1. Introduction
NSPB (non-segregated phase bus) LV, MV is an assembly of bus conductors with associated connections, joints and insulating
supports confined within a metal enclosure without inter-phase barriers.
The insulation property of NSPB LV-MV is very reliable, because bus bars are adequately separated and insulated with
EPOXY from each other.
To optimize bus bar supports and bus bar size, LSC use mechanical, thermal and electrical analysis. NSPB LV-MV is designed
and produced for IEEE C 37.23 and IEC 62271-200, and has certification of PT & T (LSIS, KOLAS) and KERI (Korea electro
technology research institute) about short-circuit strength, dielectric properties and temperature-rise limits.

HOUSING
Housing of NSPB LV-MV is usually Aluminum Alloy, but user can optionally choose SPCC (three-planes) and STS (one
plane). Housing is basically painted with 5Y/7/1, but user can customize its various colors. And the paint of housing and plate
are certificated by RoHS. To prevent dew condensation, LSC use SPACE HEATER and AIR VENTILATION in outdoor
products.

GROUNDING SYSTEM
Aluminum housing has PE(Protect Earth) function. Whereas user wants SPCC, additional Ground Bar can be applied. Fault
current that is caused by ground accident can be flowed out through ground bar so that it can maintain its performance in
contact with body and others.

CONDUCTOR
Bus conductors are fixed by bolted connections, which surfaces are tin-plated. Bus conductors can continuously carry the rated
current without exceeding the hottest temperature rise of 65 over the outside ambient temperature at 40.

CONDUCTOR INSULATION
The insulation of bus bars is Epoxy powder coated by Fluidized method. Total thickness after insulation becomes 1~1.2mm.
The process of insulating shall be performed under clean condition and the insulation class is B (130).

CONDUCTOR SUPPORTORS
SUPPORTING INSULATOR
Epoxy mold which has good electric and mechanic properties is applied to bus bars supports. To maintain the stability in shortcircuit condition; it is optimized by using CAE (Computer Aided Engineering) analysis. It is made of highly-effective (high
endurance and fire resistance) and eco-friendly materials.

SILICONE SPACER
To support bus bars, silicone is applied with epoxy mold. Silicone can contribute to both the ease of assembling and impactabsorbing by short-circuit condition. Additionally, it can reduce the rattling noise that caused by bus bar vibration during
operation.

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

165.244.42.57 / 2011.02.10 13:24 / 20090273

APPLIED STANDARD
IEEE C 37.23 : Metal-Enclosed Bus.
IEC 62271-200 : AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV.

TEMPERATURE RISE
The bus will be capable of carrying rated current continuously without exceeding a conductor temperature rise of 65C over an
outside ambient temperature of 40C, as required by IEEE C 37.23.

SHORT CIRCUIT WITHSTAND ABILITY


NSPB LV-MV are designed to withstand electrical and mechanical forces generated by momentary peak (during 10 cycle) and
short-time (LV : 1sec., MV : 2 sec.) short circuit currents in accordance with the latest IEEE C 37.23. For LV application, 4cycle momentary current withstand rating up to 50 kA (rms symmetrical) is also available.

1.1 Product Description


Splice Joint
Conductors are tin-plated for maximum conductivity (silver-plating is optional).
While the higher ratings use two conductors per phase, adjacent sections are electrically bonded together by means of plated
copper splice plates to provide electrical continuity. All splice joints should be fastened by 250kg.cm torque.

Bolt-Nut Boot Connection


Bolt-nuts of Bus joints are insulated with a flame-retardant PVC boot, easily removable for joint inspection.

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

165.244.42.57 / 2011.02.10 13:24 / 20090273

2. Specification and Dimension


2.1 Construction
Bus joints are solidly made by bolting the bus bars together with splice plates on each side. All joint surfaces are tin-plated or
silver-plated to ensure maximum conductivity through the joint.
After bolting, each standard joint is covered by a preformed, flame-retardant insulating bolt-nut boots so that it can provide full
insulation for bus conductors (5 kV and above). These boots are easily removable for inspection of the joints at any future time.
The copper bus bars are mounted on supports of track resistant, flame-retardant reinforced epoxy support. If boots are not
available for connection, taping the joint will be required.

Detail Construction

2.2 Technical data


Impulse
Rated Max.

