Você está na página 1de 42

Section 6

E
E
L
L
E
E
C
C
T
T
R
R
I
I
C
C
A
A
L
L
S
S
E
E
R
R
V
V
I
I
C
C
E
E
S
S


Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 2 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6 CONTENTS
6.1 INTRODUCTION................................................................................................................................. 3
6.2 MAIN ELECTRICAL SWITCHBOARD................................................................................................... 3
6.2.1 Switchboard Design............................................................................................................. 3
6.2.2 Switchboard Labelling......................................................................................................... 4
6.2.3 Meters and Instruments........................................................................................................ 5
6.2.4 Fuses with Enclosed Fuse Links ............................................................................................ 5
6.2.5 Schematic Wiring Diagram................................................................................................. 5
6.3 DISTRIBUTION SWITCHBOARDS, CONTROL PANELS AND CABLES.................................................. 6
6.3.1 Distribution Switchboards .................................................................................................... 6
6.3.2 Control Panels ....................................................................................................................... 6
6.3.3 Cables .................................................................................................................................... 7
6.3.3.1 PVC Cable...............................................................................................................................................7
6.3.3.2 Metal Cable Duct ...................................................................................................................................7
6.3.3.3 Cable Tray and Cable Ladder .............................................................................................................7
6.3.3.4 Skirting Wall Duct.....................................................................................................................................7
6.3.3.5 Chasing-in of Cables..............................................................................................................................7
6.4 LIGHT FITTINGS/LUMINAIRES ............................................................................................................ 7
6.4.1 Fluorescent Luminaires......................................................................................................... 7
6.4.1.1 Ballasts ......................................................................................................................................................7
6.4.1.2 1200 mm Lamps ......................................................................................................................................7
6.4.1.3 Capacitors ...............................................................................................................................................8
6.4.1.4 Starter Switches .......................................................................................................................................8
6.4.1.5 Lamp Holders...........................................................................................................................................8
6.4.1.6 Fuse Protection........................................................................................................................................8
6.4.1.7 Fixings ........................................................................................................................................................8
6.4.1.8 General ....................................................................................................................................................8
6.4.2 Incandescent Light Fittings/Luminaires ............................................................................. 9
6.4.3 Extra Low Voltage (ELV) Light Fittings ................................................................................ 9
6.4.4 Down Lights.......................................................................................................................... 10
6.4.5 Wiring.................................................................................................................................... 10
6.4.6 External Light Fittings/Luminaires ...................................................................................... 10
6.4.7 Internal Light Fittings/Luminaires....................................................................................... 11
6.4.8 Bollard Luminaires, Post Top Luminaires and Inground Lighting.................................. 11
6.5 OTHER ELECTRICAL INSTALLATIONS............................................................................................... 11
6.5.1 Switched socket Outlets .................................................................................................... 11
6.5.2 Light Switches ...................................................................................................................... 12
6.5.3 Automatic Sliding Doors .................................................................................................... 12
6.5.4 Fire Alarm Systems (See section 2.16).............................................................................. 12
6.5.5 Emergency and Exit Lighting ............................................................................................ 12
6.5.6 Communications Rooms ................................................................................................... 13
6.5.7 Electric Motors..................................................................................................................... 13
6.5.8 Labelling............................................................................................................................... 13
APPENDIX 6.A: ELECTRICAL SERVICES STANDARD SPECIFICATION............................................................ 14
APPENDIX 6.B: OPERATING AND MAINTENANCE MANUALS SCHEDULE OF CONTENTS ......................... 42


Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 3 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.1 INTRODUCTION
The installation of electrical services and equipment in buildings shall comply with the standards
as set out in Section 1 of this Brief and Electrical Services Standard Specification Appendix 6.A.
The electrical supply distribution system for the campus is 3 phase, 4 wire 415/240 volts, 50 Hz.
The supply originates from Supply Authority sub-stations distributed around the Campus.
Early in the Design Stage, the Consultant shall calculate the Maximum Demand (MD) and energy
consumption for each project or installation, and discuss the selection of the appropriate tariff and
load management techniques with the Manager, Engineering and Maintenance.
The Consultant shall submit to the Services Project Manager a detailed report for each project,
including the MD calculations and recommended tariff selection.
Electrical Services to be designed in consultation with the Services Project Manager.
6.2 MAIN ELECTRICAL SWITCHBOARD
The main electrical switchboard shall be specified as a custom built switchboard and shall be
designed in accordance with the relevant sections of A.S. 3439 & AS 3947.
Tenderers shall submit full details of the switchboard with their tender, together with the name of
the testing authority and relevant information regarding the fault current rating of the
switchboard.
Full shop drawings, together with all relevant data relating to a proposed main switchboard, shall
be delivered to the Services Consultants and the Manager, Engineering and Maintenance prior to
manufacturing the switchboard.
Switchboards are to have the capacity to withstand prospective fault for a given substation.
6.2.1 Switchboard Design
Switchboard design shall incorporate the following:
the Consultant shall confirm with the Services Project Manager the requirement for spare
capacity for future C.F.S. and/or ACB units (recommended 40%).
copper busbars shall be designed to limit temperature rise to a maximum of 40oC when
carrying the maximum current rating of each and all associated items of switchgear;
busbars for the red, white and blue phases shall be colour coated. Colouring shall be by
means of full length heat shrink (Thermoshrink or similar). Strips, or bands of heat shrink
shall be utilised to identify the neutral and earth conductors;
the main switchboard shall be of a front connected design up to 800 amp rating;
all "live" sections of a main switchboard, within wiring chambers etc., shall be fully
insulated to prevent contact with live parts;
the main switchboard shall be free-standing, dust and vermin proof;
control of outgoing supplies shall be as follows-
~ Up to 800 amps C.F.S. unit
~ 800 amps and over A.C.B. unit
Where Moulded Case Circuit Breakers (MCCB) are requested the confirmation of the
Services Project Manager should be sought.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 4 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
the minimum capacity for any CFS unit shall be 200 amps;
CFS units shall be manufactured by Nilsen or other University-approved manufacturers.
Each CFS assembly shall be withdrawable from the body from the front of the switchboard;
ACB units shall be manufactured by Nilsen (D-PRO series) or other University-approved
manufacturers;
the provision of a positive air ventilation system for the main switchboard room to
minimise dust entry shall be considered;
lift-off hinges shall be supplied for all hinged doors;
doors shall be supplied with lockable latches; lock cylinders shall be keyed to CL-001 keys;
removable panels shall be supplied with-
~ Suitable lifting handles
~ Captive knurl-headed fixing screws
removable panels shall be supported by locating dowels or pins to provide support for the
panel when the fixing bolts are removed;
the design shall incorporate adequate space for:
~ Supply Authority metering equipment
~ University BAS connections
~ Termination of incoming and outgoing circuits
~ University KWH check metering and for all outgoing submains
~ Future extensions or additions
A separate, wall-mounted, steel, lockable cabinet, keyed to a CL001 key shall be provided in
a suitable location in the main switchboard room.
~ The cabinet shall be labelled SPARE FUSES AND EQUIPMENT
~ the cabinet shall contain spare parts, tools, and a full set of spare HRC fuse cartridges
for all CFS units installed on the main switchboard
The Contractor shall install a copy of the schematic wiring drawing, in a suitable enclosure
inside the main switchboard room; (Refer to clause 6.2.5)
6.2.2 Switchboard Labelling
All switchgear, apparatus, terminal strips, and controls shall be labelled in accordance with the
Supply Authority's requirements and to the satisfaction of the Manager, Engineering and
Maintenance. The following guidelines shall be observed:
Lift-off panels shall be labelled to identify their location on the main switchboard;
Labels shall be provided for Essential Supplies, which are deemed to include the following:
~ fire protection equipment.
~ fire indicating panel.
~ passenger elevators.
~ circuits supplying computer LAN, WAN or computer equipment.
~ circuits controlling emergency luminaires.
~ circuits controlling security or building access control equipment.
all incoming and outgoing circuits shall be adequately labelled, including all essential
supply circuits.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 5 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Traffolyte labels shall be installed on the front door of a C.F.S. unit and shall indicate the
capacity of the unit and the rating of installed fuse cartridges. Labels shall also be installed
adjacent to the load terminals.
6.2.3 Meters and Instruments
The installation of switchboard instrumentation is a complex issue. Design discussions with
relevant University representatives shall take place at an early stage. Consideration shall be given
to the following:
CALMU smartmeters (check meters) or equal;
Maximum Demand ammeters;
a voltmeter;
kWh check meters (with volt free, impulse contacts for connection to the BAS system)
the type of current transformers;
test links for current transformer secondary terminals;
fused potential terminals for connection of portable recording equipment;
indicating lights.
See also Appendix 6.A Section 6.A.3 for guidelines for the installation of Circuited power
analysis meters.
6.2.4 Fuses with Enclosed Fuse Links
Fuses shall comply with A.S. 2005 (Parts 1 and 2). All fuse cartridges shall be of the HRC type.
Fuses shall be suitable for the fault current of the installation and shall discriminate properly with
other protective equipment.
The installation of motor start fuse cartridges shall be avoided.
All fuse cartridges (excluding those installed in CFS units) shall be held in a fully enclosed fuse
base with shrouded fuse contacts. Glow lamps for each HRC fuse assembly shall be specified.
6.2.5 Schematic Wiring Diagram
A schematic wiring diagram of the complete switchboard shall be supplied. The wiring diagram
shall include, but shall not be limited to, the following information:
circuit breaker capacities and trip settings
fuse sizes
capacity of CFS units installed
size and capacity of installed busbar
capacity of incoming supply
capacity of outgoing circuits
destination of submain supplies
size of main earth conductor and location of main earth electrode
type test rating of the Main Switchboard

