Escolar Documentos
Profissional Documentos
Cultura Documentos
I
n
c
r
e
a
s
e
d
c
o
l
u
m
n
s
i
z
e
t
o
s
u
p
p
o
r
t
f
l
o
o
r
M
e
c
h
a
n
i
c
a
l
c
o
r
e
s
m
u
s
t
e
i
t
h
e
r
b
e
r
a
i
s
e
d
o
r
(
h
a
n
d
i
c
a
p
p
e
d
)
r
a
m
p
i
n
g
i
n
s
t
a
l
l
e
d
S
l
a
b
-
t
o
-
s
l
a
b
h
e
i
g
h
t
i
n
c
r
e
a
s
e
i
f
s
p
a
c
e
f
l
o
o
r
-
t
o
-
c
e
i
l
i
n
g
h
e
i
g
h
t
i
s
t
o
b
e
m
a
i
n
-
t
a
i
n
e
d
C
o
s
t
o
f
t
h
e
r
a
i
s
e
d
f
l
o
o
r
a
n
d
p
r
e
m
i
u
m
f
o
r
c
a
r
p
e
t
t
i
l
e
s
(
v
s
.
r
o
l
l
e
d
c
a
r
p
e
t
)
B
a
s
i
c
S
t
r
u
c
t
u
r
e
C
o
s
t
s
:
N
o
f
i
n
a
l
s
l
a
b
l
e
v
e
l
i
n
g
a
s
f
l
o
o
r
i
s
l
a
s
e
r
l
e
v
e
l
e
d
B
a
s
i
c
S
t
r
u
c
t
u
r
e
C
o
s
t
s
:
S
l
a
b
m
u
s
t
b
e
c
l
e
a
n
e
d
(
a
n
d
t
r
e
a
t
e
d
w
i
t
h
a
n
a
n
t
i
m
i
c
r
o
b
i
a
l
a
g
e
n
t
)
p
r
i
o
r
t
o
f
l
o
o
r
i
n
s
t
a
l
l
a
t
i
o
n
B
a
s
i
c
S
t
r
u
c
t
u
r
e
C
o
s
t
s
:
S
l
a
b
-
t
o
-
s
l
a
b
h
e
i
g
h
t
m
a
y
b
e
r
e
d
u
c
e
d
a
s
H
V
A
C
e
q
u
i
p
m
e
n
t
a
n
d
d
u
c
t
w
o
r
k
a
r
e
r
e
m
o
v
e
d
f
r
o
m
t
h
e
c
e
i
l
i
n
g
p
l
e
n
u
m
R
e
m
o
v
a
l
o
f
H
V
A
C
e
q
u
i
p
m
e
n
t
f
r
o
m
o
v
e
r
h
e
a
d
p
l
e
n
u
m
m
a
y
e
l
i
m
i
-
n
a
t
e
n
e
e
d
f
o
r
f
a
l
s
e
c
e
i
l
i
n
g
P
o
w
e
r
/
V
o
i
c
e
/
D
a
t
a
S
e
r
v
i
c
e
C
o
s
t
s
:
P
o
w
e
r
/
V
o
i
c
e
/
D
a
t
a
S
e
r
v
i
c
e
C
o
s
t
s
:
P
o
w
e
r
w
i
r
i
n
g
u
s
e
s
h
o
m
e
r
u
n
p
o
w
e
r
m
o
d
-
u
l
e
s
t
h
r
o
u
g
h
o
u
t
t
h
e
s
p
a
c
e
t
o
r
e
d
u
c
e
c
a
b
l
i
n
g
r
e
q
u
i
r
e
m
e
n
t
s
F
l
o
o
r
o
u
t
l
e
t
b
o
x
e
s
i
n
e
a
c
h
w
o
r
k
s
t
a
t
i
o
n
e
l
i
m
i
n
a
t
e
t
h
e
n
e
e
d
t
o
e
l
e
c
t
r
i
f
y
f
u
r
n
i
t
u
r
e
M
o
d
u
l
a
r
p
l
u
g
s
i
n
o
u
t
l
e
t
b
o
x
e
s
r
e
d
u
c
e
t
h
e
r
e
q
u
i
r
e
d
c
o
n
n
e
c
t
i
o
n
t
i
m
e
f
o
r
P
V
D
s
e
r
v
i
c
e
s
I
n
s
t
a
l
l
a
t
i
o
n
c
o
s
t
s
a
r
e
r
e
d
u
c
e
d
d
u
e
t
o
t
h
e
e
a
s
e
o
f
w
o
r
k
i
n
g
a
t
f
l
o
o
r
l
e
v
e
l
C
o
n
d
u
i
t
c
o
s
t
s
m
a
y
b
e
s
i
g
n
i
f
i
c
a
n
t
l
y
r
e
d
u
c
e
d
o
r
e
l
i
m
i
n
a
t
e
d
i
f
p
l
e
n
u
m
r
a
t
e
d
c
a
b
l
e
i
s
u
s
e
d
P
o
w
e
r
/
V
o
i
c
e
/
D
a
t
a
S
e
r
v
i
c
e
C
o
s
t
s
:
P
o
w
e
r
/
V
o
i
c
e
/
D
a
t
a
S
e
r
v
i
c
e
C
o
s
t
s
:
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
135
H
V
A
C
S
y
s
t
e
m
C
o
s
t
s
:
H
V
A
C
S
y
s
t
e
m
C
o
s
t
s
:
H
V
A
C
S
y
s
t
e
m
C
o
s
t
s
:
T
h
o
r
o
u
g
h
s
e
a
l
i
n
g
o
f
c
o
m
p
o
n
e
n
t
s
/
s
u
r
-
f
a
c
e
s
t
h
a
t
c
o
m
p
o
s
e
t
h
e
u
n
d
e
r
f
l
o
o
r
s
u
p
-
p
l
y
p
l
e
n
u
m
A
d
d
i
t
i
o
n
o
f
d
u
c
t
s
o
r
a
i
r
h
i
g
h
w
a
y
s
t
o
e
n
s
u
r
e
p
r
o
p
e
r
d
e
l
i
v
-
e
r
y
o
f
t
h
e
c
o
n
d
i
-
t
i
o
n
e
d
a
i
r
t
h
r
o
u
g
h
t
h
e
u
n
d
e
r
f
l
o
o
r
p
l
e
-
n
u
m
H
i
g
h
e
r
d
i
f
f
u
s
e
r
c
o
s
t
d
u
e
t
o
i
n
c
r
e
a
s
e
d
q
u
a
n
t
i
t
y
a
n
d
r
e
l
a
-
t
i
v
e
l
y
h
i
g
h
e
r
c
o
s
t
(
$
/
c
f
m
)
o
f
t
h
e
o
u
t
-
l
e
t
s
A
d
d
i
t
i
o
n
a
l
s
m
o
k
e
d
e
t
e
c
t
o
r
s
f
o
r
u
n
d
e
r
-
f
l
o
o
r
p
l
e
n
u
m
S
p
e
c
i
a
l
a
i
r
h
a
n
d
l
e
r
s
w
i
t
h
b
y
p
a
s
s
H
V
A
C
S
y
s
t
e
m
C
o
s
t
s
:
R
e
d
u
c
t
i
o
n
(
o
r
e
l
i
m
i
n
a
t
i
o
n
)
o
f
h
o
r
i
-
z
o
n
t
a
l
(
b
r
a
n
c
h
)
d
u
c
t
w
o
r
k
f
e
e
d
i
n
g
t
e
r
m
i
n
a
l
u
n
i
t
s
R
e
d
u
c
t
i
o
n
o
f
(
r
e
c
t
a
n
g
u
l
a
r
a
n
d
f
l
e
x
i
-
b
l
e
)
d
i
s
c
h
a
r
g
e
d
u
c
t
w
o
r
k
a
n
d
d
a
m
p
-
e
r
s
R
e
d
u
c
t
i
o
n
o
f
r
e
q
u
i
r
e
d
t
h
e
r
m
a
l
i
n
s
u
-
l
a
t
i
o
n
a
s
s
u
p
p
l
y
a
i
r
p
a
s
s
e
s
t
h
r
o
u
g
h
a
n
a
l
r
e
a
d
y
c
o
n
d
i
t
i
o
n
e
d
p
l
e
n
u
m
R
e
d
u
c
e
d
o
u
t
l
e
t
b
a
l
a
n
c
i
n
g
r
e
q
u
i
r
e
-
m
e
n
t
s
a
s
m
o
s
t
d
i
f
f
u
s
e
r
s
a
l
l
o
w
o
c
c
u
-
p
a
n
t
a
d
j
u
s
t
m
e
n
t
E
l
i
m
i
n
a
t
i
o
n
o
f
r
a
d
i
a
t
i
o
n
d
a
m
p
e
r
s
o
n
s
u
p
p
l
y
o
u
t
l
e
t
s
R
e
d
u
c
t
i
o
n
i
n
t
h
e
n
u
m
b
e
r
o
f
r
e
q
u
i
r
e
d
t
e
r
m
i
n
a
l
u
n
i
t
s
(
e
s
p
e
c
i
a
l
l
y
i
n
i
n
t
e
r
i
o
r
z
o
n
e
s
)
R
e
d
u
c
e
d
n
u
m
b
e
r
o
f
s
p
a
c
e
t
h
e
r
m
o
-
s
t
a
t
s
a
n
d
a
s
s
o
c
i
a
t
e
d
w
i
r
i
n
g
a
s
t
h
e
n
u
m
b
e
r
o
f
t
e
r
m
i
n
a
l
u
n
i
t
s
a
r
e
r
e
d
u
c
e
d
P
o
t
e
n
t
i
a
l
r
e
d
u
c
t
i
o
n
i
n
r
e
t
u
r
n
o
u
t
l
e
t
s
i
f
f
a
l
s
e
c
e
i
l
i
n
g
i
s
e
l
i
m
i
n
a
t
e
d
R
e
d
u
c
e
d
i
n
s
t
a
l
l
a
t
i
o
n
c
o
s
t
s
a
s
w
o
r
k
i
s
d
o
n
e
a
t
f
l
o
o
r
l
e
v
e
l
P
o
s
s
i
b
l
e
r
e
d
u
c
t
i
o
n
i
n
a
i
r
-
h
a
n
d
l
i
n
g
u
n
i
t
s
i
z
e
a
n
d
c
a
p
a
c
i
t
y
(
w
h
e
r
e
d
e
s
i
g
n
a
i
r
f
l
o
w
q
u
a
n
t
i
t
y
c
a
n
b
e
r
e
d
u
c
e
d
)
T
a
b
l
e
1
0
.
1
a
:
C
o
s
t
C
o
n
s
i
d
e
r
a
t
i
o
n
s
f
o
r
t
h
e
A
d
d
i
t
i
o
n
o
f
R
a
i
s
e
d
F
l
o
o
r
a
n
d
U
F
A
D
S
y
s
t
e
m
s
:
F
i
r
s
t
C
o
s
t
s
(
C
o
n
t
i
n
u
e
d
)
CHAPTER 10COST CONSIDERATIONS
136
T
a
b
l
e
1
0
.
1
b
:
C
o
s
t
C
o
n
s
i
d
e
r
a
t
i
o
n
s
f
o
r
t
h
e
A
d
d
i
t
i
o
n
o
f
R
a
i
s
e
d
F
l
o
o
r
a
n
d
U
F
A
D
S
y
s
t
e
m
s
:
L
i
f
e
-
C
y
c
l
e
C
o
s
t
s
A
d
d
i
t
i
o
n
o
f
R
a
i
s
e
d
F
l
o
o
r
S
y
s
t
e
m
F
u
r
t
h
e
r
A
d
d
i
t
i
o
n
o
f
U
F
A
D
S
y
s
t
e
m
T
y
p
i
c
a
l
C
o
s
t
A
d
d
s
T
y
p
i
c
a
l
C
o
s
t
R
e
d
u
c
t
i
o
n
s
T
y
p
i
c
a
l
C
o
s
t
A
d
d
s
T
y
p
i
c
a
l
C
o
s
t
R
e
d
u
c
t
i
o
n
s
U
t
i
l
i
t
y
C
o
s
t
s
:
U
t
i
l
i
t
y
C
o
s
t
s
:
U
t
i
l
i
t
y
C
o
s
t
s
:
U
t
i
l
i
t
y
C
o
s
t
s
:
R
e
d
u
c
e
d
f
a
n
o
p
e
r
a
t
i
o
n
a
l
c
o
s
t
d
u
e
t
o
l
o
w
e
r
f
a
n
s
t
a
t
i
c
p
r
e
s
s
u
r
e
s
P
o
s
s
i
b
l
e
r
e
f
r
i
g
e
r
a
t
i
o
n
p
l
a
n
t
o
p
e
r
a
t
i
o
n
a
l
c
o
s
t
s
a
v
i
n
g
s
d
u
e
t
o
i
n
c
r
e
a
s
e
d
c
h
i
l
l
e
r
e
f
f
i
c
i
e
n
c
y
u
s
i
n
g
w
a
r
m
e
r
r
e
t
u
r
n
w
a
t
e
r
E
x
t
e
n
d
e
d
e
c
o
n
o
m
i
z
e
r
c
y
c
l
e
o
p
e
r
a
t
i
o
n
d
u
e
t
o
h
i
g
h
e
r
s
u
p
p
l
y
/
r
e
t
u
r
n
a
i
r
t
e
m
p
e
r
a
t
u
r
e
s
M
a
i
n
t
e
n
a
n
c
e
/
O
p
e
r
a
-
t
i
o
n
C
o
s
t
s
:
M
a
i
n
t
e
n
a
n
c
e
/
O
p
e
r
a
t
i
o
n
C
o
s
t
s
:
R
e
d
u
c
e
d
c
a
r
p
e
t
r
e
p
l
a
c
e
m
e
n
t
c
o
s
t
s
r
e
s
u
l
t
i
n
g
f
r
o
m
u
s
e
o
f
r
e
p
l
a
c
e
a
b
l
e
c
a
r
p
e
t
t
i
l
e
s
R
e
d
u
c
t
i
o
n
o
f
w
o
r
k
s
t
a
t
i
o
n
r
e
l
o
c
a
t
i
o
n
a
n
d
/
o
r
s
e
r
v
i
c
e
r
e
c
o
n
f
i
g
u
r
a
t
i
o
n
c
o
s
t
s
d
u
e
t
o
m
o
d
u
l
a
r
c
a
b
l
i
n
g
a
n
d
e
a
s
i
l
y
m
o
v
a
b
l
e
P
V
D
s
e
r
v
i
c
e
b
o
x
e
s
M
a
i
n
t
e
n
a
n
c
e
/
O
p
e
r
a
t
i
o
n
C
o
s
t
s
:
M
a
i
n
t
e
n
a
n
c
e
/
O
p
e
r
a
t
i
o
n
C
o
s
t
s
:
R
e
d
u
c
e
d
f
a
i
l
u
r
e
s
o
f
c
o
n
t
r
o
l
c
o
m
p
o
n
e
n
t
s
d
u
e
t
o
r
e
d
u
c
t
i
o
n
o
f
t
e
r
m
i
n
a
l
u
n
i
t
s
R
e
d
u
c
e
d
c
a
l
l
s
t
o
m
a
i
n
t
e
n
a
n
c
e
r
e
g
a
r
d
i
n
g
c
o
m
-
f
o
r
t
c
o
m
p
l
a
i
n
t
s
d
u
e
t
o
i
n
c
r
e
a
s
e
d
l
e
v
e
l
o
f
i
n
d
i
-
v
i
d
u
a
l
c
o
n
t
r
o
l
C
a
s
h
F
l
o
w
R
e
l
a
t
e
d
I
n
t
a
n
g
i
b
l
e
s
:
C
a
s
h
F
l
o
w
R
e
l
a
t
e
d
I
n
t
a
n
g
i
b
l
e
s
:
P
o
s
s
i
b
l
e
a
c
c
e
l
e
r
a
t
e
d
d
e
p
r
e
c
i
a
t
i
o
n
o
n
a
c
c
e
s
s
f
l
o
o
r
a
n
d
c
a
r
p
e
t
(
n
o
n
-
f
i
x
e
d
a
s
s
e
t
s
)
C
a
s
h
F
l
o
w
R
e
l
a
t
e
d
I
n
t
a
n
g
i
b
l
e
s
:
C
a
s
h
F
l
o
w
R
e
l
a
t
e
d
I
n
t
a
n
g
i
b
l
e
s
:
P
o
s
s
i
b
l
e
r
e
d
u
c
t
i
o
n
i
n
i
n
s
t
a
l
l
a
t
i
o
n
t
i
m
e
o
f
H
V
A
C
s
y
s
t
e
m
r
e
d
u
c
e
s
t
o
t
a
l
c
o
n
s
t
r
u
c
t
i
o
n
t
i
m
e
a
n
d
e
n
a
b
l
e
s
e
a
r
l
i
e
r
o
c
c
u
p
a
n
c
y
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
137
10.1 STANDARD FIRST COST COMPONENTS
Components labeled as standard are considered to be a required
or integral part of the installation of a UFAD system.
10.1.1 Raised Floor System
The raised floor system is the component with the single largest
cost increase of a UFAD system over a conventional air distribution
system. Like any other building component, the cost of raised flooring
can vary depending upon program requirements, location (shipping),
union or non-union labor, and size of the project. Since a raised floor
system forms an integrated service plenum that serves cabling, HVAC,
and other distribution needs, assigning the entire cost of the floor instal-
lation to the HVAC system alone is unwarranted. Instead, the cost jus-
tification for raised floor systems should be based on the benefits of the
entire (HVAC, power, voice, and data) service delivery system. The
percentage of new raised floor office buildings using UFAD has
increased significantly in recent years and is now near 40% [Hockman
2002]. The added first cost of the raised floor system must be weighed
against other first cost savings and the flexibility and reduced costs
associated with reconfiguring building services over the lifetime of the
building. As discussed below, normally not all of the total floor plate
area will be covered by an access floor system on any given floor of an
office building.
10.1.2 Slab Modification and Preparation
At the service core of a building, where restrooms, kitchenettes, and
elevators are located, it has been common to omit a raised floor. How-
ever, raised floors can be used in the core area as well with added ben-
efit and reduced cost. In particular, the cost of installing plumbing,
including the setting of traps, has the potential to be reduced. Previ-
ously, a raised concrete core was poured in these areas in order to
accommodate the difference in floor height between the service core
and the finished raised floor level in the surrounding area. The raised
concrete core is an expensive unit addition, although it represents a rel-
atively small fraction of a buildings floor area. In office buildings, the
core consumes anywhere from 3% to 4% of a given floor plate. The
HVAC and elevator vertical services typically account for about 4% to
5% of the floor plate. Conversely, raised flooring systems are leveled
during installation, eliminating the necessity (and associated costs) of
adding a finishing level to the floor.
CHAPTER 10COST CONSIDERATIONS
138
10.1.3 Cleaning and Sealing the Plenum
The cost of cleaning and sealing the underfloor plenum is directly
linked to the scheduling of the overall project (see Chapter 8). This is
an add-on cost compared to conventional systems and can become
larger than expected if mistakes are made. It is imperative for the
project to be extremely well organized, as there is a long list of con-
struction activities that would require a duplicate cleaning of the ple-
num prior to final placement of the finished raised floor surface.
10.1.4 Fire Detection and Sprinkler Systems
The cost variables of fire safety systems will vary according to the
local code requirements. If the raised floor is above a certain height,
typically 18 in. (0.46 m), the code may require a sprinkler system. For
this reason, many UFAD jobs limit the height of the underfloor plenum
to less than 18 in. Local inspectors often require a smoke detection sys-
tem in the plenum area. The fire safety cost components will not affect
all underfloor projects. It will depend on the local jurisdiction. The sig-
nificance of this category has much more to do with code requirements
and interpretation and less with the design of the underfloor system.
10.2 DESIGN-DEPENDENT FIRST COST COMPONENTS
Building components whose costs are more likely to change with
the choice of a UFAD system are labeled as design-dependent.
10.2.1 UFAD System Design
A very preliminary assessment shows that total costs for HVAC are
in the range of $10-15/ft
2
($110-160/m
2
) (~60% core and 40% tenant
improvement (TI)), which is roughly 10% of the total building cost.
Generally, the core HVAC costs will remain about the same for both
UFAD and overhead systems. Therefore, the primary difference will be
in TI costs, about $4-6/ ft
2
($43-65/m
2
) or 4% of total building costs.
This suggests that small differences in HVAC costs may not have a
large impact on the overall costs and differences from traditional sys-
tems. Other system design-dependent factors that affect TI HVAC costs
are described below.
10.2.1.1 Diffuser Type. Diffuser costs will be largely depen-
dent on the choice of diffusers for the interior zones of the building,
accounting for the majority of air delivery for a given floor plan. The
cost of perimeter zone diffusers, often linear grilles or variable-air-vol-
ume (VAV) diffusers, makes up a relatively small portion of total dif-
fuser costs. Although plastic diffusers have been the most commonly
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
139
installed to date, code officials in some jurisdictions may interpret cur-
rent fire code language to require metal diffusers because of the fire/
smoke danger with plastic material. This can increase the cost of dif-
fusers by as much as 35%. Also, automatic VAV diffusers and active
(fan-driven) diffusers are generally more expensive than passive (man-
ually controlled) diffusers. If a furniture- or partition-based TAC dif-
fuser is selected, installed costs may also be higher. The added first cost
and operating costs (fan energy use) of active floor or TAC diffusers
must be traded off against the improved personal control of local air-
flow provided to a nearby occupant.
10.2.1.2 System Category. Constant air volume (CAV) vs.
variable air volume (VAV) are the two predominant categories used
some systems use a combination of the two. The category will impact
the types and complexity of terminal devices used in perimeter and core
areas. How perimeter zone heating is accommodated will also impact
costs, but the cost differences between heating methods may be small
unless it includes electrical vs. hot water.
10.2.1.3 Underfloor Plenum Ductwork and Partitioning.
The extent that air highways and/or ducting and partitioning are used
for distribution and zoning must be compared to the typically large
amount of ductwork required for overhead air distribution in traditional
designs. If a relatively open underfloor plenum configuration can be
used, greater savings in the amount of required ductwork can be real-
ized. The range of cost savings associated with the elimination of over-
head ductwork is usually enough to offset a significant portion of the
added cost of the raised floor system.
10.2.1.4 Controls. These costs may not be significantly
affected if the basic zoning used for traditional systems is preserved in
the UFAD system design.
10.2.2 Cable Management Systems
Access floor systems provide a convenient platform for managing
cable systems that meet the demands of modern office space. With the
latest trend toward structured cabling, all telecommunications func-
tions power, data, and audio/video are contained within a single wir-
ing infrastructure. Although first costs of structured cabling will be
higher than standard cabling, installation costs can be significantly
reduced (working at floor level instead of up in the ceiling plenum),
resulting in a net savings in overall cabling first costs. The flexibility
of these integrated plug-and-play cabling systems makes them well
suited for office spaces with high churn rates. In terms of efficiency and
low-cost operation/maintenance, when structured cabling is installed
CHAPTER 10COST CONSIDERATIONS
140
as part of a raised floor system, in-house personnel using simple tools
and standardized connector pieces can easily carry out reconfiguration.
By comparison, traditional cabling systems consist of fixed outlets,
connections, and long cable runs for which changes usually involve
contracting outside labor and considerable disruption within the work-
place (see Section 10.3.1 on churn).
In open plan offices with partitioned workstations, a second cabling
cost consideration is the need for electrified workstations with built-in
cable management systems. By delivering power, voice, and data
cabling directly to virtually any location on the floor plate, raised floor
systems can allow non-electrified partitions and furniture to be
installed. Although there is a large range in price of workstations and
personal furniture, electrified furniture can cost as much as 20% more
than non-electrified equivalents.
10.2.3 Floor-to-Floor Heights
With the use of an underfloor system, the heights from slab-to-slab
have the potential to be reduced as much as 6 in. to 1 ft (0.15 to 0.3 m)
per floor. The amount of reduction is dependent on the structural and
plenum design of the baseline conventional building. Concrete flat
slab construction can be especially effective at reducing floor-to-floor
heights in comparison to standard steel beam construction. This new
dimension correlates to a reduction of up to about 7% in vertical struc-
tural, thermal, and mechanical components. The reduced area of the
curtain wall can be an important cost factor. The savings associated
with this component will primarily apply to high-rise office building
construction. It can be an important cost consideration in high-rise
development where building heights are limited by local building
codes.
10.2.4 Ceiling Finishes and Acoustical Treatment
If air distribution and power and data cabling are installed under the
floor, it opens up other design options for finishing the ceiling, includ-
ing the elimination of the suspended ceiling tiles and plenum space
above. In most cases, acoustical treatment of some kind will still be
needed on the ceiling, particularly with the documented reduced
mechanical noise levels for UFAD systems. Designing for acceptable
acoustical privacy in open plan offices is challenging enough, and if the
masking noise typically available with traditional HVAC design is
absent, careful attention must be paid to this issue.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
141
10.3 LIFE-CYCLE COST COMPONENTS
Life-cycle cost components include those building elements whose
costs are affected over the lifetime of the building and represent the pri-
mary means by which building owners can expect to receive a greater
return on their initial investment.
10.3.1 Churn (Reconfiguration)
In modern businesses, churn is a fact of life; a 1997 survey found
the national average churn rate (defined as the percentage of workers
per year and their associated work spaces in a building that are moved,
reconfigured, or undergo significant changes) to be 44% [IFMA 1997].
The cost savings associated with reconfiguring building services is a
major factor in the decision to install access flooring. By integrating a
buildings HVAC and cable management systems into one easily acces-
sible underfloor plenum, floor diffusers, along with all power, voice,
and data outlets, can be placed almost anywhere on the raised floor grid.
