Escolar Documentos
Profissional Documentos
Cultura Documentos
1. APPLICATIONS
Photovoltaic power supply of
- power plants of remote villages, huts in the mountains.
- signal installations of the air-, sea-, road- and railway transport
- radio relay stations of telecommunication services, cellular phone stations
Hybrid power supply (photovoltaic, wind generator and Diesel engine): In these cases the battery serves to buffer load peaks, to smooth the current
and to reduce the operation time of Diesel engines at low power demand.
2. TECHNICAL DATA
C 100
C 20
C 10
C5
C1
Ri
Ik
mass
dimensions
Ah
Ah
Ah
Ah
Ah
kA
kg
m x mm x mm
Ue 80%
1,91V
1,91V
1,90V
1,87V
1,74V
Ue 100%
1,80V
1,80V
1,80V
1,77V
1,67V
12V 1 OPzS 50
72
60
51
41,5
28,5
19,2
0,64
40
145
120
103
84
56,5
9,60
1,28
51
215
180
154
125
85
6,40
1,92
71
6V 4 OPzS 200
335
240
205
167
115
2,40
2,56
48
6V 5 OPzS 250
360
300
256
208
143
1,92
3,20
62
6V 6 OPzS 300
430
360
308
250
172
1,60
3,84
69
LxBxH
C 20
C 10
C5
page 2
C1
Ri
Ik
mass
dimensions
kA
kg
mm x mm x mm
Ah
Ah
Ah
Ah
Ah
Ue 80%
1,91V
1,91V
1,90V
1,87V
1,74V
Ue 100%
1,80V
1,80V
1,80V
1,77V
1,67V
4 OPzS 200
290
225
210
175
114
0,95
2,16
17,2
5 OPzS 250
370
305
270
220
143
0,76
2,70
20,8
6 OPzS 300
440
365
320
262
170
0,63
3,24
24,3
5 OPzS 350
550
455
400
336
205
0,70
2,90
26,9
6 OPzS 420
680
560
490
400
245
0,58
3,48
31,5
7 OPzS 490
790
650
570
470
285
0,50
4,06
36,1
6 OPzS 600
930
760
670
560
330
0,47
4,32
44,8
LxBxH
8 OPzS 800
1230
1020
890
740
440
0,35
5,76
61,3
10 OPzS 1000
1550
1280
1120
930
550
0,28
7,20
74,5
12 OPzS 1200
1860
1530
1340
1100
660
0,23
8,64
88
12 OPzS 1500
2350
1930
1690
1400
820
0,23
9,18
114,3
16 OPzS 2000
3130
2580
2250
1850
1100
0,17
12,2
151,5
20 OPzS 2500
3900
3220
2810
2300
1375
0,14
15,3
193,0
24 OPzS 3000
4700
3870
3380
2800
1640
0,11
18,4
234,5
16 OPzS 2000
80%
70%
60%
50%
40%
30%
20%
10%
Cycles OPzS-cell
1500
1700
2000
2400
3000
4000
5000
10000
1200
1350
1600
1900
2400
3200
4000
8000
20C
15C
10C
5C
0C
-5C
-10C
-20C
C100
100%
98%
94%
90%
85%
79%
72%
55%
5. Operation
At lower voltages as U80% the battery has to be disconnected to avoid a damage of the battery.
The charging current may vary from 5 x I10 to 0,01 x I10. The charging voltage has to be restricted to 2,30V to 2,40V.
At daily discharge below 0,2 C100
2,30V - 2,35V
2,35V - 2,40V
At higher daily discharges a not acceptable electrolyte stratification occurs, if not regularly gassing charging is applied or BAE OPzS EU - cells (with
electrolyte agitation) are used.