 13 Page 7

.4

Obtain at least two consecutive satisfactory bacteriological samples from piping, analyzed by certified laboratory, and submit results prior to piping being placed into service.

3.5 FIELD QUALITY CONTROL

.1

Site Test, Inspection: .1 Perform test to determine compliance with specified requirements in presence of Departmental Representative .2 Test, inspect, and approve piping before covering or concealing. .3 Preliminary Tests: Hydrostatically test each system at 200 .1 psig for a 2 hour period with no leakage or reduction in pressure. .2 Flush piping with potable water in accordance with NFPA 13. .3 Piping above suspended ceilings: tested, inspected, and approved before installation of ceilings. .4 Formal Tests and Inspections: .1 Do not submit request for formal test and inspection until preliminary test and corrections are completed and approved. .2 Submit written request for formal inspection at least 15 days prior to inspection date. .3 Repeat required tests as directed. .4 Correct defects and make additional tests until systems comply with contract requirements. .5 Furnish appliances, equipment, instruments, connecting devices, and personnel for tests. Authority of Jurisdiction, will witness .6 formal tests and approve systems before they are accepted.

3.6

CLEANING

.1

Remove surplus materials, excess materials, rubbish, tools and equipment. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management.

.2

END OF SECTION

Project No. R.050134.002

DRY CHEMICAL FIRE EXTINGUISHER

Section 21 24 00 Page 1

PART 1 - GENERAL

1.1 RELATED REQUIREMENTS

.1 .2 .3 .4

Section 01 33 00 - Submittal Procedures. Section 01 78 00 - Closeout Submittals. Section 01 61 00 - Common Product Requirements. Section 01 74 21 - Construction/Demolition Waste Management.

1.2

REFERENCES

.1

Department of National Defence Canada (DND)/Infrastructure and Environment/Construction and Property Services .1 Canadian Forces Fire Marshal (CFFM). National Fire Prevention Association (NFPA) .1 NFPA 10-13, Standard for Portable Fire Extinguishers.

.2

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for fire extinguishing systems and include product characteristics, performance criteria, physical size, finish and limitations.

.2

1.4 CLOSEOUT SUBMITTALS

.1

Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for dry chemical fire extinguishing systems for incorporation into manual.

.2

1.5 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions.

.2

Delivery and Acceptance Requirements: deliver materials to site in original factory packaging,

Project No. R.050134.002

DRY CHEMICAL FIRE EXTINGUISHER

Section 21 24 00 Page 2

labelled with manufacturer's name and address. .3 Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect fire extinguishing systems from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan Waste Reduction Workplan in accordance with Section 01 74 21 Construction/Demolition Waste Management.

.4

PART 2 - PRODUCTS

2.1

FIRE EXTINGUISHER .1

FE-1: Shall be 10 lb multipurpose dry chemical extinguisher, complete with heavy duty wall mounting bracket.

PART 3 - EXECUTION

3.1

INSTALLATION

.1

Install in accordance with UL listing.

END OF SECTION

Project No. R.050134.002

USE OF HVAC SYSTEMS DURING CONSTRUCTION

Section 23 05 01 Page 1

PART 1 - GENERAL

1.1

SUMMARY

.1

Section Includes: .1 Use of mechanical systems during construction.

1.2

USE OF SYSTEMS

.1

Use of new and or existing permanent heating and or ventilating systems for supplying temporary heat or ventilation is permitted only under following conditions:. .1 Entire system is complete, pressure tested, cleaned, flushed out. .2 Building has been closed in, areas to be heated/ventilated are clean and will not thereafter be subjected to dust-producing processes. .3 There is no possibility of damage. .4 Supply ventilation systems are protected by 60 % filters, inspected daily, changed every week 2 weeks or more frequently as required. .5 Return systems have approved filters over openings, inlets, outlets. .6 Systems will be: .1 Operated as per manufacturer's recommendations and instructions. .2 Operated by Contractor. .3 Monitored continuously by Contractor. .7 Warranties and guarantees are not relaxed. .8 Regular preventive and other manufacturers recommended maintenance routines are performed by Contractor at own expense and under supervision of Departmental Representative. .9 Refurbish entire system before static completion; clean internally and externally, restore to "as- new" condition, replace filters in air systems.

PART 2 - PRODUCTS

2.1

NOT USED

.1

Not Used.

Project No. R.050134.002

USE OF HVAC SYSTEMS DURING CONSTRUCTION

Section 23 05 01 Page 2

PART 3 - EXECUTION

3.1

NOT USED

.1

Not Used.

END OF SECTION

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 1

PART 1 - GENERAL

1.1

SUMMARY

.1

TAB is used throughout this Section to describe the process, methods and requirements of testing, adjusting and balancing for HVAC. TAB means to test, adjust and balance to perform in accordance with requirements of Contract Documents and to do other work as specified in this section.

.2

1.2 QUALIFICATIONS OF TAB PERSONNEL

.1

Submit names of personnel to perform TAB to Departmental Representative within 90 days of award of contract. Provide documentation confirming qualifications, successful experience. TAB: performed in accordance with the requirements of standard under which TAB Firm's qualifications are approved: .1 Associated Air Balance Council, (AABC) National Standards for Total System Balance, MN-12002. .2 National Environmental Balancing Bureau (NEBB) TABES, Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems-1998. Sheet Metal and Air Conditioning Contractors' .3 National Association (SMACNA), HVAC TAB HVAC Systems - Testing, Adjusting and Balancing-2002. Recommendations and suggested practices contained in the TAB Standard: mandatory. Use TAB Standard provisions, including checklists, and report forms to satisfy Contract requirements. Use TAB Standard for TAB, including qualifications for TAB Firm and Specialist and calibration of TAB instruments. Where instrument manufacturer calibration recommendations are more stringent than those listed in TAB Standard, use manufacturer's recommendations. TAB Standard quality assurance provisions such as performance guarantees form part of this contract. .1 For systems or system components not covered in TAB Standard, use TAB procedures developed by TAB Specialist.

.2

.3

.4

.5

.6

.7

.8

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 2

.2 Where new procedures, and requirements, are applicable to Contract requirements have been published or adopted by body responsible for TAB Standard used (AABC, NEBB, or TABB), requirements and recommendations contained in these procedures and requirements are mandatory.

1.3

PURPOSE OF TAB

.1

Test to verify proper and safe operation, determine actual point of performance, evaluate qualitative and quantitative performance of equipment, systems and controls at design, average and low loads using actual or simulated loads Adjust and regulate equipment and systems to meet specified performance requirements and to achieve specified interaction with other related systems under normal and emergency loads and operating conditions. Balance systems and equipment to regulate flow rates to match load requirements over full operating ranges.

.2

.3

1.4

EXCEPTIONS

.1

TAB of systems and equipment regulated by codes, standards to satisfaction of authority having jurisdiction.

1.5

CO-ORDINATION

.1

Schedule time required for TAB (including repairs, re-testing) into project construction and completion schedule to ensure completion before acceptance of project. Do TAB of each system independently and subsequently, where interlocked with other systems, in unison with those systems.

.2

1.6

PRE-TAB REVIEW

.1

Review contract documents before project construction is started and confirm in writing to Departmental Representative adequacy of provisions for TAB and other aspects of design and installation pertinent to success of TAB. Review specified standards and report to Departmental Representative in writing proposed procedures which vary from standard.

.2

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 3

.3

During construction, co-ordinate location and installation of TAB devices, equipment, accessories, measurement ports and fittings.

1.7

START-UP

.1

Follow start-up procedures as recommended by equipment manufacturer unless specified otherwise. Follow special start-up procedures specified elsewhere in Division 23.

.2

1.8 OPERATION OF SYSTEMS DURING TAB

.1

Operate systems for length of time required for TAB and as required by Departmental Representative for verification of TAB reports.

1.9

START OF TAB

.1

Notify Departmental Representative 7 days prior to start of TAB. Start TAB when building is essentially completed. Installation of ceilings, doors, windows, other construction affecting TAB. Application of weatherstripping, sealing, and caulking. Pressure, leakage, other tests specified elsewhere Division 23. Provisions for TAB installed and operational. Start-up, verification for proper, normal and safe operation of mechanical and associated electrical and control systems affecting TAB including but not limited to: .1 Proper thermal overload protection in place for electrical equipment. .2 Air systems: .1 Filters in place, clean. .2 Duct systems clean. .3 Ducts, air shafts, ceiling plenums are airtight to within specified tolerances. .4 Correct fan rotation. .5 Access doors, installed, closed. .6 Outlets installed, volume control dampers open.

.2 .3

.4

.5

.6 .7

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 4

1.10 APPLICATION TOLERANCES

.1

Do TAB to following tolerances of design values: .1 HVAC systems: plus 5 %, minus 5 %.

1.11 ACCURACY TOLERANCES

.1

Measured values accurate to within plus or minus 2 % of actual values.

1.12

INSTRUMENTS

.1

Prior to TAB, submit to Departmental Representative list of instruments used together with serial numbers. Calibrate in accordance with requirements of most stringent of referenced standard for either applicable system or HVAC system. Calibrate within 3 months of TAB. Provide certificate of calibration to Departmental Representative DCC Representative Consultant.

.2

.3

1.13 PRELIMINARY TAB REPORT

.1

Submit for checking and approval of Departmental Representative, prior to submission of formal TAB report, sample of rough TAB sheets. Include: .1 Details of instruments used. .2 Details of TAB procedures employed. .3 Calculations procedures. .4 Summaries.

1.14

TAB REPORT

.1 .2

Format in accordance with referenced standard. TAB report to show results in SI units and to include: .1 Project record drawings. .2 System schematics. Submit 6 copies of TAB Report to Departmental Representative DCC Representative Consultant for verification and approval, in English French both official languages in D-ring binders, complete with index tabs.

.3

1.15

VERIFICATION

.1

Reported results subject to verification by Departmental Representative. Provide personnel and instrumentation to verify up to 30 % of reported results.

.2

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 5

.3

Number and location of verified results as directed by Departmental Representative. Pay costs to repeat TAB as required to satisfaction of Departmental Representative.

.4

1.16

SETTINGS

.1

After TAB is completed to satisfaction of Departmental Representative, replace drive guards, close access doors, lock devices in set positions, ensure sensors are at required settings. Permanently mark settings to allow restoration at any time during life of facility. Do not eradicate or cover markings.

.2

1.17 TAB

COMPLETION OF

.1

TAB considered complete when final TAB Report received and approved by Departmental Representative.

1.18

AIR SYSTEMS

.1

Standard: TAB to most stringent of this section or TAB standards of AABC NEBB SMACNA ASHRAE. Do TAB of systems, equipment, components, controls specified Division 23. Qualifications: personnel performing TAB current member in good standing of AABC or NEBB qualified to standards of AABC or NEBB. Quality assurance: perform TAB under direction of supervisor qualified by to standards of AABC or NEBB. Measurements: to include as appropriate for systems, equipment, components, controls: air velocity, static pressure, flow rate, pressure drop (or loss), duct cross-sectional area, RPM, electrical power, voltage, noise, vibration. Locations of equipment measurements: to include as appropriate: .1 Inlet and outlet of dampers, filter, coil, humidifier, fan, other equipment causing changes in conditions. .2 At controllers, controlled device.

.2

.3

.4

.5

.6

Project No. R.050134.002

TESTING, ADJUSTING AND BALANCING FOR HVAC

Section 23 05 93 Page 6

.7

Locations of systems measurements to include as appropriate: main ducts, main branch, sub-branch, run-out (or grille, register or diffuser).

PART 2 - PRODUCTS

2.1

NOT USED

.1

Not used.

PART 3 - EXECUTION

3.1

NOT USED

.1

Not used.

END OF SECTION

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 1

PART 1 - GENERAL

1.1

SUMMARY

.1

Section Includes: .1 Materials and installation of low-pressure metallic ductwork, joints and accessories. Related Requirements .1 Section 01 33 00 - Submittal Procedures. .2 Section 01 35 29.06 - Health and Safety Requirements. .3 Section 01 47 19 - Construction/Demolition Waste Management and Disposal.