Power frequency

Short-circuit
Rated

withstand
voltage

withstand voltage

withstand

current (kArms), 2sec.

current

continuous
1.250

(kVrms)

Short-circuit
Short-circuit withstand

(kVrms), 60Hz

withstand current

current (A)

(kArms asym.)

(kVpeak)
0.635 and

19

(kApeak)

60
630~1000

104

54

130(170)

67(87)

170(208)

87(106)

4.76
1250~2000
15

36

95

27

60

125

2500~5000

* More detail current ratings show Clause 2.3


* ( ) of short-circuit current can perform in case reinforce.(optional)
* IEC Standard class can apply 7.2, 12, 24kV
* Applied standard : IEEE C37.23

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

50(65)

165.244.42.57 / 2011.02.10 13:24 / 20090273

2.3 Dimension data


1) Rated voltage : 0.635kV ~ 4.76 kV (IEC :

upto 7.2 kV)

Cross-sections

Aluminum conductor
Current

Busbar size

Total Size [mm]

Earth bar

Resistance

Reactance

Impedance

Weight [kg/m]

S [mm]
(A)

[mm]

[mm]

[/m-1]

(/m-1)

(/m-1)

Al Housing

630

6*75

416

280

6.35*41

81.87

145.26

166.74

25.1

40.8

800

6*75

416

284

6.35*41

81.87

145.26

166.74

25.1

40.8

1000

6*102

416

312

6.35*41

61.12

125.93

139.98

26.8

43.1

1250

10*100

416

310

6.35*41

39.55

124.43

130.56

31.9

48.1

1600

10*145

416

355

6.35*41

28.39

102.82

106.67

36.2

53.4

2000

10*180

416

390

6.35*41

23.52

90.9

93.89

39.5

57.5

2500

12*245

416

455

6.35*41

15.62

74.51

76.13

49.6

69.1

3200

2*12*176

932

531

6.35*41

11.43

84.15

84.92

77.9

106.7

6.35*41

8.19

65.06

65.57

95.6

126.1

Earth bar

Resistance

Reactance

Impedance

80

Fe Housing

140
4000

2*12*260

932

615

Copper conductor
Current

Busbar size

Total Size [mm]

Weight [kg/m]

S [mm]
(A)

[mm]

[mm]

[/m-1]

(/m-1)

(/m-1)

Al Housing

630

6*67

416

277

6.35*41

57.29

152.45

162.86

32.1

47.6

800

6*67

416

277

6.35*41

57.29

152.45

162.86

32.1

47.6

1000

6*67

416

277

6.35*41

57.29

152.45

162.86

32.1

47.6

1250

6*96

416

306

6.35*41

41.09

129.7

136.05

37.1

53.3

Fe Housing

80
1600

10*95

416

305

6.35*41

26.96

127.49

130.31

47.1

63.2

2000

10*133

416

343

6.35*41

20.2

107.74

109.62

59.8

76.7

2500

12*168

416

378

6.35*41

14.43

93.82

94.92

78.5

96.3

3200

12*237

416

447

6.35*41

10.77

76.12

76.88

101.6

120.9

4000

2*12*180

932

615

6.35*41

7.48

82.98

83.32

160.4

190.9

140

* Bus temperature : 80.


* LV busduct(0.635kV and below), engineering plastic supports are applied. MV busduct (above 0.635kV), epoxy supports are available

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

165.244.42.57 / 2011.02.10 13:24 / 20090273

2) Rated voltage : 15 kV (IEC - 12 kV)

Aluminum conductor
Current

Busbar size

Total Size [mm]

Earth bar

Resistance

Reactance

Impedance

Weight [kg/m]

S [mm]
(A)

[mm]

[mm]

[/m-1]

[/m-1]

[/m-1]

Al Housing

630

6*65

656

420

6.35*41

94.02

190.96

212.85

34.6

55.8

800

6*65

656

420

6.35*41

94.02

190.96

212.85

34.6

55.8

1000

6*87

656

442

6.35*41

71.04

171.53

185.96

36.0

57.6

1250

10*84

656

439

6.35*41

46.38

170.65

176.84

38.5

60.1

1600

10*125

656

480

6.35*41

32.37

145.26

148.82

42.5

64.9

2000

12*150

656

505

6.35*41

23.77

132.82

134.93

47.4

70.2

2500

12*213

656

568

6.35*41

17.6

111.54

112.92

54.5

78.6

3200

2*12*176

932

531

6.35*41

11.43

84.15

84.92

77.9

106.7

4000

2*12*260

932

615

6.35*41

8.19

65.06

65.57

95.6

126.1

Earth bar

Resistance

Reactance

Impedance

140

Fe Housing

Copper conductor
Current

Busbar size

Total Size [mm]

