Insulation Class Temperature Rise Maximum Temp of the Winding Ambient Temperature Allowance for Hot Spots
105 120 130 155 100 115 120 140 40 40 40 5 5 10 40 15 (10) 100 (105) 0
TEMPERATURE LIMITS The permitted temperature rise of the windings of an electric motor are subdivided into
http://www.bevi.dk/t_topics/tmp_insl.htm
11/5/2007
Page 2 of 3
different insulation classes and temperature limits. The above table applies for motors in an ambient temperature up to 40 degree C and an altitude of less than 1000 meters above sea level. The difference between the 'Maximum Temperature of the Winding' and the 'Temperature Limit' is because there will be hot spots in the winding which are not measured by the 'Resistance Method' which only measures the Mean Temperature of the whole winding. An Allowance is made for this difference to ensure that no part of the winding is operating at it's full thermal rating. It is not considered to be practical to try to locate and measure the hottest spot in a winding. The temperature rise of the winding is measured by the resistance method using the following formula: DT = (R2-R1) / * (235 + T1) + (T1 - T2) Where: DT=Temperature Rise in deg.K. R1 = Cold resistance of the Winding @ T1 R2 = Hot resistance of the Winding @ T2 T1 = Ambient @ Start up deg.C. T2 = Ambient @ Finish in deg.C. 235 = Reciprocal of the temperature Coefficient of the resistance of Copper at O deg.C. For a winding to comply with Class F insulation requirements all the materials must be to Class F specification or better. ADVANTAGES OF THERMAL RESERVE There are a number of advantages in buying motors with a thermal temperature reserve apart from an anticipated long service life. * Service Factor. This is really an American, (NEMA), term that is not covered in IEC standards. It means that the motor can be overloaded without serious damage of overheating. Typically NEMA specifications call for Service Factors of 1.1 or 1.15, meaning a 10% or 15% overload. Service Factor is in fact using up the thermal reserve of the motor and allowing it to operate at its full Class temperature rise. Although IEC does not acknowledge Service Factor in the same way it certainly allows motors to operate to their full class rating and in fact most motors with a generous thermal reserve will easily match the NEMA requirement for 1.1 or 1.15. Service Factor and duty rating, e.g. S1, S2, etc, should not be confused. Duty ratings are clearly covered in IEC standards for different repetitive short term overloads which can be defined and simulated to ensure the motor still meets the requirements for temperature rise. * Voltage of Frequency Variations. In some installations, especially with their own power generation, or a very weak grid, large fluctuations in voltage and/or frequency are possible, which can cause increases in the temperature rise of the motor. Motors with a
http://www.bevi.dk/t_topics/tmp_insl.htm
11/5/2007
Page 3 of 3
large thermal reserve can operate in these conditions usually without exceeding their Class rating by using some or all of their thermal reserve, depending on how large the fluctuation is.
Home
Company Profile
Products
F.A.Q's
Torque Topics
Contact Info
http://www.bevi.dk/t_topics/tmp_insl.htm
11/5/2007