Escolar Documentos
Profissional Documentos
Cultura Documentos
\
|
+ =
C = design concentration (%)
S
AIR
= specific vapour volume of air given by :-
S
AIR
= K1 + K2 * T
K1 = 0.773824
K2 = 0.002832967
T = Temperature in degrees C
Where
|
.
|
\
|
|
.
|
\
|
=
C 100
100
l n * Q
R
S
S
R
S
R
= specific reference volume of extinguishant at the reference filling temperature and at 1.013 bar (cubic
metres/ cubic metres)
Q
R
= the quantity in cubic metres of extinguishant required at the reference temperature and at a pressure of
1.013 bar.
Example Calculations for Inert Gases (values taken from BS EN 15004)
Note : in these examples peak discharge percentage relates to the stored quantity of gas
IG-55 @ 20
o
C
Temperature 20
o
C
S (IG-55) 0.7081 m
3
/kg
S
AIR
0.8305 m
3
/kg
13 of 25
Guidance on Venting of Gas Systems_Issue2
S
H
0.7752 m
3
/kg
P 500 Pa
Volume 260m
3
Design Concentration 45.2%
Flooding factor 0.8494 kg/m
3
Amount of gas required 220.84 kg
Number of containers holding 32.09kg (80 litre 300 bar) 7
Actual gas flowing 224.63 kg
Total vent area required assuming vent co-efficient of 1:
1. Peak discharge at 3%, 60 second discharge (6.74 kg/s) 0.243 m
2
2. Peak discharge at 1.5%, 120 second discharge (3.37 kg/s) 0.122 m
2
3. Constant discharge, 60 second discharge (3.744 kg/s) 0.135 m
2
IG-100 @ 5
o
C
Temperature 5
o
C
S (IG-100) 0.8143 m
3
/kg
Design Concentration 40.3%
S
AIR
0.7880 m
3
/kg
S
H
0.7986 m
3
/kg
P 250 Pa
Volume 530m
3
Flooding factor 0.6335 kg/m
3
Amount of gas required 335.73 kg
Number of containers holding 24.88kg (80 litre 300 bar) 14
Actual gas flowing 348.32kg
Total vent area required:
1. Peak discharge at 4%, 60 second discharge (13.93 kg/s) 0.803 m
2
2. Peak discharge at 2%, 120 second discharge (6.97 kg/s) 0.402 m
2
3. Constant discharge, 60 second discharge (5.80 kg/s) 0.334 m
2
IG-541 @ 35
o
C
Temperature 35
o
C
S (IG-541) 0.7416 m
3
/kg
Design Concentration 39.9%
S
H
0.8206 m
3
/kg
S
AIR
0.8730 m
3
/kg
P 350 Pa
Volume 435m
3
Flooding factor 0.691 kg/m
3
Amount of gas required 300.79 kg
Number of containers holding 57.39kg (140 litre 300 bar) 6
Actual gas flowing 344.34kg
Total vent area required:
14 of 25
Guidance on Venting of Gas Systems_Issue2
1. Peak discharge at 2.5%, 60 second discharge (8.61 kg/s) 0.376 m
2
2. Peak discharge at 1.25%, 120 second discharge (4.3 kg/s) 0.188 m
2
3. Constant discharge, 60 second discharge (5.74 kg/s) 0.252 m
2
Carbon Dioxide at 0
o
C
Temperature: 0
o
C
S (CO
2
) 0.505 m
3
/kg
Design Concentration 34%
S
H
0.6824 m
3
/kg
S
AIR
0.7738 m
3
/kg
P 100 Pa
Volume 375m
3
Flooding Factor 0.8 kg/m
3
Amount of gas required 300 kg
Number of containers holding 50kg 6
Actual Gas Flowing 300 kg
Total Vent Area Required:
Constant discharge, 60 second discharge (5 kg/s) 0.306 m
2
6.8.2 Total vent area requirements (liquefiable gases)
The US based Fire Suppression Systems Association (FSSA) have issued a Guide to Estimating Enclosure Pressure
and Pressure Relief Vent Area for Applications Using Clean Agent Fire Extinguishing Systems. This guidance has
been based upon experimental data attained via collaboration with various industry participants, including a
number of multinational organisations.
