Data Bulletin

Replaces 0100DB0501 R01/12

Short Circuit Selective Coordination


for Low Voltage Circuit Breakers
Retain for future use.

INTRODUCTION

The purpose of this data bulletin is to present short circuit selective


coordination data for various combinations of Square D low voltage circuit
breakers.
The scope of this data bulletin encompasses only breaker-to-breaker
short circuit selective coordination. Coordination between circuit breakers in
the overload region of their time-current curves, coordination with fuses and
the protection of motors, transformers and other devices, as well as
coordinated ground fault protection, is not discussed. Conventional
selective coordination studies using time-current curves are still required to
address these issues. See the REFERENCE section, on page 6, for other
data bulletins on this subject.
This data bulletin is a companion to Enhancing Short Circuit Selective
Coordination with Low Voltage Circuit Breakers, document number
0100DB0403.

Appendix Guide

SELECTIVE COORDINATION
DATA

Appendix A: Mission Critical Circuit Breakers

Page 7

Appendix B: Levels of Short Circuit Selective Coordination


for UL 489 Standard Circuit Breakers

Page 12

Appendix C: Levels of Short Circuit Selective Coordination


for ANSI Low-Voltage Power Circuit Breakers

Page 52

Appendix D: A glossary of terms used in this data bulletin.

Page 58

System designers are accustomed to determining the level of short circuit


selective coordination between combinations of low voltage circuit breakers
using time-current curves. But using time-current curves alone sometimes
leads to the determination of a selective coordination level that is lower than
can actually be achieved.

How Time-Current Curves Are Developed

Time-current curves represent the tripping characteristics of circuit breakers


at various levels of overcurrent (overload currents to high level short
circuits). They are developed by conducting interruption tests at various
current levels. The time is recorded for the circuit breaker to completely
interrupt the current. The relationship between the time to interrupt the
current and the current level is plotted on a time-current curve graph. The
time-current curve shows the individual circuit breakers tested
performance. In the instantaneous region of the time-current curve, it is
often assumed that the clearing time is constant regardless of the current
level, hence the curve is usually drawn flat in that region.

Current-Limiting Circuit Breakers

Many modern circuit breakers are designed with blow-open contacts and/or
other features to quickly clear high fault currents, resulting in clearing times
that decrease as the current increases, unlike what the conservatively
drawn time-current curves may indicate. Even circuit breakers not UL Listed
or CSA certified as current-limiting may exhibit current-limiting
characteristics.

20052013 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers

0100DB0501
R02/13, 05/2013

Dynamic Characteristics of Circuit


Breakers

All circuit breakers, when they begin to open, serve to limit the prospective
flow of current, even if they are not listed or certified as current-limiting. This
is an important factor to consider when two circuit breakers are connected in
series, especially if the downstream circuit breaker opens faster than the
upstream circuit breaker.

Impact on Selective Coordination

In the case of two circuit breakers connected in series, if the downstream


circuit breaker opens faster than the upstream circuit breaker, the
downstream circuit breaker may limit the flow of current below the point at
which the upstream circuit breaker will trip. The result may be a level of
selective coordination higher than might be determined by comparing the
time-current curves of the two individual circuit breakers.

Actual Levels of Selective Coordination

The levels of selective coordination presented in this data bulletin were


determined based on the actual performance of Square D low voltage circuit
breakers. They were determined by comparing the current let-through of the
downstream circuit breaker with the minimum instantaneous trip characteristic
of the upstream circuit breaker, taking into account manufacturing tolerances.
Thus the maximum level of selective coordination was determined for various
pairings of upstream and downstream circuit breakers.

SELECTIVE COORDINATION
AND SERIES RATINGS

It has been assumed by many that in all cases the upstream circuit breaker
will trip when two circuit breakers are connected in a series rated
combination. But this is not always the case.

Equipment Impedance

Sometimes the impedance of the equipment in which the circuit breakers


are installed, including the added impedance of the upstream circuit
breaker, is sufficient to limit the current to a point where the downstream
circuit breaker is able to interrupt the fault current by itself, without causing
the upstream circuit breaker to trip.

Downstream Circuit Breaker


Construction

Sometimes a circuit breaker manufacturer, for various reasons, may offer a


range of interrupting ratings for a given circuit breaker frame using a single
construction. For example, a circuit breaker frame might be available with
18 and 35 kA interrupting ratings, but both might actually be built with a
35 kA construction. In such an instance the 18 kA rated circuit breaker might
be offered with a 35 kA series rating, which the circuit breaker would be
capable of interrupting on its own without the assistance of an upstream
circuit breaker. Thus the pair might have a level of selective coordination
higher than anticipated.

ASSUMPTIONS

A few assumptions have been made in the compilation of this data.

Circuit Breaker Contact Position

It is assumed that all circuit breakers in the system, with the possible exception
of the branch circuit breaker nearest to the fault, are in the closed (ON) position
when the fault occurs. Low voltage power circuit breakers may incorporate a
making current release (MCR) trip function set slightly below the circuit
breaker's close and latch capability. The MCR trip level may be below that of
the adjustable instantaneous or instantaneous selective override trip functions.

Instantaneous Trip Setting

In order to maximize selective coordination, it is assumed that the


instantaneous trip setting on all upstream circuit breakers in the system, if
adjustable, will be set to the highest position. It is also assumed that if the
upstream circuit breaker has adjustable electronic trip unit (Micrologic LSI
or LSIG) where the field adjustable instantaneous trip function can be
turned off, then it will be turned off.

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Short Circuit Selective Coordination for Low Voltage Circuit Breakers

Turning off the field adjustable instantaneous trip function does not mean
that the circuit breaker loses its ability to protect against short circuits.
Square D electronic trip circuit breakers that have an OFF position on the
instantaneous switch are also equipped with a short time pick-up and delay
function, and may also be equipped with an instantaneous selective
override function if necessary for the proper functioning of the circuit
breaker.
The adjustment of trip settings does not affect any series rating that may be
employed as UL and CSA require series ratings tests to be conducted with
the instantaneous trip adjustment set to its highest position.

HOW TO USE THE TABLES

In order to use the data presented here, some basic information is needed.

System One-line Diagram

A one-line diagram of the system to be studied is absolutely necessary in


order to determine the level of system coordination.

System Voltage

System voltage impacts circuit breaker selection.

Circuit Ampacity

The instantaneous trip characteristics of a circuit breaker may be a function


of the frame or current sensor rating rather than the current rating of the
circuit breaker. However, the current rating required to meet the ampacity of
the circuit drives the circuit breaker selection, thus it needs to be known.
(See NEC Articles 210, 215, 220, 225 and 230.)

Available Short Circuit Current

The available short circuit current at each point in the system should be
determined in order to select circuit breakers with the proper interrupting
rating and in turn to determine the level of selective coordination. Short
circuit current contribution from large motors should be taken into account.
All circuit breaker testing is done at the X/R ratio indicated in the following
chart. For a system X/R ratio larger than the test X/R ratio, the available
short circuit current equivalent RMS symmetrical rating for comparison with
the values in the tables must be adjusted by a multiplying factor. See IEEE
Std. 242-2001 (Buff Book), IEEE Std. 1015-1997 (Blue Book) or NEMA
AB 3-2001 for details.
Type
Molded Case Circuit Breakers
(Including Insulated Case
Circuit Breakers)
Low Voltage Power Circuit Breakers

Determining Levels of Selective


Coordination

Standard

Interrupting
Rating

Test
X/R

UL 489

Greater than 20 kA

4.9

1020 kA

3.2

Less than 10 kA

1.7

UL 1066 (ANSI C37)

6.6

Based on this information, determine the level of selective coordination


between pairs of circuit breakers in the system using their time-current
curves. If there is overlap of the instantaneous trip characteristic of the two
circuit breakers at or below the level of short circuit current available at the
downstream circuit breaker, consult the tables presented in APPENDIX B
on page 12 and APPENDIX C on page 52. The intersection of the
upstream row and downstream circuit breakers column in the tables lists the
level of selective coordination between that pair of circuit breakers.
Example

20052013 Schneider Electric All Rights Reserved

Let's consider a 480Y/277 Vac system with 25 kA available short circuit


current. Assume that the system consists of an NF 250 A main lugs lighting
panelboard with single pole EG 35 kAIR rated circuit breakers fed from a
JGA36250 circuit breaker with a 35 kA interrupting rating located in an
3

Short Circuit Selective Coordination for Low Voltage Circuit Breakers

0100DB0501
R02/13, 05/2013

I-Line power panelboard. Determine the level of selective coordination


between the upstream JGA circuit breaker and downstream EG circuit
breakers by following these steps.
1. Find the 480 Vac table listing EG downstream circuit breakers in
APPENDIX B, Table 14: on page 27.
2. Find the column for the EG downstream circuit breaker to be studied.
3. Go down the column until the row listing the 250 A JG upstream circuit
breaker is found.
4. Read the selective coordination level at the intersection of the column
and row, namely 2.4 kA. This means that the JG upstream circuit
breaker is selectively coordinated with downstream EG circuit breakers
up to 2,000 amps.

OPTIMIZING THE SELECTIVE


COORDINATION LEVEL

The selective coordination of a circuit breaker based low voltage system can
be optimized using the techniques presented in the Enhancing Short
Circuit Selective Coordination with Low Voltage Circuit Breakers data
bulletin and the data presented in APPENDIX B on page 12 and
APPENDIX C on page 52. The following is a brief summary of the
techniques more fully presented in the Enhancing Short Circuit Selective
Coordination with Low Voltage Circuit Breakers data bulletin.

Conduct A Short Circuit Study

Conducting a short circuit study may reveal that lower interrupting rated
downstream circuit breakers can be selected, possibly resulting in higher
withstand ratings.

Increase Frame Size

By increasing the frame size of the upstream circuit breaker, it may be


possible to increase the selective coordination at that level in the system.

Change Circuit Breaker Type

By changing the upstream circuit breaker from a molded case to an


insulated case circuit breaker, it may be possible to increase the selective
coordination at that level in the system.

Using the Tables

If the level of selective coordination between the two circuit breakers initially
selected is not sufficient for the application, the tables may be used to find
an alternate upstream circuit breaker selection that will yield a higher level
of selective coordination. This may involve a larger frame size or different
type of circuit breaker, as mentioned above. This may be done by going
down the tables to find possible upstream circuit breakers that may deliver a
higher level of selective coordination.
Example

Using the same example previously stated under Determining Levels of


Selective Coordination, determine if a higher level of selective
coordination can be achieved by following these steps:
1. Move down the column for the EG downstream circuit breaker to be
studied, looking for upstream breakers that will yield a higher level of
selective coordination.
2. When the desired level of selective coordination is found, read across
the row to find the upstream circuit breaker that will yield this level. In
this case, a PG circuit breaker will yield a level of selective coordination
of 35,000 amps. This means that the upstream PG circuit breaker is fully
selective with downstream EG circuit breakers.

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

CONCLUSION

Short Circuit Selective Coordination for Low Voltage Circuit Breakers

The actual level of short circuit selective coordination between pairs of


Square D low voltage circuit breakers needs to be considered when
designing a selectively coordinated low voltage electrical system. This may be
done by finding the pair of circuit breakers in the tables presented in this data
bulletin and reading the actual level of short circuit selective coordination.
If the level of short circuit selective coordination is not sufficient for the
application, an alternate upstream circuit breaker yielding a higher level of
short circuit selective coordination may be found by reading down the table.
The alternate may be an electronic trip circuit breaker whose instantaneous
trip function can be turned OFF, a larger frame size circuit breaker or a
different type of circuit breaker.
A short circuit study to determine the level of short circuit current available at
various points in the system may allow the selection of circuit breakers with
a lower interrupting rating and a higher instantaneous trip level.
The data bulletin Enhancing Short Circuit Selective Coordination with
Low Voltage Circuit Breakers, document number 0100DB0403, should be
consulted for a further explanation of optimizing techniques for enhancing
the level of short circuit selective coordination.
Finally, do not neglect to properly adjust circuit breakers in the field as all
Square D low voltage circuit breakers are shipped from the factory with all
but the ampere-rating switch in the lowest position.

Micrologic Electronic Trip Units

In the Type column of tables covering PowerPact H, and J circuit breakers,


the U character in the third position stands for Micrologic Electronic Trip Unit.
For example:

HDU360 - 3 pole 60A HD breaker with Micrologic trip unit.


JLU3250 - 3 pole 250A JL breaker with Micrologic trip unit.

Type H and J circuit breakers with Micrologic trip units, used as upstream
circuit breakers, provide different selectivity levels (usually higher) than their
thermal magnetic equivalents.
When Type H and J circuit breakers with Micrologic trip units are used as
downstream circuit breakers, there is no difference in selectivity so the
standard types include all trip unit options.

J- and L-Frame Mission Critical


Circuit Breakers

In the upstream column of tables covering J- and L-frame mission critical


circuit breakers, there are WU characters in the third and forth positions
that stand for mission critical circuit breakers with Micrologic electronic trip
units.
For example:

JLWU3 pole 250 A JL mission critical circuit breaker with Micrologic trip
unit

LDWU4003 pole 400 A LD mission critical circuit breaker with


Micrologic trip unit

When J- and L-frame mission critical circuit breakers are used as


downstream circuit breaker, the maximum level of selective coordination is
the same as standard J- and L-frame circuit breakers.

20052013 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers

REFERENCE

0100DB0501
R02/13, 05/2013

Enhancing Short Circuit Selective Coordination with Low Voltage


Circuit Breakers
Document Number: 0100DB0403
Overcurrent Protection
Document Number: 0600DB0301
Reducing Fault Stress with Zone-selective Interlocking
Document Number: 0600DB0001

Additional Resources

Additional resources are available on this topic.


Selectivity Guidelines for Square D Panelboards
Document Number: 0100DB0604
Guide to Power System Selective Coordination 600 Vac and Below
Document Number: 0100DB0603
Guide to Low Voltage Transformer Protection and Selective
Coordination
Document Number: 0100DB0902

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Mission Critical Circuit Breakers

APPENDIX A
Mission Critical Circuit Breakers

The PowerPact J- and L-frame mission critical circuit breakers deliver high
levels of selective coordination in a flexible design that can be easily
configured for a variety of applications. Tested to be selectively coordinated
with the QO family of miniature circuit breakers and the ED, EG, and EJ
circuit breakers, this solution provides peace of mind when power
availability is critical.
An electronic trip unit provides adjustable long-time settings in three sensor
sizes, allowing coverage from 70 through 600 A on 120-240, 208Y/120,
240, and 480Y/277 V systems.
Ratings
UL 489 Listed
CSA Certified
Voltage: 480Y/277 V

Available Configurations

I-Line mounting
Main circuit breaker in NQ and NF
panelboards
Unit mount for OEM users
Plug-in base for OEM users
Drawout base for OEM users

In addition to unique design attributes, the PowerPact mission critical circuit


breakers have also undergone rigorous testing procedures to certify the
coordination with downstream circuit breakerscombining innovative
engineering with validated test results.
Apply Schneider Electric mission critical circuit breakers in emergency
power distribution systems, data centers, hospitals, or anywhere continuity
of service is desired.

Theory of Operation

There are several dynamic forces between the PowerPact mission critical
circuit breakers and downstream circuit breakers when a fault occurs
downstream of the branch circuit breaker. Many of these events cannot be
shown on the trip curve.
The PowerPact mission critical circuit breakers analyze the fault current to
make decisions which maximize selectivity with downstream circuit
breakers. The trip units deploy a special selectivity delay to allow
downstream circuit breakers to clear. However, on very high faults or if the
downstream circuit breaker does not trip, the circuit breaker trips the
mechanism instantaneously.
The combination of the PowerPact mission critical circuit breaker and
downstream circuit breakers shown in the selectivity charts in the instruction
bulletin are selective due to the fact that the series impedance and the letthrough from the downstream circuit breaker does not produce enough
energy to trip the PowerPact mission critical circuit breaker.
This system maximizes the interaction of the circuit breakers in series to
allow selectivity.
The PowerPact J- and L-frame mission critical circuit breaker is specifically
designed to provide selective coordination with QO and E-frame circuit
breakers during a short-circuit condition.

20052013 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Mission Critical Circuit Breakers

J- and L-Frame Mission Critical Circuit


Breakers used as Downstream Circuit
Breakers

0100DB0501
R02/13, 05/2013

The trip curves for the J- and L-frame mission critical circuit breakers are the
same as the standard Micrologic trip units. When the circuit breakers are
used as downstream circuit breakers, they have the same maximum level of
selective coordination as standard J- and L-frame circuit breakers.
J-frame mission critical circuit breakers are selective with QO or E-frame
circuit breakers per Table 1 when the amperage of the main circuit breaker
is at least two times the amperage of the branch circuit breaker.

J-Frame Selectivity with QO and E-Frame Circuit Breakers1


Circuit Breaker

Main

Voltage

Branch
1030 A
1P, 2P

QO(B)
JW, 250 A

3560 A

QO(B)-H

70125 A

QO(B)-VH

1030 A

QH

3P

J-Frame Mission Critical Circuit Breaker

15 kA
QO 20 A 1P

13 kA

208 V

Load

10 kA

240 V

FAULT

18 kA
10 kA

1560 A

1P, 2P, 3P

70125 A
1

12 kA

240 V

15125 A
E-Frame

15 kA

120 V

3560 A

One-Line Diagram

18 kA

240/120 V

70125 A

JW, 250 A

Current

06114961

Table 1:

480Y/277 V

QO 100 A 2P

7 kA

Load

Including AFI, CAFI, EPD and GFI circuit breakers.

L-frame mission critical circuit breakers are selective with QO-style and
E-frame circuit breakers per Table 2 when the amperage of the main circuit
breaker is at least two times greater than the amperage of the branch circuit
breaker.
L-Frame Selectivity with QO and E-Frame Circuit Breakers1
Circuit Breaker
Main

Branch
QO(B)

LW, 250 A

QO(B)-H

Voltage

1060 A

18 kA
240 V

QO(B)-VH
QH

Current

70125 A

10 kA

One-Line Diagram

06114961

Table 2:

L-Frame Mission Critical Circuit Breaker

QO 20 A 1P

Load

QO(B)
LW, 400 A

QO(B)-H

LW, 600 A

QO(B)-VH

FAULT
15150 A

240 V

30 kA
QO 100 A 2P

QH
240 V

30 kA

480Y/277 V

30 kA

LW, 250 A
LW, 400 A
LW, 600 A
1

E-Frame

Load

15125 A

Including AFI, CAFI, EPD and GFI circuit breakers.

