Você está na página 1de 107

Sub Head Description Amount

TOWERS
I Wiring
Rs. 95,315,151
II Low Tension System
Rs. 17,648,900
III Submains and Cables
Rs. 26,661,955
IV Distribution System
Rs. 63,541,127
V Earthing
Rs. 2,275,757
VI Fixtures and Fittings
Rs. 7,753,445
VII Lightning Protection
Rs. 441,428
VIII Fire Detection & Alarm System
Rs. 6,075,539
Rs. 219,713,302
PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB &
SHOPPING COMPLEX
TOWERS AND BASEMENT
SUMMARY OF COST OF INTERNAL ELECTRICAL WORKS
PART-A
TOTAL (PART - A) C/O TO PAGE-130 OF
VOLUME-2
11/07/2011 66
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
TENDER FOR INTERNAL ELECTRICAL WORKS
Sl
No.
Description Unit
Qty suuply labour
SUB-HEAD - I (WIRING)
1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC
insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick
PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5
sq mm PVC insulated stranded copper conductor 1100 volt grade wires and including
cost of providing saddles etc for surface conduiting and/or cost of cutting and filling
chases for recessed conduiting and including the cost of providing and fixing a 6 amp 240
Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc.
complete as per specifications and as per direction Project in-charge. nos 33,315 637 159
2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC
insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick
PVC surface/concealed conduit including cost of providing saddles etc for surface
conduiting and/or cost of cutting and filling chases for recessed conduiting etc. complete
as per specifications and as per direction of Project in-charge. (Cost of MCB shall be paid
in DB item) nos 1,087 1,063 266
3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper
conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC
conduit including cost of providing saddles etc for surface conduiting and/or cost of
cutting and filling chases for recessed conduiting etc. complete as per specification and
as per direction of Project in-charge.
nos 6,650 383 96
4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded
copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm
PVC insulated stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240
Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and
including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop
earthing etc. complete as per specifications and as per direction of Project in-charge.
nos 72 816 204
5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole
grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box
with including cost of providing stepped electronic fan regulator as required etc. complete
as per specification and as per direction of Project in-charge.
nos 8,726 1,038 259
6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp
240 volt single pole grid plate mounted switch with moulded cover plate in a recessed
1.6 mm thick G.I box etc. complete as per specification and as per direction of Project
in-charge.( This shall include socket and plug top near fan & switch shall be put near
entrance to toilet/kitchen) nos 5,294 715 179
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x
1.5 sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25
mm dia 2 mm thick PVC surface/concealed conduit including the cost of providing circuit
wiring with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade
wires and including cost of providing saddles etc as required for surface conduiting and/or
cost of cutting and filling chases as required and providing and fixing of a combined 5 pin
240 volt 6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate
mounted switch with moulded cover plate in recessed 1.6 mm thick G.I box etc.
complete as per specification and as per direction of Project in-charge.
nos 17,842 808 202
8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required
and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet
and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I
boxes with internal wiring and moulded front plates as per approved sample complete as
per specification and as per direction of Project in-charge. nos 50 467 117
9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet
wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing of a 6 pin 240 volt 16 amp
socket outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted
switch with moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as
per specification and as per direction of Project in-charge. nos 1,206 1,574 393
10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets
wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3
x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in
20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of providing
saddles etc as required for surface conduiting and/or cost of cutting and filling chases and
including providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with
safety shutters and 16 amp 240 volt single pole grid plate mounted switches with
moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per
direction of Project in-charge. 1,528 1,318 330
11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket
(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt
grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second
outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of
providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket
outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches
with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per
direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket
& plug top near geyser and controlling switch at door.
nos 4,190 1,574 393
12 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing of a 6 pin 240 volt 20 amp
socket outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI
box including providing and fixing a 20 amp single pole 240 volt 20 amp switch with
moulded cover plate in recessed 1.6 mm thick G.I box located separately as per
drawings/instructions for AC controls complete as per specification and as per direction of
Project in-charge.(one outlet on one circuit)
nos 414 1,574 393
13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100
volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed
and/or surface conduiting system including the cost of cutting/making good chases in
brick work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB,
industrial type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc.
complete as per specifications and as per direction of Project in-charge. nos 5 1,574 393
14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing a grid plate mounted 6 amp
240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6
mm thick GI box etc. complete as per specifications and as per direction of Project in-
charge. nos 1,206 706 177
15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including
cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost
of cutting and filling chases for recessed conduiting complete with accessories as per
specifications and as per direction of Project in-charge.
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
a) 25 mm m 189,000 39 10
b) 32 mm m 1,080 49 12
c) 40 mm m 1,080 61 15
d) 50 mm m 580 72 18
16 Supplying and fixing of the following MS Conduits including the cost of draw/junction
boxes with accessories as required and including the cost of GI fish wire etc. complete as
per specifications and as per direction of Project in-charge.
a) 25 mm dia 16 SWG m 30,080 106 26
b) 32 mm dia 16 SWG m 480 123 31
c) 38 mm dia 14 SWG m 480 143 36
d) 50 mm dia 14 SWG m 480 192 48
17 Supplying and drawing following sizes of PVC insulated copper conductor single core
stranded cables in existing surface / recessed conduits as per specifications and/or as
per direction of Project in-charge. as required.
a) 3 x 1.5 sq mm (P+N+E) m 4,500 64 16
b) 3 x 2.5 sq mm (P+N+E) m 3,000 106 26
c) 3 x 4.0 sq mm (P+N+E) m 1,600 145 36
d) 3 x 6.0 sq mm (P+N+E) m 400 170 42
18 Supply, installation, testing and commissioning of the following switches, sockets in
recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,
complete as per specifications and/or as per direction of Project in-charge.
a) 6 amp switch with box and cover plate nos 443 98 24
b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 174 44
c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 332 83
TOTAL SUB-HEAD - I carried over to Summary
SUB-HEAD - II (LOW TENSION SYSTEM)
1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system..
nos 5,473 638 159
2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system.
nos 20 595 149
3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone
tag block of Krone make constructed from 14 SWG sheet steel, finished with powder
coated paint, with hinged gasketted door and complete with adequately rated and sized
telephone terminal block to receive incoming and outgoing wires. The cost shall be
complete with fixing arrangements, foundations etc as required
a) 10 Pair nos 13 978 245
b) 20 Pair nos 4 1,234 308
c) 30 Pair nos 8 1,488 372
d) 50 Pair nos 95 3,403 851
e) 300 Pair nos 2 14,036 3,509
f) 400 Pair nos 11 15,737 3,934
4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including
the cost of digging and back filling with sand and brick protection as required and testing
and commissioning of the following multi core 0.61 mm annealed tinned copper
conductor PVC insulated and PVC sheathed and overall PVC sheathed armoured
telephone cables including making terminal joints, complete as per specification and /or
as per direction of Project in-charge.
a) 10 Pair m 80 81 20
b) 20 Pair m 50 121 30
c) 30 Pair m 300 149 37
d) 50 Pair m 4,030 183 46
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc
chromate passivated MS boxes, including termination complete in all respects as per
specification and / or as per direction of Project in-charge..
nos 5,367 723 181
6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed
conduits upto the central point complete in all respects as per specification and / or as
per direction of Project in-charge.
m 155,750 28 7
7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure
with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-
charge. nos 934 851 213
8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick
hylum sheet cover for cable TV as required at site and /or as per direction of Project in-
charge.. nos 149 1,361 340
TOTAL SUB-HEAD - II carried over to Summary
SUB-HEAD - III (SUBMAINS AND CABLES)
1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 200 50
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 396 99
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 455 114
1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 200 50
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 396 99
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 455 114
2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/
in ground including the cost of digging and back filling with sand and brick protection as
required and including testing and commissioning of the following 1100 volt grade
armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable
complete as required. The costs shall include providing a gap of 1D between all the
cables being laid and properl clamping with cable clamps and ties. Prices shall include
providing and fixing of Identification tags for all cables and route markers for cables in
ground etc. as per specification and or as per direction of Project in-charge.

a) 3 -1/2 core 300 Sq mm XLPE m 1,000 553 138
b) 3 -1/2 core 240 Sq mm XLPE m 50 485 121
c) 3 -1/2 core 185 Sq mm XLPE m 100 404 101
d) 3 -1/2 core 70 Sq mm XLPE m 4,800 298 74
e) 3 -1/2 core 50 Sq mm XLPE m 600 260 65
f) 4 core 35 Sq mm XLPE m 100 234 58
g) 4 core 25 Sq mm XLPE m 200 187 47
h) 4 core 16 Sq mm XLPE m 1,200 136 34
i) 4 core 10 Sq mm XLPE m 7,000 106 27
j) 4 core 6 Sq mm XLPE m 100 76 19
k) 2 core 10 Sq mm XLPE m 1,000 81 20
3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade
including cost of tinned copper heavy duty lugs, double compression glands, insulation
tape and all requisite material for completion of joints.
a) 3 -1/2 core 300 Sq mm XLPE nos 40 1,310 328
b) 3 -1/2 core 240 Sq mm XLPE nos 2 1,148 287
c) 3 -1/2 core 185 Sq mm XLPE nos 4 851 213
d) 3 -1/2 core 70 Sq mm XLPE nos 418 425 106
e) 3 -1/2 core 50 Sq mm XLPE nos 26 340 85
f) 4 core 35 Sq mm XLPE nos 2 298 74
g) 4 core 25 Sq mm XLPE nos 4 170 42
h) 4 core 16 Sq mm XLPE nos 66 128 32
i) 4 core 10 Sq mm XLPE nos 248 128 32
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
j) 4 core 6 Sq mm XLPE nos 4 64 16
k) 2 core 10 Sq mm XLPE nos 50 85 21
4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and
MS painted angle supports spaced 1000 mm apart throughout the length as specified,
including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash
fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction
of Project in-charge.
a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 50 319 80
b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 383 96
c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 300 425 106
d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 553 138
5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer
and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as
in item no. 4 above. kg 1,010 72 18
6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per
approved design of the following sizes, including cost of providing and fixing of 15 x 30 x
15 mm MS channel supports spaced 250 mm apart throughout the length with necessary
fixing arrangements with angle iron supports etc. as per specification and /or as per
direction of Project in-charge. Rate shall include providing and applying paint 1 coat of
primer and 2 coats of enamel paint for all the MS material .
a) 900 mm m 80 1,234 308
b) 750 mm m 150 1,067 267
c) 600 mm m 150 974 243
d) 450 mm m 350 502 125
e) 300 mm m 650 442 111
f) 150 mm m 40 378 94
7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,
fixing in position with fasteners, including a priming coat of primer and two coats of
approved synthetic enamel paint.
a) In grating, frames, ladders, brackets, similar works kg 530 72 18
8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,
refilling including compaction of soil as required for cable entry including the cost of
sealing the ends as required complete in all respects, as per spacification and /or as per
direction of Project in-charge.
a) 150 mm dia m 680 298 74
b) 200 mm dia m 500 349 87
c) 300 mm dia m 500 408 102
9 Providing and making of manhole chamber with masonry bricks and plastering inside with
1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required.
a) 600 x 600 x 750 mm deep nos 34 3,615 904
b) 450 x 450 x 750 mm deep nos 34 3,020 755
TOTAL SUB-HEAD - III carried over to Summary

SUB-HEAD - IV (DISTRIBUTION SYSTEM)
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with
interconnections and neutral bar assembly, earthing terminals complete as approved by
Project Manager. Padlocking facility shall be provided on the door.
a) 12 WAY SPN
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings
nos R/O 12,760 3,190
b) 12 WAY SPN
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with
thermal magnetic protective releases out goings.
nos R/O 7,230 1,808
c) 6 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 5,529 1,382
d) 8 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 15,737 3,934
e) 8 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of
incoming and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
nos R/O 21,265 5,316
f) 12 WAY TPN with Timer on 2-phases-Vertial DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of
incoming and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
nos R/O 27,220 6,805
g) Incomer DB for Penthouses-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 2,127 532
h) 8 Way VTPN
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings
nos R/O 15,737 3,934
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every
floor level, expansion joints, thrust pads to support weight of busbars, fully gasketed
covers, with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and
with 2 runs of aluminium strip for earthing as required .
a) 400 amps m R/O 8,506 2,127
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 8,081 2,020
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 8,932 2,233
4 Meter Boards Tap-Off Boxes
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever
necessary for large meter boards. Cable gland plates shall be provided at top and bottom
both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring
upto KWH meter & meter to MCB shall be done by using adequately rated flexible single
core copper wire. The boards shall be treated with all anticorrosive process before
painting as per standards with final approved shade of powder coated as approved 2 nos.
earthing terminals shall be provided for 3 phase meter boards and to be connected with
the earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3
phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth
etc to match with site conditions.