.2

1.2

REFERENCES

.1

American Society of Heating, Refrigerating and AirConditioning Engineers, Inc. (ASHRAE). American Society for Testing and Materials International, (ASTM). .1 ASTM A 480/A 480M-03c, Standard Specification for General Requirements for Flat-Rolled Stainless and Heat-Resisting Steel Plate, Sheet and Strip. .2 ASTM A 635/A 635M-02, Standard Specification for Steel, Sheet and Strip, Heavy-Thickness Coils, Carbon, Hot Rolled. .3 ASTM A 653/A 653M-03, Standard Specification for Steel Sheet, Zinc Coated (Galvanized) or ZincIron Alloy Coated (Galvannealed) by the Hot-Dip Process. Department of Justice Canada (Jus). Canadian Environmental Protection Act (CEPA), .1 1999, c. 33 . Health Canada/Workplace Hazardous Materials Information System (WHMIS). .1 Material Safety Data Sheets (MSDS). National Fire Protection Association (NFPA). .1 NFPA 90A-02, Standard for the Installation of Air-Conditioning and Ventilating Systems. .2 NFPA 90B-02, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA). .1 SMACNA HVAC Duct Construction Standards Metal and Flexible, 2nd Edition 1995 and Addendum No. 1, 1997. .2 SMACNA HVAC Air Duct Leakage Test Manual, 1985, 1st Edition. .3 IAQ Guideline for Occupied Buildings Under

.2

.3

.4

.5

.6

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 2

Construction 1995, 1st Edition. .7 Transport Canada (TC). .1 Transportation of Dangerous Goods Act (TDGA), 1992, c. 34.

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit shop drawings and product data in accordance with Section 01 33 00 - Submittal Procedures.

1.4 QUALITY ASSURANCE

.1

Certification of Ratings: .1 Catalogue or published ratings shall be those obtained from tests carried out by manufacturer or independent testing agency signifying adherence to codes and standards. Health and Safety: .1 Do construction occupational health and safety in accordance with Section 01 35 29.06 Health and Safety Requirements.

.2

1.5 DELIVERY, STORAGE AND HANDLING

.1

Protect on site stored or installed absorptive material from moisture damage. Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 47 19 Construction/Demolition Waste Management and Disposal. .2 Remove from site and dispose of packaging materials at appropriate recycling facilities. .3 Collect and separate for disposal paper plastic polystyrene corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan. Separate for reuse and recycling and place in .4 designated containers Steel Metal Plastic waste in accordance with Waste Management Plan. Place materials defined as hazardous or toxic .5 in designated containers. .6 Handle and dispose of hazardous materials in accordance with CEPA, TDGA, Regional and Municipal regulations. .7 Fold up metal and plastic banding, flatten and place in designated area for recycling.

.2

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 3

PART 2 - PRODUCTS

2.1 SEAL CLASSIFICATION

.1

Classification as follows:

Maximum Pressure Pa 500 250 125 125


.2

SMACNA Seal Class C C C Unsealed

Seal classification: .1 Class A: longitudinal seams, transverse joints, duct wall penetrations and connections made airtight with sealant and tape. .2 Class B: longitudinal seams, transverse joints and connections made airtight with sealant tape or combination thereof. .3 Class C: transverse joints and connections made air tight with gaskets sealant tape or combination thereof. Longitudinal seams unsealed. .4 Unsealed seams and joints.

2.2

SEALANT

.1

Sealant: oil resistant, water borne, polymer type flame resistant duct sealant. Temperature range of minus 30 degrees C to plus 93 degrees C.

2.3

TAPE

.1

Tape: polyvinyl treated, open weave fiberglass tape, 50 mm wide.

2.4

DUCT LEAKAGE

.1

In accordance with SMACNA HVAC Air Duct Leakage Test Manual.

2.5

FITTINGS

.1 .2

Fabrication: to SMACNA. Radiused elbows. .1 Rectangular: standard radius short radius with single thickness turning vanes Centreline radius: 1.5 times width of duct . .2 Round: smooth radius five piece. Centreline radius: 1.5 times diameter.

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 4

.3

Mitred elbows, rectangular: .1 To 400 mm: with single double thickness turning vanes. .2 Over 400 mm: with double thickness turning vanes. Branches: .1 Rectangular main and branch: with radius on branch 1.5 times width of duct 45 degrees entry on branch. .2 Round main and branch: enter main duct at 45 degrees with conical connection. .3 Provide volume control damper in branch duct near connection to main duct. .4 Main duct branches: with splitter damper. Transitions: .1 Diverging: 20 degrees maximum included angle. .2 Converging: 30 degrees maximum included angle. Offsets: .1 Full short radiused elbows as indicated. Obstruction deflectors: maintain full crosssectional area. .1 Maximum included angles: as for transitions.

.4

.5

.6

.7

2.6

FIRE STOPPING

.1

Retaining angles around duct, on both sides of fire separation. Fire stopping material and installation must not distort duct.

.2

2.7 GALVANIZED STEEL

.1

Lock forming quality: to ASTM A 653/A 653M, Z90 zinc coating. Thickness, fabrication and reinforcement: to SMACNA. Joints: to SMACNA proprietary manufactured duct joint. Proprietary manufactured flanged duct joint to be considered to be a class A seal.

.2

.3

2.8 HANGERS AND SUPPORTS

.1

Hangers and Supports: .1 Strap hangers: of same material as duct but next sheet metal thickness heavier than duct. .1 Maximum size duct supported by strap hanger: 500 mm.

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 5

.2 Hanger configuration: to ASHRAE and SMACNA. .3 Hangers: black galvanized steel angle with black galvanized steel rods to ASHRAE and SMACNA following table:

Duct Size (mm) up to 750 751 to 1050 1051 to 1500 1501 to 2100 2101 to 2400 2401 and over
.4

Angle Size (mm) 25 x 25 x 3 40 x 40 x 3 40 x 40 x 3 50 x 50 x 3 50 x 50 x 5 50 x 50 x 6

Rod Size (mm) 6 6 10 10 10 10

Upper hanger attachments: .1 For concrete: manufactured concrete inserts. .2 For steel joist:manufactured joist clampsteel plate washer. .3 For steel beams: manufactured beam clamps:

PART 3 - EXECUTION

3.1

GENERAL

.1

Do work in accordance with NFPA 90A NFPA 90B ASHRAE SMACNA as indicated. Do not break continuity of insulation vapour barrier with hangers or rods. .1 Insulate strap hangers 100 mm beyond insulated duct Ensure diffuser is fully seated. Support risers in accordance with SMACNA as indicated. Install breakaway joints in ductwork on sides of fire separation. Install proprietary manufactured flanged duct joints in accordance with manufacturer's instructions. Manufacture duct in lengths and diameter to accommodate installation of acoustic duct lining.

.2

.3

.4

.5

.6

Project No. R.050134.002

METAL DUCTS - LOW PRESSURE TO 500 PA

Sect 23 31 13.01 Page 6

3.2

HANGERS

.1 .2

Strap hangers: install in accordance with SMACNA. Angle hangers: complete with locking nuts and washers. Hanger spacing: in accordance with ASHRAE SMACNA as follows:

.3

Duct Size (mm) to 1500 1501 and over

Spacing (mm) 3000 2500

3.3 SEALING AND TAPING

.1

Apply sealant to outside of joint to manufacturer's recommendations. Bed tape in sealant and recoat with minimum of one coat of sealant to manufacturers recommendations.

.2

3.4

LEAKAGE TESTS

.1

In accordance with SMACNA HVAC Duct Leakage Test Manual. Do leakage tests in sections. Make trial leakage tests as instructed to demonstrate workmanship. Do not install additional ductwork until trial test has been passed. Test section minimum of 30 m long with not less than three branch takeoffs and two 90 degrees elbows. Complete test before performance insulation or concealment Work.

.2 .3

.4

.5

.6

END OF SECTION

Project No. R.050134.002

AIR DUCT ACCESSORIES

Section 23 33 00 Page 1

PART 1 - GENERAL

1.1

SUMMARY

.1

Section Includes: .1 Materials and installation for duct accessories including flexible connections, access doors, vanes and collars. Related Requirements .1 Section 01 33 00 - Submittal Procedures. .2 Section 01 78 00 - Closeout Submittals.. .3 Section 01 35 29.06 - Health and Safety Requirements. .4 Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

1.2

REFERENCES

.1

Health Canada/Workplace Hazardous Materials Information System (WHMIS). .1 Material Safety Data Sheets (MSDS). Sheet Metal and Air Conditioning Contractors' National Association (SMACNA). .1 SMACNA - HVAC Duct Construction Standards Metal and Flexible, 95.

.2

1.3 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submittals in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's printed product literature, specifications and data sheet. Indicate the following: .1 Flexible connections. Test Reports: submit certified test reports from approved independent testing laboratories indicating compliance with specifications for specified performance characteristics and physical properties. .1 Certification of ratings: catalogue or published ratings to be those obtained from tests carried out by manufacturer or independent testing agency signifying adherence to codes and standards. Certificates: submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties.

.2

.3

.4

Project No. R.050134.002

AIR DUCT ACCESSORIES

Section 23 33 00 Page 2

.5

Instructions: submit manufacturer's installation instructions. Manufacturer's Field Reports: manufacturer's field reports specified. Closeout submittals: submit maintenance and engineering data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals.

.6

.7

1.4 QUALITY ASSURANCE

.1

Health and Safety: .1 Do construction occupational health and safety in accordance with Section 01 35 29.06 Health and Safety Requirements.

1.5 DELIVERY, STORAGE AND HANDLING

.1

Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. .2 Remove from site and dispose of packaging materials at appropriate recycling facilities. .3 Collect and separate for disposal paper plastic polystyrene corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan (WMP). Separate for reuse and recycling and place in .4 designated containers Steel Metal Plastic waste in accordance with Waste Management Plan (WMP). .5 Divert unused metal materials from landfill to metal recycling facility as approved by Departmental Representative.

PART 2 - PRODUCTS

2.1

GENERAL

.1

Manufacture in accordance with SMACNA - HVAC Duct Construction Standards.

2.2 FLEXIBLE CONNECTIONS

.1

Frame: galvanized sheet metal frame mm thick with fabric clenched by means of double locked seams.

Project No. R.050134.002

AIR DUCT ACCESSORIES

Section 23 33 00 Page 3

.2

Material: .1 Fire resistant, self extinguishing, neoprene coated glass fabric, temperature rated at minus 40 degrees C to plus 90 degrees C, density of 1.3 kg/m3.

2.3 ACCESS DOORS IN DUCTS

.1

Non-Insulated Ducts: sandwich construction of same material as duct, one sheet metal thickness heavier, minimum 0.6 mm thick complete with sheet metal angle frame. Gaskets: neoprene foam rubber. Hardware: .1 Up to 300 x 300 mm: two sash locks complete with safety chain. .2 301 to 450 mm: four sash locks complete with safety chain. .3 451 to 1000 mm: piano hinge and minimum two sash locks. .4 Doors over 1000 mm: piano hinge and two handles operable from both sides. .5 Hold open devices. .6 300 x 300 mm glass viewing panels.

.2 .3

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and data sheet.

3.2

INSTALLATION

.1

Flexible Connections: .1 Install in following locations: .1 Inlets and outlets to supply air units and fans. .2 Inlets and outlets of exhaust and return air fans. .3 As indicated. .2 Length of connection: 100mm. .3 Minimum distance between metal parts when system in operation: 75 mm. .4 Install in accordance with recommendations of SMACNA. .5 When fan is running: Ducting on sides of flexible connection .1 to be in alignment.

Project No. R.050134.002

AIR DUCT ACCESSORIES

Section 23 33 00 Page 4

.2 Ensure slack material in flexible connection. .2 Access Doors and Viewing Panels: .1 Size: .1 600 x 600 mm for person size entry. .2 300 x 300 mm for servicing entry. .3 200 x 200 mm for viewing. .4 As indicated. .2 Locations: .1 Fire and smoke dampers. .2 Control dampers. .3 Devices requiring maintenance. .4 Required by code. .5 Reheat coils. .6 Elsewhere as indicated.