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

PowerPact D-Frame Mission Critical

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Mission Critical Circuit Breakers

The Square D PowerPact D-frame mission critical circuit breaker will go


into obsolescence July 2013, and will be available until the end of 2013.
Tested to be selectively coordinated with QO and QOB branch circuit
breakers through 30 kA fault current, this solution provides peace of mind
when power availability is critical. An electronic trip unit provides adjustable
long-time trip settings in four sizes, allowing coverage from 60 A through
600 A on a 208Y/120 Vac system. In conjunction with QO and QOB branch
circuit breakers, the PowerPact
D-frame mission critical circuit breaker delivers full selective coordination
downstream of Square D transformers ranging from 15 kVA to 300 kVA.
Ratings:

UL489 Listed
CSA certified
Voltage: 208Y/120 Vac
Handle Ratings: 60600 A
AIR: 65 kA

Available Configurations:

LA/LH Mission Critical

Four sizes: 150 A, 250 A, 400 A, 600 A


Main circuit breaker in NQ panelboards
Unit mount for OEM users
Plug-in base for OEM users
Drawout base for OEM users

High-magnetic withstand capabilities delivered in the simplicity of a basic


thermal-magnetic circuit breaker design. Fixed settings designed to deliver
tested coordination levels take the guess work out of installation and
maintenance. Fully-coordinated systems are possible downstream of
Square D transformers from 15 kVA to 225 kVA when the LA or LH
mission critical circuit breaker is applied with QO and QOB branch circuit
breakers.
Ratings:

UL489 Listed
CSA certified
Voltage: dual-rated for 480Y/277 Vac and 208Y/120 Vac
Handle Ratings: 200 A, 225 A, 250 A, 400 A

Available Configurations:

20052013 Schneider Electric All Rights Reserved

I-Line panel construction


Main circuit breaker in 400 A NQ and NF panel construction
Unit mount for OEM users

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac QO/B

0100DB0501
R02/13, 05/2013

Selective Coordination Levels


Table 3:

D-Frame Mission Critical Circuit Breakers


Main Circuit Breakers

D-MC 150 A

Branch Circuit Breaker Standard AIR (10 kA)

D-MC
400 A/600 A

D-MC 250 A

QO/QOB
1- and 2-pole

QO/QOB
1- and 2-pole

QO/QOB
1- and 2-pole

Branch Continuous Current Rating

1570 A

15100 A

15100 A

Branch Circuit Breakers High AIR (22 kA)

QO/QOB-VH
1-, 2,- and 3-pole

QO/QOB-VH
1-, 2,- and 3-pole

QO/QOB-VH
1-, 2,- and 3-pole

208Y/120 Vac
Branch Continuous Current Rating

1570 A

15125 A

15150 A

Level of Selective Coordination

30 kA

30 kA

30 kA

Series Ratings with QO/QOB

65 kA

65 kA

65 kA

Series Ratings with QO/QOB-VH

65 kA

65 kA

65 kA

NOTE: Maximum branch circuit breaker ampacity is 50% of the main circuit
breaker ampacity (long time setting).
Table 4:

LA/LH Mission Critical Circuit Breakers UL 208Y/120 Vac QO/QOB 1550 A Downstream Circuit Breakers

Upstream
Circuit Breaker

Downstream Circuit Breaker - Type / Ampacity / Voltage Rating / Number of Poles / kAIR
Maximum Level of Selective Coordination Shown in kA
QO/QOB

Type
Max.
Cont.
Current
Rating

15 A

20 A

30 A

40 A

2 Pole
120/240 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

200 A

182

182

162

182

182

102

72

102

6.52

225 A

182

182

182

182

182

162

112

182

82

10

10

7.5

182

182

182

182

182

182

182

182

142

10

10

10

10

10

400 A

182

182

182

182

182

182

182

182

182

10

10

10

10

10

10

200 A

182

182

162

182

182

102

72

102

6.52

5.5

225 A

182

182

182

182

182

162

112

182

82

10

10

7.5

10

10

182

182

182

182

182

182

182

182

142

10

10

10

10

10

182

182

182

182

182

182

182

182

182

10

10

10

10

10

10

kAIR1

250 A

250 A

42

65

3 Pole
240 V

1 Pole
120 V

50 A

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

5.5

10

10

10 kAIR

LA-MC

LH-MC

400 A
1

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

The panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

Table 5:

LA/LH Mission Critical Circuit Breakers UL 208Y/120 Vac QO/QOB 60100 A Downstream Circuit Breakers

Upstream
Circuit Breaker

Downstream Circuit BreakerType / Ampacity / Voltage Rating / Number of Poles / kAIR


Maximum Level of Selective Coordination Shown in kA
QO/QOB

Type
Max.
Cont.
Current
Rating

60 A

70 A

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

200 A

52

62

52

52

62

225 A

82

102

6.52

72

102

102

102

82

102

400 A

102

102

102

200 A

52

62

52

225 A

82

102

102
102

250 A
400 A

42

65

90100 A

2 Pole
120/240 V

3 Pole
240 V

2 Pole
120/240 V

3 Pole
240 V

52

62

102

7.52

10

7.5

10

7.5

102

102

102

10

10

10

10

52

62

52

6.52

72

102

62

102

82

102

102

7.52

10

7.5

10

7.5

102

102

102

102

102

10

10

10

10

kAIR1

250 A

80 A
3 Pole
240 V
10 kAIR

LA-MC

LH-MC

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

The panelboard in which the QO circuit breaker is located is fully rated 10 kA and series rated 18 kA.

10

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 6:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac QO/B

LA/LH Mission Critical Circuit Breakers UL 208Y/120 Vac QO-VH/QOB-VH 1550 A Downstream Circuit
Breakers

Upstream
Circuit Breaker

Downstream Circuit BreakerType / Ampacity / Voltage Rating / Number of Poles / kAIR


Maximum Level of Selective Coordination Shown in kA
QO-VH/QOB-VH

Type
Max.
Cont.
Current
Rating

15 A

20 A

30 A

40 A

2 Pole
120/240 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

200 A

22

22

16

22

22

10

10

6.5

225 A

22

22

16

22

22

16

11

22

11

18

7.5

22

22

18

22

22

18

22

22

14

22

18

10

400 A

22

22

18

22

22

18

22

22

18

22

22

200 A

22

22

16

22

22

10

10

6.5

22

22

16

22

22

16

11

22

11

18

7.5

10

18

22

22

18

22

22

18

22

22

14

22

18

10

12

18

22

22

18

22

22

18

22

22

18

22

22

18

22

22

18

kAIR1

250 A

225 A
250 A

42

65

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

3 Pole
240 V

5.5

10

18

12

18

18

22

22

18

5.5

10 kAIR

LA-MC

LH-MC

400 A
1

3 Pole
240 V

50 A

1 Pole
120 V

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Table 7:

LA/LH Mission Critical Circuit Breakers UL 208Y/120 Vac QO-VH/QOB-VH 60100 A Downstream Circuit
Breakers

Upstream
Circuit Breaker

Downstream Circuit BreakerType / Ampacity / Voltage Rating / Number of Poles / kAIR


Maximum Level of Selective Coordination Shown in kA
QO-VH/QOB-VH

Type
Max.
Cont.
Current
Rating

60 A

70 A

80 A

2 Pole
120/240 V

3 Pole
240 V

1 Pole
120 V

2 Pole
120/240 V

200 A

225 A

13

6.5

10

kAIR1

250 A

42

3 Pole
240 V

2 Pole
120/240 V

90100 A

1 Pole
120 V

3 Pole
240 V

2 Pole
120/240 V

3 Pole
240 V

10 kAIR

LA-MC

10

13

10

11

7.5

11

7.5

10

7.5

400 A

22

22

18

22

22

18

22

18

22

18

200 A

225 A

13

6.5

10

250 A

65

LH-MC

400 A
1

10

13

10

11

7.5

11

7.5

10

7.5

22

22

18

22

22

18

22

18

22

18

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Table 8:

LA/LH Mission Critical Circuit Breakers UL 480Y/277 Vac ED Downstream Circuit Breakers

Upstream
Circuit Breaker
Max.
Cont.
Current
1
Rating kAIR

Downstream Circuit Breaker - Type / Ampacity / kAIR


Maximum Level of Selective Coordination Shown in kA
ED (18kA)/EG (35 kA)

Type
15 A

20 A

30 A

40 A

50100 A

200 A

18

10

225 A

18

14

18

18

18

10

18

18

18

18

18

250 A

30

LA-MC

400 A
200 A

18

10

225 A

18

14

18

18

18

10

18

18

18

18

18

250 A
400 A
1

35

LH-MC

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

20052013 Schneider Electric All Rights Reserved

11

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac QO/B

0100DB0501
R02/13, 05/2013

APPENDIX B
Levels of Short Circuit Selective
Coordination for UL 489 Standard Circuit
Breakers

The data in the following tables for UL 489 Listed molded and insulated
case circuit breakers also applies to CSA C22.2 #5-02 and ANCE NMX
J-266 Certified circuit breakers. All data is at 60 Hz. The data does not apply
to circuit breakers that are Certified to IEC 60947-2 only or at frequencies
other than 60 Hz.

Appendix A
Type

Volts

Downstream
Circuit Breaker
(type or frame size)
QO/B

12

10

15

250 A

11

19

400 A

12

22

6001200 A

13

25

100150 A

14

27

250 A

15

31

400 A

16

35

6001200 A

17

38

100150 A

18

40

250 A

19

44

400 A

20

48

6001200 A

21

50

480

600

Table 9:

Fully rated and series rated pairs of circuit breakers where there is a
reasonable expectation of selective coordination are shown. Pairings of the
same frame size or where the upstream circuit breaker might be a currentlimiting circuit breaker are not shown as such pairings would not be
expected to selectively coordinate.

Page No.

100150 A
240

UL

Table No.

It should be noted that series ratings vary by equipment type, thus published
information regarding the specific type of Square D equipment being
studied should be consulted for the actual series ratings available in that
equipment.
Based on laboratory testing, Schneider Electric certifies the following levels
of selective coordination based upon the construction of the specific circuit
breakers referenced as of the date of publication of this document.

UL 240 Vac QO/B Selective Coordination

Upstream
Circuit Breaker1

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA

Type2
Max.
Cont.
Current
Rating

QO/B-VH3

QH/B3

QO/B-GFI/EPD

QO/BVHGFI/
EPD

QO/BAFI

QO/BVHAFI

1 Pole
2 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole 1 Pole
2 Pole
1 Pole 1 Pole 1 Pole
120 V 120/240 V 240 V
240 V
120 V 120/240 V 240 V
120 V 120/240 V 240 V
120 V 120/240 V 120 V
120 V
120 V
15-70 A 15-125 A 15-100 A 15-100 A 15-30 A 15-150 A 15-100 A 15-30 A 15-30 A 15-30 A 15-30 A 15-60 A 15-30 A 15-20 A 15-20 A
kAIR4

10

Mission
Critical 5

50

65

10

10

10

22

22

22

65

65

65

10

10

22

10

22

See Appendix A

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HDU360

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

HDU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-N
800/250 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

50.0

50.0

50.0

10.0

10.0

22.0

10.0

22.0

HD
25

100/
150 A

QO/B3

FH

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HG 6

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HGU360

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

HGU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-H
800/250 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

HJ

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

HJU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

HL 6

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

0.78

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

100 HJU360

125 HLU360
HLU3150

Continued on next page

12

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 9:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac QO/B

UL 240 Vac QO/B Selective Coordination (continued)

Upstream
Circuit Breaker1

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA

Type2
Max.
Cont.
Current
Rating

QO/B3

QO/B-VH3

QH/B3

QO/B-GFI/EPD

QO/BVHGFI/
EPD

QO/BAFI

QO/BVHAFI

1 Pole
2 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole 1 Pole
2 Pole
1 Pole 1 Pole 1 Pole
120 V 120/240 V 240 V
240 V
120 V 120/240 V 240 V
120 V 120/240 V 240 V
120 V 120/240 V 120 V
120 V
120 V
15-70 A 15-125 A 15-100 A 15-100 A 15-30 A 15-150 A 15-100 A 15-30 A 15-30 A 15-30 A 15-30 A 15-60 A 15-30 A 15-20 A 15-20 A
kAIR4

10

Mission
Critical 5
10

25

65

10

10

10

22

22

22

65

65

65

10

10

22

10

22

See Appendix A

QB

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

JD 6

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JDU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

QD 6, 7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

LD

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

JG 6

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JGU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LG

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

NT-H
800/250 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PG

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PK

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

QG 6, 7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

NW-N
800/250 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

PJ 8

10.0

10.0

10.0

10.0

22.0

6.3

6.3

65.0

65.0

6.3

10.0

10.0

22.0

10.0

22.0

QJ 6, 7, 9, 10

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

JL 6

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

125 JLU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LL

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

250 A

JJ

JJU3250
100 LJ

Mission
Critical 5

See Appendix A

25

LD

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

42

LA11

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

DG

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

10.0

3.1

LG

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

400 A
65

LH

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

MG 8

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

NT-H
800 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

NW-N
2000 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PG

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PK

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

100

LJ

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

125

LL

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

Continued on next page

20052013 Schneider Electric All Rights Reserved

13

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac QO/B

Table 9:

UL 240 Vac QO/B Selective Coordination (continued)

Upstream
Circuit Breaker1

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA

Type2
Max.
Cont.
Current
Rating

QO/B3

QO/B-VH3

QH/B3

QO/B-GFI/EPD

QO/BVHGFI/
EPD

QO/BAFI

QO/BVHAFI

1 Pole
2 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole
1 Pole
2 Pole
3 Pole 1 Pole
2 Pole
1 Pole 1 Pole 1 Pole
120 V 120/240 V 240 V
240 V
120 V 120/240 V 240 V
120 V 120/240 V 240 V
120 V 120/240 V 120 V
120 V
120 V
15-70 A 15-125 A 15-100 A 15-100 A 15-30 A 15-150 A 15-100 A 15-30 A 15-30 A 15-30 A 15-30 A 15-60 A 15-30 A 15-20 A 15-20 A
kAIR4

10

Mission
Critical 5
25

600 A

0100DB0501
R02/13, 05/2013

65

10

10

10

22

22

22

65

65

65

10

10

22

10

22

5.49

See Appendix A

LD

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

DG

10.0

4.6

4.6

10.0

22.0

4.6

4.6

65.0

4.6

4.6

10.0

4.6

22.0

10.0

22.0

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MG 8

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

NT-H
1200 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

NW-N
2000 A

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PG

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

PK

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

RG

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

RK

10.0

10.0

10.0

10.0

22.0

22.0

22.0

65.0

65.0

65.0

10.0

10.0

22.0

10.0

22.0

100

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

125

LL

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

Number after NW-x indicates frame size.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit breakers,
they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information.

QO plug-on and bolt-on circuit breakers.

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

See Mission Critical Circuit Breakers in Appendix A.

Series rating with 35150 A QO/B-VH 3-pole circuit breakers only

Series ratings limited to 70225 A only.

Series rating at 42 kA with 1530 A QO/B-VH 2- and 3-pole circuit breakers only.

Rated 208Y/120 Vac

10

Series rating with 35150 A QO/B-VH 2-pole circuit breakers only.

11

Series rating with 15125 A QO circuit breakers only.

14

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 10:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 100150 A

UL 240 Vac 100150 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker 1


Max. Cont.
kAIR 2
Current Rating

25
50

65

100/150 A
100

125

200

25

50

65

250 A

100

125

200

Type 3
Mission Critical 6
HD
HDU3150
NT-N 800/250 A
FH
HG
HGU3150
NT-H 800/250 A
NW-N 800/250 A
HJ
HJU3150
NT-L1 800/250 A
NW-H 800/250 A
HL
HLU3150
NT-L 800/250 A
NT-LF 800/250 A
NW-L 800/250 A
NW-LF 800/250 A
Mission Critical 6
JD
JDU3250
JDWU
QD
LD
LDWU250
NT-N 800/250 A
JG
JGU3250
JGWU
LG
LGWU250
NT-H 800/250 A
PG
PK
QG
NW-N 800/250 A
JJ
JJU3250
JJWU
LJ
LJWU250
NT-L1 800/250 A
NW-H 800/250 A
PJ
QJ 7
JL
JLU3250
JLWU
LL
LLWU250
PL
NT-L 800/250 A
NT-LF 800/250 A
NW-L 800/250 A
NW-LF 800/250 A

EDB
ECB 4
25
65
See Appendix A
1.3
1.3
1.94
1.94
25.0
50.0
1.3
1.3
1.3
1.3
1.94
1.94
25.0
65.0
25.0
65.0
1.3
1.3
1.94
1.94
25.0
65.0
25.0
65.0
1.3
1.3
1.94
1.94
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
See Appendix A
2.5
2.5
2.6
2.6
18
18
1.7
1.7
2.6
2.6
25
25
25.0
50.0
2.5
2.5
2.6
2.6
18
18
2.6
2.6
25
30
25.0
65.0
25.0
65.0
25.0
65.0
1.7
1.7
25.0
65.0
2.5
2.5
2.6
2.6
18
18
2.6
2.6
25
30
25.0
65.0
25.0
65.0
25.0
65.0
1.7
1.7
2.5
2.5
2.6
2.6
18
18
2.6
2.6
25
30
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0

20052013 Schneider Electric All Rights Reserved

EGB
65

EJB
100

FA 5
25

HD
25

FH
65

HG
65

FJ
100

HJ
100

HL
125

FI
200

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
6.3
65.0
1.3
1.94
6.3
6.3
65.0
65.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
6.3
100.0
1.3
1.94
6.3
6.3
100.0
100.0

1.3
1.94
25.0
1.3
1.3
1.94
25.0
25.0
1.3
1.94
6.3
25.0
1.3
1.94
6.3
6.3
25.0
25.0

1.3
1.94
25.0
1.3
1.3
1.94
25.0
25.0
1.3
1.94
25.0
25.0
1.3
1.94
25.0
25.0
25.0
25.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
6.3
65.0
1.3
1.94
6.3
6.3
65.0
65.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
33.5
65.0
1.3
1.94
33.5
33.5
65.0
65.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
6.3
100.0
1.3
1.94
6.3
6.3
100.0
100.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
33.5
100.0
1.3
1.94
33.5
33.5
100.0
100.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
33.5
100.0
1.3
1.94
33.5
33.5
125.0
125.0

1.3
1.94
50.0
1.3
1.3
1.94
65.0
65.0
1.3
1.94
30.8
100.0
0.9
1.94
30.8
30.8
200.0
200.0

