The document provides comments from Pöyry Energy on the outline drawing for a low pressure feedwater heater (LP-3) for the Two(2) x 500MW Mong Duong 1 Thermal Power Plant project. Pöyry provides several general comments regarding references to other drawings and documents, operating conditions, and design details. They also provide specific comments on issues with nozzle sizes and typographical errors in the outline drawing. The contractor addresses each comment and details the changes or references made in response. Pöyry closes most comments on further revisions, requesting any changes be cloud marked for easy identification.
The document provides comments from Pöyry Energy on the outline drawing for a low pressure feedwater heater (LP-3) for the Two(2) x 500MW Mong Duong 1 Thermal Power Plant project. Pöyry provides several general comments regarding references to other drawings and documents, operating conditions, and design details. They also provide specific comments on issues with nozzle sizes and typographical errors in the outline drawing. The contractor addresses each comment and details the changes or references made in response. Pöyry closes most comments on further revisions, requesting any changes be cloud marked for easy identification.
The document provides comments from Pöyry Energy on the outline drawing for a low pressure feedwater heater (LP-3) for the Two(2) x 500MW Mong Duong 1 Thermal Power Plant project. Pöyry provides several general comments regarding references to other drawings and documents, operating conditions, and design details. They also provide specific comments on issues with nozzle sizes and typographical errors in the outline drawing. The contractor addresses each comment and details the changes or references made in response. Pöyry closes most comments on further revisions, requesting any changes be cloud marked for easy identification.
APPROVED WITH COMMENTS AC Approved Subject to Incorporation of comments RETURNED FOR CORRECTION RT Insufficient Information/ Detail Resubmit for Approval REJECTED RJ Complete redesign required RECEIVED FOR INFORMATION I Returned without comments RECEIVED FOR INFORMATION IC Returned with comments any obligations covered under contract Engineer: Discipline: Date: Note: Approval or comments does not relieve the Contractor of Pyry Energy TWO(2) X 500MW MONG DUONG 1 THERMAL POWER PLANT David Langhorne Senior Mec Engineer 5-Mar-13 Pyry Comment Two(2) x 500MW Mong Duong 1 Thermal Power Plant Project
Dwg. / Doc. Title Outline Drawing for LP-3 Low Pressure FWH Dwg. / Doc. No. MD1-0-V-114-01-00001 HDEC DT No. MD1-HDH-EVN-X-1036 Submitted Date 2012.11.02 Rev. B Pyry TR No. 9A000323-002559 Received Date 2012.11.28 New HDEC DT No. MD1-HDH-EVN-X-2233 Re-Submitted Date 2013.02.05 Rev. C Status Received for Information Returned with Comments
Page1 / 4 No. Pyrys Comments Contractors Reply / Action G General comments G1 <Pyrys Comments on Rev.A> HDEC is requested to check carefully all relative latest P&I drawings, piping arrangement drawing to make sure that nozzle number, nozzle size and nozzle orientation on the outline drawing are matched. <Contractors Reply / Action on Rev.A> Noted.
<Contractors Reply / Action on Rev.B> Closed.
G2 <Pyrys Comments on Rev.A> Please confirm the heaters shall be provided with the ASME U stamp.
<Pyrys Comments on Rev.B> Closed. <Contractors Reply / Action on Rev.A> Refer to Contract GTR 4.13 All pressure vessels and heat exchangers shall be manufactured by an approved ASME U-stamp holder. SEC is an ASME U-stamp holder. Heaters are manufactured by an ASME U-stamp holder, but are not provided with U-stamp.
G3 <Pyrys Comments on Rev.A> Condensate water levels (low alarm, normal level control, high alarm, emergency control) in the shell side shall be shown. . <Pyrys Comments on Rev.B> Closed. <Contractors Reply / Action on Rev.A> Reflected. G4 <Pyrys Comments on Rev.A> Shell side and tube side operating condition (inlet/outlet temperature and pressure of steam and water) at VWO condition to be included in the design data table.
<Pyrys Comments on Rev.B> Noted, please include a cross reference to this document on each Heater Outline Drawing.
<Pyrys Comments on Rev.C> Reference document should include the technical data sheet in additional to the mentioned drawings. It is noted that the list of reference drawings is on hold at present so please add the technical data sheet to the reference list. <Contractors Reply / Action on Rev.A> For VWO operating condition, please refer to the Technical Data Sheet. MD1-0-V-114-09-00002
<Contractors Reply / Action on Rev.B> Reflected. Page2 / 4
No. Pyrys Comments Contractors Reply / Action G5 <Pyrys Comments on Rev.A> Water velocity in the tube side shall be indicated in the design data table.
<Pyrys Comments on Rev.B> Noted, see G4 above.