3.3 FIELD QUALITY CONTROL

.1

Manufacturer's Field Services: Have manufacturer of products, supplied under .1 this Section, review Work involved in the handling, installation/application, protection and cleaning, of its products and submit written reports, in acceptable format, to verify compliance of Work with Contract. .2 Manufacturer's Field Services: provide manufacturer's field services consisting of product use recommendations and periodic site visits for inspection of product installation in accordance with manufacturer's instructions. .3 Schedule site visits, to review Work, at stages listed: After delivery and storage of products, .1 and when preparatory Work, or other Work, on which the Work of this Section depends, is complete but before installation begins. .2 Twice during progress of Work at 25% and 60% complete. .3 Upon completion of the Work, after cleaning is carried out. .4 Obtain reports, within 3 days of review, and submit, immediately, to Departmental Representative.

3.4

CLEANING

.1

Perform cleaning operations as specified in Section and in accordance with manufacturer's recommendations. Upon completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment. END OF SECTION

.2

Project No. R.050134.002

HVAC FANS

Section 23 34 00 Page 1

PART 1 - GENERAL

1.1

SUMMARY

.1

Section Includes: .1 Fans, motors, accessories and hardware for commercial use. Related Requirements .1 Section 01 33 00 - Submittal Procedures. .2 Section 01 78 00 - Closeout Submittals. .3 Section 01 35 29.06 - Health and Safety Requirements. .4 Section 01 61 00 - Common Product Requirements. .5 Section 01 74 21 - Construction/Demolition Waste Management and Disposal. .6 Section Section 23 33 00 - Air Duct Accessories.

.2

1.2

REFERENCES

.1

Air Conditioning and Mechanical Contractors (AMCA) .1 AMCA Publication 99-2003, Standards Handbook. .2 AMCA 300-1996, Reverberant Room Method for Sound Testing of Fans. .3 AMCA 301-1990, Methods for Calculating Fan Sound Ratings from Laboratory Test Data. American National Standards Institute (ANSI)/American Society of Mechanical Engineers (ASME) .1 ANSI/AMCA 210-1999, Laboratory Methods of Testing Fans for Aerodynamic Performance Rating. Canadian General Standards Board (CGSB) .1 CAN/CGSB 1.181-99, Ready-Mixed Organic ZincRich Coating. Health Canada/Workplace Hazardous Materials Information System (WHMIS) .1 Material Safety Data Sheets (MSDS).

.2

.3

.4

1.3 SYSTEM DESCRIPTION

.1

Performance Requirements: .1 Catalogued or published ratings for manufactured items: obtained from tests carried out by manufacturer or those ordered by manufacturer from independent testing agency signifying adherence to codes and standards in force. .2 Capacity: flow rate, total static pressure, bhp W, efficiency, revolutions per minute, power, model, size, sound power data and as indicated on schedule.

Project No. R.050134.002

HVAC FANS

Section 23 34 00 Page 2

.3 Fans: statically and dynamically balanced, constructed in conformity with AMCA 99. .4 Sound ratings: comply with AMCA 301, tested to AMCA 300. Supply unit with AMCA certified sound rating seal. .5 Performance ratings: based on tests performed in accordance with ANSI/AMCA 210. Supply unit with AMCA certified rating seal, except for propeller fans smaller than 300 mm diameter.

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

Product Data: .1 Submit manufacturer's printed product literature, specifications and datasheet in accordance with Section 01 33 00 - Submittal Procedures. Include product characteristics, performance criteria, and limitations. .1 Submit two copies of Workplace Hazardous Materials Information System (WHMIS) Material Safety Data Sheets (MSDS) in accordance with Section 01 33 00 - Submittal Procedures. Shop Drawings: .1 Submit shop drawings and product data in accordance with Section 01 33 00 - Submittal Procedures. Provide : .1 Fan performance curves showing point of operation, bhp and efficiency. .2 Sound rating data at point of operation. Quality assurance submittals: submit following in accordance with Section 01 33 00 - Submittal Procedures. .1 Certificates: submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties. .2 Instructions: submit manufacturer's installation instructions. .1 Departmental Representative will make available 1 copy of systems supplier's installation instructions. Closeout Submittals: .1 Provide operation and maintenance data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals.

.2

.3

.4

.5

Project No. R.050134.002

HVAC FANS

Section 23 34 00 Page 3

1.5 QUALITY ASSURANCE

.1

Health and Safety Requirements: do construction occupational health and safety in accordance with Section 01 35 29.06 - Health and Safety Requirements.

1.6

MAINTENANCE

.1

Extra Materials: .1 Provide maintenance materials in accordance with Section 01 78 00 - Closeout Submittals. .2 Furnish list of individual manufacturer's recommended spare parts for equipment, include: .1 Bearings and seals. .2 Addresses of suppliers. .3 List of specialized tools necessary for adjusting, repairing or replacing.

1.7 DELIVERY, STORAGE, AND HANDLING

.1

Packing, shipping, handling and unloading: .1 Deliver, store and handle in accordance with Section 01 61 00 - Common Product Requirements. .2 Deliver, store and handle materials in accordance with manufacturer's written instructions. Waste Management and Disposal: .1 Construction/Demolition Waste Management and Disposal: separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

.2

PART 2 - PRODUCTS

2.1 CABINET FANS GENERAL PURPOSE

.1

Fan characteristics and construction: as centrifugal fans. Casing floor mounted Cabinet hung single or multiple wheel with DWDI centrifugal fans in factory fabricated casing complete with vibration isolators and seismic control measures, motor, variable speed V-belt drive and guard insideor outside casing. Fabricate casing of zinc coated or phosphate treated steel of mm thickness thickness as indicated reinforced and braced for rigidity. Provide removable panels for access to interior. Paint uncoated, steel parts with corrosion resistant paint to CAN/CGSB 1.181. Finish inside

.2

.3

Project No. R.050134.002

HVAC FANS

Section 23 34 00 Page 4

and out, over prime coat, with rust resistant enamel. Internally line cabinet with 50 mm thick rigid acoustic insulation, pinned and cemented, kg/m density, complete with perforated metal liner complete with metal nosings on exposed edges.

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheet.

3.2 FAN INSTALLATION

.1

Install fans as indicated, complete with resilient mountings, flexible electrical leads and flexible connections in accordance with Section 23 33 00 Air Duct Accessories. Provide sheaves and belts required for final air balance. Bearings and extension tubes to be easily accessible. Access doors and access panels to be easily accessible.

.2

.3

.4

3.3 ANCHOR BOLTS AND TEMPLATES

.1

Size anchor bolts to withstand seismic acceleration and velocity forces as specified.

3.4 CLEANING

.1

Upon completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment.

END OF SECTION

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International) .1 CSA C22.1-12, Canadian Electrical Code, Part 1 (22nd Edition), Safety Standard for Electrical Installations. .2 CSA C22.2. .3 CAN/CSA-C22.3 No. 1-01(Update March 2005), Overhead Systems. .4 CAN3-C235-83(R2000), Preferred Voltage Levels for AC Systems, 0 to 50,000 V. Electrical and Electronic Manufacturer's Association of Canada (EEMAC) .1 EEMAC 2Y-1-1958, Light Gray Colour for Indoor Switch Gear. Institute of Electrical and Electronics (IEEE)/National Electrical Safety Code Product Line (NESC) .1 IEEE SP1122-2000, The Authoritative Dictionary of IEEE Standards Terms, 7th Edition.

.2

.3

1.2 DEFINITIONS

.1

Electrical and electronic terms: unless otherwise specified or indicated, terms used in these specifications, and on drawings, are those defined by IEEE SP1122.

1.3 DESIGN REQUIREMENTS

.1 .2

Operating voltages: to CAN3-C235. Motors, electric heating, control and distribution devices and equipment to operate satisfactorily at 60 Hz within normal operating limits established by above standard. .1 Equipment to operate in extreme operating conditions established in above standard without damage to equipment. Language operating requirements: provide identification nameplates for control items in English and French. Use one nameplate for both languages. All equipment and materials indicated to be new unless otherwise noted.

.3

.4 .5

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 2

1.4 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submittals: in accordance with Section 01 33 00 Submittal Procedures. Product Data: submit WHMIS MSDS in accordance with Section 01 00 10 - General Instructions. Shop drawings: .1 Submit drawings stamped and signed by professional engineer registered or licensed in Province of Ontario, Canada. .2 Submit wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure co-ordinated installation. .3 Identify on wiring diagrams circuit terminals and indicate internal wiring for each item of equipment and interconnection between each item of equipment. .4 Indicate of drawings clearances for operation, maintenance, and replacement of operating equipment devices. .5 Submit six copies of 600 x 600 mm minimum size drawings and product data to Engineer. .6 If changes are required, notify Departmental Representative of these changes before they are made. Quality Control: in accordance with Section 01 00 10 - General Instructions. Provide CSA certified equipment and material. .1 Where CSA certified equipment and material is .2 not available, submit such equipment and material to inspection authorities for approval before delivery to site. .3 Submit test results of installed electrical systems and instrumentation. .4 Permits and fees: in accordance with General Conditions of contract. Submit, upon completion of Work, load balance .5 report as described in PART 3 - LOAD BALANCE. .6 Submit certificate of acceptance from authority having jurisdiction upon completion of Work to Departmental Representative. Manufacturer's Field Reports: submit to Departmental Representative manufacturer's written report, within 3 days of review, verifying compliance of Work and electrical system and instrumentation testing, as described in PART 3 FIELD QUALITY CONTROL.

.2

.3

.4

.5

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 3

1.5 QUALITY ASSURANCE

.1

Quality Assurance: in accordance with Section 01 00 10 - General Instructions. Qualifications: electrical Work to be carried out by qualified, licensed electricians who hold valid Master Electrical Contractor license or apprentices in accordance with authorities having jurisdiction as per the conditions of Provincial Act respecting manpower vocational training and qualification. .1 Employees registered in provincial apprentices program: permitted, under direct supervision of qualified licensed electrician, to perform specific tasks. .2 Permitted activities: determined based on training level attained and demonstration of ability to perform specific duties. Site Meetings: .1 In accordance with Section 01 00 10 - General Instructions. .2 Site Meetings: as part of Manufacturer's Field Services described in Part 3 - FIELD QUALITY CONTROL, and in appropriate NMS Section, schedule site visits, to review Work, at stages listed. After delivery and storage of products, .1 and when preparatory Work is complete but before installation begins. .2 Twice during progress of Work at 25% and 60% complete. Upon completion of Work, after cleaning .3 is carried out. Health and Safety Requirements: do construction occupational health and safety in accordance with Section 01 35 29.06 - Health and Safety Requirements.

.2

.3

.4

1.6 DELIVERY, STORAGE AND HANDLING

.1

Material Delivery Schedule: provide Departmental Representative with schedule within 2 weeks after award of Contract. Construction/Demolition Waste Management and Disposal: separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

.2

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 4

1.7 SYSTEM STARTUP

.1

Instruct Departmental Representative and operating personnel in operation, care and maintenance of systems, system equipment and components. Arrange and pay for services of manufacturer's factory service engineer to supervise start-up of installation, check, adjust, balance and calibrate components and instruct operating personnel. Provide these services for such period, and for as many visits as necessary to put equipment in operation, and ensure that operating personnel are conversant will aspects of its care and operation.

.2

.3

1.8 OPERATING INSTRUCTIONS

.1

Provide for each system and principal item of equipment as specified in technical sections for use by operation and maintenance personnel. Operating instructions to include following: .1 Wiring diagrams, control diagrams, and control sequence for each principal system and item of equipment. .2 Start up, proper adjustment, operating, lubrication, and shutdown procedures. .3 Safety precautions. .4 Procedures to be followed in event of equipment failure. .5 Other items of instruction as recommended by manufacturer of each system or item of equipment. Print or engrave operating instructions and frame under glass or in approved laminated plastic. Post instructions where directed. For operating instructions exposed to weather, provide weather-resistant materials or weatherproof enclosures. Ensure operating instructions will not fade when exposed to sunlight and are secured to prevent easy removal or peeling.

