EE 512L

Illumination Design Laboratory



Beato Angelico Building

Quizon, Angelo Christopher
Reodica, Kevin
Santos, Divine Grace
5EEB






Ground Floor

Ground Floor Hallway
Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground
A 0 0 AG 11 33 BM 40 21
B 0 0 AH 36 17 BN 45 2
C 0 0 AI 51 30 BO 39 41
D 0 0 AJ 2 0 BP 41 25
E 55 42 AK 48 52 BQ 53 16
F 15 35 AL 19 56 BR 43 40
G 40 32 AM 19 14 BS 33 30
H 11 3 AN 7 7 BT 56 51
I 2 45 AO 5 4
J 30 54 AP 2 30
K 34 44 AQ 14 28
L 45 20 AR 16 53
M 46 29 AS 56 21
N 36 17 AT 2 39
O 49 25 AU 10 4
P 20 5 AV 8 20
Q 0 23 AW 44 33
R 33 36 AX 41 28
S 46 55 AY 29 19
T 10 30 AZ 4 15
U 47 20 BA 38 7
V 38 5 BB 28 31
W 20 24 BC 8 0
X 18 17 BD 34 46
Y 2 52 BE 33 46
Z 28 12 BF 50 7
AA 3 26 BG 56 40
AB 52 22 BH 50 26
AC 46 46 BI 27 35
AD 17 14 BJ 44 34
AE 31 43 BK 28 10
AF 56 6 BL 48 12
Average: 28.33 Lux Measured; 100 Lux - Standard
Comments and Recommendations:
We have observed that on the left end of the hallway we recorded 0 lux for both ground and
workplace levels due to the fact that there was no luminaire fixture for that part. The
luminaires used were two double tube fluorescent lamp equipped with a diffuser. It was not
bright enough to cover the entire hallway properly thus yielding the data above and failing to
pass the required standard. We recommend using at least two more luminaires of the same
type or putting pin lights at the left end of the hallway. The left end of the hallway is very
important to be illuminated properly because it is where an emergency exit door is located.






















Gallery 1
Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground
A 461 358 AJ 445 251 BT 538 534 DC 502 476
B 136 424 AL 388 351 BU 301 233 DD 195 41
C 451 45 AM 600 342 BV 43 134 DE 501 407
D 381 152 AN 370 285 BW 558 546 DF 594 341
E 348 528 AO 432 219 BX 188 100
F 516 393 AP 199 293 BY 142 128
G 500 407 AQ 267 21 BZ 306 357
H 96 327 AR 156 230 CA 270 168
I 67 328 AS 56 214 CB 559 510
J 403 323 AT 5 137 CC 524 380
K 21 58 AU 280 544 CD 272 569
L 227 593 AV 313 433 CE 134 423
M 515 115 AW 305 479 CF 516 155
N 433 125 AX 314 103 CG 124 43
O 135 477 AY 459 222 CH 368 288
P 384 15 AZ 180 31 CI 454 6
Q 527 0 BA 32 513 CJ 365 320
R 173 7 BB 20 577 CK 134 213
S 230 559 BC 554 10 CL 454 20
T 462 474 BD 442 423 CM 464 575
Average: 309.98 lux Measured; 300 lux Standard
Comments and Recommendations:
We have observed that the luminaires used in Gallery 1 and how they were positioned was very
good and very appropriate for the venue. Sunlight was also allowed to pass through Gallery 1
since it had very large window space. Its ambience was perfect for the Art Works to be clearly
seen and appreciated by everyone inside. It also passed its standard requirement of lux.