2.5
2.6
18
1.7
2.6
25
50.0
2.5
2.6
18
2.6
30
65.0
65.0
65.0
1.7
65.0
2.5
2.6
18
2.6
30
6.3
65.0
6.3
1.7
2.5
2.6
18
2.6
30
6.3
6.3
6.3
65.0
65.0

2.5
2.6
18
1.7
2.6
25
50.0
2.5
2.6
18
2.6
30
65.0
65.0
65.0
1.7
65.0
2.5
2.6
18
2.6
30
6.3
100.0
6.3
1.7
2.5
2.6
18
2.6
30
6.3
6.3
6.3
100.0
100.0

2.5
2.6
2.6
1.7
2.6
2.6
25.0
2.5
2.6
2.6
2.6
2.6
25.0
25.0
25.0
1.7
25.0
2.5
2.6
2.6
2.6
2.6
6.3
25.0
6.3
1.7
2.5
2.6
2.6
2.6
2.6
6.3
6.3
6.3
25.0
25.0

2.5
2.6
8
1.7
2.6
8
25.0
2.5
2.6
8
2.6
8
25.0
25.0
25.0
1.7
25.0
2.5
2.6
8
2.6
8
25.0
25.0
25.0
1.7
2.5
2.6
8
2.6
8
25.0
25.0
25.0
25.0
25.0

2.5
2.6
2.6
1.7
2.6
2.6
50.0
2.5
2.6
2.6
2.6
2.6
65.0
65.0
65.0
1.7
65.0
2.5
2.6
2.6
2.6
2.6
6.3
65.0
6.3
1.7
2.5
2.6
2.6
2.6
2.6
6.3
6.3
6.3
65.0
65.0

2.5
2.6
8
1.7
2.6
8
50.0
2.5
2.6
8
2.6
8
65.0
65.0
65.0
1.7
65.0
2.5
2.6
8
2.6
8
33.5
65.0
33.5
1.7
2.5
2.6
8
2.6
8
33.5
33.5
33.5
65.0
65.0

2.5
2.6
8
1.7
2.6
8
50.0
2.5
2.6
8
2.6
8
65.0
65.0
65.0
1.7
65.0
2.5
2.6
8
2.6
8
6.3
100.0
6.3
1.7
2.5
2.6
8
2.6
8
6.3
6.3
6.3
100.0
100.0

2.5
2.5
2.5
2.6
2.6
2.6
8
8
8
1.7
1.7
1.7
2.6
2.6
2.6
8
8
8
50.0
50.0
50.0
2.5
2.5
2.5
2.6
2.6
2.6
8
8
8
2.6
2.6
2.6
8
8
8
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
1.7
1.7
1.7
65.0
65.0
65.0
2.5
2.5
2.5
2.6
2.6
2.6
8
8
8
2.6
2.6
2.6
8
8
8
33.5
33.5
30.8
100.0
100.0
100.0
33.5
33.5
30.8
1.7
1.7
1.7
2.5
2.5
2.5
2.6
2.6
2.6
8
8
8
2.6
2.6
2.6
8
8
8
33.5
33.5
30.8
33.5
33.5
30.8
33.5
33.5
30.8
100.0
125.0
200.0
100.0
125.0
200.0
Continued on next page

15

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 100150 A

Table 10:

UL 240 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker 1


Max. Cont.
kAIR 2
Current Rating

25
42
50

65

400 A

100

125

200

25
50

65

600 A

100

125

16

0100DB0501
R02/13, 05/2013

Type 3
Mission Critical 6
LD
LDWU3400
LA
LA-MC6
NT-N 800 A
DG
LG
LGWU3400
LH
LH-MC6
MG
NT-H 800 A
NW-N 2000 A
PG
PK
DJ
LJ
LJWU3400
MJ
NT-L1 800 A
NW-H 2000 A
PJ
LL
LLWU3400
PL
NT-L 800 A
NT-LF 800 A
NW-L 1600 A
NW-LF 1600 A
Mission Critical 6
LD
LDWU3600
NT-N 1200 A
DG
LG
LGWU3600
MG
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK
DJ
LJ
LJWU3600
MJ
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
LL
LLWU3600
PL
RL

EDB
ECB 4
25
65
See Appendix A
4.17
4.17
25
25
4.0
4.0
7.0
7.0
25.0
50.0
3.1
3.1
4.17
4.17
25
30
4.0
4.0
7.0
7.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
3.1
3.1
4.17
4.17
25
30
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
4.17
4.17
25
30
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
See Appendix A
5.49
5.49
25
25
25.0
50.0
4.6
4.6
5.49
5.49
25
30
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
4.6
4.6
5.49
5.49
25
30
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
25.0
65.0
5.49
5.49
25
30
25.0
65.0
25.0
65.0

EGB
65

EJB
100

FA 5
25

HD
25

FH
65

HG
65

FJ
100

HJ
100

HL
125

FI
200

4.17
25
4.0
7.0
50.0
3.1
4.17
30
4.0
7.0
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
65.0
65.0
65.0
65.0
4.17
30
65.0
65.0
65.0
65.0
65.0

4.17
25
4.0
7.0
50.0
3.1
4.17
30
4.0
7.0
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
100.0
100.0
100.0
100.0
4.17
30
100.0
100.0
100.0
100.0
100.0

4.17
4.17
4.0
7.0
25.0
3.1
4.17
4.17
4.0
7.0
25.0
25.0
25.0
25.0
25.0
3.1
4.17
4.17
25.0
25.0
25.0
25.0
4.17
4.17
25.0
25.0
25.0
25.0
25.0

4.17
25
4.0
12.4
25.0
3.1
4.17
25
4.0
12.4
25.0
25.0
25.0
25.0
25.0
3.1
4.17
25
25.0
25.0
25.0
25.0
4.17
25
25.0
25.0
25.0
25.0
25.0

4.17
4.17
4.0
7.0
50.0
3.1
4.17
4.17
4.0
7.0
10.8
65.0
65.0
65.0
65.0
3.1
4.17
4.17
10.8
9.0
65.0
9.0
4.17
4.17
9.0
9.0
9.0
65.0
65.0

4.17
25
4.0
12.4
50.0
3.1
4.17
30
4.0
12.4
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
65.0
65.0
65.0
65.0
4.17
30
65.0
65.0
65.0
65.0
65.0

4.17
25
4.0
7.0
50.0
3.1
4.17
30
4.0
7.0
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
100.0
100.0
100.0
100.0
4.17
30
100.0
100.0
100.0
100.0
100.0

4.17
25
4.0
12.4
50.0
3.1
4.17
30
4.0
12.4
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
100.0
100.0
100.0
100.0
4.17
30
100.0
100.0
100.0
100.0
100.0

4.17
25
4.0
12.4
50.0
3.1
4.17
30
4.0
12.4
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
100.0
100.0
100.0
100.0
4.17
30
125.0
125.0
125.0
125.0
125.0

4.17
25
4.0
13.0
50.0
3.1
4.17
30
4.0
13.0
65.0
65.0
65.0
65.0
65.0
3.1
4.17
30
100.0
100.0
100.0
100.0
4.17
30
100.0
100.0
100.0
200.0
200.0

5.49
25
50.0
4.6
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
30
65.0
65.0
65.0
65.0
65.0
5.49
30
65.0
65.0

5.49
25
50.0
4.6
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
30
100.0
100.0
100.0
100.0
100.0
5.49
30
100.0
100.0

5.49
5.49
25.0
4.6
5.49
5.49
25.0
25.0
25.0
25.0
25.0
25.0
25.0
4.6
5.49
5.49
25.0
25.0
25.0
25.0
25.0
5.49
5.49
25.0
25.0

5.49
25
25.0
12.8
5.49
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
12.8
5.49
25
25.0
25.0
25.0
25.0
25.0
5.49
25
25.0
25.0

5.49
5.49
50.0
4.6
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
5.49
10.8
9.0
65.0
9.0
65.0
5.49
5.49
9.0
65.0

5.49
25
50.0
12.8
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
12.8
5.49
30
65.0
65.0
65.0
65.0
65.0
5.49
30
65.0
65.0

5.49
25
50.0
4.6
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
30
100.0
100.0
100.0
100.0
100.0
5.49
30
100.0
100.0

5.49
5.49
5.49
25
25
25
50.0
50.0
50.0
12.8
12.8
13.5
5.49
5.49
5.49
30
30
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
12.8
12.8
13.5
5.49
5.49
5.49
30
30
30
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
5.49
5.49
5.49
30
30
30
100.0
125.0
100.0
100.0
125.0
125.0
Continued on next page

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 10:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 100150 A

UL 240 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker 1


Max. Cont.
kAIR 2
Current Rating

600 A

200

50

65

800 A
100

125

200

50

65

1000 A

100

125

200

50

1200 A

65

Type 3
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
MG
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK
MJ
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
PL
RL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
PL
RL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK

EDB
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

ECB 4
65
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

20052013 Schneider Electric All Rights Reserved

EGB
65
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

EJB
100
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

FA 5
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

HD
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

FH
65
9.0
9.0
65.0
65.0
50.0
10.8
65.0
65.0
65.0
65.0
65.0
65.0
10.8
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

HG
65
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

FJ
100
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

HJ
HL
FI
100
125
200
100.0
125.0
100.0
100.0
125.0
100.0
100.0
125.0
200.0
100.0
125.0
200.0
50.0
50.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
125.0
100.0
100.0
125.0
125.0
100.0
125.0
100.0
100.0
125.0
100.0
100.0
125.0
200.0
100.0
125.0
200.0
50.0
50.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
125.0
100.0
100.0
125.0
125.0
100.0
125.0
100.0
100.0
125.0
100.0
100.0
125.0
200.0
100.0
125.0
200.0
50.0
50.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
Continued on next page

17

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 100150 A

Table 10:

UL 240 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker 1


Max. Cont.
kAIR 2
Current Rating

100

1200 A

125

200

65

1600 A

100
125
200

65

2000 A

100
125
200
65

25003000 A

40006000 A

0100DB0501
R02/13, 05/2013

100
125
200
100
200

Type 3
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
PL
RL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NW-N 2000 A
RG
RK
NW-H 2000 A
RJ
RL
NW-L 1600 A
NW-LF 1600 A
NW-N 2000 A
RG
RK
NW-H 2000 A
RJ
RL
NW-L 2000 A
NW-LF 2000 A
RG
RK
NW-H 3000 A
RJ
RL
NW-L 3000 A
NW-H 6000 A
NW-L 6000 A

EDB
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

ECB 4
65
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

EGB
65
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

EJB
100
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0

FA 5
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

HD
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

FH
65
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

HG
65
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

FJ
100
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0

HJ
100
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0

HL
125
100.0
100.0
100.0
100.0
125.0
125.0
125.0
125.0
125.0
125.0
65.0
65.0
65.0
100.0
100.0
125.0
125.0
125.0
65.0
65.0
65.0
100.0
100.0
125.0
125.0
125.0
65.0
65.0
100.0
100.0
125.0
125.0
100.0
125.0

FI
200
100.0
100.0
100.0
100.0
100.0
125.0
100.0
100.0
200.0
200.0
65.0
65.0
65.0
100.0
100.0
125.0
200.0
200.0
65.0
65.0
65.0
100.0
100.0
125.0
200.0
200.0
65.0
65.0
100.0
100.0
125.0
200.0
100.0
200.0

Number after NW-x indicates frame size.

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit breakers,
they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information.
When used as downstream circuit breakers, there is no difference in selectivity so the standard HD, etc. types include all trip unit options.

3-pole 30A ECB circuit breaker is rated 42kA at 240V.

600 Vac rated FA - 240 Vac rated FA has AIR of 10 kA.

See Mission Critical Circuit Breakers in Appendix A.

Rated 208Y/120 Vac.

18

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 11:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 250 A

UL 240 Vac 250 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type4

Max. Cont.
Current
kAIR1
Rating
25
42
50

65

400 A

100

125

200

25
50

65

600 A

100

125

QB

QD

JD

QG

JG

PG

QJ3

JJ

LD

LG

LJ

LL

LE

LX

PJ

JL

PL

KI

10

25

25

65

65

65

100

100

25

65

100

125

100

100

100

125

125

200

LD

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

LDWU3400
LA
LA-MC
NT-N 1200 A
DG
LG
LGWU3400
LH-MC
LH
MG
NT-H 1200 A
NW-N 2000 A
PG
PK
DJ

4.17
4.0
7.0
10.0
3.1
4.17

4.17
4.0
7.0
25.0
3.1
4.17

25
4.0
10.3
25.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

25
4.0
10.3
50.0
3.1
4.17

4.17
4.0
7.0
36.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

25
4.0
10.3
50.0
3.1
4.17

4.17
4.0
7.0
25.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

4.17
4.0
7.0
50.0
3.1
4.17

4.17
4.0
7.0
36.0
3.1
4.17

25
4.0
10.3
50.0
3.1
4.17

4.17
4.0
7.0
36.0
3.1
4.17

4.17
4.0
10.2
50.0
3.1
4.17

4.17
7.0
4.0
10.0
10.0
10.0
10.0
10.0
3.1

4.17
7.0
4.0
25.0
25.0
25.0
25.0
25.0
3.1

25
10.3
4.0
25.0
25.0
25.0
25.0
25.0
3.1

4.17
7.0
4.0
10.8
65.0
65.0
65.0
65.0
3.1

30
10.3
4.0
65.0
65.0
65.0
65.0
65.0
3.1

4.17
7.0
4.0
10.8
36.0
36.0
21.6
21.6
3.1

4.17
7.0
4.0
10.8
65.0
65.0
65.0
65.0
3.1

30
10.3
4.0
65.0
65.0
65.0
65.0
65.0
3.1

4.17
7.0
4.0
10.8
25.0
25.0
21.6
21.6
3.1

4.17
7.0
4.0
10.8
65.0
65.0
21.6
21.6
3.1

4.17
7.0
4.0
10.8
65.0
65.0
21.6
21.6
3.1

4.17
7.0
4.0
10.8
65.0
65.0
21.6
21.6
3.1

4.17
7.0
4.0
10.8
65.0
65.0
65.0
65.0
3.1

4.17
7.0
4.0
10.8
65.0
65.0
65.0
65.0
3.1

4.17
7.0
4.0
10.8
36.0
36.0
21.6
21.6
3.1

30
10.3
4.0
125
65.0
65.0
65.0
65.0
3.1

4.17
7.0
4.0
10.8
36.0
36.0
21.6
21.6
3.1

4.17
10.2
4.0
65.0
65.0
65.0
65.0
65.0
3.1

LJ
LJWU3400
MJ
NT-L1 1200 A
NW-H 2000 A
PJ
LL
LLWU3400
PL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A

4.17
4.17
10.0
10.0
10.0
10.0
4.17
4.17
10.0
10.0
10.0
10.0

4.17
4.17
25.0
25.0
25.0
25.0
4.17
4.17
25.0
25.0
25.0
25.0

4.17
25
25.0
25.0
25.0
25.0
4.17
25
25.0
25.0
25.0
25.0

4.17
4.17
10.8
9.0
65.0
9.0
4.17
4.17
9.0
9.0
9.0
65.0

4.17
30
65.0
65.0
65.0
65.0
4.17
30
65.0
65.0
65.0
65.0

4.17 4.17 4.17 4.17


4.17 4.17
30
4.17
10.8 10.8 100.0 10.8
9.0
9.0 100.0
9
36.0 100.0 100.0 25
9.0
9.0 100.0 9.0
4.17 4.17 4.17 4.17
4.17 4.17
30
4.17
9.0
9.0 100.0 9.0
9.0
9.0 100.0 9.0
9.0
9.0 100.0 9.0
31.5 100.0 100.0 25.0

4.17 4.17 4.17 4.17


4.17 4.17 4.17 4.17
10.8 10.8 10.8 10.8
9
9
9
9.0
65 100.0 100.0 100.0
9.0
9.0
9.0
9.0
4.17 4.17 4.17 4.17
4.17 4.17 4.17 4.17
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
65.0 100.0 125.0 100.0

4.17
4.17
10.8
9.0
100.0
9.0
4.17
4.17
9.0
9.0
9.0
100.0

4.17
4.17
10.8
9.0
36.0
9.0
4.17
4.17
9.0
9.0
9.0
31.5

4.17
30
100.0
100.0
100.0
100.0
4.17
30
107.0
107.0
107.0
125.0

4.17
4.17
10.8
9.0
36.0
9.0
4.17
4.17
9.0
9.0
9.0
31.5

4.17
4.17
100.0
69.7
100.0
69.7
4.17
4.17
69.7
69.7
69.7
200.0

NW-LF 1600 A
LD
LDWU3600
NT-N 1200 A
DG
LG
LGWU3600
MG
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK
DJ
LJ
LJWU3600
MJ
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
LL
LLWU3600
PL
RL

10.0
5.49
5.49
10.0
4.6
5.49
5.49
10.0
10.0
10.0
10.0
10.0
10.0
10.0
4.6
5.49
5.49
10.0
10.0
10.0
10.0
10.0
5.49
5.49
10.0
10.0

25.0
5.49
5.49
25.0
4.6
5.49
5.49
25.0
25.0
25.0
25.0
25.0
25.0
25.0
4.6
5.49
5.49
25.0
25.0
25.0
25.0
25.0
5.49
5.49
25.0
25.0

25.0
5.49
25
25.0
10.6
5.49
25
25.0
25.0
25.0
25.0
25.0
25.0
25.0
10.6
5.49
25
25.0
25.0
25.0
25.0
25.0
5.49
25
25.0
25.0

65.0
5.49
5.49
50.0
4.6
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
5.49
10.8
9.0
65.0
9.0
65.0
5.49
5.49
9.0
65.0

65.0
5.49
25
50.0
10.6
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
10.6
5.49
30
65.0
65.0
65.0
65.0
65.0
5.49
30
65.0
65.0

21.6
5.49
5.49
36.0
4.6
5.49
5.49
10.8
36.0
36.0
21.6
21.6
51.3
51.3
4.6
5.49
5.49
10.8
9.0
36.0
9.0
40.8
5.49
5.49
9.0
40.8

65.0
5.49
5.49
50.0
4.59
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.59
5.49
5.49
10.8
9.0
65.0
9.0
65.0
5.49
5.49
9.0
65.0

100.0
5.49
5.49
50.0
4.6
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
5.49
10.8
9.0
100.0
9.0
100.0
5.49
5.49
9.0
100.0

21.6
5.49
5.49
36.0
4.6
5.49
5.49
10.8
36.0
36.0
21.6
21.6
65.0
65.0
4.6
5.49
5.49
10.8
9.0
36.0
9.0
40.8
5.49
5.49
9.0
40.8

20052013 Schneider Electric All Rights Reserved

100.0
5.49
5.49
50.0
4.6
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
5.49
10.8
9.0
100.0
9.0
100.0
5.49
5.49
9.0
100.0