.2

.3

.4 .5

.6

PART 2 - PRODUCTS

2.1 SUSTAINABLE REQUIREMENTS

.1

Materials and products in accordance with Section 01 00 10 - General Instructions.

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 5

.2

Do verification requirements in accordance with Section 01 00 10 General Instructions: Contractor's Verification.

2.2 MATERIALS AND EQUIPMENT

.1

Provide material and equipment in accordance with Section 01 61 00 - Common Product Requirements. Material and equipment to be CSA certified. Where CSA certified material and equipment are not available, obtain special approval from inspection authorities before delivery to site and submit such approval as described in PART 1 - SUBMITTALS. Factory assemble control panels and component assemblies.

.2

.3

2.3 ELECTRIC MOTORS, EQUIPMENT AND CONTROLS

.1

Verify installation and co-ordination responsibilities related to motors, equipment and controls, as indicated. Control wiring and conduit: by electrical contractor except for conduit, wiring and connections below 50 V which are related to control systems specified in mechanical sections and as shown on mechanical drawings.

.2

2.4 WARNING SIGNS

.1

Warning Signs: in accordance with requirements of authority having jurisdiction, inspection authorities and Departmental Representative. Decal signs, minimum size 175 x 250 mm.

.2

2.5 WIRING TERMINATIONS

.1

Ensure lugs, terminals, screws used for termination of wiring are suitable for either copper or aluminum conductors.

2.6 EQUIPMENT IDENTIFICATION

.1

Identify electrical equipment with nameplates and labels as follows: .1 Nameplates: lamicoid 3 mm melamine, matt white finish face, black core, lettering accurately aligned and engraved into core mechanically attached with self tapping screws.

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 6

.2 NAMEPLATE SIZES Size 1 Size 2 Size 3 Size 4 Size 5 Size 6 Size 7

Sizes as follows:

10 x 50 mm 12 x 70 mm 12 x 70 mm 20 x 90 mm 20 x 90 mm 25 x 100 mm 25 x 100 mm

1 line 1 line 2 lines 1 line 2 lines 1 line 2 lines

3 mm high letters 5 mm high letters 3 mm high letters 8 mm high letters 5 mm high letters 12 mm high letters 6 mm high letters

.2

Labels: embossed plastic labels with 6mm high letters unless specified otherwise. Wording on nameplates and labels to be approved by Departmental Representative prior to manufacture. Allow for minimum of twenty-five (25) letters per nameplate and label. Nameplates for terminal cabinets and junction boxes to indicate system and/or voltage characteristics. Identify equipment with Size 3 labels engraved "ASSET INVENTORY NO. " as directed by Departmental Representative. Disconnects, starters and contactors: indicate equipment being controlled and voltage. Terminal cabinets and pull boxes: indicate system and voltage. Transformers: indicate capacity, primary and secondary voltages.

.3

.4

.5

.6

.7 .8

.9

2.7 WIRING IDENTIFICATION

.1

Identify wiring with permanent indelible identifying markings, coloured plastic tapes, on both ends of phase conductors of feeders and branch circuit wiring. Maintain phase sequence and colour coding throughout. Colour coding: to CSA C22.1.

.2

.3

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 7

.4

Use colour coded wires in communication cables, matched throughout system.

2.8 CONDUIT AND CABLE IDENTIFICATION

.1

Colour code conduits, boxes and metallic sheathed cables. Code with plastic tape or paint at points where conduit or cable enters wall, ceiling, or floor, and at 15 m intervals. Colours: 25 mm wide prime colour and 20 mm wide auxiliary colour. Prime Yellow Yellow Green Green Auxiliary Green Blue

.2

.3

up to 250 V up to 600 V Telephone Other Communication Systems Fire Alarm Emergency Voice Other Security Systems

Red Red Red

Blue Yellow

2.9 FINISHES

.1

Shop finish metal enclosure surfaces by application of rust resistant primer inside and outside, and at least two coats of finish. Paint outdoor electrical equipment "equipment .1 green" finish. .2 Paint indoor switchgear and distribution enclosures light gray to EEMAC 2Y-1.

PART 3 - EXECUTION

3.1 INSTALLATION

.1

Do complete installation in accordance with CSA C22.1 except where specified otherwise. Do overhead and underground systems in accordance with CSA C22.3 No.1 except where specified otherwise.

.2

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 8

3.2 NAMEPLATES AND LABELS

.1

Ensure manufacturer's nameplates, CSA labels and identification nameplates are visible and legible after equipment is installed.

3.3 CONDUIT AND CABLE INSTALLATION

.1

If plastic sleeves are used in fire rated walls or floors, remove before conduit installation. Install cables, conduits and fittings embedded or plastered over, close to building structure so furring can be kept to minimum.

.2

3.4 LOCATION OF OUTLETS

.1

Locate outlets in accordance with Section 26 05 32 - Outlet Boxes, Conduit Boxes and Fittings. Do not install outlets back-to-back in wall; allow minimum 150 mm horizontal clearance between boxes. Change location of outlets at no extra cost or credit, providing distance does not exceed 3000 mm, and information is given before installation. Locate light switches on latch side of doors. .1 Locate disconnect devices in mechanical and elevator machine rooms on latch side of floor.

.2

.3

.4

3.5 MOUNTING HEIGHTS

.1

Mounting height of equipment is from finished floor to centreline of equipment unless specified or indicated otherwise. If mounting height of equipment is not specified or indicated, verify before proceeding with installation. Install electrical equipment at following heights unless indicated otherwise. .1 Local switches: 1200 mm. .2 Wall receptacles: .1 General: 400 mm. .2 Above top of continuous baseboard heater: 200 mm. Above top of counters or counter splash .3 backs: 175 mm. .4 In mechanical rooms: 1200 mm. .3 Telephone and interphone outlets: 400 mm. .4 Wall mounted telephone and interphone outlets: 1200 mm. .5 Fire alarm stations: 1200 mm.

.2

.3

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 9

.6 .7

Television outlets: 400 mm. Wall mounted fire alarm speakers: 2100 mm.

3.6 CO-ORDINATION OF PROTECTIVE DEVICES

.1

Ensure circuit protective devices such as overcurrent trips, relays and fuses are installed to required values and settings.

3.7 FIELD QUALITY CONTROL

.1

Load Balance: .1 Measure phase current to panelboards with normal loads (lighting) operating at time of acceptance; adjust branch circuit connections as required to obtain best balance of current between phases and record changes. .2 Measure phase voltages at loads and adjust transformer taps to within 2% of rated voltage of equipment. Provide upon completion of work, load balance .3 report as directed in PART 1 - SUBMITTALS: phase and neutral currents on panelboards, dry-core transformers and motor control centres, operating under normal load, as well as hour and date on which each load was measured, and voltage at time of test. Conduct following tests in accordance with Section 01 00 10 - General Instructions. .1 Power generation and distribution system including phasing, voltage, grounding and load balancing. Circuits originating from branch distribution .2 panels. .3 Lighting and its control. .4 Motors, heaters and associated control equipment including sequenced operation of systems where applicable. .5 Systems: fire alarm system. .6 Insulation resistance testing: .1 Megger circuits, feeders and equipment up to 350 V with a 500 V instrument. .2 Megger 350-600 V circuits, feeders and equipment with a 1000 V instrument. .3 Check resistance to ground before energizing. Carry out tests in presence of Departmental Representative. Provide instruments, meters, equipment and personnel required to conduct tests during and at conclusion of project.

.2

.3

.4

Project No. R.050134.002

COMMON WORK RESULTS FOR ELECTRICAL

Section 26 05 00 Page 10

.5

Manufacturer's Field Services: .1 Obtain written report from manufacturer verifying compliance of Work, in handling, installing, applying, protecting and cleaning of product and submit Manufacturer's Field Reports as described in PART 1 - SUBMITTALS. .2 Provide manufacturer's field services consisting of product use recommendations and periodic site visits for inspection of product installation in accordance with manufacturer's instructions. .3 Schedule site visits, to review Work, as directed in PART 1 - QUALITY ASSURANCE.

3.8 CLEANING

.1

Clean and touch up surfaces of shop-painted equipment scratched or marred during shipment or installation, to match original paint. Clean and prime exposed non-galvanized hangers, racks and fastenings to prevent rusting.

.2

3.9 DEMOLITION

.1

Full extent of demolition is not illustrated on drawings. Disconnect and remove all equipment located on existing ceilings and walls to be demolished. Remove wiring and conduit formerly serving demolished equipment back to source. Remove from site unless otherwise noted. Reconnect any existing loads which do not appear on panel details and which are to be re-used. Maintain electrical services and systems at all times to areas beyond the construction area. Reinstate immediately any existing services disrupted during demolition not intended to be removed as part of this contract.

.2

.3

END OF SECTION

Project No. R.050134.002

WIRE AND BOX CONNECTORS (0-1000 V)

Section 26 05 20 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

CSA International .1 CAN/CSA-C22.2 No.18-98(R2003), Outlet Boxes, Conduit Boxes and Fittings. .2 CAN/CSA-C22.2 No.65-03(R2008), Wire Connectors (Tri-National Standard with UL 486A-486B and NMX-J-543-ANCE-03). Electrical and Electronic Manufacturers' Association of Canada (EEMAC) .1 EEMAC 1Y-2-1961, Bushing Stud Connectors and Aluminum Adapters (1200 Ampere Maximum Rating). National Electrical Manufacturers Association (NEMA)

.2

.3

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for wire and box connectors and include product characteristics, performance criteria, physical size, finish and limitations. Sustainable Design Submittals: .1 Construction Waste Management: .1 Submit project Waste Management Plan highlighting recycling and salvage requirements. .2 Submit calculations on end-of-project recycling rates, salvage rates, and landfill rates demonstrating % of construction wastes recycled or salvaged.

.2

.3

1.3 CLOSEOUT SUBMITTALS

.1

Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for wire and box connectors for incorporation into manual.

.2

Project No. R.050134.002

WIRE AND BOX CONNECTORS (0-1000 V)

Section 26 05 20 Page 2

1.4 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect wire and box connectors from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new. Develop Construction Waste Management Plan related to Work of this Section. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

.3

.4

.5

PART 2 - PRODUCTS

2.1 MATERIALS

.1

Pressure type wire connectors to: CAN/CSA-C22.2 No.65, with current carrying parts of copper sized to fit copper conductors as required. Fixture type splicing connectors to: CAN/CSA-C22.2 No.65, with current carrying parts of copper sized to fit copper conductors 10 AWG or less. Clamps or connectors for armoured cable, flexible conduit, as required to: CAN/CSA-C22.2 No.18.

.2

.3

Project No. R.050134.002

WIRE AND BOX CONNECTORS (0-1000 V)

Section 26 05 20 Page 3

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for wire and box connectors installation in accordance with manufacturer's written instructions. .1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative.

3.2 INSTALLATION

.1

Remove insulation carefully from ends of conductors and cables and: Apply coat of zinc joint compound on aluminum .1 conductors prior to installation of connectors. .2 Install mechanical pressure type connectors and tighten screws with appropriate compression tool recommended by manufacturer. Installation shall meet secureness tests in accordance with CAN/CSA-C22.2 No.65. .3 Install fixture type connectors and tighten to CAN/CSA-C22.2 No.65. Replace insulating cap.

3.3 CLEANING

.1

Progress Cleaning: clean in accordance with Section 01 00 10 - General Instructions. .1 Leave Work area clean at end of each day. Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment in accordance with Section 01 00 10 - General Instructions. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. .1 Remove recycling containers and bins from site and dispose of materials at appropriate facility.

.2

.3

END OF SECTION

Project No. R.050134.002

WIRES AND CABLES (0-1000 V)

Section 26 05 21 Page 1

PART 1 - GENERAL

1.1 PRODUCT DATA

.1

Provide product data in accordance with Section 01 33 00 - Submittal Procedures.

1.2 DELIVERY, STORAGE AND HANDLING

.1

Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding and packaging materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

PART 2 - PRODUCTS

2.1 BUILDING WIRES

.1

Conductors: stranded for 10 AWG and larger. Minimum size: 12 AWG. Copper conductors: size as indicated, with 600 V insulation of cross-linked thermosetting polyethylene material rated RW90 XLPE, Jacketted.