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards.
a) 6 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 55,291 13,823
b) 5 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 52,739 13,185
c) 4 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 46,785 11,696
d) 3 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 38,278 9,570
e) 2 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 4 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 25,519 6,380
f) 9 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 12 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 80,810 20,202
5 Dual Pre-Paid meter
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
Design,supply ,installation testing and commissioning of BIS approved single phase dual
energy meter for recording dual electric supply from grid and DG with KWH & KVAH max
demand communication port,billing,storage facilities ,control panel for sensing supply
from DG sets, data transfer & receiving hub, AMR system. DLC with energy management
software with load manager system and recharge coupon generation software &
connecting accessories for prepaid system.
1 phase digital electronic energy meter (for tariff application)
nos R/O 15,312 3,828
ALTERNATIVELY
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with
interconnections and neutral bar assembly, earthing terminals complete as approved by
Project Manager. Padlocking facility shall be provided on the door.
a) 12 WAY SPN
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings
nos 18 7,230 1,808
b) 12 WAY SPN
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with
thermal magnetic protective releases out goings.
nos 20 6,635 1,659
c) 6 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 1,098 12,334 3,084
d) 8 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 5 15,737 3,934
e) 8 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of
incoming and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
nos 35 18,714 4,679
f) 12 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of
incoming and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
nos 10 22,610 5,652
g) Incomer DB for Penthouses-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings.
nos 72 2,722 680
h) 8 Way VTPN-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings
nos 2 14,631 3,658
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
j) 8 WAY SPN
1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings
nos 1 5,529 1,382
k) 4 WAY SPN
1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings nos 194 2,977 744
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every
floor level, expansion joints, thrust pads to support weight of busbars, fully gasketed
covers, with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and
with 2 runs of aluminium strip for earthing as required .
a) 400 amps m 620 4,679 1,170
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos 169 10,208 2,552
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos 12 11,484 2,871
4 Meter Boards Tap-Off Boxes
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever
necessary for large meter boards. Cable gland plates shall be provided at top and bottom
both and windows for meter reading, locking arrangement (pad-lock & seal) with wiring
upto KWH meter & meter to MCB shall be done by using adequately rated flexible single
core copper wire. The boards shall be treated with all anticorrosive process before
painting as per standards with final approved shade of powder coated as approved 2 nos.
earthing terminals shall be provided for 3 phase meter boards and to be connected with
the earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3
phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth
etc to match with site conditions.
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards.
a) 6 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
8 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 153 42,532 10,633
b) 5 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
8 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 6 38,278 9,570
c) 4 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
6 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 34,025 8,506
d) 3 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
6 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 4 25,519 6,380
e) 2 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
4 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 18,714 4,679
f) 9 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 2 102,075 25,519
5 Dual Pre-Paid meter
Design,supply ,installation testing and commissioning of BIS approved three phase 4wire
dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH
max demand communication port,billing,storage facilities ,control panel for sensing
supply from DG sets, data transfer & receiving hub, AMR system. DLC with energy
management software with load manager system and recharge coupon generation
software & connecting accessories for prepaid system.
3 phase digital electronic energy meter (for tariff application) nos 1,026 9,357 2,339
6 Design ,supply ,installation, testing and commissioning of required software to make the
kWH meter functional in coordination with kWH meter manufacturer and facility
mangement team for prepaid/postpaid tariff application system for dual resistor (
recording) KWH meter to effectively monitor/control the tariff as per individual site
condition complete with latest version of computer & printer etc as required. ( Integrated
with existing software installed) job 1 170,126 42,532
7 Design, manufacture, supply, installation, testing and commissioning of cubical type
electrical control panel comprising of necessary contactors.PLA relays terminals etc to
provide signaled DC supply to the dual source energy meters.( Integrated with existing
software installed) set 1 255,189 63,797
8 Design, manufacture, supplying, fixing in position, testing and commissioning of the
following rating Adopter Box for Rising Mains complete with interconnections as required.
The Adopter box shall be complete with voltmeter and ammeter with requisite CT's
a) 1-400 amp TPN switch isolator nos 24 11,909 2,977
9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface
including providing coupler, junction boxes complete as required from DG panel to all
meter boards ( to get 24V DC signal to energy meter to record consumotions ON DG
seperately)
a 25mm dia PVC conduit m 3,200 39 10
b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment
m 31,000 33 8
c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 81 20
9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing
conduit from Meter Board to freedom display units.
Three pair 0.61 mm dia (telephone wire) m 31,000 19 5
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
10 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free
standing, dust and vermin proof, switchboard with IP42 protection with hinged and
lockable doors complete with interconnections, tinned copper crimping lugs, bonding to
earth and powder coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system,
and suitable for a fault level of 25 MVA symmetrical at 415 volts.
All switchboards shall have provision for entry of cables from the top or bottom as
required.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing
feeders doors and switch handles shall be lockable in OFF position.
The short circuit rating for MCCB's shall be Ics values
10.1 SWITCHBOARD - TOWER (1 TO 12)
INCOMINGS
2 nos 630 amp 4P Switch Isolator complete with

a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CTs
class 1.0 accuracy 10 VA Burden.
d) 1 set of RYB Phase indicating lamps (LED type)
e) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%
capacity.
BUS COUPLER
1 nos 630 amp 4P Switch Isolator complete
INTERLOCKING
The Incoming & Buscoupler shall be electrically & mechanically interlocked such that
incomers cannot be paralleled.
OUTGOING UNITS

LEFT HAND SECTION
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
RIGHT HAND SECTION
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 297,720 74,430
10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12)
INCOMINGS
1 no. 160 amp 4-P Changeover switch complete with
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 set of RYB Phase indicating lamps (LED type)
d) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS
3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 127,595 31,899
10.3 SWITCHBOARD - BASEMENT VENTILATION
INCOMINGS
1 nos 160 amp TPN Switch Isolator complete with
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 set of RYB Phase indicating lamps (LED type)
d) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS
8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 144,607 36,152
11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter
system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries
backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,
transformers, controls, protection and instruments etc complete as required.
nos 12 26,369 6,592
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
12 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free
standing, dust and vermin proof, switchboard with IP42 protection with hinged and
lockable doors complete with interconnections, tinned copper crimping lugs, bonding to
earth and powder coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system,
and suitable for a fault level of 25 MVA symmetrical at 415 volts.
All switchboards shall have provision for entry of cables from the top or bottom as
required.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing
feeders doors and switch handles shall be lockable in OFF position.
The short circuit rating for MCCB's shall be Ics values
A. EWS MAIN PANEL
INCOMING
1 nos 400 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity.
INDICATING PANEL
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering
b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch
c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch
d) 1 set of three White phase indicating lamps
OUTGOING UNITS
11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 127,595 31,899
B EWS COMMON PANEL
INCOMING
2 nos 100 amp 4P Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%
capacity.
INDICATING PANEL
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering
b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch
c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch
d) 1 set of three White phase indicating lamps
INTERLOCKING
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
The Incoming shall be interlocked such that incomers cannot be paralleled.
OUTGOING UNITS
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 119,088 29,772
E SWITCHBOARD - CLUB
INCOMING
1 nos 400 amp TPN Switch Isolator complete with
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering
b) 1 no digital electronic ammeter 400 amps
c) 1 no digital electronic voltmeter 500 volts
d) 1 set of three White phase indicating lamps (LED type)
e) Red / Green ON/OFF indicator (LED type)
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity.
OUTGOING UNITS
2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable
for remote data logging
S
12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital
Electronic Energy Meter with requisite CT suitable for remote data logging
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required
nos 1 161,620 40,405
3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever
necessary. Cable gland plates shall be provided at top and bottom both and windows for
meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &
meter to MCB shall be done by using adequately rated flexible single core copper wire.
The boards shall be treated with all anticorrosive process before painting as per
standards with final approved shade of powder coated as approved, 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for
415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length,
height, depth etc to match with site conditions.
The Meter Board shall be in Non-compartmentalized construction.
An approval shall be taken for each panel before manufacturing.
A SHOPPING METER BOARD
INCOMING
1 nos 100 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand
symmetrical fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
OUTGOING UNITS
1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases.
4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.
14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with
provision for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid
electronic energy meter.
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 1 72,303 18,076
B METER BOARD -EWS
INCOMING
1 nos 100 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand
symmetrical fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
OUTGOING UNITS
2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.
20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with
provision for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid
electronic energy meter.
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 9 68,050 17,013
C Design,Supply installation testing & commissioning of BIS approved single phase dual
register energy meter for recording dual electric supply from grid and DG with kWH &
kWAh max demand communication port, billing storage facilities, control panel for
sensing supply from DG sets, data transfer & receiving hub,AMR system. DLC with
energy management software with load manager system & recharge coupon generation
software & connecting accessories for prepaid system.
single phase dual register digital electronic prepaid energy meter ( for tariff application)
nos 194 12,760 3,190

TOTAL SUB-HEAD - IV carried over to Summary
SUB HEAD V : EARTHING
1 Supplying and laying of the following earthing clamped to wall with suitable clamps
saddles and fixing bolts/ in ground/RCC slab along with submain conduit including the
cost of digging and back filling with sand and brick protection as required and complete
as required to comply with IS 3043:1987
a) 25 mm x 6 mm GI strip m 3,800 83 21
b) 8 SWG GI Wire m 102,200 7 2
c) 6 SWG GI Wire m 20,400 8 2
2 Supply and laying of the following GI pipe in ground including excavation, refilling as
required for earth strips etc. as required complete
a) 80 mm dia m 181 298 74
3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. nos 80 7,230 1,808
4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25
mm dia. GI pipe from earth electrode as required as per specifications. m 181 128 32
TOTAL SUB HEAD V carried over to Summary
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
SUB-HEAD -VI (FIXTURES AND FITTINGS)
1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.
copper wound ballast, HPF condensors, starters, holders etc. complete as required
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 800/-) nos 780 927 232
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 600/-) nos 3,693 681 170
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories (base Rate Rs 800/-) nos 790 1,084 271
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) nos 530 564 141
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) nos 24 468 117
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories (base Rate Rs 1200/-) nos 970 1,276 319
1b Receiving, assembling, erection, connecting, testing and commissioning of the following
light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,
HPF condensors, starters, holders etc. complete as required
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories nos 780 64 16
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories nos 3,693 64 16
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories nos 790 64 16
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories nos 530 64 16
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories nos 24 64 16
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories nos 970 64 16
2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200
mm Sweep including supply of 19 mm heavy gauge GI down rod of length as required
complete. nos 17 1,488 372
3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust
Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top
as required. nos 17 1,531 383
4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and
commissioning of 240 Volt single phase Buzzer as required complete. nos 1,206 64 16
TOTAL SUB-HEAD - VI carried over to Summary
SUB HEAD VII : LIGHTNING PROTECTION
1 Air Terminal & Accessories
Supplying, Erection & commissioning of External Lightning Wide Area Protection System
based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.