100.0
5.49
25
50.0
10.6
5.49
30
65.0
65.0
65.0
65.0
65.0
65.0
65.0
10.6
5.49
30
100.0
100.0
100.0
100.0
100.0
5.49
30
100.0
100.0

25.0
5.49
5.49
25.0
4.59
5.49
5.49
10.8
25.0
25.0
25.0
25.0
25.0
25.0
4.59
5.49
5.49
10.8
9.0
25.0
9.0
25.0
5.49
5.49
9.0
25.0

100.0
5.49
5.49
50.0
4.59
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.59
5.49
5.49
10.8
9.0
100.0
9.0
100.0
5.49
5.49
9.0
100.0

125.0
5.49
5.49
50.0
4.59
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.59
5.49
5.49
10.8
9.0
100.0
9.0
100.0
5.49
5.49
9.0
125.0

100.0
5.49
5.49
50.0
4.6
5.49
5.49
10.8
65.0
65.0
65.0
65.0
65.0
65.0
4.6
5.49
5.49
10.8
9.0
100.0
9.0
100.0
5.49
5.49
9.0
100.0

125.0 21.6 200.0


5.49 5.49 5.49
25
5.49 5.49
50.0 36.0 50.0
10.6
4.6
10.6
5.49 5.49 5.49
30
5.49 5.49
65.0 10.8 65.0
65.0 36.0 65.0
65.0 36.0 65.0
65.0 21.6 65.0
65.0 21.6 65.0
65.0 65.0 65.0
65.0 65.0 65.0
10.6
4.6
10.6
5.49 5.49 5.49
30
5.49 5.49
100.0 10.8 100.0
100.0 9.0
69.7
100.0 36.0 100.0
100.0 9.0
69.7
100.0 40.8 100.0
5.49 5.49 5.49
30
5.49 5.49
107.4 9.0
69.7
125.0 40.8 125.0
Continued on next page

19

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 250 A

Table 11:

UL 240 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
kAIR1
Rating

600 A

200

50
65

65

800 A
100

125

200

50

65

1000 A

100

125

200

50

65
1200 A

100

20

0100DB0501
R02/13, 05/2013

Type4

QB
10

25

25

65

65

NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
MG
NT-H 1200 A
NW-N 2000 A
PG
PK
RG

10.0
10.0
10.0

25.0
25.0
25.0

25.0
25.0
25.0

9.0
9.0
65.0

65.0
65.0
65.0

9.0
9.0 100.0 9.0
9.0
9.0 100.0 9.0
31.5 100.0 100.0 25.0

9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
65.0 100.0 125.0 100.0 100.0

10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

65.0
50.0
10.8
65.0
65.0
65.0
65.0
65.0

65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

21.6 100.0 100.0 25.0


36.0 50.0 50.0 25.0
10.8 10.8 65.0 10.8
36.0 65.0 65.0 25.0
36.0 65.0 65.0 25.0
21.6 65.0 65.0 25.0
21.6 65.0 65.0 25.0
51.3 65.0 65.0 25.0

65.0 100.0 125.0


50.0 50.0 50.0
10.8 10.8 10.8
65.0 65.0 65.0
65.0 65.0 65.0
65.0 65.0 65.0
65.0 65.0 65.0
65.0 65.0 65.0

RK
MJ
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
PL
RL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
NT-H 1200 A
NW-N 2000 A
PG
PK
RG

10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

65.0
10.8
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0

51.3
10.8
9.0
36.0
9.0
40.8
9.0
40.8
9.0
9.0
31.5
21.6
36.0
36.0
36.0
21.6
21.6
51.3

65.0
10.8
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0

25.0
10.8
9.0
25.0
9.0
25.0
9.0
25.0
9.0
9.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

65.0
10.8
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
10.8
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0

RK
NT-L1 1200 A
NW-H 2000 A
PJ
RJ
PL
RL
NT-L 1200 A
NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NT-N 1200 A
NT-H 1200 A
NW-N 2000 A
PG
PK
RG
RK
NT-L1 1200 A
NW-H 2000 A
PJ
RJ

10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

65.0
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
65.0
9.0
65.0

65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

51.3
9.0
36.0
9.0
40.8
9.0
40.8
9.0
9.0
31.5
21.6
36.0
36.0
36.0
21.6
21.6
51.3
51.3
9.0
36.0
9.0
40.8

65.0
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
100.0
9.0
100.0

65.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0

25.0
9.0
25.0
9.0
25.0
9.0
25.0
9.0
9.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
9.0
25.0
9.0
25.0

65.0
9.0
65.0
9.0
65.0
9.0
65.0
9.0
9.0
65.0
65.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
65.0
9.0
65.0

65.0
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
100.0
9.0
100.0

QD

JD

QG

JG

PG

QJ3

JJ

LD

65

100

100

25

LG

LJ

LL

LE

LX

PJ

JL

PL

65

100

125

100

100

KI

100

125

125

200

9.0
9.0
31.5

107.4
107.4
125.0

9.0
9.0
31.5

69.7
69.7
200.0

100.0
50.0
10.8
65.0
65.0
65.0
65.0
65.0

100.0 21.6
50.0 36.0
10.8 10.8
65.0 36.0
65.0 36.0
65.0 21.6
65.0 21.6
65.0 65.0

125.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

21.6
36.0
10.8
36.0
36.0
21.6
21.6
65.0

200.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0

65.0
10.8
9.0
100.0
9.0
100.0
9.0
125.0
9.0
9.0
125.0
125.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
10.8
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0 65.0
10.8 10.8
9.0
9.0
100.0 36.0
9.0
9.0
100.0 40.8
9.0
9.0
100.0 40.8
9.0
9.0
9.0
9.0
100.0 31.5
100.0 21.6
50.0 36.0
65.0 36.0
65.0 36.0
65.0 21.6
65.0 21.6
65.0 65.0

65.0
100.0
100.0
100.0
100.0
100.0
107.4
125.0
107.4
107.4
125.0
125.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
10.8
9.0
36.0
9.0
40.8
9.0
40.8
9.0
9.0
31.5
21.6
36.0
36.0
36.0
21.6
21.6
65.0

65.0
100.0
69.7
100.0
69.7
100.0
69.7
125.0
69.7
69.7
200.0
200.0
50.0
65.0
65.0
65.0
65.0
65.0

65.0
9.0
100.0
9.0
100.0
9.0
125.0
9.0
9.0
125.0
125.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
100.0
9.0
100.0

65.0
9.0
100.0
9.0
100.0
9.0
100.0
9.0
9.0
100.0
100.0
50.0
65.0
65.0
65.0
65.0
65.0
65.0
9.0
100.0
9.0
100.0

65.0 65.0
9.0
9.0
100.0 36.0
9.0
9.0
100.0 40.8
9.0
9.0
100.0 40.8
9.0
9.0
9.0
9.0
100.0 31.5
100.0 21.6
50.0 36.0
65.0 36.0
65.0 36.0
65.0 21.6
65.0 21.6
65.0 65.0
65.0 65.0
9.0
9.0
100.0 36.0
9.0
9.0
100.0 40.8

65.0 65.0 65.0


100.0 9.0
69.7
100.0 36.0 100.0
100.0 9.0
69.7
100.0 40.8 100.0
107.4 9.0
69.7
125.0 40.8 125.0
107.4 9.0
69.7
107.4 9.0
69.7
125.0 31.5 200.0
125.0 21.6 200.0
50.0 36.0 50.0
65.0 36.0 65.0
65.0 36.0 65.0
65.0 21.6 65.0
65.0 21.6 65.0
65.0 65.0 65.0
65.0 65.0 65.0
100.0 9.0
69.7
100.0 36.0 100.0
100.0 9.0
69.7
100.0 40.8 100.0
Continued on next page

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 11:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 250 A

UL 240 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
kAIR1
Rating
125
1200 A
200

65

1600 A

100
125
200

65

2000 A

100
125
200
65

Type4

QB

QD

JD

QG

JG

PG

QJ3

JJ

LD

65

100

100

25

LG

LJ

LL

LE

LX

PJ

65

100

125

100

100

JL

PL

KI

10

25

25

65

65

100

125

125

200

PL
RL
NT-L 1200 A

10.0
10.0
10.0

25.0
25.0
25.0

25.0
25.0
25.0

9.0
65.0
9.0

65.0
65.0
65.0

9.0
9.0 100.0 9.0
40.8 100.0 100.0 25.0
9.0
9.0 100.0 9.0

9.0
9.0
9.0
9.0
9.0
65.0 100.0 125.0 100.0 100.0
9.0
9.0
9.0
9.0
9.0

9.0
40.8
9.0

107.4
125.0
107.4

9.0
40.8
9.0

69.7
125.0
69.7

NT-LF 1200 A
NW-L 1600 A
NW-LF 1600 A
NW-N 2000 A
RG
RK
NW-H 2000 A
RJ
RL
NW-L 1600 A
NW-LF 1600 A
NW-N 2000 A
RG
RK

10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

9.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

9.0
31.5
21.6
36.0
51.3
51.3
36.0
40.8
40.8
31.5
21.6
36.0
51.3
51.3

9.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0

100.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0

9.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0

9.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

9.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0

9.0
125.0
125.0
65.0
65.0
65.0
100.0
100.0
125.0
125.0
125.0
65.0
65.0
65.0

9.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0

9.0
100.0
100.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
65.0
65.0
65.0

9.0
31.5
21.6
36.0
65.0
65.0
36.0
40.8
40.8
31.5
21.6
36.0
65.0
65.0

107.4
125.0
125.0
65.0
65.0
65.0
100.0
100.0
125.0
125.0
125.0
65.0
65.0
65.0

9.0
31.5
21.6
36.0
65.0
65.0
36.0
40.8
40.8
31.5
21.6
36.0
65.0
65.0

69.7
200.0
200.0
65.0
65.0
65.0
100.0
100.0
125.0
200.0
200.0
65.0
65.0
65.0

NW-H 2000 A
RJ
RL
NW-L 2000 A
NW-LF 2000 A
RG

10.0
10.0
10.0
10.0
10.0
10.0

25.0
25.0
25.0
25.0
25.0
25.0

25.0
25.0
25.0
25.0
25.0
25.0

65.0
65.0
65.0
65.0
65.0
65.0

65.0
65.0
65.0
65.0
65.0
65.0

36.0
40.8
40.8
65.0
21.6
51.3

100.0
100.0
100.0
100.0
100.0
65.0

100.0
100.0
100.0
100.0
100.0
65.0

25.0
25.0
25.0
25.0
25.0
25.0

65.0
65.0
65.0
65.0
65.0
65.0

100.0
100.0
100.0
100.0
100.0
65.0

100.0
100.0
125.0
125.0
125.0
65.0

100.0
100.0
100.0
100.0
100.0
65.0

100.0 36.0 100.0 36.0 100.0


100.0 40.8 100.0 40.8 100.0
100.0 40.8 125.0 40.8 125.0
100.0 100.0 125.0 125.0 200.0
100.0 21.6 125.0 21.6 200.0
65.0 65.0 65.0 65.0 65.0

RK
10.0 25.0 25.0 65.0 65.0 51.3 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0
NW-H 3000 A 10.0 25.0 25.0 65.0 65.0 65.0 100.0 100.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0
100
RJ
10.0 25.0 25.0 65.0 65.0 40.8 100.0 100.0 25.0 65.0 100.0 100.0 100.0 100.0 40.8 100.0 40.8 100.0
125 RL
10.0 25.0 25.0 65.0 65.0 40.8 100.0 100.0 25.0 65.0 100.0 125.0 100.0 100.0 40.8 125.0 40.8 125.0
200 NW L 3000 A
10.0 25.0 25.0 65.0 65.0 65.0 100.0 100.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 125.0 125.0 200.0
40006000 100 NW-H 6000 A 10.0 25.0 25.0 65.0 65.0 65.0 100.0 100.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0
A
200 NW-L 6000 A
10.0 25.0 25.0 65.0 65.0 65.0 100.0 100.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 125.0 125.0 200.0
1 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.
25003000
A

Number after NW-x indicates frame size.

3 pole QJ circuit breakers are rated 100 kA at 208Y/120 Vac.

When J- and L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as
standard J- and L-frame circuit breaker.

20052013 Schneider Electric All Rights Reserved

21

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 400 A

Table 12:

UL 240 Vac 400 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
Rating

0100DB0501
R02/13, 05/2013

Type4
kAIR1

Q4

LA

LAMC

LH

LHMC

DG

DJ

DJMC3

PG

LD

LG

LJ

LL

LC

LE

LX

PJ

PL

LI

LXI

25

42

42

65

65

65

100

65

65

25

65

100

125

100

100

100

100

125

200

200

25

LD

5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49

50

NT-N 1200 A

25.0 42.0 42.0 50.0 50.0 50.0 50.0 50.0 36.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 50.0 50.0

65

600 A
100

125

200

50

65

800 A
100

125

200

DG

4.6

LG

5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49

4.6

4.6

4.6

4.6

4.6

4.6

MG

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 19.5 19.5

NT-H 1200 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

4.6

4.6

4.59 4.59 4.59 4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

PG

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

PK

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0
4.6

4.6

4.6

4.6

4.6

4.6

4.6

9.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

LL

5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49
9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0
9.0

9.0

9.0

PJ

9.0

9.0

9.0

RJ

9.0

9.0

9.0

4.6

NT-L1 1200 A

9.0

9.0

4.6

4.6

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 19.5 19.5
9.0

4.6

4.59 4.59 4.59 4.59

MJ

9.0

4.6

4.6

4.6

5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49 5.49
9.0

4.6

4.6

DJ
LJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

25.0 42.0 42.0 31.5 65.0 65.0 100.0 65.0 31.5 25.0 65.0 100.0 125.0 100.0 100.0 100.0 31.5 31.5 200.0 200.0

NW-LF 1600 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0

NT-N 1200 A

25.0 42.0 42.0 50.0 50.0 50.0 50.0 50.0 36.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0

MG

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

NT-H 1200 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

PG

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

PK

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

MJ

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 19.5 19.5

50

50

NT-L1 1200 A

9.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

9.0
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0
9.0

9.0

9.0

PJ

9.0

9.0

9.0

RJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

25.0 42.0 42.0 31.5 31.5 65.0 100.0 65.0 31.5 25.0 65.0 100.0 125.0 100.0 100.0 100.0 31.5 31.5 200.0 200.0

NW-LF 1600 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0
Continued on next page

22

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 12:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 400 A

UL 240 Vac 400 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
Rating

Type4
kAIR1
50

65
1000 A

100

125
1000 A
200

50

65

1200 A

100

125

200

65

1600 A

100
125
200

NT-N 1200 A

Q4

LA

LAMC

LH

LHMC

DG

DJ

DJMC3

PG

LD

LG

LJ

LL

LC

LE

LX

PJ

PL

LI

LXI

25

42

42

65

65

65

100

65

65

25

65

100

125

100

100

100

100

125

200

200

25.0 42.0 42.0 50.0 50.0 50.0 50.0 50.0 36.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 50.0 50.0

NT-H 1200 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

PG

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

PK

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

NT-L1 1200 A

9.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

9.0
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0
9.0

9.0

9.0

PJ

9.0

9.0

9.0

RJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

25.0 42.0 42.0 31.5 31.5 65.0 100.0 65.0 31.5 25.0 65.0 100.0 125.0 100.0 100.0 100.0 31.5 31.5 200.0 200.0

NW-LF 1600 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0

NT-N 1200 A

25.0 42.0 42.0 50.0 50.0 50.0 50.0 50.0 36.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 50.0 50.0

NT-H 1200 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

PG

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

PK

21.6 21.6 21.6 21.6 21.6 65.0 65.0 65.0 21.6 25.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

NT-L1 1200 A

9.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

9.0
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0
9.0

9.0

9.0

PJ

9.0

9.0

9.0

RJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

25.0 42.0 42.0 31.5 31.5 65.0 100.0 65.0 31.5 25.0 65.0 100.0 125.0 100.0 100.0 100.0 31.5 31.5 200.0 200.0

NW-LF 1600 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

RJ

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

NW-L 1600 A

25.0 42.0 42.0 31.5 31.5 65.0 100.0 65.0 31.5 25.0 65.0 100.0 125.0 100.0 100.0 100.0 31.5 31.5 200.0 200.0

NW-LF 1600 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0
Continued on next page

20052013 Schneider Electric All Rights Reserved

23

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 400 A

Table 12:

UL 240 Vac 400 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
Rating

Type4
kAIR1

65

2000 A

100
125
200
65
65

2500
3000 A

4000
6000 A

0100DB0501
R02/13, 05/2013

Q4

LA

LAMC

LH

LHMC

DG

DJ

DJMC3

PG

LD

LG

LJ

LL

LC

LE

LX

PJ

PL

LI

LXI

25

42

42

65

65

65

100

65

65

25

65

100

125

100

100

100

100

125

200

200

NW-N 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 36.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 65.0 65.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

NW-H 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 36.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 100.0 100.0

RJ

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

NW-L 2000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 125.0 200.0 200.0

NW-LF 2000 A

21.6 21.6 21.6 21.6 21.6 65.0 100.0 65.0 21.6 25.0 65.0 100.0 125.0 100.0 100.0 100.0 21.6 21.6 141.0 141.0

RG

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

RK

25.0 42.0 42.0 65.0 65.0 65.0 65.0 65.0 51.3 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0

NW-H 3000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

RJ

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 100.0 100.0

125

RL

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 40.8 25.0 65.0 100.0 125.0 100.0 100.0 100.0 40.8 40.8 125.0 125.0

200

NW-L 3000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 125.0 200.0 200.0

100

NW-H 6000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0

200

NW-L 6000 A

25.0 42.0 42.0 65.0 65.0 65.0 100.0 65.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 125.0 200.0 200.0

100

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

DJ-MC circuit breakers are rated 65 kA at 208Y/120 Vac.

When L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as standard Lframe circuit breaker.