.2

2.2 ARMOURED CABLES

.1 .2 .3

Conductors: insulated, copper, size as indicated. Type: AC90. Armour: interlocking type fabricated from aluminum strip. Connectors: anti short connectors.

.4

2.3 CONTROL CABLES

.1

Type: LVT: 2 soft annealed copper conductors, sized as indicated: .1 Insulation: thermoplastic. .2 Sheath : thermoplastic jacket, FT-6 Type: 600 V solid annealed copper conductors, minimum size 16 AWG in conduit. Fire alarm and signal cables: type FAS90.

.2

.3

Project No. R.050134.002

WIRES AND CABLES (0-1000 V)

Section 26 05 21 Page 2

PART 3 - EXECUTION

3.1 FIELD QUALITY CONTROL

.1

Perform tests in accordance with Section 26 05 00 Common Work Results for Electrical. Perform tests using method appropriate to site conditions and to approval of Departmental Representative and local authority having jurisdiction over installation. Perform tests before energizing electrical system.

.2

.3

3.2 GENERAL CABLE INSTALLATION

.1

Terminate cables in accordance with Section 26 05 20 - Wire and Box Connectors - (0-1000 V). Cable Colour Coding: to Section 26 05 00 - Common Work Results for Electrical. Conductor length for parallel feeders to be identical. Lace or clip groups of feeder cables at distribution centres, pull boxes, and termination points. Wiring in walls: typically drop or loop vertically from above to better facilitate future renovations. Generally wiring from below and horizontal wiring in walls to be avoided unless indicated. Branch circuit wiring for permanently wired computer and electronic equipment, dimmed lighting and dedicated circuits to be 2-wire circuits only, i.e. common neutrals not permitted. Provide numbered wire collars for control wiring. Numbers to correspond to control shop drawing legend. Obtain wiring diagram for control wiring.

.2

.3

.4

.5

.6

.7

3.3 INSTALLATION OF BUILDING WIRES

.1

Install wiring as follows: In conduit systems in accordance with Section .1 26 05 34 - Conduits, Conduit Fastenings and Conduit Fittings.

Project No. R.050134.002

WIRES AND CABLES (0-1000 V)

Section 26 05 21 Page 3

3.4 INSTALLATION OF ARMOURED CABLES

.1 .2

Group cables wherever possible on channels. Maximum length: 3 meters.

3.5 INSTALLATION OF CONTROL CABLES

.1 .2

Install control cables in conduit. Ground control cable shield.

END OF SECTION

Project No. R.050134.002

GROUNDING - SECONDARY

Section 26 05 28 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

American National Standards Institute /Institute of Electrical and Electronics Engineers ( ANSI/IEEE ) .1 ANSI/IEEE 837-02, IEEE Standard for Qualifying Permanent Connections Used in Substation Grounding.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for grounding equipment and include product characteristics, performance criteria, physical size, finish and limitations. Sustainable Design Submittals: .1 Construction Waste Management: .1 Submit project Waste Management Plan highlighting recycling and salvage requirements. .2 Submit calculations on end-of-project recycling rates, salvage rates, and landfill rates demonstrating % of construction wastes recycled or salvaged.

.2

.3

1.3 CLOSEOUT SUBMITTALS

.1

Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for grounding equipment for incorporation into manual.

.2

1.4 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address.

.2

Project No. R.050134.002

GROUNDING - SECONDARY

Section 26 05 28 Page 2

.3

Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect grounding equipment from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new. Develop Construction Waste Management Plan related to Work of this Section. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.4

.5

PART 2 - PRODUCTS

2.1 EQUIPMENT

.1

Clamps for grounding of conductor: size as required. Grounding conductors: bare stranded copper, soft annealed, size as indicated. Insulated grounding conductors: green, copper conductors, size as indicated. Non-corroding accessories necessary for grounding system, type, size, material as indicated, including but not necessarily limited to: .1 Grounding and bonding bushings. .2 Protective type clamps. .3 Bolted type conductor connectors. .4 Bonding jumpers, straps. .5 Pressure wire connectors.

.2

.3

.4

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for grounding equipment installation in accordance with manufacturer's written instructions.

Project No. R.050134.002

GROUNDING - SECONDARY

Section 26 05 28 Page 3

.1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative.

3.2 INSTALLATION GENERAL

.1

Install complete permanent, continuous grounding system including, conductors, connectors, accessories. Where EMT is used, run ground wire in conduit. Install connectors in accordance with manufacturer's instructions. Protect exposed grounding conductors from mechanical injury. Use mechanical connectors for grounding connections to equipment provided with lugs. Soldered joints not permitted. Install bonding wire for flexible conduit, connected at both ends to grounding bushing, solderless lug, clamp or cup washer and screw. Neatly cleat bonding wire to exterior of flexible conduit. Make grounding connections in radial configuration only, with connections terminating at single grounding point. Avoid loop connections. Bond single conductor, metallic armoured cables to cabinet at supply end, and load end.

.2

.3

.4

.5 .6

.7

.8

3.3 SYSTEM AND CIRCUIT GROUNDING

.1

Install system and circuit grounding connections to neutral of, secondary system.

3.4 EQUIPMENT GROUNDING

.1

Install grounding connections to typical equipment included in, but not necessarily limited to following list. Service equipment, transformers,

Project No. R.050134.002

GROUNDING - SECONDARY

Section 26 05 28 Page 4

switchgear, duct systems, frames of motors, motor control centres, starters, control panels, building steel work, generators, elevators and escalators, distribution panels, outdoor lighting, cable trays.

3.5 FIELD QUALITY CONTROL

.1

Perform tests in accordance with Section 26 05 00 Common Work Results for Electrical. Perform ground continuity and resistance tests using method appropriate to site conditions and to approval of Departmental Representative and local authority having jurisdiction over installation. Perform tests before energizing electrical system. Disconnect ground fault indicator during tests.

.2

.3 .4

3.6 CLEANING

.1

Progress Cleaning: clean in accordance with Section 01 00 10 General Instructions. .1 Leave Work area clean at end of each day. Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment in accordance with Section 01 00 10 General Instructions. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. .1 Remove recycling containers and bins from site and dispose of materials at appropriate facility.

.2

.3

END OF SECTION

Project No. R.050134.002

Hangers and Supports for Electrical Systems

Section 26 05 29 Page 1

PART 1 - GENERAL

1.1 WASTE MANAGEMENT AND DISPOSAL

.1

Separate and recycle waste materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management And Disposal. Remove from site and dispose of all packaging materials at appropriate recycling facilities. Collect and separate for disposal paper plastic polystyrene corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan. Divert unused metal materials from landfill to metal recycling facility as approved by Departmental Representative. Fold up metal banding, flatten and place in designated area for recycling.

.2

.3

.4

.5

PART 2 - PRODUCTS

2.1 SUPPORT CHANNELS

.1

U shape, size 41 x 41 mm, 2.5 mm thick, surface mounted.

PART 3 - EXECUTION

3.1 INSTALLATION

.1

Secure equipment to masonry, tile and plaster surfaces with nylon shields. Secure equipment to poured concrete with expandable inserts. Secure equipment to hollow masonry walls or suspended ceilings with toggle bolts. Secure surface mounted equipment with twist clip fasteners to inverted T bar ceilings. Ensure that T bars are adequately supported to carry weight of equipment specified before installation. Support equipment, conduit or cables using clips, spring loaded bolts, cable clamps designed as accessories to basic channel members.

.2

.3

.4

.5

Project No. R.050134.002

Hangers and Supports for Electrical Systems

Section 26 05 29 Page 2

.6

Fasten exposed conduit or cables to building construction or support system using straps. .1 One-hole steel straps to secure surface conduits and cables 50 mm and smaller. .2 Two-hole steel straps for conduits and cables larger than 50 mm. .3 Beam clamps to secure conduit to exposed steel work. Suspended support systems. Support individual cable or conduit runs with .1 6 mm diameter threaded rods and spring clips. .2 Support 2 or more cables or conduits on channels supported by 6 mm diameter threaded rod hangers where direct fastening to building construction is impractical.

.7

.8

Provide metal brackets, frames, hangers, clamps and related types of support structures where indicated or as required to support conduit and cable runs. Ensure adequate support for raceways and cables dropped vertically to equipment where there is no wall support. Do not use wire lashing or perforated strap to support or secure raceways or cables. Do not use supports or equipment installed for other trades for conduit or cable support except with permission of other trade and approval of Departmental Representative. Install fastenings and supports as required for each type of equipment cables and conduits, and in accordance with manufacturer's installation recommendations.

.9

.10

.11

.12

END OF SECTION

Project No. R.050134.002

SPLITTERS, JUNCTION, PULL BOXES AND CABINETS

Section 26 05 31 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International) .1 CSA C22.1 Canadian Electrical Code, Part 1.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Provide manufacturer's printed product literature, specifications and datasheet and include product characteristics, performance criteria, physical size, finish and limitations. Provide shop drawings: in accordance with Section 01 33 00 - Submittal Procedures.

.2

.3

1.3 DELIVERY, STORAGE AND HANDLING

.1

Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

PART 2 - PRODUCTS

2.1 JUNCTION AND PULL BOXES

.1 .2

Construction:

welded steel enclosure.

Covers Flush Mounted: 25 mm minimum extension all around. Covers Surface Mounted: screw-on flat covers.

.3

2.2 CABINETS

.1

Construction: welded sheet steel hinged door, handle, latch lock 2 keys and catch. Type E Empty: surface return flange flush overlapping sides mounting as indicated. Type T Terminal: surface return flange flush overlapping sides mounting as indicated containing 19 mm G1S plywood backboard.

.2

.3

Project No. R.050134.002

SPLITTERS, JUNCTION, PULL BOXES AND CABINETS

Section 26 05 31 Page 2

PART 3 - EXECUTION

3.1 JUNCTION, PULL BOXES AND CABINETS INSTALLATION

.1

Install pull boxes in inconspicuous but accessible locations. Mount cabinets with top not higher than 2 m above finished floor except where indicated otherwise. Install terminal block as indicated in Type T cabinets. Only main junction and pull boxes are indicated. Install additional pull boxes as required by CSA C22.1.

.2

.3

.4

3.2 IDENTIFICATION

.1

Equipment Identification: to Section 26 05 00Common Work Results for Electrical . Identification Labels: size 2 indicating system name voltage and phase or as indicated.

.2

END OF SECTION

Project No. R.050134.002

OUTLET BOXES, CONDUIT BOXES AND FITTINGS

Section 26 05 32 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International) .1 CSA C22.1 Canadian Electrical Code, Part 1.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Submit samples for floor box in accordance with Section 01 33 00 - Submittal Procedures.

.2

1.3 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements. Waste Management and Disposal: .1 Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

.2

PART 2 - PRODUCTS

2.1 OUTLET AND CONDUIT BOXES GENERAL

.1 .2 .3 .4

Size boxes in accordance with CSA C22.1. 102 mm square or larger outlet boxes as required. Gang boxes where wiring devices are grouped. Blank cover plates for boxes without wiring devices. 347 V outlet boxes for 347 V switching devices. Combination boxes with barriers where outlets for more than one system are grouped.

.5 .6

2.2 GALVANIZED STEEL OUTLET BOXES

.1

One-piece electro-galvanized construction.

Project No. R.050134.002

OUTLET BOXES, CONDUIT BOXES AND FITTINGS

Section 26 05 32 Page 2

.2

Single and multi gang flush device boxes for flush installation, minimum size 76 x 50 x 38 mm or as indicated. 102 mm square outlet boxes when more than one conduit enters one side with extension and plaster rings as required. Utility boxes for outlets connected to surfacemounted EMT conduit, minimum size 102 x 54 x 48 mm. 102 mm square or octagonal outlet boxes for lighting fixture outlets. Extension and plaster rings for flush mounting devices in finished plaster, or tile walls.