Device shall emit electromagnetic impulse in the form of a controlled emission of
streamers into the air 60 microseconds earlier than naturally formed streamers & polarise
the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE
21186 standards. The device shall be mounted at least 5 meter clear to the highest point
by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85
micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm
floor area & upto 600mm height complete as required
sets 3 8,932 2,233
2 Low Impedance high voltage down conductor & accessories
Supply, installation, testing & commissioning of down conductor. The Down conductor
shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2
fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down
the elevation pole and take the shortest direct route down the outside of the building to
the earth termination network, avoiding any sharp corners, thereby providing a low
impedance path from the air terminal to its earth termination system.
m 300 95 24
3 Lightning Discharge Counter
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
Supply, installation, testing & commissioning of Lightning Discharge Counter. The
lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof
IP67 enclosure with fixing clamps, etc. sets 3 21,265 5,316
4 Maintenance Free Earthing
Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic
Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod
moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,
The earthing pit shall be provided with suitable sturdy Test Well for observation. The
Earth Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures
should be followed as instructed by the Earth Electrode Supplier)
nos 6 15,312 3,828
5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per
Wipro Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required
nos 3 6,380 1,595
6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic
ON/OFF of Aviation light as required. nos 3 5,529 1,382
7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper
conductor armoured cable from M/C room DB to aviation light. m 200 132 33
8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical
conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles
complete as required. m 50 83 21
9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with
suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as
required. m 200 83 21
10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth
plate at one end and vertical conductor strip at the other end including the cost of digging
and back filling complete m 30 179 45
11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. nos 2 7,230 1,808
12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various
Lightning arrestor earth pits, including the cost of digging and back filling, complete as
required. m 200 115 29
13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4
Nos. GI bolts, nuts, check nuts and spring washers complete as required. nos 2 166 41
14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube
having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as
required. nos 1 1,531 383
15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports
wherever is required. nos 30 485 121
TOTAL SUB-HEAD - VII carried over to Summary
SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM)
1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC
illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'
painted in red including the cost of in-built rechargeable batteries suitable for 30 minute
operation and including the cost of accessories for surface or recessed or ceiling
suspended mounting complete as required. nos 514 1,849 462
2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes
with push button to initiate audio visual alarm with breakable glass cover as per detailed
specifications complete with a steel chain including the cost of accessories for surface
mounted as required nos 514 554 139
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-
hooter units with line matching transformer suitable for broadcast of speech and alarm
siren complete as required suitable for recessed/surface mounting complete with
enclosure as approved by Project Manager and as required.
nos 211 740 185
4 Supply, installation, testing and commissioning of wall recess mounting 24 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete. nos 10 62,873 15,718
4 Supply, installation, testing and commissioning of wall recess mounting 16 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete.
nos 2 55,476 13,869
5 Supply, installation, testing and commissioning of wall recess mounting 15 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete.
nos 1 51,777 12,944
6 Supply, installation, testing and commissioning of wall recess mounting 10 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete. nos 1 48,079 12,020
7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade
wires in existing concealed/surface MS conduit etc. as per specification and as required
including the cost of crimped termination's.
m 36,500 40 10
8 Supply and laying control cabling with copper conductor PVC insulated and PVC
sheathed armoured Control cables in existing pipes/conduits or on existing tray including
the cost of making connections, complete etc. etc. as per specification and as required
as below:

a) 10 core 2.5 sq mm m 5,100 229 57
TOTAL SUB-HEAD -VIII carried over to Summary
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
TENDER FOR INTERNAL ELECTRICAL WORKS
supply
amount
Labour
Amount
rate Amount
21,232,316 5,308,079 797 26,540,395
1,155,594 288,899 1,328.88 1,444,493
2,548,918 637,230 479.12 3,186,148
58,774 14,694 1,020.39 73,468
9,055,773 2,263,943 1,297.24 11,319,716
3,785,549 946,387 893.83 4,731,936
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
14,419,476 3,604,869 1,010.22 18,024,345
23,368 5,842 584.21 29,211
1,898,080 474,520 1,967.33 2,372,600
2,013,953 503,488 1,647.54 2,517,441
6,594,490 1,648,623 1,967.33 8,243,113
651,580 162,895 1,967.33 814,475
7,869 1,967 1,967.33 9,837
851,465 212,866 882.53 1,064,331
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
7,346,808 1,836,702 48.59 9,183,510
52,721 13,180 61.02 65,902
66,390 16,597 76.84 82,987
41,946 10,486 90.40 52,432
-
3,181,501 795,375 132.21 3,976,877
59,013 14,753 153.68 73,766
68,559 17,140 178.54 85,699
91,991 22,998 239.56 114,989
-
288,828 72,207 80.23 361,035
317,304 79,326 132.21 396,630
231,424 57,856 180.80 289,280
67,981 16,995 212.44 84,976
-
43,251 10,813 122.04 54,064
77,291 19,323 218.09 96,614
19,906 4,977 414.71 24,883
76,252,121 19,063,030 20,151 95,315,151
3,489,636 872,409 797.01 4,362,044
11,906 2,977 744.13 14,883
-
12,718 3,180 1,222.90 15,898
4,935 1,234 1,542.08 6,168
11,906 2,977 1,860.33 14,883
323,245 80,811 4,253.23 404,057
28,071 7,018 17,544.58 35,089
173,107 43,277 19,671.20 216,383
-
6,473 1,618 101.14 8,091
6,050 1,512 151.24 7,562
44,759 11,190 186.50 55,949
735,874 183,968 228.25 919,842
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
3,880,201 970,050 903.72 4,850,252
4,392,898 1,098,224 35.26 5,491,122
794,503 198,626 1,063.31 993,129
202,839 50,710 1,701.67 253,548
14,119,120 3,529,780 52,007 17,648,900
1,367,777 341,944 249.59 1,709,722
32,046 8,012 494.54 40,058
184,279 46,070 568.76 230,349
-
379,383 94,846 249.59 474,229
11,869,068 2,967,267 494.54 14,836,335
1,911,043 477,761 568.76 2,388,804
-
552,995 138,249 691.24 691,244
24,235 6,059 605.88 30,294
40,380 10,095 504.75 50,475
1,428,725 357,181 372.06 1,785,906
155,880 38,970 324.75 194,850
23,382 5,845 292.27 29,227
37,411 9,353 233.82 46,764
163,002 40,751 169.79 203,753
743,034 185,758 132.68 928,792
7,645 1,911 95.56 9,556
80,908 20,227 101.14 101,135
-
52,405 13,101 1,637.64 65,506
2,297 574 1,435.37 2,871
3,403 851 1,063.31 4,253
177,785 44,446 531.65 222,231
8,839 2,210 424.95 11,049
595 149 372.06 744
680 170 212.47 850
8,426 2,107 159.59 10,533
31,663 7,916 159.59 39,578
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
255 64 79.79 319
4,268 1,067 106.71 5,335
-
15,959 3,990 398.97 19,948
38,302 9,575 478.77 47,877
127,597 31,899 531.65 159,496
55,299 13,825 691.24 69,124
72,724 18,181 90.00 90,905
-
98,693 24,673 1,542.08 123,366
160,108 40,027 1,334.24 200,135
146,079 36,520 1,217.33 182,599
175,621 43,905 627.22 219,526
287,560 71,890 553.00 359,450
15,113 3,778 472.27 18,891
-
38,162 9,540 90.00 47,702
-
202,403 50,601 372.06 253,003
174,436 43,609 436.09 218,045
204,128 51,032 510.32 255,160
-
122,906 30,726 4,518.60 153,632
102,665 25,666 3,774.46 128,332
21,329,564 5,332,391 29,971 26,661,955
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
15,949.62
-
9,038.12
-
6,911.50
-
19,671.20
-
-
-
26,581.77
-
-
-
34,024.93
-
2,658.27
-
19,671.20
-
10,633.09
10,101.43
11,164.74
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
-
-
-
-
-
-
69,114.10
-
-
-
-
-
-
65,924.18
-
-
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
58,481.01
-
-
-
-
-
-
47,847.94
-
-
-
-
-
-
31,898.32
-
-
-
-
-
-
101,012.41
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
19,139.54
-
-
-
130,149 32,537 9,038.12 162,686
-
132,704 33,176 8,293.99 165,880
-
13,543,144 3,385,786 15,417.97 16,928,930
-
78,685 19,671 19,671.20 98,356
-
-
-
654,998 163,749 23,392.77 818,747
-
-
-
226,097 56,524 28,262.10 282,621
-
195,978 48,995 3,402.40 244,973
-
29,262 7,315 18,288.71 36,577
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
5,529 1,382 6,911.50 6,911
-
577,589 144,397 3,721.58 721,986
-
2,900,703 725,176 5,848.19 3,625,878
1,725,111 431,278 12,759.70 2,156,389
137,805 34,451 14,354.66 172,256
-
-
-
-
-
-
-
-
-
6,507,332 1,626,833 53,164.48 8,134,165
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
229,670 57,418 47,847.94 287,088
-
-
-
-
-
-
272,201 68,050 42,531.39 340,251
-
-
-
-
-
-
102,075 25,519 31,898.32 127,593
-
-
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
149,714 37,428 23,392.77 187,142
-
-
-
-
-
-
204,151 51,038 127,594.19 255,188
-
-
9,600,399 2,400,100 11,696.39 12,000,499
170,126 42,532 212,657.91 212,658
255,189 63,797 318,985.93 318,986
-
285,817 71,454 14,886.31 357,272
-
123,523 30,881 48.25 154,403
1,012,507 253,127 40.83 1,265,634
283,178 70,795 101.14 353,973
-
575,333 143,833 23.20 719,166
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
3,572,644 893,161 372,150.40 4,465,805
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1,531,137 382,784 159,493.43 1,913,921
-
-
-
-
-
-
-
-
-
-
-
-
1,735,283 433,821 180,758.66 2,169,104
316,432 79,108 32,961.63 395,540
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
127,595 31,899 159,493.43 159,493
-
-
-
-
-
-
-
-
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
-
-
119,088 29,772 148,860.35 148,860
-
-
-
-
-
-
-
-
-
-
-
-
-
161,620 40,405 202,024.82 202,025
-
-
-
-
-
-
-
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
-
-
-
-
72,303 18,076 90,379.33 90,379
-
-
-
-
-
-
-
-
612,452 153,113 85,062.80 765,565
-
2,475,381 618,845 15,949.62 3,094,227
50,832,902 12,708,225 2,501,366 63,541,127
315,901 78,975 103.91 394,876
682,753 170,688 8.35 853,442
166,528 41,632 10.20 208,160
-
53,875 13,469 372.06 67,344
578,440 144,610 9,038.12 723,050
23,109 5,777 159.59 28,886
1,820,605 455,151 9,692 2,275,757
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
723,136 180,784 1,158.87 903,920
2,513,702 628,426 850.83 3,142,128
856,521 214,130 1,355.25 1,070,651
298,947 74,737 705.06 373,684
11,223 2,806 584.54 14,029
1,237,690 309,422 1,594.96 1,547,112
-
49,789 12,447 79.79 62,236
235,730 58,932 79.79 294,662
50,427 12,607 79.79 63,034
33,831 8,458 79.79 42,288
1,532 383 79.79 1,915
61,916 15,479 79.79 77,396
25,300 6,325 1,860.33 31,626
26,032 6,508 1,914.14 32,540
76,981 19,245 79.79 96,226
6,202,756 1,550,689 10,583 7,753,445
26,795 6,699 11,164.74 33,494
-
28,503 7,126 118.76 35,629
-
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
63,796 15,949 26,581.77 79,745
-
91,870 22,967 19,139.54 114,837
19,140 4,785 7,974.81 23,924
16,588 4,147 6,911.50 20,734
26,426 6,606 165.16 33,032
4,157 1,039 103.91 5,196
16,626 4,157 103.91 20,783
5,367 1,342 223.62 6,708
14,461 3,615 9,038.12 18,076
23,010 5,753 143.82 28,763
331 83 206.91 414
1,531 383 1,914.14 1,914
14,541 3,635 605.88 18,177
353,142 88,286 84,397 441,428
950,505 237,626 2,311.54 1,188,131
284,987 71,247 693.06 356,234
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
156,074 39,019 924.61 195,093
628,726 157,181 78,590.72 785,907
110,951 27,738 69,344.56 138,689
51,777 12,944 64,721.48 64,721
48,079 12,020 60,099.22 60,099
1,460,733 365,183 50.03 1,825,916
-
1,168,598 292,150 286.42 1,460,748
4,860,431 1,215,108 277,022 6,075,539
Internal Electrical work for Towers, Basement, EWS, Club Shopping Complex.