The FSSA work is by far the most in-depth investigation to-date, on the estimation of enclosure pressure and total
vent area requirements.
Due to the unique status of the FSSA Guidance at this juncture, together with the backing of appropriate
experimental data, the same calculation methodology for halocarbon extinguishants is used within this FIA
guidance document. It should be noted, that the form of the equations have been consolidated into a single
expression and to represent SI units.
The calculation methodology provides means to estimate the pressure excursion expected for a specified
extinguishing agent and to estimate the required vent size in order to limit the maximum and minimum pressure
within the enclosure.
The following input parameters are required to use the calculation methodology:
- Extinguishing agent
- Protected enclosure volume
- Extinguishing system discharge time
- Extinguishing concentration
- Relative humidity of enclosure
If the enclosure strength is known it is possible to calculate the required total vent area.
15 of 25
Guidance on Venting of Gas Systems_Issue2
If the total vent area is known then it is possible to calculate the expected pressure excursion following an
extinguishing system discharge.
Parameter Unit Definition
+vePE Pa Positive Pressure Excursion
-vePE Pa Negative Pressure Excursion
TotalVentArea m
2
the sum of the free vent area and the natural leakage area
Volume m
3
Protected enclosure volume
Conc % Suppressant concentration used in the protected enclosure
t
d
s Gaseous fire fighting system discharge time
%RH % Relative humidity within the enclosure
+veEPL Pa Enclosure positive pressure limit
-veEPL Pa Enclosure negative pressure limit
+veFVA m
2
Positive free vent area required to ensure that the positive pressure excursion
is below the enclosure positive pressure limit (+veEPL)
-veFVA m
2
Negative free vent area required to ensure that the negative pressure
excursion is below the enclosure negative pressure limit (-veEPL)
CAUTION: The magnitude of both +veEPL and veEPL for each extinguishant have limits of applicability. The
calculation methodology is based on experimental data and therefore the prediction of the calculation tool must
remain within the data envelope investigated. Calculations based on parameters outside the limits of applicability
will not be accurate and it is strongly advised that such calculations are treated accordingly.
If the relative humidity level is not known, 50% is the recommended value to use.
FK-5-1-12 : Limits of applicability:
6s t
d
10s
4.2% Conc 6.0%
20% RH% 80%
+veEPL 240Pa
-veEPL -1200Pa
Pressure Excursion for FK-5-1-12
+vePE |
.
|
\
|
- + - |
.
|
\
|
- - =
100
%RH
0.51 0.81
Conc
t
Volume
rea TotalVentA
0.042649
1.0334
d
Equ. 1
-vePE |
.
|
\
|
- - |
.
|
\
|
- - =
100
%RH
1.79 - 1.68
Conc
t
Volume
rea TotalVentA
0.32170
1.0318
d
Equ. 2
Total Vent Area for FK-5-1-12
Positive
Total Vent Area
0.9677
d
100
%RH
0.51 0.81
veEPL
Volume
t
Conc
0.04678
|
|
|
|
.
|
\
|
- +
+
- -
|
|
.
|
\
|
- =
Equ. 3
16 of 25
Guidance on Venting of Gas Systems_Issue2
Negative
Total Vent Area
0.9692
d
100
%RH
1.79 1.68
veEPL
Volume
t
Conc
0.34309
|
|
|
|
.
|
\
|
-
- -
|
|
.
|
\
|
- =
Equ. 4
HFC-227-ea : Limits of applicability:
6s t
d
10s
6.25% Conc 10.5%
20% RH% 80%
+veEPL 380Pa
-veEPL -1000Pa
Pressure Excursion for HFC-227-ea
+vePE |
.