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 6 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
The Contractor shall install a copy of the above drawing in a suitable enclosure inside the main
switchboard room.
The Contractor shall supply AutoCAD copies of the diagram as per Section 1.
6.3 DISTRIBUTION SWITCHBOARDS, CONTROL PANELS AND
CABLES
6.3.1 Distribution Switchboards
Spare capacity of 50% shall be provided for all distribution boards (i.e. 50% full). Standard
distribution boards shall be manufactured University-approved suppliers.
Circuit breakers controlling final sub-circuits shall be Cutler-Hammer or other University-approved
equivalent. Installation of LOCK DOGS for all circuit breakers controlling computer outlets or
special equipment shall be specified.
The installation of DUPLEX circuit breakers shall not be permitted.
Cutler-Hammer, NPH Terasaki or similar circuit breakers shall be specified for all phase power
circuits.
Installation of a centre mounted main switch, to control each distribution board, shall be specified.
All busbar tee-offs shall be fully insulated.
6.3.2 Control Panels
Sprecher and Schuh contactors, panel mounted control switches or equal approved shall be
specified. Contactors, relays, control switch etc. shall be DIN-Rail mounted. 100% spare capacity
shall be provided on the panel for future expansion (i.e. 50% full).
all cables shall be identified by numbered ferrules at each termination including field
terminations.
equipment within the panel shall be logically laid out and labelled
there shall be sufficient space between items to permit safe maintenance a minimum of
50 mm between contactors
automatic controls shall be mounted external to the switchboard in a separate cabinet
containing only extra-low voltage wiring; control wiring entering the switchboard shall be
insulated to the appropriate rating;
there shall be adequate cabinet ventilation to ensure against temperature rise and thermal
overload operation.
Circuit breakers are preferred in lieu of HRC fuses. Where HRC fuses are specified, they shall be
complete with glow lamps.
Time-switch clocks are the standard for the University.
Schematic diagrams, complete with wire numbers, shall be installed at each control panel.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 7 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.3.3 Cables
All cables shall be stranded copper conductors, PVC insulated 0.6 kV, V75 grade conforming to
A.S. 3147.
General power circuits shall be wired in not less than 2.5 mm
2
(7/.067) TPS cable (black colour).
General light circuits shall be wired in not less than 2.5 mm
2
(7/.067) TPS cable (white colour).
Control cabling shall conform to the specification in Section 7 of this Project Standard.
6.3.3.1 PVC Cable
Cables shall be concealed wherever possible. Cables installed as surface wiring shall be enclosed
in PVC mini ducting in lieu of PVC conduit subject to approval. The duct shall be fixed to the
wall with suitable fixings, not double sided adhesive tape.
6.3.3.2 Metal Cable Duct
Where permitted to specify, metal duct shall be selected from the Dencol range or equal.
6.3.3.3 Cable Tray and Cable Ladder
Cable tray and cable ladder shall be specified from the Burndy or Dencol range or equal.
6.3.3.4 Skirting Wall Duct
Skirting/wall duct shall be specified from the MODULINE range or other University approved
suppliers.
All material ladders and ducts shall be earthed including joints for electrical continuity.
6.3.3.5 Chasing-in of Cables
Any cables chased into masonry shall be installed in suitable PVC conduit.
6.4 LIGHT FITTINGS/LUMINAIRES
6.4.1 Fluorescent Luminaires
Refer to Section 4.7.3 regarding the use of T5 fluorescent lamps. As a minimum the Consultant
shall specify luminaires which incorporate 1200 mm long, 26 diameter fluorescent lamps. All
light fittings shall be HPF. Min 0.9 P.F.
The following items shall be taken into account when specifying fluorescent luminaires. (See also
Section 4).
6.4.1.1 Ballasts
Separate ballast shall be specified for each fluorescent lamp. Ballasts shall be complete with
quick-connect terminals. They shall be of the full low-loss Atco LLEC range or similar.
6.4.1.2 1200 mm Lamps
The colour temperature of the lamps shall be 3000 degrees kelvin. The minimum lumen output
for a 36W fluorescent lamp at 100 hours shall be minimum 2700 lumens. Lamps shall be selected
from the Thorn, Sylvania, Osram, or Philips range.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 8 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.4.1.3 Capacitors
Capacitors shall maintain the Power Factor at or better than 0.9 lagging and have a minimum
clearance of 75 mm and 100 mm from any ballast.
6.4.1.4 Starter Switches
Starter switches shall be Wotan ST171 or similar for 36 watt lamps and shall be capable of a
minimum of 5000 operations. They shall be complete with a manual reset.
6.4.1.5 Lamp Holders
Tombstone lamp holders, HPM 380 or similar, shall be specified. Lamp holders shall be made from
non-flammable materials and shall not be starter/lamp holder combined type.
Lamp holders with snap-in wiring terminals shall only be accepted if solid conductor (1/0.80)
wiring is utilised.
6.4.1.6 Fuse Protection
Each light fitting shall be provided with a fuse of a suitable rating to isolate the fitting in the event
of a fault within the light fitting.
Such fuses shall be readily accessible.
6.4.1.7 Fixings
Cadmium plated loxins, dynabolts or approved metal expansion devices shall be used for
securing light fittings to concrete ceilings. Wooden or plastic plugs will not be accepted. The
MINIMUM number of fixings per light fitting shall be as follows:
1 x 36 watt fluorescent light fitting 2 fixings
2 x 36 watt fluorescent light fitting 4 fixings.
6.4.1.8 General
Diffusers, reflectors etc., shall be installed just prior to Practical Completion so as to limit dust
build up.
Reflectors shall be manufactured from high quality steel or aluminium.
Luminaires shall be selected for ease of lamp changing and cleaning and have adequate
mechanical and electrical features to ensure durability and lack of deterioration.
Diffusers shall be strong and of rigid construction.
Luminaires selected for computer laboratories or VDU applications shall be of the low brightness
type.
Switching shall be arranged to provide for 50% illuminance
Where entire floor levels are being documented, the installation of 24 hour light fittings at
strategic locations for general security lighting shall be discussed.
Excess illumination shall be discouraged.
Where possible, all luminaires shall be installed using the plug-in method.
Installations shall conform to A.S. 3145 for minimum radio interference.
Prismatic diffusers for office, public or common areas shall be K19 (only where there is no screen
based task application); and for special purpose rooms K19 with silver tint.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 9 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Fittings which incorporate single end PL or PLC fluorescent lamps shall not be specified without
approval from the Services Project Manager.
Each luminaire shall be supplied with a fixed terminal block. The terminal block shall
accommodate a minimum 4 mm
2
cable. Each terminal block shall incorporate a spare 'loop'
terminal.
Incandescent Light Fittings/Luminaires
Installation of incandescent luminaires shall be avoided. This clause may not apply to lecture
theatres; in all cases the Consultant shall discuss this issue with the Manager, Engineering and
Maintenance Branch. Incandescent light fittings shall only be considered where there are no other
possible solutions.
Where permitted, incandescent light fittings shall be supplied with long-life 250 volt lamps and
the lamp holders shall be porcelain.
6.4.2 Extra Low Voltage (ELV) Light Fittings
A separate step down transformer shall be required for each ELV lamp. The transformer for each
ELV light fitting shall be readily accessible. Traffolyte labels shall be installed (light fitting and
associated transformer) where the transformer is installed remote from the light fitting and not
more than 2 metres from the lamp.
ELV Luminaires shall be selected on the following criteria:
adequate ventilation;
ease of lamp replacement;
ease of cleaning.
Where the luminaires are recessed, the fitting shall incorporate a design to prevent contact with
materials such as ceiling insulation, with the ELV lamp, or hot luminaire components.
ELV dichroic halogen lamps shall be GE, or approved equivalent, with an average rated lamp life
of 3,000 hours as a minimum.
Where dimming of ELV lamps is required, the dimmer unit shall incorporate the following:
Soft start;
digital control;
halogen clean-up cycle;
in-built surge protector;
internal time clock;
RF suppression;
ELV dimmer units shall be selected from the DYNALITE range or similar University-approved.
Lamp holders shall be the bi pin, high temperature, ceramic base variety. The wattage of the lamp
shall be identified at the lamp holder. In particular applications ELV lamps shall be supplied with
a suitable UV filter glass.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 10 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.4.3 Down Lights
Luminaires shall be selected from the range which incorporate compact fluorescent or HID lamps.
Down lights with incandescent lamps will not be accepted.
A separate ballast shall be provided for each lamp and a suitable label shall be located adjacent to
each lamp holder as a means of identification of the required lamp wattage.
Ballasts should be the switched-start type with losses after fifteen minutes of no greater than:
7 watt lamp 3.5 watts
9 watt lamp 3.5 watts
18 watt lamp 5.5 watts.
Reflectors should be of high quality, chromed aluminium.
6.4.4 Wiring
The installation shall be designed so that future additional luminaires can be easily added to the
circuit. The current load of the initial circuit when installed should not be more than 50% of
capacity. Unswitched active conductors shall terminate in each luminaires. This will allow for
simple future alterations, should they occur. Ceiling pull cord switches are not acceptable.
6.4.5 External Light Fittings/Luminaires
External luminaires shall be specified from the HID range and shall conform to the following:
self-ballasted lamps will not be accepted;
HID ballasts shall be of energy efficient design;
capacitors for each light fitting shall maintain the Power Factor at, or better than, 0.90
lagging.
Luminaires which incorporate the following types of lamps will not be accepted:
QI lamps;
incandescent lamps;
dichroic (halogen) ELV lamps.
External luminaires shall be individually protected by HRC fuses and have adequate ventilation.
Reflectors should be manufactured from high quality (purity) aluminium.
Luminaires shall be selected for ease of lamp changing and cleaning and have adequate
mechanical and electrical features to ensure durability and lack of deterioration. They shall be
treated to prevent corrosion.
External security and street lighting shall be colour corrected mercury vapour. External building
security lighting shall be an approved type, painted to match the building structure. Street
lighting shall comply with the principles detailed in the Technical Notes, Urban Spaces City and
Bundoora Campus, June 1996. All external security and street lighting shall be controlled by
photo cell switching. By-pass switches shall be provided on all circuits. Each street light poles
shall be separately fused. Where appropriate photo-electric cell switching is to be considered.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 11 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.4.6 Internal Light Fittings/Luminaires
Internal security lighting shall be provided in the following areas of the Buildings.
Balconies, verandas, corridors and all stairways and exterior doors. The lighting shall be
controlled by an externally mounted photo electric cell and a bypass switch, located in the
distribution switchboard cupboard.
Light Switching Two way switching and time clock control shall be provided on all stairways
and corridors subject to approval.
Light switches in tunnels shall be fitted with continuously operating amber coloured neon
indicators.
Light switches in tunnels and all service areas shall be the protected type.
Sufficient controls, both automatic and manual, shall be provided so that energy can be saved
when spaces are not in use or when systems require modification.
Energy management timing systems shall be considered for lecture rooms, seminar rooms,
laboratories and any other areas have high usage. Consideration shall be given to the use of
occupancy sensors.
Rooms containing one or more luminaires shall be provided with multiple switching.
Emergency light fittings or fittings incorporating an additional lamp for emergency lighting shall
also comply with A.S. 2293 complete with "NATA" Test Certificate.
Metalware shall be not less than 0.8 mm thickness with adequate folds and return edges etc. to
provide stiffness and rigidity. All corners and joints exposed to view shall be welded, ground
smooth and filed where necessary before painting. All metal work shall be treated with a rust
inhibitor or alternatively manufactured out of zincanneal.
All recessed luminaires diffusers shall be prismatic hinged frame supported.
All luminaire shall be power factor corrected to not less than 0.9 lagging.
Luminaire in computer areas shall be provided with low brightness glare control diffusers to
prevent discomfort to computer operators.
A fluorescent luminaires and power point shall be provided in every telephone and computer
frame cupboard.
6.4.7 Bollard Luminaires, Post Top Luminaires and Inground Lighting
Consultants should contact the Project Manager and Campus Planning for advice of specialist
lighting. Installation should reflect the current installations.
6.5 OTHER ELECTRICAL INSTALLATIONS
6.5.1 Switched socket Outlets
Switched Socket Outlets (SSO) shall be selected from the Clipsal range single plate or other
University-approved and shall be specified as white from the standard Clipsal colour range.
Double outlet combinations shall be specified throughout an installation. Clipsal IP56 Series shall
be specified for wet areas. The circuit current load shall be no more than 60% of capacity when
initially installed.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 12 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
All circuits for SSOs shall be protected by earth leakage circuit breakers or RCDs. Emergency stop
buttons shall be installed for safety control for laboratory power outlets.
The location of RCD or ELCB shall be approved by the Manager, Engineering and Maintenance
Branch.
6.5.2 Light Switches
Light switches shall be selected from the Clipsal range single plate and shall be specified as white
from the standard Clipsal colour range. Clipsal 30-FLM-15 amp mechanisms shall be specified for
all standard light switches.
Refer Appendix 6A Clause 06.A.6.6 for further details.
6.5.3 Automatic Sliding Doors
Power to automatic sliding doors at entrance(s) to a building shall be key switch operated.
Refer to clause 2.9.2 for keying details.
A further requirement will be that the sliding door must remain in an open position during
normal hours when Fire Indicator Board is in alarm mode.