PART - B -ANCILLIARY AREAS (NURSERY & PRIMARY SCHOOL)
Sub
Head
Description Amount
TOWERS
I Wiring
Rs. #REF!
II Low Tension System
Rs. #REF!
III Submains and Cables
Rs. #REF!
IV Distribution System
Rs. #REF!
V Earthing
Rs. #REF!
VI Fixtures and Fittings
Rs. #REF!
VII Lightning Protection
Rs. #REF!
VIII Fire Detection & Alarm System
Rs. #REF!
Rs. #REF!
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
SUMMARY OF COST
TENDER FOR INTERNAL ELECTRICAL WORKS
TOTAL (PART - B) C/O TO PAGE-130 OF
VOLUME-2
Prepared by Pradeep Kumar K.N. 7/16/2014 Page 97

Prepared by Pradeep Kumar K.N. 7/16/2014 Page 98
Internal Electrification BOQ for Nursery Primary School. PART - B -ANCILLIARY AREAS (NURSERY & PRIMARY SCHOOL)
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
TENDER FOR INTERNAL ELECTRICAL WORKS
Sl No. Description Unit QTY labour labour
rate amount
SUB-HEAD - I (WIRING)
1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq.
mm PVC insulated stranded copper conductor 1100 Volt grade wires in
20/25 mm dia 2 mm thick PVC surface/concealed conduit including the
cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and
filling chases for recessed conduiting and including the cost of providing
and fixing a 6 amp 240 Volt grid plate mounted switch with moulded
cover plate in 1.6 mm thick G.I box etc. complete as per specifications
and as per direction Project in-charge.
nos 110 198 21,782
0 0
2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq.
mm PVC insulated stranded copper conductor 1100 Volt grade wires in
20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost
of providing saddles etc for surface conduiting and/or cost of cutting and
filling chases for recessed conduiting etc. complete as per specifications
and as per direction of Project in-charge. (Cost of MCB shall be paid in
DB item) nos 10 119 1,189
0 0
3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated
stranded copper conductor 1100 Volt grade wires in surface/concealed
20/25 mm dia 2 mm thick PVC conduit including cost of providing
saddles etc for surface conduiting and/or cost of cutting and filling
chases for recessed conduiting etc. complete as per specification and
as per direction of Project in-charge.
nos 300 222 66,597
0 0
4 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated
stranded copper conductor 1100 volt grade wires in 20/25 mm dia 2 mm
thick PVC surface/concealed conduit including the cost of providing
circuit wiring with 3 x 2.5 sq mm PVC insulated stranded copper
conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing fan
hook box, a 6 amp 240 volt single pole grid plate mounted switch with
moulded cover plate in a recessed 1.6 mm thick G.I box with including
cost of providing stepped electronic fan regulator as required etc.
complete as per specification and as per direction of Project in-charge.
nos 168 489 82,102
0 0
5 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated
stranded copper conductor 1100 volt grade wires in 20/25 mm dia 2 mm
thick PVC surface/concealed conduit including the cost of providing
circuit wiring with 3 x 2.5 sq mm PVC insulated stranded copper
conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing 5 pin
6 amp shuttered socket outlet a 6 amp 240 volt single pole grid plate
mounted switch with moulded cover plate in a recessed 1.6 mm thick
G.I box etc. complete as per specification and as per direction of
Project in-charge.( This shall include socket and plug top near fan &
switch shall be put near entrance to toilet/kitchen)
nos 18 0 0
0 0
6 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket
outlet with 3 x 1.5 sq. mm PVC insulated stranded copper conductor
1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including the cost of providing circuit wiring
with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt
grade wires and including cost of providing saddles etc as required for
surface conduiting and/or cost of cutting and filling chases as required
and providing and fixing of a combined 5 pin 240 volt 6 amp socket
outlet with safety shutters and 6 amp 240 volt single pole grid plate
mounted switch with moulded cover plate in recessed 1.6 mm thick G.I
box etc. complete as per specification and as per direction of Project in-
charge.
nos 65 12 779
0 0
7 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket
outlets (1 outlet wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated
stranded copper conductor 1100 volt grade wires in 20/25mm dia 2 mm
thick PVC surface/concealed conduit including cost of providing saddles
etc as required for surface conduiting and/or cost of cutting and filling
chases as required and including providing and fixing of a 6 pin 240 volt
16 amp socket outlet with safety shutters and 16 amp 240 volt single
pole grid plate mounted switch with moulded cover plate in a recessed
1.6 mm thick G.I boxes etc. complete as per specification and as per
direction of Project in-charge.
nos 25 19 478
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
8 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket
outlets (2 outlets wired on 1 circuit) with PVC insulated stranded copper
conductor 1100 volt grade wires, 3 x 4.0 sq mm upto the first outlet and
3 x 4.0 sq mm from first to the second outlet, in 20/25 mm dia 2 mm
thick PVC surface/concealed conduit including cost of providing saddles
etc as required for surface conduiting and/or cost of cutting and filling
chases and including providing and fixing of two sets of 6 pin 240 volt
16 amp socket outlet with safety shutters and 16 amp 240 volt single
pole grid plate mounted switches with moulded cover plate in a
recessed 1.6 mm thick G.I box etc. complete and as per direction of
Project in-charge. nos 10 0 0
0 0
9 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/ concealed conduit including cost of providing saddles etc as
required for surface conduiting and/or cost of cutting and filling chases
as required and including providing and fixing a grid plate mounted 6
amp 240 volt Bell push with1.6 mm thick GI boxes provided with
minimum 3mm thick plastic/hylam sheets with beveled edges fitted to
the box with countersunk carmium plated screws and including the cost
of running 1.5 sq mm PVC insulated copper conductor wire for loop
earthing etc. complete as per specifications and as required, complete
as required.
nos 38 0
0 0
10 Supplying and Laying of 2 mm thick PVC conduiting system
recessed/surface including cost of providing GI fish wire saddles, Bends
(PVC), Junction Boxes (MS) etc. and/or cost of cutting and filling
chases for recessed conduiting complete with accessories as per
specifications and as per direction of Project in-charge. 59 0
0 0
a) 25 mm m 5,500 12 64,636
b) 32 mm m 20 15 298
c) 40 mm m 20 19 375
d) 50 mm m 20 22 438
0 0
11 Supplying and fixing of the following MS Conduits including the cost of
draw/junction boxes with accessories as required and including the cost
of GI fish wire etc. complete as per specifications and as per direction of
Project in-charge. 0 0
0 0
a) 25 mm dia 16 SWG m 20 32 646
b) 32 mm dia 16 SWG m 20 38 750
c) 38 mm dia 14 SWG m 20 44 872
d) 50 mm dia 14 SWG m 20 58 1,166
0 0
TOTAL SUB-HEAD I carried over to Summary 0 242,111
0 0
0 0
Note: The rate shall include the following 0 0
0 0
a) All junction boxes shall be covered with PVC cover. 0 0
b) All fan boxes shall be covered with 3 mm thick hylum sheet 0 0
c) All lights/ceiling fans / exhaust fans points shall be terminated
with PVC connectors. 0 0
0 0
0 0
SUB HEAD II - LOW TENSION SYSTEM 0 0
0 0
1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned
electrolytic copper conductor PVC insulated unshielded twisted wire in
25 mm dia PVC surface/concealed conduit upto central point and
including cost of providing saddles etc for surface conduiting and/or cost
of cutting and filling chases for recessed conduiting and including the
cost of providing and fixing of a single telephone cord grid plate
mounted outlet unit (RJ-11) with moulded cover plate in recessed 1.6
mm thick GI box complete as required for telephone/intercom system..
nos 10 198 1,980
0 0
2 Supply and fixing of the following sheet steel clad wall/recess/floor
mounting telephone tag block of Krone make constructed from 14 SWG
sheet steel, finished with powder coated paint, with hinged gasketted
door and complete with adequately rated and sized telephone terminal
block to receive incoming and outgoing wires. The cost shall be
complete with fixing arrangements, foundations etc as required
304 0
0 0
a) 5/10 Pair nos 2 0 0
b) 20 Pair nos 0 0
c) 50 Pair nos 0 0
d) 400 Pair nos 57 0
0 0
3 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in
ground including the cost of digging and back filling with sand and brick
protection as required and testing and commissioning of the following
multi core 0.61 mm annealed tinned copper conductor PVC insulated
and PVC sheathed and overall PVC sheathed armoured telephone
cables including making terminal joints, complete as per specification
and /or as per direction of Project in-charge. 9 0
0 0
a) 50 pair m 15 423 6,342
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
0 0
4 Supply and fixing of co-axial outlets for TV with moulded cover plate in
recessed 1.6 mm thick GI boxes, including termination complete in all
respects as per specification and / or as per direction of Project in-
charge.. nos 2 29 58
0 0
5 Supply and laying of coaxial cable RG-59 for Branch line in existing
surface/concealed conduits upto the central point complete in all
respects as per specification and / or as per direction of Project in-
charge.
m 250 9 2,147
0 0
6 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV
in MS enclosure with 3 mm thick hylum sheet cover as required at site
and /or as per direction of Project in-charge. nos 1 259 259
0 0
7 Supply, erection and commissioning of 6 way tap off in MS enclosures
with 3 mm thick hylum sheet cover for cable TV as required at site and
/or as per direction of Project in-charge.. nos 1 414 414
0 0
8 Steel work welded in built up sections/ framed work including cutting,
fixing in position with fasteners and applying a priming coat of primer
and two coats of approved synthetic enamel paint. 0 0
0 0
a) In grating, frames, ladders, brackets, similar works kgs 5 28 142
0 0
TOTAL SUB-HEAD II carried over to Summary 0 11,343
0 0
0 0
SUB HEAD III - SUBMAINS AND CABLES 0 0
0 0
1 Wiring for Submains with PVC insulated stranded copper conductor
1100 volt grade wires in surface/concealed conduit including cost of
providing saddles, Bends (PVC), Junction Boxes (MS) etc as required
and/or the cost of cutting and filling chases as required and including
cost of PVC insulated copper wires and making suitable end
connections complete in all respects as per specification and /or as per
direction of Project in-charge.
