Atelier Management and Design Consultancy (Vietnam) Co.

, Ltd

SEL9-MO O! S A! E!S"#

SECTION 9: MOTOR STARTERS 9.1 9.1.1 GENERAL Functional description Motor starters covers the scope of work for the electrical control of all electrical motors. 9.1.2 Cross references General Comply with the General requirements worksection. Related worksections Refer to the following worksections: Electrical General Requirements, Electrical Commissioning 9.1. !tandard General "o "C#$ 2%&1991'2(&1991. "C#$ 2%&1991 )iring Rules 9.1.* +nterpretations De initions Rated currents: Rated currents are continuous uninterrupted current ratings within the assem,ly environment under in-service operating conditions. 9.! 9.2.1 "#ALIT$ !u,missions General !u,mit data certificates for components. 9.% 9. .1 MATERIAL .lternating current start motors Selection /rovide direct on-line starters less for less than % k) motors. /rovide star-delta starters for greater than %.0 k) motors. Mini&'& rated (al'es Rated operational current: "he full load current of the load controlled. Switchboard Components, Switchboards,

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S"$

Rated duty: +ntermittent class 0.1. 1tilisation category: .C- . Mechanical endurance: . 9. .2 $irect-on-line starters General !tandard: "o "C2 20&193*. "ype: $irect-switching electromagnetic contactor. 4verload protection: "hermal overload unit giving overload protection in each phase of supply. 9. . Reversing starters General Comply with Direct)on)line starters and the following: 2 main line contactor5 mechanically and electrically interlocked to prevent simultaneous closure. "riple pole thermal overload relay. "ime delay relay with nominal 0 6 plugging of the motor. 8mergency stop push-,utton. 9. .* Multi-speed starters General Comply with Direct)on)line starters and the following: Mechanically and electrically interlocked. "ime delay relay with nominal 0 6 0 s ad7usta,le time delay. !eparate thermal overload protection for each speed configuration. 9. .% !tar-$elta starters General !tandard: "o "C2 20&193*. Controlgear: /rovide electromagnetically operated controlgear incorporating the following: Main line contactor or e9uivalent. !tar and delta contactors mechanically and electrically interlocked to prevent simultaneous operation. "riple pole thermal overload relay5 fitted to line contactor. +f overload is 0 s ad7usta,le time delay5 to prevent

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S"%

connected into motor phase winding circuits5 provide a name plate fi:ed to starter5 stating full load current of motor phase winding. "ime delay relay with nominal 0 6 star to delta switching contactors. 9. .; <aria,le speed drive controllers Standard "o "C2 20&193*. General /rovide high efficiency5 varia,le motor controllers. 2ote re9uirement for main line contactors = line filtering for all <!$s5 unless otherwise approved. T*+e >eneral: Microprocessor designed5 solid state electronic type5 providing motor speed control of phase s9uirrel cage induction motors ,y means of varia,le fre9uency5 stepless sine wave output. Controller: 4ffering speed ranges suita,le for the load duties. O+eratin, te&+erat'res 8nsure sta,le operation under the following operating temperatures: Full load: %0oC ?ma:imum@ am,ient for continuous full load operation. 2ormal range: -10 to A %0oC. Selection !elect to suit full load current stated on motor nameplate. C-aracteristics Bocal operator panel: /rovide facilities for local display and control5 including indication of run condition5 motor speed or output fre9uency5 input control parameters5 output current and voltage5 and alarm conditions' light emitting diode indication of power on5 Cero speed5 ena,le5 earth fault5 short circuit5 over current5 under voltage5 over temperature and remote trip' facilities for automaticDoffDmanual control' local and remote analog input5 to control fre9uency output of controller when in manual or automatic mode' and for remote control5 interfaces for analog input and output associated with speed control5 startDstop5 and voltage free contacts for alarm fault indication. !afety protection: +nclude protection against the following: +nstantaneous power failure. +nstantaneous over current. 0 s ad7usta,le time delay5 to control the

