POWER GRID CORPORATION OF INDIA LTD.


( A GOVERNMENT OF INDIA ENTERPRISER)
"SOUDAMINI", 3rd FLOOR, PLOT NO.-2
SECTOR-29, GURGAON-122001, HARYANA

PROJECT

DESIGN, ENGINEERING, SUPPLY, ERECTION(INCLUDING CIVIL WORK), TESTING AND


COMMISSIONING FOR CONSTRUCTION OF SUB-STATION PACKAGE-'PB-S3' UNDER TRANSMISSION
SYSTEM ASSOCIATED WITH PALLATNA GBPP & BONGAIGAON TPS IN NORTH EASTERN REGION

EX WORKS SUPPLY CONTRACT AGREEMENT: REF. NO. C-62010-S219A-3/G7/CA-I/3476 DATED 6.10.2010


SERVICE CONTRACT AGREEMENT: REF. NO. C-62010-S219A-3/G7/CA-II/3477 DATED 6.10.2010
PSC ENGINEERS PVT. LTD., KOLKATA
CONTRACTOR
TITLE

132KV BAY EXTENSION AT PURBO KANCHAN BARI SUB-STATION - SAG TENSION CALCULATION
AND STRINGING CHART

DRG. NO.

K2010PS003A-245

REVISION

R1

PREPARED BY

ANUPAM

CHECKED BY

ANUPAM

APPROVED BY

TPK

DATE

23/3/2011

REVISED AS PER PGCIL COMMENTS

ANUPAM

23/3/2011

FIRST SUBMISSION FOR APPROVAL

ANUPAM

8/2/2011

REVISION

DESCRIPTION

SIGN

DATE

Sag Tension Calculation and Stringing Chart

Page 2 of 13

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

SAG TENSION CALCULATION AND STRINIGING CHART FOR 132KV BAY EXTENSION AT PURBO KANCHAN BARI SUBSTATION (TRIPURA)
SUMMARY
1.0

INTRODUCTION :
For 132kV Bay Extension at Purbo Kanchan Bari Sub-Station (Tripura)
1) Single Zebra ACSR Conductor is proposed for Transfer Bus - A & B.
2) Single Zebra ACSR Conductor is proposed for high level bus (jack bus).
3) The initial tensile force is considered as per technical specification i.e. 1000 kg per conductor for Single Zebra
ACSR.
The present report is brought out to determine tension and sag under different conditions for conductor
and also to check vertical clearances.

2.0

STANDARDS & REFERENCES :


Following standards/references are used for present report :-

i)

IS : 802 ( Part 1 / Sec 1 ) : 1995

ii)

IS : 875 ( Part 3 ) - 1987

iii)

Technical specification of PGCIL for substation package-'PB-S3' under transmission system associated with pallatna
GBPP & Bongaigaon TPS in nort eastern region.

iv)

Tamilnadu Electricity Board Engineer's association"Power Engineer's Hand-Book" (Part-I)

v)

Overhead Line Practice By John McCombe (Book)

vi)

Drawings

3.0

Layout Plan- K2010PS003A-203 Rev. 2


Layout Sections- K2010PS003A-204 Rev.2

METHODOLOGY :
To compute sag and tension, calculations are carried out for following conditions as stated in clause 10 of IS 802
( Part 1 / Sec 1 ) : 1985.
a) 0 oC -- Nil wind and 36 % wind Force.
b) 32 oC -- Nil Wind and Full Wind Force.
b) 75 oC -- Nil Wind condition.
Sag at these temperatures for Nil wind condition is checked for adequate Vertical clearance.Tension for 00C & 36% wind,
320C & full wind has been computed to check it against design value of 1T per conductor for Single Zebra ACSR
conductor.

4.0

CONCLUSION :
The results are tabulated in the table kept below as Annexure-A.
Sag and tension values for all temperatures from 00C to 850C and nil wind condition are tabulated in the table kept
below as Annexure-1, 2 & 3 respectively.
The Sample calculation for different conditions are enclosed herewith.
It is seen that the vertical clearances adopted are adequate.