24

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 13:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 6001200 A

UL 240 Vac 6001200 A Selective Coordination

Upstream Circuit
Breaker2
Max.
Cont.
Current
1
Rating kAIR
50

65

800 A
100

125

200

Type4

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA
DG

DJ

DJMC3

LD

LG

LJ

LXI

MG

MJ

PG

PK

PJ

65

100

65.0

25

65

100 125 100 100 100 200 200

65

100

65

65

100 125

LL

LC

LE

LX

LI

PL

NT- NTN
H

NTL1

NTL

50

100

200

65

NT-N 1200 A

50.0 50.0 50.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

MG

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 19.5 19.5 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

NT-H 1200 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-N 2000 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

PG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

PK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

MJ

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 19.5 19.5 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

NT-L1 1200 A

9.0

NW-H 2000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PJ

9.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-LF 1600 A 65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
50

NT-N 1200 A

50.0 50.0 50.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

NT-H 1200 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-N 2000 A 65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0
65

1000 A

100

125

200

PG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

PK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

NT-L1 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A 65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0
PJ

9.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

9.0
9.0

6.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-LF 1600 A 65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
Continued on next page

20052013 Schneider Electric All Rights Reserved

25

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 240 Vac 6001200 A

Table 13:

UL 240 Vac 6001200 A Selective Coordination (continued)

Upstream Circuit
Breaker2
Max.
Cont.
Current
1
Rating kAIR
50

65

1200 A

100

125

200

0100DB0501
R02/13, 05/2013

Type4

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA
DG

DJ

DJMC3

LD

LG

LJ

LXI

MG

MJ

PG

PK

PJ

65

100

65.0

25

65

100 125 100 100 100 200 200

65

100

65

65

100 125

LL

LC

LE

LX

LI

PL

NT- NTN
H

NTL1

NTL

50

100

200

65

NT-N 1200 A

50.0 50.0 50.0 25.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

NT-H 1200 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-N 2000 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

PG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

PK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

NT-L1 1200 A

9.0

NW-H 2000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PJ

9.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8
9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-L 1600 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-LF 1600 A 65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
NW-N 2000 A
65

1600 A

100
125
200

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

NW-H 2000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

NW-L 1600 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-LF 1600 A 65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
NW-N 2000 A

65

2000 A

100
125
200
65

2500
3000 A

100
125

4000
6000 A

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

NW-H 2000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0 36.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

NW-L 2000 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 65.0 100.0 65.0 65.0 100.0 125.0 50.0 65.0 100.0 200.0

NW-LF 2000 A 65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
RG

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

RK

65.0 65.0 65.0 25.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 51.3 51.3 51.3 65.0 65.0 50.0 51.3 51.3 65.0

NW-H 3000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 65.0 100.0 65.0 65.0 100.0 100.0 50.0 65.0 100.0 100.0

RJ

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

RL

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8 40.8

200

NW-L 3000 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 100.0 100.0 65.0 100.0 65.0 65.0 100.0 125.0 50.0 65.0 100.0 200.0

100

NW-H 6000 A

65.0 100.0 65.0 25.0 65.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 65.0 100.0 65.0 65.0 100.0 100.0 50.0 65.0 100.0 100.0

200

NW-L 6000 A

65.0 100.0 65.0 25.0 65.0 100.0 125.0 100.0 100.0 100.0 200.0 200.0 65.0 100.0 65.0 65.0 100.0 125.0 50.0 65.0 100.0 200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

DJ-MC circuit breakers are rated 65 kA at 208Y/120 Vac.

When L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as standard
L-frame circuit breaker.

26

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 14:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

UL 480 Vac 100150 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type3

Max. Cont.
Current Rating kAIR1

Mission Critical 5
18

35
50
100/
150 A

65

100

150

65

FJ4

FI

HD

HG

HJ

HL

25

65

200

18

35

65

100
1.3

See Appendix A
1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HDU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

HG

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HGU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-N/H 800/250 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

HJ

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HJU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-L1 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NW-N 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

HL

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HLU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-L 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NT-LF 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NW-H 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

See Appendix A

JD

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JDU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

JDWU6

See Appendix AMission Critical


2.6

2.6

2.6

LDWU32506

14

18

18

18

2.6

2.6

JG

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JGU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

JGWU6
LGU3250

See Appendix AMission Critical


2.6

2.6

2.6

2.6

14

18

30

30

2.6

2.6

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-N/H 800/250 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

JJ

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JJU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LJ
LJWU32506

See Appendix AMission Critical


2.6

2.6

2.6

14

18

30

30

2.6

2.6

NT-L1 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NW-N 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

JL

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JLU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LL

150

FH

18

1.3

JLWU6
100

FA

65

1.3

JJWU6

250 A

EJB4

35

1.3

LGWU32506

50

EGB4

18

HD

LDU3250

35

EDB4

14
FA

Mission Critical 5

18

ECB4

LLWU32506

See Appendix AMission Critical


2.6

2.6

2.6

14

18

30

30

2.6

2.6

NT-L 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NT-LF 800/250 A

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NW-H 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

PL

14.0

6.3

6.3

6.3

6.3

6.3

6.3

22.5

18.0

18.0

18.0

18.0

NW-L 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 800/250 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

Continued on next page

20052013 Schneider Electric All Rights Reserved

27

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

Table 14:

UL 480 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type3

Max. Cont.
Current Rating kAIR1

Mission Critical 5
18
30

35

50
400 A

100

150

35

50

EJB4

FA

FH

FJ4

FI

HD

HG

HJ

HL

35

65

18

25

65

200

18

35

65

100
4.17

See Appendix A
4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

18

18

18

4.17

4.17

18

18

18

18

18

18

LA

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

LA-MC4

See Appendix A

DG

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LG

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

LGWU34006

14

18

30

30

4.17

4.17

30

30

18

30

30

30

LH

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

LH-MC4

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

7.0

MG

14.0

18.0

35.0

35.0

18.0

10.8

35.0

35.0

18.0

35.0

35.0

35.0

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-N/H 1200 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

DJ

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LJ

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

14

18

30

30

4.17

4.17

30

30

18

30

30

30

MJ

14.0

18.0

35.0

65.0

18.0

10.8

65.0

65.0

18.0

35.0

65.0

65.0

NT-L1 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

LL

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

LLWU34006

14

18

30

30

4.17

4.17

30

30

18

30

30

30

NT-L 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NT-LF 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

PL

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0
5.49

NW-LF 1600 A

See Appendix A
5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

LDWU36006

14

18

18

18

5.49

5.49

18

18

18

18

18

18

DG

4.6

4.6

4.6

4.6

4.6

4.6

4.6

11.8

4.6

4.6

4.6

4.6

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

14

18

30

30

5.49

5.49

30

30

18

30

30

30

MG

14.0

18.0

35.0

35.0

18.0

10.8

35.0

35.0

18.0

35.0

35.0

35.0

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-N/H 1200 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

DJ

4.6

4.6

4.6

4.6

4.6

4.6

4.6

11.8

4.6

4.6

4.6

4.6

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

LD

LGWU36006

LJWU36006
65

EGB4

18

14

Mission Critical 5
18

EDB4

14
4.17

LJWU34006
65

ECB4

LDWU34006

LD

Mission Critical 5

600 A

0100DB0501
R02/13, 05/2013

14

18

30

30

5.49

5.49

30

30

18

30

30

30

MJ

14.0

18.0

35.0

65.0

18.0

10.8

65.0

65.0

18.0

35.0

65.0

65.0

NT-L1 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

Continued on next page

28

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 14:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

UL 480 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type3

Max. Cont.
Current Rating kAIR1
LL

100
600 A

150

35

50

65
800 A

100

150
35
50
1000 A
65

100
1000 A

150
35
50
1200 A
65

ECB4

EDB4

EGB4

EJB4

FA

FH

FJ4

FI

HD

HG

HJ

HL

14

18

35

65

18

25

65

200

18

35

65

100
5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

LLWU36006

14

18

30

30

5.49

5.49

30

30

18

30

30

30

NT-L 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NT-LF 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

PL

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

MG

14.0

18.0

35.0

35.0

18.0

10.8

35.0

35.0

18.0

35.0

35.0

35.0

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-H 1200 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

MJ

14.0

18.0

35.0

65.0

18.0

10.8

65.0

65.0

18.0

35.0

65.0

65.0

NT-L1 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

NT-L 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NT-LF 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

PL

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-N/H 1200 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

NT-L1 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

NT-L 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NT-LF 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

PL

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

PG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NT-N/H 1200 A

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

PK

14.0

18.0

35.0

50.0

18.0

25.0

50.0

50.0

18.0

35.0

50.0

50.0

NT-L1 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

PJ

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

Continued on next page

20052013 Schneider Electric All Rights Reserved

29

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

Table 14:

UL 480 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type3

Max. Cont.
Current Rating kAIR1

100
1200 A

150
35
65

1600 A

100

150
35
65

2000 A

100

150

35
65
2500
3000 A

100

150
4000
6000 A

0100DB0501
R02/13, 05/2013

ECB4

EDB4

EGB4

EJB4

FA

FH

FJ4

FI

HD

HG

HJ

HL

14

18

35

65

18

25

65

200

18

35

65

100
45.9

NT-L 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

NT-LF 1200 A

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0
100.0

NW-H 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

PL

14.0

18.0

35.0

9.0

18.0

9.0

9.0

53.4

18.0

35.0

45.9

45.9

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-L 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0
100.0

NW-H 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 1600 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-L 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

NW-N 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

NW-H 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-H 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-H 6000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 2000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-L 3000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-L 6000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

NW-LF 2000

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

RG

14.0

18.0

35.0

35.0

18.0

25.0

35.0

35.0

18.0

35.0

35.0

35.0

RJ

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

RK

14.0

18.0

35.0

65.0

18.0

25.0

65.0

65.0

18.0

35.0

65.0

65.0

NW-H 3000A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0
100.0

NW-H 6000A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

RL

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

NW-L 3000A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0
100.0

NW-L 6000A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100

NW-H 6000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

100.0

18.0

35.0

65.0

100.0

150

NW-L 6000 A

14.0

18.0

35.0

65.0

18.0

25.0

65.0

150.0

18.0

35.0

65.0

100.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit
breakers, they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information. When used as
downstream circuit breakers, there is no difference in selectivity so the standard Types include all trip unit options.

Rated 480Y/277 Vac. (3-pole 30 A ECB circuit breaker is rated 42 kA at 240 Vac)

See Mission Critical Circuit Breakers in Appendix A for additional information.

Mission critical circuit breakers are rated at 480Y/277 Vac.

30

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 15:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

UL 480 Vac 250 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating kAIR1
18

35
50

100/
150 A

65

100

150

18

35

50

250 A

65

100

150
18
30

400 A
35

Type3
FA
HD
HDU3150
HG
HGU3150
NT-N/H 800/250 A
HJ
HJU3150
NT-L1 800/250 A
NW-N 800/250 A
HL
HLU3150
NT-L 800/250 A
NT-LF 800/250 A
NW-H 800/250 A
NW-L 800/250 A
NW-LF 800/250 A
JD
JDU3250
LD
LDWU32505
JG
JGU3250
LG
LGWU32505
PG
NT-N/H 800/250 A
PK
JJ
JJU3250
LJ
LJWU32505
NT-L1 800/250 A
NW-N 800/250 A
PJ
JL
JLU3250
LL
LLWU32505
NT-L 800/250 A
NT-LF 800/250 A
NW-H 800/250 A
PL
NW-L 800/250 A
NW-LF 800/250 A
LD
LDWU34005
LA
LA-MC5
DG
LG
LGWU34005
LH
LH-MC5
MG
PG

JD
18
1.3

JG
35
1.3

JJ
65
1.3

JL
100
1.3

KI
200
1.3

LD
18
1.3

LG
35
1.3

LJ
65
1.3

LL
100
1.3

LE
65
1.3

LX
65
1.3

PG
35
1.3

PJ
65
1.3

PL
100
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.3
1.94
1.3

1.94
18.0
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
18.0
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
21.6
1.3

1.94
6.3
18.0

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
18.0

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.94
6.3
21.6

1.3
1.94
6.3
6.3
18.0
18.0
18.0
2.5
2.6
2.6
8
2.5
2.6
2.6
8
18.0
18.0
18.0
2.5
2.6
2.6
8
6.3
18.0
6.3
2.5
2.6
2.6
8
6.3
6.3
18.0
6.3
18.0
18.0
4.17
18
4.0
7.0
3.1
4.17
18
4.0
7.0
18.0
18.0

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
8
2.5
2.6
2.6
8
21.6
21.6
21.6
2.5
2.6
2.6
8
6.3
21.6
6.3
2.5
2.6
2.6
8
6.3
6.3
21.6
6.3
21.6
21.6
4.17
18
4.0
7.0
3.1
4.17
30
4.0
7.0
35.0
35.0

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
8
2.5
2.6
2.6
8
21.6
21.6
21.6
2.5
2.6
2.6
8
6.3
21.6
6.3
2.5
2.6
2.6
8
6.3
6.3
21.6
6.3
21.6
21.6
4.17
18
4.0
7.0
3.1
4.17
30
4.0
7.0
35.0
35.0

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
8
2.5
2.6
2.6
8
21.6
21.6
21.6
2.5
2.6
2.6
8
6.3
21.6
6.3
2.5
2.6
2.6
8
6.3
6.3
21.6
6.3
21.6
21.6
4.17
18
4.0
7.0
3.1
4.17
30
4.0
7.0
35.0
35.0

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
8
2.5
2.6
2.6
8
21.6
21.6
21.6
2.5
2.6
2.6
8
6.3
21.6
6.3
2.5
2.6
2.6
8
6.3
6.3
21.6
6.3
21.6
21.6
4.17
18
4.0
7.0
3.1
4.17
30
4.0
7.0
35.0
35.0

1.32
1.94
6.3
6.3
18.0
6.3
6.3
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
18.0
18.0
18.0
2.5
2.6
2.6
2.6
6.3
2.5
6.3
2.5
2.6
2.6
2.6
6.3
6.3
18.0
6.3
6.3
6.3
4.17
4.17
4.0
7.0
3.06
4.17
4.17
4.0
7.0
10.8
18.0

1.32
1.94
6.3
6.3
21.6
6.3
6.3
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
21.6
21.6
21.6
2.5
2.6
2.6
2.6
6.3
2.5
6.3
2.5
2.6
2.6
2.6
6.3
6.3
21.6
6.3
6.3
6.3
4.17
4.17
4.0
7.0
3.06
4.17
4.17
4.0
7.0
10.8
21.6

1.32
1.94
6.3
6.3
21.6
6.3
6.3
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
21.6
21.6
21.6
2.5
2.6
2.6
2.6
6.3
2.5
6.3
2.5
2.6
2.6
2.6
6.3
6.3
21.6
6.3
6.3
6.3
4.17
4.17
4.0
7.0
3.06
4.17
4.17
4.0
7.0
10.8
21.6

1.32
1.94
6.3
6.3
21.6
6.3
6.3
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
21.6
21.6
21.6
2.5
2.6
2.6
2.6
6.3
2.5
6.3
2.5
2.6
2.6
2.6
6.3
6.3
21.6
6.3
6.3
6.3
4.17
4.17
4.0
7.0
3.06
4.17
4.17
4.0
7.0
10.8
21.6

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
21.6
21.6
21.6
2.5
2.6
2.6
2.6
6.3
21.6
6.3
2.5
2.6
2.6
2.6
6.3
6.3
21.6
6.3
21.6
21.6
4.17
4.17
4.0
7.0
3.1
4.17
4.17
4.0
7.0
10.8
35.0

1.3
1.94
6.3
6.3
21.6
21.6
21.6
2.5
2.6
2.6
2.6
2.5
2.6
2.6
2.6
21.6
21.6
21.6
2.5
2.6
2.6
2.6
6.3
21.6
6.3
2.5
2.6
2.6
2.6
6.3
6.3
21.6
6.3
21.6
21.6
4.17
4.17
4.0
7.0
3.1
4.17
4.17
4.0
7.0
10.8
35.0

20052013 Schneider Electric All Rights Reserved

1.3
1.3
1.3
1.94 1.94
1.94
6.3
6.3
6.3
6.3
6.3
6.3
21.6 21.6
21.6
21.6 21.6
21.6
21.6 21.6
21.6
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
21.6 21.6
21.6
21.6 21.6
21.6
21.6 21.6
21.6
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
6.3
6.3
6.3
21.6 21.6
21.6
6.3
6.3
6.3
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
6.3
6.3
6.3
6.3
6.3
6.3
21.6 21.6
21.6
6.3
6.3
6.3
21.6 21.6
21.6
21.6 21.6
21.6
4.17 4.17
4.17
4.17 4.17
4.17
4.0
4.0
4.0
7.0
7.0
7.0
3.1
3.1
3.1
4.17 4.17
4.17
4.17 4.17
4.17
4.0
4.0
4.0
7.0
7.0
7.0
10.8 10.8
10.8
21.6 21.6
21.6
Continued on next page

31

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

Table 15:

UL 480 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating kAIR1
50

65

400 A

100

150
18

35

50

600 A

65

100

150

35

50
800 A

65

32

0100DB0501
R02/13, 05/2013

Type3

JD
18
18.0

JG
35
35.0

JJ
65
50.0

JL
100
50.0

KI
200
50.0

LD
18
18.0

LG
35
21.6

LJ
65
21.6

LL
100
21.6

LE
65
50.0

LX
65
50.0

PG
35
35.0

PJ
65
36.0

PL
100
36.0

PK
DJ
LJ
LJWU34005
MJ
NT-L1 1200 A
NW-N 2000 A
PJ
LL
LLWU34005
NT-L 1200 A
NT-LF 1200 A

18.0
3.1
4.17

35.0
3.1
4.17

50.0
3.1
4.17

50.0
3.1
4.17

50.0
3.1
4.17

18.0
3.06
4.17

21.6
3.06
4.17

21.6
3.06
4.17

21.6
3.06
4.17

50.0
3.1
4.17

50.0
3.1
4.17

21.6
3.1
4.17

21.6
3.1
4.17

21.6
3.1
4.17

18
18.0
18.0

30
35.0
35.0

30
65.0
36.3

30
65.0
36.3

30
49.7
32.8

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

4.17
10.8
9.0

18.0
18.0
4.17

35.0
35.0
4.17

65.0
36.3
4.17

65.0
36.3
4.17

65.0
32.8
4.17

18.0
9.0
4.17

35.0
21.6
4.17

65.0
21.6
4.17

65.0
21.6
4.17

65.0
9.0
4.17

65.0
9.0
4.17

35.0
9.0
4.17

36.0
9.0
4.17

36.0
9.0
4.17

18
18.0
18.0

30
35.0
35.0

30
36.3
36.3

30
36.3
36.3

30
32.8
32.8

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

4.17
9.0
9.0

NW-H 2000 A
PL
NW-L 1600 A
NW-LF 1600 A
LD
LDWU36005
DG
LG
LGWU36005
MG
PG
RG
NT-N/H 1200 A
PK
DJ

18.0
18.0
18.0
18.0
5.49
18
4.6
5.49
18
18.0
18.0
18.0
18.0
18.0
4.6
5.49
18
18.0
18.0
18.0
18.0
18.0
18.0
5.49
18
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0