An approved electronic lock and mounting position is required where security access control
systems are installed.
6.5.4 Fire Alarm Systems (See section 2.16)
6.5.5 Emergency and Exit Lighting
The University has standardised on two types of emergency lighting systems:
Minitronics Single Point Premium range;
Minitronics Single Point Computer Monitored range.
The Consultant shall calculate the best installation option based on life cycle cost over a 12 to 15
year period.
Self contained emergency and exit lighting shall be provided throughout the buildings in
accordance with A.S. 2293. The emergency and exit lighting shall be connected to a Computer
monitoring facility as directed by the Services Project Manager.
All exit lighting shall be sustained circuit, two tube 10 watt fluorescent luminaires.
Emergency and exit lighting circuits shall be wired direct from distribution switchboards and
shall be labelled with engraved plastic labels in accordance with A.S. 2293. Provide a key
operated "auto-off-manual" switch adjacent the distribution switchboards for testing of emergency
and exit lighting.
Emergency lighting shall be installed in every toilet, essential area and switch room. Luminaires
shall be a non-sustained circuit minimum 36 watt, with lighting levels designed to provide
adequate lighting to carry out operations under power failure conditions in switch rooms.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 13 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
6.5.6 Communications Rooms
All SSOs in Communications Rooms shall be surge protected.
6.5.7 Electric Motors
The following are preferred:
Fractional H.P. "G.M.F."
Ball bearing 3 phase up to 12 kW "Crompton Parkinson", ASEA
Ball bearing 3 phase 12 kW to 40 kW - "ASEA"
6.5.8 Labelling
Each item of equipment (i.e. switched socket outlets, light switches, computer outlet plates, etc.)
shall be labelled by the following method:
IPA studs to indicate phase and circuit number;
Supplementary information shall be provided at the rear of equipment.
Traffolyte labels shall be specified for all main and submain feeders.
Monitoring cables shall be labelled every 3 metres and/or at change in direction.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 14 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
APPENDIX 6.A:
ELECTRICAL SERVICES STANDARD SPECIFICATION
6.A.1 INTRODUCTION
6.A.1.1 General
This standard specification sets out the minimum requirements for the design and construction of
its electrical services within the University. Equipment supplied and workmanship shall be of best
quality.
The work shall comply with the requirements of all relevant Legislation, Standards including
current wiring regulations and any other Authority having jurisdiction over the project.
For all intents and practical purposes, RMIT City Campus is considered as a Supply Authority.
Prior to the issue of the Certificate of Practical completion the contractor shall certify that the
applicable statutory requirements, regulations and standards. A copy of all certificates shall be
forwarded to RMIT.
Requests for departure from this standard shall be confirmed in writing to the RMIT Services
Project Manager, Property Services prior to documentation installation.
False alarms caused by the installation shall be the responsibility of the Contractor.
Refer to clause 12a.33 installation of existing services.
6.A.2 Underground Wiring
6.A.2.1 Underground System
All underground cabling shall be installed in Category A system. Location of existing underground
services shall be established before excavation. Trenching shall not commence until cable,
conduits, etc., are on site. Refer to clause 12a.26 determining existing services prior to
excavation.
Where existing services are encountered during excavation, provisions shall be made not to
damage such services.
Trenches shall not be backfilled before cables are surveyed by the Services Project Manager,
Construction and marked by the Contractor on "as built" drawings.
All MV and LV conduits shall be installed at a minimum depth of 600 mm below the finished
surface. Conduit(s) shall be embedded and totally covered in 50 mm clean washed sand.
Conduits installed in same trench shall be spaced to a minimum of 50 mm. Marker tapes shall be
provided 100 mm above the conduit. Spare conduit provided in each trench shall be a minimum
of 50%. End caps shall be provided on spare conduits with draw wire. Packings shall be provided
at conduit ends where cables are installed.
Cutting pavement, backfill and making good of roadways, paths and gardens shall be included in
this work. Excess spoil after allowance for subsidence shall be removed by the Contractor.
Compaction of backfill shall be provided.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 15 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Cable markers shall be provided where the cable changes direction and where cable enters or
leaves a building. Markers shall be of a flush type warning plate with direction indicators.
Where conduits change more than two (2) different directions, cable pits shall be provided. Pits
shall be of the reinforced concrete waterproof type with drainage. Gatic type covers shall be
provided. Conduits entering these pits shall protrude not less than 50 mm into the concrete pit
wall for the installation of cables and/or end caps. Conduit ends shall be free of sharp edges. All
conduit ends with cables shall be sealed for waterproof purposes as directed.
All trenches shall be installed with two (2) 63 mm diameter spare conduits for future
Communication cables.
Underground conduits shall be electrical orange for 415/240v cables. Other data conduits shall be
white.
6.A.2.2 Underground Cable
Underground multi core and single core cables shall be double insulated copper conductors. New
cables shall be installed without joints. Subject to the approval, joints to the existing underground
services may be allowed. Refer to clause 04.00 for further requirements of mains and submains.
6.A.2.3 Anti-Termite Treatment
The ground surrounding cables, pipe enclosures and cable pits shall be treated to provide
protection against termite attack. The anti-termite treatment shall be carried out to approval by a
firm specialising in the work. Notices shall be provided.
6.A.3 METERING
6.A.3.1 Supply Authority Metering
Supply and install all fixings, panels, wiring links and hardware to the requirements of the Supply
Authority for the most economical tariff.
Provide all co-ordination and make all necessary applications for the provision of metering
equipment.
Pay all associated charges for the provision of metering equipment as may be rendered by the
Supply Authority.
6.A.3.2 In-House Metering
Supply and install all necessary fixings, wiring and hardware for the polyphase kilowatt hours
metering to each of the main building services emanating from the main switchboard. Metering
shall be for the following services:
Incoming mains.
Lifts.
Mechanical switchboards.
All submains.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 16 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Other specialised power e.g. computer services as directed. Metering, for each floor, shall
be provided to monitor lighting and power consumption. Meters, of approved type, shall
measure voltages, amperes, kilowatts, kilowatt-hours, power factors and frequency. Such
outputs shall also be monitored via the BAS system.
Time/consumption graphic charts shall be provided and storage of data via PC software. Refer to
clause 08.00 for other information.
Meter shall be Circutor Modbus compatible meters or equivalent.
6.A.4 SWITCHBOARDS
6.A.4.1 General
The quality of the materials used and the standard of workmanship shall comply with the latest
issue of the Australian Standards and to the satisfaction of the authorities. The quality of
manufacture shall include main switchboards, distribution switchboards and control assemblies.
6.A.4.2 Main Switchboards
All main switchboards with ratings of 800 A and above, on the incoming supply conductors shall
be constructed to Form 3, free standing metal clad cubicle back connected type to AS3439.
The degree of protection shall be by mechanical means.
Smaller switchboards can be wall mounted type or free-standing metal clad to Form 2 construction
and dead front, to approval by the Manager, Engineering and Maintenance Branch.
The proposed switchboard manufacturer shall be submitted for approval prior to acceptance of
tender or quotation.
Type tested certificate shall be provided.
Switchboards shall be complete in every respect, fully wired and factory tested. Design to
facilitate easy access to and removal of component parts.
Switchboards shall be provided with suitable means of securing the complete assembly to floor or
wall. Free standing type shall be provided with plinth or suitable channel support of not less than
75 mm high with provision for future extension and cabling. Trenches shall be accessible. The
degree of protection shall be minimum IP33.
All holes shall be provided with suitable bushing. Coverplates shall be of the removable type.
All equipment shall be flush front type.
Louvred vents with mesh wire shall be provided for switchboards with horizontal length greater
than one metre.
Switchboards shall be designed to prevent the ingress of dust and insects. Lifting eyebolts shall
be provided to switchboards weighing more than 300kg. Switchboards shall be coloured internal
gloss white and external grey.
Busbars within the switchboard and distribution switchboards shall be manufactured from high
conductivity hand drawn copper bar with smooth edges. Rating of busbars shall include the total
capacity (rating) of the functional units to A.S. 1136 including spares, plus 40% spare capacity for
future extension. All joints, terminations and fixings shall be fully accessible. Adequate support
shall be provided so that they can withstand the stresses caused by the prospective maximum
fault current as specified for a period of one (1) second and in no case shall have a fault capacity
of less than 18 kA. Busbars shall be electro-tinned, coated with acid free petroleum jelly and
bolted together with cadmium plated steel bolts, washers, nuts and locknuts. Neutral busbars
shall have the same current rating and size as the active phases. Provision shall be given for
future extension of the main busbars system.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 17 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
An earthing copper bar shall be provided where MEN system is installed. Labels shall be provided
at the external and internal switchboard.
Phase coloured as follows:
A phase Red.
B phase White.
C phase Blue.
Neutral Black.
Earth Green.
Wrapping with tape will not be accepted.
Marking of busbars of manufacturing purposes shall be by means of crayon or similar marker.
Busbars shall be designed for a maximum temperature rise of 40C above an ambient of 40C.
Cabinets shall be clean and free from rust, corrosion, grease and scale, rough surfaces filled and
rubbed smooth.
Cable zone for outgoing cables shall be installed with appropriate cable tray for cable anchorage.
All terminations shall be of adequate size to accommodate the cable lugs.
Busbar stub connections shall be provided on terminals for cables rated at 100 A and above, and
shall be suitable for the connection of bolted cable lugs.
All bolts, screws and nuts shall have hexagonal shaped heads, non-ferrous metal and be fitted
with washers. Self tapping screws will not be accepted.
Small wiring or control wiring shall include wiring within main switchboard, distribution boards and
control assemblies. Such cables shall be multi strand copper conductor, PVC insulated of 0.6/1
kV grade, V75. Minimum size 1.5 mm
2
for ELV and 2.5 mm
2
for LV.
All cable ends shall be identified by clip on markers to approval. Adhesive markers are not
acceptable. The numbering shall be shown on the "as built" circuit diagrams and no number shall
be duplicated on the same unit unless additional distinguishing markers are added.
Cable end lugs shall be fitted for termination at terminal posts, studs and similar locations. A
separate lug shall be provided for each cable end.
Control fuses where practical shall be mounted on busbars, otherwise shall be as close as
possible to the busbars and installed with busbar links.
Functional units (outgoing) of 100 A rating and above, shall be of the Nilsen or approved, installed
in tiers with 30% spare spaces (minimum). Busbars shall be extended to these spare spaces.
Functional units rated at 800 A and above shall be air circuit breaker type.
Ammeters, voltmeters, in-house kWh and power factor meters shall be installed on all main
switchboards, incoming and outgoing supplies.
Confirm the requirements with the Manager, Engineering and Maintenance Branch and previous
Clause 6.A.3.2.
All ammeters and voltmeters shall be selected type such that normal deflection is 80% of the full
scale range. Voltmeter with selector switch and 3 ammeters with maximum demand indicator
shall be provided on main switchboard incoming supply.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 18 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Mechanical services boards and control assemblies shall be fitted with "hour-run" meter to monitor
plant run hours.
Shop drawings shall provide the following information:
Full details of cabinet construction and dimensions including its IP rating.
Method of support busbars and equipment.
Form of construction to A.S. 13439.
Description of materials.
Busbars dimension and ratings.
Internal wiring sizes, ratings and route.
Size and wording of labels.
Wiring diagrams and schematics of instrument protection and control circuits.
Front elevation of switchboard.
Vertical section through each compartment.
Sheet metal details.
Weights of switchboard.
Location for the future extension of busbars.
Labelling shall be provided on all switchboards.
Main earth electrode where installed shall be shown on "as built" drawings.
Suitably hinged frame(s) or as built drawings shall be provided in the main switch room showing
the layout and schematics of the main switchboard.
6.A.4.3 Distribution Switchboards
Distribution switchboards shall generally be proprietary type boards with similar requirements as
applicable to that of main switchboards.
Distribution switchboards shall be constructed to Form 1 assemblies.
Distribution switchboard shall be:
Equivalent to Cutler-Hammer, Quicklag or NHP Terasaki circuit breaker type.
Provided with centre main switch. Distribution switchboard (including load centre) shall be
protected by fuses or circuit breaker at the upstream. These protective devises shall be
rated NOT less than 60 A.
Provided with separate sections for time clocks, contactors, relays and other equipment.
Provided with separate sections for lighting and power.
Provided with bottom mounted neutral and earth bars. Neutral and earth bar shall be
provided with equal number of tunnels (to phase circuits) for terminals including spares and
labelled.
Provided with escutcheon plate which shall be hinged. Plates greater than one metre high
shall be four point locking, or in two separate hinge plates.
Provided with lockable doors (keyed to CL001). Where distribution switchboard is located
in dedicated cupboards, switchboard doors need not be provided.
Provided with labelling