In-house maintenance personnel can carry out these reconfigurations at
significantly reduced expense using simple tools and modular hard-
ware. The amount of savings from churn is directly dependent on three
variables, whose value may vary from building to building and from
organization to organization: (1) annual churn rate, (2) cost savings of
moves and reconfigurations per worker (large differences exist
between simple moves and moves requiring renovation), and (3)
amount of floor area per worker. Firms that are more likely to install
underfloor systems are also, for the very same reasons, more likely to
churn at a higher rate.
10.3.2 Operation and Maintenance
The primary elements of operation and maintenance costs are: (1)
the salaries of operations personnel required to service and maintain the
HVAC system and to respond to occupant complaints, (2) replacement
costs for equipment, and (3) energy costs. Any differences in commis-
sioning costs between UFAD systems and traditional systems should
also be considered. It may be difficult to obtain long-term maintenance
cost data for UFAD systems since experience with these systems is lim-
ited in U.S. buildings. Some engineers believe that equipment mainte-
nance costs for raised floor-based systems will be slightly higher than
those for conventional systems. However, research suggests that the
frequency of occupant complaints will be reduced when occupants are
given some individual control over their local environment [Bauman et
al. 1998]. Most practicing engineers agree that UFAD systems have the
potential to save energy in comparison to traditional designs. To date,
CHAPTER 10COST CONSIDERATIONS
142
energy use data are only available on a project-by-project basis. Energy
costs are difficult to predict since no reliable whole-building energy
simulation tools are currently available that accurately model UFAD
system performance (see Chapter 14).
10.3.3 Tax Savings
Under some circumstances, raised flooring and other movable com-
ponents have the potential to qualify as personal property. As a seven-
year property, its cost could be depreciated at a favorable rate compared
to standard flooring systems, which would normally be 39-year prop-
erty. Seven-year property qualifies for double declining balance depre-
ciation, while 39- year property depreciates at a slower rate and over a
longer period of time. This potential savings should be investigated
carefully and will be largely dependent on tax law interpretations.
10.3.4 Increased Property Value and Rents
It is well documented that office tenants are willing to pay a pre-
mium for office space possessing the amenities they prefer. Naturally,
market conditions will continuously fluctuate, but in assessing the real
premium (if any) paid for a raised floor system, a secondary consider-
ation is the premium that tenants are willing to pay for space with raised
flooring. If raised flooring can be directly linked to increased rents and
sales prices, the first cost of a raised floor system may be inconsequen-
tial by comparison.
10.3.5 Productivity and Health
Research indicates that occupant satisfaction and productivity can
be increased by giving individuals greater control over their local envi-
ronment and by improving the quality of indoor environments (ther-
mal, acoustical, ventilation, and lighting). Improved ventilation and
thermal environments, which well-designed UFAD systems can pro-
vide, have also been associated with a reduction in the prevalence or
severity of adverse indoor health effects [Fisk 2000]. The financial
implications of improving productivity or reducing absenteeism
caused by illness by even a small amount have the potential to be very
large as employee salary and benefits costs typically make up at least
90% of all costs (including construction, operation, and maintenance)
over the lifetime of a building. Nationwide, a mere 1% increase in
worker productivity would translate into a potential annual cost benefit
of $25 billion. In todays competitive world economy, a companys
employees make up its most valuable economic assets. Protecting and
improving the productivity of these employees will have a strong influ-
ence on future investments.
143
Chapter 11
Standards, Codes,
and Ratings
Since UFAD technology is relatively new to the building industry,
its characteristics may require consideration of unfamiliar code
requirements and, in fact, may be in conflict with the provisions of
some existing standards and codes. Applicable standards should be
reviewed carefully; revisions and exceptions that are more compatible
with UFAD technology will likely be forthcoming as additional
research results are obtained. Local building codes and the interpreta-
tions of local officials should be considered early in the design process
of a building using underfloor air supply plenums. Experience has
shown that the first UFAD project in an area governed by an unfamiliar
jurisdiction will usually end up establishing the ground rules for code
interpretations on future projects.
Listed below are brief discussions of the applicable building stan-
dards and codes that have important provisions related to the design,
installation, and operation of UFAD systems. In addition, a brief
description of the LEED (Leadership in Energy & Environmental
Design) Rating System is provided.
11.1 ANSI/ASHRAE STANDARD 55-1992: THERMAL ENVI-
RONMENTAL CONDITIONS FOR HUMAN OCCUPANCY
[ASHRAE 1992]
Earlier versions of Standard 55 were based on the assumption of a
well-mixed and uniformly conditioned environment. UFAD systems,
however, usually involve greater variability of thermal conditions over
both space and time. The effect of providing occupant control has not
been fully taken into account, although it is well established that occu-
pants will tolerate greater fluctuations in environmental conditions if
they have control over them. The rather strict air velocity limitations
CHAPTER 11STANDARDS, CODES, AND RATINGS
144
that were specified in the previous version of Standard 55 were incom-
patible with the increased local air velocities that are possible with
UFAD and task/ambient conditioning (TAC) systems. The current ver-
sion of ASHRAE Standard 55 [ASHRAE 1992] was revised to allow
higher air velocities than the previous version of the standard, if the
occupant has control over the local air speed. Figure 3 in Standard 55-
1992 (reproduced in Figure 11.1) was added to show the air speed
required to offset increases in temperature above those allowed in the
summer comfort zone. For example, Figure 11.1 indicates that at equal
air and radiant temperatures (tr ta = 0), a local air speed of 150 fpm
(0.75 m/s) can offset a temperature rise of about 4.4F (2.4C) for a pri-
marily sedentary building occupant wearing 0.5 clo. The figure is based
only on sensible heat transfer; total cooling would be expected to be
higher if latent effects are taken into account.
Standard 55-1992 also specifies allowable air speeds as a function
of air temperature and turbulence intensity with the objective of avoid-
ing unwanted drafts when the occupant has no direct local control. At
warmer temperatures, however, occupants will desire additional cool-
ing. Increased air movement (and turbulence) is an easy way of achiev-
ing such direct occupant cooling. Standard 55-1992 allows these
velocity limits, based on turbulence intensity level, to be exceeded if the
occupant has control over the local air speed.
Figure 11.1 Air speed required to offset increased temperature
[ASHRAE 1992].
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
145
11.2 ANSI/ASHRAE STANDARD 62-2001: VENTILATION FOR
ACCEPTABLE INDOOR AIR QUALITY [ASHRAE 2001b]
Standard 62-2001 provides guidelines for the determination of ven-
tilation rates that will maintain acceptable indoor air quality. This most
recent version of Standard 62 allows some adjustment in ventilation
rates based on the ventilation effectiveness (E
v
) of the air distribution
system. Mixing-type air distribution systems can at best achieve a per-
fectly mixed space, defined as having an E
v
of 1.0, as determined in
accordance with ASHRAE Standard 129 (see below). By definition,
mixing-type systems cannot provide preferential ventilation (E
v
> 1),
in which some credit could be obtained for improved air change effec-
tiveness at the breathing level in the space.
Displacement ventilation systems that deliver supply air at low
velocity near floor level and extract air at ceiling level are known to pro-
vide improved ventilation effectiveness in the occupied zone (see
Chapter 2). This performance characteristic is being addressed more
specifically in the newest addendum of Standard 62 [ASHRAE 2003]
in which default values for E
v
are recommended for different air dis-
tribution system configurations and modes of operation. These values
can and should be used to determine required outdoor air quantities if
it is decided to not measure E
v
directly. The recommended values of E
v
are (1) 1.2 for displacement ventilation system, (2) 1.0 for an overhead
system in cooling mode, and (3) 0.8 for an overhead system in heating
mode (known to cause shortcircuiting). UFAD systems are not explic-
itly addressed since more definitive research on ventilation effective-
ness is still needed, but it is expected that E
v
for UFAD with floor
diffusers will be less than or equal to 1.2 but higher than 1.0. Research
has shown that E
v
for personally controlled TAC diffusers can be sig-
nificantly higher than 1.2 when the supply air is directed toward the
occupants breathing level [Faulkner et al. 2002; Melikov et al. 2002].
It has not yet been determined how to apply these elevated performance
numbers for TAC diffusers in Standard 62, since ventilation perfor-
mance will change when an individual moves away from their local air
supply or decides to turn it off.
Standard 62-2001 sets minimum ventilation rates for office space
and conference rooms at 20 cfm (9.4 L/s) per person and reception
areas at 15 cfm (7.1 L/s) per person. In the design and operation of TAC
systems containing a large number of occupant-controlled supply mod-
ules, some means must be provided to ensure that minimum ventilation
rates are maintained, even when people choose to turn off their local air
supply.
CHAPTER 11STANDARDS, CODES, AND RATINGS
146
11.3 ANSI/ASHRAE/IESNA STANDARD 90.1-2001: ENERGY
STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESI-
DENTIAL BUILDINGS [ASHRAE 2001c]
ASHRAE Standard 90.1 describes requirements for the energy-
efficient design of new buildings intended for human occupancy. In
Section 9.5.2, the prescriptive criteria for zone controls state that there
can be no simultaneous operation of heating and cooling systems to the
same zone. Some of the unique aspects of UFAD and TAC systems may
be in conflict with this requirement. For example, if occupants have
control of supply air temperature for heating or cooling from their local
diffusers, situations may occur in which some people are requesting
heating and others are requesting cooling at the same time within the
same zone. In another example, with underfloor air distribution con-
figured to have fan coil units in the perimeter fed from cool plenum air
from the interior zone, if there is a call for heating, this will require local
reheating of the underfloor supply air to satisfy the heating demand (see
Title 24 below for further discussion). These and other relevant situa-
tions should be carefully considered as there are exceptions to the cri-
teria described in Standard 90.1 and perhaps subtle differences in the
operation of UFAD and TAC systems compared to a conventional over-
head air distribution system.
11.4 ANSI/ASHRAE STANDARD 113-1990: METHOD OF TEST-
ING FOR ROOM AIR DIFFUSION [ASHRAE 1990]
ASHRAE Standard 113-1990 is the only currently available build-
ing standard for evaluating the air diffusion performance of an air dis-
tribution system. The current version of Standard 113, however, is
based on the assumption of a single uniformly mixed indoor environ-
ment, as provided by a conventional overhead air distribution system.
This assumption is not appropriate for evaluating the performance of
UFAD and TAC systems that deliver conditioned air directly into the
occupied zone of the building through supply outlets that are in close
proximity to and under the control of the building occupants. UFAD
and TAC systems, therefore, not only promote thermal stratification in
the space but also may actually encourage other nonuniformities
between workstations. Efforts are now underway to revise Standard
113 to include new methods of performance evaluation that are appli-
cable to air distribution systems that deliver air directly into the occu-
pied zone of the building, including UFAD, TAC, and displacement
ventilation systems.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
147
11.5 ASHRAE STANDARD 129-1997: MEASURING AIR
CHANGE EFFECTIVENESS [ASHRAE 1997]
ASHRAE Standard 129-1997 describes a test method for evaluat-
ing an air distribution system's ability to provide required levels of ven-
tilation air to the building occupants. The results of the tests may be
used to determine compliance with ASHRAE Standard 62. If this test
method demonstrates that enhanced ventilation effectiveness is pro-
vided at breathing level by a UFAD or TAC systems, then credit may
be taken by reducing the required outdoor air quantity accordingly.
11.6 TITLE-24: CEC SECOND GENERATION NONRESIDEN-
TIAL STANDARDS [CALIFORNIA ENERGY COMMISSION
2001]
The CEC Nonresidential Standards (Title-24) defers to applicable
ASHRAE standards in most cases. Title-24 does, however, address a
few areas that should be taken into consideration in the operation of
UFAD systems in California. Title-24 mandates off-hour controls for
central HVAC systems and stipulates that the largest sized zone that can
be controlled in isolation is 25,000 ft
2
(2,300 m
2
). In buildings with
large floor plates, this size limitation will require that the underfloor
plenum be divided into smaller zones using underfloor partitions or
other suitable means. Local fire codes may require that the plenum be
divided into considerably smaller zones.
Title-24 addresses simultaneous heating and cooling, particularly
in relation to variable-air-volume (VAV) system operation. When
changing over from cooling to heating in a zone, the supply volume
must first be reduced to 30% of peak before beginning the heating
cycle. This has implications for UFAD system designs that employ an
open plenum in which variable-speed fan-coil units in the perimeter
draw their primary air from the interior zone of the plenum. On a call
for heating in the winter or early morning, fan speeds in these perimeter
units will need to be reduced. In addition, it may be difficult to meet this
requirement if swirl diffusers are placed in the perimeter zone, since
they will not automatically reduce their cooling supply volume in heat-
ing mode.
The use of electric resistance heating is prohibited according to the
prescriptive method in Title-24 for determining a buildings allowable
energy performance. However, if the alternative computer simulation
method is used to predict a buildings energy performance for compar-
ison with the Title-24 target energy budget, it may be possible to trade
off the use of electric heat with energy savings in other UFAD system
CHAPTER 11STANDARDS, CODES, AND RATINGS
148
components (e.g., improved chiller efficiency or increased economizer
operation).
Title-24 requires thermostatic zone controls with adjustable set-
points. Since TAC systems may maintain temperature differences
between locally conditioned zones (workstations) and unconditioned
or centrally conditioned areas of the workplace (e.g., corridors), atten-
tion should be paid to placing zone controls in representative locations.
In general, Title-24 focuses on the effects of overall systems. As a
result, the integration between the local and central controls should be
carefully considered. The effects of individual thermal preferences on
overall air quality and comfort should also be taken into account.
Although the current version of Title 24 does not specifically
address underfloor air distribution, if enough supporting energy- and
cost-saving data can be obtained, UFAD systems could be added to the
subsequent revision (three-year cycle).
11.7 NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS [NFPA
1999]
NFPA 90A is the most widely used and referenced code in relation
to the installation of HVAC systems. This code contains language writ-
ten several years ago before the widespread introduction of UFAD sys-
tems that, depending on ones interpretation, appears to prohibit or
restrict the application of underfloor air supply plenums. Selected
examples of key language that most frequently come up in the review
of an UFAD installation by code officials are described below.
In the section titled Location of Air Outlets (Section 2-3.6.3.1),
which applies equally to inlets, the code states air outlets shall be
located at least 3 in. (7.6 cm) above the floor. This appears to rule out
the use of floor diffusers; however, an exception is given as where pro-
visions have been made to prevent dirt and dust accumulations from
entering the system. Thus, any floor diffuser without a basket-type
device or other means of collecting dirt and debris located underneath
the access floor surface would not be acceptable. Where linear grille
diffusers, often located in perimeter zones, are specified, an alternative
means of collecting dust/dirt must be provided. In addition, outlets
located less than 7 ft (2.1 m) above the floor must be protected by a
grille or screen through which a -in. (1.3-cm) sphere cannot pass.
Both the collection device and -in. grille spacing requirements are
easily satisfied by most commercially available diffuser models,
thereby complying with the exception identified in NFPA 90A. To fully
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
149
satisfy the intent of the code language to ensure a clean air distribution
system, regular vacuuming of the dust/dirt collection devices should be
included in the maintenance schedule.
In terms of the combustibility of diffusers, Sections 2-3.6.2 and 2-
3.7.2 state that air outlets and inlets shall be constructed of non-com-
bustible material or a material that has a maximum flame spread index
of 25 and a maximum smoke developed index of 50. There has been
considerable debate about the acceptability of diffusers made from
polycarbonate materials, which appear to violate the intent of NFPA
90A. For nearly 20 years several established diffuser models have been
regularly used in UFAD system installations and yet are made from a
plastic material that satisfies the required flame spread index but cannot
comply with the smoke index of 50. One argument commonly put for-
ward in defense of plastic diffusers is that the smoke test protocol
(ASTM E 84, NFPA 255requiring that a large 25-ft [7.6-m] sample
of the material be burned) cannot reasonably be applied to polycarbon-
ate material. In any event, metal diffusers fully comply with NFPA
90A, and designers should proceed cautiously with the use of plastic
materials unless specific exception has been granted by the local build-
ing code authority.
The combustibility of material in the underfloor plenum is also gov-
erned by NFPA 90A in Section 2-3.10.6.
The space between the top of the finished floor and the underside
of a raised floor shall be permitted to be used to supply air to the
occupied area, or return or exhaust air from the occupied area,
provided that the following conditions are met:
1. All materials exposed to the airflow shall be noncombusti-
ble or limited combustible and shall have a maximum smoke
developed index of 50.
An exception is given, however, for materials ranging from electri-
cal wires, cables, and optical fiber cables to raised floor panels and fire
sprinkler piping. In addition to referencing the codes to which each
exempt material must comply, these materials must have a maximum
peak optical density of 0.5 or less, an average optical density of 0.15 or
less, and a maximum flame spread distance of 5 ft (1.5 m) or less when
tested in accordance with the specified test method. Refer to NFPA 90A
for additional conditions relevant to the underfloor plenum. In general,
placing wires and cables in an air supply plenum is not a problem as
long as they are contained in conduit or are rated to be noncombustible.
CHAPTER 11STANDARDS, CODES, AND RATINGS
150
11.8 UNIFORM BUILDING AND OTHER APPLICABLE CODES
Local fire codes sometimes place restrictions on the size of open
supply air plenums without any smoke breaks in the form of partitions
separating the plenum into smaller zones. These fire codes may limit
the total area (e.g., less than 3,000 ft
2
[280 m
2
]) and horizontal dimen-
sion in one direction (e.g., less than 30 ft [9 m]) of an unobstructed
underfloor air supply plenum.
A typical underfloor plenum contains a low level of combustible
materials; thus, in certain codes plenums under 18 in. (45 cm) in height
do not require sprinklers. The issue of whether sprinklers need to be
installed in a plenum is contentious for a number of reasons. First, as
electric cabling is typically the only source of fire risk, water is not the
best source of fire suppression. Also, if fire/smoke detectors are
required by code to be placed within the floor plenum, the question
arises as to the effectiveness of standard detection devices within such
a low-height cavity. Fundamentally, the codes governing underfloor
plenums should be no different than those for ceiling plenums.
11.9 LEED (LEADERSHIP IN ENERGY & ENVIRONMENTAL
DESIGN) RATING SYSTEM
The United Stated Green Building Council (USGBC) established
the LEED rating system with the intent of creating a method to rate the
environmental performance of a building. The system works by assign-
ing points to various design and construction process features.
Depending on the overall number of points a building earns, it can
achieve a Certified, Silver, Gold, or Platinum rating.
The LEED rating system consists of five major categories:
1. Sustainable sites
2. Water efficiency
3. Energy and atmosphere
4. Materials and resources
5. Indoor environmental quality
In each category, there are both prerequisites and credits. For a
building to achieve any level of certification, it must meet the require-
ments of all the prerequisites. Prerequisites earn no points. Each credit
then is assigned a point value or range of point values that can be earned
for the building.
UFAD systems have relevance in the Energy and Atmosphere as
well as Indoor Environmental Quality sections of LEED. In the Energy
and Atmosphere section, Credit 1 allows points for optimizing the
energy performance of a building.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
151
In the Indoor Environmental Quality section of LEED, UFAD sys-
tems can be relevant related to Credit 2Increase Ventilation Effec-
tiveness. As discussed earlier in this section, UFAD systems may have
a higher ventilation effectiveness than overhead systems. Credit 2
requires that the ventilation effectiveness of the installed system be
designed to achieve an E
v
above 0.9 as determined by ASHRAE Stan-
dard 129-1997 for measuring air change effectiveness. Compliance is
demonstrated through testing or by a narrative and calculations
describing how the high-performance system was designed.
153
Chapter 12
Design Methodology
This chapter provides a concise list of issues to be considered, and
decisions to be made, during the design process. For more detailed dis-
cussions and background information, the reader is referred to other
sections of this guide. The focus is on those areas in which the design
of UFAD systems differs from conventional air distribution system
design. For further reading and design guidance, see Spoormaker
[1990], Sodec and Craig [1991], Houghton [1995], McCarry [1995],
Shute [1995], Bauman and Arens [1996], Bauman et al. [1999a], Bau-
man et al. [2000a], and AEC [2000].
12.1 UFAD VS. CONVENTIONAL OVERHEAD
SYSTEM DESIGN
UFAD systems are similar to conventional overhead systems in
terms of the types of equipment used at the cooling and heating plants
and primary air-handling units (AHU). Key differences arise with
UFAD systems in their use of an underfloor air supply plenum, warmer
supply air temperatures into the room, delivery of air in the near vicinity
of occupants (with or without individual control) and the resulting
floor-to-ceiling air flow pattern, and the solutions used for perimeter
systems. In order to successfully employ a UFAD system, it is essential
that the implications of these differences be considered, starting at an
early stage in the design process.
12.2 BUILDING STRUCTURE CONSIDERATIONS
12.2.1 Building Plan
The modularity of all components of raised floor systems can be an
advantage in space planning, particularly over large open plan areas.
CHAPTER 12DESIGN METHODOLOGY
154
Consider the compatibility of anticipated building plan geometries
with the dimensions of the floor grid established by the raised floor sys-
tem.
Raised floor panel dimensions: 24 in. (610 mm) square
Underfloor plenum pedestal spacing: same as floor panels, e.g., 24 in.
(610 mm)
12.2.2 New Construction
In new construction, underfloor air distribution has the potential to
achieve a reduction in floor-to-floor heights compared to projects with
ceiling-based air distribution. This is accomplished by reducing the
overall height of service plenums and/or by changing from standard
steel beam construction to a concrete (flat slab) structural approach. A
single large overhead plenum to accommodate large supply ducts and
other building services can be replaced with a smaller ceiling plenum
for air return and piping for sprinklers combined with a lower-height
underfloor plenum for unducted air flow and other building services
[Kight 1992]. Floor-to-floor heights for overhead systems using steel
beam construction can also be reduced by using beam penetrations for
ducts and other building services. In this comparison, if steel beam con-
struction is used in both designs, floor-to-floor heights should be equal
or lower for UFAD buildings. Significantly reduced vertical height
requirements can be achieved using concrete flat slab construction,
which is usually more expensive than steel beam construction but is
preferred for underfloor systems due to thermal storage benefits. In the
example shown in Figure 12.1, the underfloor/flat slab configuration
allows 10 in. (0.25 m) to be saved in floor-to-floor height compared to
overhead/steel beam system design.
Even greater savings (up to 22 in. [0.56 m]) can be realized if the
ceiling plenum is completely eliminated, exposing the concrete ceil-
ings and providing an opportunity for creative internal design, enhanc-
ing daylighting and artificial lighting effects. However, if the
conventional suspended acoustic tile ceiling is eliminated, leaving an
exposed concrete ceiling or other configuration, careful consideration
must be made of the acoustic and/or lighting quality of the space.
Designers will also need to consider possible conflicts with local codes
(e.g., fire code). High side-wall return is the most common return air
configuration for this exposed ceiling design.
Table 12.1 presents a comparison of typical floor-to-floor dimen-
sions for a midsize (5-10 stories), high-tech class A office building
(assuming a 40-ft clear span between columns). Dimensions are shown
UNDER FLOOR AIR DISTRIBUTION DESIGN GUIDE
155
F
i
g
u
r
e
1
2
.
1
C
o
m
p
a
r
i
s
o
n
o
f
t
y
p
i
c
a
l
f
l
o
o
r
-
t
o
-
f
l
o
o
r
h
e
i
g
h
t
s
f
o
r
c
e
i
l
i
n
g
-
b
a
s
e
d
a
n
d
u
n
d
e
r
f
l
o
o
r
a
i
r
d
i
s
t
r
i
b
u
t
i
o
n
s
y
s
t
e
m
s
.
CHAPTER 12DESIGN METHODOLOGY
156
T
a
b
l
e
1
2
.
1
:
C
o
m
p
a
r
i
s
o
n
o
f
T
y
p
i
c
a
l
F
l
o
o
r
-
t
o
-
F
l
o
o
r
H
e
i
g
h
t
s
B
u
i
l
d
i
n
g
E
l
e
m
e
n
t
S
t
e
e
l
B
e
a
m
C
o
n
s
t
r
u
c
t
i
o
n
w
i
t
h
O
v
e
r
h
e
a
d
A
i
r
D
i
s
t
r
i
b
u
t
i
o
n
S
t
e
e
l
B
e
a
m
C
o
n
s
t
r
u
c
t
i
o
n
w
i
t
h
U
n
d
e
r
f
l
o
o
r
A
i
r
D
i
s
t
r
i
b
u
t
i
o
n
C
o
n
c
r
e
t
e
F
l
a
t
S
l
a
b
C
o
n
s
t
r
u
c
t
i
o
n
w
i
t
h
U
n
d
e
r
f
l
o
o
r
A
i
r
D
i
s
t
r
i
b
u
t
i
o
n
S
t
r
u
c
t
u
r
e
C
o
n
c
r
e
t
e
M
e
t
a
l
d
e
c
k
2
.
5
i
n
.
(
6
5
m
m
)
2
.
5
i
n
.
(
6
5
m
m
)
C
o
n
c
r
e
t
e
M
e
t
a
l
d
e
c
k
2
.
5
i
n
.
(
6
5
m
m
)
2
.
5
i
n
.
(
6
5
m
m
)
C
o
n
c
r
e
t
e
f
l
o
o
r
8
i
n
.
(
2
0
0
m
m
)
S
t
e
e
l
b
e
a
m
F
i
r
e
p
r
o
o
f
i
n
g
2
1
i
n
.
(
5
3
0
m
m
)
2
i
n
.
(
5
0
m
m
)
S
t
e
e
l
b
e
a
m
F
i
r
e
p
r
o
o
f
i
n
g
2
1
i
n
.
(
5
3
0
m
m
)
2
i
n
.
(
5
0
m
m
)
C
o
n
c
r
e
t
e
b
e
a
m
1
2
i
n
.
(
3
0
5
m
m
)
C
e
i
l
i
n
g
p
l
e
n
u
m
2
1
-
2
6
i
n
.
(
5
3
0
-
6
6
0
m
m
)
8
-
1
2
i
n
.
(
2
0
0
-
3
0
5
m
m
)
8
-
1
2
i
n
.
