PLANT ROOM - SECONDARY CHW PUMP
1
On/Off Command
2 Run Status
3 High current Alarm
4
Chilled water common supply temp
5
Chilled water common return temp
6 Outside Air Temperature Monitoring
7 Outside Air RH Monitoring
8 Sec Pump Controller Common fault monitoring
9 Sec Pump Controller Common On/Off Command
10 VFD Integration
11 Secondary Pump's VFD Speed Feedback
12 Secondary Pump's VFD Frequency
13 Secondary Pump's VFD Current
14 Secondary Pump's VFD Voltage
15 Secondary Pump's VFD Power
16 Secondary Pump's VFD Run Time
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
16 Secondary Pump's VFD Run Time
B AHU
1 On/Off Command
2 Run Status
3 Auto Manual status
4 Trip Status
5 Filter status
6 Supply Air Temperature Monitoring
7 Return Air Temperature Monitoring
8 Valve Modulation
9 VFD control Signal
10 VFD modulation using diff press transmitter
(Location of Diff. pressure sensor to be in SA Duct within AHU room
itself)
11 VFD soft integration
12 AHU's VFD Speed Feedback
13 AHU's VFD Frequency
14 AHU's VFD Current
15 AHU's VFD Voltage
16 AHU's VFD Power
17 AHU's VFD Run Time
C FAHU
1 of 6
A
SITE ENGR QC ENGR
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
1 Supply Air Temperature Monitoring
2 Temperature After Heat Recovery
3 Exhaust Temperature before heat recovery
4 Ambient temperature Monitoring
5 Temperature After Heat wheel
6 Supply Fan Run Status
7 Supply Fan Trip Status
8 Exhaust Fan Run Status
9 Exhaust Fan Trip Status
10 HW Motor Run Status
11 HW Motor Trip Status
12 Filter before HW on Exhaust
13 Pre Filter Fresh Air
14 Bag Filter Fresh Air
15 FAHU Start/Stop
16 HOA Switch
17 Valve Modulation
18 VFD control Signal
19 VFD modulation using diff press transmitter
20 VFD soft integration
21 AHU's VFD Speed Feedback
22 AHU's VFD Frequency
23 AHU's VFD Current
24 AHU's VFD Voltage
25 AHU's VFD Power
26 AHU's VFD Run Time
E FCU FOR COMMON AREAS
1 Space Temperature
2 Space Temperature Setpoint
3 FCU Valve Modulation
4 FCU On/Off Command
5 FCU Fan High Speed Command
6 FCU Fan Medium Speed Command
7 FCU Fan Low Speed Command
II FANS
A SMOKE EXTRACT FAN
1 `Auto' position of H/O/A switch
2 Fan trip alarm
2 of 6
A
SITE ENGR QC ENGR
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
3 Fan Start/Stop Command
4 Fan run status
5 FA signal
D CAR PARK JET FANS
1 `Auto' position of H/O/A switch
2 Fan trip alarm
3 Fan run status
E EXTRACT FAN (DUAL SPEED)
1 `Auto' position of H/O/A switch
for Fire + Normal Starters
2 Fan trip alarm
Fire Mode + Normal Mode
3 Fan run status
Fire Mode + Normal Mode
F EXTRACT FAN (SINGLE SPEED)
1 `Auto' position of H/O/A switch
2 Fan trip alarm 2 Fan trip alarm
3 Fan run status
IV PUBLIC HEALTH ENGINEERING
A TRANSFER PUMP
1 H/O/A Switch in auto position
2 Run Status
3 Trip Status
4 On/Off Command
B SUMP PUMP
1 Unit Fault status
2 Run Status
3 Auto Manual Status
D FIRE WATER TANK (3 Bsmt + 3 Terrace)
1 Tank Level
2 High/Low Level Alarm
3 Water Flow Meter
V FIRE FIGHTING SYSTEM
A FIRE FIGHTING PUMP
3 of 6
A
SITE ENGR QC ENGR
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
1 Pump auto-manual status
2 Pump run status
3 Trip Status
B JOCKEY PUMP
1 Pump auto-manual status
2 Pump run status
3 Trip Status
C DIESEL ENGINE PUMP
1 Pump auto-manual status
2 Pump run status
3 Trip Status
VI ELECTRICAL SYSTEM
A LV PANEL 1
Incoming breaker
1 ON/OFF Status of each main incoming breaker
2 Trip alarm indication of main incoming breaker
3 Breaker Trip Command
Outgoing breaker
1 ON/OFF Status of each main outgoing breaker
2 Trip alarm indication of main outgoing breaker
3 Breaker Trip Command
B LV PANEL 2
Incoming breaker
1 ON/OFF Status of each main incoming breaker
2 Trip alarm indication of main incoming breaker
3 Breaker Trip Command
Outgoing breaker
1 ON/OFF Status of each main outgoing breaker
2 Trip alarm indication of main outgoing breaker
3 Breaker Trip Command
C LV PANEL 3
Incoming breaker
1 ON/OFF Status of each main incoming breaker
2 Trip alarm indication of main incoming breaker
3 Breaker Trip Command
Outgoing breaker
1 ON/OFF Status of each main outgoing breaker
4 of 6
A
SITE ENGR QC ENGR
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
2 Trip alarm indication of main outgoing breaker
3 Breaker Trip Command
D ESMDB
Incoming breaker
1 ON/OFF Status of each main incoming breaker
Outgoing breaker
2 ON/OFF Status of each main incoming breaker
E MCC - B
Incoming breaker
1 ON/OFF Status of each main incoming breaker
F EMCC - B
Incoming breaker
1 ON/OFF Status of each main incoming breaker
G SMDB - B
Incoming breaker
1 ON/OFF Status of each main incoming breaker
H MCC - PUMP
Incoming breaker
1 ON/OFF Status of each main incoming breaker 1 ON/OFF Status of each main incoming breaker
I MCC SUMP PUMP
Incoming breaker
1 ON/OFF Status of each main incoming breaker
J MCC ETS
Incoming breaker
1 ON/OFF Status of each main incoming breaker
K SMDB - G
Incoming breaker
1 ON/OFF Status of each main incoming breaker
Q SMDB UPS
Incoming breaker
1 ON/OFF Status of each main incoming breaker
V MCC FF
Incoming breaker
1 ON/OFF Status of each main incoming breaker
Y TRANSFORMERS
1 Signals for monitoring
2 Signals for monitoring
Z HT PANELS/BREAKERS
1 Signals for monitoring
2 Signals for monitoring
AD UPS
5 of 6
A
SITE ENGR QC ENGR
Floor :
RESULT
(OK/NA)
SIGNATURE
REMARKS
INTEGRATED COMMISSIONING REPORT - (FLOOR LEVEL) -BASEMENT FLOOR
Date :
ANC CONTRACTING INDIA LTD
FORMAT NO.
1 O/P Voltage - R
2 O/P Voltage - Y
3 O/P Voltage - B
4 O/P Current - R
5 O/P Current - Y
6 O/P Current - Y
7 Battery Voltage
8 Battery Charge Remaining
9 Frequency
10 Alarm Status
VII PA/ACCESS/CCTV
1 Check of Door Access through Access Cards in Normal & Fire Mode
2 Check for Public Addressing system by Announcing in the console.
Check for Evacuation Message in Fire Mode.
Check for Views of Cameras as per Design requirement
Remarks (if any):