Escolar Documentos
Profissional Documentos
Cultura Documentos
GB
PQI-DA Operating Manual 1
PQI-DA
Tel.: +49 (0) 911 / 62 81 08 0
Fax: +49 (0) 911 / 62 81 08 96
E-mail: info@a-eberle.de
Internet: www.a-eberle.de
PQI-DA
Power Quality Interface & Disturbance Recorder
Operating Manual
Version: October 2009
Copyright 2003 by A. Eberle GmbH & Co. KG
Published by
A. Eberle GmbH & Co. KG
Aalener Strae 30/32
90441 Nuremberg
Germany
The company A. Eberle GmbH & Co. KG cannot be held liable for any damages
or losses resulting from printing errors or changes in this operating manual.
Furthermore, A. Eberle GmbH&Co. KG does not assume responsibility for any
damages and losses resulting from faulty devices or from devices altered by
the user.
PQI-DA
PQI-DA Operating Manual
2
Inhaltsverzeichnis
Information: ................................................................................................................... 7
1. Technical Concept ................................................................................................... 8
1.1 Application ..................................................................................................... 8
1.2 Features of the Power-Quality-Interface & Disturbance Recorder .................. 10
1.3 Description ................................................................................................... 10
2. Application ............................................................................................................ 11
2.1 PQI-DA as a Recorder (Fault Recorder) ......................................................... 11
2.1.1 Recorder A ..............................................................................................................11
2.1.2 Recorder B ..............................................................................................................12
2.1.3 Recorder C ..............................................................................................................14
2.1.4 Events .....................................................................................................................15
2.2 PQI-DA as System Component .................................................................... 16
3. Technical Data ...................................................................................................... 17
3.1 Standards ..................................................................................................... 17
3.2 Voltage inputs ............................................................................................... 17
3.3 Current inputs ............................................................................................... 18
3.4 Binary inputs (BI) ........................................................................................... 18
3.5 Binary outputs (BO) ...................................................................................... 19
3.6 Limit value monitoring ................................................................................... 19
3.7 Measurement quantities ............................................................................... 19
3.8 Reference conditions .................................................................................... 20
3.9 Measurement data acquisition ...................................................................... 20
3.10 Storage of measured values ......................................................................... 20
3.11 Electromagnetic Compatibility ....................................................................... 21
3.12 Electrical safety ............................................................................................. 21
3.13 Operating voltages ....................................................................................... 22
3.14 Power supply ............................................................................................... 22
3.15 Environmental conditions .............................................................................. 22
3.16 Data storage ................................................................................................. 23
4. Mechanical Design ............................................................................................... 23
4.1 Housing ........................................................................................................ 23
4.1.1 PQI-DA 4U / 4I .........................................................................................................24
4.1.2 PQI-DA 8U ...............................................................................................................25
4.1.3 PQI-DA 4U/4I und 8U ............................................................................................26
(n)
9.2.1.8 Active power of the phase
( ) ( ) n i n u n p
N 1 1 1
) ( =
( ) ( ) n i n u n p
N 2 2 2
) ( =
( ) ( ) n i n u n p
N 3 3 3
) ( =
max
min
max
min
2
) 2 / (
n
n n
n
n
n n
n
T rms
w
n u w
U
This results in 512 (256) sampling points or 5 (3) r.m.s. values per period for 50
Hz (60 Hz) networks.
The average of two consecutive r.m.s. values that is calculated every half-period
is known as the average half-period r.m.s. value.
It is used as a trigger quantity for start / stop events and is also a quantity stored
by recorder B.
It is calculated as follows:
2
) (
2
) 2 / (
2
1
) 2 / 1 (
n U
U
T rms
n
rms
=
=
For transformer congurations 3..5, the calculated sampling values are applied to
the virtual neutral point to calculate the r.m.s. phase voltages.
PQI-DA
PQI-DA Operating Manual
66
For transformer congurations 6..11, the unavailable voltages U
ab
are replaced
with the value of the measured voltage U
m
, after a correction factor (see Table
5) has been applied to it.
m ab
U U =
9.2.2.2 10/12-period r.m.s. voltage values
2048
) (
2048
1
2
12 / 10
=
=
n
rms
n u
U
R.m.s. values > 1.5 Un and < 0.5 Un are highlighted.