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 2 of 13

ANNEXURE-A
SAG-TENSION TABLE FOR CONDUCTOR WITH DIFFERENT SPANS
FOR 132KV BAY EXTENSION AT PURBO KANCHAN BARI SUB-STATION (TRIPURA)
FOLLOWING SAG VALUES HAVE BEEN CALCULATED AS PER IS-802 (PART-2), 1993

SPAN LENGTH

TEMP. OF
CONDUCTOR

WIND LOAD

TENSION (Kgf)

SAG (m)

NIL

459

0.65

36%

500

----

NIL

156

1.69

FULL

293

----

NIL

96

2.33

0oC
132 KV
21 mtrs.
Single Zebra
Transfer Bus-A

32 C

75 C
Minimum Phase-Phase / Phase-Ground clearance require
under sag condition.

=
=
=

Maximum Sag + Phase to Phase clearance


0.93 + 1.3
3.63

Clearance actually provided

=
=
=
=

Tower height - Equipment Height


8 - 4.6
7.3
3.67

Margin available
Hence it is Safe.
SPAN LENGTH

TEMP. OF
CONDUCTOR

WIND LOAD

TENSION (Kgf)

SAG (m)

NIL

#REF!

#REF!

36%

#REF!

----

NIL

#REF!

#REF!

FULL

#REF!

----

NIL

#REF!

#REF!

0oC
132 KV
52.55 mtrs.
Single Zebra
Jack Bus

32 C

75oC
Minimum Phase-Phase / Phase-Ground clearance require
under sag condition.

=
=
=

Maximum Sag + Phase to Phase clearance


1.64 + 1.3
#REF!

Clearance actually provided

=
=
=

Higher Tower Height - Lower Tower Height


12.0 - 8.0
#REF!

Margin available

#REF!

WIND LOAD

TENSION (Kgf)

SAG (m)

NIL

#REF!

#REF!

36%

#REF!

----

NIL

#REF!

#REF!

FULL

#REF!

----

NIL

#REF!

#REF!

Hence it is Safe.
SPAN LENGTH

TEMP. OF
CONDUCTOR
0oC

132 KV
52.50 mtrs.
Single Zebra
Transfer Bus-B

32oC

75 C
Minimum Phase-Phase / Phase-Ground clearance require
under sag condition.

=
=
=

Maximum Sag + Phase to Phase clearance


1.64 + 1.3
#REF!

Clearance actually provided

=
=
=
=

Tower height - Equipment Height


8 - 4.6
#REF!
#REF!

Margin available
Hence it is Safe.

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 3 of 13

ANNEXURE-B
CALCULATION OF WIND EFFECTS (Ref. IS 802 Part 1/Sec 1 : 1995)

1.0 Basic wind speed

Vb

2.0 Design wind speed

Vd

VR x K1 x K2

K1

Risk co-efficient

K2

Terrain roughness coefficient which is

39

m/sec

Where

Factor to convert 3 second peak


gust speed into
average speed of wind during 10
minutes period

K0

1.375

Meteorological reference wind


speed

VR

Vb / K0

m/sec

28.36

3.0 Design wind pressure

5.0 Wind load on each conductor

Vd

28.36

Pd

0.6 Vd2

482.70

N/m2

49.25

Kgf/m2

Fwc

Pd x cdc x L x D x Gc

Wind span i.e. the sum of half the spans on either side in mtrs

Cdc

Drag coefficient

Dia. of conductor

0.03177

Gc

Gust Response factor

(Cl. 9.2 of Ref IS)

Where,

--------

Refer Table: 7 of IS 802


Part 1 / Sec 1, 1995

Therefore

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

Fwc

2.12

For 8 m height

32.51

N/m

For12 m height

3.31

Kg/m

For 12 m height

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 4 of 13

SAG TENSION CALCULATIONS

( 132KV Single Zebra ACSR Conductor )

21M SPAN (SINGLE ZEBRA ACSR)----------132kV Transfer Bus-A

22
23

General Perticulars :
Span Length
Girder width
Span length excluding girder width
Spacer Span
Length of Disc Insulator String (One side) (li)
Total Length of Hardware (With Turn Bucckle + Without Turn Bucckle)
Diameter of disc insulator string (di)
Length of conductor
Span length excluding girder width ,Hardware and string ( L)
Initial Tension per conductor
Dia of Conductor
Weight of Conductor
No. of Spacers
Unit Weight of spacer
Unit weight of single tension disc insulator string
Unit weight of single tension hardware with turnbuckle.
Unit weight of single tension hardware without turnbuckle
Unit weight of Disc Insulator with hardware (Wi)
Length of Turnbuckle
(lt)
Width of Turnbuckle
(Bt)
Weight of turnbuckle
(Wt)
Weight of conductor with spacers
100% wind load on conductor per phase (n FWC)---- [Refer Annexure-B]

