Home Abstract Abstract of CPWD-Part 1 Abstract of IS Code. IS 1255 IS 15652/11171/1445/1678 IS 3043 / 5039 IS 694 / 1554 / 11892 IS 5613 IE Rules for DP Structure Abstract of IE Rules Electrical Notes Electrical Q&A Electrical Q&A Part-1 Electrical Q&A Part-2 Electrical Q&A Part-3 Electrical Q&A Part-4 Electrical Tools Excel Tools Posts Comments Uncategorized Single Earthed Neutral and Multi Earthed Neutral. Calculate Transverse Load on PCC/RCC/Tublar/RSJ Pole.
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
1 / 10
9/7/2013
These ELCBs monitored the voltage on the earth wire, and disconnected the supply if the earth wire voltage was over 50 volts. These devices are no longer used due to its drawbacks like if the fault is between live and a circuit earth, they will disconnect the supply. However, if the fault is between live and some other earth (such as a person or a metal water pipe), they will NOT disconnect, as the voltage on the circuit earth will not change. Even if the fault is between live and a circuit earth, parallel earth paths created via gas or water pipes can result in the ELCB being bypassed. Most of the fault current will flow via the gas or water pipes, since a single earth stake will inevitably have a much higher impedance than hundreds of meters of metal service pipes buried in the ground.
The way to identify an ELCB is by looking for green or green and yellow earth wires entering the device. They rely on
voltage returning to the trip via the earth wire during a fault and afford only limited protection to the installation and no personal protection at all. You should use plug in 30mA RCDs for any appliances and extension leads that may be used outside as a minimum.
Advantages
ELCBs have one advantage over RCDs: they are less sensitive to fault conditions, and therefore have fewer nuisance trips. While voltage and current on the earth line is usually fault current from a live wire, this is not always the case, thus there are situations in which an ELCB can nuisance trip. When an installation has two connections to earth, a nearby high current lightning strike will cause a voltage gradient in the soil, presenting the ELCB sense coil with enough voltage to cause it to trip. If the installations earth rod is placed close to the earth rod of a neighboring building, a high earth leakage current in the other building can raise the local ground potential and cause a voltage difference across the two earths, again tripping the ELCB. If there is an accumulated or burden of currents caused by items with lowered insulation resistance due to older equipment, or with heating elements, or rain conditions can cause the insulation resistance to lower due to moisture tracking. If there is a some mA which is equal to ELCB rating than ELCB may give nuisance Tripping. If either of the earth wires become disconnected from the ELCB, it will no longer trip or the installation will often no longer be properly earthed. Some ELCBs do not respond to rectified fault current. This issue is common for ELCBs and RCDs, but ELCBs are on average much older than RCB so an old ELCB is more likely to have some uncommon fault current waveform that it will not respond to. Voltage-operated ELCB are the requirement for a second connection, and the possibility that any additional connection to earth on the protected system can disable the detector. Nuisance tripping especially during thunderstorms.
Disadvantages:
They do not detect faults that dont pass current through the CPC to the earth rod. They do not allow a single building system to be easily split into multiple sections with independent fault protection, because earthing systems are usually use common earth Rod. They may be tripped by external voltages from something connected to the earthing system such as metal pipes, a TN-S earth or a TN-C-S combined neutral and earth. As electrically leaky appliances such as some water heaters, washing machines and cookers may cause the ELCB to trip. ELCBs introduce additional resistance and an additional point of failure into the earthing system.
Can we assume whether Our Electrical System is protected against Earth Protection or not by only Pressing ELCB Test Switch?
Checking the health of the ELCB is simple and you can do it easily by pressing TEST Push Button Switch of ELCB. The test push-button will test whether the ELCB unit is working properly or not. Can we assume that If ELCB is Trip after Pressing TEST Switch of ELCB than your system is protected against earth protection? Then you are wrong. The test facility provided on the home ELCB will only confirm the health of the ELCB unit, but that test does not confirm that the ELCB will trip when an electric shock hazard does occur. It is a really sad fact that all the while this misunderstanding has left many homes totally unprotected from the risk of electric shocks. This brings us or alarming us to think over second basic requirement for earth protection. The second requirement for the proper operation of a home shock protection system is electrical grounding. We can assume that the ELCB is the brain for the shock protection, and the grounding as the backbone. Therefore, without a functional grounding (Proper Earthing of Electrical System) there is totally no protection against electrical shocks in your house even if You have installed ELCB and its TEST switch show proper result. Looking after the ELCB alone is not enough. The electrical Earthing system must also be in good working order for the shock protection system to work. In addition to routine inspections that should be done by the qualified electrician, this grounding should preferably be inspected regularly at shorter intervals by the homeowner and need to pour Water in Earthing Pit at Regular interval of Time to minimize Earth Resistance.
9/7/2013
residual-current devices. However, some companies use the term ELCB to distinguish high sensitivity current operated 3 phase devices that trip in the milliamp range from traditional 3 phase ground fault devices that operate at much higher currents.
