PROJECT: BMW SHOWROOM SUBJECT: PLUMBING AND FIRE FIGHTING DATE: 23-01-2013 WATER CONSUMPTION DEMAND FOR WATER

SUPPLY I. WATER DEMAND FOR STAFF AND VISITOR 1.FRONT OFFICE -Number of staff estimated -Flow rate per staff Total flow rate for staff -Number of passenger/visitor -Flow rate per person Total flow rate for visitor 35 15 57 525 1988 70 5 19 350 1325 875 3312 25 30 114 750 2839 7 staff Gallons Liters Gallons Liters pers Gallons Liters Gallons Liters Gallons Liters staff Gallons Liters Gallons Liters Cu.m

Flow rate for staff and visitor 1.Work shop -Number of staff estimated -Flow rate per staff Total flow rate for staff

WATER DEMAND PER DAY

II. WATER DEMAND FOR CAR WASHER -Water consumption estimated Total flow rate for staff WATER DEMAND PER DAY 792 2998 792 3 Gallons Liters Gallons Cu.m

III. IRRIGATION -Water consumption estimated Total flow rate for staff WATER DEMAND PER DAY 792 2998 792 3 Gallons Liters Gallons Cu.m

GRAND TOTAL WATER DEMAND

13

Cu.m

Water consumption calculation

Page 1 of 9

-Safety factor - Time reserve GRAND TOTAL WATER DEMAND CHOOSE STAINLESS WATER TANK

10% 1 15 10

day Cu.m/day Cu.m

WATER CONSUMPTION DEMAND FOR FIRE FIGHTING -Fire hose reel -Flow rate per hose reel -Time reserve Total flow rate for hose reels Total flow rate for hose reels 2 0.55 90 99 5.94 running l/s mn l/mn Cu/m

Water consumption calculation

Page 2 of 9

PROJECT: BMW SHOWROOM SUBJECT: PLUMBING AND FIRE FIGHTING DATE: 23-01-2013 SEPTICA TANK CALCULATION I. FRONT OFFICE - Depend on Water consumption - The liquid volume of the tank in gallons V= V= - Refering from technical data of septic tank Maximum depth for septic tank is And Assume 2m as the width of tank Thus, L= to the value fo L. Thus, Thus, Total L= Total length of the septic tank (L)= SIZE OF SEPTIC TANK: II. WORK SHOP - Depend on Water consumption - The liquid volume of the tank in gallons V= V= - Refering from technical data of septic tank Maximum depth for septic tank is And Assume 2m as the width of tank Thus, L= to the value fo L. Thus, Thus, Total L= Total length of the septic tank (L)= SIZE OF SEPTIC TANK: III. COMBINED OFFICE AND WORK SHOP - Depend on Water consumption - The liquid volume of the tank in gallons 1625 6151 Gallons Liters 3.3 3.3 m m 1.5 2 2.2 m m m 1688 6.4 Gallons Cu.m 750 2839 Gallons Liters 3.5 3.5 m m 1.5 2 2.3 m m m 1782 6.8 Gallons Cu.m 875 3312 Gallons Liters

- The value of L is ony for the length of the digestion chamber. Divide it by 2 then add

3.5m(L)x2.0m(W)x1.5m(D)

- The value of L is ony for the length of the digestion chamber. Divide it by 2 then add

3.5m(L)x2.0m(W)x1.5m(D)

Water consumption calculation

Page 3 of 9

V= V= - Refering from technical data of septic tank Maximum depth for septic tank is And Assume 2m as the width of tank Thus, L= to the value fo L. Thus, Thus, Total L= Total length of the septic tank (L)= SIZE OF SEPTIC TANK:

2344 8.9 1.5 2 3

Gallons Cu.m m m m

- The value of L is ony for the length of the digestion chamber. Divide it by 2 then add 4.5 4.5 m m

4.5m(L)x2.0m(W)x1.5m(D)

Water consumption calculation

Page 4 of 9

PROJECT: SUBJECT: PLUMBING SYSTEM DATE: 2012 DOMESTIC WATER SUPPLY SYSTEM MAIN PIPE SIZING I. 12th floor
Item 1 2 3 4 5 6 7 8 9 10 Description Water Closet Wash Basin/Lavatory Urinal Kitchen sink/Sink(G1/2) Kitchen sink/Sink(G1) Bathup (G 3/4) Bathup (G 1) Shower Washing machine Dish washing machine TOTAL Fixture No. U/Flow Rate(l/s) T/Flow Rate(l/s) 15 0.10 1.500 16 0.10 1.600 1 0.10 0.100 2 0.20 0.400 0 0.30 0.000 9 0.35 3.150 0 0.60 0.000 4 0.25 1.000 3 0.40 1.200 3 0.40 1.200 53 10.150 : : : : : : : 53 10.15 l/s 0.139 1.41 l/s 50 mm 0.8 m/s 300 Pa/m

Total Sanitary Fixture Total Flow Rate K Facture Total cold water flow rate required Pipe Sizing Calculated OD Velocity Pressure drop References: 1. Le formulare des installations sanitaires 2. Pipe sizing - 1997 ASHRAE Fundamentals Handbook (SI)