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

17.00
1.50
15.5
0.00
3.00
0.05
0.05
9.45
9.45
500.00
0.0318
2.0040
0.0000
0.0000
165.0000
1.0000
1.0000
166
0.0500
0.0220
1.0000
2.0040
3.3100

24
25
26
27

Area of cross section of conductor


Modulus of Elasticity of conductor
Coefficient of Thermal expansion
Maximum temperature considered

AREA
ES
ET
Tmax

=
=
=
=

5.97
686000.0000
0.0000193
85

n
h

=
=

1
11.9

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

28 Number of subconductors
29 Bus Height

m
m
m
m
m
m
m
m
m
Kg
m
Kg/m
Kg
Kg
Kg
Kg
Kg
m
m
Kg
Kg/m
Kg/m
Sq.cm
Kg/Sq.cm
/oC
C

1.0 The equation for finding stress (f2) in different air conditions and for different temperature ranges is as under :=

q22 2 L2 x E / 24

Refer T.N.E.B. Handbook

. Eq-(I)

SAG

q1**L2
n 8 f2

f1

Initial stress in conductor at temperature t1 (kg/cm2)

f2

Final stress in conductor at temperature t2 (kg/cm2)

q1

Still wind loading factor

q2

36% Maximum wind loading factor

q3

Maximum wind loading factor

Weight Factor in kg/m/cm2

Span (m)

Modulus of Elasticity in kg/cm2

Co-efficient of linear expansion

Overall Diameter of conductor (m)

Cross sectional area of conductor (cm2)

P2

Wind load on conductor 36% (kgf/m)

P3

Wind load on conductor (max.) (kgf/m)

f22 x { f2 - [f1 - (q12 2 L2 E / 24 f12) - E t] }


f22 x

{ f2 - [f1 -

(q12

L E / 24

f12)

- E t]

}-(q22

L E / 24)

The Sag can be calculated from the following equation Eq-(II)

Where,

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 5 of 13

t1

Initial temperature (oC)

t2

Final temperature (oC)

T1

Initial tension in conductor at temp t1 = f1 x A (kgf)

T2

Final tension in conductor at temp t2 = f2 x A (kgf)

S1

Sag at initial condition T1 (m)

S2

Sag at final condition T2 (m)

W
A

2.00

Kg/m

5.97

cm2

0.34

kg/m/cm2

At 36% wind

P2

1.19

Kg/m

At Full wind

P3

3.3100

Kg/m

At Still wind

q1

At 36% wind

q2

2.0 Parameters
2.1 Weight factor
Weight of conductor with accessories/Phase
Cross sectional area
Therefore

Wc

2.2 Wind factors


Refer S.No. 23 above

2.3 Loading factors

=
At Full wind

q3

1.16

1.93

2.4 Temperature factors


E t32

423.6736

E t85

1125.383

E t0

WcL2
n8T2

(Starting condition is assumed


at 32oC and 36% of full wind)

Therefore from above formulas sag can be calculated as, Sag

. Eq-(III)

Where "n" represents nos. of subconductor


3.0 Calculation of Sag and Tension

Here Sag is calculated at 00C, 320C and 850C for Nil wind condition.
Reference condition is assumed as 00C and 36% of Full Wind,
So, Tension at reference condition is,
T1

500

kgf

And Stress in conductor at reference condition is ,

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 6 of 13

f1

nT1
A

f1

83.7521

kg/cm2

f1

83.75

kg/cm2

At 32oC

3.1

3.1.1 For Nil wind condition :i.


SAG DUE TO CONDUCTOR
Reference stress at 00C and 36% of full wind condition is,

L2 * 2 * E * q
24 * f 1 2

Now,

Tension Factor at Nill wind

L 2 * 2 * E * q 12
24

2
2

= 55.5022

= 287622.7691

E t32

423.6736

f23-f22[ f1-((L2 2 x E q22) / (24 f12))-(E t32) ]

(L2 2 E q12) / (24)

f23-f22 [206.40 - 50.3251 - 434.8411] - 932927.6838

f2

26.12

Kg/cm2

Tension T2

155.94

Kg

Sag at 320C and Nill Wind (Sc)

