Você está na página 1de 2

Universal cable with system integrity

Safety rst!
The ability of safety-related equipment such as emergency lighting, communications or emergency phone and alert systems to maintain system integrity saves lives in the event of re. Wherever large numbers of people congregate, be it in the transport area such as in airports, train stations, car tunnels, underground trains or buildings such as hotels, department stores and hospitals, the prime objective is to avoid exposure to danger and it is vital that ber optic cables maintain system integrity. Optical connections using ber optic cables must therefore be constructed with multi-layered re barriers, preventing a complete outage of the system by the destructive eect of a re.

re secured U-D(ZN)BH n
LEONI Fiber Optics oers such a cable that maintains its circuit and insulation integrity for 90 minutes. It is the specially designed re secured U-D(ZN)BH n..., a universal ber optic cable that enables safety-related systems to continue operating in the event of a re. VDE in Oenbach, an accredited testing institute, tested the cables construction to the IEC 60331-11 and 25 (maintaining circuit integrity) as well as EN 50200 (maintaining insulation integrity) standards. The cable passed these demanding tests. While meeting the criteria for acceptance under the IEC standard is already a major

Typical change of attenuation at 1300 nm under test acc. to EN 50200 (DIN VDE 00482 Part 1)

Increase of attenuation [dB]

10

20

30

40

50

60

70

80

90

challenge, the EN 50200 test also subjects the cable to mechanical vibration while exposing it to ames. This is intended to simulate the potential destruction of the cable systems by falling debris and the associated incalculable, additional mechanical strain also exerted particularly in the event of a re.

Time in minutes

The results of the re test conrm that LEONIs re secured product meets the criteria for maintaining circuit and insulation integrity for a period of 90 minutes in the event of re.

re secured

Part-No. 84040

U-D(ZN)BH n
Universal ber optic cables with a central tube (2500 N) that maintain circuit and insulation integrity for 90 minutes in the event of a re Outer jacket Loose tube, gel lled Ripcord Inner re protection tape Outer re protection tape Application/installation universal ber optic cables for signal and control circuits that maintains circuit integrity in the event of re for xed installation both inside and outside buildings; in cable ducts, conduits and on cable trays

Construction

Description of composition
Cable core Loose tube, gel lled 3.5 mm diameter with 2 to 12 optical bers or 4.0 mm dia. with 14 to 24 optical bers. Fiber colour code: 1 to 12: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink 13 - 24: red, green, blue, yellow, white, grey, brown, violet, turquoise, transparent, orange, pink (each with black ring markings) as an inner barrier against re multi-functional, strengthened E-glass yarn covering, double-ply (S and Z), as outer re protection barrier halogen-free and ame-retardant material (SHF1), rated wall thickness of 1.7 mm, colour: blue two diametrically aligned ripcords Outer diameter: see table Inkjet imprint in black: re secured U-D(ZN)BH n ber type (alternating current symbol x2), (order number), (reel number), (meter marking)

Mechanical properties
min. bending radius max. tensile load max. lateral pressure resistance installed when installed constant constant 15 x outer diameter 20 x outer diameter 2500 N 3000 N/dm

Thermal properties
Transport and storage Installation Operating temperature 25 C to +70 C 5 C to +50 C 20 C to +60 C

Tape Armouring Cable jacket

Behaviour in re
Flame retardant Density of smoke Halogen free Circuit integrity IEC 60332-1 and IEC 60332-3 Cat. A IEC 61034-1 and 61034-2 IEC 60754-2 90 min acc. to IEC 60331-11 and -25 max. attenuation change 2.0 dB VDE test report 111100-9020-0001/11291 Insulation integrity 90 min acc. to EN 50200/DIN VDE 0482 Part 1 max. attenuation change 2.0 dB VDE test report 5005019-0001/62755 no corrosive or toxic conagration gases

Designs
available optical bers: E9/125 m, G50/125 m, G62,5/125 m or special bers

Approvals by classication companies


Germanischer Lloyd

Standards
DIN VDE 0888, Part 6; IEC 60794-2

No. of bers
max. 12 24

Outer-
(mm) 10.3 10.8

Weight
(kg/km) 115 125

Fire load
(MJ/m) 1.03 1.28

Cable deliveries on disposable drums or KTG-drums