0 0
0 0
a) 2 x 6 sq mm PVC 25 mm dia 2 mm thick conduit m 150 62 9,301
b) 2 x 10 sq mm PVC 25 mm dia 2 mm thick conduit m 20 123 2,457
c) 4 x 16 sq mm PVC 40 mm dia 2 mm thick conduit m 150 141 21,196
0 0
2 Supply and laying in cable Tray/clamped to wall with suitable clamps
saddles and bolts/ in ground including the cost of digging and back filling
with sand and brick protection as required and including testing and
commissioning of the following 1100 volt grade armoured PVC/XLPE
insulated and sheathed aluminium conductor armoured cable complete
as required. The costs shall include providing a gap of 1D between all
the cables being laid and properl clamping with cable clamps and ties.
Prices shall include providing and fixing of Identification tags for all
cables and route markers for cables in ground etc. as per specification
and or as per direction of Project in-charge.
92 0
0 0
a) 3.5 core 70 Sq mm PVCA/XLPE m 100 42 4,219
b) 4 core 25 Sq mm PVCA/XLPE m 19 0 0
c) 4 core 16 Sq mm PVCA/XLPE m 38 132 5,019
0 0
3 Providing and fixing of Cable jointing of the following XLPE cables 1100
Volt grade including cost of tinned copper heavy duty lugs, double
compression glands, insulation tape and all requisite material for
completion of joints. 40 0
0 0
a) 3.5 core 70 Sq mm PVCA/XLPE nos 3 119 357
b) 4 core 25 Sq mm PVCA/XLPE nos 1 22 22
c) 4 core 16 Sq mm PVCA/XLPE nos 2 0 0
0 0
4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per
approved design and MS painted angle supports spaced 1000 mm
apart throughout the length as specified, including the cost of 1 meter
MS threaded rod hangers duly painted, hooks, dash fasteners etc. for
suspension from ceiling etc. as per specification and/or as per direction
of Project in-charge.
0 0
0 0
a) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and
10 mm dia MS rod hangers) m 15 0 0
0 0
5 Supply and fixing of additional length of MS rod hangers duly painted
with 2 coats of spray paint for supporting the Cable Trays, complete for
extension of the supports as in 4 above. The rate shall be
proportionately applicable to the length of rod actually required. kg 10 938 9,378
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on
both ends as per approved design of the following sizes, including cost
of providing and fixing of 15 x 30 x 15 mm MS channel supports spaced
250 mm apart throughout the length with necessary fixing arrangements
with angle iron supports etc. as per specification and /or as per direction
of Project in-charge. Rate shall include providing and applying paint 1
coat of primer and 2 coats of enamel paint for all the MS material .
2 0
0 0
a) 150 mm m 10 115 1,150
0 0
7 Supply and laying of the following RCC Hume pipe including excavation,
refilling including compaction of soil as required for cable entry including
the cost of sealing the ends as required complete
0 0
0 0
a) 150 mm dia m 37 91 3,353
0 0
8 Providing and making of manhole chamber with masonry bricks and
plastering inside with 1:3:6 and fixing of Heavy duty frame and pre cast
RCC cover as required. 0 0
0 0
a) 600 x 600 x 750 mm deep nos 2 1,101 2,201
b) 450 x 450 x 750 mm deep nos 2 919 1,839
0 0
9 Supplying and laying of following earthing GI wire in slab/wall along with
Submain pipe from meter panel to distribution boards including
connections at both end with tinned copper lugs with tinned washers
etc. as required and as per specifications. 0 0
a) 1 x 8 SWG GI wire m 2,000 2 4,068
0 0
TOTAL SUB HEAD III carried over to Summary 0 64,561
0 0
0 0
SUB HEAD IV - DISTRIBUTION SYSTEM 0 0
0 0
1 Supply, erection, testing and commissioning of the following sheet steel
clad wall recess mounting dust and vermin proof distribution boards
constructed from 18 SWG sheet steel IP 42 construction, duly powder
coated with hinged gasketted door and housing the following complete
with suitably rated PVC insulated copper busbars with interconnections
and neutral bar assembly, earthing terminals complete as approved by
Project Manager. Padlocking facility shall be provided on the door.
0 0
0 0
a) 8 WAY SPN 0 0
1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB
with thermal magnetic protective releases out goings nos 0 0
0 0
b) 4 WAY SPN 0 0
1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB
with thermal magnetic protective releases out goings nos 0 0
0 0
c) 12 WAY SPN 0 0
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases
incoming with 1-63 amp DP 30 mA ELCB incoming and 12 nos
6/16/20/25 amps SP 10 kA MCB with thermal magnetic protective
releases out goings. nos 3 2,245 6,736
0 0
d) 8 WAY TPN (per phase isolation)-Vertical DB 0 0
1-40 amp TPN 10 kA MCB with thermal magnetic protective releases
incoming with 3 single phase banks each comprising of 1-40 amp 30 mA
DP ELCB incoming and 6 no. 6/16/20/32 amps SP 10 kA MCB with
thermal magnetic protective releases out goings. nos 3 4,887 14,662
0 0
e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases
incoming with 0 0
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming
and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic
protective releases out goings 0 0
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB
incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 8 no. 6/16/20 amps SP 10
kA MCB with thermal magnetic protective releases out goings
nos 0 0
0 0
2 Design, manufacture, supplying fixing in position, testing and
commissioning of the following front operated cubicle type, front access
2mm thick steel enclosed free standing, dust and vermin proof,
switchboard with IP42 protection with hinged and lockable doors
complete with interconnections, tinned copper crimping lugs, bonding to
earth and powder coating suitable for use at 415 volts, 3 phase 4 wire
50 Hertz system, and suitable for a fault level of 25 MVA symmetrical at
415 volts. 0 0
0 0
All switchboards shall have provision for entry of cables from the top or
bottom as required. 0 0
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
All live accessible parts shall be shrouded and all equipment shall be
finger touch proof. The Busbars insulation shall be with heat shrinkable
sleeves. SMC/DMC shrouds and busbar supports shall be used.
Padlocking facility shall be provided on all outgoing feeders doors and
switch handles shall be lockable in OFF position.
0 0
0 0
The short circuit rating for MCCB's shall be Ics values 0 0
0 0
A. EWS MAIN PANEL 0 0
0 0
INCOMING 0 0
0 0
1 nos 400 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 400 amps having a maximum current density of 1.0 amp per sq
mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415
volts. The neutral busbar is to be of 50% capacity.
0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for
metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF
selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF
selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
OUTGOING UNITS 0 0
0 0
11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release
and short circuit magnetic release complete with ON/OFF indicating
lamps 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers,
internal wiring, labels etc complete as required nos 0 0
0 0
B EWS COMMON PANEL 0 0
0 0
INCOMING 0 0
0 0
2 nos 100 amp 4P Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 100 amps having a maximum current density of 1.0 amp per sq
mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415
volts. The neutral busbar is to be of 100% capacity.
0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for
metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF
selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF
selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
INTERLOCKING 0 0
0 0
The Incoming shall be interlocked such that incomers cannot be
paralleled. 0 0
0 0
OUTGOING UNITS 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers,
internal wiring, labels etc complete as required nos 0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
0 0
C NURSERY SCHOOL MAIN PANEL 0 0
0 0
INCOMING 0 0
0 0
1 nos 100 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 100 amps having a maximum current density of 1.0 amp per sq
mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415
volts. The neutral busbar is to be of 100% capacity.
0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for
metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF
selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF
selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
OUTGOING UNITS 0 0
0 0
2 nos 63 amp 10 KA TPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
6 nos 32 amp 10 KA SPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers,
internal wiring, labels etc complete as required nos 1 35,663 35,663
0 0
D PRIMARY SCHOOL MAIN PANEL 0 0
0 0
INCOMING 0 0
0 0
1 nos 125 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 200 amps having a maximum current density of 1.0 amp per sq
mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415
volts. The neutral busbar is to be of 100% capacity. 0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 200/5 ratio Class 1.0 for
metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-200 amps with 3 way and OFF
selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 200 volts with 3 way & OFF
selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
OUTGOING UNITS 0 0
0 0
2 nos 63 amp 10 KA TPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
5 nos 40 amp 10 KA TPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
2 nos 32 amp 10 KA SPN MCB with thermal magnetic protective
releases with ON indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers,
internal wiring, labels etc complete as required nos 1 42,267 42,267
0 0
E SWITCHBOARD - CLUB 0 0
0 0
INCOMING 0 0
0 0
1 nos 400 amp TPN Switch Isolator complete with 0 0
0 0
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for
metering 0 0
b) 1 no digital electronic ammeter 400 amps 0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
c) 1 no digital electronic voltmeter 500 volts 0 0
d) 1 set of three White phase indicating lamps (LED type) 0 0
e) Red / Green ON/OFF indicator (LED type) 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 600 amps having a maximum current density of 1 amp per sq
mm suitable to with stand symmetrical fault level of 25 M.V.A. at 415
volts. The neutral busbar is to be of 50% capacity.
0 0
0 0
OUTGOING UNITS 0 0
0 0
2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release
and short circuit magnetic release complete with Digital Electronic
Energy Meter with requisite CT suitable for remote data logging
0 0
0 0
12 nos 63 amp 10 kA TPN MCB with thermal magnetic release
complete with Digital Electronic Energy Meter with requisite CT suitable
for remote data logging 0 0
0 0
The Switchboard shall be complete with all interconnections, risers,
internal wiring, labels etc complete as required nos 0 0
0 0
3 Design, fabrication, assembling, wiring & supply, installation, testing &
commissioning of meter boards fabricated out of 14 gauge CRCA
painted sheet steel in cubicle formation with reinforcement of suitable
size angle iron, channels, T irons, flats wherever necessary. Cable
gland plates shall be provided at top and bottom both and windows for
meter reading, locking arrangement (pad-lock & seal) with wiring upto
KWH meter & meter to MCB shall be done by using adequately rated
flexible single core copper wire. The boards shall be treated with all
anticorrosive process before painting as per standards with final
approved shade of powder coated as approved, 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be
connected with the earthing of rising mains by 2 nos. 25 X 6 mm GI
strips. The boards shall be suitable for 415 V, 3 phase, 4 wire, 50 Hz
supply system. Boards shall be fabricated in length, height, depth etc to
match with site conditions.
0 0
0 0
The Meter Board shall be in Non-compartmentalized construction. 0 0
0 0
An approval shall be taken for each panel before manufacturing. 0 0
0 0
A SHOPPING METER BOARD 0 0
0 0
INCOMING 0 0
0 0
1 nos 100 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbar
rated at 100 amp having a maximum current density of 1 amp per sq.
mm suitable to withstand symmetrical fault level of 25 M.V.A at 415
volts .The neutral busbar is of 100% capacity. 0 0
0 0
OUTGOING UNITS 0 0
0 0
1 no 63 amp TPN 10 kA MCB with thermal magnetic protective
releases. 0 0
0 0
4 no 32 amp TPN 10 kA MCB with thermal magnetic protective
releases. 0 0
0 0
14-32 amp SPN 10 kA MCB with thermal magnetic protective releases
each with provision for fixing of 32 A DHBVNL approved Single phase
digital dual register prepaid electronic energy meter. 0 0
0 0
The switchboard shall be complete with all interconnection, riser ,
internal wiring, labels etc. complete as required.
nos 0 0
0 0
B METER BOARD -EWS 0 0
0 0
INCOMING 0 0
0 0
1 nos 100 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
Electrolytic high conductivity aluminium three phase and neutral busbar
rated at 100 amp having a maximum current density of 1 amp per sq.
mm suitable to withstand symmetrical fault level of 25 M.V.A at 415
volts .The neutral busbar is of 100% capacity.