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S"&

+nternal and e:ternal overload. 1nder and over voltage. 4ver temperature of the controller. 8arth fault. Contact with live parts with door open. $esign: /rovide the following: !oft start ?initially start motors on low speed@. .d7usta,le ma:imum current limit. Radio fre9uency suppression5 harmonic and line transient filtering. .utomatic resetDrestart of system after removal of fault or power failure condition. +f the num,er of resetDrestart attempts is limited for safety and e9uipment protection5 provide for safe shut down and manual restart in the event of an unsuccessful attempt to resetDrestart. .,ility to immediately restart a motor following momentary interruption of supply5 even if the motor is rotating. Main line contactors. Enclos're +nstall each controller5 together with associated e9uipment5 in separate ventilated su,sections with hinged door or forced fan ventilated with air filtering as necessary5 meeting the level of separation for the overall enclosure. 9. .( Motor protection General /rovide over-current protection as part of the e9uipment assem,ly for each motor starter. T-er&al o(erload +rotection rela*s !tandard: "o "C2 20&193*. Construction: Comply with Current transformers (protection) 5 in the Switchgear accessories su,section. For phase operation provide triple pole relays with differential trip ,ar operation for single phase protection5 and am,ient temperature compensation. /rovide the following: 4ne normally-open and one normally-closed set of au:iliary contacts with minimum operational current of * . at 2*0 < a.c. "hermal overloads connected directly to contactor ,y means of proprietary links5 e:cept where operated separately ,y current transformers. Current transformers to operate protection type thermal overloads5 saturating at 10 - 1% : full load current5 Class 10/. Mounting: 8nsure relays are not affected ,y the shock of mechanical contactor operation. /rovide sufficient clear space for the disconnection5 removal and

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S"'

replacement of heaters5 without disconnecting other e9uipment and wiring. Reset: Manual. Sin,le +-ase &otor +rotection Comply with T-er&al o(erload +rotection rela*s and provide overload units matching the motor heating curve characteristics. % +-ase &otor +rotection /rovide thermal overload protection relays for each motor5 or select one of the following: "hermistor overload relay with thermal overload relay. 8lectronic motor protection relay. /rogramma,le electronic motor protection relay. T-er&istor +rotection rela*s !tandard: "C2 20&193*. "hermistor control unit: Compati,le with thermistor installed in the motor. Contacts: /rovide at least one normally-open and one normally-closed set of contacts rated at the starter control circuit voltage and minimum * .. Connect contacts to open the starter at the setting temperature. 1tilisation category: .C-11. "ype: .utomatic reset following power failure. .rrange the circuit so that thermistor failure5 failure of other control system components5 or e:cessive winding temperature5 causes the motor circuit to trip. Reset: Manual5 to restore the motor circuit when tripped due to e:cessive winding temperature. Bight emitting diode indication: /rovide on the thermistor control unit5 to indicate that circuit is in normal operating mode. Electronic &otor +rotection rela*s !tandard: "C2 20&193*. Characteristics: /rovide the following: !ingle phasing protection and phase se9uence protection. "hermal overload protection. Boss of load protection. 8:cessive motor run-up and stall protection. 8arth fault protection. .d7usta,le settings conditions. of protection parameters: B8$ indication of fault

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S"(

Manual reset. 4ne normally-open and one normally-closed set of au:iliary contacts with minimum current rating of * . at 2*0 < a.c. Facilities for relay testing. C'rrent trans or&ers Comply with Current transformers (protection)5 in the Switchgear accessories su,section. !aturating at 10 - 1% : full load current5 Class 10/. /rovide ad7ustment facilities allowing matching of current transformer characteristics. .ro,ra&&a/le electronic &otor +rotection rela*s Characteristics: /rovide the following: /rogramma,le micro-processor ,ased protection: Comply with Electronic &otor +rotection rela*s. $iagnostic data gathering and retrieval to determine the cause of shut-down. +nterrogation and display of data to give actual running conditions at time of interrogation. 2on-volatile memory retaining program and data upon loss of power. R!*22 communications port. /rogramming key pad. !oftware for communications with +EM-compati,le personal computers. 9.0 9.*.1 COM.LETION "raining .ro,ra&&a/le lo,ic controllers Make availa,le one programmer and su,mit associated instruction manual % days ,efore start of operator training. 9.*.2 !pares Tools .ccessories: !upply one set of racking tools for circuit ,reakers5 and special installation5 operation and servicing tools. +ndicator lights: /rovide spare lamps and one lamp e:tractor per 10 indicating lights. Bocate in spares ca,inet. .larm annunciators: /rovide spare lamps5 lamp remover5 screen remover ?if applica,le@5 mounted on clips in the assem,ly enclosure or in spares ca,inet. 9.*. Completion tests General Carry out the following tests:

Atelier Management and Design Consultancy (Vietnam) Co., Ltd

SEL9-MO O! S A! E!S")

8lectrical operation. $ielectric. 9.*.* Maintenance General >eneral: Carry out the following: Monthly inspections and maintenance work to maintain the assem,ly5 including ,attery systems. Rectify faults5 make ad7ustments5 and replace consuma,le and faulty materials and e9uipment within 2* hours of notification. !tandard: "o "C2 20&193*'"C#$ 2%&1991' 2(&1991.