(
2
0
0
-
3
0
5
m
m
)
F
l
o
o
r
-
t
o
-
c
e
i
l
i
n
g
9
f
t
(
2
.
7
0
m
)
9
f
t
(
2
.
7
0
m
)
9
f
t
(
2
.
7
0
m
)
U
n
d
e
r
f
l
o
o
r
p
l
e
n
u
m
1
2
-
1
8
i
n
.
(
3
0
5
-
4
6
0
m
m
)
1
2
-
1
8
i
n
.
(
3
0
5
-
4
6
0
m
m
)
T
o
t
a
l
f
l
o
o
r
-
t
o
-
f
l
o
o
r
h
e
i
g
h
t
1
3
f
t
1
i
n
.
-
1
3
f
t
6
i
n
.
(
4
.
0
-
4
.
1
m
)
1
3
f
t
-
1
3
f
t
1
0
i
n
.
(
4
.
0
-
4
.
2
m
)
1
2
f
t
4
i
n
.
-
1
3
f
t
2
i
n
.
(
3
.
8
-
4
.
0
m
)
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
157
for a conventional overhead system with steel beam construction, and
two UFAD system configurations, one with steel beam and one with
flat slab construction.
Underfloor plenums accommodating both cable/electrical distribu-
tion and an UFAD system are often deeper than those employed solely
for cable management purposes. However, the additional height
required for acceptable airflow performance is not large, based on
recent research results [Bauman et al. 1999a]. Underfloor plenum
heights are usually determined by
largest HVAC components (e.g., fan coil units, terminal boxes,
ducts, dampers) located under the floor,
requirements for underfloor cabling, and
additional clear space for underfloor air flow (usually 3 in. [76 mm]
minimum).
12.2.3 Retrofit Applications
Due to the tremendous size of the existing building stock, retrofit
construction will play an important role in the future for the building
industry. Projects requiring the addition of an HVAC system often
encounter the problem of having limited space for accommodating
ducts and other components. Because of the comparable dimensions
discussed above, UFAD can be quite feasible in retrofit projects. The
most practical retrofit applications will involve (1) buildings with an
existing raised floor system (no UFAD), (2) projects where the existing
air distribution system (typically overhead) will be renovated, and (3)
high ceiling spaces, such as warehouses [Webster et al. 2002c]. The use
of raised floor systems in warehouse type buildings can also eliminate
problems associated with existing uneven slab surfaces. The biggest
challenge with the installation of a raised floor system in an existing
building is that stairs, elevators, bathrooms, and other core facilities
exist at the original floor level. While elevator stops can be reset, other
facilities will usually require steps, ramps, or some other transitional
element.
The installation of a raised floor system can be less disruptive than
that of ducting for overhead systems as the floor can be easily installed,
and removed, as an independent platform leaving relatively few struc-
tural scars. This issue is important in buildings where maintaining the
integrity of the existing building structure is important for heritage/cul-
tural/structural reasons [Guttmann 2000]. Furthermore, installation
CHAPTER 12DESIGN METHODOLOGY
158
can be a relatively dry process, once the concrete structural slab has
been adequately sealed, minimizing damage to other building ele-
ments.
12.3 DETERMINATION OF SPACE COOLING
AND HEATING LOADS
Cooling and heating loads for a building with a UFAD system are
calculated in much the same manner as for a conventional overhead
(OH) system. For more information, see Chapter 29 in the 2001
ASHRAE HandbookFundamentals and Pedersen et al. [1998]. How-
ever, the determination of design cooling air quantities must take into
account key differences between these systems.
12.3.1 Space Cooling Load Calculation
This section discusses the ways that conventional load calculation
methods used for OH systems may be changed to capture performance
characteristics of stratified spaces associated with UFAD systems.
Although not discussed below, cooling loads can also be affected by
heat transferred to the underfloor plenum air supply, either through the
slab from the adjacent return air plenum or through the floor panels
from the room. Chapter 4 and Section 12.7 address this issue in greater
detail.
12.3.1.1 Mixing Assumptions for UFAD and OH Cooling
Load Calculation. The following load calculation example demon-
strates what happens if the assumption of a fully mixed room is applied
to a UFAD system.
The standard room energy-balance equation for an OH system is as
follows:
where
Q = heat loads in a room, Btu/h,
CFM = airflow moving through a room, ft
3
/min, and
T = temperature difference between the room setpoint temperature
and the supply air temperature, F.
The validity of this equation relies on two assumptionsthat the
room is at steady state and that the room is fully mixed. The assumption
Q 1.1
Btu
h cfm F
---------------------------
CFM T =
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
159
that a room is fully mixed is not valid for UFAD systems, and, as such,
this simple room energy balance equation cannot be applied here.
Consider this example of a room in cooling mode, which sheds
some light on the common question asked of UFAD systems, Do
UFAD systems need more air than OH systems? In fact, current
research indicates that airflow rates are very comparable to overhead
systems [Webster et al. 2002a].
12.3.1.2 How UFAD Stratification Affects Loads. Under-
standing how air becomes stratified in spaces employing UFAD is key
to developing a correct cooling load calculation model. As discussed in
Chapter 2, the floor-to-ceiling air flow pattern driven by rising thermal
plumes in UFAD systems produces a vertical temperature gradient in
the space. Unless air supply quantities are exceedingly high, a stratifi-
cation height is established in the room that divides the room into an
upper zone and one or two lower zones (depending on diffuser throw
height). In general, the fact that once room air has risen above this strat-
ification height it will not reenter the lower zones represents a funda-
mental difference from the fully mixed room assumed in OH system
CHAPTER 12DESIGN METHODOLOGY
160
load calculations. This principle allows convective heat gains from
sources above the stratification height in the room to be exhausted
directly at ceiling level and therefore to not be included in the air-side
load. In practice, to optimize thermal comfort, ventilation, and energy
performance, a good design goal is to maintain the stratification height
near the top of the occupied zone (4-6 ft [1.2-1.8 m]) above respiration
level, depending on whether the primary occupancy is sitting or stand-
ing.
The fact that the air in the top portion of a room above the stratifi-
cation height is warmer than the air in the bottom portion is used to the
advantage of UFAD systems in that it is primarily only the air temper-
atures in the lower portion of the room that determine the conditions
that affect the comfort of the occupant (see further discussion of ther-
mal comfort in Chapter 3). In the following discussion, this lower por-
tion of the room will be called the occupied zone. Air above the
occupied zone can be allowed to warm up beyond what would other-
wise be comfortable temperatures. The zone above the occupied zone
will be called the unoccupied zone.
12.3.1.3 Assigning Heat Gains to Occupied and Unoc-
cupied Zones. Heat loads are physically located in either the occu-
pied or unoccupied zone. For example, a ceiling pendant-mounted light
fixture is located in the unoccupied zone. A computer sitting on a desk
is located in the occupied zone. Figure 12.2 is a schematic diagram
showing some typical loads in an office.
The heat from a load is not necessarily allocated only to the occu-
pied or unoccupied zone where the load physically resides. Heat
sources must be analyzed based on their convective and radiant com-
ponents, a subject addressed by Hosni et al. [1999]. Both the location
and the convective/radiant split characterizing a specific type of heat
load determine where the heat from a load needs to be assigned. Lou-
dermilk [1999] has described a space heat gain analysis using this
approach based on empirical estimates. Unfortunately, no research-
based guidance exists to guide the assignment of loads to the occupied
and unoccupied zones. This is particularly true for heat sources located
near the stratification height (e.g., most desktop computers and equip-
ment). Using the same examples as above, the convective portion of the
light fixture can logically be assigned to the unoccupied zone, but a
good deal of the radiant portion of that energy needs to be assigned to
the occupied zone. In the case of the computer, some amount of both
the convective and radiant portions of the load can likely be assumed
to be in the unoccupied as well as the occupied zones. Table 12.2 doc-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
161
Table 12.2: Radiant/Convective Splits for
Typical Office Heat Sources
Heat Source
Radiant
Portion
Convective
Portion
[%] [%]
Transmitted solar, no inside shade 100 0
Window solar, with inside shade 63 37
Absorbed (by fenestration) solar 63 37
Fluorescent lights, suspended, unvented 67 33
Fluorescent lights, recessed, vented to return air 59 41
Fluorescent lights, recessed, vented to return air and
supply air
19 81
Incandescent lights 80 20
People, moderate office work 38 62
Conduction, exterior walls 63 37
Conduction, exterior roof 84 16
Infiltration and ventilation 0 100
Machinery and appliances 20 to 80 80 to 20
Figure 12.2 Typical loads in an office showing convective and radiant
split.
CHAPTER 12DESIGN METHODOLOGY
162
uments the radiant and convective splits of some typical office heat
loads [ASHRAE 2001a, chapter 29].
The designer needs to use his or her judgment based on an under-
standing of the physical properties of the loads and room to assign these
properly. As discussed in Section 12.3.1.1, being overly conservative
and assigning too much load to the occupied zone has the disadvantage
of requiring more air than is needed in a zone. This results in more
equipment and higher minimum air flow quantities for VAV systems
than would otherwise be needed.
12.3.1.4 Simplified Two-Zone UFAD Load Calculation
Model. Instead of modeling a single mixed zone as with OH load cal-
culations, the simplified UFAD model uses the assumption of two dis-
tinct mixed zones, one below the stratification height and a second one
above the stratification height, as illustrated in Figure 12.3.
In the two-step procedure below, Q
occupied
and Q
unoccupied
are cal-
culated based on guidance from Section 12.3.1.3. Other terms are
defined as illustrated in Figure 12.3. In step 1, the supply air quantity
(CFM) is calculated based on the heat load and temperature difference
across the lower occupied zone only. Note that if the temperature
near the top of this lower zone is higher than the average setpoint tem-
perature (T
set
) due to stratification, this higher temperature can be sub-
Figure 12.3 Definition of two zones for simplified UFAD load calcu-
lation model.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
163
stituted for T
set
, resulting in a lower supply air quantity. In step 2, the
return air temperature (T
return
) is calculated based on the heat load in
the upper unoccupied zone, the supply air quantity from step 1, and
the temperature near the top of the lower zone (T
set
or other), as used
in step 1.
12.3.1.5 Load Calculation Software Programs. This two-
zone UFAD method is not supported by any of the commercially avail-
able load calculation programs, nor is it a part of any standard
ASHRAE load calculation method. One possible way to approximate
assigning some room loads to the unoccupied zone is to artificially
assign a high proportion of the light heat directly to the return air not
physically correct, but thermodynamically similar to the real situation.
Some of the load calculation programs allow users to assign loads in
this way. It should be noted that modifying load calculation program
inputs in this way represents a departure from the guidance provided by
the software publishers and the designer needs to be fully aware of any
impacts this may have on the final load calculation values.
12.3.1.6 Thermal Bypass in Perimeter Zones. In perimeter
zones, there is the potential for significant levels of thermal bypass
associated with the windows under high solar load conditions. The
warm interior surface temperatures (due to either highly absorptive
glazing or intercepted solar radiation if blinds are present) will form a
strong vertical plume if undisturbed by nearby diffuser air flow. By
locating the return grille directly above the window, this window ther-
mal plume supports a bypassing of convective energy directly into the
overhead return air plenum, thereby reducing the air-side load [Webster
et al. 2002b].
CHAPTER 12DESIGN METHODOLOGY
164
12.3.2 Space Heating Load Calculation
In most applications, heating is primarily needed only near the
building envelope where heat loss to the outdoors can cool spaces and
may cause discomfort. Heating may also be needed in some top floor
interior zones and during periods of low occupancy (e.g., nights and
weekends).
In operation, delivering warm air from rapidly mixing diffusers
near floor level is very effective at providing heat to the conditioned
space. Due to buoyancy effects, the characteristic thermal stratification
obtained in cooling operation is replaced with a well-mixed, uniform
temperature distribution. The calculation of heating loads can therefore
use the same methods as for conventional overhead air distribution sys-
tems.
Effective heating systems isolate the source of warm air from the
thermal lag effect of the concrete slab (which is usually slightly cooler
than room temperature). This can be done, for example, by ducting
from an underfloor fan coil unit or by using baseboard radiation or con-
vection units. Quick response on heating can be very important during
morning start-up, particularly if a nighttime setback strategy is used.
12.4 DETERMINE VENTILATION AIR REQUIREMENTS
Minimum outside air requirements should be determined according
to applicable codes and standards (e.g., ASHRAE Standard 62-2001).
Some improvement in ventilation effectiveness is expected by
delivering the fresh supply air near the occupant at floor or desktop
level, allowing an overall floor-to-ceiling air flow pattern to more effi-
ciently remove contaminants from the occupied zone of the space. An
optimized strategy is to control supply outlets to allow mixing of supply
air with room air up to the stratification height, typically no higher than
head height (4-6 ft [1.2-1.8 m] depending on primary space occu-
pancy). Above this height, stratified and more polluted air is allowed to
occur. The air that the occupant breathes will have a lower percentage
of pollutants compared to conventional uniformly mixed systems.
If an enhanced ventilation effectiveness (E
v
) can be shown to exist
in comparison to well-mixed overhead systems (see ASHRAE Stan-
dard 129-1997) the current version of Standard 62 allows some reduc-
tion in ventilation air quantities. The magnitude of this improved
ventilation effectiveness will be largest during times of outside-air
economizer use. The fact that the number of hours of economizer oper-
ation is typically greater for UFAD systems also contributes to overall
increased ventilation effectiveness (see Chapter 11 for further discus-
sion).
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
165
12.5 TEMPERATURE CONTROL AND ZONING
Please refer to Chapter 6, Controls, Operation, and Maintenance,
for a more detailed discussion of control issues. There are several
approaches to address zones with significantly different thermal loads,
including:
plenum partitioning with ducted VAV devices supplying air to each
zone;
plenum partitioning with fan-powered terminal devices supplying
air to each zone;
thermostatically controlled VAV diffusers, which may be used in
both partitioned and open plenums;
local fan-driven supply outlets, which may be used in both parti-
tioned and open plenums;
open plenums with mixing boxes and ducted outlets.
Partitioning and any other obstructions in the underfloor plenum
should be kept to the minimum necessary to optimize system perfor-
mance and efficiency, as this helps to maintain the plenum for its
intended purpose to serve as a highly flexible and accessible service
plenum.
Although not a requirement, some designers recommend limiting
the size of underfloor zones (partitioned or otherwise) that are served
by a single ducted primary air inlet from the air handler (see below).
This ensures the systems ability to avoid unacceptable variations in
supply air temperature (due to heat gain from or loss to the concrete slab
and raised floor structure).
In some system designs, using multiple medium- or small-sized
(floor-by-floor) AHUs can minimize or totally eliminate ductwork and
improve zone control when AHU capacities correspond to the specific
requirements of each plenum zone.
12.5.1 Interior Zones
Interior zones (typically defined as areas located farther than 15 ft
(5 m) from exterior walls) are usually exposed to relatively constant and
lower (compared to perimeter zones) thermal loads (almost always
cooling in typical office buildings). In many completed projects, these
zones have been adequately served by a constant volume (or constant
pressure in a pressurized system) control strategy. The need for
dynamic control of these (typically) large zones can be reduced due to
the ability of occupants to make small local adjustments to individual
diffusers. This configuration with a minimum amount of underfloor
CHAPTER 12DESIGN METHODOLOGY
166
partitioning helps to maintain flexibility in the relocation of other ser-
vices (e.g., cabling).
However, with modern energy-efficient office equipment and high
diversity rates of personnel, it is recognized that interior loads can still
fluctuate significantly; control strategies and system designs need to be
well thought out to accommodate these conditions. For example, using
a VAV strategy can result in the same benefits as for an overhead sys-
tem. The interaction between interior and perimeter systems also needs
careful consideration. If plenum air is used to supply cooling for perim-
eter zones, reset of supply air temperature (SAT) to a higher tempera-
ture for the core zones (e.g., at part load) may compromise the
perimeter systems ability to satisfy a simultaneous peak cooling load
condition. In this case, a VAV strategy may be advisable to allow the
coolest supply temperature possible to be available in the perimeter
zone.
12.5.2 Perimeter Zones
The largest loads typically occur near the skin of the building. Since
these areas are influenced by climatic variations, rapid fluctuations in
heating and cooling demands can occur, with peak loads often occur-
ring only for several hours per day and relatively few days of the year.
Code-regulated energy-efficient envelope design is always the first
stage of defense against excessive perimeter loads.
The purposes of the perimeter system are to (1) neutralize the skin
load, thereby isolating the perimeter from the interior system; (2) pro-
vide heating, required in almost all buildings; and (3) provide auto-
matic control to allow quick response to rapid load changes. Due to the
thermal inertia of the slab, UFAD systems serving interior zones (com-
monly open plenums with passive diffusers) tend to be very stable in
operation. As a result, perimeter zone considerations often lead to
hybrid system designs in which active, fan-powered supply units are
used to increase the rate at which the system can respond to changes in
load. Many perimeter zone solutions have been successfully applied in
practice (see Chapter 9 for further discussion). Some manufacturers
offer equipment and recommended configurations for perimeter sys-
tems.
12.5.3 Other Special Areas
Other special zones having large and rapid changes in cooling load
requirements, such as conference rooms or lecture halls, should incor-
porate fan-powered or other VAV air supply solutions. This can require
underfloor partitioning for these areas. Automatic controls to these
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
167
zones should be capable of meeting both peak demand and significant
turndown during periods of little or no occupancy (see Chapter 9 for
further discussion). Manual control of these zones has also been used
in some installations.
12.6 AIR DISTRIBUTION SYSTEM CONFIGURATION
12.6.1 Plenum Configuration
The installation of a raised floor system and the many advantages
that it produces in terms of improved cable management, flexibility,
and life-cycle cost savings will, in many cases, be the main driver in jus-
tifying the use of underfloor air distribution. Once an underfloor air
supply plenum is included in the design, there are three basic
approaches to configuring it: (1) pressurized plenum with a central air
handler delivering air through the plenum and into the space through
passive grilles/diffusers; (2) zero-pressure, or neutral, plenum with air
delivered into the conditioned space through local fan-powered (active)
supply outlets in combination with the central air handler; and (3) in
some cases, ducted air supply through the plenum to terminal devices
and supply outlets. In practice, although not a requirement, the final
designs often end up as hybrid solutions including some combination
of the above components. For example, a common pressurized plenum
design uses passive diffusers in the interior zone, active fan-driven dif-
fusers in the perimeter or special zones with rapid load changes, and
some amount of distribution ductwork in the underfloor plenum.
The largest dimension of ductwork and other non-movable system
components that can reasonably fit between underfloor pedestals is 22
in. (560 mm). For components such as fan coils and terminals whose
relocation or removal (for maintenance considerations) is foreseen, this
maximum dimension should be limited to 19 in. (480 mm). The
removal of any component larger than 19 in. between pedestals requires
the removal of one or more rows of pedestal heads. The removal of one
pedestal head requires that all four of the floor tiles it supports be
removed.
In recent years there have been many different system configura-
tions employed by UFAD system designers these should be carefully
reviewed and considered during the initial design concept develop-
ment. The most up-to-date information on lessons learned, both suc-
cessful and unsuccessful, will generally be available from design
engineers, facility managers, or occupants in buildings with recently
installed UFAD systems [e.g., McCarry 1995; Shute 1995; Daly 2002].
In the discussion below, we will focus on the two plenum-based supply
CHAPTER 12DESIGN METHODOLOGY
168
configurations, as guidelines for fully ducted systems are well estab-
lished. For additional details, see Chapter 4.
12.6.1.1 Pressurized Plenums. Supply air that has been fil-
tered and conditioned to the required temperature and humidity, includ-
ing at least the minimum required volume of outside air, is delivered
from the air-handling unit (AHU) through a minimal amount of duct-
work to the underfloor plenum. The central AHU is controlled to main-
tain a small, but positive, pressure in the underfloor plenum relative to
the conditioned space. Typical plenum pressures fall in the range of
0.05-0.1 in. H
2
O (12.5-25 Pa). The number of plenum inlet locations
is determined by the size of control zones, access points available in the
building, amount of distribution ductwork used under the floor, and
other design issues. Within the underfloor plenum, it is always desir-
able to the extent possible to have the supply air flow un-ducted to the
supply outlets.
Research has shown that pressurized plenums can maintain a rela-
tively constant plenum pressure across a single control zone [Bauman
et al. 1999a]. This allows any passive diffuser of the same size and con-
trol setting (typical damper opening) located in the zone to deliver the
same amount of air to the space. In contrast, field experience suggests
that maintaining uniform temperature distribution in a zone is a more
significant design challenge. Especially for diffusers located far from
the plenum inlet, a substantial variation in supply air temperature can
occur as a result of heat transfer through the raised floor and the slab
(see Section 12.7).
There is some evidence from completed projects that uncontrolled
air leakage from the pressurized plenum can impair system perfor-
mance. Proper attention must be given to the sealing of junctions
between plenum partitions, structural slab, access floor panels, and
exterior or interior permanent walls during the construction phase of
the project. It is particularly important to minimize leakage to the out-
side of the building, as this directly affects the energy performance of
the system. Due to the relatively low pressure (0.05-0.1 in. H
2
O
[12.5-25 Pa]) used in pressurized plenums, proponents of pressurized
plenums claim that leakage into adjacent zones is minimal, and much
of the leakage (between raised floor panels) will be into the same
conditioned zone of the building [Sodec and Craig 1991]. In any case,
carpet tiles (preferably overlapping the floor seams) with rubberized
backing should be employed to ensure acceptable floor leakage rates.
This is a design issue that is still in need of further investigation (see
Chapter 4).
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
169
12.6.1.2 Zero-Pressure Plenums. Primary supply air from
the central air handler is delivered to the underfloor plenum in much the
same manner as with pressurized plenums. In this case, since the ple-
num is maintained at very nearly the same pressure as the conditioned
space, local fan-powered supply outlets are required to supply the air
into the occupied zone of the space.
A major advantage of zero-pressure plenums is that they pose no
risk of uncontrolled air leakage to the conditioned space, adjacent
zones, or outside. In addition, the removal of floor panels for service or
maintenance activities does not disrupt overall supply-air flow.
Local fan-powered outlets under thermostatic or individual control
allow supply air conditions to be controlled over a wide range as nec-
essary. This controllability can be used to handle zones with signifi-
cantly different thermal loads without underfloor partitioning. The use
of partitioning for zone control can also be applied in a similar way as
for pressurized plenums.
The advantages of no leakage and improved local control of air flow
must be traded off against several factors. Fan-powered supply outlets
have a cost premium compared to passive diffusers used in pressurized
plenum designs. In terms of energy use, although central fan energy
consumption will be reduced compared to that for a pressurized ple-
num, this savings will be offset by the energy consumed by the large
number of small local fans that are typically less efficient than larger
fans. However, if a pressurized plenum leaks at a high rate, this can also
lead to excessive fan energy use. Another consideration with local fan-
driven units is the potential for increased noise levels, but this can usu-
ally be handled with proper fan design. As a general rule, underfloor
systems have been found to be quieter than conventional overhead sys-
tems.
Since the supply air in the underfloor plenum is in direct contact
with the concrete structural slab, the same thermal storage strategies as
with pressurized systems can be used. Similarly, the frequency of
ducted primary air inlets to the plenum must take into consideration the
heat exchange between the supply air and the underfloor plenum struc-
tural mass.
By relying on both a primary air handler and local fan-powered out-
lets to draw air from the plenum into the space, zero-pressure config-
urations can more reliably maintain some amount of cooling effect,
even if the air handler is shut down for repair or servicing. In particular,
this feature may allow after-hours cooling to be provided at isolated
locations at a substantial savings, since the central plant does not need
CHAPTER 12DESIGN METHODOLOGY
170
to operate. In this case the active diffusers will continue to provide local
air motion and cooling due to the thermal inertia of the concrete slab.
The greater ability of zero-pressure systems using active diffusers
to provide localized cooling [Tsuzuki et al. 1999] suggests their suit-
ability in projects involving high and diversified heat loads. In fact, this
is why fan-driven solutions are frequently applied in perimeter zones
and special zones with rapidly changing loads.
12.6.2 Duct Requirements
Within the underfloor plenum, the designer must first define the
temperature control zones (Section 12.5) and whether or not this zon-
ing will require the installation of underfloor partitioning. Additional
partitioning in the plenum may also be required to comply with local
energy and/or fire codes. The amount of ductwork to be installed in the
underfloor plenum is then determined by considering the following
issues.
Ensure that an adequate and relatively uniform amount of supply air
is delivered to all parts of the floor plate. Perimeter and special
zones will have higher airflow requirements. Research has shown
that plenum pressures and airflow are quite uniform in pressurized
plenums as shallow as 8-in. (200-mm) over a distance of up to 80 ft
(24 m) [Bauman et al. 1999a].
Provide an acceptable degree of thermal decay (temperature varia-
tion) as the supply air passes through the open plenum (see Section
12.7 for more details).
Deliver supply air to terminals supplying (partitioned) control
zones.
Isolate heated air (typically from fan coil units) from the cooler slab
and other surfaces in the plenum, and allow fan-driven supply air to
quickly respond to changes in load (perimeter diffusers are usually
ducted from these terminals). In all cases it is recommended to min-
imize ductwork and partitioning in order to reduce costs and con-
flicts with other trades and to maintain an open and highly flexible
underfloor service plenum.
If multiple vertical shafts are used in the building, horizontal duct-
work in the plenum can be reduced or eliminated.
Coordinate with wiring, conduit, and piping distribution needs in the
plenum.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
171
The design and layout of main ducts from the central plant to ple-
num inlet locations is similar to that of conventional overhead systems
except that access must be provided for the ducts to reach the under-
floor plenum. The amount of main ductwork can be reduced in designs
using medium to small-sized air handlers (floor-by-floor units) that are
located closer to the point of use. However, ductwork for ventilation air
is still required and must be sized accordingly in climates where the use
of an outside-air economizer will be an important operating strategy.