WcL2

Stress (f2) is calculated as under,


. Eq-(I)

n8T2

ii

0.14

SAG DUE TO INSULATOR


The parameters required are expressed as follows,
U1

(li2 + (di/2)2)

3.00

U2

((li/2)2 + (di/2)2)

1.50

Tan-1 [(di/2)/li]

0.01

radians

Tan-1 [di/li]

0.02

radians

TP1

(W c*L/2) * U1 * Cos + Wi * U2 * Cos - n * T2 * U1 * Sin

273.51

TP2

n * T2 * U1 * Cos * + W c * (L/2) * U1 * Sin + W i * U2 * Sin

472.21

0.525

radians

1.53

-1

Tan (TP1 / TP2)

Sag due to insulator = Si = U1 * Sin( + )


iii

SAG DUE TO TURNBUCKLE


The parameters required are expressed as follows,
V1

(It2 + (Bt/2)2)

0.05

V2

((It/2)2 + (Bt/2)2)

0.03

Tan-1 [(Bt/2)/It]

0.22

radians

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 7 of 13

Tan-1 [Bt/It]

0.41

radians

TP3

(W c*(L/2)+Wi) *V1*Cos1+Wt* V2*Cos1-n*T2*V1*Sin1

7.083

TP4

n*T2*V1*Cos1*+(W c*(L/2)+Wi)*V1*Sin1+W t*V2*Sin1

7.92

Tan-1 (TP3 / TP4)

0.73

radians

0.02

1.69

Sag due to Turnbuckle = St = V1 * Sin(1 + 1)/2


Total maximum sag of single moose conductor Sg = Sc+Si+St

3.1.2 For full wind condition :Reference stress at 00C and 36% of full wind condition is,
f1

L 2 * 2 * E * q 22
24 * f 1 2

Now,

Tension Factor at Full wind

L 2 * 2 * E * q 32
24

kg/cm2

= 55.5022

= 1072286.9289

E t32

Stress (f2) is calculated as under,


f23-f22[ f1-((L2 2 x E q22) / (24 f12))-(E t32) ]

(L2 2 E q32) / (24)

[206.40 - 50.3251 - 434.8411] - 10276580.2456

f2

49.11

Kg/cm2

Tension T2

293.21

Kg

f1

f23-f22

3.2

83.75

423.6736

. Eq-(I)

At 85 C

3.2.1 For Nil wind condition :i. SAG DUE TO CONDUCTOR


Reference stress at 00C and 36% of full wind condition is,

Now,

83.75

L 2 * 2 * E * q 22
24 * f 1 2

L 2 * 2 * E * q 12
24

E t85

1125.3830

f23-f22[ f1-((L2 2 x E q22) / (24 f12))-(E t32) ]

(L2 2 E q12) / (24)

f23-f22 [206.40 - 50.3251 - 1019.1587] - 932927.6838

f2

16.07

Tension Factor at Nill wind

kg/cm2

= 55.5022

= 287622.7691

Stress (f2) is calculated as under,

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

. Eq-(I)

Kg/cm2

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

ii

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 8 of 13

Tension T2

95.96

Sag at 850C and Nill Wind (Sc)

WcL2
n8T2

0.23

SAG DUE TO INSULATOR


The parameters required are expressed as follows,
U1

(li2 + (di/2)2)

3.00

U2

((li/2)2 + (di/2)2)

1.50

Tan-1 [(di/2)/li]

0.01

radians

Tan-1 [di/li]

0.02

radians

TP1

(W c*L/2) * U1 * Cos + Wi * U2 * Cos - n * T2 * U1 * Sin

275.01

TP2

n * T2 * U1 * Cos * + W c * (L/2) * U1 * Sin + W i * U2 * Sin

292.27

0.75

radians

2.07

-1

Tan (TP1 / TP2)

Sag due to insulator = Si = U1 * Sin( + )


iii

SAG DUE TO TURNBUCKLE


The parameters required are expressed as follows,
V1

(It2 + (Bt/2)2)

0.05

V2

((It/2)2 + (Bt/2)2)

0.03

Tan-1 [(Bt/2)/It]

0.22

radians

Tan-1 [Bt/It]

