Escolar Documentos
Profissional Documentos
Cultura Documentos
*
PLC/TRI >8XD min 3XD
125 9.9 12.6
160 16.9 21.9
200 28.3 31.0
250 47.9 51.5
315 78.6 -
TCE - Conical Ceiling Diffuser
2
0
/
T
C
E
/
3
5
0
0
/
0
6
0
6
/
E
N
Installation
CODE DESCRIPTION
1 PLC Plenum box
2 TCE
The TCE diffuser can be installed flush with a
suspended ceiling or fully exposed in the space.
The diffuser is connected either directly to the duct or
using a PLC plenum or TRI balancing plenum.
When it is connected directly to ductwork, a safety
distance of minimum 3xD upstream of the diffuser
should be maintained.
TCE (D) D1 TRI W1 H1 H2
100 100 TRI-100-100 305 16 260...290
125 125 TRI-125-125 305 16 285...315
160 160 TRI-160-160 305 16 320...350
200 200 TRI-200-200 482 17 403...433
250 250 TRI-250-250 482 17 453...483
When the TRI spigot is installed in the plenum, the H2
dimension can be reduced by 60 mm.
Installation with plenum TRI or PLC
Adjustment
The airflow rate can be adjusted and measured only
when the diffuser is installed.
In order to enable airflow adjustment and
measurement of airflow rate, it is recommended that
the diffuser be connected to a plenum equipped with
the MSM module.
The supply flow rate is determined using
measurement and adjustment module MSM.
Detach the conical central core and pass the tubes
and control spindle through the diffuser.
Measure the differential pressure with a manometer.
The flow rate is calculated using the formula below.
Adjust the airflow rate by rotating the control spindle
until the desired setting is achieved.
Lock the damper position with a screw.
Replace the tubes and spindle in the plenum and push
the conical central core back into place.
K factor for installations with different safety distances
(D= duct diameter)
Airflow adjustment damper DC
The airflow rate is adjusted by turning the damper
blades behind the diffuser with a screwdriver. The
measurement is carried out when the diffuser is
installed.
The technical performance for the combination of
supply air diffuser and TRI plenum is presented
separately for the two different installations. See HIT
Design software.
146 147
TCE - Conical Ceiling Diffuser
2
0
/
T
C
E
/
3
5
0
0
/
0
6
0
6
/
E
N
Pressure drop, throw pattern and sound data
Selection example :
Requirements : qv = 105 l/s Selection : TCE-200
LpA < 30 dB(A) LpA < 30 dB(A)
L0.2 < 4,5 m L0.2 < 4,5 m
DPtot = 11 Pa
Note: Recommended minimum supply temperature 12 C below room
SOUND LEVEL DATA
qv DPst DPtot F (Hz) LpA NR NC
(l/s) (m
3
/h) (Pa) (Pa) 125 250 500 1000 2000 4000 8000 [dB(A)]
TCE-100 25 90 2 8 36 21 22 23 23 16 6 25 23 20
30 108 2 11 41 26 27 28 28 21 11 30 27 25
36 130 4 16 46 31 32 33 33 26 16 35 32 30
43 155 5 23 51 36 37 38 38 31 21 40 37 35
TCE-125 33 119 3 7 40 26 25 23 21 16 9 25 20 17
40 144 5 11 45 31 30 28 26 21 14 30 25 22
48 173 7 16 50 36 35 33 31 26 19 35 30 27
57 205 9 23 55 41 40 38 36 31 24 40 35 33
TCE-160 48 173 6 9 27 21 27 25 23 17 15 25 22 19
59 212 8 13 32 26 32 30 28 22 20 30 27 24
72 259 12 20 37 31 37 35 33 27 25 35 32 29
87 313 18 29 42 36 42 40 38 32 30 40 37 34
TCE-200 90 324 3 8 31 30 26 24 22 15 9 25 21 19
109 392 4 11 36 35 31 29 27 20 14 30 26 24
134 482 6 17 41 40 36 34 32 25 19 35 31 29
163 587 9 25 46 45 41 39 37 30 24 40 36 34
TCE-250 111 400 4 7 30 24 26 23 22 16 6 25 22 19
135 486 6 10 35 29 31 28 27 21 11 30 27 24
164 590 9 15 40 34 36 33 32 26 16 35 32 29
200 720 13 23 45 39 41 38 37 31 21 40 37 34
LpA values presented with room attenuation 4 dB (red 10m
2
- sab). When using room attenuation 8 dB (red 25m
2
- sab): LpA - 4dB.