At plenum inlets, it is recommended to limit discharge velocities to
about 1,500 fpm (7.6 m/s) for acoustical purposes. Although not an
issue of the same magnitude as it is in computer room applications with
much larger air delivery rates, to avoid reentry of room air through dif-
fusers it is recommended to place floor diffusers at least about 6 ft (2
m) away from major plenum inlet locations.
The largest distribution ducts in the underfloor plenum can be stan-
dard rectangular or round ducts, but they must have a maximum width
of 22 in. (560 mm) to fit between raised floor pedestals and a maximum
height of at least 2 in. (50 mm) less than the finished floor height to
account for the thickness of the floor panels. Wider ducts can be accom-
modated, but this adds complexity and cost to the raised floor installa-
tion, requiring special bridging to span across the ductwork.
In recent years, air highways have been introduced, which are
fabricated rectangular ducts that use the underside of the floor panel as
the top, concrete slab as the bottom, and sealed sheet metal partitioning
for the sides. Air highways are often designed to be two floor panels in
width (4 ft [1.2 m]).
The advantages of using air highways instead of single or multiple
standard ducts running between floor pedestals in the plenum include
lower costs due to less sheet metal and lower labor rates for floor install-
ers; lower pressure drop because they provide larger effective duct area;
and reduced coordination and conflicts.
In practice, built projects are finding that actual cost savings are
questionable due to the lack of familiarity of construction by floor con-
tractors and the general contractor. Other issues that need to be con-
sidered are the code equivalence to a duct when it comes to crossing
corridors. Construction coordination can be impacted because the
ducts are not complete until floor tiles installed. The air highways are
also susceptible to damage by other trades. Finally, although the goal
is a leak-free installation, the air highways have only limited pressure
capability, and overpressurized air-highways can lead to substantial air
leakage.
CHAPTER 12DESIGN METHODOLOGY
172
Underfloor ducts serving specific zones should be sized to accom-
modate peak cooling loads. The capacity of the central chiller plant, air
handlers and main duct risers can generally be reduced by accounting
for time variations and load diversity (up to 30%).
The amount of recirculation ductwork can be reduced by taking
some of the return air at ceiling level directly back into the underfloor
plenum without returning it to the air handler. For example, return air
can be brought down induction shafts formed with furring spaces along
structural columns [e.g., see Shute 1995]. This alternative configura-
tion of bypass control can only be used as long as proper dehumidifi-
cation is maintained back at the air handler and complete blending of
return and supply air is achieved within the underfloor plenum. An
additional consideration is that directly returned air of this kind will not
be filtered back at the AHU.
In both zero-pressure and pressurized plenums, the delivery of air
through fan-powered outlets is even more reliable than that through
passive diffusers in pressurized plenums. Active diffusers are less sus-
ceptible to pressure variations (such as when access floor panels are
removed) and other flow restrictions.
If desktop- or partition-based diffusers are specified, small-sized
ductwork (e.g., flex duct, passageways integrated into the furniture,
etc.) will be required to bring supply air up from the underfloor plenum
(or down from an overhead system) to serve these outlets.
12.7 DETERMINE ZONE SUPPLY AIR TEMPERATURE
AND AIR FLOW REQUIREMENTS
Because the air is supplied directly into the occupied zone and close
to occupants, supply air temperatures must be warmer than that used for
Figure 12.4 A typical air highway detail.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
173
conventional overhead system design. For cooling applications, supply
air temperatures entering the plenum should be maintained in the range
of 61-65F (16-18C) with 63-65F (17-18C) as a good target for sup-
ply air temperatures at the diffusers to avoid overcooling nearby occu-
pants. By comparison, overhead systems typically deliver 55F (13C)
air at ceiling level. This supply temperature can be reset even higher
under partial-load conditions. In temperate climates, where high
humidity is not a problem, these warmer supply air temperatures
increase the potential for economizer use and allow higher cooling coil
temperatures to be set, if desired. See Section 12.10 for further discus-
sion of humidity control.
Mixed air temperature after the cooling coil, or plenum inlet tem-
perature, must be determined by taking into account temperature
increase as the air flows through the underfloor plenum. Under most
conditions, heat will be transferred to the plenum air from the slab (heat
conducted from the return air plenum of the floor below) and from the
raised floor panels (heat conducted from the room). Current estimates
for typical air flow rates in an underfloor plenum with a slab that is 5F
(3C) warmer than the plenum inlet air temperature call for a 2F (1C)
increase for every 33 ft (10 m) of distance traveled through the plenum.
Some manufacturers also provide guidance for thermal decay rates
[York 1999]. This supply air temperature increase (sometimes referred
to as thermal decay) has important implications for the maximum
distance that a diffuser should be located from the nearest plenum inlet.
For example, if the design objective is to limit thermal decay to 3F
(2C), then the farthest diffuser should be located a maximum of about
50 ft (15 m) from the closest supply point into the plenum. It is also pos-
sible under suitable weather conditions to reduce thermal decay by
employing a nighttime precooling strategy of thermal mass in the
underfloor plenum (see Section 12.11).
Other considerations in selecting a minimum plenum air tempera-
ture include avoiding excessively cool floor surfaces and preventing
condensation on cool surfaces in the plenum. Current recommenda-
tions are to control plenum air temperature to be no colder than in the
range of 61-65F (16-18C).
Cooling air quantities for UFAD systems should be carefully deter-
mined. Higher supply air temperatures would suggest that higher sup-
ply air volumes are required, but the higher return temperatures created
by stratification reduce the required increase in volume. As previously
described in Section 12.3.1, properly controlled stratification in the
space allows cooling air quantities for UFAD systems to be very similar
to those required under the same conditions using overhead air distri-
CHAPTER 12DESIGN METHODOLOGY
174
bution. Daly [2002] discusses this issue and notes that in many com-
pleted UFAD projects, measured return air temperatures are not as high
as anticipated. This evidence suggests that over-airing is a common
problem, leading to reduced stratification and higher fan energy use. If
a designer conservatively assigns too large a fraction of the heat sources
to the lower occupied zone, excessive air quantities will be supplied
to the space. In a constant-air-volume (CAV) zone, as many interior
zones are designed for simplicity, high air supply volumes will lead to
overcooling.
In pressurized plenums, another factor affecting air supply quanti-
ties is the additional cooling effect provided by air leakage through the
raised floor combined with the heat transferred from the room through
the raised floor panels to the underfloor plenum. Recent testing has
measured air leakage rates for one type of floor panel with offset carpet
tiles (covering the gaps between panels) in the range of 0.1-0.2 cfm/ft
2
(0.5-1.0 L/(s
.
m
2
)). Accounting for the additional heat loss through the
floor, this amount can be a substantial fraction (approaching 50%) of
the total required cooling in the zone. Unless this is considered, even
more overcooling may develop. Zero-pressure plenum designs are not
impacted by air leakage, although heat transfer through the floor will
still be an issue.
12.8 SELECT AND LOCATE DIFFUSERS
Floor diffusers are most commonly used and offer the widest selec-
tion of products to the designer. Due to growing interest in UFAD sys-
tems in the U.S., several new designs have been introduced in the last
five years and this trend is expected to continue. Floor diffusers can be
passive or active, depending on the plenum configuration and mode of
operation (see below). TAC supply outlets that provide a wider range
of control by the occupant are typically fan-driven (active) and may be
located in the floor, furniture, partitions, or ceiling. Please see Chapter
5, UFAD Equipment, for a more detailed discussion of diffuser
options.
Passive diffusers are defined as air supply outlets that rely on a pres-
surized underfloor plenum to deliver air from the plenum through the
diffuser into the conditioned space of the building. Active diffusers are
defined as air supply outlets that rely on a local fan to deliver air from
the plenum through the diffuser into the conditioned space of the build-
ing. Passive diffusers can generally be converted to active diffusers by
simply attaching a fan-powered outlet box to the underside of the dif-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
175
fuser or grille. Most manufacturers provide both passive and active dif-
fusers.
Three types of floor diffusers currently in use are:
1. Swirl diffuser: This is the most commonly installed type of dif-
fuser in UFAD systems; more models are commercially available
than for any other design. The swirling air flow pattern of air dis-
charged from this round floor diffuser provides rapid mixing of
supply air with the room air in the occupied zone. Occupants may
have limited control of the amount of air being delivered by rotat-
ing the face of the diffuser or by opening the diffuser and adjust-
ing a volume control damper. Designs are also available with
integral automatic volume control.
2. Variable-area diffuser: This diffuser is designed for variable-air-
volume operation. It uses an automatic internal damper to main-
tain close to a constant discharge velocity as air flow is reduced.
Air is supplied through a slotted square floor grille in a jet-type
air flow pattern. Occupants can adjust the direction of the supply
jets by changing the orientation of the grille. Supply volume may
be controlled by a thermostat on a zone basis or, if available, as
adjusted by an individual user.
3. Linear floor grille: Linear grilles have been used for many years
in underfloor applications where occupant control is not an issue.
Air is supplied in a jet-type planar sheet, making them well
matched for ducted applications in perimeter zones adjacent to
exterior windows. Although linear grilles often have multi-blade
dampers, they are not designed for frequent adjustment by indi-
viduals and are therefore not typically used in densely occupied
interior office space.
In addition to the three types of floor diffusers described above for
passive diffusers, several other types of active diffusers are available.
See Chapter 3 for data on effective cooling rates for three of the fol-
lowing fan-driven diffusers:
1. Floor supply module: Multiple discharge grilles (jet-type) are
mounted in a single raised floor panel. Fixed vanes in the grilles
are inclined at 40 so that air flow direction can be adjusted by
rotating the grilles. Integral fan speed control allows the air sup-
ply volume to be controlled.
2. Desktop air supply pedestals: Two supply pedestals located near
the back of the desk surface allow adjustment of air flow direction
and flow rate. Air is supplied from a mixing box that is typically
hung in the back or corner of the knee space of the desk and con-
nected by flexible duct to the two desktop supply nozzles. The
CHAPTER 12DESIGN METHODOLOGY
176
mixing box uses a small variable-speed fan to pull air from the
underfloor plenum and deliver a free-jet-type air flow from the
nozzles.
3. Underdesk diffuser: One or more fully adjustable (for air flow
direction) grilles, similar to a car's dashboard, are mounted just
below and even with the front edge of the desk surface (other
positions are possible). A fan unit located either adjacent to the
desk or in the underfloor plenum delivers air through flexible duct
to the grilles.
4. Partition-based diffuser: Grilles are mounted in the partitions
immediately adjacent to the desk. Air is delivered through pas-
sageways that are integrated into the partition design to controlla-
ble supply grilles that may be located just above desk level or just
below the top of the partition.
It is recommended that you contact the diffuser manufacturers
directly to obtain the most up-to-date product information on the afore-
mentioned TAC diffusers.
The flexibility of mounting supply diffusers in movable raised floor
panels is a major advantage for UFAD systems. The inherent ability to
easily move diffusers to more closely match the distribution of loads in
the space makes the placement of diffusers a much easier task. In open
plan offices, it is highly desirable to install one local task diffuser in
each workstation, thereby providing the potential for individual control
by each occupant. After initial placement of the diffusers during the
final stages of construction, final adjustments can take place after the
location of furniture and loads, as well as the preferences of individual
occupants, are more accurately determined.
12.9 DETERMINE RETURN AIR CONFIGURATION
For optimal cooling operation of a UFAD system, it is important to
locate return grilles at ceiling level or, at a minimum, above the occu-
pied zone (1.8 m [6 ft]). Air is typically returned through grilles located
in a suspended ceiling or through high side-wall grilles if no ceiling ple-
num is present. This supports an overall floor-to-ceiling air flow pattern
that takes advantage of the natural buoyancy produced by heat sources
in the office and more efficiently removes heat loads and contaminants
from the space.
A certain portion of return air is mixed with primary air from the
AHU to achieve desired air temperatures and humidity and enable
reduced energy costs. In many climates, to achieve proper humidity
control, conventional cooling coil temperatures must be used (produc-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
177
ing a coil leaving temperature of 55F [13C]). In this situation, a return
air bypass control strategy can be employed in which a portion of the
return air is bypassed around the cooling coil and then mixed with the
air leaving the coil to produce the desired warmer supply air tempera-
ture entering the plenum (61-65F [16-18C]).
In some cases, a percentage of return air can be recirculated directly
back into the underfloor plenum via return shafts near the ceiling or
from the ceiling plenum. As mentioned earlier, this configuration does
not allow filtering of return air back at the AHU. Room air flowing back
into the plenum through open floor grilles can also serve as makeup air
for zero pressure plenum designs when local fan-powered outlets
require more air than that being supplied from the central AHU.
If recirculation takes place directly in the underfloor plenum, the
supply and return air streams must be well mixed within the underfloor
plenum before delivery to the conditioned space. This can usually be
achieved by distributing the primary air at regularly spaced intervals
throughout the plenum and/or employing fan-powered local supply
units to aid mixing of primary supply air with the return air.
12.10 SELECT AND SIZE PRIMARY HVAC EQUIPMENT
Due to the reduction in supply ductwork and to the low operational
static pressures in pressurized underfloor air supply plenums (typical
pressures are around 0.05-0.1 in. H
2
O [12.5-25 Pa]), central fan energy
use and installed horsepower can potentially be reduced relative to tra-
ditional ducted overhead air distribution systems (see Webster et al.
[2000] for a more complete discussion of this issue). Similarly, in zero-
pressure plenums, fan-assisted supply outlets further reduce central fan
sizing. As discussed in Section 12.7, cooling air quantities, and there-
fore air-handler capacities, for UFAD systems should be carefully
determined and may be equal to or less than those required under the
same conditions using overhead systems.
Humidity control is a key consideration in the selection of air-han-
dling units (AHU) and the mechanical cooling plant. In all climates
requiring dehumidification of the outside air, a cooling coil leaving
temperature in the range of 50-55F (10-13C) will typically be used.
To produce the higher plenum inlet temperatures (61-65F [16-18C])
required for UFAD systems, a non-standard AHU configuration, such
as face and bypass, must be specified. With this approach, the incoming
outside air and a portion of the return air are dehumidified (minimum
amount needed for humidity control). The remaining return air is
bypassed around the coil, if done at the air handler, and mixed with the
CHAPTER 12DESIGN METHODOLOGY
178
cool primary air to produce supply air of the proper temperature and
humidity before being delivered directly into the underfloor plenum. In
this configuration, a range of coil temperatures can be utilized, includ-
ing low-temperature air systems with or without ice storage. The only
adjustment would be the required amount of bypassed return air to mix
and produce the desired plenum inlet temperature. This and other
equipment selection challenges are discussed by Int-Hout [2001].
It is recommended that in designs with both UFAD and overhead air
distribution systems, separate AHU and mechanical cooling systems
be selected with each type of system. If the same chiller and AHU are
used, this can lead to system inefficiencies for the UFAD system. For
example, during mild weather, a single cooling plant would need to be
operated to serve the colder supply air requirements of the overhead
system, even though the UFAD system (using a warmer supply air tem-
perature) would need no cooling. For further discussion of this subject,
see AEC [2001].
Consideration must also be given to the need for a heating coil at the
AHU. Such a coil may be needed for morning warm-up or to produce
the required higher supply air temperatures during cold weather at min-
imum outdoor air.
12.11 THERMAL STORAGE OPPORTUNITIES
In all but the earliest fully ducted UFAD installations there is some
amount of supply air flowing through the underfloor plenum in direct
contact with the concrete floor slab. Control strategies should carefully
consider thermal storage in the slab and other components (e.g., floor
panels). UFAD systems are very stable in operation with only gradual
(usually unnoticeable to occupants) changes in supply temperature
over time, unless the supply air is isolated from the mass.
Energy and operating cost savings can be achieved using a thermal
storage strategy in the concrete slab. In temperate climates, cool night-
time air can be brought into the underfloor plenum where it effectively
cools the slab overnight. During the following day's cooling operation,
higher supply air temperatures can be used to meet the cooling demand,
thereby reducing refrigeration loads for at least part of the day. This 24-
hour thermal storage strategy benefits from lower off-peak utility rates
and extends the hours of economizer operation. For this strategy to be
successful, the following issues must be addressed:
Heating night setback must be used.
Since a precooled slab will be at its coolest temperature in the
morning, the design, capacity, and response rate of the heating sys-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
179
tem, if needed, will be particularly important under morning start-
up conditions. Ultimately, the most important consideration is to
optimize the control of the slab precooling system such that morn-
ing warm-up is minimized while still taking maximum advantage of
the potential mechanical cooling reduction during the following
day.
Enthalpy-based economizer control must be used to maintain
proper humidity levels of the incoming nighttime air and to protect
against condensation in the plenum.
Lower limit control switches for both slab and space temperatures
must be activated to prevent overcooling.
Preliminary estimates indicate that a precooled slab is most effective
at reducing daytime cooling loads during morning hours only.
If the slab is not pre-cooled at night, then supply outlet temperatures
will likely increase with distance from the primary air inlet to the ple-
num due to the effects of stored heat in the slab (particularly from warm
return air from the next floor down flowing along the underside of the
slab).
Thermal storage performance of underfloor air supply plenums is
the subject of ongoing research. Please refer to Chapter 4, Underfloor
Air Supply Plenums, for further discussion.
181
Chapter 13
UFAD Project
Examples
One of the best ways to educate the engineering and design com-
munity on how to apply UFAD technology is to review the work of oth-
ers as described in case studies and other reports on completed
installations. This section presents a list of references, web sites, and
other sources describing examples of UFAD and TAC system designs.
Inclusion of a particular project, designer, or product in the following
list does not constitute an endorsement but rather is intended to dem-
onstrate the range of possible solutions that have been applied in prac-
tice.
ArchitectureWeek. 2000. Building for Harmony with nature. Archi-
tectureWeek, June 14, http://www.architectureweek.com/2000/
0614/building_1-1.html.
Arnold, D. 1990. Raised floor air distributiona case study. ASHRAE
Transactions, Vol. 96, Pt. 2.
Barker, C.T., G. Anthony, R. Waters, A. McGregor, and M. Harrold. 1987.
Lloyd's of London. Air Conditioning: Impact on the Built Environ-
ment. New York: Nichols Publishing Company.
Bauman, F., K. Powell, R. Bannon, A. Lee, and T. Webster. 2000. Under-
floor air technology web site: http://www.cbe.berkeley.edu/under-
floorair. Center for the Built Environment, University of California,
Berkeley, December.
Beck, P. 1993. Intelligent design passes IQ test. Consulting-Specifying
Engineer, January.
Cornell University. 1999. Case study: 901 Cherry Gap Headquarters.
http://dea.human.cornell.edu/Ecotecture/Case%20Studies/Gap/
CHAPTER 13UFAD PROJECT EXAMPLES
182
gap_home.htm. Ecotecture site, Department of Design and Envi-
ronmental Analysis, Cornell University, Ithaca, NY.
Daly, A. 2002. Underfloor air distribution: Lessons learned. ASHRAE
Journal, Vol. 44, No. 5, May, pp. 21-24.
Energy Design Resources. 2000. Underfloor air distribution offers
energy efficiency and much more! eNews for Designers, Issue 18,
October 27, http://www.energydesignresources.com.
Guttmann, S. 2000. Raising the bar, with raised floors. Consulting-
Specifying Engineer, October.
HGA. 2002. ADC World Headquarters & Technology Campus. Ham-
mel, Green and Abrahamson, Inc., Minneapolis, MN.
Kight, D. 1992. Epson flexes its technological muscles. Facilities
Design and Management, February.
Loftness, V., P. Mathew, G. Gardner, C. Mondor, T. Paul, R. Yates, and M.
Dellana. 1999. Sustainable development alternatives for specula-
tive office buildings: A case study of the Soffer Tech office build-
ing. Final report. Center for Building Performance and
Diagnostics, Carnegie Mellon University, Pittsburgh, PA.
Matsunawa, K., H. Iizuka, and S. Tanabe. 1995. Development and appli-
cation of an underfloor air conditioning system with improved out-
lets for a smart building in Tokyo. ASHRAE Transactions, Vol.
101, Pt. 2.
McCarry, B. 1998. Innovative underfloor system. ASHRAE Journal,
Vol. 40, No. 3, March, pp. 76-79.
McQuillen, D. 2001. 3 case studies for improved IAQ. Environmental
Design + Construction, posted 1/24/2001, http://www.edc-
mag.com.
Portland General Electric. 2002. Earth Advantage/Building Profile:
CNF Information Technology Center. http://www.earthadvan-
tage.com/commercial/projects.asp. Portland General Electric,
Commercial and Industrial Energy Efficiency Programs, Portland,
OR.
Shute, R.W. 1992. Integrated access floor HVAC. ASHRAE Transac-
tions, Vol. 98, Pt. 1.
Tuddenham, D. 1986. A floor-based approach. ASHRAE Journal (July).
Warson, A. 1990. The pin-striped office. Canadian Building, March.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
183
Webster, T., et al. 1999-2002. UFAD Project Profiles. http://
www.cbe.berkeley.edu/underfloorair/whereHasItBeenDone.htm.
Underfloor air technology web site, Center for the Built Environ-
ment, University of California, Berkeley.
Six project profiles and two case studies are provided for the fol-
lowing projects: (1) BC Hydro, Burnaby, British Columbia; (2)
California State Automobile Association (CSAA), Livermore, CA;
(3) First National Bank of Omaha (FNBO) Technology Center,
Omaha, NE; (4) Sacramento Municipal Utility District (SMUD)
Customer Service Center (CSC), Sacramento, CA; (5) Teledesic
Broadband Center, Bellevue, WA; and (6) Telus, Vancouver, British
Columbia.
Webster, T., R. Bannon, and D. Lehrer. 2002. Teledesic Broadband Cen-
ter. Center for the Built Environment, University of California,
Berkeley, CA, April.
185
Chapter 14
Future Directions
Underfloor air distribution (UFAD) represents an approach to space
conditioning in buildings that has several advantages over traditional
ceiling-based air distribution systems. Depending on the design and
application, these systems have the potential to (1) improve indoor
environmental quality, worker satisfaction, and productivity by provid-
ing personal comfort control and improved ventilation efficiency, (2)
reduce energy use through a variety of system design and operating
strategies, and (3) reduce life-cycle building costs by improving flex-
ibility in providing and maintaining building services.
While it is true that UFAD systems are being designed, installed,
and operated right now, as an overall technology they are still relatively
new and unfamiliar to the building industry at large. In this design
guide, we have described UFAD systems in detail, and have presented
recommendations and design methods based on the most current and
best available data and information. Where available, we have also pro-
vided preliminary guidance for the design of task/ambient conditioning
(TAC) systems. Throughout the guide, we have also identified areas
where more work is needed. Additional research and development
within the industry could provide significantly more guidance by iden-
tifying and investigating from both a fundamental and practical per-
spective some of the key differences between UFAD and TAC systems
and overhead systems. These findings could then be incorporated into
updated design guides, design tools, workshops, and other forms of
technology transfer to help inform the design community about these
systems.
This section summarizes ongoing and future research, standards
development, and activities within the building industry addressing
UFAD and TAC technology needs.
CHAPTER 14FUTURE DIRECTIONS
186
14.1 RESEARCH
14.1.1 Room Air Stratification
One of the most critical pieces of missing information on UFAD
systems is the fundamental performance of stratified floor-to-ceiling
air flow and the implications for energy savings, thermal comfort, and
indoor air quality. Optimizing the control of stratification can reduce
the volume of supply air required to maintain comfort conditions in the
occupied zone with corresponding energy savings. Research is now
underway investigating the energy impacts of room air stratification
[CBE 2002].
14.1.2 Underfloor Air Supply Plenums
Research is needed to address the control and energy-related
aspects of delivering supply air through a plenum in contact with an
exposed concrete slab and floor panels. Thermal performance issues
include variations in supply air temperature with distance traveled in
the plenum and thermal storage strategies for achieving energy and
operating cost savings. Research is currently underway investigating
underfloor plenum thermal performance [CBE 2002].
14.1.3 Whole-Building Energy Simulation Model
A whole-building energy simulation program capable of accurately
modeling UFAD systems currently does not exist. This is one of the top
technology needs identified by system designers. Models for both of
the above two elements (room air stratification and underfloor plenum)
would need to be incorporated into such a system model that would
allow the comparison of the energy performance of UFAD systems
with that of conventional system design. The development of such a
model is the goal of a new research project scheduled for completion
in 2005 [CBE 2002].
14.1.4 Thermal Comfort
To allow the optimization of UFAD and TAC system performance,
effective comfort criteria need to be developed. Relevant thermal com-
fort research should address the impact of thermal stratification and the
provision of individual control on thermal acceptability and occupant
satisfaction.
14.1.5 Ventilation Performance
Laboratory and field measurements of ventilation performance are
needed to more accurately quantify the ventilation efficiency of UFAD
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
187
and TAC system configurations. These studies should investigate the
ventilation improvement of both stratified floor-to-ceiling airflow and
TAC diffusers that deliver fresh air in the near vicinity and under per-
sonal control of building occupants.
14.1.6 Field Studies
As more UFAD installations are completed in the coming years, it
will be important to conduct field studies to collect whole-building per-
formance data in the form of energy use, indoor environmental quality,
occupant satisfaction, comfort, health, and productivity, and first and
life-cycle (operating) costs to quantify the relative benefits of the tech-
nology. See Chapter 13 for a discussion of example projects based pri-
marily on field and case study efforts. Other ongoing field studies are
reported by CBE (2002).
14.1.7 Productivity Studies
Due to the recognized significance of potential productivity gains
from UFAD and TAC system performance, more research is needed to
improve our understanding of what impact the provision of individual
control and improved building environmental quality has on worker
productivity. Due to the difficulty in quantifying productivity in todays
largely knowledge-based work environment, innovative research
approaches must be devised to address this issue of critical economic
significance.