|
\
|
- + -
|
|
.
|
\
|
|
|
.
|
\
|
-
-
- - =
100
%RH
0.51 0.81 27.922
t rea TotalVentA
Conc Volume
ln 4.2 48.359
d
Equ.5
-vePE |
.
|
\
|
- -
|
|
.
|
\
|
|
|
.
|
\
|
-
-
- - =
100
%RH
1.79 - 1.68 62.76
t rea TotalVentA
Conc Volume
ln 9.41 46.444
d
Equ. 6
Total Vent Area for HFC227-ea
Positive
Total Vent Area
|
|
|
|
.
|
\
|
- +
+ -
- -
|
|
.
|
\
|
- =
100
%RH
0.51 0.81
veEPL 0.00497
exp Volume
t
Conc
0.00130
d
Equ. 7
Negative
Total Vent Area
|
|
|
|
.
|
\
|
-
-
- -
|
|
.
|
\
|
- =
100
%RH
1.79 1.68
veEPL 0.00222
exp Volume
t
Conc
0.00127
d
Equ. 8
HFC-23 : Limits of applicability:
6s t
d
10s
18% Conc 30%
20% RH% 80%
+veEPL -1400Pa
Pressure Excursion for HFC-23
+vePE |
.
|
\
|
- + - |
.
|
\
|
- - =
100
%RH
0.51 0.81
Conc
t
Volume
rea TotalVentA
0.08827
1.165
d
Equ. 9
Total Vent Area for HFC-23
Positive Total
Vent Area
0.8587
d
100
%RH
0.51 0.81
veEPL
Volume
t
Conc
0.12384
|
|
|
|
.
|
\
|
- +
+
- -
|
|
.
|
\
|
- =
Equ. 10
HFC-125 : Limits of applicability:
6s t
d
10s
8.0% Conc 10.5%
20% RH% 80%
17 of 25
Guidance on Venting of Gas Systems_Issue2
+veEPL 480Pa
-veEPL -480Pa
Pressure Excursion for HFC125
+vePE |
.
|
\
|
- + - |
.
|
\
|
- - =
100
%RH
0.51 0.81
Conc
t
Volume
rea TotalVentA
0.045349
1.037
d
Equ. 11
-vePE |
.
|
\
|
- - |
.
|
\
|
- - =
100
%RH
1.79 - 1.68
Conc
t
Volume
rea TotalVentA
0.03949
1.039
d
Equ. 12
Total Vent Area for HFC125
Positive
Total Vent Area
0.964
d
100
%RH
0.51 0.81
veEPL
Volume
t
Conc
0.050
|
|
|
|
.
|
\
|
- +
+
- -
|
|
.
|
\
|
- =
Equ. 13
Negative
Total Vent Area
0.9622
d
100
%RH
1.79 1.68
veEPL
Volume
t
Conc
0.04589
|
|
|
|
.
|
\
|
-
- -
|
|
.
|
\
|
- =
Equ. 14
Example Calculation 1:
Protected Enclosure
Volume = 125m
3
Air Conditioned 50%RH
Room Strength = 500Pa
Total Vent Area = 0.042m
2
Extinguishing System
Agent = HFC227ea
Concentration = 8.5vol%
System Discharge time = 9.2s
Calculate the expected pressure excursion following the discharge of the extinguishing system:
Select the HFC227ea equation (Equ.5 ) for positive pressure excursion (+vePE)
+vePE |
.
|
\
|
- + -
|
|
.
|
\
|
|
|
.
|
\
|
-
-
- - =
100
%RH
0.51 0.81 27.922
t rea TotalVentA
Conc Volume
ln 4.2 48.359
d
Equ. 15
+vePE |
.
|
\
|
- + -
|
|
.
|
\
|
|
.