35.0
35.0
35.0
35.0
5.49
18
4.6
5.49
30
35.0
35.0
35.0
35.0
35.0
4.6
5.49
30
35.0
35.0
35.0
35.0
35.0
35.0
5.49
30
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0

65.0
36.3
65.0
65.0
5.49
18
4.6
5.49
30
35.0
35.0
35.0
50.0
50.0
4.6
5.49
30
65.0
36.3
65.0
36.3
65.0
65.0
5.49
30
36.3
36.3
65.0
36.3
65.0
65.0
65.0
35.0
35.0
35.0
50.0
50.0
65.0
36.3
65.0
36.3
65.0
65.0

100.0
36.3
100.0
100.0
5.49
18
4.6
5.49
30
35.0
35.0
35.0
50.0
50.0
4.6
5.49
30
65.0
36.3
65.0
36.3
65.0
65.0
5.49
30
36.3
36.3
100.0
36.3
100.0
100.0
100.0
35.0
35.0
35.0
50.0
50.0
65.0
36.3
65.0
36.3
65.0
65.0

100.0
32.8
150.0
150.0
5.49
18
4.6
5.49
30
35.0
35.0
35.0
50.0
50.0
4.6
5.49
30
49.7
32.8
65.0
32.8
65.0
65.0
5.49
30
32.8
32.8
100.0
32.8
100.0
150.0
150.0
35.0
35.0
35.0
50.0
50.0
49.7
32.8
65.0
32.8
65.0
65.0

18.0
9.0
18.0
18.0
5.49
5.49
4.59
5.49
5.49
10.8
18.0
18.0
18.0
18.0
4.59
5.49
5.49
10.8
9.0
18.0
9.0
18.0
18.0
5.49
5.49
9.0
9.0
18.0
9.0
18.0
18.0
18.0
10.8
18.0
18.0
18.0
18.0
10.8
9.0
18.0
9.0
18.0
18.0

35.0
9.0
35.0
35.0
5.49
5.49
4.59
5.49
5.49
10.8
35.0
35.0
35.0
35.0
4.59
5.49
5.49
10.8
9.0
35.0
9.0
35.0
35.0
5.49
5.49
9.0
9.0
35.0
9.0
35.0
35.0
35.0
10.8
35.0
35.0
35.0
35.0
10.8
9.0
35.0
9.0
35.0
35.0

65.0
9.0
65.0
65.0
5.49
5.49
4.59
5.49
5.49
10.8
35.0
35.0
50.0
50.0
4.59
5.49
5.49
10.8
9.0
65.0
9.0
65.0
65.0
5.49
5.49
9.0
9.0
65.0
9.0
65.0
65.0
65.0
10.8
35.0
35.0
50.0
50.0
10.8
9.0
65.0
9.0
65.0
65.0

100.0
9.0
100.0
100.0
5.49
5.49
4.59
5.49
5.49
10.8
35.0
35.0
50.0
50.0
4.59
5.49
5.49
10.8
9.0
65.0
9.0
65.0
65.0
5.49
5.49
9.0
9.0
100.0
9.0
100.0
100.0
100.0
10.8
35.0
35.0
50.0
50.0
10.8
9.0
65.0
9.0
65.0
65.0

65.0
9.0
65.0
65.0
5.49
5.49
4.6
5.49
5.49
10.8
35.0
35.0
50.0
50.0
4.6
5.49
5.49
10.8
9.0
65.0
9.0
65.0
65.0
5.49
5.49
9.0
9.0
65.0
9.0
65.0
65.0
65.0
10.8
35.0
35.0
50.0
50.0
10.8
9.0
65.0
9.0
65.0
65.0

65.0
9.0
65.0
65.0
5.49
5.49
4.6
5.49
5.49
10.8
35.0
35.0
50.0
50.0
4.6
5.49
5.49
10.8
9.0
65.0
9.0
65.0
65.0
5.49
5.49
9.0
9.0
65.0
9.0
65.0
65.0
65.0
10.8
35.0
35.0
50.0
50.0
10.8
9.0
65.0
9.0
65.0
65.0

NT-N/H 1200 A

LJ
LJWU36005
MJ
NT-L1 1200 A
NW-N 2000 A
PJ
RJ
RK
LL
LLWU36005
NT-L 1200 A
NT-LF 1200 A
NW-H 2000 A
PL
RL
NW-L 1600 A
NW-LF 1600 A
MG
PG
RG
NT-H 1200 A
PK
MJ
NT-L1 1200 A
NW-N 2000 A
PJ
RJ
RK

35.0 36.0
36.0
9.0
9.0
9.0
31.5 31.5
31.5
21.6 21.6
21.6
5.49 5.49
5.49
5.49 5.49
5.49
4.6
4.6
4.6
5.49 5.49
5.49
5.49 5.49
5.49
10.8 10.8
10.8
21.6 21.6
21.6
35.0 35.0
35.0
35.0 36.0
36.0
21.6 21.6
21.6
4.6
4.6
4.6
5.49 5.49
5.49
5.49 5.49
5.49
10.8 10.8
10.8
9.0
9.0
9.0
35.0 36.0
36.0
9.0
9.0
9.0
35.0 40.8
40.8
35.0 65.0
51.3
5.49 5.49
5.49
5.49 5.49
5.49
9.0
9.0
9.0
9.0
9.0
9.0
35.0 36.0
36.0
9.0
9.0
9.0
35.0 40.8
40.8
31.5 31.5
31.5
21.6 21.6
21.6
10.8 10.8
10.8
21.6 21.6
21.6
35.0 35.0
35.0
35.0 36.0
36.0
21.6 21.6
21.6
10.8 10.8
10.8
9.0
9.0
9.0
35.0 36.0
36.0
9.0
9.0
9.0
35.0 40.8
40.8
35.0 65.0
51.3
Continued on next page

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 15:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

UL 480 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating kAIR1

100
800 A

150
35
50

65
1000 A

100

150
35
50

65

1200 A

100

150
35
65

1600 A

100

150

Type3
NT-L 1200 A
NT-LF 1200 A
NW-H 2000 A
PL
RL
NW-L 1600 A
NW-LF 1600 A
PG

JD
18
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0

JG
35
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0

JJ
65
36.3
36.3
65.0
36.3
65.0
65.0
65.0
35.0

JL
100
36.3
36.3
100.0
36.3
100.0
100.0
100.0
35.0

KI
200
32.8
32.8

LD
18
9.0
9.0

LG
35
9.0
9.0

LJ
65
9.0
9.0

LL
100
9.0
9.0

LE
65
9.0
9.0

LX
65
9.0
9.0

PG
35
9.0
9.0

PJ
65
9.0
9.0

PL
100
9.0
9.0

100.0
32.8
100.0
150.0
150.0
35.0

18.0
9.0
18.0
18.0
18.0
18.0

35.0
9.0
35.0
35.0
35.0
35.0

65.0
9.0
65.0
65.0
65.0
35.0

100.0
9.0
100.0
100.0
100.0
35.0

65.0
9.0
65.0
65.0
65.0
35.0

65.0
9.0
65.0
65.0
65.0
35.0

35.0
9.0
35.0
31.5
21.6
21.6

36.0
9.0
40.8
31.5
21.6
21.6

36.0
9.0
40.8
31.5
21.6
21.6

RG
NT-N/H 1200 A
PK
NT-L1 1200 A
NW-N 2000 A
PJ
RJ
RK
NT-L 1200 A
NT-LF 1200 A
NW-H 2000 A
PL
RL
NW-L 1600 A
NW-LF 1600 A
PG
RG
NT-N/H 1200 A
PK
NT-L1 1200 A
NW-N 2000 A
PJ
RJ
RK
NT-L 1200 A
NT-LF 1200 A
NW-H 2000 A
NW-H 3000 A
PL
RL
NW-L 1600 A
NW-L 3000 A
NW-LF 2000 A
RG
NW-N 2000 A
RJ
RK
NW-H 2000 A
NW-H 3000 A
RL
NW-L 1600 A
NW-L 3000 A
NW-LF 2000 A

18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0

35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0

35.0
50.0
50.0
36.3
65.0
36.3
65.0
65.0
36.3
36.3
65.0
36.3
65.0
65.0
65.0
35.0
35.0
50.0
50.0
36.3
65.0
36.3
65.0
65.0
36.3
36.3
65.0
65.0
36.3
65.0
65.0
65.0
65.0
35.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

35.0
50.0
50.0
36.3
65.0
36.3
65.0
65.0
36.3
36.3
100.0
36.3
100.0
100.0
100.0
35.0
35.0
50.0
50.0
36.3
65.0
36.3
65.0
65.0
36.3
36.3
100.0
100.0
36.3
100.0
100.0
100.0
100.0
35.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0

35.0
50.0
50.0
32.8
65.0
32.8
65.0
65.0
32.8
32.8
100.0
32.8
100.0
150.0
150.0
35.0
35.0
50.0
50.0
32.8
65.0
32.8
65.0
65.0
32.8
32.8
100.0
100.0
32.8
100.0
150.0
150.0
150.0
35.0
65.0
65.0
65.0
100.0
100.0
100.0
150.0
150.0
150.0

18.0
18.0
18.0
9.0
18.0

35.0
35.0
35.0
9.0
35.0

35.0
50.0
50.0
9.0
65.0

35.0
50.0
50.0
9.0
65.0

35.0
50.0
50.0
9.0
65.0

35.0
50.0
50.0
9.0
65.0

35.0
35.0
21.6
9.0
35.0

35.0
36.0
21.6
9.0
36.0

35.0
36.0
21.6
9.0
36.0

9.0
18.0
18.0
9.0
9.0
18.0
9.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
9.0
18.0
9.0
18.0
18.0
9.0
9.0
18.0
18.0
9.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0

9.0
35.0
35.0
9.0
9.0
35.0
9.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
9.0
35.0
9.0
35.0
35.0
9.0
9.0
35.0
35.0
9.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0
35.0

9.0
65.0
65.0
9.0
9.0
65.0
9.0
65.0
65.0
65.0
35.0
35.0
50.0
50.0
9.0
65.0
9.0
65.0
65.0
9.0
9.0
65.0
65.0
9.0
65.0
65.0
65.0
65.0
35.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

9.0
65.0
65.0
9.0
9.0
100.0
9.0
100.0
100.0
100.0
35.0
35.0
50.0
50.0
9.0
65.0
9.0
65.0
65.0
9.0
9.0
100.0
100.0
9.0
100.0
100.0
100.0
100.0
35.0
65.0
65.0
65.0
100.0
100.0
100.0
100.0
100.0
100.0

9.0
65.0
65.0
9.0
9.0
65.0
9.0
65.0
65.0
65.0
35.0
35.0
50.0
50.0
9.0
65.0
9.0
65.0
65.0
9.0
9.0
65.0
65.0
9.0
65.0
65.0
65.0
65.0
35.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

9.0
65.0
65.0
9.0
9.0
65.0
9.0
65.0
65.0
65.0
35.0
35.0
50.0
50.0
9.0
65.0
9.0
65.0
65.0
9.0
9.0
65.0
65.0
9.0
65.0
65.0
65.0
65.0
35.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0
65.0

20052013 Schneider Electric All Rights Reserved

9.0
9.0
9.0
35.0 40.8
40.8
35.0 65.0
51.3
9.0
9.0
9.0
9.0
9.0
9.0
35.0 36.0
36.0
9.0
9.0
9.0
35.0 40.8
40.8
31.5 31.5
31.5
21.6 21.6
21.6
21.6 21.6
21.6
35.0 35.0
35.0
35.0 36.0
36.0
21.6 21.6
21.6
9.0
9.0
9.0
35.0 36.0
36.0
9.0
9.0
9.0
35.0 40.8
40.8
35.0 65.0
51.3
9.0
9.0
9.0
9.0
9.0
9.0
35.0 36.0
36.0
35.0 65.0 100.0
9.0
9.0
9.0
35.0 40.8
40.8
31.5 31.5
31.5
35.0 65.0 100.0
21.6 21.6
21.6
35.0 35.0
35.0
35.0 36.0
36.0
35.0 40.8
40.8
35.0 65.0
51.3
35.0 36.0
36.0
35.0 65.0 100.0
35.0 40.8
40.8
31.5 31.5
31.5
35.0 65.0 100.0
21.6 21.6
21.6
Continued on next page

33

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 100250 A

Table 15:

UL 480 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Type3
Max. Cont.
Current Rating kAIR1
35 RG
NW-N 2000 A
65

2000 A

0100DB0501
R02/13, 05/2013

100

150

JD
18
18.0
18.0

JG
35
35.0
35.0

JJ
65
35.0
65.0

JL
100
35.0
65.0

KI
200
35.0
65.0

LD
18
18.0
18.0

LG
35
35.0
35.0

LJ
65
35.0
65.0

LL
100
35.0
65.0

LE
65
35.0
65.0

LX
65
35.0
65.0

PG
35
35.0
35.0

PJ
65
35.0
36.0

PL
100
35.0
36.0

RJ
RK
NW-H 2000 A

18.0
18.0
18.0

35.0
35.0
35.0

65.0
65.0
65.0

65.0
65.0
100.0

65.0
65.0
100.0

18.0
18.0
18.0

35.0
35.0
35.0

65.0
65.0
65.0

65.0
65.0
100.0

65.0
65.0
65.0

65.0
65.0
65.0

35.0
35.0
35.0

40.8
65.0
36.0

40.8
51.3
36.0

NW-H 3000 A
NW-H 6000 A
RL

18.0
18.0
18.0

35.0
35.0
35.0

65.0
65.0
65.0

100.0
100.0
100.0

100.0
100.0
100.0

18.0
18.0
18.0

35.0
35.0
35.0

65.0
65.0
65.0

100.0
100.0
100.0

65.0
65.0
65.0

65.0
65.0
65.0

35.0
35.0
35.0

65.0
65.0
40.8

100.0
100.0
40.8

NW-L 2000 A
NW-L 3000 A

18.0
18.0

35.0
35.0

65.0
65.0

100.0
100.0

150.0
150.0

18.0
18.0

35.0
35.0

65.0
65.0

100.0
100.0

65.0
65.0

65.0
65.0

35.0
35.0

65.0
65.0

100.0
100.0

NW-L 6000 A
18.0
35.0
65.0
100.0 150.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
NW-LF 2000
18.0
35.0
65.0
100.0 150.0
18.0
35.0
65.0
100.0 65.0 65.0 21.6 21.6
21.6
35 RG
18.0
35.0
35.0
35.0
35.0
18.0
35.0
35.0
35.0
35.0 35.0 35.0 35.0
35.0
RJ
18.0
35.0
65.0
65.0
65.0
18.0
35.0
65.0
65.0
65.0 65.0 35.0 40.8
40.8
65
RK
18.0
35.0
65.0
65.0
65.0
18.0
35.0
65.0
65.0
65.0 65.0 35.0 65.0
51.3
NW-H 3000A
18.0
35.0
65.0
100.0 100.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
2500
3000 A
100 NW-H 6000A
18.0
35.0
65.0
100.0 100.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
RL
18.0
35.0
65.0
100.0 100.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 40.8
40.8
NW-L 3000A
18.0
35.0
65.0
100.0 150.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
150
NW-L 6000A
18.0
35.0
65.0
100.0 150.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
100 NW-H 6000 A
18.0
35.0
65.0
100.0 100.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
4000
6000 A
150 NW-L 6000 A
18.0
35.0
65.0
100.0 150.0
18.0
35.0
65.0
100.0 65.0 65.0 35.0 65.0 100.0
1 This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.
2

Number after NW-x indicates frame size.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit
breakers, they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information. When used as
downstream circuit breakers, there is no difference in selectivity so the standard Types include all trip unit options.
When J- and L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as
standard J- and L-frame circuit breaker.

See Mission Critical Circuit Breakers in Appendix A for additional information.

Mission critical circuit breakers are rated at 480Y/277 Vac.

34

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 16:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 400 A

UL 480 Vac 400 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
1
Rating kAIR
18

35

50

600 A

65

100

150

35

50

65
800 A

100

150

LA

LAMC

LH

LHMC

DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

PG

PJ

PL

30

30

35

35

35

65

18

35

65

100

65

65

65

200

200

35

65

100

LD

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

DG

4.6

4.6

4.6

4.6

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MG

10.8

10.8

10.8

10.8

10.8

10.8

10.8

65.0

100.0

100.0

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

PG

21.6

21.6

21.6

21.6

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-N/H 1200 A

30.0

30.0

35.0

35.0

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

35.0

36.0

36.0

PK

21.6

21.6

21.6

21.6

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

21.6

21.6

21.6

DJ

4.6

4.6

4.6

4.6

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MJ

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

NT-L1 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

Type3

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

LL

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

PL

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

40.8

9.0

9.0

9.0

NW-L 1600 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 31.5

31.5

31.5

NW-LF 1600 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

64.2

64.2

21.6

21.6

21.6

MG

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

16.6

16.6

10.8

10.8

10.8

PG

21.6

21.6

21.6

21.6

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-N 1200 A

30.0

30.0

35.0

35.0

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

35.0

36.0

36.0

PK

21.6

21.6

21.6

21.6

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

21.6

21.6

21.6

MJ

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

16.6

16.6

10.8

10.8

10.8

NT-L1 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

PL

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

40.8

NW-L 1600 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 31.5

31.5

31.5

NW-LF 1600 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

21.6

21.6

9.0

9.0

64.2

9.0

64.2

21.6

Continued on next page

20052013 Schneider Electric All Rights Reserved

35

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 400 A

Table 16:

UL 480 Vac 400 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
1
Rating kAIR
35
50

65
1000 A

100

150
35
50

65

1200 A

100

150
35
65

1600 A

100

150

0100DB0501
R02/13, 05/2013

LA

LAMC

LH

LHMC

DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

PG

PJ

PL

30

30

35

35

35

65

18

35

65

100

65

65

65

200

200

35

65

100

PG

21.6

21.6

21.6

21.6

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-N/H 1200 A

30.0

30.0

35.0

35.0

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

35.0

36.0

36.0

PK

21.6

21.6

21.6

21.6

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

21.6

21.6

21.6

NT-L1 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

Type3

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

PL

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

40.8

9.0

9.0

9.0

NW-L 1600 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 31.5

31.5

31.5

NW-LF 1600 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

64.2

64.2

21.6

21.6

21.6

PG

21.6

21.6

21.6

21.6

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-N/H 1200 A

30.0

30.0

35.0

35.0

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

35.0

36.0

36.0

PK

21.6

21.6

21.6

21.6

35.0

50.0

18.0

35.0

50.0

50.0

50.0

50.0

50.0

50.0

50.0

21.6

21.6

21.6

NT-L1 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

NW-H 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

PL

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

40.8
31.5

9.0

9.0

9.0

NW-L 1600 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 31.5

31.5

NW-L 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

NW-LF 2000 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

64.2

64.2

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

NW-H 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

40.8

NW-L 1600 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 31.5

31.5

31.5

NW-L 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

NW-LF 2000 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

21.6

64.2

64.2

21.6

21.6

Continued on next page

36

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 16:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 400 A

UL 480 Vac 400 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max.
Cont.
Current
1
Rating kAIR
35
65

2000 A

100

150

35
65
2500
3000 A

100

150

Type3

RG

LA

LAMC

LH

LHMC

DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

PG

PJ

PL

30

30

35

35

35

65

18

35

65

100

65

65

65

200

200

35

65

100

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

NW-N 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

36.0

36.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NW-H 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

36.0

36.0

NW-H 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

NW-H 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

NW-L 2000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

40.8

NW-L 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

NW-L 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

NW-LF 2000 A

21.6

21.6

21.6

21.6

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0

64.2

64.2

21.6

21.6

21.6

RG

30.0

30.0

35.0

35.0

35.0

35.0

18.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

35.0

RJ

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

40.8

40.8

RK

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0

65.0

65.0

65.0

65.0

65.0

65.0

35.0

65.0

51.3

NW-H 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

NW-H 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

RL

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

40.8

NW-L 3000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

40.8

NW-L 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

4000

100

NW-H 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 100.0 100.0 35.0

65.0 100.0

6000 A

150

NW-L 6000 A

30.0

30.0

35.0

35.0

35.0

65.0

18.0

35.0

65.0 100.0 65.0

65.0

65.0 150.0 150.0 35.0

65.0 100.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

When L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as standard
L-frame circuit breaker.