14.1.8 Cost Studies
In addition to analyzing cost data from completed projects, the
development of a comprehensive and robust cost model is needed to
allow comparisons between UFAD system designs with conventional
systems.
14.2 DESIGN TOOLS
As more research is completed to improve the fundamental under-
standing of several key design issues related to energy and comfort per-
formance of UFAD systems, new design tools can be developed. Such
tools are needed to address several important topics, including the fol-
lowing:
Energy simulation model: As described above, the development of a
whole-building energy simulation program is of critical importance
to designers.
CHAPTER 14FUTURE DIRECTIONS
188
Cooling load calculation: The determination of design cooling air
quantities must take into account key differences between a ther-
mally stratified space and a well-mixed space. Practitioners cite this
issue as one of the most important unanswered questions regarding
UFAD design.
Thermal decay in underfloor plenum: The prediction of variations
in supply air temperatures throughout the plenum is needed for
proper system design.
Thermal storage strategies: The optimization and control of the
exposed thermal mass (slab and floor panels) in the underfloor ple-
num may allow improved energy performance.
14.3 STANDARDS AND CODES
As discussed in Chapter 11, since UFAD and TAC systems are rel-
atively new to the building industry, some features and performance
characteristics of these systems may be interpreted to be in conflict
with applicable standards and codes. Efforts are now underway within
ASHRAE to revise some of these standards to make them more com-
patible with UFAD and TAC technology [e.g., ASHRAE 1990, 1992].
It is highly likely that other standards and code language (for example,
NFPA, 90A, UBC, etc.) may need revisions and/or new sections spe-
cifically addressing UFAD and TAC applications.
14.4 BUILDING INDUSTRY DEVELOPMENTS
As UFAD technology continues to grow, it can be expected that
more manufacturers, designers, and contractors will become involved.
Developments that are needed from these key players include addi-
tional UFAD products, new design methods, and improved construc-
tion and installation techniques. All of these developments should lead
to reduced system costs.
14.5 TECHNOLOGY TRANSFER
As more information becomes available, it is important that various
forms of technology transfer be used to help inform the industry at large
about UFAD systems. These include publications, training courses,
workshops, design guides and tools, and targeted training packages for
building operators and occupants. The objective is to help design
UFAD systems that are energy efficient, intelligently operated, and
effective in their performance.
189
Glossary
access floor
A platform structure typically consisting of 0.6 m 0.6 m (2 ft 2
ft) concrete-filled steel floor panels supported on pedestals 0.2 to 0.46
m (8 in. to 18 in.) above the concrete structural floor slab. Each panel
can be independently removed for easy access to the underfloor plenum
created below and can include openings for electrical outlets, grilles, or
any other floor accessory in its thickness. In most office installations,
carpet tiles are laid on top to provide a finished floor surface. Raised
floor systems provide maximum flexibility and significantly lower
costs associated with reconfiguring building services.
active diffuser
Any air supply outlet that relies on a local fan to deliver air from the
plenum through the diffuser into the conditioned space of the building.
air change effectiveness (ACE)
Air change effectiveness describes the ability of an air distribution
system to provide ventilation (outside) air at the breathing zone (where
occupants breathe). ACE is defined as the age of air that would occur
throughout the space if the air were perfectly mixed, divided by the
average age of air where occupants breathe.
air changes per hour (ACH)
A measure of the air exchange rate of a building, or space, that gives
the time unit in hours.
air exchange rate
A measure of the rate at which the volume of air contained within
a space is replaced by supply (outside, conditioned, or recirculated) air.
This is expressed in terms of air changes per hour (ACH) and found by
GLOSSARY
190
dividing the airflow rate (volume per hour) by the volume of the space
or building.
airflow
The movement of airtypically defined as that within a defined
volume such as a room, duct, or plenum.
air-handling unit (AHU)
The component of an HVAC system that is responsible for condi-
tioning and delivering air through the system. Within the AHU, a por-
tion of the return air from the conditioned space is recirculated and
mixed with incoming outside air for conditioning and delivery to the
space, and the remainder is exhausted to the outside. The AHU typi-
cally contains one or more supply and return fans for maintaining air
movement and heating/cooling coils and filters to condition the air. The
cooling coil and other equipment, as necessary, are used to control the
moisture content of the air.
air inlet (see also air outlet)
Inlets are apertures through which air is intentionally drawn from
a conditioned space. Grilles, diffusers, and louvered openings can all
serve as inlets. Examples are return inlets at ceiling level and floor dif-
fusers that become return inlets for specially designed perimeter heat-
ing solutions for open plenum designs.
air outlet (see also air inlet)
Outlets are apertures through which air is intentionally delivered
into a conditioned space. Grilles, diffusers, and louvered openings can
all serve as outlets. Examples are floor and ceiling diffusers.
air supply volume
The volume of supply air flowing through a cross-sectional plane
of a duct per unit time. Found by multiplying air velocity by the cross-
sectional area of the duct, measured in cubic feet per minute (cfm) or
liters per second (L/s).
air velocity
The rate at which air travels in a given direction, measured as a dis-
tance per unit time. The units used vary according to the scale of the
phenomenon; in the HVAC field, air velocity is commonly expressed
as feet per minute (fpm) or meters per second (m/s).
ambient air
Air in the general surroundings of the space in question, whether an
external or internal space. Generally this refers to areas outside of work
locations for the building occupants.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
191
ASHRAE
American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
cable management
Addresses the distribution, routing, and overall organization of
cable networks installed in underfloor plenums. Raised floors came
into widespread use as a means of containing and concealing the exten-
sive cabling of typical voice, power, and data systems and are now a
common feature in contemporary office buildings. In this respect, con-
cerns that the installation of a UFAD system will entail additional con-
struction costs can be mitigatedthe decision to install a raised floor
system is often made for communications purposes, regardless of the
type of HVAC system chosen.
ceiling-based systems
A ceiling-based air distribution system supplies air to, and removes
air from, a conditioned space at ceiling level. Both supply and return
grilles are located in the ceiling plane, above which there will be a ceil-
ing plenum of sufficient depth to accommodate the extensive supply
ductwork, as well as other building services. Relying on the principle
of mixing-type air distribution, ceiling-based supply and return sys-
tems are designed to condition the entire volume of the space (floor to
ceiling), thereby providing a single uniform thermal and ventilation
environment. This control strategy provides no opportunity to satisfy
different thermal preferences among the building occupants.
ceiling plenum
The open space between the underside of a structural concrete slab
and a suspended ceiling, through which supply (ceiling-based system)
or return air (both ceiling- and floor-based systems) is delivered.
churn rate
This term (%/year) is used to describe the annual percentage of
workers and their associated work spaces in a building that are recon-
figured or undergo significant changes. A recent IFMA survey found
an average churn rate of 44% for U.S. office buildings. Although pri-
marily addressing the reorganization of staff members, any changes
within the personnel structure of a company typically involve the relo-
cation, upgrading, or expansion of equipment and/or office furniture
and even space planning. With conventional ceiling-based HVAC sys-
tems, changes in workspace configurations can be restricted by the
location of ceiling grilles; due to the higher cost associated with recon-
figuring overhead ducted systems, these changes are often not made,
GLOSSARY
192
resulting in potentially poorer performance by the system. The flexi-
bility of UFAD systems, in terms of quick replacement/relocation of
diffusers and easy access to the underfloor plenum, helps reduce a com-
pany's churn costs significantly. However, by being located on the
floor, UFAD diffusers will generally need to be reconfigured more fre-
quently in response to changes in the office layout than with overhead
systems; this increases the likelihood of improved system perfor-
mance.
clear zone
During the placement of floor diffusers, a clear zone is typically
defined as an imaginary cylinder of specified diameter around the cen-
ter point of the diffuser. Clear zones are generally 0.9-1.8 m (3-6 ft) in
diameter, depending on manufacturer's data, and represent an area
within which long-term occupancy is not recommended.
Although local thermal conditions may be acceptable for short-
term occupancy, and when under direct individual control by the occu-
pant, air velocities may be too high and temperatures too low (under
cooling conditions) within clear zones to satisfy the thermal comfort
preferences of a large majority of occupants (> 80%). Diffuser place-
ment should take this into consideration and maintain a distance of at
least half the diameter of the clear zone between occupants' seating and
their diffusers.
conditioned air
Air that has been treated, typically in an air-handling unit, by alter-
ing one or more of the following properties: temperature, humidity,
cleanliness (filtering), or mixture of outside and recirculated air.
conditioned space
A space within a building served by an HVAC system supplying
conditioned air in order to achieve acceptable thermal comfort and
indoor air quality conditions.
constant air volume, variable temperature (CAV-VT)
A control strategy of an air supply system in which varying heating
and cooling loads are met by adjusting the temperature of the supply air,
keeping the airflow volume constant. Alternatively a variable-air-vol-
ume (VAV) system can be employed in which the airflow volume is var-
ied, while the temperature remains constant.
conventional systems
A typical, conventional air distribution system supplies air to, and
removes air from, a conditioned space at ceiling level. Both supply and
return grilles are located in the ceiling plane, above which there will be
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
193
a ceiling plenum of sufficient depth to accommodate the extensive sup-
ply ductwork, as well as other building services. Relying on the prin-
ciple of mixing-type air distribution, ceiling-based supply and return
systems are designed to condition the entire volume of the space (floor
to ceiling), thereby providing a single uniform thermal and ventilation
environment. This control strategy provides no opportunity to satisfy
different thermal preferences among the building occupants.
cooling load
In the context of HVAC systems, the cooling load of a space is the
amount of heat generated within that space (from any source) that the
HVAC system must remove. Sources of heat in an office space typically
include occupants, electrical equipment, artificial lighting, and solar
radiation through the building envelope.
core zone
Typically the area at the center of the floor plan containing the ser-
vices and circulation spaces, such as the elevator shaft, fire escape
stairs, and equipment room. The AHU is also often located in this zone.
damper
A device that varies the volume of air flowing through a contained
cross section (e.g., a duct, inlet, outlet, or plenum) by varying the cross-
sectional area through which the air is routed.
diffuser
An air supply outlet through which conditioned air is discharged
into a space.
A wide variety of diffusers can be located in the ceiling (ceiling-
based HVAC system), floor (underfloor air distribution system), or
integrated into the furniture (task/ambient conditioning system) and
configured to deliver air in various directions and patterns.
displacement ventilation (DV)
In displacement ventilation systems (used for cooling only), low-
velocity supply air at a temperature slightly below room temperature is
introduced into the occupied zone of a space at low leveldiffusers are
usually configured as large-area floor pedestals or low side-wall. By
extracting air from the space at ceiling level, an overall floor-to-ceiling
airflow pattern is produced. This upward movement of air in the room
takes advantage of the natural buoyancy of heat gain to the space. As
air is heated and rises into the region above the occupied zone, some of
it exits the space with only partial mixing with the room air. Space con-
taminants also migrate upward, producing higher concentrations in the
warm, stratified air near the ceiling. Displacement ventilation systems
GLOSSARY
194
aim to minimize mixing of supply air with room air, instead maintain-
ing conditions in the occupied zone as close as possible to that of the
conditioned supply air, leading to an improved air change effective-
ness.
draft
Movement of air causing undesirable local cooling of a body due to
one or more of the following factors: low air temperature, high velocity,
or inappropriate airflow direction.
dry-bulb temperature
The air temperature indicated by an ordinary thermometer.
duct
A duct is an encased conduit, usually constructed of sheet metal and
having a round, square, or rectangular cross section through which air
moves around an HVAC system. Other types of duct construction
include fibrous glass ducts (rigid fiberglass with aluminum facing) and
flexible ducts (used to connect diffusers, mixing boxes, and other ter-
minal units to the air distribution system).
ductwork
The network of ducts comprising an HVAC system, typically con-
necting the AHU to supply, return, intake, and exhaust grilles and
underfloor and ceiling plenums. Ductwork can be exposed or con-
cealed within floor or ceiling plenums, services zones, and plant rooms.
economizer (see outside air economizer)
energy use
A term referring to the energy used by a system or component in the
course of its operation. In the context of HVAC, this would include
energy used by components such as fans, refrigeration and heating
equipment, cooling towers, and pumps.
entrainment (see also secondary air motion)
Air discharged from an outlet creates a swirling, jet, or other air
motion that pulls (entrains) the surrounding air into its path where it
mixes with the supply air.
exfiltration (see also infiltration)
The uncontrolled, unintentional flow of inside air out of a building.
This can occur through cracks in any building component, around
openings that are not airtight, and during the everyday use of windows
and doors. Like natural ventilation, exfiltration is caused by differences
in air-pressure or density between inside and outside.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
195
exhaust air
The air extracted from a space and discharged to the outdoors. This
is distinct from air extracted from one space and sent to another or recir-
culated within the HVAC system.
exhaust opening, or inlet
Any opening, a grille for example, through which air is removed
from a space.
fan coil unit
A fan terminal unit with a heating (electric or hot water) and/or
cooling (chilled water) coil on the discharge of the unit.
fan-powered mixing box
A compartment containing an integral fan that mixes two air sup-
plies before being discharged. In underfloor applications, these boxes
may be configured as having one ducted inlet supplying room or return
air, for example, to be mixed with plenum air entering the box through
an unducted opening. A reheat coil can be added to the discharge of the
unit.
fan terminal unit
A compartment containing an integral fan that delivers a constant
or variable volume of air to the space. These units are often used in
perimeter and other special zones where large and rapid changes in
cooling and/or heating load requirements occur.
first costs
The initial costs involved in a building project, typically incurred
during the construction and installation stages.
floor-to-floor height
The vertical height between the finished-floor level of a space in a
multi-story building and that of the floor immediately above or below
it.
forced ventilation
A term used to describe the use of fans and intake and exhaust vents
to mechanically distribute ventilation and other conditioned air
throughout a building. Buildings operating forced ventilation systems
are generally pressurized to reduce infiltration. This term is often con-
trasted with natural ventilation.
grille
A perforated or louvered covering on any area that air passes
through. Grilles can be placed in the ceiling, floor, or wall and can be
fixed, or adjustable.
GLOSSARY
196
HVAC (heating, ventilating, and air-conditioning) system
An HVAC system provides heating, ventilation, and air-condition-
ing to a building, either as a combined process or as individual opera-
tions.
individual control
Used to describe a system incorporating individual, or occupant,
control in which occupants are able to adjust the operating parameters
according to their personal preferences. In the context of HVAC, under-
floor systems can include grilles designed for easy occupant adjust-
ment of the direction and volume of supply air serving their workspace.
indoor air quality (IAQ)
This term generally refers to quantifiable properties of the respira-
ble air inside a building. Chemical, biological, and physical factors,
such as the air temperature, humidity, gaseous composition, and con-
centrations of pollutants, are considered indicators of the quality of air
to which occupants are exposed. Providing a sufficient rate of ventila-
tion to exhaust heat, moisture, and pollutants generated inside a build-
ing is a key component of meeting IAQ standards such as those in
ASHRAE Standard 62, which provides designers with guidelines for
achieving acceptable ventilation rates and indoor air quality.
infiltration (see also exfiltration)
The uncontrolled, unintentional flow of outdoor air into a building.
This can occur through cracks in any building component, around
openings that are not airtight, and during the everyday use of windows
and doors. Like natural ventilation, infiltration is caused by differences
in air pressure or density between inside and outside.
interior zone
Spaces located farther than 5 m (15 ft) from the faade, which can
be either high-occupancy (accommodating a number of work spaces)
or low-occupancy (circulation or general meeting areas, for example).
Except on the top floor of a building, spaces within this zone are gen-
erally not directly affected by loads generated by the building envelope,
such as solar heat gain or heat loss.
isothermal
Of constant temperature (e.g., an isothermal air jet has the same
temperature as the surrounding air).
life-cycle costs
A measure of the total costs involved in a building project, calcu-
lated by including initial costs (e.g., construction and installation) and
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
197
those estimated over the lifetime of the building (e.g., long-term oper-
ation and maintenance). Considerations of life-cycle costs are impor-
tant when making decisions at the initial design stage.
localized ventilation (see also underfloor air distribution
[UFAD] system)
Air distribution systems that supply air to a number of localized
areas within the occupied zone, typically at floor or desktop level, are
termed localized ventilation. Underfloor air distribution systems oper-
ate on the principles of localized ventilation.
lower zone
The volume of a conditioned space below the stratification height
produced by a DV or UFAD system.
mechanical ventilation
A term used to describe the use of fans and intake and exhaust vents
to mechanically distribute ventilation and other conditioned air
throughout a building. Buildings operating mechanical ventilation sys-
tems are generally pressurized to reduce infiltration. This term is often
contrasted with natural ventilation.
mixing systems (also known as mixing-type air distribution)
In mixing systems, conditioned air is delivered to the space at veloc-
ities much greater than those acceptable to occupants. Conventional
overhead air distribution is an example of a mixing system. Supply air
temperature may be above, below, or equal to the air temperature in the
occupied zone. The incoming high-velocity air mixes rapidly with the
room air by entrainment so that by the time it enters the occupied zone
its temperature and velocity are within an acceptable range. Mixing
systems are designed to maintain the entire volume of air in the space
(floor to ceiling) at a relatively uniform temperature, humidity, and air
quality condition.
natural ventilation
When air moves into and out of a building through intentional or
planned routes, without the assistance of mechanical equipment, this is
termed natural ventilation. Generally driven by pressure differences,
inlets and outlets include windows, doors, grilles, roof openings, and
other designed apertures. This is often contrasted with forced or
mechanical ventilation.
occupant control
Used to describe a system incorporating individual, or occupant,
control in which occupants are able to adjust the operating parameters
according to their personal preferences. In the context of HVAC, under-
GLOSSARY
198
floor systems can include grilles designed for easy occupant adjust-
ment of the direction and volume of supply air serving their workspace.
occupied zone
The volume of a conditioned space containing the occupants of the
space. Typically this is taken as extending from floor level up to a height
of 1.8 m (6 ft), and sometimes considered as set in 0.6 m (2 ft), on plan,
from external walls.
outside air
This term can denote either the air outside a building or air taken
into a building that has not previously been circulating through the
HVAC system.
outside air economizer
An HVAC control strategy that uses outside air under suitable cli-
matic conditions to reduce or eliminate the required mechanical cool-
ing. When the outside air temperature is less than the required supply
air temperature during cooling periods, the economizer allows a build-
ings mechanical ventilation system to use up to 100% outside air,
thereby reducing the energy required to cool the mixture of outside air
and warm recirculated air under normal operating conditions. This
method of cooling, often described as free cooling, is widely used in
temperate climates where outside air temperatures rarely go above 21-
24C (70-75F) during most days and periodically will be less than the
supply air temperatures (nighttime economizer cycles are frequently
employed, for example). As UFAD systems supply air at a higher tem-
perature than that for ceiling-based systems (typically 18C (65F) for
UFAD, 13C (55F) for ceiling HVAC), many North American tem-
perate climates will have a significantly larger number of daytime
hours during which the economizer can be used. Some method of vari-
able-volume relief must be provided to exhaust the extra outside air to
the outside. In addition, enthalpy-based economizer control is recom-
mended to maintain proper humidity levels (particularly during night-
time) and protect against condensation in the plenum. See Chapter 7 for
more discussion.
overhead systems
A typical, overhead air distribution system supplies air to, and
removes air from, a conditioned space at ceiling level. Both supply and
return grilles are located in the ceiling plane, above which there will be
a ceiling plenum of sufficient depth to accommodate the extensive sup-
ply ductwork, as well as other building services. Relying on the prin-
ciple of mixing-type air distribution, ceiling-based supply and return
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
199
systems are designed to condition the entire volume of the space (floor
to ceiling), thereby providing a single uniform thermal and ventilation
environment. This control strategy provides no opportunity to satisfy
different thermal preferences among the building occupants.
passive diffuser
Any air supply outlet that relies on a pressurized underfloor plenum
to deliver air from the plenum through the diffuser into the conditioned
space of the building. Passive diffusers have no local fans associated
with them, although they can be converted to an active diffuser by
attaching a fan-powered outlet box to the underside of the diffuser.
perimeter zone
This is the zone immediately adjacent to, and within 5 m (15 ft) of,
the external faade, which is affected by weather and outside condi-
tions. Perimeter spaces require special consideration in terms of their
heating and cooling loads, which are significantly different from and
change much more frequently than those of internal/core zone areas.
This is due to the influence of factors such as solar gain and heat gain/
loss through the building envelope.
plenum (see also service plenum)
Any defined space, typically above a suspended ceiling or beneath
a raised floor, through which supply air and/or voice, power, and data
cabling and other building services can be distributed.
plenum height
The vertical distance between the top surface of a structural floor
slab and the top surface of the raised floor system above it, which con-
tains, and defines, the underfloor plenum. Accounting for the typical
thickness of raised floor panels, the clear space within the underfloor
plenum will be 33 mm (1.3 in.) less than the plenum height.
plenum inlet
Any location in an underfloor plenum where conditioned air that
has been ducted from the air handler is discharged into the plenum.
plenum partition
A partition, typically formed from vertically oriented sheet metal,
erected within the plenum in order to divide up the plan of a conditioned
space and create separate zones within the underfloor area.
pressurized plenum
In this system configuration, the underfloor plenum is under a pos-
itive static pressure produced by the central AHU that drives the air
GLOSSARY
200
along the plenum and up through the diffusers. Typical pressures are
quite low (12.5-25 Pa [0.05-0.1 in. H2O]).
psychrometric
Relating to psychrometry, the study of atmospheric conditions
particularly the level of moisture in air. In terms of HVAC systems, psy-
chrometric charts are useful for illustrating the relationship between
properties such as wet- and dry-bulb temperatures and absolute and rel-
ative humidities when determining the desired supply air conditions.
raised floor
A platform structure typically consisting of 0.6 m 0.6 m (2 ft 2
ft) concrete-filled steel floor panels supported on pedestals 0.2 to 0.46
m (8 in. to 18 in.) above the concrete structural floor slab. Each panel
can be independently removed for easy access to the underfloor plenum
created below and can include openings for electrical outlets, grilles, or
any other floor accessory in its thickness. In most office installations,
carpet tiles are laid on top to provide a finished floor surface. Raised
floor systems provide maximum flexibility and significantly lower
costs associated with reconfiguring building services.
recirculated air
Return air that is diverted from the exhaust route, mixed with
incoming outside air (in some systems, recirculated air bypasses the
cooling coil and is mixed with the cool air leaving the coil to produce
the warmer supply air temperatures used in UFAD designs), passed
through the AHU for conditioning, and delivered to the conditioned
spaceessentially a means of recycling the air circulating through an
HVAC system for energy-saving purposes.
return air
The air extracted from a conditioned space (typically at ceiling
level) and returned to the air-handling unit (AHU), where a portion is
recirculated and the remainder is exhausted to the outside.
secondary air motion (see also entrainment)
Air discharged from an outlet creates a swirling, jet, or other air
motion that pulls (entrains) the surrounding air into its path where it
mixes with the supply air.
sensor
A device that can detect and measure a variable, for example, air
temperature, velocity, humidity, or light levels.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
201
service plenum
Any defined space, typically above a suspended ceiling or beneath
a raised floor, through which supply air and/or voice, power, and data
cabling and other building services can be distributed.
stagnant zone
A volume of a space in which there is low air velocity and the poten-
tial for increased stratification and poorer air quality.
static pressure (see also total pressure; velocity pressure)
Pressure is the force exerted per unit area by a gas or liquid. In air
distribution systems, static pressure is equal to the total pressure minus
velocity pressure and represents the pressure exerted by the air at rest.
Air distribution pressures are typically measured in inches of water (in.
H
2
O) or pascals (Pa).
stratification (see also thermal stratification)
The creation of a series of horizontal layers of air with different
characteristics (e.g., temperature, pollutant concentration) within a
conditioned space. UFAD systems, and other displacement ventilation-
based systems, rely on the upward convection of air driven by thermal
plumes to remove heat loads and contaminants from a space. This
results in both thermal and pollutant stratification in which a layer of
warmer, more polluted air forms above the occupied zone where it will
not affect the occupants.
stratification height (see also displacement ventilation)
In a displacement ventilation (DV) system, a horizontal interface,
known as the stratification height, is established at the height in the
room where the airflow rate in the thermal plumes equals the total sup-
ply air volume entering the room at or near the floor level. The strati-
fication height divides the room into two zones (upper and lower)
having distinct airflow conditions. The lower zone below the stratifi-
cation height has no recirculation and is close to displacement flow.
The upper zone above the stratification height is characterized by recir-
culating flow producing a fairly well-mixed region. In a properly
designed displacement ventilation system, the stratification height is
maintained near the top of the occupied zone (1.8 m [6 ft]). In UFAD
systems, a stratification height similar to that found in DV systems is
formed, but the airflow conditions in the lower zone are changed due
to the greater mixing provided by the turbulent floor diffusers.
supply air
The air entering a space through an outlet, diffuser, or grille, having
been delivered from the air-handling unit (AHU).