.3

.4

.5

2.3 MASONRY BOXES

.1

Electro-galvanized steel masonry single and multi gang boxes for devices flush mounted in exposed block walls.

2.4 CONCRETE BOXES

.1

Electro-galvanized sheet steel concrete type boxes for flush mount in concrete with matching extension and plaster rings as required.

2.5 FLOOR BOXES

.1

Electro-galvanized sheet steel floor boxes with adjustable finishing rings to suit raised floor finish with faceplate. Device mounting plate to accommodate short or long ear duplex receptacles. Minimum depth: 73 mm for receptacles and communication outlets.

2.6 CONDUIT BOXES

.1

Cast FS or FD boxes with factory-threaded hubs and mounting feet for surface wiring of devices.

2.7 FITTINGS GENERAL

.1

Bushing and connectors with nylon insulated throats. Knock-out fillers to prevent entry of debris. Conduit outlet bodies for conduit up to 35 mm and pull boxes for larger conduits. Double locknuts and insulated bushings on sheet metal boxes.

.2 .3

.4

Project No. R.050134.002

OUTLET BOXES, CONDUIT BOXES AND FITTINGS

Section 26 05 32 Page 3

PART 3 - EXECUTION

3.1 INSTALLATION

.1 .2

Support boxes independently of connecting conduits. Fill boxes with paper, sponges or foam or similar approved material to prevent entry of debris during construction. Remove upon completion of work. For flush installations mount outlets flush with finished wall using plaster rings to permit wall finish to come within 6 mm of opening. Provide correct size of openings in boxes for conduit, mineral insulated and armoured cable connections. Do not install reducing washers. Vacuum clean interior of outlet boxes before installation of wiring devices. Identify systems for outlet boxes as required.

.3

.4

.5

.6

END OF SECTION

Project No. R.050134.002

CONDUITS, CONDUIT FASTENINGS Section 26 05 34 AND CONDUIT FITTINGS Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International) .1 CAN/CSA C22.2 No. 18-98(R2003), Outlet Boxes, Conduit Boxes, Fittings and Associated Hardware, A National Standard of Canada. .2 CSA C22.2 No. 56-04, Flexible Metal Conduit and Liquid-Tight Flexible Metal Conduit. .3 CSA C22.2 No. 83-M1985(R2003), Electrical Metallic Tubing.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product data: submit manufacturer's printed product literature, specifications and datasheets. .1 Submit cable manufacturing data. Quality assurance submittals: .1 Test reports: submit certified test reports. .2 Certificates: submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties. .3 Instructions: submit manufacturer's installation instructions.

.2

.3

1.3 WASTE MANAGEMENT AND DISPOSAL

.1

Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. Place materials defined as hazardous or toxic waste in designated containers. Ensure emptied containers are sealed and stored safely for disposal away from children.

.2

.3

PART 2 - PRODUCTS

2.1 CABLES AND REELS

.1

Provide cables on reels or coils. .1 Mark or tag each cable and outside of each reel or coil, to indicate cable length, voltage rating, conductor size, and manufacturer's lot number and reel number.

Project No. R.050134.002

CONDUITS, CONDUIT FASTENINGS Section 26 05 34 AND CONDUIT FITTINGS Page 2

.2

Each coil or reel of cable to contain only one continuous cable without splices. Identify cables for exclusively dc applications.

.3

2.2 CONDUITS

.1

Electrical metallic tubing (EMT): to CSA C22.2 No. 83, with couplings. Flexible metal conduit: to CSA C22.2 No. 56, aluminum liquid-tight flexible metal.

.2

2.3 CONDUIT FASTENINGS

.1

One hole steel straps to secure surface conduits 50 mm and smaller. .1 Two hole steel straps for conduits larger than 50 mm. Beam clamps to secure conduits to exposed steel work. Channel type supports for two or more conduits. Threaded rods, 6 mm diameter, to support suspended channels.

.2

.3 .4

2.4 CONDUIT FITTINGS

.1

Fittings: to CAN/CSA C22.2 No. 18, manufactured for use with conduit specified. Coating: same as conduit. Ensure factory "ells" where 90 degrees bends for 25 mm and larger conduits. Watertight connectors and couplings for EMT. .1 Set-screws are not acceptable.

.2

.3

2.5 FISH CORD

.1

Polypropylene.

Project No. R.050134.002

CONDUITS, CONDUIT FASTENINGS Section 26 05 34 AND CONDUIT FITTINGS Page 3

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheets.

3.2 INSTALLATION

.1

Install conduits to conserve headroom in exposed locations and cause minimum interference in spaces through which they pass. Conceal conduits except in mechanical and electrical service rooms and in unfinished areas. Use electrical metallic tubing (EMT) except where specified otherwise. Use flexible metal conduit for connection to motors in dry areas. Use liquid tight flexible metal conduit for connection to motors or vibrating equipment in damp, wet or corrosive locations, and for branch connections to wiring devices from local junction boxes under raised floor. Minimum conduit size for lighting and power circuits: 19 mm. Bend conduit cold: .1 Replace conduit if kinked or flattened more than 1/10th of its original diameter. Mechanically bend steel conduit over 19 mm diameter. Install fish cord in empty conduits. Remove and replace blocked conduit sections. .1 Do not use liquids to clean out conduits. Dry conduits out before installing wire.

.2

.3

.4

.5

.6

.7

.8

.9 .10

.11

3.3 SURFACE CONDUITS

.1 .2

Run parallel or perpendicular to building lines. Locate conduits behind infrared or gas fired heaters with 1.5 m clearance.

Project No. R.050134.002

CONDUITS, CONDUIT FASTENINGS Section 26 05 34 AND CONDUIT FITTINGS Page 4

.3

Run conduits in flanged portion of structural steel. Group conduits wherever possible on channels. Do not pass conduits through structural members except as indicated. Do not locate conduits less than 75 mm parallel to steam or hot water lines with minimum of 25 mm at crossovers.

.4 .5

.6

3.4 CONCEALED CONDUITS

.1 .2 .3

Run parallel or perpendicular to building lines. Do not install horizontal runs in masonry walls. Do not install conduits in terrazzo or concrete toppings.

3.5 CLEANING

.1

Proceed in accordance with Section 01 00 10 General Instructions. On completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment.

.2

END OF SECTION

Project No. R.050134.002

WIRING DEVICES

Section 26 27 26 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

CSA International .1 CSA C22.2 No.42-10, General Use Receptacles, Attachment Plugs and Similar Devices. .2 CAN/CSA C22.2 No.42.1-00(R2009), Cover Plates for Flush-Mounted Wiring Devices (Bi-national standard, with UL 514D). .3 CSA C22.2 No.55-M1986(R2008), Special Use Switches. .4 CSA C22.2 No.111-10, General-Use Snap Switches (Bi-national standard, with UL 20).

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for wiring devices and include product characteristics, performance criteria, physical size, finish and limitations. Sustainable Design Submittals: .1 Construction Waste Management: .1 Submit project Waste Management Plan highlighting recycling and salvage requirements. .2 Submit calculations on end-of-project recycling rates, salvage rates, and landfill rates demonstrating % of construction wastes recycled or salvaged.

.2

.3

1.3 CLOSEOUT SUBMITTALS

.1

Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for wiring devices for incorporation into manual.

.2

1.4 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address.

.2

Project No. R.050134.002

WIRING DEVICES

Section 26 27 26 Page 2

.3

Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect wiring devices from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new. Develop Construction Waste Management Plan related to Work of this Section. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.4

.5

PART 2 - PRODUCTS

2.1 SWITCHES

.1

20 A, 120 V or 347 V, single pole, double pole, three-way, four-way switches to: CSA C22.2 No.55 CSA C22.2 No.111. Manually-operated general purpose AC switches with following features: .1 Terminal holes approved for No. 10 AWG wire. .2 Silver alloy contacts. .3 Urea or melamine moulding for parts subject to carbon tracking. .4 Suitable for back and side wiring. .5 White toggle. Toggle operated fully rated for tungsten filament and fluorescent lamps, and up to 80% of rated capacity of motor loads and heating loads. Switches of one manufacturer throughout project.

.2

.3

.4

2.2 RECEPTACLES

.1

Duplex receptacles, CSA type 5-15 R, 125 V, 15 A, U ground, to: CSA C22.2 No.42 with following features: .1 Orange urea moulded housing. .2 Suitable for No. 10 AWG for back and side wiring.

Project No. R.050134.002

WIRING DEVICES

Section 26 27 26 Page 3

.3 Break-off links for use as split receptacles. .4 Eight back wired entrances, four side wiring screws. .5 Triple wipe contacts and rivetted grounding contacts. .6 Isolated ground (IG) .2 Other receptacles with ampacity and voltage as indicated. Receptacles of one manufacturer throughout project.

.3

2.3 SPECIAL WIRING DEVICES

.1

Special wiring devices: .1 Clock hanger outlets, 15 A, 125 V, 3 wire, grounding type, suitable for No. 10 AWG for installation in flush outlet box. .2 Pilot lights as indicated, with neon type 0.04 W, 125 V lamp and red plastic jewel flush type.

2.4 COVER PLATES

.1

Cover plates for wiring devices to: CSA C22.2 No.42.1. Sheet steel utility box cover for wiring devices installed in surface-mounted utility boxes. Stainless steel, vertically brushed, 1 mm thick cover plates for wiring devices mounted in flushmounted outlet box. Sheet metal cover plates for wiring devices mounted in surface-mounted FS or FD type conduit boxes.

.2

.3

.4

2.5 SOURCE QUALITY CONTROL

.1

Cover plates from one manufacturer throughout project.

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for wiring devices installation in accordance with manufacturer's written instructions.

Project No. R.050134.002

WIRING DEVICES

Section 26 27 26 Page 4

.1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative.

3.2 INSTALLATION

.1

Switches: .1 Install single throw switches with handle in "UP" position when switch closed. .2 Install switches in gang type outlet box when more than one switch is required in one location. Mount toggle switches at height in accordance .3 with Section 26 05 00 - Common Work Results for Electrical. Receptacles: .1 Install receptacles in gang type outlet box when more than one receptacle is required in one location. .2 Mount receptacles at height in accordance with Section 26 05 00 - Common Work Results for Electrical. .3 Where split receptacle has one portion switched, mount vertically and switch upper portion. .4 Install GFI type receptacles as indicated. Cover plates: .1 Install suitable common cover plates where wiring devices are grouped. .2 Do not use cover plates meant for flush outlet boxes on surface-mounted boxes.

.2

.3

3.3 CLEANING

.1

Progress Cleaning: clean in accordance with Section 01 00 10 General Instructions. .1 Leave Work area clean at end of each day. Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment in accordance with Section 01 00 10 General Instructions. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

.3

Project No. R.050134.002

WIRING DEVICES

Section 26 27 26 Page 5

.1 Remove recycling containers and bins from site and dispose of materials at appropriate facility.

3.4 PROTECTION

.1

Protect installed products and components from damage during construction. Protect stainless steel cover plate finish with paper or plastic film until painting and other work is finished. Repair damage to adjacent materials caused by wiring device installation.

.2

.3

END OF SECTION

Project No. R.050134.002

MOULDED CASE CIRCUIT BREAKERS

Sect 26 28 16.02 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International). .1 CSA-C22.2 No. 5-02, Moulded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures (Tri-national standard with UL 489, tenth edition, and the second edition of NMX-J-266ANCE).

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit product data in accordance with Section 01 33 00 - Submittal Procedures.

1.3 WASTE MANAGEMENT AND DISPOSAL

.1

Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. Collect and separate for disposal paper plastic polystyrene corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan. Separate for reuse and recycling and place in designated containers Steel Metal Plastic waste in accordance with Waste Management Plan.

.2

.3

PART 2 - PRODUCTS

2.1 BREAKERS GENERAL

.1

Moulded-case circuit breakers, Circuit breakers, and Ground-fault circuit-interrupters: to CSA C22.2 No. 5 Bolt-on moulded case circuit breaker: quick- make, quick-break type, for manual and automatic operation. Common-trip breakers: with single handle for multipole applications. Magnetic instantaneous trip elements in circuit breakers to operate only when value of current reaches setting.