20052013 Schneider Electric All Rights Reserved

37

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 6001200 A

Table 17:

UL 480 Vac 6001200 A Selective Coordination

Upstream Circuit
Breaker2
Max.
Cont.
Current
Rating kAIR1
35

50

65
800 A

100

150
35
50

65
1000 A

100

150
35
50
1200 A
65

0100DB0501
R02/13, 05/2013

Type3

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA
DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PL

RG

RJ

RL

35

65

18

35

65

100

65

65

65

200

200

35

65

35

65

100

35

65

100

NT

NT

NT

NT

N/H

L1

LF

50

65

100

100

MG

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

PG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 51.3 35.0 51.3 51.3 35.0 51.3 51.3 50.0 51.3 51.3 51.3

NT-N/H 1200 A 35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0
PK

35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 21.6 21.6 35.0 21.6 21.6 35.0 21.6 21.6 21.6 21.6 21.6 21.6

MJ

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

NT-L1 1200 A

9.0

NW-N 2000 A

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PJ

9.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 51.3 51.3 35.0 51.3 51.3 50.0 51.3 51.3 51.3

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

NW-L 1600 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 31.5 31.5 31.5 31.5 35.0 31.5 31.5 31.5 31.5 31.5 31.5

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-LF 1600 A 35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 64.2 64.2 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
PG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

NT-N/H 1200 A 35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0
PK

35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

NT-L1 1200 A

9.0

NW-N 2000 A

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PJ

9.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 51.3 51.3 35.0 51.3 51.3 50.0 51.3 51.3 51.3

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PL

9.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

NW-L 1600 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 31.5 31.5 31.5 31.5 31.5 35.0 31.5 31.5 31.5 31.5 31.5 31.5

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-LF 1600 A 35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 64.2 64.2 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
PG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 51.3 51.3 51.3 51.3 51.3 50.0 51.3 51.3 51.3

NT-N/H 1200 A 35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0
PK

35.0 50.0 18.0 35.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6

NT-L1 1200 A

9.0

NW-N 2000 A

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

PJ

9.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 51.3 51.3 35.0 51.3 51.3 50.0 51.3 51.3 51.3

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

Continued on next page

38

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 17:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 480 Vac 6001200 A

UL 480 Vac 6001200 A Selective Coordination (continued)

Upstream Circuit
Breaker2
Max.
Cont.
Current
Rating kAIR1

100
1200 A

150

Type3

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA
NT

NT

NT

N/H

L1

LF

100

50

65

100

100

DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

MG

MJ

PG

PJ

PL

RG

RJ

RL

35

65

18

35

65

100

65

65

65

200

200

35

65

35

65

100

35

65

NT

NT-L 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-LF 1200 A

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-H 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-H 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

PL

9.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 40.8 40.8 40.8 40.8

NW-L 1600 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-L 3000A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-LF 2000 A 35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 64.2 64.2 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
35
65

1600 A

100

150

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0

NW-N 2000 A

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 65.0 51.3 35.0 51.3 51.3 50.0 51.3 65.0 65.0

NW-H 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-H 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

NW-L 1600 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

NW-L 3000A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-LF 2000 A 35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 64.2 64.2 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
35
65

2000 A

100

150

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0

NW-N 2000 A

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 65.0 51.3 35.0 51.3 51.3 50.0 51.3 65.0 65.0

NW-H 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 36.0 35.0 36.0 36.0 35.0 36.0 36.0 36.0 36.0 36.0 36.0

NW-H 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-H 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

NW-L 2000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-L 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-L 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

NW-LF 2000 A 35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 64.2 64.2 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
35
65
2500
3000 A

100

150
4000
6000 A

RG

35.0 35.0 18.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0

RJ

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

RK

35.0 65.0 18.0 35.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 35.0 51.3 35.0 65.0 51.3 35.0 51.3 51.3 50.0 51.3 65.0 65.0

NW-H 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-H 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

RL

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 40.8 35.0 40.8 40.8 35.0 40.8 40.8 50.0 40.8 40.8 40.8

NW-L 3000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 58.5 50.0 58.5 100.0 100.0

NW-L 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

100

NW-H 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 100.0 100.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

150

NW-L 6000 A

35.0 65.0 18.0 35.0 65.0 100.0 65.0 65.0 65.0 150.0 150.0 35.0 65.0 35.0 65.0 100.0 35.0 65.0 67.5 50.0 65.0 100.0 100.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

When L-frame mission critical circuit breakers are used as downstream circuit breakers, the maximum level of selective coordination is the same as standard L-frame
circuit breaker.

20052013 Schneider Electric All Rights Reserved

39

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

Table 18:

UL 600 Vac 100150 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type3
kAIR1
14

18

25
100/150 A

0100DB0501
R02/13, 05/2013

35

50

85
100

14

18

25
250 A
35

50

85
100
14

18

400 A
25

35

EDB4

EGB4

EJB4

FA

FH

FJ4

HD

HG

HJ

HL

FI

14

18

25

14

18

25

14

18

25

50

100
1.3

FA

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HD

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HDU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94
1.3

FH

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HG

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HGU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

HJ

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HJU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-N 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

HL

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HLU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-H 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-N 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-H 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

JD

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JDU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LD

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

JG

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JGU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LJ

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

JJ

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JJU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LJ

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

PJ

14.0

6.3

6.3

6.3

6.3

6.3

14.0

14.3

14.3

14.3

19.3

NT-N 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

JL

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JLU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LL

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

NT-H 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-N 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-H 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 800/250 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

LD

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

DG

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LG

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

MG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

DJ

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LJ

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

LH

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

MJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

PJ

14.0

18.0

25.0

14.0

9.0

25.0

14.0

18.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

Continued on next page

40

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 18:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

UL 600 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

400 A

Type3
kAIR1

EGB4

EJB4

FA

FH

FJ4

HD

HG

HJ

HL

FI

14

18

25

14

18

25

14

18

25

50

100

LL

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

50

NT-H 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

85

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

LD

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

DG

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

10.6

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

DJ

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

10.6

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

PJ

14.0

18.0

25.0

14.0

9.0

25.0

14.0

18.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

LL

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

NT-H 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

65

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

85

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

MG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

MJ

14.0

18.0

25.0

14.0

14.0

25.0

14.0

18.0

25.0

25.0

25.0

PJ

14.0

18.0

25.0

14.0

9.0

25.0

14.0

18.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

NT-H 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

100
14

18

25
600 A

EDB4

35

50

100

18

25
35
800 A
50

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

65

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

85

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

100

Continued on next page

20052013 Schneider Electric All Rights Reserved

41

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

Table 18:

UL 600 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type3

EDB4

EGB4

EJB4

FA

FH

FJ4

HD

HG

HJ

HL

FI

14

18

25

14

18

25

14

18

25

50

100

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

PJ

14.0

18.0

25.0

14.0

9.0

25.0

14.0

18.0

25.0

25.0

25.0

RJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

NT-H 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-H 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

PG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

PJ

14.0

18.0

25.0

14.0

9.0

25.0

14.0

18.0

25.0

25.0

25.0

RJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

35.0

35.0

NT-H 1200 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

PK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-H 3000A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

18

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

25

RJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

kAIR1
18
25
35

1000 A

50

65
85

100

18
25
35

1200 A

50

65
85

100

50
1600 A

0100DB0501
R02/13, 05/2013

65
85

100

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-H 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

Continued on next page

42

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 18:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

UL 600 Vac 100150 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type3
kAIR1

40006000 A

FA

FH

FJ4

HD

HG

HJ

HL

FI

14

18

25

14

18

25

14

18

25

50

100

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

RJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

NW-N 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

NW-H 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-H 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

NW-L 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

NW-LF 2000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

65

100

3000 A

EJB4

25

85

2500 A

EGB4

18

50
2000 A

EDB4

18

RG

14.0

18.0

18.0

14.0

18.0

18.0

14.0

18.0

18.0

18.0

18.0

25

RJ

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

25.0

25.0

50

RL

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

50.0

65

RK

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

65.0

85

NW-H 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

100

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

85

NW-H 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

100

NW-L 3000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

85

NW-H 6000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

85.0

100

NW-L 6000 A

14.0

18.0

25.0

14.0

18.0

25.0

14.0

18.0

25.0

50.0

100.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit
breakers, they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information. When used as
downstream circuit breakers, there is no difference in selectivity so the standard Types include all trip unit options.

Rated 600Y/347 Vac

20052013 Schneider Electric All Rights Reserved

43

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

Table 19:

UL 600 Vac 250 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type3
kAIR1

14

18

25
100/150 A

0100DB0501
R02/13, 05/2013

35

50

85
100

14

18

25
250 A
35

50

85
100

JD

JG

LD

LG

LJ

LL

PG

JJ

PJ

LE

LX

JL

KI

14

18

14

18

25

50

18

25

25

35

35

50

100
1.3

FA

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HD

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HDU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94
1.3

FH

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HG

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HGU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

HJ

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HJU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-N 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

18.0

21.6

21.6

21.6

21.6

21.6

HL

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

HLU3150

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

1.94

NT-H 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-N 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-H 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-L 800/250 A

14.0

18.0

6.3

6.3

6.3

6.3

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-LF 800/250 A

14.0

18.0

6.3

6.3

6.3

6.3

18.0

21.6

21.6

21.6

21.6

21.6

21.6

JD

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JDU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LD

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

JG

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JGU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LJ

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

JJ

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JJU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LJ

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

PJ

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

6.3

NT-N 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

JL

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

JLU3250

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

LL

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

2.6

NT-H 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-N 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

PK

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-H 800/250 A

14.0

18.0

14.0

18.0

21.6

21.6

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-L 800/250 A

14.0

18.0

6.3

6.3

6.3

6.3

18.0

21.6

21.6

21.6

21.6

21.6

21.6

NW-LF 800/250 A

14.0

18.0

6.3

6.3

6.3

6.3

18.0

21.6

21.6

21.6

21.6

21.6

21.6

Continued on next page

44

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 19:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

UL 600 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type3

14

18

25
400 A

JG

LD

LG

LJ

LL

PG

JJ

PJ

LE

LX

JL

KI

14

18

14

18

25

50

18

25

25

35

35

50

100

LD

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

DG

3.1

3.1

3.06

3.06

3.06

3.06

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LG

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

MG

14.0

18.0

10.8

10.8

10.8

10.8

10.8

18.0

10.8

10.8

10.8

18.0

18.0

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

DJ

3.1

3.1

3.06

3.06

3.06

3.06

3.1

3.1

3.1

3.1

3.1

3.1

3.1

LJ

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

LH

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

MJ

14.0

18.0

10.8

10.8

10.8

10.8

10.8

25.0

10.8

10.8

10.8

25.0

25.0

PJ

14.0

18.0

9.0

9.0

9.0

9.0

9.0

25.0

9.0

9.0

9.0

25.0

21.7

35

NT-N 1200 A

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

35.0

35.0

35.0

35.0

LL

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

4.17

50

NT-H 1200 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

PK

14.0

18.0

14.0

18.0

21.6

21.6

18.0

25.0

21.6

35.0

35.0

50.0

50.0

85

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

100
14

18

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

LD

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

DG

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MG

14.0

18.0

10.8

10.8

10.8

10.8

10.8

18.0

10.8

10.8

10.8

18.0

18.0

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0
18.0

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

DJ

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MJ

14.0

18.0

10.8

10.8

10.8

10.8

10.8

25.0

10.8

10.8

10.8

25.0

25.0

PJ

14.0

18.0

9.0

9.0

9.0

9.0

9.0

25.0

9.0

9.0

9.0

25.0

21.7

NT-N 1200 A

14.0

18.0

14.0

18.0

25.0

35.0

18.0

25.0

25.0

35.0

35.0

35.0

35.0

LL

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

NT-H 1200 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

NW-N 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

PK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

65

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

85

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

25
600 A

JD

kAIR1

35

50

100

Continued on next page

20052013 Schneider Electric All Rights Reserved

45

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

Table 19:

UL 600 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type3
kAIR1

18

25
35
800 A

JG

LD

LG

LJ

LL

PG

JJ

PJ

LE

LX

JL

KI

14

18

14

18

25

50

18

25

25

35

35

50

100

MG

14.0

18.0

10.8

10.8

10.8

10.8

10.8

18.0

10.8

10.8

10.8

18.0

18.0

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

MJ

14.0

18.0

10.8

10.8

10.8

10.8

10.8

25.0

10.8

10.8

10.8

25.0

25.0

PJ

14.0

18.0

9.0

9.0

9.0

9.0

9.0

25.0

9.0

9.0

9.0

25.0

21.7

NT-N 1200 A

14.0

18.0

14.0

18.0

25.0

35.0

18.0

25.0

25.0

35.0

35.0

35.0

35.0

NT-H 1200 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

PK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

65

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

85

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0
100.0

100
18
25
35

50

65
85

100

18
25
35

1200 A

JD

NW-N 2000 A

50

1000 A

0100DB0501
R02/13, 05/2013

50

65
85

100

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

PJ

14.0

18.0

9.0

9.0

9.0

9.0

9.0

25.0

9.0

9.0

9.0

25.0

21.7

RJ

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

25.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

14.0

18.0

25.0

35.0

18.0

25.0

25.0

35.0

35.0

35.0

35.0

NT-H 1200 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

NW-N 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

PK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-H 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

PG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

PJ

14.0

18.0

9.0

9.0

9.0

9.0

9.0

25.0

9.0

9.0

9.0

25.0

21.7

RJ

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

25.0

25.0

25.0

25.0

NT-N 1200 A

14.0

18.0

14.0

18.0

25.0

35.0

18.0

25.0

25.0

35.0

35.0

35.0

35.0

NT-H 1200 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

NW-N 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

PK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-H 3000A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

Continued on next page

46

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 19:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 100250 A

UL 600 Vac 250 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type3
kAIR1

LL

PG

JJ

PJ

LE

LX

JL

KI

25

50

18

25

25

35

35

50

100

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

25.0

25.0

25.0

25.0

65

NW-N 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-H 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-LF 1600 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

18

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

25

RJ

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

25.0

25.0

25.0

25.0

65
85

100

40006000 A

LJ

18

RJ

50

3000 A

LG

14

RG

100

2500 A

LD

18

25

85

2000 A

JG

14

18

50
1600 A

JD

NW-N 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

NW-H 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-H 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

NW-L 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

NW-LF 2000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

21.6

35.0

35.0

50.0

100.0

18

RG

14.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

25

RJ

14.0

18.0

14.0

18.0

25.0

25.0

18.0

25.0

25.0

25.0

25.0

25.0

25.0

50

RL

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

50.0

65

RK

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

65.0

85

NW-H 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

100

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

85

NW-H 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

100

NW-L 3000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

85

NW-H 6000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

85.0

100

NW-L 6000 A

14.0

18.0

14.0

18.0

25.0

50.0

18.0

25.0

25.0

35.0

35.0

50.0

100.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Type H and J circuit breakers with the U character in the third position are equipped with Micrologic Electronic Trip Units. When used as upstream circuit
breakers, they provide different selectivity levels (usually higher) than their thermal-magnetic equivalents. See page 5 for additional information. When used as
downstream circuit breakers, there is no difference in selectivity so the standard Types include all trip unit options.