0.41

radians

TP3

(W c*(L/2)+Wi) *V1*Cos1+Wt* V2*Cos1-n*T2*V1*Sin1

7.743

TP4

n*T2*V1*Cos1*+(W c*(L/2)+Wi)*V1*Sin1+W t*V2*Sin1

6.74

0.85

radians

0.02

2.33

-1

Tan (TP3 / TP4)


Sag due to Turnbuckle = St = V1 * Sin(1 + 1)/2

Total maximum sag of single moose conductor Sg = Sc+Si+St

3.3

Kg

At 0oC

3.3.1 For Nil wind condition :i.

SAG DUE TO CONDUCTOR


Reference stress at 00C and 36% of full wind condition is,
f1

83.75

L 2 * 2 * E * q 22

Now,

kg/cm2

= 55.5022

24 * f 1 2

Tension Factor at Nill wind

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

L 2 * 2 * E * q 12
24

= 287622.7691

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 9 of 13

E t0

0.0000

f23-f22[ f1-((L2 2 x E q32) / (24 f12))-(E t32) ]

(L2 2 E q12) / (24)

[206.40 - 50.3251 - (0)] - 932927.6838

f2

76.89

Kg/cm2

Tension T2

459.06

Kg

Sag at 00C and Nill Wind (Sc)

=
=

WcL2
n8T2
0.05

Stress (f2) is calculated as under,

f23-f22

ii

SAG DUE TO INSULATOR


The parameters required are expressed as follows,
U1

(li2 + (di/2)2)

3.00

U2

((li/2)2 + (di/2)2)

1.50

Tan-1 [(di/2)/li]

0.01

radians

Tan-1 [di/li]

0.02

radians

TP1

(W c*L/2) * U1 * Cos + Wi * U2 * Cos - n * T2 * U1 * Sin

265.93

TP2

n * T2 * U1 * Cos * + W c * (L/2) * U1 * Sin + W i * U2 * Sin

1381.57

0.19

radians

0.59

-1

Tan (TP1 / TP2)

Sag due to insulator = Si = U1 * Sin( + )


iii

. Eq-(I)

SAG DUE TO TURNBUCKLE


The parameters required are expressed as follows,
V1

(It2 + (Bt/2)2)

0.05

V2

((It/2)2 + (Bt/2)2)

0.03

-1

0.22

radians

-1

Tan [Bt/It]

0.41

radians

Tan [(Bt/2)/It]

TP3

(W c*(L/2)+Wi) *V1*Cos1+Wt* V2*Cos1-n*T2*V1*Sin1

3.749

TP4

n*T2*V1*Cos1*+(W c*(L/2)+Wi)*V1*Sin1+W t*V2*Sin1

24.89

Tan-1 (TP3 / TP4)

0.15

radians

0.01

0.65

Sag due to Turnbuckle = St = V1 * Sin(1 + 1)/2


Total maximum sag of single moose conductor Sg = Sc+Si+St

3.1.2 For 36% wind condition :Reference stress at 00C and 36% of full wind condition is,
f1

Now,

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

kg/cm2

83.75
L2 * 2 * E * q
24 * f 1 2

2
2

= 55.5022

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 10 of 13

L 2 * 2 * E * q 22
24

E t0

Stress (f2) is calculated as under,


f23-f22[ f1-((L2 2 x E q22) / (24 f12))-(E t32) ]

(L2 2 E q22) / (24)

f23-f22 [206.40 - 50.3251 - (0)] - 2143865.0558

f2

83.75

Kg/cm2

Tension T2

500.00

Kg

Tension Factor at 36% wind

= 389315.2442

. Eq-(I)

4.0 The results are tabulated below:SPAN


LENGTH

TEMP. OF
CONDUC.

WIND
LOAD

TENSION= STRESS (f2) X AREA


Kgf

SAG
IN MTRS.

NIL

459

0.65

36%

500

-----

NIL

156

1.69

FULL

293

-----

NIL

96

2.33

0oC
220 KV
17 mtrs.
Single
Moose

32oC

85oC

5.0 Verification of Clearances :-

Vertical Clearance:
Minimum Phase-Phase / Phase-Ground Clearance require under Sag
condition

=
=
=

Minimum Phase to Phase Clearance + Maximum Sag


1.3 + 2.04
3.63
mtrs.

Clearance actually provided

=
=
=
=

Tower Height - Equipment Height


11.9 - 4.6
7.30
mtrs.
3.67
mtrs.