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 19 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
The requirements of energy management may require a separate distribution board for its control
of lighting, including the installation of contactors, relays, and other equipment for its total
operation. As an alternative, distribution switchboard cupboards shall be provided with space for
the mounting of such control equipment, including in-house meters. Such space shall include
future capacity.
Miniature circuit breakers (moulded case) shall incorporate both thermal and magnetic tripping
mechanism, with visual indication in the centre tripped position. The interrupting capacity for the
maximum prospective fault current shall be not less than 6 kA.
Circuit breaker rating shall be minimum 20 A.
Spare capacity shall be not less than 50% of installed outgoing protective devices. Busbars shall
be extended to these spare spaces.
Generally these boards serve final subcircuits; it is required that further to legends, a schematic
and floor layout plans shall be included which identify the circuits, lighting, power, RCDs and other
specialised items.
6.A.4.4 Contactors
All contactors shall be suitable for AC3 utilisation and shall have a minimum current rating of the
protective device. Contactors shall be capable of withstanding the let through current of the
protective device preceding it.
Contactors rated at 20 A and above shall be mechanical latching type.
6.A.4.5 Switches and Isolators
Switches and isolators rated at 100A and above shall be fault make and load break type.
The prospective fault-level must have a corresponding peak value of at least 2.1 times the RMS
value.
Equipment shall have double make and break contacts.
6.A.4.6 Monitoring Systems
Refer to clause 08.00 for further requirement to switchboard equipment requiring contacts, links
and/or transducers.
6.A.4.7 Time Switches
Time switches shall be simple in operation and in programming the On/Off functions. Contacts
shall be rated at 20 A minimum.
Time switches shall be a minimum seven (7) day operating device with 48 hour battery operated
reserve.
By-pass switch shall be provided for Manual/Off/Auto operation. Refer to clause 6.A.6.8.
6.A.4.8 Load Centre Type Switchboards
Equipment provided for load centre type switchboards shall generally comply with clauses as
specified for distribution switchboard. Busbars arrangement with adequate support shall be for
three phase circuit breakers. Neutral and earth bars shall be provided, sized for equal number of
poles. Main switch shall be provided. The number of poles shall in no case be less than 12
excluding main switch. Switchboards shall be easily expandable when another chassis is added.
6.A.4.9 Indicating Lights
Indicating lights installed in all switchboards shall be of the encapsulated transformer type suitable
for 240 V AC and employing a 6 V MES lamp. Minimum size of lamps shall be 25 mm.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 20 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.4.10 Schedule Cards
All distribution switchboards shall be provided with type schedule cards showing its circuit number,
connected equipment, destination and location. Schedule card shall be located within the
distribution board. In a refurbished area, the total schedule card shall be retyped to include the
existing services.
6.A.4.11 Fuse Cartridges
All fuses shall be HRC cartridge type. Spare cartridges for each rating shall be provided for each
switchboard unit installed. Spare cartridges shall be mounted on a suitable rack. At the main
switchboard position, fuses shall be located in a wall mounted enclosure in the switch room. At
distribution boards, the fuses shall be mounted in a convenient location in the respective
cupboards.
6.A.4.12 Control panels and equipment on distribution switchboards
Sprecher and Schuh contactors or equal approved, panel mounted control switches, shall be
specified. Contactors, relays, control switch etc. shall be DIN-Rail mounted. 50% spare capacity
shall be provided on the panel for future expansion.
All cables shall be identified by number ferrules at each termination including field termination.
Equipment within the panel shall be logically laid out and labelled.
There shall be sufficient space between items to permit safe maintenance a minimum of 50 mm
between contractors.
Automatic controls shall be mounted external to the switchboard in a separate cabinet containing
only extra-low voltage wiring; control wiring entering the switchboard shall be insulated to the
appropriate ratings.
There shall be adequate cabinet ventilation to ensure against temperature rise and thermal
overload operation.
Circuit breakers are preferred in lieu of HRC fuses.
Schematic diagrams, complete with wire numbers, shall be installed at each control panel.
6.A.5 MAINS, SUB-MAINS AND WIRING
6.A.5.1 General
All cabling shall have stranded copper conductors and shall be insulated with 0.6/1kV grade PVC
compound type V75 or higher, unless specified otherwise.
Insulation coloured code shall be as follows:
Active phase red.
Active phase white.
Active phase blue.
Neutral black.
Earth green or green/yellow.
Double insulation colour code shall be as follows:
Lighting white.
Power black.
Fire services red.
Others as specified and approved
Aluminium conductors shall not be used.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 21 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
All cables shall be new, unless specified otherwise. All cables shall be brought to the site in their
original packages with their labels intact, otherwise they shall be rejected. All wiring in which kinks
or abrasions occur shall be condemned and shall be replaced at no cost to RMIT. All neutral
cables shall have the same current rating and size at the active phase (s).
Existing cabling, conduits and accessories not satisfying all current Australian Standards shall be
replaced.
All redundant wiring and equipment shall be totally removed.
6.A.5.2 Installation
Single core mains and sub-mains cable shall be installed in trefoil formation, on parallel paths,
with proper radiused curves of not less than six times the cable diameter.
Different sets of mains or sub-mains cable installed in the same route on cable trays or ladder
shall be spaced to avoid derating.
All penetrations of wiring through floors, ceilings and walls shall be fire stopped to approval.
All wiring shall be installed so that it can be readily renewed, repaired or relocated without
affecting building finishes and construction. Wiring for other systems, e.g. MATV, public address,
telephone, etc., shall be installed in a similar manner to light and power wiring in the same area.
Communication cables, where run parallel to light and power cables shall be spaced to a minimum
of 600 mm for length greater than 10 m.
Cable runs shall be installed parallel or right angles to building structure and planning grids.
Cables radiating from distribution switchboards shall be neatly installed on cable trays or enclosed
duct. Grouping of cables, (final sub-circuits) in excess of 10 circuits, shall be installed on cable
tray over common routes. Other cabling shall be adequately fixed and supported with purpose
made clips, cleats or saddles.
Joints are not permitted.
Loop-in and loop-out principle for connection of final sub-circuits.
Catenary wire used for the support of cables shall be properly supported. In concealed space,
fixing of cables to catenary shall not exceed 1200 mm spacing. Catenary wire shall not be
supported on false ceiling suspension.
Vertical runs of all cables shall be supporting at spacing not exceeding 1500 mm.
Catenary wire shall not be used as an earthing conductor.
Cables shall be installed above ducts, pipes and other building components which may become
dislodged and cause interference to the cables.
Where necessary, cabling installed under such services shall be rated as WS33.
Minimum cable size for light and power shall be 2.5 mm
2
.
All cabling shall be concealed, unless stated otherwise. Unsheathed cables can only be installed
in conduit.
6.A.5.3 Mineral Insulated Metal Sheathed (MIMS) Cable
MIMS cable shall be installed by qualified tradesmen suitably skilled in this work. Installation shall
be to manufacturer's recommendations. MIMS cables shall be fitted with cold seal pots, suitable
glands, sleeving lugs and saddles. Support with copper saddles shall be spaced at maximum 600
mm centres. MIMS cable shall be 1kW 1kV grade. ESR system shall be approved. Sheath shall
be copper.


Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 22 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.5.4 Fire Rated Cables
Fire rated cables shall be of the approved circular type.
Colour of sheath shall be red.
Cables shall be of the 90C temperature rated type or higher.
Installation shall generally be similar to that of PVC cables.
6.A.5.5 Bus Ducts
Bus ducts shall generally be used for mains cabling and for demand in excess of 1600A per
phase. Easy installation of bus duct over acceptable route shall be provided for maintenance and
extension. Acceptable bus duct manufacturers are Square "D" and Pyrotenax or equivalent.
6.A.5.6 Cable Termination
Cable termination lugs shall be installed on all conductors except where tunnel terminals are
provided on equipment. Lugs shall be copper installed with a ratchet type crimping tool. Sub-
mains earth cables (including cables of 4 mm
2
and above) shall be terminated to approval with
locking nuts.
6.A.5.7 Final Sub-Circuit Connection
Subject to the size and loading for a given circuit as required by the Wiring Regulations the
maximum number of points per 2.5 mm
2
circuit shall be as follows:
Lighting
25 (typical 2 x 36 W luminaires) or not more than 2.0 kW connected load.
Power
6 (single Switched Socket outlets in non-air conditioning building).
12 (single Switched Socket outlets in air conditioning building).
Note: Subject to specialised areas where equipment load demands are low and are considered
permanent, the number of points can be extended. The total connected load of the equipment for
that power circuit shall not exceed 70% of the rated protective device. Typical situations are
switch socket outlets for computer laboratories and classrooms. Ensure that these switch socket
outlets numbered and with their circuit identification.
Individual circuit for each item of permanently connected equipment.
Individual circuit for each 15 A switched socket outlet.
Combined lighting and power in a circuit will not be permitted.
Wiring to permanently connected appliances which vibrate or may be moved shall have
terminating conductors protected by flexible conduits of length as short as possible.
Wiring to permanently connected static equipment which is unlikely to be moved in service, except
by skilled tradesmen, shall have terminating conductors protected by screwed steel or rigid uPVC
conduit to suit the particular application.
Refer to clause 06.04 for isolators required for permanently connected equipment.
Each final sub-circuit shall be installed with earth cable directly connected to their respective
distribution switchboard earth bar and labelled. Common earth cable with tee off will NOT be
permitted.
6.A.5.8 Voltage Drop
Voltage drop between the point of supply and the last connected equipment at its worst case shall
be limited to a maximum of 5%. Voltage drop shall be not more than 2% between the point of
supply to distribution switchboards or control assemblies.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 23 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.5.9 Derating of Cables
Generally, groups of cables shall be installed to avoid derating as far as practical. Sub-mains
cables including parallel cables installed shall be adequately spaced on cable ladder or cable tray
to avoid derating.
6.A.5.10 Tee-Off Boxes
Tee-off boxes, as required for connection of sub-mains shall be provided with fuses or links.
Construction shall be for easy access of the equipment from the front. Tee-off boxes shall be of
the approved type.
6.A.5.11 Power Factor
Equipment installed in buildings shall maintain a power factor not less than 0.9 lagging. Where
installed equipment is found to be less than 0.9 lagging, such rectification will not be a variation to
the contract and at no cost to RMIT.
6.A.5.12 CASCADING AND DISCRIMINATION
Fuses and devices installed in a system shall cascade and discriminate with the upstream
protective unit. Further to the requirement of clause 03.03, the minimum protective device for
distribution switchboards (and load centres) servicing final subcircuits, shall be rated at 60 A.
Therefore, all upstream shall provide these similar elements.
6.A.5.13 Conduit Installation
All conduits shall be nominal diameter of approved manufacturer and shall be circular in section.
All conduits shall be installed on the "draw-in loop in" system. No wiring shall be installed until all
the conduits with draw wires have been installed.
All conduits shall be in long lengths, straight. Manufactured bends and tees shall be kept to a
minimum.
Conduits shall be neatly run and securely fastened by means of approved saddles at intervals not
exceeding 600 mm and lesser spacing to eliminate sagging. Saddles shall be provided within 150
mm of all fittings or terminations. All burrs and sharp edges shall be removed from ends and
screwed bushes shall be fitted to the ends of conduit runs.
During installation, the ends of conduits shall be temporarily plugged to prevent the ingress of dirt.
The direction of conduit run shall be parallel to the wall, floors and ceilings, wherever practicable
and no threads shall be visible after erection other than running joints.
Running threads shall be thoroughly painted with black enamel for enamelled conduit and with
aluminium paint for galvanised conduit.
Conduit shall be installed so as to avoid all mechanical duct systems and other pipe systems and
services, and shall in all cases, be at least 80 mm from heating pipes, and at least 460 mm from
boilers or furnaces.
Surface mounting of conduits is to be avoided and routes are to be discussed with the Project
Manager and Services Project Manager, Construction prior to documenting. In Heritage
buildings Campus Planning is to be consulted and formal approval received prior to
installation.
Where conduits are exposed to view other than plant room shall be given one coat of primer, then
two finishing coats to approval, colour to match surroundings. Where conduits are required to be
painted, approved labelling shall be provided at 3 m intervals.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 24 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
All junctions and draw-in boxes and fittings shall be installed in a true horizontal or vertical plane.
Where boxes are exposed to weather, the lids shall be sealed with an approved gasket. The
boxes shall be of ample size to enable the cables to be neatly diverted from one conduit to
another without undue cramping.
All conduits shall be provided with expansion joint as required.
Where conduits are run concealed, the following shall apply:
Conduits Cast in Concrete
Conduits shall be installed above the bottom re-reinforcing bars.
Termination shall be in deep pattern junction boxes for ceiling outlets embedded in concrete
and/or steel wall boxes for all flush wall outlets and switches.
Subject to the approval of the Structural Consultant, generally conduits shall be installed in the
centre of concrete slabs.
The Services Project Manager, Construction shall be notified on completion of each section of
conduit and prior to pouring of the concrete so that the work may be inspected and marked on "as
built" drawings.
Crossings of conduits shall be avoided if an alternative route exists. Conduits in slabs shall be
spaced apart by not less than 75 mm over the conduit and its fittings.
Where conduits are buried in concrete, plaster, etc., they shall be adequately sealed and
protected during pouring and plastering operations and all necessary precautions shall be taken to
ensure that no movement of conduit, distortion of the walls or fittings occurs during the placement
of reinforcement, concrete, plaster, etc. All damage and movement of conduits shall be made
good at no cost to RMIT. Where expansion or construction joint in the concrete occurs an
expansion joint shall be made in the conduit with flexible couplings to 600 mm on either side.
Conduits Concealed in Plaster
Conduits which are installed within hard plaster or concrete render wall finishes shall be securely
fixed to prevent movement or vibration and to permit a depth of at least 10 mm of plaster or render
to be maintained over the conduit and its fittings.
Where necessary, conduits shall be chased or otherwise recessed into walls to ensure that this
minimum cover is obtained. In no case, however, will chasing exceeding 35 mm of a single brick
wall be permitted. Provide suitable chases during erection of the brickwork.
Rigid UPVC Conduit
Rigid UPVC conduit must be installed in accordance with the earlier clauses covering
requirements for conduits.
All necessary precautions shall be taken during construction to protect the conduits from damage
or movement from position by equipment being used by the Contractor and other trades. In
particular, conduits projecting through floor slabs, walls, etc., shall be adequately protected
against damage.
Rigid UPVC conduit and fittings shall be of unplasticised PVC (UPVC) manufactured to the
relevant Australian Standard.
Heavy duty rigid UPVC conduit shall be used for wiring exposed to view and run underground.
Conduits shall not be installed in areas subject to ambient temperature in excess of 50C.
Conduits shall be fastened to the side of timber batten where installed across rafters or joists in
accessible ceilings.
Rigid UPVC conduit shall be installed so as to enable cables to be "drawn-in" after erection and
boxes to be provided for this purpose.
Screwed fittings shall not be used.
Joints shall be used with an approved solvent cement.
Conduits and fittings damaged during installation or delivery will be condemned and shall be
removed from site.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 25 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Flexible Conduit
Flexible conduit shall only be provided between fixed conduit and equipment which is likely to be
moved or subject to vibration, and its length shall be as short as practical. In no case shall length
of conduit exceed 1200 mm.
Brass or nylon terminators shall be used.
Steel Conduit
Steel conduit shall be galvanised where installed in exterior, plant room, service trenches,
locations subject to dampness or condensation, and areas as required by Regulations.
Wiring system shall be minimum WS33.
Electrical continuity shall be provided, and shall be earthed.
Conduit shall be cut square, threaded with the minimum number of threads being consistent with
the union, painted over the threads with conductive paint, reamed to remove burrs and adequately
terminated into threaded connections with no threads showing after assembly. Seals shall be
provided in all joints.
Fixing at maximum of 1200 mm between centres where installed on surface.
Metal Ducts
The duct shall have a removable metal cover fixed to the troughing by galvanised metal thread
screws with captive nuts located at a maximum of 500 mm centres.
The troughing and covers shall be of sheet steel, minimum thickness 1 mm and shall be free from
rags, burrs and sharp edges.
Electrical continuity shall be provided and earthed.
Mitred corners shall be provided with earth cable connections.
Edges and cut-outs shall be provided with gaskets securely fixed to the duct.
Manufacturer's bends, tees, adaptors, coupling pieces, etc., must be used, except where specials
may be required and all bends and tees, etc., must be radial or flat throat pattern.
Where specials are required they shall be manufactured to the same standard and finish as
specified for cable ducting and trunking including standard accessories.
All duct work shall run neatly and squarely on all walls, ceilings, etc. The ducts shall also be
installed so as to be inconspicuous by running in corners, etc., and parallel to wall and ceiling
edges. They shall be installed in such a manner that the demountable covers are accessible, and
shall be adequately supported and the means of support shall be adequate to support an
additional load of 70 kg at midspan without permanently deforming the duct.
The metal ducts shall be supported by approved means at a maximum of 1200 mm centres.
All metal ducts and covers shall be given one coat of zinc chromate primer, then two finishing
coats of enamel to approval. Metal ducts are not acceptable for use in locations exposed to the
weather.
Cables installed in vertical ducts shall be adequately supported by cleating to the enclosure at
intervals not exceeding 1500 mm. In no case shall deflection exceed 10 mm.
Retaining clips shall be installed to support wiring where the removable cover is on the lower side
of the duct.
A spare space of 50% shall be provided in any duct enclosure.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 26 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Plastic Ducts
Generally, the requirements for this clause shall be similar to metal ducts including the following:
Plastic ducts shall be grey colour of rigid UPVC plastic moulded troughing with removable covers
of the clip-on type. The troughing and covers shall be robustly constructed from heavy gauge
material to avoid sagging between supports and to avoid warping.
Ducts shall be supported by approved means at a maximum of 600 mm centres.
Rigid UPVC ducts shall not be used where exposed to mechanical damage, weather and
temperatures above 50C or moisture.
Cable Trays
Cable trays shall be perforated sheet steel electro-zinc plated with a minimum of 40% of its
surface area open for air circulation.
Manufacturer's standard bends, risers, curves reducers and fishplates shall be used.
Edges shall be folded type.
Trays shall be fixed to approved steel brackets and hangers with deflection not exceeding 10 mm
when fully loaded with consideration to future installation of cables.
Installed parallel or at right angles to the building structure and planning grids.
Trays shall be sized to allow for multi run of different sets of cable including spare capacity.
A spare space of 50% of installed capacity shall be provided.
Trays shall be electrically continuous and shall be earthed at one end.
Sharp edges shall be avoided and at tray ends bushing or grommeting shall be provided.
Where practical, cable trays shall be mounted at a height not less than 2300 mm above finished
floor level and installed above other services.
Adequate access shall be provided to cable trays; a minimum of 300 mm above the tray and 600
mm on one side of the tray for future installation of cables.
Cable Ladder
The method of installation and general requirements shall be similar to that for cable trays.
Approved type ladder shall generally be used for mains and sub-mains. Ladders exposed to
weather shall be provided with lids secured by mechanical means. All parts of ladder shall be
galvanised, including hangers and brackets.
6.A.6 LUMINAIRES AND INSTALLATION
6.A.6.1 General
The level of illumination on the working plane shall be in accordance with the requirements of A.S.
1680. Over illumination shall be discouraged. Particular areas nominated for specialised
requirements will be identified by the user and the appropriate lighting levels recommended.
Luminaires shall be manufactured from Australian made components and be approved by the
Supply Authority.
Standard office type luminaires including prototype and emergency luminaires shall have NATA
test report.
Samples including prototypes shall be submitted before final approval.
One sample shall remain on site after approval.
Samples shall be complete with lamps, starters, flexible cable, plug top and supports.
Incandescent lamps shall not be used.
Non-Standard lamps and luminaires shall be used ONLY with prior approval of the Manager,
Engineering and Maintenance Branch.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 27 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
All luminaires shall have appropriate diffusers easily removable and all components shall be easily
accessible for maintenance purposes. Luminaires mounted below 2500 mm above floor level
shall be of the protected or vandal-resistant type. Luminaires required to be dismantled in order to
replace lamps shall not be used. Luminaires shall be high efficiency type and the light output ratio
shall not be less than 60%. Layout design shall satisfy the intensity requirements for open offices
and shall have sufficient flexibility for relocation due to partitioning of individual perimeter or island
offices.
Lobbies, foyers, public thoroughfare and external lighting shall generally be illuminated by high
intensity discharge luminaires.
Mounting of any luminaires greater than 4 m high above floor level that are not easily accessible
shall not be specified or installed. Recommendations to the use of cherry-pickers or scaffolding
for maintenance purposes shall be avoided.
All recessed luminaires shall be provided with 1500 mm PVC flexible cable fitted with plug top.
Luminaires in car parking areas, plant and other services rooms shall be protected type.
In plant rooms, luminaires shall be mounted below services and under no circumstances be
mounted below 2100 mm above floor level. All surface and suspended luminaires shall be
supported at two points. Illumination above these luminaires shall be at least 30% of the
downward component. Luminaires shall be left in a clean, operating and undamaged condition at
the time of Practical Completion. Repair and/or replacement of luminaires which may be
damaged whilst in his charge will not be a variation to the contract.
The number of luminaires incorporating 2 x 36 W fluorescent lamps connected to a final subcircuit
shall not exceed 25 or 2.0 kW of connected load.
Labels shall be provided on all luminaires indicating manufacturer's name, lamp size, and type
number. Labels shall be concealed from normal view.
High level of third harmonics created by luminaires shall be eliminated.
Fuse and fuse carrier shall be provided to all luminaires, combined with their terminal block.
Generally 2 A rated fuse shall be used.
Noise and vibration in all luminaires during operation shall be kept to a minimum.
Where sound pressure levels are deemed unacceptable, luminaires will be replaced at no cost to
RMIT.
6.A.6.2 Fluorescent Luminaires
(Refer also to section 6.4
Further to the general requirements, fluorescent luminaires shall be designed and be suitable for
operation of both 26 mm and 38 mm diameter fluorescent lamps.
Colour temperature shall be better than 3000K (including compact fluorescent lamps).
Nominal lamps life shall be better than 5000 hours.
Lumens output for a 36 W fluorescent lamp shall be minimum 2700 after 100 hours operation.
Maintenance factor of 0.8 shall be considered.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 28 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
In the new generation of lighting and energy conservation, it is recommended where possible,
triphosphor lamps shall be sited, as being the preferred lamp to the standards as described above.
To further enhance the requirement, 28 watt lamps should be considered as its output is
equivalent to 2900 lumens. In all cases glare and uniformity shall be observed to comply with
AS1680.
Different lamp manufacturer throughout the installation shall be avoided, and shall be equivalent to
the existing installed lamps where appropriate.
Compact fluorescent lamps shall be GE Biax or Woltan type. Lamps with overall length greater
than 200 mm, mounted horizontally, shall be supported at the "U" shape end.
The metal chassis of fluorescent luminaires shall be constructed of 0.9 mm thick prime quality,
bright planished sheet steel free from surface blemishes, scale and corrosion. Subject to
approval, a lighter gauge metal could be used if the shape and manufacture of the luminaires
incorporate adequate stiffeners, folds or ribs to prevent warping or sagging. Full details of this
construction shall be submitted with Tender. All seams and joints shall be continuously welded,
ground flat, filled and rubbed smooth. Sharp edges shall be avoided.
Office type luminaires shall be provided with gear tray and/or removable cover for auxiliary
equipment and wiring which shall be separated from the lamp(s) compartment. Auxiliaries shall
be mounted on the back of this cover (reflector) or tray. The reflector shall be fitted with
removable chains or nylon cord to allow for the initial partial lowering of the reflector. It shall be
possible to readily disconnect the wiring and chains, and then completely remove the reflector.
Reflectors and appropriate auxiliary channels shall be securely fixed to the body of the fitting with
a minimum of four screws to prevent sagging. Holes in the metal backplate of the luminaires shall
not be used for the mounting of control equipment and cable assembly. Where required, holes
shall be a minimum. Cable entry holes shall be provided at the centre for wiring and shall be
grommeted or bushed. All other holes shall be filled in to prevent entry of dust, insects and the
prevention of light leakage.
Recessed 2 x 36 W or 2 x 18 W luminaires shall be capable of "back-to-back" installation.
Low brightness louvres and prismatic diffusers can be interchangeable in any typical office type
luminaires. Louvres shall be positioned above lamps. Recessed luminaires, when fixed in
position, shall provide no gap between its body and the ceiling "T" bar or between diffuser and
fitting.
Sagging of diffuser will not be allowed.
The paintwork of fluorescent luminaires shall be applied after all surfaces are thoroughly cleaned
back to the parent metal. Luminaires shall be etch-primed, undercoated and spray painted with
two coats of wet on wet, high reflectivity, gloss acrylic white paint, heat dried to give a total cover
of not less than 0.035 mm thickness to both internal and external surfaces.
Capacitors shall be provided to all luminaires. The power factor shall be not less than 0.9 lagging.
Ballast for fluorescent luminaires shall be provided for each lamp and shall have class H insulation
to copper windings. Minimum spacing between ballasts shall be 75 mm and 100 mm from
capacitor. Unless specified otherwise, ballast shall be suitable for switch-start type with hot loss
operation limited to the following:
Lamp Maximum ballast loss.
Ramp (W) Ballast
7.9 3.5
18 5.5
36 5.5