.2

.3

.4

Project No. R.050134.002

MOULDED CASE CIRCUIT BREAKERS

Sect 26 28 16.02 Page 2

.1 Trip settings on breakers with adjustable trips to range from 3-10 times current rating. .5 Circuit breakers to have minimum 10,000 A symmetrical rms (root mean square) interrupting capacity rating.

2.2 THERMAL MAGNETIC BREAKERS

.1

Moulded case circuit breaker to operate automatically by means of thermal and magnetic tripping devices to provide inverse time current tripping and instantaneous tripping for short circuit protection.

2.3 OPTIONAL FEATURES

.1

Include: .1 Shunt trip. .2 On-off locking device.

PART 3 - EXECUTION

3.1 INSTALLATION

.1

Install circuit breakers as indicated.

END OF SECTION

Project No. R.050134.002

DISCONNECT SWITCHES - FUSED AND NON-FUSED

Section 26 28 23 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International). .1 CAN/CSA C22.2 No.4-M89 (R2000), Enclosed Switches.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit product data in accordance with Section 01 33 00 - Submittal Procedures.

1.3 HEALTH AND SAFETY

.1

Do construction occupational health and safety in accordance with Section 01 35 29.06 - Health and Safety Requirements.

1.4 WASTE MANAGEMENT AND DISPOSAL

.1

Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal. Remove from site and dispose of packaging materials at appropriate recycling facilities. Collect and separate for disposal paper plastic polystyrene corrugated cardboard packaging material in appropriate on-site bins for recycling in accordance with Waste Management Plan. Separate for reuse and recycling and place in designated containers Steel Metal Plastic waste in accordance with Waste Management Plan. Fold up metal banding, flatten and place in designated area for recycling.

.2

.3

.4

.5

PART 2 - PRODUCTS

2.1 DISCONNECT SWITCHES

.1

Non-fusible, horsepower rated disconnect switch in CSA Enclosure, to CAN/CSA C22.2 No.4 size as indicated. Provision for padlocking in on-off switch position.

.2

Project No. R.050134.002

DISCONNECT SWITCHES - FUSED AND NON-FUSED

Section 26 28 23 Page 2

.3

Mechanically interlocked door to prevent opening when handle in ON position. Quick-make, quick-break action. ON-OFF switch position indication on switch enclosure cover.

.4 .5

2.2 EQUIPMENT IDENTIFICATION

.1

Provide equipment identification in accordance with Section 26 05 00 - Common Work Results for Electrical. Indicate name of load controlled on size 4 nameplate.

.2

PART 3 - EXECUTION

3.1 INSTALLATION

.1

Install disconnect switches.

END OF SECTION

Project No. R.050134.002

LIGHTING

Section 26 50 00 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

American National Standards Institute (ANSI) .1 ANSI C82.1-04, Lamp Ballasts-Line Frequency Fluorescent Lamp Ballast. American National Standards Institute/Institute of Electrical and Electronics Engineers ( ANSI/IEEE ) .1 ANSI/IEEE C62.41-1991, Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits. ASTM International Inc. .1 ASTM F 1137-00(2006), Standard Specification for Phosphate/Oil and Phosphate/Organic Corrosion Protective Coatings for Fasteners. Canadian Standards Association (CSA International) ICES-005-07, Radio Frequency Lighting Devices. Underwriters' Laboratories of Canada (ULC)

.2

.3

.4 .5 .6

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Provide manufacturer's printed product literature, specifications and datasheet and include product characteristics, performance criteria, physical size, finish and limitations. Provide complete photometric data prepared by .2 independent testing laboratory for luminaires where specified, for approval by Departmental Representative. .3 Photometric data to include: VCP Table where applicable. Samples: .1 Provide samples as indicated. Quality assurance submittals: provide following in accordance with Section 01 00 10 General Instructions. .1 Manufacturer's instructions: provide manufacturer's written installation instructions and special handling criteria, installation sequence, cleaning procedures.

.2

.3

.4

Project No. R.050134.002

LIGHTING

Section 26 50 00 Page 2

1.3 QUALITY ASSURANCE

.1

Provide mock-ups in accordance with Section 01 00 10 General Instructions.

1.4 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements. Deliver materials to site in original factory packaging, labelled with manufacturer's name, address. Packaging Waste Management: remove for reuse and return by manufacturer of pallets crates padding and packaging materials in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. Divert unused metal materials from landfill to metal recycling facility. Disposal and recycling of fluorescent lamps as per local regulations. Disposal of old PCB filled ballasts.

.2

.3

.4

.5

.6

PART 2 - PRODUCTS

2.1 LAMPS

.1

Incandescent lamps to be - clear, A19, 100 Watt with 1000 hour lamp life, rough-service rated; or as indicated.. Tungsten halogen lamps to be - clear, T-3, 300 Watt, RSC base, 2000 hour lamp life, 5000 lumens; or as indicated. Fluorescent lamps to be - T8, 32 Watt, medium bipin, rapid-start, 4100 K, 30,000 hour lamp life, 2950 initial lumens, CRI 85; or as indicated.

.2

.3

.4

Compact fluorescent lamps to be - 12,000 hour lamp life, 4100 K, CRI 85; or as indicated.

Project No. R.050134.002

LIGHTING

Section 26 50 00 Page 3

2.2 BALLASTS

.1

Fluorescent ballast: CBM and CSA certified, energy efficient type, IC electronic. .1 Voltage Rating: 60 Hz as indicated, for use with two(2) 32W lamps, rapid start type. .2 Totally encased and designed for 40 degrees Celsius ambient temperature. .3 Power factor: minimum 95% with 95% of rated lamp lumens. .4 Current crest factor: 1.7 maximum. .5 Harmonics: 10% maximum THD. Operating frequency of electronic ballast: 20 .6 kHz minimum. .7 Total circuit power: 62 Watts. .8 Ballast factor: greater than 0.90. .9 Sound rated: Class A. .10 Mounting: integral with luminaire.

2.3 FINISHES

.1

Light fixture finish and construction to meet ULC listings and CSA certifications related to intended installation.

2.4 OPTICAL CONTROL DEVICES

.1

As indicated in luminaire schedule.

2.5 LUMINAIRES

.1

As indicated in luminaire schedule.

PART 3 - EXECUTION

3.1 INSTALLATION

.1 .2

Locate and install luminaires as indicated. Provide adequate support to suit ceiling system.

3.2 WIRING

.1

Connect luminaires to lighting circuits: .1 Install flexible or rigid conduit for luminaires as indicated.

3.3 LUMINAIRE SUPPORTS

.1

For suspended ceiling installations support luminaires independently of ceiling.

Project No. R.050134.002

LIGHTING

Section 26 50 00 Page 4

3.4 LUMINAIRE ALIGNMENT

.1

Align luminaires mounted in continuous rows to form straight uninterrupted line. Align luminaires mounted individually parallel or perpendicular to building grid lines.

.2

3.5 CLEANING

.1

Clean in accordance with Section 01 00 10 General Instructions. .1 Remove surplus materials, excess materials, rubbish, tools and equipment. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

END OF SECTION

Project No. R.050134.002

EMERGENCY LIGHTING

Section 26 52 00 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

CSA International .1 CSA C22.2 No.141-10, Emergency Lighting Equipment.

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for emergency lighting and include product characteristics, performance criteria, physical size, finish and limitations.

.2

1.3 CLOSEOUT SUBMITTALS

.1

Submit in accordance with Section 01 78 00 Closeout Submittals. Operation and Maintenance Data: submit operation and maintenance data for emergency lighting for incorporation into manual.

.2

1.4 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect emergency lighting from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new.

.2

.3

Project No. R.050134.002

EMERGENCY LIGHTING

Section 26 52 00 Page 2

.4

Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

PART 2 - PRODUCTS

2.1 EQUIPMENT

.1 .2 .3 .4 .5 .6

Emergency lighting equipment: to CSA C22.2 No.141. Supply voltage: 120 V, AC. Output voltage: 24 V DC. Operating time: 30 minutes. Battery: sealed, maintenance free. Charger: solid state, multi-rate, voltage/current regulated, inverse temperature compensated, short circuit protected with regulated output of plus or minus 0.01 V for plus or minus 10% input variations. Solid state transfer circuit. Low voltage disconnect: solid state, modular, operates at 80% battery output voltage. Signal lights: solid state, for 'AC Power ON' and 'High Charge'. Lamp heads: integral on unit and remote, 345 degrees horizontal and 180 degrees vertical adjustment. Lamp type: quartz halogen MR-16, 12 W. Cabinet: suitable for direct or shelf mounting to wall and c/w knockouts for conduit. Removable or hinged front panel for easy access to batteries. Finish: White

.7 .8

.9

.10

.11

.12

.13

Auxiliary equipment: .1 Test switch. .2 Battery disconnect device. .3 AC input and DC output terminal blocks inside cabinet. .4 Cord and plug connection for AC.

Project No. R.050134.002

EMERGENCY LIGHTING

Section 26 52 00 Page 3

2.2 WIRING OF REMOTE HEADS

.1

Conduit: type EMT, in accordance with Section 26 05 34 - Conduits, Conduit Fastenings and Conduit Fittings. Conductors: RW90 type in accordance with Section 26 05 21 - Wires and Cables (0-1000 V), sized as indicated.

.2

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for emergency lighting installation in accordance with manufacturer's written instructions. .1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative.

3.2 INSTALLATION

.1 .2 .3

Install unit equipment and remote mounted fixtures. Direct heads. Connect exit lights to unit equipment.

3.3 CLEANING

.1

Progress Cleaning: clean in accordance with Section 01 00 10 General Instructions. .1 Leave Work area clean at end of each day.

.2

Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment in accordance with Section 01 00 10 General Instructions. Waste Management: separate waste materials for

.3

Project No. R.050134.002

EMERGENCY LIGHTING

Section 26 52 00 Page 4

reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. .1 Remove recycling containers and bins from site and dispose of materials at appropriate facility.

3.4 PROTECTION

.1

Protect installed products and components from damage during construction. Repair damage to adjacent materials caused by emergency lighting installation.

.2

END OF SECTION

Project No. R.050134.002

EXIT SIGNS

Section 26 53 00 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Canadian Standards Association (CSA International) .1 CSA C22.2 No.141-02, Unit Equipment for Emergency Lighting. .2 CSA C860-01(December 2002), Performance of Internally-Lighted Exit Signs. National Building Code of Canada .1 NBCC-2010.

.2

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Provide submittals in accordance with Section 01 33 00 - Submittal Procedures. Product Data: .1 Submit manufacturer's printed product literature, specifications and datasheet and include product characteristics, performance criteria, physical size, finish and limitations. Submit WHMIS MSDS - Material Safety Data Sheets in accordance with Section 01 00 10 General Instructions. Quality Assurance Submittals: submit following in accordance with Section 01 00 10 General Instructions. .1 Instructions: submit manufacturer's installation instructions and special handling criteria, installation sequence, cleaning procedures.

.2

.3

.4

1.3 WASTE MANAGEMENT AND DISPOSAL

.1

Separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

PART 2 - PRODUCTS

2.1 STANDARD UNITS

.1 .2

Exit lights: to CSA C22.2 No.141 and CSA C860. Housing: extruded aluminum housing, white baked enamel finish. Face and back plates: extruded aluminum.

.3

Project No. R.050134.002

EXIT SIGNS

Section 26 53 00 Page 2

.4 .5

Lamps: LED 50,000 hours. Operation: designed for 50,000 hours of continuous operation without relamping. Letters: 150 mm high x 19 mm, with 13 mm thick stroke, red on die-cast aluminum face, reading EXIT and SORTIE. Downlight: translucent acrylic in bottom of unit.

.6

.7

.8

Face plate to remain captive for relamping.

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheets.

3.2 INSTALLATION

.1

Install exit lights to manufacturer's recommendations, listing requirements, and local regulatory requirements. Connect fixtures to exit light circuits. Connect emergency lamp sockets to emergency circuits. Ensure that exit light circuit breaker is locked in on position.

.2 .3

.4

3.3 CLEANING

.1

Proceed in accordance with Section 01 00 10 General Instructions. On completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment.