GLOSSARY
202
supply duct
Any duct through which supply air is delivered to the conditioned
space from the AHU, local fan, or other air movement device.
task/ambient conditioning (TAC) system
Any space conditioning system that allows occupants to individu-
ally control the thermal environment in the localized zone of their work
space while still maintaining acceptable environmental conditions in
the buildings ambient spaces (circulation and open-use spaces, for
example). This is typically achieved by enabling occupants to adjust
the volume and direction of the air supply serving their workspace,
according to their personal preferences. TAC systems, therefore, gen-
erally include a large number of supply diffusers throughout a building,
many located in close proximity to the occupants. Although not a
requirement, most TAC systems are integrated with the use of under-
floor air distribution.
thermal comfort
That condition of mind that expresses satisfaction with the thermal
environment. Thermal comfort is influenced by both subjective and
objective factors. Heat transfer between the human body and the envi-
ronment, and hence acceptance of the thermal environment, is influ-
enced by a combination of environmental factors (air temperature,
radiant temperature, air velocity, humidity) and personal factors (cloth-
ing and activity level). There is also evidence that people who know
they have control over their local thermal environment are more toler-
ant of temperature variations, making it easier to satisfy their comfort
preferences.
thermal plume
The upward movement of warm air due to buoyancy forces above
a heat source (e.g., person, computer, lights) in a room. The air volume
in a rising thermal plume increases with height as the plume entrains
ambient air.
thermal stratification (see also stratification)
The creation of a series of horizontal layers of air having increasing
temperature with height within a conditioned space. UFAD systems,
and other displacement ventilation-based systems, rely on the upward
convection of air driven by thermal plumes to remove heat loads and
contaminants from a space. This results in both thermal and pollutant
stratification in which a layer of warmer, more polluted air forms above
the occupied zone where it will not affect the occupants.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
203
thermostat
An automatic control device that is responsive to temperature and
used to control temperature in a conditioned space or zone. In the con-
text of UFAD systems, thermostats located in an office space (typically
installed on walls) register changes in ambient air temperature. These
devices communicate information to the HVAC control unit, which
adjusts the temperature, or airflow volume, of the supply air to maintain
the temperature measured at the thermostat within a pre-programmed
comfort range around a setpoint temperature.
thermostatic control
A means of automatically controlling the operation of an HVAC
system component, collection of components, or complete system in
response to information about air temperatures as registered by one or
more thermostats located within the conditioned space.
total pressure (see also static pressure; velocity pressure)
Pressure is the force exerted per unit area by a gas or liquid. In air
distribution systems, total pressure is equal to the sum of static pressure
and velocity pressure. Air distribution pressures are typically measured
in inches of water (in. H
2
O) or pascals (Pa).
underfloor air distribution (UFAD) system
An underfloor air distribution (UFAD) system uses an underfloor
plenum (open space between the structural concrete slab and the under-
side of a raised floor system) to deliver conditioned air, from the AHU,
directly into the occupied zone of the building. Air can be delivered
through a variety of supply outlets typically located at floor level or
integrated as part of the office furniture and partitions. Return grilles
are located at ceiling level or at least above the occupied zone. Under
cooling conditions, underfloor systems produce an overall floor-to-
ceiling airflow pattern, similar in principle to displacement ventilation.
This upward convection of warm air is used to efficiently remove heat
loads and contaminants from the space. In contrast to true displacement
ventilation systems, UFAD systems deliver supply air at higher vol-
umes and higher velocities, enabling higher heat loads to be met.
Although the supply air is delivered in close proximity to occupants,
the risk of draft discomfort is minimized, as supply air temperatures are
higher than those for conventional ceiling-based systems, and occu-
pants have some amount of control (typically volume and sometimes
direction and temperature) over their local air supply conditions.
GLOSSARY
204
underfloor plenum
The open space between a structural concrete slab and the under-
side of a raised access floor system. Commonly used as the access route
for telecommunications cabling, in underfloor systems the supply air is
also delivered through this space.
upper zone
The volume of a conditioned space above the stratification height
produced by a DV or UFAD system.
variable air volume (VAV)
A control strategy of an air supply system in which varying heating
and cooling loads are met by adjusting the airflow volume, keeping the
temperature of the air constant. Alternatively, a constant air volume,
variable temperature (CAV-VT) system can be employed in which the
temperature of the airflow is varied, while the volume is kept constant.
VAV box
A variable-air-volume control box. Typically, a VAV box is ducted
on its inlet and uses dampers to control the volume of air discharged
from the unit.
velocity pressure (see also static pressure; total pressure)
Pressure is the force exerted per unit area by a gas or liquid. In air
distribution systems, velocity pressure is the pressure due to the veloc-
ity and density of the moving air. Air distribution pressures are typi-
cally measured in inches of water (in. H
2
O) or pascals (Pa).
ventilation
The process of intentionally supplying outside air to a building
achieved by either natural or mechanical (forced) means.
ventilation effectiveness
Ventilation effectiveness describes the systems ability to remove
pollutants generated by internal sources in a space, zone, or building.
In comparison, air change effectiveness describes the ability of an air
distribution system to ventilate a space, zone, or building.
zero-pressure plenum
In this system configuration, the underfloor plenum is maintained
at very nearly the same static pressure as that of the conditioned space.
Supply air is delivered to the plenum by the central AHU, and small
fan-powered air outlets are used to discharge air from the plenum into
the conditioned space. Some systems may create a slight negative pres-
sure in the plenum to draw recirculated air (typically directly from the
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
205
room through open floor grilles, or down from the ceiling through
shafts) into the plenum where it is mixed with the supply air from the
AHU.
zone
Also known as a control zone for an HVAC system, a zone is
defined as a space or group of spaces in a building having similar heat-
ing and cooling requirements throughout its occupied area so that com-
fort conditions may be controlled by a single thermostat.
zoning (see also interior zone; perimeter zone)
The practice of dividing a building into smaller zones for control of
the HVAC system. For example, buildings may be zoned into individ-
ual floors, rooms, or spaces with distinct loads, such as perimeter and
interior zones.
207
References and
Annotated Bibliography
Addison, M., and D. Nall. 2001. Cooling via underfloor air distribution:
Current design issues and analysis options. From: Cooling Fron-
tiers: The Advanced Edge of Cooling Research and Applications in
the Built Environment. College of Architecture and Environmental
Design, Arizona State University.
AEC. 2000. Design Brief: Underfloor air distribution and access floors.
Energy Design Resources web site, http://www.energydesignre-
sources.com. Architectural Energy Corporation, Boulder, CO.
This design brief is an introduction to underfloor air and access
floor systems and addresses the following topics: displacement
ventilation and hybrid underfloor systems, energy savings and
indoor air quality improvement, access floor system design and
construction, economics of combined underfloor air and access
floor systems, comfort and productivity issues, and applications of
underfloor air and access floor systems.
Akimoto, T., T. Nobe, and Y. Takebayashi. 1995. Experimental study on
the floor-supply displacement ventilation system. ASHRAE
Transactions, Vol. 101, Pt. 2.
Akimoto, T., T. Nobe, S.Tanabe, and K. Kimura. 1996. Experimental
study on indoor thermal environment and air quality of the floor-
supply displacement ventilation system. Proceedings, Indoor Air
1996, Nagoya, Japan, July 21-26.
Architectural Institute of Japan. 1993. Proceedings, Symposium on Floor-
Based Air Supply HVAC Systems, Tokyo, October 1 (in Japanese).
Useful for its brief outline of a wide range of subjects contained
within nine presentations on floor-based systems, covering general
energy conservation, indoor conditions, design and operation fun-
damentals, and specific examples of different installations.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
208
Architecture Week. 2000. Building for Harmony with nature. Archi-
tectureWeek, June 14, http://www.architectureweek.com/2000/
0614/building_1-1.html.
Arens, E.A., F. Bauman, L. Johnston, and H. Zhang. 1991. Testing of
localized ventilation systems in a new controlled environment
chamber. Indoor Air, No. 3, pp. 263-281.
Arens, E.A., and F.S. Bauman. 1994. Improving the performance of task
conditioning systems. Proceedings, International Symposium:
Issues on Task-Ambient Conditioning, Nagoya University, Nagoya,
Japan, January 11, pp. 77-94.
Arens, E., M. Fountain, T. Xu, K. Miura, H. Zhang, and F. Bauman. 1995.
A study of occupant cooling by two types of personally controlled
air movement. Proceedings, Pan Pacific Symposium on Building
and Urban Environmental Conditioning in Asia, Nagoya Univer-
sity, Nagoya, Japan, March 16-18.
This paper presents controlled environment chamber experi-
ments, using human subjects, on the effectiveness of air movement
cooling. Primarily relevant to residences, the findings are useful in
addressing the design of TAC systems. The desirable air velocities
chosen by participants were evaluated with reference to existing
comfort standards and used to propose a comfort zone for person-
ally controlled air movement.
Argon Corporation. 2002. Product information. Argon Corporation,
Naples, FL, http://www.argonair.com.
Arnold, D. 1990. Raised floor air distribution A case study. ASHRAE
Transactions, Vol. 96, Pt. 2.
Early case study on a building from design stage through to con-
struction highlights problem areas such as the construction and
sealing of underfloor plenums. Other issues include how to conceal
extract ducts in a building without ceiling voids, coordination of the
floor services installation and finishes, and optimum supply air
temperatures.
ASHRAE. 1990. ANSI/ASHRAE Standard 113-1990, Method of testing
for room air diffusion. Atlanta: American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE. 1992. ANSI/ASHRAE Standard 55-1992, Thermal environ-
mental conditions for human occupancy. Atlanta: American Soci-
ety of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE. 1993. Air-Conditioning Systems Design Manual. Atlanta:
American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
209
ASHRAE. 1996. ASHRAE Guideline 1-1996, The HVAC Commissioning
Process. Atlanta: American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
ASHRAE. 1997. ASHRAE Standard 129-1997, Measuring air change
effectiveness. Atlanta: American Society of Heating, Refrigerating
and Air-Conditioning Engineers, Inc.
ASHRAE. 2000. 2000 ASHRAE HandbookHVAC Systems and Equip-
ment. Atlanta: American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc.
ASHRAE. 2001a. 2001 ASHRAE HandbookFundamentals. Atlanta:
American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
ASHRAE. 2001b. ANSI/ASHRAE Standard 62-2001, Ventilation for
acceptable indoor air quality. Atlanta: American Society of Heat-
ing, Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE. 2001c. ANSI/ASHRAE/IESNA Standard 90.1-2001, Energy
standard for buildings except low-rise residential buildings.
Atlanta: American Society of Heating, Refrigerating and Air-Con-
ditioning Engineers, Inc.
ASHRAE. 2002. 2002 ASHRAE HandbookRefrigeration. Atlanta:
American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
ASHRAE. 2003a. 2003 ASHRAE HandbookHVAC Applications
Atlanta: American Society of Heating, Refrigerating and Air-Con-
ditioning Engineers, Inc.
ASHRAE. 2003b. Addendum n to ANSI/ASHRAE Standard 62-2001, Ven-
tilation for acceptable indoor air quality. Atlanta: American Soci-
ety of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASTM. 2000. ASTM E779-99: Test Method for Determining Air Leakage
Rate by Fan Pressurization. Philadelphia: American Society for
Testing and Materials.
Barker, C.T. 1985. Ensuring insurers work in comfort. Chartered
Mechanical Engineer, November.
Barker, C.T., G. Anthony, R. Waters, A. McGregor, and M. Harrold. 1987.
Lloyds of London. Air Conditioning: Impact on the Built Environ-
ment. New York: Nichols Publishing Company.
A comprehensive study of one of the earliest buildings to use an
underfloor plenum as a services zone. Discussion ranges from the
technical (e.g., thermal performance of the slab) to the conceptual
(e.g., the architecture of air conditioning).
Barnaby, C., E. Dean, F. Fuller, D. Nall, T. Shelley, and T. Wexler. 1980.
Utilizing the thermal mass of structural systems in buildings for
REFERENCES AND ANNOTATED BIBLIOGRAPHY
210
energy conservation and peak power reduction. Shelley, Dean and
Fuller, Architects, Berkeley Solar Group, Berkeley, Calif.
A comprehensive report on structural systems and their energy-
and power-savings benefit within the context of two North Amer-
ican climates. The report covers three areas: (1) building sub-
systems related to structural cooling, (2) thermal performance of a
prototypical building comprising the optimum subsystems, (3) esti-
mated cost and life-cycle cost analysis for the prototype building.
Bauman, F.S., L. Johnston, H. Zhang, and E. Arens. 1991a. Performance
testing of a floor-based, occupant-controlled office ventilation sys-
tem. ASHRAE Transactions, Vol. 97, Pt. 1.
Presents the results of experiments in a controlled chamber con-
figured to resemble an office with modular partitions, investigating
the effects of supply volume, location, and direction, supply/return
temperature difference, heat load density, and workstation size and
layout. Using ASHRAE test methods current in 1991, overhead
supply systems scored a higher performance rating. This paper con-
cludes the comfort benefits of occupant control over the local envi-
ronment are not adequately addressed in existing performance and
comfort standards.
Bauman, F.S., K. Heinemeier, H. Zhang, A. Sharag-Eldin, E. Arens, W.
Fisk, D. Faulkner, D. Pih, P. McNeel, and D. Sullivan. 1991b.
Localized thermal distribution for office buildings, Final report
Phase I. Center for Environmental Design Research, University of
California, Berkeley, June, 81 pp.
Bauman, F.S., G. Brager, E. Arens, A. Baughman, H. Zhang, D. Faulkner,
W. Fisk, and D. Sullivan. 1992. Localized thermal distribution for
office buildings, Final reportPhase II. Center for Environmental
Design Research, University of California, Berkeley, December,
220 pp.
This report presents the results of research in five key areas: (1)
survey of industry perspective on task conditioning systems, (2)
laboratory experiments, (3) recommendations to improve localized
thermal distribution system performance, (4) whole building
energy simulations, and (5) building standards and codes.
Bauman, F.S., and M. McClintock. 1993. A study of occupant comfort
and workstation performance in PG&Es advanced office systems
testbed. Center for Environmental Design Research, University of
California, Berkeley, May, 135 pp.
Bauman, F.S., H. Zhang, E. Arens, and C. Benton. 1993. Localized com-
fort control with a desktop task conditioning system: Laboratory
and field measurements. ASHRAE Transactions, Vol. 99, Pt. 2.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
211
This paper presents the results of both laboratory and field mea-
surements investigating the thermal performance of desktop task
conditioning systems. Interesting for its consideration of the ther-
mal conditions resulting from a range of nozzle sizes.
Bauman, F., E. Arens, M. Fountain, C. Huizenga, K. Miura, T. Xu, T.
Akimoto, H. Zhang, D. Faulkner, W. Fisk, and T. Borgers. 1994.
Localized thermal distribution for office buildings, Final report
Phase III. Center for Environmental Design Research, University
of California, Berkeley, July, 115 pp.
This report presents the results of research completed during
phase III of the localized thermal distribution (LTD) project, cov-
ering three task areas: (1) whole-building energy simulations, (2)
field studies, and (3) LTD engineering applications guide outline.
Includes comprehensive field studies on two buildings, located in
Phoenix, Arizona, and San Ramon, California.
Bauman, F.S., E.A. Arens, S. Tanabe, H. Zhang, and A. Baharlo. 1995.
Testing and optimizing the performance of a floor-based task con-
ditioning system. Energy and Buildings, Vol. 22, No. 3, pp. 173-
186.
A comprehensive report of controlled environmental chamber
experiments studying the thermal performance of a floor-based
TAC system. Discussion includes a summary of research to date,
use of the latest thermal manikin model, analysis involving the
effect of supply volume, grille direction and Archimedes number of
air supply jets, and concise design recommendations for improving
TAC system performance.
Bauman, F., ed. 1995. Proceedings: Workshop on task/ambient condition-
ing systems in commercial buildings, San Francisco, CA, 4-5 May
1995. Center for Environmental Design Research, University of
California, Berkeley, October.
A collection of literature from contributors to this workshop. A
broad range of industry interests are represented, from manufactur-
ers to commercial and academic research organizations.
Bauman, F., and T. Akimoto. 1996. Field study of a desktop task condi-
tioning system in PG&Es advanced office systems testbed. Cen-
ter for Environmental Design Research, University of California,
Berkeley.
Bauman, F.S. 1996. Task/ambient conditioning systems: Engineering
and application guidelines. Proceedings, 3rd International Con-
ference on Energy and Environment: Towards the Year 2000. Capri,
Italy.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
212
A concise, informative introduction to the concept of TAC sys-
tems in buildings. Provides a system description, and addresses
issues such as benefits, and how to achieve them, limitations (real
and perceived), and technology demands.
Bauman, F.S., and E.A. Arens. 1996. Task/ambient conditioning sys-
tems: Engineering and application guidelines. Center for Environ-
mental Design Research, University of California, Berkeley.
A comprehensive report on TAC, expanding on information in
the previous paper (see above reference), including detailed discus-
sions on issues such as system configurations, components and
mechanisms, room air distribution, relevant standards and codes,
energy use, design and construction guidelines, and system costs.
Bauman, F.S., T.G. Carter, A.V. Baughman, and E.A. Arens. 1998. Field
study of the impact of a desktop task/ambient conditioning system
in office buildings. ASHRAE Transactions, Vol. 104, Pt. 1, pp.
125-142.
This paper presents field measurements, including subjective
surveys and physical monitoring, carried out in three office build-
ings in San Francisco. The study is useful for its range of compar-
ative units of analyses. Measurements were taken in the buildings
before and after installation of the TAC systems and included a con-
trol group of workers without TAC units; follow-up tests performed
three months later were repeated under three different room tem-
perature conditions.
Bauman, F., P. Pecora, and T. Webster. 1999a. How low can you go? Air
flow performance of low-height underfloor plenums. Center for
the Built Environment, University of California, Berkeley, October.
This comprehensive report summarizes results from full-scale
testing of pressurized underfloor plenum configurations and their
influence on the uniform distribution of supply air to floor grilles.
Useful technical recommendations are cited, such as minimum,
plenum heights, the effect of obstructions or removing floor panels,
and plenum inlet conditions.
Bauman, F., K. Tsuzuki, H. Zhang, T. Stockwell, C. Huizenga, E. Arens,
and A. Smart. 1999b. Experimental comparison of three individ-
ual control devices: Thermal manikin tests. Final Report. Center
for Environmental Design Research, University of California, Ber-
keley.
Bauman, F. 1999. Giving occupants what they want: Guidelines for
implementing personal environmental control in your building.
Proceedings, World Workplace 99, Los Angeles, CA, 3-5 October
1999.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
213
Concise description of the principles of an underfloor TAC sys-
tem, potential benefits, guidelines on how to achieve them, and
ongoing work addressing current barriers (real and perceived) to
widespread use of the technology. Incorporates recent research
findings and outlines areas for future study.
Bauman, F., K. Powell, R. Bannon, A. Lee, and T. Webster. 2000a. Under-
floor air technology web site: http://www.cbe.berkeley.edu/under-
floorair. Center for the Built Environment, University of California,
Berkeley, December.
Bauman, F., V. Inkarojrit, and H. Zhang. 2000b. Laboratory test of the
Argon personal air-conditioning system (APACS). Center for
Environmental Design Research, University of California, Berke-
ley, April.
Bauman, F., and T. Webster. 2001. Outlook for underfloor air distribu-
tion. ASHRAE Journal, June, pp.18-25.
This paper first offers a system description, discusses the bene-
fits of underfloor technology, and then lists and discusses the tech-
nology needs or the current barriers to its widespread adoption.
Beck, P. 1993. Intelligent design passes IQ test. Consulting-Specifying
Engineer, January.
Case study of the West Bend Mutual Insurance Company Head-
quarters, Wisconsin, detailing the pressurized underfloor HVAC
system and environmentally responsive workstation control mod-
ules. Emphasizes the benefits of integrated system design and rela-
tionships between improved staff productivity and a more
comfortable work environment.
Brager, G.S., M.E. Fountain, C.C. Benton, E.A. Arens, and F.S. Bauman.
1993. A comparison of methods for assessing thermal sensation
and acceptability in the field. Proceedings, Thermal Comfort:
Past, Present and Future, ed. Nigel Oseland. British Research
Establishment, Watford, United Kingdom.
Brager, G.S., and R.J. de Dear. 1998. Thermal adaptation in the built
environment: A literature review. Energy and Buildings, Vol. 27,
pp. 83-96.
Brager, G.S., and R.J. de Dear. 2000. A standard for natural ventilation.
ASHRAE Journal, Vol. 42, No. 10, October, pp. 21-28.
Brill, M., and S. Margulis. 1984. Using office design to increase produc-
tivity. Buffalo, N.Y.: Buffalo Organization for Social and Techno-
logical Innovation.
Brown, M., and L. Scott. 2000. Underfloor air conditioning systems
Principles and applications. Carrier Global Engineering Confer-
ence, May 2000.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
214
Focusing on description and analysis of commercial systems
employing turbulent mixed flow outlets and displacement, this
paper includes case studies for applications such as an airport ter-
minal, aquatic center, university auditorium, trading floors within
high-rise office buildings, and a casino.
Building Owners and Managers Association (BOMA) International and
the ULI, the Urban Land Institute. 1999. What do office tenants
want: 1999 BOMA/ULI office tenant survey report. Washington,
D.C.: BOMA International and the ULI-the Urban Land Institute.
This paper presents a survey of 1,829 office tenants in the U.S.
and Canada. In the survey, the office tenants were asked to rate the
importance of 53 building features and amenities and to report how
satisfied they were with their current office space for those same
categories.
California Energy Commission. 2001. Nonresidential Manual for Com-
pliance with Californias 2001 Energy Efficiency Standards. Pub-
lication Number: P400-01-005, California Energy Commission.
CBE. 2002. Center for the Built Environment web site: http://
www.cbe.berkeley.edu. Center for the Built Environment, Univer-
sity of California, Berkeley.
Cho, S.H., W.T. Kim, K.T. Na, and K.S. Chung. 1998. Experimental
study on thermal characteristics of personal environment module
(PEM) system. Proceedings, Second International Conference on
Human-Environment System, Yokohama.
This paper presents the results of experiments, carried out in a
test chamber, comparing the thermal performance of PEM and
underfloor systems. The relative performance of each system is
considered in three zonesabove, below, and around the desk area
concluding the PEM provides a more advantageous overall thermal
environment, improving as flow rate increases. The effect of heat
generated by the system motor is also addressed.
Chung, K.-S., H.-T. Han, C.-G. Cho, S.-H. Kong, and M.-K. Cho. 1999.
A study on the characteristics of indoor environment and comfort
in office building with underfloor air-conditioning (UFAC) sys-
tem. Proceedings, Indoor Air 99, Edinburgh, Scotland.
Physical measurements indicated noise levels from floor termi-
nal units served by a fan-powered air supply are overcome by typ-
ical background office noise, and recorded contaminant levels are
cited as much lower than those for a conventional ceiling supply
system as measured by another research team.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
215
Commonwealth of Pennsylvania. 1999. Guidelines for Creating High
Performance Green Buildings. Pennsylvania Department of Envi-
ronmental Protection.
This study looks at green systems (including site, enclosure,
mechanical, interiors, and materials) as well as the green design
and construction process. It includes 12 case studies.
Cornell University. 1999. Case study: 901 Cherry Gap Headquarters.
http://dea.human.cornell.edu/Ecotecture/Case%20Studies/Gap/
gap_home.htm. Ecotecture site, Department of Design and Envi-
ronmental Analysis, Cornell University, Ithaca, N.Y.
Crockett, J. 2002. Undervalued? Underfloor air systems have been
around for quite some time now, but is the market embracing the
technology or discounting it as a specialty solution? Consulting-
Specifying Engineer, January.
This article looks at the current status of underfloor systems in
the marketplace. Crockett discusses reasons why underfloor is still
not commonly used, some of its benefits, and available web
resources.
Croome, D.J., and D. Rollason. 1988. Freshness, ventilation and tem-
perature in offices. Proceedings of CIB Conference on Healthy
Buildings 88, 5-8 September, Stockholm.
Daly, A. 2002. Underfloor air distribution: Lessons learned. ASHRAE
Journal, Vol. 44, No. 5, May, pp. 21-24.
Presents three strategies for capturing as many benefits of under-
floor air distribution as possible while keeping the initial cost to a
minimum: minimize the ductwork in the plenum, prevent plenum
leakage, and dont oversize airflows.
Dasher, C., A. Potter, and K. Stum. 2002. Commissioning to meet
green expectations. Portland Energy Conservation, Inc. web
site: http://www.peci.org.
David, J. 1984. Under floor air conditioning. Journal of the Chartered
Institution of Building Services, August.
de Dear, R., and G.S. Brager. 1998. Developing an adaptive model of
thermal comfort and preference. ASHRAE Transactions, Vol. 104,
Pt. 1.
Under the hypothesis that contextual factors and past thermal
history modify building occupants thermal expectations and pref-
erences, a worldwide thermal comfort database was compiled
examining thermal sensation, acceptability, and preference from
observations in 160 buildings. The results formed the basis of a pro-
posal for a variable indoor temperature standard.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
216
Drake, P., P. Mill, and M. Demeter. 1991. Implications of user-based
environmental control systems: three case studies. IAQ 91,
Healthy Buildings. Atlanta: American Society of Heating, Refrig-
erating and Air-Conditioning Engineers, Inc.
Presents the results of surveys of the occupants of three buildings
with underfloor systems allowing user-controls, in order to argue
the case for designers, owners, and managers considering a broader
range of user-responsive systems.
Drake, P., P. Mill, V. Hartkopf, V., Loftness, F. Dubin, G. Zigara, and J.
Posner. 1991. Strategies for health promotion through user-based
environmental control: a select international perspective. IAQ 91,
Healthy Buildings. Atlanta: American Society of Heating, Refrig-
erating and Air-Conditioning Engineers, Inc.
Ellison, J., and B. Ramsey. 1989. Access flooring: Comfort and conve-
nience can be cost-justified. Building Design & Construction,
April.
Energy Design Resources. 2000. Underfloor air distribution offers
energy efficiency and much more! eNews for Designers, Issue 18,
October 27, http://www.energydesignresources.com.
Engineering Interface Limited. 1993. Personal control and 100% out-
side-air ventilation for office buildings. Report prepared for Effi-
ciency and Alternative Energy Technology Branch, CANMET,
Canada.
Faulkner, D., W.J. Fisk, and D.P. Sullivan. 1993. Indoor air flow and pol-
lutant removal in a room with desktop ventilation. ASHRAE
Transactions, Vol. 99, Pt. 2.
Faulkner, D., W.J. Fisk, and D.P. Sullivan. 1995. Indoor air flow and pol-
lutant removal in a room with floor-based task ventilation: Results
of additional experiments. Building and Environment, Vol. 30, No.
3, pp. 323-332.
