Você está na página 1de 2

How To Connect Current Transformers?

The primary of a current transformer typically has only one turn. This is not really a turn or wrap around
the core but just a conductor or bus going through the window. The primary never has more than a very
few turns, while the secondary may have a great many turns, depending upon how much the current must be
stepped down. In most cases, the primary of a current transformer is a single wire or busbar,and the
secondary is wound on a laminated magnetic core, placed around the conductor in which the current needs to
be measured, as illustrated in figure 1.
If primary current exists and the secondary circuit of a CT is closed, the winding builds and maintains a
counter or back EMF to the primary magnetizing force.
Should the secondary be opened with current in the primary, the counter EMF is removed; and the primary
magnetizing force builds up an extremely high voltage in the secondary, which is dangerous to personnel
and can destroy the current transformer.

Figure 1 Current Transformer
CAUTION:
For this reason, the secondary of a current transformer should always be shorted before removing a relay
from its case or removing any other device that the CT operates. This protects the CT from overvoltage.
Current transformers are used with ammeters, wattmeters, powerfactor meters, watt-hour meters,
compensators, protective and regulating relays, and trip coils of circuit breakers. One CT can be used to
operate several instruments, provided the combined loads of the instruments do not exceed that for which the
CT is rated.
Secondary windings are usually rated at 5 amperes. A variety of current transformers are shown in figure 2.
Many times, CTs have several taps on the secondary winding to adjust the range of current possible to
measure on the primary.

Você também pode gostar