For transformer congurations 3..5, the calculated sampling values are applied to
the virtual neutral point to calculate the r.m.s. phase voltages.
For transformer congurations 6..11, the unavailable voltages U
ab
are replaced
with the value of the measured voltage U
m
, after a correction factor (see Table 5)
has been applied to it.
9.2.2.3 150/180-period r.m.s voltage values
The 150/180-period r.m.s. values are each calculated from 15 consecutive
10/12-period r.m.s. values. Each 10/12-period r.m.s. value is included exactly
once in a 150/180-period r.m.s. value calculation.
( )
15
15
1
2
12 / 10
180 / 150
=
=
n
rms
rms
n U
U
If more than 7 of the 15 10/12-period r.m.s. values are highlighted or are not
available, the corresponding 150/180-period r.m.s. value is also highlighted.
{ } ( )
=
=
1024
cos
1024
1
Im
2047
0
m k
m x C
m
k
{ } 0 Re =
k
C fr
where k = n N
9.2.6.2 Phase difference between the reference voltge and the measurement
voltage (basic frequency)
The phase difference between the measurement voltages and the reference voltage
is calculated from the phase angle of the 10/12-period fundamental waves, when
the r.m.s. values exceed the corresponding signicance threshold C
sig
.
UC TVSIG C
sig
=
:
sig rms
C C
( ) ( )
12 / 10 1 12 / 10 1 12 / 10 1
= Cref arc C arc
:
sig rms
C C <
0
12 / 10 1
=
with
L Index of the conductor
U
LN-1-10/12
Complex fundamental wave of the phase voltage
I
L-1-10/12
Complex fundamental wave of the conductor current
Symmetrical networks with a phase voltage and current of the same conductor:
The value of the measured phase (see above) is also applied to the other two
phases.
Symmetrical networks whose voltage and current have different phases:
A correction angle is subtracted from the phase difference that is measured
The value of the measured phase is also assigned to the other two phases
(see above).
Table 1 : Correction angle
I
1-10/12
U
1-10/12
I
1
I
2
I
3
U
1E
(0) 120 -120
U
2E
-120 (0) 120
U
3E
120 -120 (0)
U
12
30 150 -90
U
23
-90 30 150
U
31
150 -90 30
The 150/180-period, 10-minute and 2-hour values are calculated as linear
average values.
9.2.6.9 Direction of the rotating eld
Voltage transformer congurations 1..4 :
{ } { } { } { } ( )
1 1 1 3 1 1 1 3
Im Re Re Im
=
N N N N
U U U U Sgn rot
red = +1 : Direction of the rotating eld = 123
red = -1 : Direction of the rotating eld = 321
U
LN-1
= complex fundamental wave of the phase voltage (10/12-period values)
Voltage transformer congurations 6..11 :
red = 0 : Direction of the rotating eld cannot be measured
PQI-DA
PQI-DA Operating Manual
76
9.2.7 Active Powers
Asymmetrical networks:
The 10/12-period values of the active power of the phase are calculated from the
sampling values of a synchronisation cycle using
2048
) (
2048
1
12 / 10
=
=
n
L
L
n p
P
where L = phase index
The 10/12-period values of the active power of the network are dened using
12 / 10 3 12 / 10 2 12 / 10 1 12 / 10
+ + = P P P P
Symmetrical network with a phase voltage and a phase current of the same conductor L
n
:
The measured active power P
n
(see above) of phase L
n
is also applied to the two
unavailable phases.
12 / 10 12 / 10 3 12 / 10 2 12 / 10 1
= = =
n
P P P P
The active power of the network corresponds to the sum of the active powers of
the phases.
12 / 10 3 12 / 10 2 12 / 10 1 12 / 10
+ + = P P P P
Symmetrical networks whose voltage and current have different phases:
The active power of the network is calculated from the apparent network power
using
) cos(
12 / 10 1 12 / 10 12 / 10
= S P
where
11 . 2 . 9 . :
12 / 10
s S
7 . 6 . 2 . 9 . :
12 / 10 1
s
1/3 of the active power of the network is assigned to each of the active powers
of the phases:
The 150/180-period, 10-minute and 2-hour values are calculated from the cor-
responding values of the active powers, apparent powers and the phase ang-
les.