NR/NC noise criteria
Servicing
Remove the central core by gently drawing it out by
the central panel (simultaneously, a small pin on the
inner side of the external cone is pushed and the
assembly is turned clockwise, until it comes free).
Clean the parts by wiping them with a damp cloth.
Push the central core back into place so that the
springs lock.
Option: with balancing plenum TRI + MSM or PLC
+ MSM
Remove the measurement and adjustment module by
gently pulling the shaft (not the control spindle).
Wipe the parts with a damp cloth, instead of
immersing in water.
Reassemble the measurement and adjustment
module by pushing the shaft until the module meets
the stopper.
Push the central core back into place so that the pins
lock.
146 147
TCE - Conical Ceiling Diffuser
2
0
/
T
C
E
/
3
5
0
0
/
0
6
0
6
/
E
N
SOUND LEVEL DATA
qv DPst DPtot F (Hz) LpA NR NC
(l/s) (m
3
/h) (Pa) (Pa) 125 250 500 1000 2000 4000 8000 [dB(A)]
TCE-100 25 90 2 8 36 21 22 23 23 16 6 25 23 20
30 108 2 11 41 26 27 28 28 21 11 30 27 25
36 130 4 16 46 31 32 33 33 26 16 35 32 30
43 155 5 23 51 36 37 38 38 31 21 40 37 35
TCE-125 33 119 3 7 40 26 25 23 21 16 9 25 20 17
40 144 5 11 45 31 30 28 26 21 14 30 25 22
48 173 7 16 50 36 35 33 31 26 19 35 30 27
57 205 9 23 55 41 40 38 36 31 24 40 35 33
TCE-160 48 173 6 9 27 21 27 25 23 17 15 25 22 19
59 212 8 13 32 26 32 30 28 22 20 30 27 24
72 259 12 20 37 31 37 35 33 27 25 35 32 29
87 313 18 29 42 36 42 40 38 32 30 40 37 34
TCE-200 90 324 3 8 31 30 26 24 22 15 9 25 21 19
109 392 4 11 36 35 31 29 27 20 14 30 26 24
134 482 6 17 41 40 36 34 32 25 19 35 31 29
163 587 9 25 46 45 41 39 37 30 24 40 36 34
TCE-250 111 400 4 7 30 24 26 23 22 16 6 25 22 19
135 486 6 10 35 29 31 28 27 21 11 30 27 24
164 590 9 15 40 34 36 33 32 26 16 35 32 29
200 720 13 23 45 39 41 38 37 31 21 40 37 34
LpA values presented with room attenuation 4 dB (red 10m
2
- sab). When using room attenuation 8 dB (red 25m
2
- sab): LpA - 4dB.
NR/NC noise criteria
Suggested Specifications
The diffuser shall comprise several stamped square
cones, made of epoxy-painted steel with a white (RAL
9010) or grey (RAL7004) colour.
The diffuser shall be suitable for installation on
exposed ductwork or flush to the ceiling.
The diffuser shall be connected to the ductwork
using a TRI balancing plenum, which utilises polyester
fibre with a washable surface as sound attenuation
material.
Option
The diffuser shall be connected to the ductwork using
a PLC plenum, which utilises mineral wool as sound
attenuation material.
The plenum shall comprise an airflow measurement
and adjustment module.
The diffuser shall be suitable for installation in
450 x 450-mm, 600 x 600-mm and 675 x 675-mm
suspended ceilings.
The conical central core shall be removable.
The supply air pattern shall be radial in an angle of 360
degrees.
Product Code
TCE/S-D-W
S = Model
A Standard
B Suspended ceiling installation
600 x 600 mm
C Suspended ceiling installation
450 x 450 mm
D Suspended ceiling installation
675 x 675 mm
D = Diameter of duct connection
S=A, S=B, S=D: 100, 125, 160, 200, 250
S=C: 100, 125, 160
W = Width
S=B: 600
S=C: 450
S=D: 670
Specifics and accessories
CO = Colour
W White
G Grey
Code example
TCE/A-100, CO=W
Sub products
PLC Plenum (Ceiling diffusers)
TRI Plenum (Diffusers)
LD Airflow adjustment damper