0 0
0 0
OUTGOING UNITS 0 0
0 0
2 no 32 amp TPN 10 kA MCB with thermal magnetic protective
releases. 0 0
0 0
20-32 amp SPN 10 kA MCB with thermal magnetic protective releases
each with provision for fixing of 32 A DHBVNL approved Single phase
digital dual register prepaid electronic energy meter. 0 0
0 0
The switchboard shall be complete with all interconnection, riser ,
internal wiring, labels etc. complete as required. nos 0 0
0 0
C Design,Supply installation testing & commissioning of BIS approved
single phase dual register energy meter for recording dual electric
supply from grid and DG with kWH & kWAh max demand
communication port, billing storage facilities, control panel for sensing
supply from DG sets, data transfer & receiving hub,AMR system. DLC
with energy management software with load manager system &
recharge coupon generation software & connecting accessories for
prepaid system. 0 0
single phase dual register digital electronic prepaid energy meter ( for
tariff application) nos 0 0
0 0
TOTAL SUB HEAD IV carried over to Summary 0 99,329
0 0
SUB HEAD V : EARTHING 0 0
0 0
1 Providing and making earthpits including the cost of 600 mm x 600 mm
x 6 mm GI plate electrode 20 mm dia GI pipe, CI funnel with wiremesh
charcoal, salt, all earth work, masonry enclosure with CI frame & cover
plate having locking arrangement complete as per IS 3043:1987.
nos 4 2,245 8,982
0 0
2 Supplying and laying of the following earthing clamped to wall with
suitable clamps saddles and fixing bolts/ in ground including the cost of
digging and back filling with sand and brick protection as required and
complete as required to comply with IS 3043:1987
0 0
0 0
a) 25 mm x 6 mm GI strip m 500 26 12,909
b) 8 SWG GI Wire m 1,500 2 3,112
0 0
3 Supply and laying of the following GI pipe in ground including
excavation, refilling as required for earth strips etc. as required complete
0 0
0 0
a) 80 mm dia m 20 92 1,849
0 0
4 Providing and laying earth connections from earth electrode with 2 x 6
SWG GI wire in 25 mm dia. GI pipe from earth electrode as required as
per specifications. m 20 40 793
0 0
TOTAL SUB HEAD V carried over to Summary 0 27,645
0 0
0 0
SUB HEAD VI : FIXTURES AND FITTINGS 0 0
0 0
1a Supply of the following light fixtures complete with housing, reflectors, all
accessories i.e. copper wound ballast, HPF condensors, starters,
holders etc. complete as required 0 0
0 0
a) 1x18 W CFL recess mounting downlighter as approved including
providing lamps and other accessories (base Rate Rs 800/-) nos 60 288 17,275
b) 1x18 W CFL surface mounting downlighter as approved including
providing lamps and other accessories (base Rate Rs 600/-) nos 100 211 21,139
c) 1x28 W T5 lamp surface mounting box type fixture as approved
including providing lamps and other accessories (base Rate Rs 800/-)
nos 260 330 85,827
0 0
1b Receiving, assembling, erection, connecting, testing and commissioning
of the following light fixtures complete with housing, reflectors, all
accessories i.e. copper wound ballast, HPF condensors, starters,
holders etc. complete as required 0 0
0 0
a) 1x18 W CFL recess mounting downlighter as approved including
providing lamps and other accessories nos 60 20 1,189
b) 1x18 W CFL surface mounting downlighter as approved including
providing lamps and other accessories nos 100 20 1,982
c) 1x28 W T5 lamp surface mounting box type fixture as approved
including providing lamps and other accessories nos 260 20 5,154
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
2 Supply, fixing, testing and commissioning of 240 Volt single phase
ceiling fans of 1200 mm Sweep including supply of 19 mm heavy gauge
GI down rod of length as required complete. nos 5 462 2,311
0 0
3 Supply, fixing, testing and commissioning of 240 Volt single phase
Heavy duty Exhaust Fans 300 mm dia complete with all accessories as
required and with 6 amp 3 pin plug top as required. nos 5 476 2,378
0 0
4 Supply, fixing, testing and commissioning of 240 Volt single phase
Buzzer as required complete. nos 0 0
0 0
TOTAL SUB-HEAD VI carried over to Summary 0 137,256
0 0
0 0
SUB HEAD VII : LIGHTNING PROTECTION 0 0
0 0
1 Supply and fixing GI strip 25 mm x 6 mm along outside wall/
columns as vertical conductors with suitable GI fasteners, brass fixing
screws, copper clamps & saddles complete as required. m 25 26 645
0 0
2 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal
conductors with suitable GI fasteners, brass fixing screws, copper
clamps & saddles complete as required. m 80 26 2,065
0 0
3 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to
the GI earth plate at one end and vertical conductor strip at the other
end including the cost of digging and back filling complete
m 15 56 833
0 0
4 Providing and making earthpits including the cost of 600 mm x 600 mm
x 6 mm GI plate electrode 50 mm dia GI pipe, CI funnel with wiremesh
charcoal, salt, all earth work, masonry enclosure with CI frame & cover
plate having locking arrangement complete as per IS 3043:1987.
nos 2 2,245 4,491
0 0
5 Supplying and laying in ground of GI strip 32 mm x 6 mm for
interconnecting the various Lightning arrestor earth pits, including the
cost of digging and back filling, complete as required. m 49 36 1,751
0 0
6 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125
mm long with 4 Nos. GI bolts, nuts, check nuts and spring washers
complete as required. nos 2 51 103
0 0
7 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300
mm long GI tube having a single prong at the top with 85 mm dia 6 mm
thick GI base plate complete as required. nos 1 476 476
0 0
8 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut
Bolts supports wherever is required. nos 12 151 1,806
0 0
TOTAL SUB HEAD VII carried over to Summary 0 12,171
0 0
0 0
SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM) 0 0
0 0
0 0
1 Supply, installation, testing and commissioning of wall or ceiling
mounted 240 Volt AC illuminated Signs having on its front a white
perspex sheet with the letters 'FIRE EXIT' painted in red including the
cost of in-built rechargeable batteries suitable for 30 minute operation
and including the cost of accessories for surface or recessed or ceiling
suspended mounting complete as required. nos 0 0
0 0
2 Supply installation testing and commissioning of dust and vermin proof
Manual call boxes with push button to initiate audio visual alarm with
breakable glass cover as per detailed specifications complete with a
steel chain including the cost of accessories for surface mounted as
required nos 0 0
0 0
3 Supply installation test and commissioning of the following 8 ohm size
speaker-cum-hooter units with line matching transformer suitable for
broadcast of speech and alarm siren complete as required suitable for
recessed/surface mounting complete with enclosure as approved by
Project Manager and as required. nos 0 0
0 0
4 Supply, installation, testing and commissioning of wall recess mounting
10 zone microprocessor based Conventional Fire Control Panel with PA
amplifier and 5 potential free contacts as per detailed specifications with
alarms, controls and indications as per detailed specifications and with
an integral power supply unit and complete with a suitably rated set of
batteries and trickle charged from 240 volt AC mains supply, including
the cost of mounting accessories as required, complete.
nos 0 0
0 0
Internal Electrification BOQ for Nursery Primary School. Sl No. Description Unit QTY labour labour
5 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS
660/1100 volts grade wires in existing concealed/surface MS conduit
etc. as per specification and as required including the cost of crimped
termination's. m 0 0
0 0
6 Supply and laying control cabling with copper conductor PVC
insulated and PVC sheathed armoured Control cables in existing
pipes/conduits or on existing tray including the cost of making
connections, complete etc. etc. as per specification and as required as
below:
0 0
0 0
a) 10 core 2.5 sq mm m 0 0
TOTAL SUB-HEAD -VIII carried over to Summary -
594,415.74
PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
TENDER FOR INTERNAL ELECTRICAL WORKS
Sl
No.
Description Unit
Qty labour Labour Amount
SUB-HEAD - I (WIRING)
1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC
insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick
PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5 sq
mm PVC insulated stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing a 6 amp 240 Volt grid
plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc. complete as
per specifications and as per direction Project in-charge. nos 33,315 145 4,830,675
0 0
2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC insulated
stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including cost of providing saddles etc for surface conduiting
and/or cost of cutting and filling chases for recessed conduiting etc. complete as per
specifications and as per direction of Project in-charge. (Cost of MCB shall be paid in DB
item) nos 1,087 145 157,615
0 0
3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper
conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC
conduit including cost of providing saddles etc for surface conduiting and/or cost of cutting
and filling chases for recessed conduiting etc. complete as per specification and as per
direction of Project in-charge.
nos 6,650 125 831,250
0 0
4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded
copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm
PVC insulated stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240
Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and
including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop
earthing etc. complete as per specifications and as per direction of Project in-charge. nos 72 145 10,440
0 0
5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole
grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box
with including cost of providing stepped electronic fan regulator as required etc. complete
as per specification and as per direction of Project in-charge.
nos 8,726 145 1,265,270
0 0
6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp
240 volt single pole grid plate mounted switch with moulded cover plate in a recessed 1.6
mm thick G.I box etc. complete as per specification and as per direction of Project in-
charge.( This shall include socket and plug top near fan & switch shall be put near
entrance to toilet/kitchen) nos 5,294 145 767,630
0 0
7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x 1.5
sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia
2 mm thick PVC surface/concealed conduit including the cost of providing circuit wiring
with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade wires and
including cost of providing saddles etc as required for surface conduiting and/or cost of
cutting and filling chases as required and providing and fixing of a combined 5 pin 240 volt
6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate mounted
switch with moulded cover plate in recessed 1.6 mm thick G.I box etc. complete as per
specification and as per direction of Project in-charge.
nos 17,842 160 2,854,720
0 0
8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required
and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet
and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I
boxes with internal wiring and moulded front plates as per approved sample complete as
per specification and as per direction of Project in-charge. nos 50 114 5,700
0 0
9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet
wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100 volt
grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including cost of
providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases as required and including providing and fixing of a 6 pin 240 volt 16 amp socket
outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted switch with
moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as per
specification and as per direction of Project in-charge. nos 1,206 200 241,200
0 0
10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets
wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3
x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in 20/25
mm dia 2 mm thick PVC surface/concealed conduit including cost of providing saddles etc
as required for surface conduiting and/or cost of cutting and filling chases and including
providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with safety shutters
and 16 amp 240 volt single pole grid plate mounted switches with moulded cover plate in
a recessed 1.6 mm thick G.I box etc. complete and as per direction of Project in-charge.