<Pyrys Comments on Rev.C> Reference document should include the technical data sheet in additional to the mentioned drawings. <Contractors Reply / Action on Rev.A> For water velocity in the tube side, please refer to the Technical Data Sheet. MD1-0-V-114-09- 00002
<Contractors Reply / Action on Rev.B> Reflected. G6 <Pyrys Comments on Rev.A> Include the Heater KKS identifier in the document title.
<Pyrys Comments on Rev.B> Closed. <Contractors Reply / Action on Rev.A> Reflected. G7 <Pyrys Comments on Rev.A> Confirm how the tubes are expanded into the tube sheet. Indicate whether there is a seal weld.
<Pyrys Comments on Rev.B> The question is how are the tubes expanded? The fact that they are expanded was already noted on the Rev A document.
<Pyrys Comments on Rev.C> Closed. <Contractors Reply / Action on Rev.A> Refer to the design table on outline drawings. LP Heater : Expand only HP Heater : Expand +Seal weld
<Contractors Reply / Action on Rev.B> Please refer to the ATT#1 (Tube Expanding Procedure Sample) Drawing/documents to also be provided for all Heaters.
D1 <Pyrys Comments on Rev.A> Design Calculation Sheets for heat transfer calculations and to support the data provided in the tables on the outline drawing. The calculation document should also identify the number or percentage of surplus tubes.
<Pyrys Comments on Rev.B> Noted. The margin of spare tubes over the calculated tube requirements should be 3%.
Closed as a comment on these documents however the percentage of spare tubes shall be identified in the calculations.
<Contractors Reply / Action on Rev.A> SEC will submit Design Calculation Sheets for heat transfer calculations later. SEC has considered margin for heat transfer surface. And also, SEC has shop margins for tube plugging of four(4) to five(5) ea.
<Contractors Reply / Action on Rev.B> Closed. D2 <Pyrys Comments on Rev.A> Design Detail Drawings which indicate: - arrangement of instrument equipments and tube bundle. - Name plate, stamping plate location shall be indicated <Contractors Reply / Action on Rev.A> Noted. SEC will submit drawings the following; 1. Outline drawing 2. Embedded detail drawing 3. Name plate drawing Page3 / 4
No. Pyrys Comments Contractors Reply / Action - Heater shell diameter and thickness - Earth lugs - Access to the heater waterbox and tube sheet - Inspection manholes to allow visual inspection of the internal condition of the heat exchanger tubes. - Measures implemented to prevent erosion and corrosion on other details requested in Clause 6.4.3 of the ERQ.
<Pyrys Comments on Rev.B> Noted.
And also, you can refer to the outline drawing you want information such as heater shell diameter, thickness, Earth lug, Access to the channel barrel and tube sheet. In case of prevent erosion and corrosion, you can refer to the impingement plate from stainless steel for tube erosion and corrosion.
<Contractors Reply / Action on Rev.B> Closed. Detail comments on MD1-0-V-114-01-00001 1 <Pyrys Comments on Rev.A> There are two (2) steam inlet line having pipe size of DN650mm (refer to P&ID No. MD1-0-M- 110-21-00033 Rev. C). Therefore, there should be two (2) nozzles DN650 instead of one nozzle DN550 as shown in the nozzle data table. Please check and correct.
<Pyrys Comments on Rev.B> Closed. <Contractors Reply / Action on Rev.A> There are two(2) steam inlet nozzle (C1, C2) in the nozzle data table. And nozzle size was calculated as per HEI code and standard. Two(2) DN550 steam inlet were reflected to P&ID. 2 <Pyrys Comments on Rev.A> Complete the nozzle bevel detail table.
<Pyrys Comments on Rev.B> Closed. <Contractors Reply / Action on Rev.A> Noted. 3 <Pyrys Comments on Rev.A> Emergency drain outlet (F) and Drain outlet (E) having nozzle size of DN250mm while it is DN200 in P&ID No. MD1-0-M-110-21-00042. Please clarify.
<Pyrys Comments on Rev.B> Closed.
<Contractors Reply / Action on Rev.A> The nozzle sizes are calculated as per HEI standard. HDEC will use 250 x 200 reducer for drain outlet. 4 <Pyrys Comments on Rev.A> Correct nozzle size for channel relief valve from DN80(3/4) to DN80(3).
<Pyrys Comments on Rev.B> Closed.
<Contractors Reply / Action on Rev.A> Correct nozzle size for channel relief valve from DN80(3/4) to DN80(3).
5 <Pyrys Comments on Rev.A> Correct typing error word in the nozzle data table from Sehll level to Shell level.
<Pyrys Comments on Rev.B> Closed.
Reflected. Page4 / 4
No. Pyrys Comments Contractors Reply / Action 6 <Pyrys Comments on Rev.B> Any change from the previous version shall be cloud marked.
<Pyrys Comments on Rev.C> Closed. <Contractors Reply / Action on Rev.B> Reflected.