|
\
|
-
-
- - =
100
50
0.51 0.81 27.922
9.2 0.042
8.5 125
ln 4.2 48.359
Equ. 16
+vePE ( ) ( ) ( ) 065 . 1 922 . 27 2750 ln 2 . 4 359 . 8 4 - - - =
Equ. 17
+vePE ( ) ( ) ( ) 065 . 1 922 . 27 919 . 7 2 . 4 359 . 8 4 - - - =
Equ. 18
+vePE ( ) ( ) 065 . 1 339 . 5 359 . 8 4 - - =
Equ. 19
+vePE +275 Pa Equ. 20
Select the HFC227ea equation ( Equ. 6) for negative pressure excursion (-vePE)
-vePE |
.
|
\
|
- -
|
|
.
|
\
|
|
|
.
|
\
|
-
-
- - =
100
%RH
1.79 - 1.68 62.76
t rea TotalVentA
Conc Volume
ln 9.41 46.444
d
Equ. 21
18 of 25
Guidance on Venting of Gas Systems_Issue2
-vePE |
.
|
\
|
- - |
.
|
\
|
|
.
|
\
|
-
-
- - =
100
50
1.79 - 1.68 62.76
9.2 0.042
8.5 125
ln 9.41 46.444
Equ. 22
-vePE ( ) ( ) ( ) 0.785 62.76 2750 ln 9.41 46.444 - - - =
Equ. 23
-vePE ( ) ( ) ( ) 0.785 62.76 7.919 9.41 46.444 - - - =
Equ. 24
-vePE ( ) ( ) 0.785 11.758 46.444 - - =
Equ. 25
-vePE -429Pa Equ. 26
19 of 25
Guidance on Venting of Gas Systems_Issue2
Example Calculation 2:
Protected Enclosure
Volume = 7500m
3
Air Conditioned 50%RH
Room Strength = 500Pa
Extinguishing System
Agent = HFC227ea
Concentration = 7.9vol%
System Discharge time = 9.6s
Calculate the expected required free vent area following the discharge of the extinguishing system:
Select the HFC227ea equation (Equ. 7) for positive total vent area such that the enclosure positive pressure limit
is not exceeded. A key point here, is that the limit of applicability for the +veEPL must be adhered; for HFC227ea
this limit is 380Pa and so this is entered into the calculation even though the enclosure can withstand 500Pa.
Positive
Total Vent Area
|
|
|
|
.
|
\
|
- +
+ -
- -
|
|
.
|
\
|
- =
100
%RH
0.51 0.81
veEPL 0.00497
exp Volume
t
Conc
0.00130
d
Equ. 27
Positive
Total Vent Area
|
|
|
|
.
|
\
|
- +
-
- - |
.
|
\
|
- =
100
50
51 . 0 81 . 0
380 00497 . 0
exp 7500
9.6
7.9
0.00130
Equ. 28
Positive
Total Vent Area
( ) ( ) 773 . 1 exp 7500 0.8229 0.00130 - - - =
Equ. 29
Positive
Total Vent Area
1.363 m
2
Equ. 30
Select the HFC227ea equation (Equ. 8) for negative total vent area such that the enclosure negative pressure limit
is not exceeded.
Negative
Total Vent Area
|
|
|
|
.
|
\
|
-
-
- -
|
|
.
|
\
|
- =
100
%RH
1.79 1.68
veEPL 0.00222
exp Volume
t
Conc
0.00127
d
Equ. 31
Negative
Total Vent Area
|
|
|
|
.
|
\
|
-
-
- - |
.
|
\
|
- =
100
50
1.79 1.68
500 0.00222
exp 7500
9.6
7.9
0.00127
Equ. 32
Negative
Total Vent Area
( ) ( ) 1.414 exp 7500 0.8229 0.00127 - - - =
Equ. 33
Negative
Total Vent Area
1.906 m
2
Equ. 34
6.8.3 Natural leakage
When determining the overall vent area required, it may be acceptable to take into account the natural leakage
area. This natural leakage area is the equivalent leakage area (ELA) as determined by the room integrity test.