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 29 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Electronic ballasts and starters, subject to approval, can be used.
Internal wiring of fluorescent luminaires shall be 105
o
C (minimum) 250 V grade, PVC insulated
colour coded cable of minimum 1.0 mm
2
. Cross sectional areas wiring shall be neatly secured
within the luminaires clear of all control gear. Adhesive tape shall not be used for looming and
securing cabling. Terminal block shall be provided mounted adjacent to cable entry and of
adequate size to accommodate these cables and as well, a maximum size of 4 mm
2
conductors.
Terminal block shall be provided with fuse carrier. Wiring exposed shall not be concealed from
where practical, e.g. luminaires with louvres and including removable prismatic diffusers.
Lamp holders shall be suitable for both 26 mm and 38 mm diameter standard fluorescent lamps.
Holders shall be proprietary type of moulded construction with plastic rotor and moulding for lamp
pin separation.
Starter holders shall be fixed in position with screws and nuts and positioned so that starter is
readily removed without removing the gear cover. Non-tracking starters shall incorporate radio
interference suppression capacitor and be capable of 5000 operations, minimum.
Wrap around prismatic lens panels shall be of one piece construction. Appropriate end caps shall
be provided.
Opal diffusers shall not be used.
Prismatic lens shall be injection moulded type.
Metal or plastic type louvres shall generally be the ultra-low brightness suitable for screen-based
task work area.
Such areas will be defined by the user. Louvres shall be of the self cleaning type, without dust
accumulation. Protective gloves shall be used for the installation of these louvres.
6.A.6.3 High Intensity Discharge Luminaires
Chassis shall be substantially fabricated to ensure rigidity. Ferrous components treated to prevent
corrosion and designed to promote adequate cooling. Recessed or high bay type luminaires with
lamp wattage greater than 100W, shall be chain or rod suspended from the upper floor slab with
safety chain. Where ceiling is inaccessible, luminaires shall be provided with a minimum of three
spring adjustable loaded clips for fixing into the ceiling trimming and adjacent remote mounting of
control gear.
Other discharge type recessed down lights shall be mounted with a minimum of two spring
adjustable loaded clips.
Lamp holders shall be E27 (ES) or mogul porcelain type.
Internal wiring of luminaires shall be 1.0 mm
2
stranded copper cable. Glass insulation of class C
shall be used.
Control gear shall include power factor capacitors corrected to not less than 0.9 lagging. Gear
and terminal block shall be an integral part of the luminaires. A 2A class Q1 fuse in a fuse carrier
and base shall be connected. Lamps and/or control gear perceived to show "flicker" shall be
replaced. Preference shall be given to constant wattage type ballast. Luminaires shall be
provided with flexible cable and plug top.
Lamps
Mercury vapour lamps shall be the deluxe white type with 24000 hours average rate life and
nominal colour temperature of 4000K.
High pressure sodium lamps shall be deluxe type with 12000 hours average rated life and nominal
colour temperature of 2200K. Colour rendition (Ra) equivalent to 65.
Metal halide lamps shall be equivalent to Venture pro-arc and super pro-arc lamps. Average rated
life shall be not less than 10000 hours and nominal colour temperature of not less than 3700K.
Double-ended lamps shall not be used.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 30 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.6.4 Extra Low Voltage (ELV) Wiring and Installation
Extra low voltage installation shall be installed only where approved by the Services Project
Manager and have a minimum clearance of 300 mm from any low or medium voltage equipment.
Thermal insulation shall not cover any part (or touching) the ELV installation. Luminaires
mounting and cabling size and length shall be in accordance with the manufacturer's
recommendation. A minimum of 50 mm spacing all round the luminaires shall be free from any
insulation.
Individual transformer of 5% regulation or better shall be provided to each ELV luminaires.
Transformer shall be provided with fuse in the primary circuitry and shall be easily accessible.
Mounting bracket shall be provided to allow for adequate cooling. Laying on plaster board ceiling
space will not be permitted. A permanent label showing the specified lamp wattage shall be
installed on each luminaires. Label shall be clearly visible when lamp is removed.
Where dimming of ELV lamps is required, the dimmer unit shall incorporate the following:
Soft start
Digital control
Halogen clean-up cycle
In-built surge protector
Internal time clock
RF suppression
ELV dimmer shall be selected from the DYNALITE range or similar University approved.
Extra low voltage (12V Dichroic halogen lamp) luminaires shall have nominal average life better
than 3,000 hours. Miniature E.S. type globes are to be specified.
6.A.6.5 Area Lighting Control
The later clauses regarding energy management shall be considered, but the basic lighting control
shall be as follows:
Luminaires located near windows shall be grouped to one switch circuit.
Other areas, control shall be circuited to alternate luminaires.
Security lighting shall generally be provided at corridors and intersections. In large open
areas, spacing should be at every 25 m.
Dimming and/or time switch controls for the dot point items (1) and (2) above shall be
provided.
Plant rooms, corridors, foyers, lobbies and other service areas control shall also be circuited
to alternate luminaires.
Stair lighting, on each floor, shall be time-switch controlled, to the satisfaction of the Building
Code.
One circuit shall be provided for luminaires located on each floor and a separated circuit for
luminaires located on each intermediate landing.
Time switching for corridors, toilets, foyers and lobbies shall be to approval.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 31 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
An economical means of automatically switching OFF luminaires after use in office areas,
lecture theatres, libraries and classrooms shall be considered.
6.A.6.6 Light Switches
Switches shall be a 240 V 15 A rated rocker operation mounted horizontally under a moulded
impact resistance plastic single piece flush plate.
Where four or more switches are located adjacent to each other, they shall be ganged under a
common stainless steel flush plate. Stainless steel plates shall be a minimum of 2.5 mm in
thickness and engraved to indicate the purpose of each switch. Where separate circuits are
provided to this plate, total segregation shall be provided and internally labelled.
Switches shall be located on the lock side of door frames.
In plant rooms, switches shall be protected type. Where located externally and in damp situations,
switches shall be IP55 rating.
In masonry walls, pressed steel wall box shall be provided. Metal bracket shall be fixed to stud
partitions.
Shrouds shall be provided where located within metal door frames, walls or the like.
Circuit number labelling shall be provided.
6.A.6.7 Light Sensitive Switch
Light sensitive switch rated at 20A shall be suitable for switching the controlled lighting systems at
an adjustable illuminance of 10 to 50 lux minimum, incorporate time delay to prevent unwanted
operation during transient lighting conditions. Switch shall be adequately positioned for dusk-to-
dawn operation. This equipment shall be indicated on as built document as appropriate.
6.A.6.8 Time Switches for Lighting
Time switches shall be of the solid state controller suitable for 365 days operation. Operating
functions shall be simple for the programming of the On/Off functions. 20 A contacts and 48hour
battery reserve shall be provided. Time-switches shall be an approved type, located within
switchboard or its vicinity. This equipment shall be indicated on as built document as appropriate.
6.A.6.9 Dimmers
Dimmers shall be rated at 20 A and shall be suitably mounted in an approved position and
secured to avoid unauthorised adjustment. Dimmers shall be suitable for both manual and/or
automatic control. Dimmers shall be solid state controller and where appropriate shall be an
integral part of the intelligent lighting control system.
6.A.6.10 By-Pass Switch
All specialised lighting controls, such as dimmers, time-switches, light sensitive switches shall
incorporate "Manual\Off\Auto" switch.
Switch shall be rated at 20 A and located in an approved position as indicated on the as built
documents. Further to this requirement and in consultation with other clauses, provisions for
voltage free contacts for building monitoring system (BMS) and relays or contactors for energy
management system shall be provided.


Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 32 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.6.11 Emergency Luminaires and Exit Signs
Emergency lighting and exit sign shall be installed throughout the whole building. Where works
are required in a particular level or section of a floor and conditions have changed, that whole floor
shall be provided with emergency lighting and exit signs. Irrespective of a section of floor which
does not require works, this emergency lighting system shall consider the whole area for
compliance. Particular emphasis shall be the path of escape to fire escape stairs, within the stairs
and to the final exit.
Emergency luminaires and exit signs shall be of the single point, self-contained type.
All Luminaires shall contain a mains failure relay and sealed nickel cadmium battery cells.
Batteries shall be rated with a seven years life and guaranteed three years life when operated in
accordance with manufacturer's directions.
All luminaires shall have an automatic two rate battery charger operating with boost and trickle
rate charge.
Red LED indication of charging mode shall be flashing for boost and constant for trickle charge.
Test switch to simulate main failure shall be provided.
Notwithstanding the general requirements, recessed 10 W, tungsten halogen luminaires shall
have classification (Co and C90 planes) shown and labelled on the luminaires and be exposed to
view.
Recessed luminaires with flexible cable, shall have polarised plug top.
Emergency exit signs shall be of the 2 x 10 W fluorescent lamp type with one lamp for emergency
operation and the other lamp for 240 V operation. Sustained emergency luminaires shall not be
used. i.e., emergency luminaires shall not be used for normal lighting.
All emergency luminaires and exit signs shall have NATA test reports and shall be submitted upon
request.
All exit signs shall be installed at a minimum of 2200 mm above floor level to the bottom of the
luminaires. Ensure adequate support to all luminaires.
All luminaires shall be suitable for termination to an automatic computerised maintenance system.
Exit sign luminaires shall be circuited separately from the local distribution board. A lockable 20A
switch on the distribution switchboard shall be provided for the normal control of these exit signs.
Emergency luminaires shall sense power failure in its locality.
In the event of a lighting control system that controls a lighting chassis, the sensing of power
failure shall be most appropriately selected for that particular phase circuit. Phase failure relays
and contractors shall not be used.
Protected type emergency luminaires shall be provided in all toilets.
Further to these requirements, provisions for relays or contractors for energy management system
shall be provided to emergency exit signs luminaires, where in an area the normal illumination is
deemed sufficient to view an exit sign.
In restricted areas where the access by the public is not allowed, exit signs shall generally not be
illuminated. They shall be switched N (the 240V internal lamp when the general lighting in that
locality are switched ON. Such areas are enclosed plant rooms, main switch room and the like.
An automatic and computerised monitoring/maintenance system will be required where more than
50 luminaires are installed and as directed by the Manager, Engineering and Maintenance.
All emergency luminaires and exit signs installed in the computerised system, shall be connected
via a "loop-in and loop-out" system using a two core "figure 8" cable.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 33 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
The system shall incorporate its own battery on mains failure. System shall satisfy all periodic
tests required by A.S. 2293.2 at preselected convenient times and intervals. Malfunction both in
normal and emergency modes of operation shall be reported automatically. This system shall
display and print faults, test results, malfunctions, with reference to dates, time and address of the
relevant luminaires. Green and red LED lamps shall be provided with sound beeper associated
with the red lamp. System shall be adjustable when new luminaires are added or deleted.
Provide approved labelling to emergency luminaires and layout plans of their positions.
The location of the system controller will be subject to the approval.
The system controller should be capable of interfacing with the building monitoring system and/or
energy management system.
Loop wiring system for Communication between luminaires shall be installed in a logical pattern
e.g. floor by floor and section by section. Within fire-rated stairs, wiring can be on separate rising
loop cable. It is recommended that during installation experienced personnel be responsible for
the entire system.
6.A.6.12 Testing, Maintenance and Log Book for Emergency Luminaires
The Emergency Lighting System shall be tested to the satisfaction of the Inspecting Authority and
the Services Project Manager, Construction.
On completion of the installation and just prior to the date of practical completion the Contractor
shall demonstrate the operation of the emergency lighting system by performing the 12 monthly
test as specified in A.S. 2293. A commission test of 120 minutes for all emergency luminaires
shall be carried out 3 days prior to this demonstration.
All units which fail to operate for the required period will be rejected and shall be replaced with
new units which shall be similarly tested in situ. Results of the test at practical completion shall be
recorded in a log book.
During the defects liability period, the Contractor shall perform the six and twelve monthly tests as
specified in A.S. 2293 Part 2 and record the results in the log book and as printed out from the
computer system.
All defects, including replacement of failed lamps during the defects liability period shall be
rectified by the Contractor.
Further to the monitoring system, log book and maintenance manuals for the emergency lighting
system shall be provided. Details shall be as required in AS2293 Part 1 Section 7 and Part 2. In
addition, provide one separate copy of the log book and maintenance manual for the emergency
lighting system in the overall project. The log book and/or maintenance manuals shall comprise:
Hard cover plastic ring binder.
Embossed lettering for project title and manual title on the front cover.
Front page with Project, Subcontractor, Project Architects and Consulting Engineers.
Names and addresses as appropriate.
Index.
Sections as required and separated by indexed section dividers.
Reduced size (A3 or A4) copies of all floor plans showing locations and numbering system
of emergency luminaires and illuminated exit signs. Dedicated plans only for these
systems.
Description and manufacturer's brochures and catalogue number of all emergency
luminaires and illuminated exit signs.
A schedule of all emergency luminaires and illuminated exit signs depicting location,
manufacture, catalogue number, circuit and switchboard origin.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 34 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Log sheets for six and twelve monthly test of functions as described in A.S. 2293 Part 2.
Each luminaire shall be listed in the log sheet and sufficient sheets shall be provided for
recording test results over a 5 year period.
6.A.6.13 Computer Data and Software
Software shall be of the latest issue and be simple to use.
It shall be the responsibility of the Consultant and/or the Contractor to complete the entire
information as required in the software, e.g. room names, floor levels, locations, numbering
system as appropriate. Consultation with the Services Project Manager, Construction and the
Manager, Engineering and Maintenance for the acceptance of such data to be included into the
software and identified in the as built information.
Dedicated plans shall be provided.
6.A.7 OUTLETS AND EQUIPMENT
6.A.7.1 General
All outlets and equipment shall be of approved manufacture and shall be selected to meet the
requirements of the location and function.
Refer to clause 04.04 for the number of points per final sub circuit for Switch Socket Outlets
(SSOs).
All socket outlet mountings shall have the earth pin located at the 6 o'clock position when viewed
from front.
Flush plates for outlets shall be impact resistant plastic moulded, suitably reinforced.
Generally, Switched Socket outlets required in office areas, laboratories, classrooms, and the like
shall be looped locally. SSOs for other equipment such as urns, portable electric heaters and
vacuum cleaners should be on a separate circuit so that tripping will not interrupt the former areas.
In areas where computers are used, SSOs circuit shall not be mixed with other outlets for others
use e.g. looping to SSOs located in corridor or the office areas will not be permitted. Generally
SSOs circuit for computer shall be dedicated.
Unless specific requirements are detailed, allow generally one double switched socket outlet per
8m
2
of net useable space. Academic offices are to be fitted with 4 double SSOs per office. All
outlets shall be white colour and shall be of the same type and manufacture as light switches.
Outlets for three phase supplies shall be installed with full size neutral and earth conductors.
Outlets shall be installed at a suitable mounting height as follows:
On skirting duct (mounting height of duct to be advised).
On walls, not less than 300 mm above finished floor level and as directed.
Plant rooms, services rooms, and damp situations not less than 1200 mm above finished
floor level.
Other areas as directed by the Services Project Manager.
Mixed circuits between lighting, power outlets and fixed item of equipment will not be allowed.
Chain suspended outlets generally will not be accepted but subject to specific requirements.
Wiring and fittings, e.g. SSOs, switches and the like shall not be painted.
Emergency stop buttons where required for the control of switch sockets outlets in a locality shall
be easily accessible. Identification of the switchboard it controls shall be provided. These buttons
shall be a mushroom type with manual reset by a responsible person. Mechanical latching type
shall be provided.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 35 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.7.2 SWITCHED SOCKET OUTLETS (SSOs)
SSOs shall comprise a 10A rocker operated switch and 3-pin plug base with flat pins, flush in a
wall box. All SSOs shall be double pole switching.
Surface mounted outlets shall be installed in a plastic moulded block.
Double SSOs shall comprise two switches and plug bases similarly describe for singles SSO
within a common standard sized flush plate.
Standard service plate shall be 115 mm x 70 mm.
Pressed metal box shall be provided where located in masonry walls. In study partitions, SSOs
shall be fixed to wall bracket.
In plant rooms and machine rooms SSOs shall be of the protected type.
In damp situations and externally located, SSOs shall be IP55 minimum rating.
6.A.7.3 Earth Leakage Protection
Unless specifically stated otherwise and in writing from the Services Project Manager,
Construction, all SSOs shall be protected by earth leakage current operated detector or Residual
Current Device, with a sensitivity of 30mA minimum. Earth leakage circuit breakers (ELCBs)
installed on the distribution switchboard shall be discouraged for the protection of SSOs located in
laboratories, classrooms and similar functional areas. Earth leakage circuit breaker
proposed/installed on the main switch on any distribution switchboard is NOT acceptable.
Equipment that may not need protection are refrigerators and other equipment that are related to
long term food preservation. Electric heaters, fans, hand dryers, urns and the like shall be
protected.
Generally, SSOs incorporating earth leakage protection shall be installed, so that resetting
of the tripped circuit can be operated locally. The first SSOs incorporating the earth leakage
protection device shall be easily located and shall protect other SSOs in its locality. Identification
of such a system shall be provided. Such areas or rooms where protection is installed, a hung
floor plan in a clear Perspex covered frame shall be installed showing SSOs, protective device
and circuits.
6.A.7.4 Three Phase Outlets
There phase outlets shall be heavy duty 415 V triple pole five (5) pin switch socket with spring
loaded flap lid, screw neck and matching plug top. The capacity of the outlet shall be suitable for
the load and shall not be less than 20 A rating. The outlet shall be of impact resistant
polycarbonate or iron clad (galvanised) and shall match other power outlets in the same area.
They shall be of the flush or surface mounted as directed. Provide termination of equipment
supplied by other trades to plug top. Provide the necessary hardware for proper mounting.
6.A.7.5 Permanently Connected Equipment
Permanently connected equipment shall be provided with isolating switch and dedicated circuit for
each item installed. Isolating switch shall be rated as the circuit current rating or better and shall
isolate both conductors. Switch shall be located adjacent to and within 2 m of the equipment at a
height between 300 mm and 1500 mm above floor level unless otherwise directed by the
Manager, Engineering and Maintenance Branch. Such equipment is defined as electric heaters,
fans, package unit air conditioners, motors and the like. Toilet hand dryers and urns, which are
supplied with flexible cables and plug tops, shall each be connected to a dedicated 15 A or 20 A
switch socket outlet as generally described for SSOs. Provide matching plug top as appropriate
and terminate to equipment. Current rating of equipment shall be confirmed before installation.
Equipment, where isolating switches are provided by other trade the Contractor shall provide
termination of cable to this equipment. All final terminations shall be provided and ready for
testing and commissioning by other trades.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 36 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
Where terminations are specifically nominated to be terminated by other trades, leave sufficient
length of cable neatly coiled besides the equipment. Cable ends shall be temporarily sealed and
labelled.
Other permanently installed equipment in remote areas, not easily accessible, requiring SSOs
connections, shall be protected by ELCB or RCD and on separate dedicated circuit(s).
6.A.7.6 Skirting Duct
Skirting duct shall be of the approved type. Certificate of suitability from the Authorities shall be
provided.
Installation shall generally be similar to the clause 04.12 Metal Ducts.
Skirting duct shall be electrically continuous and bends shall be properly mitred. End plates shall
be provided. Skirting duct shall be separately earthed to the local distribution board.
Front cover plates shall be screw fixed to the duct in a continuous threaded section.
A separate short length lid outlet section die punched to received a flushed SSO, telephone outlet
or computer outlet shall be provided.
Colour shall be grey.
Skirting duct shall be secured to walls at 750 mm centres and shall be installed at a spacing of 50
mm between the bottom of the duct and the finished floor level, carpets and/or benches.
All holes or cut-outs for cable entry shall be provided with grommet securely fixed in position.
It is expected that skirting duct is dedicated to power circuits only. Separate similar duct shall be
used for Communication cable.
Where combined two channel duct is proposed, ensure that "RCDed" SSOs are easily installed on
the duct without modification of the SSO or the installation of mounting block. Ensure acceptability
by RMIT Computer and Communication Centres.
6.A.8 MARKING AND LABELLING
6.A.8.1 General
All equipment supplied and installed shall be identified by marking or labelling to the approval of
the Manager, Engineering and Maintenance Branch. Characters shall generally be 5 mm
(minimum) high for most equipment and 10 mm (minimum) high for major equipment such as main
switchboard, distribution switchboard names and as directed.
Engraved traffolyte plastic laminate with bevelled edges shall be provided with black characters on
white background, except for "Danger" and "Fire Services" which shall be white characters on red
background. Further to the requirements of other clauses, this section of the standard shall also
be complimentary where physical characteristics of the items require marking or labelling is
restricted, other means of labelling shall be provided but subject to the approval of the Services
Project Manager, Construction
Labels shall be attached to the switchboard or equipment by means of machine screws. Self-
tapping screws shall not be used. At least two fixings per label shall be used. Machine screws
securing labels in position shall be inserted into holes tapped in the equipment, or alternatively
through clearance holes with each screw backed with a nut and locknut. In either case screws
shall not project further than is necessary to provide a secure fixing.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 37 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.8.2 Switchboards
Labels shall be provided to indicate function of main controls, sub-main controls, relays, fault
current limiters, links, contactors, relays, starters, switches and current rating of fuses. For back-
connected switchboards, labelling shall be provided at the back of main and sub-mains controls.
MEN point, as applicable, shall be identified.
A line diagram of all main switchboard connections and controls shall be mounted in a clear acrylic
windowed frame located adjacent to the switchboard.
Circuit breakers in distribution boards shall be numbered via plastic circular tags, colour coded
pinned to the escutcheon.
Neutral and earth terminals shall similarly be labelled.
6.A.8.3 Luminaires
Labels shall be of the photo sensitive aluminium "Letraset" type, securely fixed onto the chassis of
the luminaires. Where physical characteristics of the luminaires restricts the installation, transfers
may be used and shall be approved. Transfers shall be suitably factory printed, gum backed,
varnish faced and after fixing shall be given one coat of an approved clear, non- yellowing type of
lacquer so as to provide permanent protection to the transfer.
6.A.8.4 Switches and Power Outlets
Engraved labels fastened by two pins to switches and outlets shall indicate appropriate
switchboard, circuit number and any special grade of power to which they are connected. Plastic
circular tags, with flat circular head engraved with circuit number and pinned to the flush plate or
face of the switch or power outlet shall be approved.
IPA studs, where approved, shall be securely fixed to the body of the outlet.
6.A.9 ENERGY MANAGEMENT
6.A.9.1 General
Power and lighting systems shall be installed to assist the conservation of energy with a view to
minimising energy consumption and thus, running costs. Further to the basic controls and
techniques as described in the various sections of this standard, further methods of decreasing
consumption shall be considered and incorporated into a project. (Refer also to Section 4 Energy
Management). A system shall be provided so that the monitoring of equipment, hardware, meters
shall be an open protocol. Future installation of meters shall not constitute another software or
closed system.
6.A.9.2 Lighting Control
The control of lighting shall generally be described in clauses 05.05 to 05.11 including the normal
control of emergency exit signs.
Subject to the approval, luminaires located near windows where natural sunlight is available, shall
be automatic dimmer controlled. (Note: natural sunlight can provide illumination to the work area
up to a horizontal distance equal to twice the height of its window.)
In any typical room where illumination level is designed at 350 lux average or as recommended in
AS 1680, the dimmer system shall control the levels from 100% to 40%. The dimmer controller
shall be located in the distribution switchboard cupboard, or in a secured location.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 38 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.9.3 Air Conditioning and Heating Units
Individual air conditioning unit shall be provided with local "On/Off" push button control, and shall
also be provided with time switch control. Co-ordinate with other services for the installation of a
seven day time switch. Upon switching "Off" by the time-switch, the local push button control shall
automatically be in the "Off" position. All heaters shall be provided with time-switch and local
isolator, similarly installed as for air conditioners.
Fans shall be similarly installed.
6.A.9.4 Building Management Systems
The Services Project Manager, Construction in consultation with Manager, Engineering and
Maintenance will advise the installation of a building management system in the project.
Generally, the management system shall monitor the functions and consumption of the electrical
services. The remote "On/Off" operation of any equipment shall be incorporated into the
monitoring system.
The following shall be provided:
Main Switchboard
All the functional units of the main switchboard shall be monitored and shall include the busbar
zones for temperature rise of the incoming and outgoing sections.
Transducers, voltage free contacts relays, contactors and other equipment shall be installed for
future installation of monitoring cables. Refer to clause 02.02 for its requirement.
Distribution Switchboards
The lighting zone of all distribution switchboards shall be monitored and shall also be remotely
controlled via the energy management system. Contactors, relays will be installed in the future for
energy management. Links shall presently be installed. Provision of 300 mm wide x 600 mm high
space shall be provided in cupboard for future mounting of equipment.
Cabling Access
Cabling access and routes for energy management and building monitoring system shall be
provided. Penetrations of 200 mm x 100 mm shall be provided on all floors.
Monitoring of Other Systems
Other systems, such as fire alarms, emergency warning and intercommunication systems, lift
installation shall be monitored. Provisions of relays, contactors shall also be allowed for future
installation of cables.
Generally, monitoring systems will have a minimum spare capacity of 50%.
6.A.10 MISCELLANEOUS WORK
6.A.10.1 Security Of Equipment
Keys
All keying shall be compatible to RMIT standard keys e.g. all switchboards shall be keyed to
420PL, and/or as directed.
Ensure correct keying to other items with the University Locksmith.
Security Systems or access control system where required will be directed in association with the
Security Manager.
Refer also to Section 10, Electronic Security.
Due to a high level of vandalism, equipment supplied or otherwise shall be protected and well
secured.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 39 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.10.2 Radio Interference
In the event of such interference being detected in the system installation, rectification shall be
provided without cost to RMIT.
6.A.10.3 Heaters, Package Air Conditioning Units and Equipment
Equipment rated at more than 2kW shall be installed with star/delta starters or appropriate auto-
transformer starter. Refer to standard clause 06.04 for permanently connected equipment.
6.A.10.4 Existing Installation
Any extension to existing installation shall be compatible and equivalent.
6.A.10.5 Clocks
In a major project, a master clock system shall be similar to that installed in the campus/ building.
Generally clocks are required in all classrooms, laboratories, passage ways and as directed by the
Manager, Engineering and Maintenance Branch. In minor projects, clocks can be single point
type, or extended to the existing master system.
The master clock system shall be of the wireless type with each clock complete with a radio codes
receiver unit to allow automatic synchronisation with a radio time code signal or GPS system
The clock shall be HX-800 series, Telechron Smart Clocks from HPM Technologies or approved
equivalent.
Preference shall be given to analogue clocks and they shall have:
nominal 300 mm diameter,
red sweep second hand and;
white dial with black numerals or numeral markers and black hour and minute hands.
The mounting height of all clocks shall generally be 2410 mm above floor level. All clocks shall be
aligned and securely fixed in position with anti theft mounting brackets
6.A.10.6 Power Outlets Services Poles
All outlets shall not be suspended by chain or other movable supports. All outlets shall be
securely fixed. Where required on "island" workbench, tables and the like, approved services
poles or equivalent shall be provided. Colour shall be white, or to match the surrounding.
6.A.10.7 Power Outlets Locations
Notwithstanding users requirements for the number of SSOs in educational rooms and offices, the
general requirements are as follows:
Toilets: one double SSO for every two wash basins.
Kitchen: two double SSOs above bench spaced apart (extra outlets are required for other
equipment).
Passageway: one SSO at a spacing of not more than 20 m apart.
Electrical and Telecom cupboards: one SSO per cupboard.
Plant rooms: minimum of one, 3 phase 20 A outlet and two SSOs.
6.A.10.8 Computer Wiring and Audio-Visual Wiring
In all renovations and new projects discuss with RMIT's I.T.S. Group and Facility Services, the
requirement of computer wiring, ducts, dedicated riser shaft and connection to the existing centre.
Ensure skirting duct is compatible. As an option, two separate ducts are recommended.
Electrical supply to computer equipment and air conditioning units shall be cabled from the main
switchboard respectively.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 40 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.10.9 Telephone Services
Refer to Section 8 Communications and co-ordinate with the Communication Services Department
for the installation of telecommunication block cabling to be connected to the existing PABX in
Building 10, City Campus.
6.A.10.10 Surge Protection
Where required surge protection shall be provided on main switchboard or distribution
switchboards. Protection shall be provided for areas in PABX, computer rooms and specialised
areas.
6.A.10.11 Master Antenna Television System (MATV)
In a major project, and upon direction by the Services Project Manager, Construction, a MATV
system shall be installed. Tests shall be extensively carried out before and after installation. Final
testing shall be witnessed by the Manager, Engineering and Maintenance. All outlets shall be
tested, to the satisfaction of the Services Project Manager, Construction.
6.A.10.12 Lightning Protection
For any major project, as assessment for the requirement of lightning protection shall be provided.
An outline of the assessment whether required or not shall be provided in writing.
6.A.10.13 Earthing
The electrical installation shall be adequately earthed to ensure effective protection to the Building
& Occupants in accordance with the relevant current Australian Standards (AS/NZS 3000: 2000)
6.A.10.14 Existing Documents
RMIT, engineering and Maintenance are currently providing master document of emergency
lighting system and the major electrical systems for the whole campuses. It is proposed that any
refurbishment works that affect these master documents shall be upgraded.
Individual documents submitted will not be approved. All other documents shall also be upgraded.