20052013 Schneider Electric All Rights Reserved

47

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 400 A

Table 20:

UL 600 Vac 400 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type
kAIR1
14

DG

LD

LG

LJ

LL

LA

LH

DJ

PJ

LC

LE

LX

PK

LI

LXI

18

18

14

18

25

50

22

25

25

25

35

35

35

50

100

100

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LG

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MG

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

PG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

DJ

4.6

4.6

4.59

4.59

4.59

4.59

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

4.6

LJ

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

MJ

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-N 1200 A

18.0

18.0

14.0

18.0

25.0

35.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

35.0

35.0

35.0

LL

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

5.49

NT-H 1200 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

PK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

65

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

85

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-L 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

31.5

100.0

100.0

NW-LF 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

MG

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

PG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

MJ

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

10.8

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NT-N 1200 A

18.0

18.0

14.0

18.0

25.0

35.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

35.0

35.0

35.0

25

35

50

100

18

25
35

NT-H 1200 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

PK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

65

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

85

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-L 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

31.5

100.0 100.0

800 A
50

100
18
25
35

1000 A

LD

PG

DG
18

600 A

0100DB0501
R02/13, 05/2013

50

65
85

100

NW-LF 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

PG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

PJ

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RJ

18.0

18.0

14.0

18.0

25.0

25.0

22.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

NT-N 1200 A

18.0

18.0

14.0

18.0

25.0

35.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-H 1200 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

PK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

85.0

NW-L 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-LF 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

Continued on next page

48

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 20:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 400 A

UL 600 Vac 400 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type

18

LA

LH

DJ

PJ

LC

LE

LX

PK

LI

LXI

50

22

25

25

25

35

35

35

50

100

100

PG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

14.0

18.0

25.0

25.0

22.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

NT-N 1200 A

18.0

18.0

14.0

18.0

25.0

35.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

35.0

35.0

35.0

NT-H 1200 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

PK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

85.0

NW-L 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-LF 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

18

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

25

RJ

18.0

18.0

14.0

18.0

25.0

25.0

22.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

85.0

NW-L 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-LF 1600 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

18

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

25

RJ

18.0

18.0

14.0

18.0

25.0

25.0

22.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

NW-N 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

50.0

50.0

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

NW-H 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

36.0

85.0

85.0

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

85.0

NW-L 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

NW-LF 2000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

21.6

25.0

21.6

35.0

35.0

35.0

21.6

58.5

58.5

18

RG

18.0

18.0

14.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

18.0

25

RJ

18.0

18.0

14.0

18.0

25.0

25.0

22.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

25.0

50

RL

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

40.8

50.0

50.0

65

RK

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

65.0

65.0

85

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

85.0

100

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

50

50
65
85

100

50
65
85

100

4000
6000 A

LL

25

18.0

100

3000 A

LJ

18

9.0

85

2500 A

LG

14

18.0

65

2000 A

LD

18

RJ

35

1600 A

DG

18

PJ

25

1200 A

PG

kAIR1

85

NW-H 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

100

NW-L 3000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

85.0

85

NW-H 6000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

85.0

100

NW-L 6000 A

18.0

18.0

14.0

18.0

25.0

50.0

22.0

25.0

25.0

25.0

35.0

35.0

35.0

50.0

100.0 100.0

85.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

20052013 Schneider Electric All Rights Reserved

49

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 6001200 A

Table 21:

UL 600 Vac 6001200 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating
kAIR1
18

25
35
800 A
50

DG

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

MG MJ

PG

PJ

PK

RG

RJ

RL

RK

18

25

14

18

25

50

35

35

35

100

100

18

18

25

50

18

25

50

65

25

NT

NT

35

50

MG

18.0 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

PG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

RG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

MJ

18.0 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

PJ

9.0

NT-N 1200 A

18.0 25.0 14.0 18.0 25.0 35.0 35.0 35.0 35.0 35.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

35.0 18.0 25.0 18.0 25.0 35.0 18.0 25.0 35.0 35.0 35.0 35.0

9.0

NT-H 1200 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

PK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6
50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 50.0 51.3 35.0 50.0

85

NW-H 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-L 1600 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 31.5 18.0 25.0 31.5 31.5 31.5 31.5

NW-LF 1600 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 58.5

58.5 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

18
25
35

50

65
85

100

18
25
35

1200 A

Type

65

100

1000 A

0100DB0501
R02/13, 05/2013

50

65
85

100

PG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

RG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

PJ

9.0

RJ

18.0 25.0 14.0 18.0 25.0 25.0 25.0 25.0 25.0 25.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 25.0 25.0 25.0 25.0

9.0

NT-N 1200 A

18.0 25.0 14.0 18.0 25.0 35.0 35.0 35.0 35.0 35.0

35.0 18.0 25.0 18.0 25.0 35.0 18.0 25.0 35.0 35.0 35.0 35.0

NT-H 1200 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-N 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

PK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 51.3 35.0 50.0

NW-H 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-H 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-LF 1600 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 58.5

58.5 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

PG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

RG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

PJ

9.0

RJ

18.0 25.0 14.0 18.0 25.0 25.0 25.0 25.0 25.0 25.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

25.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 25.0 25.0 25.0 25.0

9.0

9.0

9.0

NT-N 1200 A

18.0 25.0 14.0 18.0 25.0 35.0 35.0 35.0 35.0 35.0

35.0 18.0 25.0 18.0 25.0 35.0 18.0 25.0 35.0 35.0 35.0 35.0

NT-H 1200 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

9.0

NW-N 2000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

PK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 51.3 35.0 50.0

NW-H 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-H 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-LF 1600 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 58.5

58.5 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6
Continued on next page

50

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 21:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


UL 600 Vac 6001200 A

UL 600 Vac 6001200 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating
kAIR1

DJ

LD

LG

LJ

LL

LC

LE

LX

LI

LXI

MG MJ

PG

PJ

PK

RG

RJ

RL

RK

18

25

14

18

25

50

35

35

35

100

100

18

18

25

50

18

25

50

65

50

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 25.0 14.0 18.0 25.0 25.0 25.0 25.0 25.0 25.0

25.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 25.0 25.0 25.0 25.0

65

NW-N 2000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 51.3 35.0 50.0

NW-H 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-H 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0

100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-LF 1600 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 58.5

58.5 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

18

RG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

25

RJ

18.0 25.0 14.0 18.0 25.0 25.0 25.0 25.0 25.0 25.0

25.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 25.0 25.0 25.0 25.0

65
85

100

NW-N 2000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 51.3 35.0 50.0

NW-H 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 36.0 18.0 25.0 36.0 36.0 35.0 36.0

NW-H 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 2000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0 100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-L 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0 100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

NW-LF 2000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 58.5

4000
6000 A

35

RJ

50

3000 A

NT

RG

100

2500 A

25

NT

25

85

2000 A

DG

18

50
1600 A

Type

58.5 18.0 21.6 18.0 21.6 21.6 18.0 21.6 21.6 21.6 21.6 21.6

18

RG

18.0 18.0 14.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0

25

RJ

18.0 25.0 14.0 18.0 25.0 25.0 25.0 25.0 25.0 25.0

25.0 18.0 25.0 18.0 25.0 25.0 18.0 25.0 25.0 25.0 25.0 25.0

50

RL

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 50.0

50.0 18.0 25.0 18.0 25.0 40.8 18.0 25.0 40.8 40.8 35.0 40.8

65

RK

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 65.0

65.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 51.3 35.0 50.0

85

NW-H 3000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

100

NW-L 3000 A

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0 100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

85

NW-H 3000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

100

NW-L 3000 A

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0 100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 58.5 35.0 50.0

85

NW-H 6000 A 18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 85.0

100

NW-L 6000 A

85.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 65.0 35.0 50.0

18.0 25.0 14.0 18.0 25.0 50.0 35.0 35.0 35.0 100.0 100.0 18.0 25.0 18.0 25.0 50.0 18.0 25.0 50.0 65.0 35.0 50.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit
breaker.

Number after NW-x indicates frame size.

20052013 Schneider Electric All Rights Reserved

51

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


ANSI 240 Vac 800 A

0100DB0501
R02/13, 05/2013

APPENDIX C
Levels of Short Circuit Selective
Coordination for ANSI Low Voltage
Power Circuit Breakers

The data in the following tables for ANSI C37.13 and C37.50, UL 1066
Listed, low voltage power circuit breakers also applies to CSA
C22.2 #31-M89 Certified low voltage power circuit breakers. All data is at 60
Hz. The data does not apply to circuit breakers that are UL 489 Listed, or
Certified to IEC 60947-2 only, or at frequencies other than 60 Hz.

Appendix C
Type

Volts

Downstream
Circuit Breaker
(frame size)

Table No.

Page No.

22

52

23

53

600

24

54

240

25

54

240
480

ANSI

800 A

26

55

600

27

56

240

28

56

29

57

30

57

480

480

1600 A

2000 A

600

Table 22:

Type

Downstream Circuit BreakerType / kAIR


Maximum Level of Selective Coordination Shown in kA
NT-N1 08

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

42

65

85

100

200

200

NW-N1 1600 A

42.0

42.0

42.0

42.0

42.0

42.0

42.0

42

NW-N1 1600 A

42.0

42.0

42.0

42.0

42.0

42.0

42.0

65

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

85

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 1600 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0
100.0

Max. Cont.
Current Rating

kAIR1

800 A

42

100
200
65

85

2000 A

100

200

65
85
3200 A

Based on laboratory testing, Schneider Electric certifies the following levels


of selective coordination based upon the construction of the specific circuit
breakers referenced as of the date of publication of this document.

ANSI 240 Vac 800 A Selective Coordination

Upstream Circuit Breaker2

1600 A

Fully rated pairs of circuit breakers where there is a reasonable expectation


of selective coordination are shown. Pairings of the same frame circuit
breakers are not shown, as such pairings would not be expected to
selectively coordinate.

100
200

NW-L1F 16

NW-H3 3200 A

42.0

42.0

65.0

76.5

76.5

100.0

NW-L1 1600 A

31.5

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-H1 2000 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

42.0

65.0

85.0

76.5

100.0

100.0

NW-H3 3200 A

42.0

42.0

65.0

85.0

76.5

100.0

100.0

NW-H3 5000 A

42.0

42.0

65.0

85.0

76.5

100.0

100.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

Continued on next page

52

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 22:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


480 Vac 800 A

ANSI 240 Vac 800 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type
kAIR1
85

4000 A

5000 A

NW-H2 5000 A

NT-N1 08

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

42

65

85

100

200

NW-L1F 16
200

42.0

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

42.0

65.0

85.0

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

42.0

65.0

85.0

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Table 23:

ANSI 480 Vac 800 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

kAIR1

800 A

42
42

1600 A

Type

NT-N1 08

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

NW-L1F 16

42

42

65

85

100

200

200

NW-N1 1600 A

42.0

42.0

42.0

42.0

42.0

42.0

42.0

NW-N1 1600 A

42.0

42.0

42.0

42.0

42.0

42.0

42.0

65

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

85

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 3200 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-H1 2000 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 3200 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

65

85

2000 A

100

200

65
85
3200 A

100
200

4000 A

5000 A

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

NW-H1 3200 A

42.0

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0
200.0

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

85

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

42.0

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

42.0

65.0

85.0

100.0

200.0

200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

20052013 Schneider Electric All Rights Reserved

53

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


ANSI 240 Vac 1600 A

Table 24:

ANSI 600 Vac 800 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type

85
130
65

85
2000 A

130

65

3200 A

85

130

4000 A

85
130

5000 A

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

65

85

85

130

130

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 3200 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H1 2000 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

65.0

85.0

85.0

130.0

130.0

kAIR1
65

1600 A

0100DB0501
R02/13, 05/2013

85
130

NW-L1F 16

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 3200 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Table 25:

ANSI 240 Vac 1600 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type

65

85

2000 A

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

65

85

100

200

200

NW-H1 2000 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

65.0

85.0

100.0

200.0

200.0

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

kAIR1

100

200

NW-L1F 16

200.0
Continued on next page

54

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 25:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


ANSI 480 Vac 1600 A

ANSI 240 Vac 1600 A Selective Coordination (continued)


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

Type
65
85

3200 A

100
200

4000 A

5000 A

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

65

85

100

200

200

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

100.0

100.0

kAIR1

NW-L1F 16

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

42.0

65.0

85.0

100.0

200.0

200.0
200.0

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

85

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Table 26:

ANSI 480 Vac 1600 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current
Rating

Type
kAIR1
65

85

2000 A

100

200

65
85
3200 A

5000 A

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

NW-L1F 16

42

65

85

100

200

200

NW-H1 2000 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

65.0

85.0

100.0

200.0

200.0
200.0

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

42.0

65.0

85.0

100.0

200.0

200.0

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

42.0

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

42.0

65.0

85.0

100.0

200.0

200.0

100
200

4000 A

NW-N1 16

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

20052013 Schneider Electric All Rights Reserved

55

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


ANSI 600 Vac 1600 A

Table 27:

0100DB0501
R02/13, 05/2013

ANSI 600 Vac 1600 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

kAIR1
65

85
2000 A

130

65

85

3200 A

130
85

4000 A

130
85

5000 A

130

NW-N1 16

NW-H1 16

NW-H2 16

NW-H3 16

NW-L1 16

42

65

85

85

130

130

NW-H1 2000 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 2000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 2000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 2000 A

31.5

31.5

31.5

31.5

31.5

31.5

NW-L1F 2000 A

21.6

21.6

21.6

21.6

21.6

21.6

NW-L1 3200 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H1 3200 A

42.0

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 3200 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

42.0

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

42.0

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

42.0

65.0

85.0

85.0

130.0

130.0

Type

NW-L1F 16

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Table 28:

ANSI 240 Vac 2000 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

kAIR1
65
85

3200 A

100
200

4000 A

5000 A

NW-H1 20

NW-H2 20

NW-H3 20

NW-L1 20

65

85

100

200

200

NW-H1 3200 A

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

65.0

76.5

76.5

100.0

100.0

Type

NW-L1F 20

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

65.0

85.0

100.0

200.0

200.0
200.0

NW-L1 5000 A

65.0

85.0

100.0

200.0

85

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

65.0

85.0

100.0

200.0

200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

56

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Table 29:

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


ANSI 600 Vac 2000 A

ANSI 480 Vac 2000 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

65
85
3200 A

100
200

4000 A

5000 A

NW-H1 20

NW-H2 20

NW-H3 20

NW-L1 20

65

85

100

200

200

NW-H1 3200 A

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

65.0

76.5

76.5

100.0

100.0

kAIR1

Type

NW-L1F 20

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

NW-L1 3200 A

65.0

105.3

100.0

200.0

200.0
200.0

NW-L1 5000 A

65.0

105.3

100.0

200.0

85

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

65.0

85.0

100.0

200.0

200.0

85

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

100

NW-H3 5000 A

65.0

76.5

76.5

100.0

100.0

200

NW-L1 5000 A

65.0

85.0

100.0

200.0

200.0

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

Table 30:

ANSI 600 Vac 2000 A Selective Coordination


Downstream Circuit BreakerType / kAIR
Maximum Level of Selective Coordination Shown in kA

Upstream Circuit Breaker2


Max. Cont.
Current Rating

65

3200 A

85

130

4000 A

85
130

5000 A

NW-H1 20

NW-H2 20

NW-H3 20

NW-L1 20

65

85

85

130

130

NW-H1 3200 A

65.0

65.0

65.0

65.0

65.0

NW-H2 3200 A

65.0

85.0

85.0

85.0

85.0

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

NW-H3 3200 A

65.0

76.5

76.5

85.0

85.0

NW-H3 5000 A

65.0

76.5

76.5

85.0

85.0

NW-L1 3200 A

65.0

85.0

85.0

130.0

130.0

NW-L1 5000 A

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

65.0

85.0

85.0

130.0

130.0

NW-H2 5000 A

65.0

85.0

85.0

85.0

85.0

NW-H3 5000 A

65.0

76.5

76.5

85.0

85.0

NW-L1 5000 A

65.0

85.0

85.0

130.0

130.0

kAIR1

85
130

Type

NW-L1F 20

This is the interrupting rating of the upstream circuit breaker, and therefore, the maximum available short circuit current on the line side of the upstream circuit breaker.

Number after NW-x indicates frame size.

20052013 Schneider Electric All Rights Reserved

57

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Glossary

0100DB0501
R02/13, 05/2013

APPENDIX D
Glossary

58

ampacityThe RMS current, in amperes, that a conductor or circuit breaker


can carry continuously under the conditions of use without exceeding its
temperature rating.
ampere ratingSee continuous current rating.
ANCE(National Association of Standardization and Certification for the
Electrical Sector) The standards and certification agency accredited by the
Mexican government.
ANSIAmerican National Standards Institute.
Canadian Standards Association(CSA) Canadian product safety testing
and certification organization.
circuit breakerA device designed to open and close a circuit by nonautomatic means and to open the circuit automatically on an overcurrent
without damage to itself when properly applied within its rating.
circuit breaker frame(1) The circuit breaker housing which contains the
current carrying components, the current sensing components, and the
tripping and operating mechanism. (2) That portion of an interchangeable
trip molded case circuit breaker remaining when the interchangeable trip unit
is removed.
close and latch ratingThe maximum level of current a circuit breaker can be
closed on and still have the mechanism latch in the fully closed position.
continuous current ratingThe designated RMS alternating or direct current
in amperes which a device or assembly will carry continuously in free air
without tripping or exceeding temperature limits.
CSASee Canadian Standards Association.
frame sizeThe largest ampere rating available in a group of circuit breakers of
similar physical configuration.
ground faultAn unintentional current path, through a grounded conductor,
enclosure, raceway or the earth, back to the source.
instantaneous selective overrideA fixed, non-adjustable, instantaneous trip
function set just below a circuit breakers withstand capability.
instantaneous tripA qualifying term indicating that no delay is purposely
introduced in the tripping action of the circuit breaker during short-circuit
conditions.
insulated case circuit breaker(ICCB) UL Standard 489 Listed non-fused
molded case circuit breakers which utilize a two-step stored energy closing
mechanism, electronic trip system and optional draw-out construction.
interrupting ratingThe highest current at rated voltage that the circuit breaker
is rated to interrupt in RMS symmetrical amperes. When the circuit breaker
can be used at more than one voltage, the interrupting rating will be shown
on the circuit breaker for each voltage level. The interrupting rating of a
circuit breaker must be equal to or greater than the available short-circuit
current at the point at which the circuit breaker is applied to the system.
kAIRAmpere Interrupting Rating in thousands of amperes. See interrupting
rating.
let-throughThe current which passes through an overcurrent protective
device during an interruption.
making current releaseA fixed, non-adjustable, instantaneous trip function
set just below a circuit breakers close and latch rating.
molded case circuit breaker(MCCB) A circuit breaker which is assembled as
an integral unit in a supportive and enclosed housing of insulating material,
generally 20 to 3000 A in size and used in systems up to 600 Vac and
500 Vdc.
NMX(Norma Mexicana X) Mexican safety standards.

20052013 Schneider Electric All Rights Reserved

0100DB0501
R02/13, 05/2013

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Glossary

selective coordinationLocalization of an overcurrent condition to restrict an


outage to the circuit or equipment affected, accomplished by the choice of
overcurrent protective devices and their ratings or settings. (NEC 100 Definitions)
time-current curveA graphical representation of the response of a circuit
breaker to current over a period of time.
ULSee Underwriters Laboratories Inc.
Underwriters Laboratories Inc.(UL) An independent, not-for-profit standards
development, product safety testing and certification organization.

20052013 Schneider Electric All Rights Reserved

59

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Glossary

60

0100DB0501
R02/13, 05/2013

20052013 Schneider Electric All Rights Reserved

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Data Bulletin

Schneider Electric
1415 S. Roselle Road
Palatine, IL 60067 USA
1-888-778-2733
www.schneider-electric.us
61

0100DB0501
R02/13, 05/2013

Electrical equipment should be installed, operated, serviced, and maintained only by


qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
20052013 Schneider Electric All Rights Reserved
Schneider Electric, Square D, PowerPact, and I-Line are trademarks owned by
Schneider Electric Industries SAS or its affiliated companies. All other trademarks are
the property of their respective owners.

Short Circuit Selective Coordination for Low Voltage Circuit Breakers


Glossary

62

0100DB0501