DN40mm

Page 5 of 9

PROJECT: BMW SHOWROOM SUBJECT: PLUMBING SYSTEM DATE: 28-02-2013

BOOSTER PUMP-01&02
Item 1 2 3 4 5 6 7 8 9 10 Description Water Closet Wash Basin/Lavatory Urinal Kitchen sink/Sink(G1/2) Kitchen sink/Sink(G1) Bathup (G 3/4) Bathup (G 1) Shower Washing machine Faucet TOTAL Fixture No. U/Flow Rate(l/s) T/Flow Rate(l/s) 9 1.50 13.500 9 0.10 0.900 6 0.10 0.600 3 0.20 0.600 0 0.30 0.000 0 0.35 0.000 0 0.60 0.000 0 0.25 0.000 0 0.40 0.000 5 0.40 2.000 32 17.600 : : : : : : : : : 32 17.6 l/s 0.144 2.53 l/s 13 m 11 m 5m 29 m 2.9 bar

Total Sanitary Fixture Total Flow Rate K Facture Total water flow rate required Pump pressure head required - Pressure at highest draw-off point - High from pump to highest draw-off point - Pressure drop Total pressure required BOOSTER PUMP CAPACITY: - Water flow rate (K factor 10%) - Water pressure head

9.108 m3/hr

: :

11 m3/hr 3.2 bar

Page 6 of 9

PROJECT: BMW SHOWROOM SUBJECT: PLUMBING SYSTEM DATE: 28-02-2013 FIRE FIGHTING PUMP
Fire hose reel system 1- Hose reel system referring to british standard design and installation. - Area identification: Office - Design density - Number of instantaneous operation - Total water flow rate required - Pressure at highest draw-off point Pump pressure head required combine all system - Pressure at highest draw-off point - High from pump to highest draw-off point - Pressure drop Total pressure required for fire pump PRINCIPAL PUMP CAPACITY: - Water flow rate (140%) - Water pressure head JOKEY PUMP CAPACITY - Water flow rate - Water pressure head (Add 10% of main pump) : : : : : : : : : 0.5 l/s 3 nos 1.5 l/s 25 m 6 m3/hr

25 m 10 m 5m 40 m 4 bar

: :

8.4 m3/hr 4 bar

: :

3.6 m3/hr 4.4 bar

GARDEN PUMP
2 garden taps Total water flow rate required Pump pressure head required - Pressure at highest draw-off point - High from pump to highest draw-off point - Pressure drop Total pressure required BOOSTER PUMP CAPACITY: - Water flow rate - Water pressure head : : : : : : : 0.8 l/s 0.8 l/s 20 m 10 m 4m 34 m 3.4 bar

2.88 m3/hr

: :

2.9 m3/hr 3.4 bar

Page 7 of 9

PROJECT:BMW SHOWROOM SUBJECT: PLUMBING AND FIRE FIGHTING SYSTEM DATE: 06-03-2013 PUMP SCHEDULE Item Description Booster pump, Inverter BP-01&02 (twin pumps, 1 duty, 1 standby) > Booster pump, Q :11.0 m3/h @ 3.3 bar, for each 1 > 1 protection panel > Pressure tank capacity: 55 Liters > Pressure switch, flow switch Fire fighting pump system: > Electrical fire pump(EFP), Q :9.0 m3/h @ 4.0 bar > Diesel fire pump(DFP), Q :9.0 m3/h @ 4.0 bar > Jokey pump(JP), Q :.3.0 m3/h @ 4.4 bar 2 > 1 protection panel for Electrical & Jokey pump > 1 protection panel for Diesel fire pump > 1 pressure tank > Pressure switch, flow switch Submersible pump 3 > Submersible pump(SP-01), Q :5.4 m3/h @ 0.8 bar > 1 protection panel Submersible pump (twin pumps, 1 duty, 1 standby) 4 > Submersible pump(SP-02&03), Q :5.4 m3/h @ 0.8 bar for each > 1 protection panel set set set set set set set set set set 1 1 1 1 1 1 1 1 1 1 near oil separator(Ground floor) Waste water Control by floatless level switch (for oil separator system) In water tank(Ground floor) Waste water Control by floatless level switch (for overflow and clean water tank) Unit set set set set set set set set set Qty 1 1 1 1 1 1 1 1 1 Pump Room(Ground floor) Fire fighting Control by pressure Pump Room(Ground floor) Water supply Control by pressure Location Service Remark

Plumbing

Page 8 of 9

PROJECT: BMW
TASK: PLUMBING SYSTEM, PRESSURE TANK DATE: 27-05-2013 Reference: Calpeda pressure tank volume calculaton

PRESSURE TANK VOLUME SELECTION

Vt= (Qm/4xZ)x1/1-((P2-2)/P1) Vt: Total volume of air cushion vessel in m3 Qm: Average pump flow in m3 Qmin: Minimum pump flow in m3 Qmax: Maximum pump flow in m3 P1: Maximum set pressure of pressure switch P2: Minimum set pressure of pressure switch Z: Mazimum nuber of starts/hours allowed by the motor Qmin: Qmax: Qm: P1: P2: Z: Vt= Thus, If, Thus, Pressure tank capacity: Pump is inverter, so, safety factor Pressure tank capacity: m3/h m3/h 11 m3/h 45 m 20 m 21 time 0.218254 219 Liters 25 % 55 Liters Recommendation Recommendation Recommendation Recommendation Qm= (Qmin + Qmax)/2