This laboratory study on the determinants of indoor air flow pat-
terns with a floor-based task ventilation system discusses relation-
ships between average age of air, the supply-airs piston-like flow
pattern, and height. Experimental variables include intra-room
transport of tobacco smoke particles (produced mechanically), sup-
ply-air flow rate, temperature, direction, and internal heat loads,
measured using a tracer gas procedure.
Faulkner, D., W.J. Fisk, D.P. Sullivan, and D.P. Wyon. 1999 Ventilation
efficiencies of desk-mounted task/ambient conditioning systems.
Indoor Air, No. 9, pp. 273-281.
Outlines required outdoor air content and supply airflow rate and
direction for optimum values of air exchange effectiveness and pol-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
217
lution removal efficiency in the breathing zone of heated manikins
with desk-mounted air outlets.
Faulkner, D., W.J. Fisk, D.P. Sullivan, and S.M. Lee. 2002. Ventilation
efficiencies of a desk-edge-mounted task ventilation system. Pro-
ceedings of Indoor Air 2002, Monterey, CA, 30 June 5 July 2002.
Federspiel, C.C., G. Liu, M. Lahiff, D. Faulkner, D. Dibartolomeo, W.J.
Fisk, P. Price, and D. Sullivan. 2002. Indoor environmental
effects on work performance. Proceedings of Indoor Air 2002,
Monterey, CA, June 30 July 5.
Fisk, W.J., D. Faulkner, D. Pih, P. McNeel, F. Bauman, and E. Arens.
1991. Indoor air flow and pollutant removal in a room with task
ventilation. Indoor Air, No. 3, pp. 247-262.
Fisk, W.J. and Faulkner, D. 1992. Air exchange effectiveness in office
buildings: Measurement techniques and results. Proceedings,
1992 International Symposium on Room Air Convection and Ven-
tilation Effectiveness, July 22-24, Tokyo, pp. 213-223. Atlanta:
ASHRAE.
Fisk, W.J., D. Faulkner, D., Sullivan, and F. Bauman, F. 1997. Air change
effectiveness and pollutant removal efficiency during adverse mix-
ing conditions. Indoor Air 7: 55-63.
Fisk, W. J. 2000. Health and productivity gains from better indoor envi-
ronments and their relationship with building energy efficiency.
LBNL-45484, Lawrence Berkeley National Laboratory, July 31.
Fisk, W.J., P. Price, D. Faulkner, D. Sullivan, D. Dibartolomeo, C. Fed-
erspiel, G. Liu, and M. Lahiff. 2002. Productivity and ventilation
rate: Analyses of time-series data for a group of call center work-
ers. Proceedings of Indoor Air 2002, Monterey, CA, June 30 July
5.
Fountain, M.E., and E.A. Arens. 1993. Air movement and thermal com-
fort. ASHRAE Journal, Vol. 35, No. 8, August, pp. 26-30.
Fountain, M.E. 1993. Locally controlled air movement preferred in
warm environments. Ph.D. dissertation, Department of Architec-
ture, University of California, Berkeley, November, 196 pp.
This research dissertation focuses on air movement at ambient
and cooler-than-ambient temperatures, examining the transition
between desirable cooling and uncomfortable draft, and proposing
a percent of satisfied people model as a function of air movement
in warm conditions. Experiments include the use of a thermal man-
ikin exposed to a range of air velocities from floor- and desk-
mounted air diffusers and human subjects exposed to the same con-
ditions but given control of the air supply velocity.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
218
Fountain, M., E. Arens, R. de Dear, F. Bauman, and K. Miura. 1994.
Locally controlled air movement preferred in warm isothermal
environments. ASHRAE Transactions, Vol. 100, Pt. 2, 14 pp.
A condensed version of the previous dissertation.
Fujita, H., and K. Sakai. 1996. Room air temperature profiles in under-
floor air distribution system. Proceedings, Indoor Air 1996,
Nagoya, Japan, July 21-26.
The proposed model for estimating room air temperature pro-
files and flow patterns indicates the significant relationship
between heat and temperature profiles and the need for accurate
measurements of heat loads.
Fukao, H., M. Oguro, K. Hiwatashi, and M. Ichihara. 1996. Environ-
ment evaluation in an office with floor-based air-conditioning sys-
tem in an office building. Proceedings, 5th International
Conference on Air Distribution in Rooms, ROOMVENT 96, Yoko-
hama, Japan.
Presents the results of field measurements and a survey ques-
tionnaire concerning the thermal environment in an office building
employing both floor- and ceiling-based systems. Significant dif-
ferences were observed only for air particle concentrations.
Includes a graphical analysis of thermal sensations over different
parts of the human body.
Fukao, H., M. Oguro, M. Ichihara, and S. Tanabe. 2002. Comparison
of underfloor versus overhead air distribution systems in an office
building. ASHRAE Transactions, Vol. 108, Pt. 1.
Genter, R.E. 1989. Air distribution for raised floor offices. ASHRAE
Transactions, Vol. 95, Pt. 2.
Greenheck. 2002. Product information. Greenheck, Schofield, WI,
http://www.greenheck.com.
GSA. 1992. GSA access floor study. U.S. General Services Admin-
istration, Washington, D.C., E.B. Commission No. 7211-911C,
September 10.
This report presents a detailed 25-year present value analysis and
study of the use of access floor systems in GSA office facilities with
the aim of determining the best value for open plan offices. Useful
and comprehensive for comparative means. In addition to studying
three different access floor systems, the analysis considers both
steel- and concrete-framed building structures.
Guttmann, S. 2000. Raising the bar, with raised floors. Consulting-
Specifying Engineer, October.
Hanzawa, H., and Y. Nagasawa. 1990. Thermal comfort with underfloor
air-conditioning systems. ASHRAE Transactions, Vol. 96, Pt. 2.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
219
Presents the results of experiments, carried out in a test chamber
with human occupants, measuring the subjective perception of sup-
ply air flow from a floor outlet. Conclusions of a low draft risk with
underfloor air systems are based on the draft charts of Fanger et al.
(1988).
Hanzawa, H., Y. Nagasawa, and T. Mortyama. 1993. Field measurements
of thermal comfort in occupied zones of buildings installed with
under-floor air-conditioning systems. Proceedings, Room Air
Convection and Ventilation Effectiveness. Atlanta: ASHRAE.
From field measurements of two office buildings with underfloor
air-conditioning systems, looking at room air temperatures, air
velocities, and responses to questionnaires on air movement and
drafts, this paper concludes that internal conditions are comfortable
according to standard thermal indexes.
Hanzawa, H., and M. Higuchi. 1996. Air flow distribution in a low-
height underfloor air distribution plenum of an air conditioning sys-
tem. AIJ Journal Technological Design, No. 3, pp. 200-205,
December.
This paper presents the results of experiments with scale models
of underfloor plenums, investigating the characteristics, observed
problems, and possible countermeasures of air flow within low-
height plenums. Experimental parameters included varying air sup-
ply inlet number and type, obstacles and guide vanes within the ple-
num. In conclusion, low-height pressurized plenums are found to
be feasible within an optimum range of floor area per outlet ratio.
Harris, L., and Associates. 1989. Office environment index 1989. Grand
Rapids, Mich.: Steelcase, Inc.
Hartman, T. 1993. New zone controls help achieve total environmental
quality. Heating/Piping/Air Conditioning, Nov. 1993.
Hasegawa, K., 1991. Installation example of the personal air condition-
ing in USA Johnson Controls Inc.s office. Journal of the Society
of Heating, Air-conditioning and Sanitary Engineers of Japan, Vol.
65, No.7.
Hawataik, H., K.-S. Chung, K.-J. Jang. 1999. Thermal and ventilation
characteristics in a room with underfloor air-conditioning system.
Proceedings, Indoor Air 99, Edinburgh, Scotland.
Outlines the results of testing in a conference room with under-
floor air-conditioning, including measurements of horizontal and
vertical room air temperature distributions and CO
2
concentrations
and infrared imaging of temperature distributions over a person
standing on a floor-based supply outlet.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
220
Hedge, A., A. Michael, and S. Parmelee. 1992. Reactions of facilities
managers and office workers to underfloor task air ventilation.
Journal of Architectural Planning and Research.
This paper presents results from field study surveys of user reac-
tion to underfloor systems as compared to overhead ventilation in
their previous workplaces, the first survey of this kind in the U.S.
Results are presented with consideration of human factors and
ergonomics and discussion as to why occupant control is often
voted a primary benefit, yet rarely exercised.
Heinemeier, K.E., G.E. Schiller, and C.C. Benton. 1990. Task condi-
tioning for the workplace: Issues and challenges. ASHRAE Trans-
actions, Vol. 96, Pt. 2.
Heinemeier, K.E., G. Brager, C. Benton, F. Bauman, and E. Arens. 1991.
Task/ambient conditioning systems in open-plan offices: Assess-
ment of a new technology. Center for Environmental Design
Research, University of California, Berkeley, September.
Early commentary on the level of knowledge regarding task/
ambient conditioning and identification of specific issues needing
further research at the start of the 90s. The detailed analysis of sys-
tem principles, strategies, and the effect of task/ambient systems on
comfort and energy use remains relevant to present-day applica-
tions.
HGA. 2002. ADC World Headquarters & Technology Campus. Ham-
mel, Green and Abrahamson, Inc., Minneapolis, Minn.
Hibiya Sogo Setsubi Corporation. 1993. Floor-based air supply HVAC
system design manual.
Hisaki, H., S. Kanno, Y. Kayahara, M. Mizuno, Y. Nakamura, M. Okubo,
and K. Ueda. 1991. Installation example of a radiant personal air
conditioning system for automated offices Kobe Harborland
area. SHASE Journal, Special Edition: Personal Air Condition-
ing, Vol. 65, No. 7. Tokyo: The Society of Heating, Air-Condition-
ing, and Sanitary Engineers of Japan.
Early case study of the application of an underfloor system with
both floor- and partition-mounted diffusers.
Hockman, R. 2002. Personal communication. Tate Access Floors, Inc.,
Jessup, Md.
Hosni, M.H., B.W. Jones, and H. Xu. 1999. Experimental results for
heat gain and radiant/convective split from equipment in build-
ings. ASHRAE Transactions, Vol. 105, Pt. 1.
Houghton, D. 1995. Turning air conditioning on its head: Underfloor air
distribution offers flexibility, comfort, and efficiency. E Source
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
221
Tech Update TU-95-8, E Source, Inc., Boulder, Colo., August, 16
pp.
A good general summary of underfloor air distribution systems,
providing an objective overview of the technology. Both the bene-
fits and potential drawbacks, including advice on how to avoid
them, are presented. Sections include an outline of different system
types, economic appraisal, market trends, products and manufac-
turers, all well illustrated with graphics and photographs.
IFMA. 1997. Benchmark III. International Facility Management Asso-
ciation, Houston, Tex.
Imagawa, N., and T. Mima. 1991. Installation example of an all air sys-
tem: Fujita headquarters building. SHASE Journal, Special Edi-
tion: Personal Air Conditioning, Vol. 65, No. 7. Tokyo: The Society
of Heating, Air-Conditioning, and Sanitary Engineers of Japan (in
Japanese).
Int-Hout, D. 1998. Air distribution for comfort and IAQ. HPAC Engi-
neering, March, pp. 59-70.
Int-Hout, D. 2001. Pressurized Plenum Access Floor Design Manual.
Carrier, November.
An overview of issues and design considerations, this manual
includes history, basic concepts, advantages of the system, design
considerations, design challenges, a summary of current research,
and the Carrier approach.
ISO. 1994. International Standard 7730. Moderate thermal environ-
ments Determination of the PMV and PPD indices and specifica-
tion of the conditions for thermal comfort. Geneva: International
Standards Organization.
Ito, H., and N. Nakahara. 1993. Simplified calculation model of room air
temperature profile in underfloor air-conditioning system. Pro-
ceedings, Room Air Convection and Ventilation Effectiveness.
Atlanta: ASHRAE.
Using this simplified calculation model, a close correlation
between calculated and measured vertical temperature distribu-
tions indicated a level of accuracy suitable for use in HVAC design
applications and that variations in room dimensions have little
influence on room air temperature profiles.
Iwamoto, S. 1999. A study on numerical prediction method of indoor
environment including human body. Proceedings, International
Conference on Air Distribution in Rooms, ROOMVENT 99.
The author compares two numerical methods of calculating a
three-dimensional model of air flow and temperature around an
occupants body, based on a curvilinear coordinate system. The
REFERENCES AND ANNOTATED BIBLIOGRAPHY
222
detailed predictions possible with such models are necessary when
evaluating personal (task-ambient) conditioning installations.
Jeong, K.-B., and J.-J. Kim.1999. Individual air distribution control sys-
tem on partition panel at personal task area. Proceedings, Indoor
Air 99, Edinburgh, Scotland.
This paper investigates the optimum location of outlets for occu-
pant comfort within a personal task area, concluding that location
is the most critical factor in improving supply air efficiency.
Johnson Controls. 2002. Product information. Johnson Controls, Mil-
waukee, WI, http://www.jci.com.
Kaczmarczyk, J., Q. Zeng, A. Melikov, and P.O. Fanger. 2002. Individ-
ual control and peoples preferences in an experiment with a per-
sonalized ventilation system. Proceedings, ROOMVENT 2002,
Copenhagen, Denmark, 8-11 September 2002.
Karvonen, A. 2001. The revolution is underfoot. Environmental Design
and Construction, January/February.
An overview of underfloor air systems, this article presents its
history, system mechanics, benefits, barriers, and resources for a
less specialized audience in the building industry.
Kight, D. 1992. Epson flexes its technological muscles. Facilities
Design and Management, February.
General case study on Epsons corporate headquarters building
in Torrance, California, in its time one of the largest applications of
an underfloor air distribution system in America. Includes a
description of the access floor and task air modules.
Kim, I.G., and H. Homma. 1992. Possibility for increasing ventilation
efficiency with upward ventilation. ASHRAE Technical Data Bul-
letin. Vol. 8, No. 2.
The results of experiments comparing upward and downward
ventilation systems, in an office-like test space with human occu-
pants, indicate changes in room CO
2
content are less affected by
upward then downward ventilation. This paper also concludes that
ventilation rates for removing occupant-produced contaminants in
the breathing zone can be low providing supply air temperatures are
less than room air temperatures.
Kim, I.G., and H. Homma. 1992 Distribution and ventilation efficiency
of CO
2
produced by occupants in upward and downward ventilated
rooms. ASHRAE Technical Data Bulletin, Vol. 8, No. 2.
This paper expands on the results of the previous experiments by
the authors (see reference above) to include a more detailed anal-
ysis of factors influencing efficient removal of CO
2
content from a
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
223
room, such as occupant-produced metabolic heat and CO
2
concen-
tration stratification.
Kim, Y., K. Lee, and H. Cho. 2001. Experimental study of flow char-
acteristics of a diffuser for underfloor air-conditioning system.
ASHRAE Transactions, Vol. 107, Pt. 1.
In this study a new diffuser for the underfloor air-conditioning
system is developed and flow characteristics for isothermal condi-
tions are studied. The new diffuser consists of two sectionsan
internal section for generating swirl flow and an edge section for
vertical flow. The study concludes that the new diffuser has desir-
able characteristics.
Kohyama, M., M. Mizuno, Y. Nakamura, Y. Sekimoto, K. Akagi, Y. Kun-
imatsu, and K. Otaka. 1996. Field measurements of the indoor
environment of an office with a task-ambient air conditioning sys-
tem. Proceedings, 5th International Conference on Air Distribu-
tion in Rooms, ROOMVENT 96, Yokohama, Japan.
Evaluation of a computer center equipped with conventional
ceiling outlets in ambient areas and occupant-controlled floor out-
lets in task areas. Outlines differences in room air temperatures
between the two zones and the need to consider varying occupant
activity levels of workers when setting task area temperatures.
Konishi, H., H. Hanzawa, and M. Higuchi. 1996. Study on occupied
zone air conditioning system using seats. Proceedings, 5th Inter-
national Conference on Air Distribution in Rooms, ROOMVENT
1996, Yokohama, Japan.
A study of the characteristics of air flow velocities and temper-
ature distributions around the human body using typical audito-
rium/theater seats fed with supply air from below the seat. Of
interest for highlighting alternative applications of personal condi-
tioning underfloor air supply systems.
Krepchin, I. 2001. Underfloor air systems gain foothold in North Amer-
ica. E Source Report, ER-01-1. Boulder, Colo.: Financial Times
Energy, Inc., January.
Presents market information. Report includes sections with
headings on The Market Expands, Why Is the Market Grow-
ing? What Challenges Remain? as well as an appendix of man-
ufacturers and buildings using underfloor air.
Kroll, K. 2001. Customer driven real estate: Fisher Properties wants to
find better ways to serve tenants need for speed and flexibility.
One step is to let them leave on 30 days notice. Building Operating
Management, May.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
224
Underfloor air distribution is cited as a way in which buildings
can be flexible to accommodate different tenants.
Kroner, W., J. Stark-Martin, and T. Willemain. 1992. Using advanced
office technology to increase productivity: The impact of environ-
mentally responsive workstations (ERWs) on productivity and
worker attitude. The Center for Architectural Research, Rensse-
laer, Troy, NY.
An in-depth case study on the ERWs with individualized con-
trols, installed in the new West Bend Mutual Insurance Headquar-
ters, Wisconsin. Useful as a reference for its range of subjective
assessment and measurement techniques and means of internal val-
idation.
Lee, H., and F. Bauman. Development of an air leakage test methodology
for underfloor plenums. To be submitted to ASHRAE Transac-
tions.
Levy, H. 2002. Individual control by individual VAV. Proceedings,
ROOMVENT 2002, Copenhagen, Denmark, 8-11 September 2002.
This paper presents a study on sensible cooling by varying air
velocity (VAV) through personal air outlets adjustable by occu-
pants. The paper concludes that the system tested and described in
the paper will air condition individual people instead of the build-
ing and will eliminate dissatisfaction with thermal conditions.
Lin, Y.-J., and P.F. Linden. 2002. Modeling an underfloor air distribu-
tion system. Proceedings, ROOMVENT 2002, Copenhagen, Den-
mark, 8-11 September 2002.
Livchak, A., and D. Nall. 2001. Displacement ventilation Application
for hot and humid climate. Proceedings, Clima 2000/Napoli 2001
World Congress, Naples, Italy, 15-18 September 2001.
Loftness, V., P. Mathew, G. Gardner, C. Mondor, T. Paul, R. Yates, and M.
Dellana. 1999. Sustainable development alternatives for specula-
tive office buildings: A case sudy of the Soffer Tech Office Build-
ing. Final report. Center for Building Performance and
Diagnostics, Carnegie Mellon University, Pittsburgh, Pa.
This 38-page report documents the analysis of sustainable
design alternatives for the Tech Office Building. Raised floor for
HVAC and networking is included along with 13 other sustainable
alternatives such as faade glazing and shading, roof insulation,
lighting, energy recovery, etc.
Loftness, V., R. Brahme, M. Mondazzi, E. Vineyard, and M. MacDonald.
2002. Energy savings potential of flexible and adaptive HVAC
distribution systems for office buildings Final report. Air Con-
ditioning and Refrigeration Technology Institute 21-CR Research
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
225
Project 605-30030, June. Full report available at http://www.arti-
21cr.org/research/completed/index.html.
This paper documents the performance of recent developments
in flexible and adaptive distribution systems in office buildings and
also documents the barriers and opportunities for both industry and
professional practice in the development of innovative, flexible,
and adaptive HVAC distribution systems.
Loomans, M.G.L.C., and P.G.S. Rutten. 1997. Task conditioning + dis-
placement ventilation, 1+1>2? Proceedings, Healthy Buildings/
IAQ 1997, Washington, D.C., Vol. 2.
Full-scale measurements and CFD simulations in an office con-
figuration with desk-based displacement ventilation lead to the
conclusion that micro/macro climate distinction, an underlying
principle of TAC systems, is less pronounced than desired and open
to improvement.
Loomans, M.G.L.C., F.J.R. van Mook, and P.G.S. Rutten. 1996. The
introduction of the desk displacement ventilation concept. Pro-
ceedings, 5th International Conference on Air Distribution in
Rooms, ROOMVENT 96, Yokohama, Japan.
Loudermilk, K. 1999. Underfloor air distribution solutions for open
office applications. ASHRAE Transactions, Vol. 105, Pt. 1.
This paper outlines design and operation criteria for underfloor
air distribution systems to optimize performance and minimize
costs. Includes a useful description of temperature distributions
and zone differentiation within a room and tables for sensible heat
gain analysis.
Mass, D. 1998. Underfloor air still an underused tool. Facilities Design
and Management, December.
Matsunawa, K., H. Iizuka, and S. Tanabe. 1995. Development and appli-
cation of an underfloor air conditioning system with improved out-
lets for a smart building in Tokyo. ASHRAE Transactions, Vol.
101, Pt. 2.
Maybaum, M. 1999. A breath of fresh air: The air side of HVAC systems
offers overlooked opportunities to reduce costs and improve IAQ.
Building Operating Management, January.
This paper discusses advances on the air side of HVAC design,
including low-temperature air distribution, demand-controlled
ventilation, filtration choices, sizing for real-world demand, and
underfloor air distribution.
McCarry, B.T. 1995. Underfloor air distribution systems: Benefits and
when to use the system in building design. ASHRAE Transactions,
Vol. 101, Pt. 2.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
226
This paper addresses the optimum context and application for
underfloor air distribution systems. Illustrated with reference to
three buildings in Vancouver, Canada, the discussion addresses
design, mechanical systems issues, potential benefits, and where
the use of an underfloor air system is, or is not, appropriate.
McCarry, B.T. 1998. Innovative underfloor system. ASHRAE Journal,
March.
Case study of a library building in Vancouver featuring a low-
pressure underfloor air distribution system. The financial and oper-
ational success of the system exemplifies the potential for under-
floor applications outside the genre of office buildings.
McQuillen, D. 2001. 3 case studies for improved IAQ. Environmental
Design + Construction, posted 1/24/2001, http://www.edc-
mag.com.
Melikov, A.K., R. Cermak, and M. Majer. 2002. Personalized ventila-
tion: Evaluation of different air terminal devices. Energy and
Buildings, Vol. 34, pp. 829-836.
Mundt, E. 1990. Convection flows above common heat sources in
rooms with displacement ventilation. Proceedings, ROOMVENT
1990, Oslo, Norway.
Murakami, S., S. Kato, T. Tanaka, D.-H. Choi, and T. Kitazawa. 1992.
The influence of supply and exhaust openings on ventilation effi-
ciency in an air-conditioned room with a raised floor. ASHRAE
Technical Data Bulletin, Vol. 8, No. 2.
Muratani, H., 1991. Office facilities institute, the latest analysis of cor-
porate office environment and personalization. Journal of the
Society of Heating, Air-conditioning and Sanitary Engineers of
Japan, Vol. 65, No. 7.
Nagoya University. 1994. Proceedings, International Symposium: Issues
on task-ambient air-conditioning. Nagoya, Japan, January 11.
Nailor Industries. 2002. Product information. Nailor Industries, Hous-
ton, TX, http://www.nailor.com.
Nakahara, N., and H. Ito. 1993a. Prediction of mixing energy loss in a
simultaneously heated and cooled room: Part 1Experimental anal-
yses of factorial effects. ASHRAE Transactions, Vol. 99, Pt. 1, pp.
100-114.
Nakahara, N., and H. Ito. 1993b. Prediction of mixing energy loss in a
simultaneously heated and cooled room: Part 2 Simulation anal-
yses on seasonal loss. ASHRAE Transactions, Vol. 99, Pt. 1, pp.
115-128.
Nakamura, Y., M. Mizuno, Y. Sekimoto, K. Akagi, Y. Kunimatu, K.
Otaka, and M. Kohyama.1996. Study on thermal comfort and
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
227
energy conservation of task-ambient air conditioning system. Pro-
ceedings, 5th International Conference on Air Distribution in
Rooms, ROOMVENT 96, Yokohama, Japan.
A comparative study of three air-conditioning systems (conven-
tional, underfloor, and task/ambient) including measurements of
temperature distributions within the 360 horizontal plane sur-
rounding an occupant, with floor outlets both on and off.
Nakamura, Y., M. Mizuno, O. Ueno, Y. Sekimoto, K. Akagi, Mishima, K.
Okata, and M. Kohyama, M. 1998. Study on thermal comfort con-
ditions of task-ambient air conditioning system. Proceedings,
International Conference on Air Distribution in Rooms, ROOM-
VENT 98, June 6, Stockholm, Vol. 1.
This study investigated the most suitable floor outlet supply-air
conditions in which sedentary occupants are comfortable. Exper-
iments with human subjects, who were able to control their supply
air volume and direction, found most subjects directed the supply
jet toward their bodies, for cooling within the optimum temperature
range, whether the air flow hit them directly or not.
Nielsen, P.V. 1996. Displacement Ventilation Theory and Design.
Department of Building Technology and Structural Engineering,
Aalborg University, Aalborg, Denmark.
NFPA. 1999. NFPA 90A, Standard for the Installation of Air-Condition-
ing and Ventilating Systems. Quincy, Mass.: National Fire Protec-
tion Association.
Oguro, M., H. Fukao, M. Ichihara, Y. Kobayashi, and N. Maehara. 1995.
Evaluation of a floor-based air-conditioning system performance
in an office building. Proceedings, Pan Pacific Symposium on
Building and Urban Environmental Conditioning in Asia. Nagoya
University, Nagoya, Japan, 16-18 March.
Comparative field measurements and a questionnaire on thermal
comfort and indoor air quality for a building with both underfloor
and ceiling-based air-conditioning systems conclude little differ-
ence in the resulting thermal environments of each, but air particle
concentration was significantly less with the underfloor system.
Okamoto, A. 1991. Thermal performance of thermoelectric terminal
cooling and heating panel. Journal of the Society of Heating, Air-
conditioning and Sanitary Engineers of Japan, Vol. 65, No.7.