Weight [kg/m]

S [mm]
(A)

[mm]

[mm]

[/m-1]

[/m-1]

[/m-1]

Al Housing

630

6*65

656

420

6.35*41

58.94

190.96

199.85

41.8

63.0

800

6*65

656

420

6.35*41

58.94

190.96

199.85

41.8

63.0

1000

6*65

656

420

6.35*41

58.94

190.96

199.85

41.8

63.0

1250

6*72

656

427

6.35*41

53.55

184.16

191.79

43.1

64.4

1600

10*80

656

435

6.35*41

31.36

173.76

176.57

53.0

74.5

2000

10*112

656

467

6.35*41

23.39

152.26

154.05

62.1

84.2

2500

12*145

656

500

6.35*41

16.36

134.92

135.91

79.2

101.9

3200

12*203

656

558

6.35*41

12.26

114.39

115.05

98.7

122.6

4000

2*12*180

932

535

6.35*41

7.48

82.98

83.32

159.1

188.0

140

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

Fe Housing

165.244.42.57 / 2011.02.10 13:24 / 20090273

3) Rated voltage : 27 kV (IEC - 24 kV)

Aluminum conductor
Current

Busbar

Total Size [mm]

Earth bar

Resistance

Reactance

Impedance

[mm]

[/m-1]

[/m-1]

[/m-1]

Weight[kg/m]

S [mm]
(A)

size [mm]
W

Al Housing

Fe Housing

630

6*61

942

546

6.35*41

94.02

222.95

241.96

44.3

73.7

800

6*61

942

546

6.35*41

94.02

222.95

241.96

44.3

73.7

1000

6*81

942

566

6.35*41

79.83

211.45

226.02

45.1

74.7

1250

10*78

942

563

6.35*41

49.67

207.11

212.98

47.7

77.3

1600

10*111

942

596

6.35*41

35.99

183.93

187.42

50.9

81.2

2000

12*134

942

619

6.35*41

26.2

170.41

172.41

55.3

86.0

2500

12*187

942

672

6.35*41

19.66

148.66

149.95

61.3

93.1

3200

2*12*146

1242

631

6.35*41

13.44

120.31

121.06

78.7

115.6

4000

2*12*235

1242

720

6.35*41

8.95

92.26

92.69

97.5

136.1

Earth bar

Resistance

Reactance

Impedance

220

Copper conductor
Current

Busbar

Total Size [mm]

Weight[kg/m]

S [mm]
(A)

size [mm]

[mm]

[/m-1]

[/m-1]

[/m-1]

Al Housing

630

6*65

942

550

6.35*41

58.94

222.95

230.61

51.6

80.9

800

6*65

942

550

6.35*41

58.94

222.95

230.61

51.6

80.9

1000

6*65

942

550

6.35*41

58.94

222.95

230.61

51.6

80.9

1250

6*72

942

557

6.35*41

53.55

216.32

222.56

52.8

82.3

1600

10*74

942

559

6.35*41

33.6

210.53

213.19

61.1

90.6

2000

10*102

942

587

6.35*41

25.35

189.52

191.21

69.0

99.1

2500

12*126

942

611

6.35*41

18.4

174.44

175.41

82.5

113.1

3200

12*180

942

665

6.35*41

13.59

151.44

151.75

100.7

132.3

4000

2*12*152

1242

637

6.35*41

8.66

117.83

118.15

147.8

184.8

220

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

Fe Housing

165.244.42.57 / 2011.02.10 13:24 / 20090273

3. Fittings
MV Busduct has a complete range of fittings to satisfy all lay-out conditions. Angles other than 90 are available. Fittings
designations are shown in the following figures and are based on the source-side and the load-side of the device. Offset and
combination elbows are used where standard elbows are not feasible.

1) Elbow fitting

Horizontal Elbow

Vertical Elbow

2) Offset

Horizontal Offset

3) Combination Elbow-Fittings

4) Tee-fittings

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

Vertical Offset

165.244.42.57 / 2011.02.10 13:24 / 20090273

4. Installation diagram

5. joint sealing
Final cover

Joint cover

Gasket
Joint cover

Final cover

<Indoor type>

LS Cable Ltd. user license only, These documents are property of LS Cable Ltd.

<Outdoor type>