20 of 25
Guidance on Venting of Gas Systems_Issue2
NOTE : When the integrity test is conducted with doors held open in adjacent rooms to the room under test,
there could be less natural leakage available than may have been assumed from the ELA value. In such cases, if
natural leakage is to be used for pressure relief, the protected enclosure must be assessed and judgement applied
in deciding what proportion of the ELA is used as a contribution to the total vent area
6.9 Cascade venting calculations
Where the over-pressure venting for a gaseous fire fighting system needs to transit through one or more adjacent
enclosures in order to vent to atmosphere the vents in the enclosure boundaries should be determined as
follows:
V1
V3
AP14
A34
A13
V2
A12
A24
A
1
V4
AP34
AP13
AP12
AP24
V4
V4
21 of 25
Guidance on Venting of Gas Systems_Issue2
All volumes are in m
3
, all free vent areas are in m
2
, and all pressure differentials are in Pa. V1, V2, V3 and V4 are
all discrete enclosures; for explanatory purposes V1 is an enclosure protected by gaseous extinguishing systems,
V2 is an adjacent enclosure, V3 is a corridor and V4 is atmosphere.
A1 free vent area if the protected enclosure vented directly to atmosphere V4.
A12 free vent area from the protected enclosure V1 into the adjacent enclosure V2.
A24 free vent area from enclosure V2 to atmosphere V4.
A13 free vent area from the protected enclosure V1 into the adjacent enclosure V3.
A34 free vent area from the enclosure V3 to atmosphere V4
P14 pressure differential between V1 and V4. With V4 representing atmosphere, this will be equivalent to the
maximum allowable pressure in V1
P12 pressure differential between V1 and V2.
P14 pressure differential between V1 and V4.
P13 pressure differential between V1 and V3.
P34 pressure differential between V3 and V4.
When venting directly to the atmosphere from the protected space the pressure loss (differential) through the
free vent area A1 is P14. When the vent flow has to pass through two vents then the optimum design occurs
when the pressure differential is equal, i.e. P12 = P24. As a result A12 = A24 = 2 x A1. This is because, in order
to achieve the same flow with only half the pressure differential, the area of each vent must be 2 x A1 when
there are two vents in the flow path. Similarly the area of each vent must be 3 x A1, if there are three equally
sized vents in the flow path etc.
Of course any combination of pressure differentials can be used as long as the sum of differential pressures does
not exceed the maximum enclosure strength. To prevent flow and pressure oscillations through the enclosures,
only one of the vents in the flow path should be a flap type vent; the remainder should be actuated to remain
fully open during the venting process.
22 of 25
Guidance on Venting of Gas Systems_Issue2
Example Calculation 3:
Example - cascade venting calculations for IG541 (Peak Discharge)
Temperature 20
o
C
S (IG541) 0.70 m
3
/kg
S
air
0.830 m
3
/kg
Design concentration 40%
S
H
0.781 m
3
/kg
Enclosure 1 284 m
3
Flooding Factor 51%
IG541 Quantity 204 kg
Peak flow rate 2.5%
P14 maximum allowable pressure 500Pa
Venting directly to atmosphere:
P14 = 500Pa
A1 = 0.025 * 204 * 0.70
(500 * 0.781)
A1 = 0.182 m
2
Cascade venting through adjacent enclosure V2 vent size optimised
P12 = P23 = 250 Pa
A12 = A24 = 0.025 * 204 * 0.70
(250 * 0.781)
A12 = A23 = 0.258 m
2
; alternatively A1 can be multiplied by 2 in this optimised condition.
Cascade venting through adjacent enclosure V3 minimising size of vent in outside wall (A34).