Sensitivity of RCB:
Medium sensitivity (MS): 100- 300- 500- 1000 mA (for fire protection) Low sensitivity (LS): 3- 10- 30 A (typically for protection of machine)
Type of RCB:
Type A: RCD for which tripping is ensured for residual sinusoidal alternating currents for residual pulsating direct currents For residual pulsating direct currents superimposed by a smooth direct current of 0.006 A, with or without phase-angle control, independent of the polarity. Type B: RCD for which tripping is ensured as for type A for residual sinusoidal currents up to 1000 Hz for residual sinusoidal currents superposed by a pure direct current for pulsating direct currents superposed by a pure direct current for residual currents which may result from rectifying circuits three pulse star connection or six pulse bridge connection two pulse bridge connection line-to-line with or without phase-angle monitoring, independently of the polarity There are two groups of devices:
Rate this:
6 Votes
Share this:
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/ 3 / 10
9/7/2013
Like this:
Like Loading...
About Jignesh.Parmar
Jignesh Parmar has completed his B.E(Electrical) from Gujarat University. He has more than 11 years experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical Projects(Planning-Designingcoordination-Execution). He is Presently associate with one of the leading business group as a Assistant Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.
3.
4.
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
4 / 10
9/7/2013
Reply 5.
7.
8.
10.
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
5 / 10
9/7/2013
Reply 12.
13.
16.
17.
18.
19.
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
6 / 10
9/7/2013
Reply 20.
Leave a Reply
Email (required)
Name (required)
Website
Notify me of follow-up comments via email. Notify me of new posts via email.
Post Comment
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
7 / 10
9/7/2013
Proud to be an IndiBlogger
electricalnotes.wordpress.c...
85
Search for:
/100
Search
Recent Posts
Electrical Thumb Rules-(Part-6) Electrical Thumb Rules-(Part-5) Electrical Thumb Rules-(Part-4) Electrical Thumb Rules-(Part-3) Electrical Thumb Rules (Part-2) Electrical Thumb Rules-(Part 1). Total Losses in Power Distribution and Transmission Lines-Part 2 Total Losses in Power Distribution & Transmission Lines-Part 1 Calculate TC Size & Voltage Drop due to starting of Large Motor Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter Calcualte Number of Lighting Fixtures & Lux Level Calculate Voltage Regulation of Distribution Line Calculate Size of Transformer and Voltage drop due to starting of large size motor Design DOL / Star-Delta Starter Calculate Size of Motor-Pump Calculate Numbers of Plate/Pipe/Strip Earthings (Part-3) Calculate Numbers of Plate/Pipe/Strip Earthings (Part-2) Calculate Numbers of Plate/Pipe/Strip Earthings (Part-1) Size and Location of Capacitor in Electrical System-(Part 2) Size and Location of Capacitor in Electrical System-(Part1)
Archives
September 2013 (2) August 2013 (3) July 2013 (3) June 2013 (3) May 2013 (3) April 2013 (2) March 2013 (3) February 2013 (2)
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/ 8 / 10
9/7/2013
January 2013 (3) December 2012 (2) November 2012 (3) October 2012 (1) September 2012 (3) August 2012 (7) July 2012 (2) May 2012 (7) April 2012 (2) March 2012 (3) February 2012 (3) January 2012 (1) December 2011 (3) November 2011 (2) October 2011 (4) September 2011 (2) August 2011 (1) June 2011 (5) May 2011 (3) April 2011 (12) March 2011 (17)
EEP
DOWNLOAD BOOKS-NOVELS
Pages
Abstract Abstract of CPWD-Part 1 Abstract of IE Rules Abstract of IS Code. IS 1255 IS 15652/11171/1445/1678 IS 3043 / 5039 IS 5613 IS 694 / 1554 / 11892 IE Rules for DP Structure Electrical Notes Electrical Q&A Electrical Q&A Part-1 Electrical Q&A Part-2 Electrical Q&A Part-3 Electrical Q&A Part-4 Electrical Tools Excel Tools
Top Clicks
electricalnotes.files.wor electricalnotes.files.wor electricalnotes.files.wor electricalnotes.files.wor jiguparmar.com
Recent Comments
Jignesh.Parmar on Electrical Thumb Rules-(P Shriram V. Bhardwaj on Abstract of IE Rules
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/ 9 / 10
9/7/2013
siva muthusamy on Electrical Thumb Rules-(P JEROME on HIPOT Testing Manivannan on Electrical Q&A Part-1 Dr. Aung Ze Ya on Effects of High Voltage Transm BIJAYA KUMAR MOHANTY on Electrical Notes parth on Current Transformer parth on Current Transformer john on Current Transformer Blog at WordPress.com. The Enterprise Theme. Follow
Sign me up
Powered by WordPress.com %d bloggers like this:
http://electricalnotes.wordpress.com/2011/10/01/working-principle-of-elcb-and-rcb/
10 / 10