Margin available
Hence its Safe.

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 11 of 13

Annexure-1
SAG AND TENSION VALUES FOR ALL TEMPERATURES FROM 00C TO 850C AND NIL WIND CONDITION
21 M SPAN (SINGLE ZEBRA ACSR)---------------------132kV TRANSFER BUS-A

Sr.
No.

Temp.

Final Stress

Tension at nil wind condition

Sag due to
conductor

Sag due to
insulator

Sag due to
turnbuckle

Total max. sag of


quad moose
conductor

Deg. C

Equation

f2

T2

Sc

Si

St

Sg

-559984.31

183.71

890.10

0.06

0.08

0.02

0.17

-499344.34

173.48

840.52

0.07

0.09

0.03

0.18

-444652.24

163.71

793.16

0.07

0.09

0.03

0.19

-395671.70

154.43

748.20

0.08

0.10

0.03

0.20

-352109.06

145.68

705.81

0.08

0.10

0.03

0.22

-313616.32

137.48

666.11

0.09

0.11

0.03

0.23

-279800.11

129.86

629.18

0.09

0.12

0.03

0.24

-250234.44

122.81

595.01

0.10

0.12

0.04

0.26

-224478.92

116.32

563.56

0.10

0.13

0.04

0.27

10

-202095.11

110.37

534.72

0.11

0.14

0.04

0.28

11

10

-182662.01

104.93

508.36

0.11

0.14

0.04

0.30

12

11

-165787.90

99.96

484.31

0.12

0.15

0.04

0.31

13

12

-151117.77

95.44

462.39

0.12

0.16

0.05

0.33

14

13

-138336.42

91.31

442.40

0.13

0.16

0.05

0.34

15

14

-127169.18

87.55

424.17

0.14

0.17

0.05

0.36

16

15

-117379.49

84.11

407.52

0.14

0.18

0.05

0.37

17

16

-108765.52

80.97

392.28

0.15

0.18

0.05

0.39

18

17

-101156.23

78.08

378.31

0.15

0.19

0.06

0.40

19

18

-94407.25

75.43

365.47

0.16

0.20

0.06

0.41

20

19

-88396.80

72.99

353.65

0.16

0.20

0.06

0.43

21

20

-83022.49

70.74

342.73

0.17

0.21

0.06

0.44

22

21

-78197.96

68.65

332.62

0.17

0.22

0.06

0.45

23

22

-73850.34

66.72

323.24

0.18

0.22

0.07

0.47

24

23

-69917.99

64.92

314.52

0.18

0.23

0.07

0.48

25

24

-66348.57

63.24

306.38

0.19

0.23

0.07

0.49

26

25

-63097.58

61.67

298.78

0.19

0.24

0.07

0.50

27

26

-60127.03

60.20

291.67

0.20

0.25

0.07

0.52

28

27

-57404.36

58.82

284.99

0.20

0.25

0.07

0.53

29

28

-54901.57

57.52

278.70

0.21

0.26

0.08

0.54

30

29

-52594.52

56.30

272.78

0.21

0.26

0.08

0.55

31

30

-50462.25

55.15

267.20

0.22

0.27

0.08

0.56

32

31

-48486.61

54.06

261.92

0.22

0.27

0.08

0.57

33

32

-46651.74

53.03

256.91

0.22

0.28

0.08

0.58

34

33

-44943.75

52.05

252.16

0.23

0.28

0.08

0.59

35

34

-43350.48

51.12

247.65

0.23

0.29

0.08

0.60

36

35

-41861.20

50.23

243.36

0.24

0.29

0.09

0.61

37

36

-40466.42

49.39

239.27

0.24

0.30

0.09

0.62

38

37

-39157.74

48.58

235.37

0.24

0.30

0.09

0.63

39

38

-37927.71

47.81

231.65

0.25

0.31

0.09

0.64

40

39

-36769.68

47.08

228.08

0.25

0.31

0.09

0.65

41

40

-35677.69

46.37

224.67

0.26

0.32

0.09

0.66

42

41

-34646.43

45.70

221.40

0.26

0.32

0.09

0.67

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Sag Tension Calculation and Stringing Chart

PGCIL 132kV Bay Extension at


Purbo Kanchan Bari Sub-Station(Tripura)

Page 12 of 13

Sr.
No.

Temp.

