Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Note Output Voltage Distortion Output Frequency (sync to mains) Waveform Type Output Connections
2700 Watts / 3000 VA 2700 Watts / 3000 VA 230V Configurable for 220 : 230 or 240 nominal output voltage Less than 5% at full load 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Sine wave (8) IEC 320 C13 (1) IEC 320 C19 (2) IEC Jumpers
Input
230V 50/60 Hz +/- 3 Hz (auto sensing) IEC-320 C20 Schuko CEE 7 / EU1-16P British BS1363A 160 - 286V
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof 3 hour(s) RBC43 1
https://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA3... 12/15/2010
Page 2 of 3
Runtime Graph
Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Graph
Communications & Management
Interface Port(s) Available SmartSlot Interface Quantity Control panel Audible Alarm Emergency Power Off (EPO)
Surge Protection and Filtering
DB-9 RS-232,SmartSlot,USB 1 LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators Alarm when on battery : distinctive low battery alarm : configurable delays Yes
480 Joules Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
89.00 mm 483.00 mm
https://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA3... 12/15/2010
Page 3 of 3
Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height Shipping Width Shipping Depth Color Units per Pallet
Environmental
Operating Environment Operating Relative Humidity Operating Elevation Storage Temperature Storage Relative Humidity Storage Elevation
Audible noise at 1 meter from 47.00 dBA surface of unit Online Thermal Dissipation
Conformance
400.00 BTU/hr
C-tick,CE,EN 50091-1,EN 50091-2,GOST,VDE 2 years repair or replace,optional on-site warranties available,optional extended warranties available RoHS 7b Exemption,China RoHS
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. Copyright American Power Conversion Corp., all rights reserved
https://www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SUA3... 12/15/2010