1,528 200 305,600
0 0
11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket
(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt
grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second
outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of
providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket
outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches
with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per
direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket
& plug top near geyser and controlling switch at door.
nos 4,190 200 838,000
0 0
7 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing of a 6 pin 240 volt 20 amp
socket outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI
box including providing and fixing a 20 amp single pole 240 volt 20 amp switch with
moulded cover plate in recessed 1.6 mm thick G.I box located separately as per
drawings/instructions for AC controls complete as per specification and as per direction of
Project in-charge.(one outlet on one circuit)
nos 414 225 93,150
0 0
13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100
volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed
and/or surface conduiting system including the cost of cutting/making good chases in brick
work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB, industrial
type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc. complete
as per specifications and as per direction of Project in-charge. nos 5 275 1,375
0 0
14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing a grid plate mounted 6 amp
240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6 mm
thick GI box etc. complete as per specifications and as per direction of Project in-charge.
nos 1,206 135 162,810
0 0
15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including
cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost
of cutting and filling chases for recessed conduiting complete with accessories as per
specifications and as per direction of Project in-charge. 0 0
a) 25 mm m 189,000 18 3,402,000
b) 32 mm m 1,080 19 20,520
c) 40 mm m 1,080 19 20,520
d) 50 mm m 580 21 12,180
0 0
16 Supplying and fixing of the following MS Conduits including the cost of draw/junction
boxes with accessories as required and including the cost of GI fish wire etc. complete as
per specifications and as per direction of Project in-charge.
0 0
a) 25 mm dia 16 SWG m 30,080 31 932,480
b) 32 mm dia 16 SWG m 480 37 17,760
c) 38 mm dia 14 SWG m 480 43 20,640
d) 50 mm dia 14 SWG m 480 57 27,360
17 Supplying and drawing following sizes of PVC insulated copper conductor single core
stranded cables in existing surface / recessed conduits as per specifications and/or as per
direction of Project in-charge. as required.
a) 3 x 1.5 sq mm (P+N+E) m 4,500 30 135,000
b) 3 x 2.5 sq mm (P+N+E) m 3,000 25 75,000
c) 3 x 4.0 sq mm (P+N+E) m 1,600 24 38,400
d) 3 x 6.0 sq mm (P+N+E) m 400 30 12,000
0 0
18 Supply, installation, testing and commissioning of the following switches, sockets in
recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,
complete as per specifications and/or as per direction of Project in-charge. 0 0
0 0
a) 6 amp switch with box and cover plate nos 443 24 10,632
b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 24 10,632
c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 24 1,440
0 0
TOTAL SUB-HEAD - I carried over to Summary 0 17,101,999
0 0
SUB-HEAD - II (LOW TENSION SYSTEM) 0 0
0 0
1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system.. nos 5,473 145 793,585
0 0
2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system. nos 20 114 2,280
0 0
3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone tag
block of Krone make constructed from 14 SWG sheet steel, finished with powder coated
paint, with hinged gasketted door and complete with adequately rated and sized telephone
terminal block to receive incoming and outgoing wires. The cost shall be complete with
fixing arrangements, foundations etc as required 0 0
0 0
a) 10 Pair nos 13 178 2,314
b) 20 Pair nos 4 237 948
c) 30 Pair nos 8 474 3,792
d) 50 Pair nos 95 474 45,030
e) 300 Pair nos 2 3,557 7,114
f) 400 Pair nos 11 4,743 52,173
0 0
4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including
the cost of digging and back filling with sand and brick protection as required and testing
and commissioning of the following multi core 0.61 mm annealed tinned copper conductor
PVC insulated and PVC sheathed and overall PVC sheathed armoured telephone cables
including making terminal joints, complete as per specification and /or as per direction of
Project in-charge. 0 0
0 0
a) 10 Pair m 80 7 560
b) 20 Pair m 50 11 550
c) 30 Pair m 300 24 7,200
d) 50 Pair m 4,030 36 145,080
0 0
5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc
chromate passivated MS boxes, including termination complete in all respects as per
specification and / or as per direction of Project in-charge..
nos 5,367 60 322,020
0 0
6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed
conduits upto the central point complete in all respects as per specification and / or as per
direction of Project in-charge.
m 155,750 5 778,750
0 0
7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure
with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-
charge. nos 934 60 56,040
0 0
8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick
hylum sheet cover for cable TV as required at site and /or as per direction of Project in-
charge.. nos 149 237 35,313
0 0
TOTAL SUB-HEAD - II carried over to Summary 0 2,252,749
0 0
SUB-HEAD - III (SUBMAINS AND CABLES) 0 0
0 0
1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
0 0
0 0
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 24 164,400
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 53 4,293
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 65 26,325
0 0
0 0
1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
0 0
0 0
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 24 45,600
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 53 1,590,000
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 65 273,000
0 0
0 0
2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/ in
ground including the cost of digging and back filling with sand and brick protection as
required and including testing and commissioning of the following 1100 volt grade
armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable
complete as required. The costs shall include providing a gap of 1D between all the cables
being laid and properl clamping with cable clamps and ties. Prices shall include providing
and fixing of Identification tags for all cables and route markers for cables in ground etc.
as per specification and or as per direction of Project in-charge.
0 0
0 0
a) 3 -1/2 core 300 Sq mm XLPE m 1,000 36 36,000
b) 3 -1/2 core 240 Sq mm XLPE m 50 36 1,800
c) 3 -1/2 core 185 Sq mm XLPE m 100 36 3,600
d) 3 -1/2 core 70 Sq mm XLPE m 4,800 36 172,800
e) 3 -1/2 core 50 Sq mm XLPE m 600 77 46,200
f) 4 core 35 Sq mm XLPE m 100 36 3,600
g) 4 core 25 Sq mm XLPE m 200 30 6,000
h) 4 core 16 Sq mm XLPE m 1,200 24 28,800
i) 4 core 10 Sq mm XLPE m 7,000 24 168,000
j) 4 core 6 Sq mm XLPE m 100 24 2,400
k) 2 core 10 Sq mm XLPE m 1,000 24 24,000
0 0
3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade
including cost of tinned copper heavy duty lugs, double compression glands, insulation
tape and all requisite material for completion of joints.
0 0
0 0
a) 3 -1/2 core 300 Sq mm XLPE nos 40 237 9,480
b) 3 -1/2 core 240 Sq mm XLPE nos 2 237 474
c) 3 -1/2 core 185 Sq mm XLPE nos 4 177 708
d) 3 -1/2 core 70 Sq mm XLPE nos 418 60 25,080
e) 3 -1/2 core 50 Sq mm XLPE nos 26 60 1,560
f) 4 core 35 Sq mm XLPE nos 2 60 120
g) 4 core 25 Sq mm XLPE nos 4 24 96
h) 4 core 16 Sq mm XLPE nos 66 24 1,584
i) 4 core 10 Sq mm XLPE nos 248 24 5,952
j) 4 core 6 Sq mm XLPE nos 4 12 48
k) 2 core 10 Sq mm XLPE nos 50 12 600
0 0
4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and
MS painted angle supports spaced 1000 mm apart throughout the length as specified,
including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash
fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction
of Project in-charge.
0 0
0 0
a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 50 30 1,500
0 0
b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 30 3,000
0 0
c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 300 30 9,000
0 0
d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 41 4,100
0 0
0 0
5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer
and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as
in item no. 4 above. kg 1,010 21 21,210
0 0
6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per
approved design of the following sizes, including cost of providing and fixing of 15 x 30 x
15 mm MS channel supports spaced 250 mm apart throughout the length with necessary
fixing arrangements with angle iron supports etc. as per specification and /or as per
direction of Project in-charge. Rate shall include providing and applying paint 1 coat of
primer and 2 coats of enamel paint for all the MS material .
0 0
0 0
a) 900 mm m 80 280 22,400
b) 750 mm m 150 280 42,000
c) 600 mm m 150 280 42,000
d) 450 mm m 350 230 80,500
e) 300 mm m 650 230 149,500
f) 150 mm m 40 207 8,280
0 0
7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,
fixing in position with fasteners, including a priming coat of primer and two coats of
approved synthetic enamel paint.
0 0
0 0
a) In grating, frames, ladders, brackets, similar works kg 530 21 11,130
0 0
8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,
refilling including compaction of soil as required for cable entry including the cost of
sealing the ends as required complete in all respects, as per spacification and /or as per
direction of Project in-charge.
0 0
0 0
a) 150 mm dia m 680 71 48,280
b) 200 mm dia m 500 95 47,500
c) 300 mm dia m 500 142 71,000
0 0
9 Providing and making of manhole chamber with masonry bricks and plastering inside with
1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required.
0 0
0 0
a) 600 x 600 x 750 mm deep nos 34 711 24,174
b) 450 x 450 x 750 mm deep nos 34 533 18,122
0 0
TOTAL SUB-HEAD - III carried over to Summary 0 3,246,216
0 0
SUB-HEAD - IV (DISTRIBUTION SYSTEM) 0 0
0 0
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with interconnections
and neutral bar assembly, earthing terminals complete as approved by Project Manager.
Padlocking facility shall be provided on the door.
0 0
0 0
a) 12 WAY SPN 0 0
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings nos R/O 3,782
0
b) 12 WAY SPN 0
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal
magnetic protective releases out goings.
nos R/O 2,143
0
c) 6 WAY TPN (per phase isolation)-Vertical DB 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 1,639
0
d) 8 WAY TPN (per phase isolation)-Vertical DB 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 4,665
0
e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
0
0
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings
nos R/O 6,304
0 0
f) 12 WAY TPN with Timer on 2-phases-Vertial DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
0 0
0 0
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings
nos R/O 8,069
0
g) Incomer DB for Penthouses-Vertical DB 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 630
h) 8 Way VTPN 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings
nos R/O 4,665
0
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor
level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,
with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and with
2 runs of aluminium strip for earthing as required . 0
0
a) 400 amps m R/O 2,522
0
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 2,395
0
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 2,648
0 0
4 Meter Boards Tap-Off Boxes 0 0
0 0
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary
for large meter boards. Cable gland plates shall be provided at top and bottom both and
windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH
meter & meter to MCB shall be done by using adequately rated flexible single core
copper wire. The boards shall be treated with all anticorrosive process before painting as
per standards with final approved shade of powder coated as approved 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4
wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to
match with site conditions.
0 0
0 0
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards.
0 0
0 0
a) 6 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 16,389
0 0
b) 5 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 15,633
0 0
c) 4 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 13,868
0 0
d) 3 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 11,346
0
e) 2 WAY 0
0
Incomer 0
Provision for direct cable connection to busbars 0
0
Bus Bars 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0
0
Outgoings 0
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 4 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 7,564
0 0
f) 9 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 12 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 23,954
0
5 Dual Pre-Paid meter 0
0
Design,supply ,installation testing and commissioning of BIS approved single phase dual
energy meter for recording dual electric supply from grid and DG with KWH & KVAH max
demand communication port,billing,storage facilities ,control panel for sensing supply from
DG sets, data transfer & receiving hub, AMR system. DLC with energy management
software with load manager system and recharge coupon generation software &
connecting accessories for prepaid system. 0
1 phase digital electronic energy meter (for tariff application)
nos R/O 4,539
0 0
0 0
0 0
ALTERNATIVELY 0 0
0 0
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with interconnections
and neutral bar assembly, earthing terminals complete as approved by Project Manager.
Padlocking facility shall be provided on the door.