P13 = 100 Pa
P34 = 400 Pa
A13 = 0.025 * 204 * 0.70
(100 * 0.781)
A13 = 0.407 m
2
A34 = 0.025 * 204 * 0.70
(400 * 0.781)
A34 = 0.204 m
2
23 of 25
Guidance on Venting of Gas Systems_Issue2
6.9.1 Cascade vent arrangements
Cascade venting is the means to vent from one area through one or more areas.; it is sometimes necessary should
the protected area be within another area, e.g. a computer room in the centre of a building rather than located
adjacent to an outside wall.
Cascade venting calculations need to determine intermediate pressures generated since these will affect the flow
of the exiting gases. This is equally applicable to flow through ducts.
As an example, the intermediate vent area is calculated with a lateral wall strength of 250Pa. The intermediate
pressure through the flow path is 125 Pa. In order to allow for this, the vent area calculation needs to be made on
125 Pa to achieve 250 Pa maximum differential. When calculating pressure losses through ducts pressure loss will
change with flows that change with the vent area, so an iterative process is required to get a more exact value.
Cascade vent arrangements, for the necessary design calculations and considerations above can be as follows:
1. Protected Area 1 to Protected Area 2 to atmosphere. Vent from Area 1 to Area 2, via a pre-opened vent,
i.e. electric or pneumatic, to atmosphere
2. Protected Area 1 to Protected Area 2 to any further protected area(s) to atmosphere. Vent from Area 1 to
Area 2, and then via pre-opened vents through any further protected area(s) and then to atmosphere
3. Protected Area 1 to atmosphere via duct work. Duct work and vents will need to be sized in accordance
with maximum lateral pressure and flow requirements.
6.9.2 Venting into adjacent enclosures
When a protected enclosure is required to have pressure relief venting fitted, and the vent path is into an
adjacent enclosure (i.e. cascade venting) it is important that the volume of the adjacent enclosure is large enough
such that the room strength is not compromised. This can be determined by the following methodology and
calculation.
V
1
is the volume (m
3
) of the enclosure (1) which employs a gaseous fire protection system and has pressure relief
fitted which connects it to an adjacent enclosure (2) of volume V
2
. If V
2
is not large enough to act as a reservoir
for flow of gas into or out of V
1
during a system discharge, then V
2
will also require pressure relief.
The following two sections detail how to determine the minimum size of V
2
such that pressure relief on V
2
is NOT
required.
6.9.2.1 Over-Pressurisation : Determination of adjacent enclosure volume
The basis for this methodology is that at equilibrium the pressure generated by the injection of extinguishant gas
into V
1
will balance across the pressure relief vent into V
2
. By taking the volume of extinguishant injected, and
calculating what volume is required for that extinguishant to exert +veEPL (differential pressure) over the
combined volume of V
1
and V
2
. For all gaseous fire fighting agents, the minimum size of an adjacent volume V
2
,
for over-pressurisation can therefore be determined by:
V
2
1
1
V
veEPL
325 101 V factor flooding
|
|
.
|
\
|
+
- -
Equ. 35
where the flooding factor is in cubic metres/cubic metres (reference BS EN 15004) and +veEPL is the lower of the
positive enclosure pressure limits (in Pa) for V
1
and V
2
.
The free vent area between V
1
and V
2
must be calculated as a cascade vent arrangement as described in Section
6.9.
24 of 25
Guidance on Venting of Gas Systems_Issue2
6.9.2.2 Under-Pressurisation : Determination of adjacent enclosure volume
For gaseous fire fighting agents that generate a negative pressure excursion during discharge (FK-5-1-12, HFC-
227ea, HFC-125) the minimum size of an adjacent volume V
2
, can be determined by:
V
2
Equ. 36
where veFVA is the free vent area (m
2
) between V
1
and V
2
based on a cascade arrangement (see Section 6.9), -
vePE
V1
is the negative pressure excursion in V
1
(Pa) and veEPL
V2
is the negative enclosure pressure limit for V
2
(Pa).
