protection
presentation outline
Definition
Connection
Operation
Advantages
Limitations
Bias calculation
C.T. saturation problem
Magnetizing inrush current problem
Diff. protection of three phase transformers
1.0 Definition
protection
opposed current differential protection
3.0 Operation
assume: two identical current transformers
( i1=i2) relay off ((external fault or no fault))
( i1≠i2 ) relay on (( internal fault ))
4.0 Advantages
1.the operation is reliable
2.absolute discrimination (i.e.) if
there is an external fault tripping
never done
3.can be instantaneous or be
adjusted
4.No P.T.’s are needed
5.it’s used for any equipment
6.it operate for all types of fault
wither to earth or bet. Phases …
5.0 Limitations
· CT ratio
· Core cross-sectional area
· Connected burden
· Magnitude of burden
· Presence and amount of remnant flux (if any)
· Saturation flux density of the core steel
There is two points to
over come this problem:
The relay could then be set
above this
value to prevent operation
due to C.T.
saturation This could require
very high
settings that may not be sensitive
enough to detect the minimum
possible
bus fault.
By introducing time delay to the over
current function, but it is difficult to
determine exactly how much time is
required to prevent operation. Even if the
time could be determined accurately, it
may be too long from a system point of
view, and it could lead to stability
problems.
8.0 Magnetizing
inrush current
problem
The inrush current occurs when a
transformer is being energized.
During the energization of the
transformer there is only current in
and no current out
the inrush current appears to the
differential relays as an internal
fault
The harmonic content of the inrush
current is different from normal load
current and from fault currents
The 2nd harmonic component does not
appear in the transformers under any
other conditions except during
energization
To keep the diff. relay keep away from
improper tripping by using a second
harmonic component to restrain the
relay from operating
connection to current
transformer
connection to current transformer
9.0 Diff. protection
of three
phase transformers
Differential protection of three phase
transformers must take into account
the change in magnitude and phase
angle of the transformed current.