Final Stress

Tension at nil wind condition

Sag due to
conductor

Sag due to
insulator

Sag due to
turnbuckle

Total max. sag of


quad moose
conductor

Deg. C

Equation

f2

T2

Sc

Si

St

Sg

43

42

-33671.11

45.05

218.26

0.26

0.32

0.09

0.68

44

43

-32747.43

44.43

215.25

0.27

0.33

0.09

0.69

45

44

-31871.49

43.83

212.35

0.27

0.33

0.10

0.70

46

45

-31039.79

43.25

209.56

0.27

0.34

0.10

0.71

47

46

-30249.14

42.70

206.87

0.28

0.34

0.10

0.72

48

47

-29496.64

42.16

204.28

0.28

0.35

0.10

0.73

49

48

-28779.67

41.65

201.79

0.29

0.35

0.10

0.73

50

49

-28095.81

41.15

199.37

0.29

0.35

0.10

0.74

51

50

-27442.88

40.67

197.04

0.29

0.36

0.10

0.75

52

51

-26818.87

40.20

194.79

0.30

0.36

0.10

0.76

53

52

-26221.94

39.75

192.61

0.30

0.36

0.10

0.77

54

53

-25650.40

39.32

190.50

0.30

0.37

0.10

0.78

55

54

-25102.68

38.90

188.46

0.31

0.37

0.11

0.78

56

55

-24577.36

38.49

186.47

0.31

0.38

0.11

0.79

57

56

-24073.12

38.09

184.55

0.31

0.38

0.11

0.80

58

57

-23588.73

37.71

182.68

0.32

0.38

0.11

0.81

59

58

-23123.07

37.33

180.87

0.32

0.39

0.11

0.81

60

59

-22675.08

36.97

179.11

0.32

0.39

0.11

0.82

61

60

-22243.80

36.62

177.40

0.32

0.39

0.11

0.83

62

61

-21828.31

36.27

175.74

0.33

0.40

0.11

0.84

63

62

-21427.79

35.94

174.12

0.33

0.40

0.11

0.84

64

63

-21041.45

35.61

172.54

0.33

0.40

0.11

0.85

65

64

-20668.57

35.29

171.00

0.34

0.41

0.11

0.86

66

65

-20308.45

34.99

169.51

0.34

0.41

0.12

0.86

67

66

-19960.46

34.68

168.05

0.34

0.41

0.12

0.87

68

67

-19624.01

34.39

166.63

0.35

0.42

0.12

0.88

69

68

-19298.54

34.11

165.24

0.35

0.42

0.12

0.89

70

69

-18983.54

33.83

163.88

0.35

0.42

0.12

0.89

71

70

-18678.50

33.55

162.56

0.35

0.43

0.12

0.90

72

71

-18382.97

33.29

161.27

0.36

0.43

0.12

0.91

73

72

-18096.52

33.03

160.01

0.36

0.43

0.12

0.91

74

73

-17818.73

32.77

158.78

0.36

0.43

0.12

0.92

75

74

-17549.24

32.52

157.57

0.37

0.44

0.12

0.93

76

75

-17287.66

32.28

156.39

0.37

0.44

0.12

0.93

77

76

-17033.67

32.04

155.24

0.37

0.44

0.12

0.94

78

77

-16786.95

31.81

154.11

0.37

0.45

0.12

0.94

79

78

-16547.18

31.58

153.01

0.38

0.45

0.12

0.95

80

79

-16314.08

31.36

151.93

0.38

0.45

0.13

0.96

81

80

-16087.38

31.14

150.87

0.38

0.46

0.13

0.96

82

81

-15866.83

30.92

149.83

0.38

0.46

0.13

0.97

83

82

-15652.17

30.71

148.81

0.39

0.46

0.13

0.97

84

83

-15443.18

30.51

147.81

0.39

0.46

0.13

0.98

85

84

-15239.63

30.31

146.84

0.39

0.47

0.13

0.99

86

85

-15041.33

30.11

145.88

0.39

0.47

0.13

0.99

PSC Engineers Pvt. Ltd.


Ex WSC Agreement Ref. C-62010-S219A-3/G7/CA-I/3476 Dt: 6.10.2010
SC Agreement Ref. C-62010-S219A-3/G7/CA-II/3477 Dt: 6.10.2010

PSC Drg. No. K2010PS003A-245 R1

Você também pode gostar