Example Calculation 4:
A 248 m
3
enclosure with a positive pressure limit of 500Pa is protected with an IG-55 inert gas suppression system
with an applied design concentration of 46vol% at 20 degrees C (flooding factor - 0.6057 m
3
/ m
3
)
6057 . 0
46 100
100
ln *
100
100
ln * Q
R
= |
.
|
\
|
|
.
|
\
|
= |
.
|
\
|
|
.
|
\
|
=
0.70812
0.69604
S
S
R
C
The over-pressure from this enclosure is to be vented into an adjacent enclosure of 20,000 cubic metres with a
positive pressure limit of 400Pa.
Determine whether or not this volume is of adequate size to ensure that the enclosure pressure limits are not
exceeded.
The free vent area required between the protected area and the adjacent enclosure must be determined under
the basis of cascade venting,
Using Equ. 35
Minimum volume of adjacent enclosure
248
400
248 325 101 0.6057
|
.
|
\
| - -
Equ. 37
Minimum volume of adjacent enclosure
37,803 m
3
Equ. 38
In this instance, the adjacent volume is not adequate on its own, and further pressure relief will be required on
the adjacent enclosure, calculated once again under the cascade venting premise.
Example Calculation 5:
An HFC227ea extinguishing system has been employed to protect a 248 m
3
enclosure with a pressure limit of
500 Pa at a design concentration of 8.0vol% at 20 degrees C and a discharge time of 9.5 seconds. The flooding
factor in cu.m/cu.m is 0.6335 kgs/cu.m multiplied by specific vapour volume at 20 degrees C of 0.1374 = 0.087
cu.m/cu.m. This enclosure is of particularly high integrity and so both under and over pressure relief has been
fitted and cascaded into an adjacent enclosure with a volume of 4,200m
3
and a pressure limit of 500 Pa. The
free vent area for the negative pressure excursion at 250Pa is 0.131m
2
(using Equ. 8 and a relative humidity of
50%).
Determine whether or not the adjacent enclosure is of adequate size to ensure that the enclosure pressure limits
are not exceeded.
Using Equ. 35 for the over-pressure calculation:
Minimum volume of adjacent enclosure
248
500
248 325 101 0.087
|
.
|
\
| - -
Equ. 39
Minimum volume of adjacent enclosure
4,124 m
3
Equ. 40
In this instance, the adjacent volume is of adequate size such that additional cascade venting is not required for
the over-pressure event.
Using Equ. 36 for the under-pressure calculation:
25 of 25
Guidance on Venting of Gas Systems_Issue2
Minimum volume of adjacent enclosure
Equ. 41
Minimum volume of adjacent enclosure
1,817 m
3
Equ. 42
In this instance, the adjacent volume is of adequate size such that additional cascade venting is not required for
the under-pressure event.
7. System Design - Post discharge venting
In protected enclosures means for prompt natural or forced-draft ventilation of areas after any system discharge
should be provided, to safely remove fire by-products and extinguishant (as per EN 15004-1 and ISO 14520-1).
Forced draft ventilation will often be necessary. Care should be taken to completely dissipate hazardous
atmospheres and not just move them to other locations. It should be noted that most extinguishants are heavier
than air.
8. Acceptance
During system handover procedures, checks should be made to ensure vents are :-
a) properly sited
b) correctly sized
c) free to operate
d) mounted for correct orientation
e) mounted for correct flow direction
f) free from internal and external obstructions in the flow path
g) functionally tested (in the case of electrically and pneumatically operated vents)
Gaseous systems should remain disabled unless and until vents have been fitted and the above checks completed.
9. Service and maintenance
During servicing and maintenance procedures (at least every six months) the following should be checked to
ensure vents are:-.
a) free to operate
b) free from internal and external obstructions in the flow path
c) functionally tested (in the case of electrically and pneumatically operated vents)
If natural leakage has been used as the means or as a contribution towards the total vent area and if any concerns
exist over changes to the natural vent area, a room integrity test should be performed.