.2

END OF SECTION

Project No. R.050134.002

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Section 27 05 28 Page 1

PART 1 - GENERAL

1.1 ACTION AND INFORMATIONAL SUBMITTALS

.1

Submit in accordance with Section 01 33 00 Submittal Procedures. Product Data: .1 Submit manufacturer's instructions, printed product literature and data sheets for communication raceway systems and include product characteristics, performance criteria, physical size, finish and limitations. Sustainable Design Submittals: .1 Construction Waste Management: .1 Submit project Waste Management Plan highlighting recycling and salvage requirements. .2 Submit calculations on end-of-project recycling rates, salvage rates, and landfill rates demonstrating % of construction wastes recycled or salvaged.

.2

.3

1.2 DELIVERY, STORAGE AND HANDLING

.1

Deliver, store and handle materials in accordance with Section 01 61 00 - Common Product Requirements and with manufacturer's written instructions. Delivery and Acceptance Requirements: deliver materials to site in original factory packaging, labelled with manufacturer's name and address. Storage and Handling Requirements: .1 Store materials off ground indoors in dry location and in accordance with manufacturer's recommendations in clean, dry, well-ventilated area. .2 Store and protect communication raceway systems from nicks, scratches, and blemishes. .3 Replace defective or damaged materials with new. Develop Construction Waste Management Plan related to Work of this Section. Packaging Waste Management: remove for reuse and return by manufacturer of pallets, crates, padding, and packaging materials as specified in Construction Waste Management Plan in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal.

.2

.3

.4

.5

Project No. R.050134.002

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Section 27 05 28 Page 2

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

.1

Empty telecommunications raceways system consists of outlet boxes, cover plates, cabinets, conduits, cable trays, pull boxes, sleeves and caps, fish wires, service fittings. Under floor cable tray distribution system.

.2

2.2 MATERIAL

.1

Conduits: type, in accordance with Section 26 05 34 - Conduits, Conduit Fastenings and Conduit Fittings. Junction boxes, cabinets type E T: in accordance with Section 26 05 31 - Splitters, Junction, Pull Boxes and Cabinets. Outlet boxes, conduit boxes, and fittings: in accordance with Section 26 05 31 - Splitters, Junction, Pull Boxes and Cabinets. Fish wire: polypropylene type.

.2

.3

.4

PART 3 - EXECUTION

3.1 EXAMINATION

.1

Verification of Conditions: verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for communication raceway systems installation in accordance with manufacturer's written instructions. .1 Visually inspect substrate in presence of Departmental Representative. .2 Inform Departmental Representative of unacceptable conditions immediately upon discovery. .3 Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Departmental Representative.

Project No. R.050134.002

PATHWAYS FOR COMMUNICATIONS SYSTEMS

Section 27 05 28 Page 3

3.2 INSTALLATION

.1

Install empty raceway system, including under floor distribution system, fish wire, terminal cabinets, outlet boxes, floor boxes, pull boxes, cover plates, conduit, sleeves and caps, cable tray, miscellaneous and positioning material to constitute complete system.

3.3 CLEANING

.1

Progress Cleaning: clean in accordance with Section 01 00 10 General Instructions. .1 Leave Work area clean at end of each day. Final Cleaning: upon completion remove surplus materials, rubbish, tools and equipment in accordance with Section 01 00 10 General Instructions. Waste Management: separate waste materials for reuse and recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and Disposal. .1 Remove recycling containers and bins from site and dispose of materials at appropriate facility.

.2

.3

3.4 PROTECTION

.1

Protect installed products and components from damage during construction. Repair damage to adjacent materials caused by pathways for communications systems installation.

.2

END OF SECTION

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 1

PART 1 - GENERAL

1.1 REFERENCES

.1

Government of Canada .1 TB OSH Chapter 3-03, 1997-01-28, Treasury Board of Canada, Occupational Safety and Health, Chapter 3-03, Standard for Fire protection Electronic Data Processing Equipment. .2 TB OSH Chapter 3-04, 1994-12-22, Treasury Board of Canada, Occupational Safety and Health, Chapter 3-04, Standard for Fire Alarm Systems. Health Canada/Workplace Hazardous Materials Information System (WHMIS) .1 Material Safety Data Sheets (MSDS). Underwriter's Laboratories of Canada (ULC) .1 CAN/ULC-S524-2001, Standard for the Installation of Fire Alarm Systems. .2 CAN/ULC-S525-1999, Audible Signal Device for Fire Alarm Systems. .3 CAN/ULC-S536-S537-2004, Burglar and Fire Alarm Systems and Components. National Fire Protection Agency .1 NFPA 72-2002, National Fire Alarm Code. .2 NFPA 90A-2002, Installation of Air Conditioning and Ventilating Systems. FMD 4007

.2

.3

.4

.5

1.2 ACTION AND INFORMATIONAL SUBMITTALS

.1

Product Data: .1 Submit manufacturer's printed product literature, specifications and datasheet in accordance with Section 01 33 00 - Submittal Procedures. .1 Submit two copies of Workplace Hazardous Materials Information System (WHMIS) Material Safety Data Sheets (MSDS) in accordance with Section 01 33 00 - Submittal Procedures. Shop Drawings: .1 Submit shop drawings in accordance with Section 01 33 00 - Submittal Procedures. Quality assurance submittals: submit following in accordance with Section 01 33 00 - Submittal Procedures.

.2

.3

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 2

.1 Certificates: submit certificates signed by manufacturer certifying that materials comply with specified performance characteristics and physical properties. .2 Instructions: submit manufacturer's installation instructions. .3 Manufacturer's Field Reports: manufacturer's field reports specified. .4 Closeout Submittals: .1 Submit maintenance and engineering data for incorporation into manual specified in Section 01 78 00 - Closeout Submittals. .2 Authority of Jurisdiction will delegate authority for review and approval of submittals required by this Section. .3 Submit to Authority of Jurisdiction 2 sets of approved submittals and drawings immediately after approval but no later than 15 working days to prior to final inspection. .4 Submit following: .1 Manufacturer's Data for: .1 Alarm speakers. .2 Mark data which describe more than one type of item to indicate which type will be provided. .3 Submit original for each item and clear, legible, first-generation photocopies for remainder of specified copies. .2 Test Reports: .1 Preliminary testing: .1 Final acceptance testing. .2 Submit for inspections and tests specified under Field Quality Control.

1.3 QUALITY ASSURANCE

.1

Qualifications: .1 Installer: company or person specializing in fire alarm system installations approved by manufacturer. Provide services of representative or technician from manufacturer of system, experienced in installation and operation of type of system being provided, to supervise installation, adjustment, preliminary testing, and final testing of system and to provide instruction to project personnel. System: .1 To TB OSH Chapter 3-04. .2 Subject to Canadian Forces Fire Marshal (CFFM) approval.

.2

.3

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 3

.3 Subject to CFFM inspection for final acceptance. .4 Extra Materials: .1 Provide maintenance materials in accordance with Section 01 78 00 - Closeout Submittals.

1.4 DELIVERY, STORAGE, AND HANDLING

.1

Packing, shipping, handling and unloading: .1 Deliver, store and handle in accordance with Section 01 61 00 - Common Product Requirements. .2 Deliver, store and handle materials in accordance with manufacturer's written instructions. Waste Management and Disposal: .1 Construction/Demolition Waste Management and Disposal: separate waste materials for reuse and recycling in accordance with Section 01 74 21 Construction/Demolition Waste Management and Disposal.

.2

PART 2 - PRODUCTS

2.1 SUSTAINABLE REQUIREMENTS

.1

Materials and products in accordance with Section 01 00 10 General Instructions.

2.2 MATERIALS

.1

Equipment and devices: ULC listed and labelled and supplied by single manufacturer. Audible signal devices: to CAN/ULC-S525.

.2

2.3 CONTROL PANEL

.1

Reuse existing Edwards control panel. Coordinate with Fire Alarm Upgrade project which is being implemented under a separate project.

2.4 AUTOMATIC ALARM INITIATING DEVICES

.1

Open-Area Smoke Detectors: reuse existing.

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 4

2.5 AUDIBLE SIGNAL DEVICES

.1

Audible device(s): .1 Speakers: flush or surface mounted, type to match existing. Do not exceed 80 percent of listed rating in amperes of notification appliance circuit. Provide additional circuits above those shown if required to meet this requirement. For surface mounting provide appliance manufacturer's approved back box. Back box finish to match appliance finish.

.2

.3

2.6 END-OF-LINE DEVICES

.1

End-of-line devices to control supervisory current in alarm circuits and signalling circuits, sized to ensure correct supervisory current for each circuit. Open, short or ground fault in any circuit will alter supervisory current in that circuit, producing audible and visible alarm at main control panel and remotely as indicated.

2.7 WIRING

.1

Wire for 120 V circuits: No. 12 AWG minimum solid copper conductor. Wire for low voltage DC circuits: No. 14 AWG minimum solid copper conductor Wire for connection to base telegraphic alarm loop: No. 10 AWG minimum solid copper conductor. Insulation 90 degrees C minimum with nylon jacket, type FAS90. Colour code wiring.

.2

.3

.4

.5

PART 3 - EXECUTION

3.1 MANUFACTURER'S INSTRUCTIONS

.1

Compliance: comply with manufacturer's written recommendations or specifications, including product technical bulletins, handling, storage and installation instructions, and datasheet.

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 5

3.2 INSTALLATION

.1

Install systems in accordance with CAN/ULC-S524 and TB OSH Chapter 3-04. Connect alarm circuits to main control panel.

.2

.3

Locate and install audible signal devices and connect to signalling circuits. Connect signalling circuits to main control panel. Install end-of-line devices at end of alarm and signalling circuits.

.4 .5

3.3 FIELD QUALITY CONTROL

.1

Site Tests: .1 Perform tests in accordance with Section 26 05 00 - Common Work Results for Electricaland CAN/ULC-S537. .2 Fire alarm system: .1 Test each device and alarm circuit to ensure manual stations, thermal and smoke detectors transmit alarm to control panel and actuate general alarm and ancillary devices. .2 Check annunciator panels to ensure zones are shown correctly. .3 Simulate grounds and breaks on alarm and signalling circuits to ensure proper operation of system. .4 Class A circuits. .1 Test each conductor on circuits for capability of providing alarm signal on each side of single opencircuit fault condition imposed near midmost point of circuit. Reset control unit after each alarm function and correct imposed fault after completion of each test. .2 Test each conductor on circuits for capability of providing alarm signal during ground-fault condition imposed near midmost point of circuit. Reset control unit after each alarm function and correct imposed fault after completion of each test. .5 Class B circuits. .1 Test each conductor on circuits for capability of providing alarm signal on line side of single open-

Project No. R.050134.002

FIRE DETECTION AND ALARM

Section 28 31 00 Page 6

circuit fault condition imposed at electrically most remote device on circuit. Reset control unit after each alarm function and correct imposed fault after completion of each test. .2 Test each conductor on circuits for capability of providing alarm signal during ground-fault condition imposed at electrically most remote device on circuit. Reset control unit after each alarm function and correct imposed fault after completion of each test. .2 Manufacturer's Field Services: .1 Obtain written report from manufacturer verifying compliance of Work, in handling, installing, applying, protecting and cleaning of product and submit Manufacturer's Field Reports as described in PART 1 - SUBMITTALS. .2 Provide manufacturer's field services consisting of product use recommendations and periodic site visits for inspection of product installation in accordance with manufacturer's instructions. .3 Schedule site visits, to review Work, as directed in PART 1 - QUALITY ASSURANCE. Verification requirements in accordance with Section 01 00 10 General Instructions, include: .1 Materials and resources. .2 Storage and collection of recyclables. .3 Construction waste management. .4 Resource reuse. .5 Recycled content. .6 Local/regional materials. .7 Low-emitting materials.

.3

3.4 CLEANING

.1

Proceed in accordance with Section 01 00 10 General Instructions. Upon completion and verification of performance of installation, remove surplus materials, excess materials, rubbish, tools and equipment.

.2

END OF SECTION