9.2.14 Active Factors
:
min 180 / 150
L L
S S
180 / 150
180 / 150
180 / 150
=
L
L
L
S
P
PF
:
min 180 / 150
<
L L
S S
1
180 / 150
=
L
PF
:
min 180 / 150
S S
180 / 150
180 / 150
180 / 150
S
P
PF =
:
min 180 / 150
S S <
1
180 / 150
= PF
The 10-minute and 2-hour values are calculated from the corresponding values
for the active powers and apparent powers.
9.2.15 Reactive Factors
:
min 180 / 150
L L
S S
180 / 150
180 / 150
180 / 150
=
L
L
L
S
Q
QF
:
min 180 / 150
<
L L
S S
0
180 / 150
=
L
QF
:
min 180 / 150
S S
180 / 150
180 / 150
180 / 150
S
Q
QF =
:
min 180 / 150
S S <
0
180 / 150
= QF
The 10-minute and 2-hour values are calculated from the corresponding values
for the reactive powers and apparent powers.
The 10-minute and 2-hour values are calculated from the corresponding values
of the active powers, active factors and the phase angles.
9.2.17 Flicker Magnitude
The short-term icker magnitude P
st
(10 minutes) and the long-term icker ma-
gnitude P
lt
(2-hours) are calculated for the phase and delta voltages. P
st
and P
lt
are dened in EN 61000-4-15.
In symmetrical networks, the measured values are applied to the quantities that
are not available (see section 7.1.4).
9.2.18 Asymmetrical Voltage
Voltage transformer congurations 1..5:
10-minute average values can be formed for the fundamental wave r.m.s. values
of the delta voltages. These 10-minute average values are used to calculate the
voltage symmetry.
:
2
min 1
2
1 31
2
1 23
2
1 12
+ + C U U U
+
=
1
1
u
u
where
2 2
1 31
2
1 23
2
1 12
4
1 31
4
1 23
4
1 12
) (
6 3
+ +
+ +
=
U U U
U U U
:
2
min 1
2
1 31
2
1 23
2
1 12
< + + C U U U
0 =
u
u
Voltage transformer congurations 6..11:
0 =
u
u
PQI-DA
PQI-DA Operating Manual
82
10. Commissioning
10.1 Safety Information
Before you begin to use the device, you should be aware of some of the dangers
that may occur if the device is used improperly.
The device belongs to safety class I. Please connect the devices protective
earth conductor to your systems earthing system before the device is con-
nected to a voltage supply.
The device may not be used to carry out measurements on circuits that contain
corona discharges.
The device must be removed from the network immediately if it is determined
that the device can no longer be operated safely due to a mechanical or elec-
trical fault.
Please note: if the Power Quality Interface & Disturbance Recorder is installed
in a housing, the secondary circuits of the current transformer must be short-
circuited before the terminal connections of the current transformer are removed
from the device. Devices in 19 enclosures are protected against short circuits
via a device built in to the terminal block. The modules can be plugged in and
out at will without having to short circuit the current transformer(s) rst.
Please note that there is a danger to life wherever a voltage with an amplitude
> 30 V r.m.s. is present.
10.2 Procedure
Preparation:
Please look at the nameplate and conrm that the supplied device conforms to
your requirements.
Is the voltage supply correct?
Information: Changes to the voltage supply range can only be carried out in
our factory.
Are the measurement quantities for the input current (1A/5A) of the applica-
tion correct?
Are the voltage and current connected correctly?
Check the connection using the phase powers. All the powers must have
the same sign (plus or minus). It should be a plus + if energy is being
drawn, and minus - if energy is being supplied.
If the polarities are not the same, the error is usually due to the current con-
nections being incorrect.
Part of the WinPQ program is specically designed for the parameterisation and
programming of the analogue outputs, binary inputs and the LEDs.
berreicht durch:
A.Eberle GmbH & Co. KG
Aalener Str. 30/32
D-90441 Nrnberg
Tel.: +49 (0) 911 / 62 81 08-0
Fax: +49 (0) 911 / 62 81 08 96
http://www.a-eberle.de
info@a-eberle.de
PQI-DA