Design Standards Brief Section 6 - Electrical Services


Property Services Construction Section 6 Page 41 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
Appendix 6.A (Cont)
6.A.11 TESTING, COMMISSIONING AND MAINTENANCE
6.A.11.1 General
All systems whether mentioned in detail or not, shall be tested and commissioned before practical
completion.
A maintenance period, which includes defects liability period shall be provided for 12 months after
practical completion. An agreed retention fee will be released after the warranty period.
Maintenance manual and/or log books shall be provided before the issue of practical completion.
All necessary arrangements and/or applications shall be made for the full permanent power to be
connected before the date of practical completion.
Sub-mains, controls and associated items for equipment and systems installed by others shall be
connected so that these services may be tested.
Prior to testing, details of proposed test methods shall be submitted to the Services Project
Manager, Construction and the Manager, Engineering and Maintenance for approval.
6.A.11.2 As Built Documentation
At practical completion of all contracts the following documents shall be handed to the Services
Project Manager, Construction:
3 sets Electrical Specifications.
3 sets Electrical Maintenance Manuals including other associated systems.
3 sets of "as built" Electrical Drawings, and one dyeline set.
3 sets of as built Computerised Emergency Lighting System
3 sets Schedules of all equipment giving make, supplier and specifications.
as specified in the other sections of this specification.
Operating instructions and the like, shall be comprehensively incorporated.
Notwithstanding the above, where CAD system or similar systems are used for documentation of
all services, a copy of such document shall be issued to the RMIT Property Services (Refer
Section 1.8.14.)
As built documentation for emergency lighting system shall specifically include:
data of luminaires installed, location, supply circuit, numbering, legend and typical
connection diagram
full technical data including lamp information
maintenance schedule for step by step six and twelve monthly tests
location of control panel (computer)
details of the operation of the computer system
log book as for non-central computer system to be included.

Section 6 - Electrical Services Design Standards Brief


Property Services Construction Section 6 Page 42 Issue No. 5, January 2003

Copyright RMIT University, Melbourne, Australia 1997
ALL RIGHTS RESERVED
APPENDIX 6.B:
OPERATING AND MAINTENANCE MANUALS SCHEDULE
OF CONTENTS
1. Description

2. Operating Procedures and Equipment Schedules

2.1 General Description
2.2 Main Switchboard
2.3 Distribution Board
2.4 Lighting
2.5 Emergency Lighting
2.6 Communications (Note: A separate bound manual is required)
2.7 Dimming
2.8 EWIS
2.9 Fire Detection
2.10 MATV
2.11 Movement Detectors
2.12 Security
2.13 Skirting Duct
2.14 Controls
2.15 Audio Visual

3. Suppliers and Subcontractors

4. Maintenance

5. Drawings

6. Manufacturers Literature

7. Commissioning

8. Certificates

9. Warranties

Você também pode gostar