U 441 145 BE 214 283 CN 120 256
V 165 457 BF 118 269 CO 572 314
W 268 115 BG 560 355 CP 484 567
X 133 205 BH 189 365 CQ 73 55
Y 422 128 BI 204 429 CR 99 527
Z 501 308 BJ 144 40 CS 437 381
AA 421 41 BK 293 282 CT 329 445
AB 87 6 BL 582 248 CU 99 132
AC 286 501 BM 239 185 CV 326 75
AD 67 435 BN 419 372 CW 107 495
AE 247 85 BO 510 235 CX 504 455
AF 376 515 BP 469 594 CY 374 274
AG 25 559 BQ 168 236 CZ 238 515
AH 108 304 BR 234 217 DA 255 368
AI 354 111 BS 527 188 DB 211 435
Gallery 2
Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground
A
456 51
AJ
378 22
BS
384 82
B 34 498 AK 243 295 BT 416 81
C 310 596 AL 338 435 BU 300 119
D 322 196 AM 309 531 BV 369 135
E
472 26 AN 336 226
BW
342 167
F
250 445 AO 557 223
BX
508 49
G
60 168 AP 188 204
BY
35 519
H 389 316 AQ 429 159 BZ 329 279
I 518 207 AR 278 392 CA 139 538
J 472 460 AS 455 355 CB 13 90
K
459 420 AT 343 358
CC
104 473
L
258 387 AU 428 2
CD
553 490
M
117 268 AV 306 537
CE
285 492
N 292 375 AW 418 97 CF 580 65
O 516 349 AX 540 141 CG 380 411
P 321 287 AY 10 26 CH 148 583
Q
530 188 AZ 564 297
CI
291 5
R
273 284 BA 151 451
CJ
460 15
S
208 331 BB 440 243 CK 46 129
T
335 328 BC 532 0 CL 474 215
U
281 450 BD 561 162 CM 212 254
V
288 389 BE 500 15 CN 148 327
W 442 497 BF 115 85 CO 290 426
X 526 52 BG 175 185 CP 455 191
Y
339 308 BH 302 363 CQ 85 312
Z
312 270 BI 38 457 CR 371 137
AA
464 536 BJ 520 457 CS 451 85
AB
288 77 BK 407 187 CT 411 175
AC 73 297 BL 140 331 CU 583 196
AD 215 45 BM 305 168 CV 497 201
AE
324 334 BN 234 480 CW 367 438
AF
214 70 BO 341 444 CX 51 271
AG
348 259 BP 371 139 CY 54 131
AH
427 396 BQ 57 545 CZ 531 97
AI 355 323 BR 496 408 DA 81 514
Average: 253.36 lux Measured; 300 lux Standard
Comments and Recommendations:
We have observed that Gallery 2 had less space than compared to Gallery 1. Also its window
space was also lessened and was not exposed enough to sunlight. Its lighting fixtures are also
not that many compared to Gallery 1. Although the same amount of track lighting was
maintained, other luminaires were missing like pin lights and recessed down lights. Therefore,
unlike Gallery 1, it failed to meet its standard requirements of 300 lux. We recommend that the
luminaires be increased in quantity to the extent that it can compensate for the lessened
window space it has.





2
nd
Floor
2
nd
Floor Hallway
Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground
A 266 215 AJ 160 247 BS 139 239
B 50 269 AK 177 138 BT 125 270
C 282 61 AL 37 37 BU 91 151
D 156 193 AM 13 28 BV 133 238
E 165 275 AN 277 218 BW 148 252
F 200 160 AO 42 77 BX 11 83
G 132 66 AP 230 37 BY 238 84
H 11 103 AQ 75 86 BZ 179 73
I 238 243 AR 267 153 CA 270 166
J 190 214 AS 197 78 CB 8 223
K 166 55 AT 198 95 CC 85 278
L 153 53 AU 15 244 CD 97 84
M 239 54 AV 110 82 CE 281 12
N 173 224 AW 16 13 CF 261 64
O 30 5 AX 203 31 CG 265 160
P 175 140 AY 135 19 CH 249 195
Q 280 28 AZ 133 278 CI 268 284
R 7 41 BA 272 235 CJ 149 130
S 259 88 BB 5 31
T 47 246 BC 20 211
U 178 94 BD 243 123
V 160 194 BE 159 178
W 160 189 BF 29 255
X 13 17 BG 239 228
Y 25 76 BH 13 191
Z 219 133 BI 205 19
AA 113 262 BJ 68 128
AB 25 249 BK 10 232
AC 68 100 BL 285 172
AD 215 4 BM 55 230
AE 124 38 BN 63 6
AF 280 193 BO 104 222
AG 142 15 BP 51 136
AH 86 248 BQ 129 42
AI 269 95 BR 145 162
Average: 150.72 lux Measured; 100 lux Standard
Comments and Recommendations:
The 2
nd
Floor Hallway was an enclosed hallway with no windows on side of it. But it was lighted
appropriately and vividly due to it being the hallway where almost all the important
administrative offices were located. It used a combination of cove lights which had pin lights on
its center and double tube fluorescent lamps which was used in the ground floor hallway. We
were not permitted to measure the offices due to it being off limits to students. It passed its
requirement of 100 lux for hallways.














3
rd
Floor




Lecture Room 303
Labels Workplace Ground Labels Workplace Ground
A 166 112 AJ 218 326
B 308 252 AK 112 239
C 244 365 AL 220 67
D 249 87 AM 261 221
E 370 277 AN 253 100
F 209 137 AO 337 240
G 201 272 AP 288 151
H 158 126
I 132 379
J 313 43
K 358 280
L 25 83
M 382 338
N 51 68
O 114 245
P 283 40
Q 236 56
R 130 119
S 256 152
T 245 376
U 209 277
V 65 87
W 224 264
X 294 15
Y 388 52
Z 217 154
AA 215 241
AB 101 155
AC 264 63
AD 115 138
AE 47 72
AF 300 60
AG 289 120
AH 178 342
AI 343 289
Average: 167.19 lux Measured; 300 lux - Standard
Comments and Recommendations:
Lecture Room 303 was the first classroom our group was able to measure. We measured very
little lux provided by the double tube fluorescent lamps with diffusers. The ceiling was too high
and therefore lessened the appropriate lux that needed to reach the workplace area. Also the
room had a good window space but some parts of the window was tinted therefore sunlight
was blocked. The corners also had very poor lighting. We recommend that they increase the
number of double tube fluorescent tubes used and remove the diffuser so that direct lighting
can be used specially at the corners of the room. Glare or shadow wont be a problem because
the ceiling height is high.