Paciuk, M. 1989. The role of personal control of the environment in ther-
mal comfort and satisfaction at the workplace. Doctoral disserta-
tion, University of Wisconsin, Milwaukee, Department of
Architecture.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
228
PECI. 2002. Portland Energy Conservation, Inc., web site: http://
www.peci.org. PECI, Portland, Ore.
Pedersen, C.O., D.E. Fisher, J.D. Spitler, and R.J. Liesen. 1998. Cooling
and Heating Load Calculation Principles. Atlanta: American
Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc.
Persily, A.K. 1986. Ventilation effectiveness measurements in an office
building. IAQ 86, Managing Indoor Air for Health and Energy
Conservation, pp. 548-567. Atlanta: American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.
Persily, A.K., and W.S. Dols. 1989. Field measurements of ventilation
and ventilation effectiveness in an office/library building. Indoor
Air, Vol. 1, No. 3, pp. 229-246.
Persily, A.K. 1999. Myths about building envelopes. ASHRAE Jour-
nal, March, pp. 39-45.
Portland General Electric. 2002. Earth Advantage/Building Profile:
CNF Information Technology Center. http://www.earthadvan-
tage.com/commercial/projects.asp. Portland General Electric,
Commercial and Industrial Energy Efficiency Programs, Portland,
Ore.
Post, N.M. 1993. Smart buildings make good sense. Engineering News
Record, May 17.
This article discusses intelligent buildings, how the building pro-
fession regards the technology, and what exactly constitutes a
smart building. Issues raised are illustrated with reference to
buildings featuring intelligent systems and advances made in the
field since the 1980s.
Price Industries. 2002. Product information. Price Industries, Suwanee,
Ga., http://www.price-hvac.com.
REHVA. 2001. Displacement Ventilation in Non-Industrial Premises (H.
Skistad, ed.). Federation of European Heating and Air-Condition-
ing Associations (REHVA).
Rock, B., and D. Zhu. 2001. A Designers Guide to Conventional Ceiling-
Based Room Air Diffusion. Atlanta: American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.
Rowlinson, D., and D.J. Croome. 1987. Supply characteristics of floor
mounted diffusers. Proceedings, ROOMVENT-87, Air Distribu-
tion in Ventilated Spaces, Session 1, 10-12 June, Stockholm.
Sandberg, M., and C. Blomqvist. 1989. Displacement ventilation sys-
tems in office rooms. ASHRAE Transactions, Vol. 95, Pt. 2.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
229
Schiller, G., E. Arens, F. Bauman, C. Benton, M. Fountain, and T.
Doherty. 1988. A field study of thermal environments and com-
fort in office buildings. ASHRAE Transactions, Vol. 94, Pt. 2.
Seem, J.E., and J. Braun. 1992. The impact of personal environmental
control on building energy use. ASHRAE Transactions, Vol. 98,
Pt. 1.
This paper compares the energy use characteristics of personal
environmental control (PEC) systems and conventional HVAC sys-
tems, concluding the benefits of increased staff productivity out-
weigh costs in other areas.
SHASE. 1991. Special edition: Personal air conditioning. SHASE
Journal., Vol. 65, No. 7. Tokyo: The Society of Heating, Air-Con-
ditioning, and Sanitary Engineers of Japan.
Shinkai, K., A. Kasuya, and M. Kato. 2000. Performance evaluation of
floor thermal storage system. ASHRAE Transactions, Vol.106, Pt.
1.
This paper describes results of peak shaving by a floor thermal
storage system in the design of the air-conditioning system for the
officially recognized environmentally conscious building No. 1
for the Osaka gas company.
Shute, R.W. 1992. Integrated access floor HVAC. ASHRAE Transac-
tions, Vol. 98, Pt. 1.
An overview of the evolution of floor-based HVAC, presented as
a case study of the six-year development period of an office project
in Toronto, Ontario, Canada. Discusses in detail two variations each
of compartmentalized and centralized systems, concluding with
comprehensive design guidelines and construction coordination
issues based on the experiences of the office project.
Shute, R.W. 1995. Integrated access floor HVAC: Lessons learned.
ASHRAE Transactions, Vol. 101, Pt. 2.
Skistad, H. 1994. Displacement Ventilation. Taunton, Somerset, England:
Research Studies Press Ltd.
Sodec, F. 1984. Air distribution systems report no. 3554A. Aachen,
West Germany: Krantz GmbH & Co., Sept. 19.
Comprehensive report from manufacturers of environmental
technology products, written in the early days of underfloor air
systems. Subjects covered range from characteristics of indoor air
flow to admissible sound pressure levels. The information-rich sec-
tions include experimental results, technical diagrams, and calcu-
lations.
Sodec, F., and R. Craig. 1990. The underfloor air supply system the
European experience. ASHRAE Transactions, Vol. 96, Pt. 2.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
230
Sodec, F., and R. Craig. 1991. Underfloor air supply system: Guidelines
for the mechanical engineer. Report No. 3787A. Aachen, West
Germany: Krantz GmbH & Co., January.
Although covering issues relevant for all designers, the language
used, and level of knowledge assumed of the reader, is targeted
toward mechanical engineers. Discussion ranges from technical
data for twist outlets to control zones to maintenance of room
humidity and underfloor air as a fire or smoke hazard.
Spoormaker, H.J. 1990. Low-pressure underfloor HVAC system.
ASHRAE Transactions, Vol. 96, Pt. 2.
This paper presents a case study of the development and opera-
tion of a low-pressure underfloor air-conditioning system installed
in a South African office building in the early 1980s. Includes use-
ful classifications of levels of flexibility, durability, reliability, and
maintainability for HVAC systems and a schematic description of
a low-pressure underfloor HVAC system.
Stanke, D., and B. Bradley. 2001. Turning air distribution upside down:
Underfloor air distribution. TRANE engineers newsletter, Vol. 30,
No. 4.
An overview for those not familiar with underfloor air, this arti-
cle touches on floor choices, air distribution options, approaches to
design, potential advantages, and growing pains.
Suwa, T., 1991. Installation example of an underfloor air conditioning
system, Toyo-cho building of Meiji Life Insurance Co. Journal of
the Society of Heating, Air-conditioning and Sanitary Engineers of
Japan, Vol. 65, No.7.
Case study of an underfloor system application featuring custom
designed floor outlets, each equipped with a 50 W fan unit and con-
trol mechanisms (manual and automatic).
Svensson, A.G.L. 1989. Nordic experiences of displacement ventilation
systems. ASHRAE Transactions, Vol. 95, Pt. 2.
TAK and Takenaka Corporation. 1993. Design and practice of under-
floor air conditioning systems. Tokyo: Gijutsu Shoin (in Japa-
nese).
Tamblyn, R.T. 1995. Toward zero complaints for office air condition-
ing. Heating/Piping/Air Conditioning, March.
This article cites 100% outside air systems and personal control
of air temperature and motion as two possibilities for reducing
occupant dissatisfaction with their office environments and dis-
cusses the means by which both can be operated without undue
increase in initial or operating costs. The hypothetical design of an
office building with these systems is used to illustrate the report.
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
231
Tamblyn, R.T. 1995. Toward zero complaints in air conditioning sys-
tems. Proceedings, 2nd International Conference on Indoor Air
Quality, Ventilation, and Energy Conservation in Buildings, Centre
for Building Studies, Concordia University, Montreal, May 9.
A study determining the microclimatic conditions, and associ-
ated occupant responses, created by a ceiling-mounted vertical air
jet conditioning system, with occupant-controlled thermostat,
installed in an office building in New York. The results conclude
that the level of individual control offered over temperature and air
motion overrides issues of air quality, temperature, and system per-
formance in determining levels of occupant satisfaction.
Tanabe, S. 1991. Role of personal air conditioning in office environ-
mental quality. Journal of the Society of Heating, Air-Condition-
ing and Sanitary Engineers of Japan, Vol. 65, No.7.
Tanabe, S. 1994. Thermal comfort aspects of underfloor air distribution
system. Proceedings, International Symposium: Issues on Task-
Ambient Air-Conditioning, Nagoya, Japan, January 11.
Tanabe, S., E. Arens, F. Bauman, H. Zhang, and T. Madsen. 1994. Eval-
uating thermal environments by using a thermal manikin with con-
trolled skin surface temperature. ASHRAE Transactions, Vol. 100,
Pt. 1, 10 pp.
Tanabe, S., and K. Kimura. 1996. Comparisons of ventilation perfor-
mance and thermal comfort among displacement, underfloor and
ceiling based air distribution systems by experiments in a real sized
office chamber. Proceedings, 5th International Conference on Air
Distribution in Rooms, ROOMVENT 96, Yokohama, Japan.
Presents the results of comparative measurements, carried out in
a test chamber with a thermal manikin, of contaminant concentra-
tions, age of air, and thermal comfort resulting from each of the
three system types. Includes an analysis of local skin temperatures
over various parts of the thermal manikin, highlighting differences
in the nonuniform thermal environments created by each air-con-
ditioning system.
Tanago, H., and M. Takeda. 1991. Experimental verification of com-
fortable personal air conditioning systems. SHASE Journal, Spe-
cial Edition: Personal Air Conditioning, Vol. 65, No. 7. Tokyo: The
Society of Heating, Air-Conditioning, and Sanitary Engineers of
Japan.
Tanago, H. 1991. Experimental estimation of personal air conditioning
system for workers. Journal of the Society of Heating, Air-Con-
ditioning and Sanitary Engineers of Japan, Vol. 65, No.7.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
232
Tanaka, H. 1991. Types and features of personal air conditioning.
SHASE Journal, Special Edition: Personal Air Conditioning, Vol.
65, No. 7. Tokyo: The Society of Heating, Air-Conditioning, and
Sanitary Engineers of Japan.
Comprehensive description of a range of generic personal air-
conditioning systems. Written at an early stage in the development
of this technology but still useful for the detail and scope of issues
addressed.
Tate Access Floors. 2002a. Product information. Tate Access Floors, Jes-
sup, Md., http://www.tateaccessfloors.com.
Tate Access Floors. 2002b. Building Technology PlatformUnder-
floor HVAC, wire and cable management system: Conceptual cost
study. Tate Access Floors, Inc., Jessup, Md.
Terranova, J. 2001. Underfloor ventilation: Raised-floor air distribution
for office environments. HPAC Engineering, March.
This article written for design engineers presents pros and cons
of raised-floor systems for office space, a cost analysis, and general
design considerations.
Trox. 1997. Building design optimization with underfloor air distribu-
tion in the San Francisco area. Trox USA, Alpharetta, Ga.
One of the most comprehensive collection of papers on under-
floor air distribution available. Provides the latest information and
guidelines on many aspects, including office space optimization,
comparisons of overhead and underfloor systems, load analysis,
design considerations, and a review of competitors systems. Each
topic is illustrated with test results, calculations (e.g., space heat
gain), charts (e.g., psychrometric), and a process analysis.
Trox. 1998. Economics of raised access floors with underfloor air for
office space environments. Trox Technik Technical Bulletin
TB080498, Trox USA, Alpharetta, Ga.
A comprehensive cost analysis of underfloor versus conven-
tional (poke through and cellular deck) systems covering issues
within constructional, operational, and relocation costs.
Trox. 2002. Product information. Trox USA, Alpharetta, Ga, http://
www.troxusa.com.
TRW FAA SETA. 1995. FAA SETA raised floor trade study. Draft Pre-
pared for the Federal Aviation Authority (FAA). This report com-
pares single-layer and triple-layer raised floor systems to determine
the optimum type for FAA facilities. A comprehensive study cov-
ering many issues from implications for electrical layouts to life-
cycle costing to environmental control. A good source of informa-
tion on an alternative raised floor configuration about which little
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
233
has been published despite examples of use cited dating from the
report (1995) back to 1984.
Tsuzuki, K., E.A. Arens, F.S. Bauman, and D.P. Wyon. 1999. Individual
thermal comfort control with desk-mounted and floor-mounted
task/ambient conditioning (TAC) systems. Proceedings of Indoor
Air 99, Edinburgh, Scotland, 8-13 August.
This paper outlines experiments comparing three TAC systems
(two desk-based, one floor-based) in terms of their effect on heat
loss from a thermal mannequin at various room temperatures.
Results indicate such systems are capable of considerably influenc-
ing control over the heat balance of an occupant.
Tuddenham, D. 1986. A floor-based approach. ASHRAE Journal, July.
Vranicar, M. 2002. Personal communication. Critchfield Mechanical,
Inc., Menlo Park, Calif.
Warson, A. 1990. The pin-striped office. Canadian Building, March.
Webster, T., et al. 1999-2002. UFAD Project Profiles. http://
www.cbe.berkeley.edu/underfloorair/whereHasItBeenDone.htm.
Underfloor air technology web site, Center for the Built Environ-
ment, University of California, Berkeley.
Webster, T., E. Ring, and F. Bauman. 2000. Supply fan energy use in
pressurized underfloor plenum systems. Center for the Built Envi-
ronment, University of California, Berkeley.
This preliminary study examines the impact of various design
assumptions on the fan energy consumption of pressurized under-
floor plenum systems, compared to traditional overhead constant-
air-volume and variable-air-volume systems.
Webster, T., F. Bauman, and J. Reese. 2002a. Underfloor air distribu-
tion: Thermal stratification. ASHRAE Journal, Vol. 44, No. 5,
May, pp. 28-36.
This article describes the idea of stratification, the control and
optimization of which is crucial for system design of underfloor
systems. This article focuses on practical implications of room air
stratification testing results for the control and operation of con-
stant-air-volume and variable-air-volume UFAD systems.
Webster, T., F. Bauman, J. Reese, and M. Shi. 2002b. Thermal stratifi-
cation performance of underfloor air distribution (UFAD) sys-
tems. Proceedings of Indoor Air 2002, Monterey, CA, 30 June5
July.
This paper presents tests to determine the impact of room air-
flow and supply air temperature (SAT) on the thermal stratification
in interior spaces, and the effect of blinds in perimeter spaces for
UFAD systems. Results are outlined and discussed.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
234
Webster, T., R. Bannon, and D. Lehrer. 2002c. Teledesic Broadband
Center. Center for the Built Environment, University of Califor-
nia, Berkeley, April.
Weiner, P.C. 1994. Time to look again at desktop control. Architectural
Record, May.
Wright, G. 1996. The underfloor air alternative. Building Design and
Construction, November.
Wyon, D.P. 1988. Ventilated floor systems with independent room air
terminals as the basis of a healthy office environment. Proceed-
ings, CIB Conference on Healthy Buildings 88, 5-8 September,
Stockholm.
Wyon, D.P. 1989. The use of thermal manikins in environmental ergo-
nomics. Scand. J. Work, Env. Health, 15 (Supplement), pp. 84-94.
Wyon, D.P., and M. Sandberg. 1990. Thermal manikin prediction of dis-
comfort due to displacement ventilation. ASHRAE Transactions,
Vol. 96, Pt. 1.
Wyon, D.P. 1994a. Thermal gradients, individual differences and air
quality. Proceedings, Healthy Buildings 94, Budapest,Vol. 2, pp.
765-770.
Wyon, D.P. 1994b. Current indoor climate problems and their possible
solution. Indoor Environment 1994:3:123-129.
Wyon, D.P. 1996. Individual microclimate control: Required range,
probable benefits and current feasibility. Proceedings, Indoor Air
96, July 21-26, Nagoya, Japan.
Based on experimental data, this paper provides new estimates
of required temperature ranges for individual control systems nec-
essary to ensure comfort for a given proportion of a group. Includes
estimates of the degree to which fan noise could be increased in
order to extend the range of individual thermal and air quality con-
trol without increasing occupant dissatisfaction and discussion of
the effects of individual control on group average productivity.
Yamanaka, T., R. Satoh, and H. Kotani. 2002. Vertical distribution of
contaminant concentration in rooms with floor-supply displace-
ment ventilation. Proceedings, ROOMVENT 2002, Copenhagen,
Denmark, 8-11 September 2002.
Ylvisaker, P. 1990. Underfloor air delivery: An ergonomic frontier?
Buildings: The Facilities Construction and Management Maga-
zine, November.
Yokoyama, K., and T. Inoue. 1991. Thermal environment with under-
floor air-conditioning system. IAQ 91, Healthy Buildings.
Evaluation of a low-pressure underfloor system with fan-pow-
ered units based on physical testing in a test chamber. Measure-
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
235
ments include contaminant concentration during smoking and
subjective experiments on occupants.
Yokoyama, K., and T. Inoue. 1993. The application of the underfloor air-
conditioning system. Proceedings, Indoor Air 93, Helsinki, Fin-
land.
An evaluation of the limitations on and requirements of under-
floor applications. Considerations include maximum internal heat
loads (uniform and nonuniform), raised floor heights, plenum cable
capacities, and partition locations.
Yokoyama, K., and T. Inoue. 1994. The evaluation of the newly devel-
oped underfloor air-conditioning system. Healthy Buildings 94,
Budapest, Hungary.
Test-chamber experiments on three HVAC systems (low-pres-
sure underfloor, pressurized underfloor, and ceiling supply) com-
pare the vertical distributions of temperature, ventilation efficiency,
and contaminant removal effectiveness of each. The results of
Yokoyamas previous papers are outlined.
York, D. 1998. Commissioning green buildings: Two Wisconsin case
studies. Proceedings, 6
th
National Conference on Building Com-
missioning. Portland Energy Conservation, Inc.
York, T.R. 1993. Can you afford an intelligent building? FM Journal,
IFMA, September/October.
Although cost values will have changed, this article is useful as
a comparative exercise aiming to prove intelligent buildings can be
built at a cost comparable to traditional buildings. A breakdown is
presented of initial building costs, life-cycle cost savings, and five-
year life-cycle costs for four different building types (two tradi-
tional, two intelligent, including one with an underfloor air distri-
bution system).
York International. 1999. York modular integrated terminals: Convec-
tion enhanced ventilation Technical manual. York International,
York, Pa.
This manual provides technical descriptions of the differences
between the new technology of floor-based and ceiling-based air
distribution systems in addition to practical guidelines and recom-
mendations for using the MITs and other York products. The user-
friendly graphics and wide range of issues addressedfrom psy-
chrometrics to fire codesmake this manufacturer's manual useful
as a general reference text for underfloor air systems.
York International. 2002. Product information. York International, York,
Pa., http://www.york.com.
REFERENCES AND ANNOTATED BIBLIOGRAPHY
236
Yuan, X., Q. Chen, and L. Glicksman. 1998. A critical review of dis-
placement ventilation. ASHRAE Transactions, Vol. 104, Pt. 1.
Yuan, X., Q. Chen, and L. Glicksman. 1999. Performance evaluation
and design guidelines for displacement ventilation. ASHRAE
Transactions, Vol. 105, Pt. 1.
Zeng, Q., J. Kaczmarczyk, A.K. Melikov, and P.O. Fanger. 2002. Per-
ceived air quality and thermal sensation with a personalized venti-
lation system. Proceedings, ROOMVENT 2002, Copenhagen,
Denmark, 8-11 September 2002.
Zhu, J., H. Ito, and N. Nakahara. 1995. Thermal comfort and energy sav-
ing of a personal air-conditioning system using fluctuating air
movement. Proceedings, 2nd International Conference on Indoor
Air Quality, Ventilation, and Energy Conservation in Buildings.
Centre for Building Studies, Concordia University, Montreal, May
9.
Zhu, J., K. Tanaka, K. Sagara, and N. Nakahara. 1996. Performance
evaluation of a task and ambient air-conditioned system using fluc-
tuating air movement in an actual office space. Proceedings,
Indoor Air 1996, Nagoya, Japan, July 21-26.
237
Index
A
access flooring 9
See also raised floor system
acoustic performance 97, 140
air change effectiveness 49, 147
air highway 66, 171
air leakage 6062, 113, 114, 168, 169, 174
air velocity 43, 4648, 143
air-handling unit 168, 177
VAV change-over 127
ANSI/ASHRAE Standard 113-1990 146
ANSI/ASHRAE Standard 55-1992 43, 44, 49, 143
ANSI/ASHRAE Standard 62-2001 145
ANSI/ASHRAE/IESNA Standard 90.1-2001 146
ASHRAE Standard 129-1997 147
C
cable management 9, 13, 55, 85, 139, 149, 157
carpet tile 8587, 114
ceiling plenum 14, 154, 155
chiller 12, 178
churn 13, 141
cleaning 96, 111, 138
clear zone 31, 48
INDEX
238
climate 19, 105
code
fire 150
NFPA 90A 148
Uniform Building 150
commissioning 116, 130
condensation 18, 173
conference rooms 130
constant-air-volume (CAV) 70, 90
construction 110, 154
concrete flat slab 14, 154
retrofit 16, 115, 157
steel beam 14, 154
control
humidity 93, 105, 177
static pressure 90
variable-speed fan coil unit 126
control strategies 89, 94, 165, 178
convector 123
costs
first 133, 137
life-cycle 13, 133, 141
D
dehumidification 18
design phase 109, 138, 153
design tools 187
diffusers
active 3, 70, 77, 81, 130, 174
combustibility of 149
fan-powered 11, 45, 48, 7881, 174
floor 1, 5, 6, 48, 69, 71, 73, 81, 174, 175
furniture-based 3, 5, 6, 4547, 49, 77, 78, 81, 175
jet 4548, 78, 79
low side-wall 28, 30
passive 11, 70, 71, 174
swirl 35, 37, 38, 47, 71, 73, 81, 175
TAC 12, 45, 49, 69, 77, 79, 145, 174
variable-area 35, 73, 122, 175
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
239
displacement ventilation (DV) 12, 24, 25, 33, 145
draft 17, 44
E
economizer 12, 102, 105, 164
integrated 105
efficiency, cooling-system 106
electronically commutated motor (ECM) 100, 125
energy use 12, 99, 116, 146, 147, 169
air distribution 99
central fan 100, 102
fan 13, 100
perimeter fan 100
equivalent homogenous temperature 4548
F
fan coil unit
constant-speed 120
heating-only 122
variable-speed 125
fan pressure 99
fan terminal 81, 84, 130
fire safety 138
floor panel 53
heat transfer through 65, 174
floor-to-floor height 14, 17, 115, 140, 154
G
grille, linear floor 75, 121, 124, 127129, 175
H
health 142
heat gain
convective 160
radiant 160
heat load 30, 34, 36
See also heat gain
heat pump 122
INDEX
240
heater, baseboard 123
heating systems 164
HVAC design 5, 7
HVAC equipment, primary 177
I
individual control 3, 6, 31, 44, 48, 51, 95
indoor air quality 12, 30, 41, 50, 145
induction shaft 94, 172
L
LEED rating system 150
load
air-side 160
space cooling 158
space heating 158, 164
load calculation 158, 162164
M
mixing-type air distribution 5, 12, 23, 24, 33, 158
morning warm-up 107, 164, 179
N
noise 120, 122, 125, 132
O
occupancy sensor 78, 130
occupant control 78, 79, 143
occupant cooling 6, 44, 45, 144
evaporative 47
sensible 4548
occupied zone 160
office building 9, 19, 30, 97
operation
cooling 116
heating 82, 107
part-load 90
operation and maintenance 96, 167
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
241
operation and maintenance costs 141
outlets 6, 69, 148
fan-driven 11, 123
supply temperature 6
overhead air distribution 3, 12, 23, 24, 33, 41, 153, 158
P
personal control 44, 46, 48, 145
pollutants 29
productivity 14, 50, 142, 187
property value 142
R
raised concrete core 137
raised floor system 5, 85, 97, 153, 157, 167
costs 137
installation of 111
reconfiguring building services 97, 141
reheat 120, 122, 125, 126, 132
return air 6, 176
return air bypass 177
room air distribution 23, 31, 146
room air distribution model 3134
room airflow rate 28, 34, 3638, 159
S
space planning 115
standards
thermal comfort 43, 44, 143
Title-24 147
stratification 6, 15, 33, 36, 37, 49, 107, 146, 159, 186
controlling 37, 91, 92, 116
stratification height 26, 2834, 36, 159
structural slab 5, 6, 178
nighttime precooling of 66, 107, 178
supply air 31
supply air volume 13, 28, 92, 94, 162, 173
INDEX
242
systems
perimeter 119
special 119, 130
T
task/ambient conditioning (TAC) 2, 8, 10, 31, 41, 94
tax savings 142
temperature
return air 102, 163, 173
supply air 38, 39, 89, 93, 102, 172
temperature difference
head-foot 37
room-supply 4548
temperature gradient 30, 34, 92, 106
temperature near the floor 35
temperature profile 30, 33, 37
thermal bypass in perimeter zones 163
thermal comfort 6, 11, 41, 44, 48, 106, 143, 186
thermal plume 27, 34, 163
thermal storage 107, 178
thermostat height 93
thermostat setpoint 93, 162
throw height 31, 34, 37
Title-24 147
U
underfloor air distribution (UFAD) 2, 810, 31, 153
benefits 1114
underfloor plenum 2, 5, 16, 53, 167, 186
dirt entering 18, 96
ducting within 59, 66, 139, 170
height of 57, 157
obstructions within 59
pressurized 5, 56, 57, 89, 168
sealing of 113, 138
thermal decay in 59, 63, 65, 66, 173
thermal performance of 63, 178
zero-pressure 6, 56, 94, 123, 169
UNDERFLOOR AIR DISTRIBUTION DESIGN GUIDE
243
underfloor plenum dividers (partitions) 127, 132, 139, 165, 170
underfloor plenum inlets 59, 64, 171
V
variable volume and temperature (VVT) 127
variable-air-volume (VAV) 7, 13, 70, 73, 91, 94, 122
VAV box 129
ventilation 49, 145, 164, 186
ventilation effectiveness 12, 24, 50, 145, 147, 164
ventilation efficiency 12
W
whole-building energy simulation 16, 186
whole-building performance 16, 187
window blinds 132
Z
zones
interior 90, 165
perimeter 81, 82, 119, 163, 165, 166
special 119, 166
zoning 165