3
rd
Floor Hallway
Labels Workplace Ground Labels Workplace Ground Labels Workplace Ground
A 157 108 AJ 85 38 BS 9 119
B 71 117 AK 56 50 BT 101 152
C 40 145 AL 167 29 BU 34 34
D 141 41 AM 96 4 BV 113 61
E 21 64 AN 42 32 BW 65 5
F 47 60 AO 144 5 BX 51 144
G 148 8 AP 90 167 BY 121 113
H 54 92 AQ 123 102 BZ 152 29
I 134 102 AR 56 12 CA 99 167
J 26 88 AS 151 45 CB 132 36
K 97 100 AT 118 138 CC 161 127
L 137 19 AU 9 141 CD 165 62
M 16 127 AV 98 60 CE 81 143
N 39 23 AW 103 88 CF 98 97
O 49 119 AX 3 13 CG 128 137
P 167 52 AY 26 82 CH 23 80
Q 165 165 AZ 56 128 CI 167 40
R 53 52 BA 162 147 CJ 103 91
S 152 125 BB 145 124
T 157 100 BC 54 26
U 79 134 BD 7 142
V 101 49 BE 74 91
W 5 5 BF 38 36
X 41 0 BG 141 161
Y 37 84 BH 74 91
Z 6 6 BI 1 3
AA 8 108 BJ 115 129
AB 20 16 BK 100 101
AC 108 89 BL 38 104
AD 121 112 BM 33 34
AE 28 14 BN 139 86
AF 131 55 BO 21 134
AG 102 161 BP 129 25
AH 101 80 BQ 2 166
AI 38 147 BR 53 145
Average: 82.91 lux Measured; 100 lux Standard
Comments and Recommendations:
The 3
rd
floor Hallway was different from the other hallways because it was not entirely linear. It
had a slanted end at the left most part which led to a conference room. The left end part had
only two double tube fluorescent lamps with diffusers. This was not enough to light the part of
the hallway properly therefore that part gave minimum lux values. As for the rest of the
hallway, it was lighted exactly the same way as the 2
nd
floor Hallway. We recommend that they
should put pin lights at the left end part of the hallway near the entrance to the conference
room because it was there where the lux had minimum values and the luminaires werent able
to light that part properly.












4
th
Floor



Lecture Room 409
Labels Workplace Ground Labels Workplace Ground
A 52 156 AG 168 95
B 57 0 AH 169 8
C 69 78 AI 173 20
D 65 0 AJ 175 19
E 59 46 AK 183 45
F 48 83 AL 174 42
G 34 99 AM 152 6
H 39 0 AN 101 3
I 48 0 AO 120 15
J 87 0 AP 228 16
K 105 34 AQ 215 18
L 95 32 AR 222 95
M 93 54 AS 178 6
N 83 46 AT 165 2
O 79 90 AU 154 28
P 76 12 AV 142 87
Q 77 46 AW 132 59
R 181 12 AX 260 141
S 186 112 AY 243 112
T 169 23 AZ 176 84
U 140 57 BA 242 132
V 144 45 BB 86 121
W 82 90 BC 176 46
X 78 0 BD 210 78
Y 153 13 BE 184 34
Z 91 0 BF 144 0
AA 153 48 BG 132 55
AB 164 128 BH 77 56
AC 142 0 BI 35 0
AD 185 0 BJ 26 0
AE 183 69 BK 0 0
AF 173 73 BL 0 0
Average: 128.63 lux Measured; 300 lux Standard
Comments and Recommendations:
Lecture 409 can be similarly compared to Lecture Room 303. They lux values did not meet the
standard requirement because of the poor lighting design. It only had 4 double tube fluorescent
lamps with diffusers. It had very poor lighting on the corners of the room and the windows did
little help due to the fact that some of them were tinted therefore blocking some sunlight that
should have passed through. We recommend that if they cannot change the windows to
become clearer they should at least remove the luminaires diffuser to allow more light to be
exposed and put pin lights on corners if the fluorescent lamps output would not be enough.
This recommendation is the same for all the classrooms located at the 4
th
floor.