0 0
0 0
a) 12 WAY SPN 0 0
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings
nos 18 711 12,798
0 0
b) 12 WAY SPN 0 0
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal
magnetic protective releases out goings.
nos 20 711 14,220
0 0
c) 6 WAY TPN (per phase isolation)-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 1,098 900 988,200
0 0
d) 8 WAY TPN (per phase isolation)-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 5 1,200 6,000
0 0
e) 8 WAY TPN with Timer on 2-phases-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
0 0
0 0
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings
nos 35 5,547 194,145
0 0
f) 12 WAY TPN with Timer on 2-phases-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 0 0
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
0 0
0 0
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings
nos 10 1,779 17,790
0 0
g) Incomer DB for Penthouses-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings.
nos 72 949 68,328
h) 8 Way VTPN-Vertical DB 0 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings
nos 2 1,186 2,372
0 0
j) 8 WAY SPN 0 0
1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings
nos 1 593 593
0 0
k) 4 WAY SPN 0 0
1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings nos 194 474 91,956
0 0
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor
level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,
with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and with
2 runs of aluminium strip for earthing as required . 0 0
0 0
a) 400 amps m 620 896 555,520
0 0
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos 169 1,186 200,434
0 0
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos 12 1,779 21,348
0 0
4 Meter Boards Tap-Off Boxes 0 0
0 0
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary
for large meter boards. Cable gland plates shall be provided at top and bottom both and
windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH
meter & meter to MCB shall be done by using adequately rated flexible single core
copper wire. The boards shall be treated with all anticorrosive process before painting as
per standards with final approved shade of powder coated as approved 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4
wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to
match with site conditions. 0 0
0 0
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards. 0 0
0 0
a) 6 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 8
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 153 4,150 634,950
0 0
b) 5 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 8
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 6 4,150 24,900
0 0
c) 4 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 6
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 3,794 30,352
0 0
d) 3 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 6
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 4 2,964 11,856
0 0
e) 2 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 4
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 2,371 18,968
0 0
f) 9 WAY 0 0
0 0
Incomer 0 0
Provision for direct cable connection to busbars 0 0
0 0
Bus Bars 0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity. 0 0
0 0
Outgoings 0 0
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 2 9,486 18,972
0 0
5 Dual Pre-Paid meter 0 0
0 0
Design,supply ,installation testing and commissioning of BIS approved three phase 4wire
dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH
max demand communication port,billing,storage facilities ,control panel for sensing supply
from DG sets, data transfer & receiving hub, AMR system. DLC with energy management
software with load manager system and recharge coupon generation software &
connecting accessories for prepaid system.
0 0
0 0
3 phase digital electronic energy meter (for tariff application) nos 1,026 474 486,324
0 0
6 Design ,supply ,installation, testing and commissioning of required software to make the
kWH meter functional in coordination with kWH meter manufacturer and facility
mangement team for prepaid/postpaid tariff application system for dual resistor (
recording) KWH meter to effectively monitor/control the tariff as per individual site
condition complete with latest version of computer & printer etc as required. ( Integrated
with existing software installed) job 1 0 0
0 0
7 Design, manufacture, supply, installation, testing and commissioning of cubical type
electrical control panel comprising of necessary contactors.PLA relays terminals etc to
provide signaled DC supply to the dual source energy meters.( Integrated with existing
software installed) set 1 3,557 3,557
0 0
8 Design, manufacture, supplying, fixing in position, testing and commissioning of the
following rating Adopter Box for Rising Mains complete with interconnections as required.
The Adopter box shall be complete with voltmeter and ammeter with requisite CT's
0 0
0 0
a) 1-400 amp TPN switch isolator nos 24 1,897 45,528
0 0
9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface including
providing coupler, junction boxes complete as required from DG panel to all meter boards
( to get 24V DC signal to energy meter to record consumotions ON DG seperately)
0 0
0 0
a 25mm dia PVC conduit m 3,200 12 38,400
b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment
m 31,000 10 310,000
c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 12 42,000
0 0
9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing
conduit from Meter Board to freedom display units. 0 0
Three pair 0.61 mm dia (telephone wire) m 31,000 5 155,000
0 0
10 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free standing,
dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors
complete with interconnections, tinned copper crimping lugs, bonding to earth and powder
coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a
fault level of 25 MVA symmetrical at 415 volts. 0 0
All switchboards shall have provision for entry of cables from the top or bottom as
required. 0 0
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing
feeders doors and switch handles shall be lockable in OFF position.
0 0
The short circuit rating for MCCB's shall be Ics values 0 0
0 0
10.1 SWITCHBOARD - TOWER (1 TO 12) 0 0
0 0
INCOMINGS 0 0
0 0
2 nos 630 amp 4P Switch Isolator complete with 0 0
0 0
a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering 0 0
b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0
c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CTs
class 1.0 accuracy 10 VA Burden. 0 0
d) 1 set of RYB Phase indicating lamps (LED type) 0 0
e) Red / Green ON/OFF indicator (LED type) 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%
capacity.
0 0
0 0
BUS COUPLER 0 0
0 0
1 nos 630 amp 4P Switch Isolator complete 0 0
0 0
INTERLOCKING 0 0
0 0
The Incoming & Buscoupler shall be electrically & mechanically interlocked such that
incomers cannot be paralleled. 0 0
0 0
OUTGOING UNITS 0 0
0 0
LEFT HAND SECTION 0 0
0 0
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
RIGHT HAND SECTION 0 0
0 0
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 3,500 42,000
0 0
10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12) 0 0
0 0
INCOMINGS 0 0
0 0
1 no. 160 amp 4-P Changeover switch complete with 0 0
0 0
The incomers shall have the following indicating panel 0 0
0 0
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering 0 0
b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0
c) 1 set of RYB Phase indicating lamps (LED type) 0 0
d) Red / Green ON/OFF indicator (LED type) 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
0 0
0 0
OUTGOING UNITS 0 0
0 0
3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 4,743 56,916
0 0
10.3 SWITCHBOARD - BASEMENT VENTILATION 0 0
0 0
INCOMINGS 0 0
0 0
1 nos 160 amp TPN Switch Isolator complete with 0 0
0 0
The incomers shall have the following indicating panel 0 0
0 0
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering 0 0
b) 1 no AVF digital meter (Ampere,Voltage Frequency) 0 0
c) 1 set of RYB Phase indicating lamps (LED type) 0 0
d) Red / Green ON/OFF indicator (LED type) 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
0 0
0 0
OUTGOING UNITS 0 0
0 0
8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 4,743 56,916
0 0
11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter
system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries
backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,
transformers, controls, protection and instruments etc complete as required.
nos 12 7,817 93,804
0 0
12 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free standing,
dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors
complete with interconnections, tinned copper crimping lugs, bonding to earth and powder
coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a
fault level of 25 MVA symmetrical at 415 volts.
0 0
0 0
All switchboards shall have provision for entry of cables from the top or bottom as
required. 0 0
0 0
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing
feeders doors and switch handles shall be lockable in OFF position.
0 0
0 0
The short circuit rating for MCCB's shall be Ics values 0 0
0 0
A. EWS MAIN PANEL 0 0
0 0
INCOMING 0 0
0 0
1 nos 400 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity.
0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
OUTGOING UNITS 0 0
0 0
11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 37,822 37,822
0 0
B EWS COMMON PANEL 0 0
0 0
INCOMING 0 0
0 0
2 nos 100 amp 4P Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%
capacity.
0 0
0 0
INDICATING PANEL 0 0
0 0
The incomers shall have the following indicating panel 0 0
a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering 0 0
b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch 0 0
c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch 0 0
d) 1 set of three White phase indicating lamps 0 0
0 0
INTERLOCKING 0 0
0 0
The Incoming shall be interlocked such that incomers cannot be paralleled. 0 0
0 0
OUTGOING UNITS 0 0
0 0
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication. 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 4,742 4,742
0 0
E SWITCHBOARD - CLUB 0 0
0 0
INCOMING 0 0
0 0
1 nos 400 amp TPN Switch Isolator complete with 0 0
0 0
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering 0 0
b) 1 no digital electronic ammeter 400 amps 0 0
c) 1 no digital electronic voltmeter 500 volts 0 0
d) 1 set of three White phase indicating lamps (LED type) 0 0
e) Red / Green ON/OFF indicator (LED type) 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity. 0 0
0 0
OUTGOING UNITS 0 0
0 0
2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable
for remote data logging 0 0
S 0 0
12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital
Electronic Energy Meter with requisite CT suitable for remote data logging 0 0
0 0
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required
nos 1 2,371 2,371
0 0
3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever
necessary. Cable gland plates shall be provided at top and bottom both and windows for
meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &
meter to MCB shall be done by using adequately rated flexible single core copper wire.
The boards shall be treated with all anticorrosive process before painting as per
standards with final approved shade of powder coated as approved, 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for
415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height,
depth etc to match with site conditions. 0 0
0 0
The Meter Board shall be in Non-compartmentalized construction. 0 0
0 0
An approval shall be taken for each panel before manufacturing. 0 0
0 0
A SHOPPING METER BOARD 0 0
0 0
INCOMING 0 0
0 0
1 nos 100 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical
fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
0 0
0 0
OUTGOING UNITS 0 0
0 0
1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0
0 0
4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0
0 0
14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision
for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic
energy meter. 0 0
0 0
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 1 1,186 1,186
0 0
B METER BOARD -EWS 0 0
0 0
INCOMING 0 0
0 0
1 nos 100 amp TPN Switch Isolator complete with 0 0
0 0
BUSBAR 0 0
0 0
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical
fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
0 0
0 0
OUTGOING UNITS 0 0
0 0
2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases. 0 0
0 0
20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision
for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic
energy meter. 0 0
0 0
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 9 1,186 10,674
0 0
C Design,Supply installation testing & commissioning of BIS approved single phase dual
register energy meter for recording dual electric supply from grid and DG with kWH &
kWAh max demand communication port, billing storage facilities, control panel for
sensing supply from DG sets, data transfer & receiving hub,AMR system. DLC with
energy management software with load manager system & recharge coupon generation
software & connecting accessories for prepaid system. 0 0
single phase dual register digital electronic prepaid energy meter ( for tariff application)
nos 194 1,186 230,084
0 0
0 0
TOTAL SUB-HEAD - IV carried over to Summary 0 4,531,026
0 0
SUB HEAD V : EARTHING 0 0
0 0
1 Supplying and laying of the following earthing clamped to wall with suitable clamps
saddles and fixing bolts/ in ground/RCC slab along with submain conduit including the cost
of digging and back filling with sand and brick protection as required and complete as
required to comply with IS 3043:1987 0 0
0 0
a) 25 mm x 6 mm GI strip m 3,800 18 68,400
b) 8 SWG GI Wire m 102,200 2 170,688
c) 6 SWG GI Wire m 20,400 3 61,200
0 0
2 Supply and laying of the following GI pipe in ground including excavation, refilling as
required for earth strips etc. as required complete 0 0
0 0
a) 80 mm dia m 181 60 10,860
0 0
3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. nos 80 2,964 237,120
0 0
4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25
mm dia. GI pipe from earth electrode as required as per specifications. m 181 24 4,344
0 0
TOTAL SUB HEAD V carried over to Summary 0 552,612
0 0
SUB-HEAD -VI (FIXTURES AND FITTINGS) 0 0
0 0
1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.
copper wound ballast, HPF condensors, starters, holders etc. complete as required
0 0
0 0
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 800/-) nos 780 274 213,720
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 600/-) nos 3,693 201 742,293
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories (base Rate Rs 800/-) nos 790 321 253,590
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) nos 530 167 88,510
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) nos 24 139 3,336
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories (base Rate Rs 1200/-) nos 970 378 366,660
0 0
1b Receiving, assembling, erection, connecting, testing and commissioning of the following
light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,
HPF condensors, starters, holders etc. complete as required
0 0
0 0
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories nos 780 60 46,800
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories nos 3,693 60 221,580
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories nos 790 60 47,400
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories nos 530 60 31,800
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories nos 24 60 1,440
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories nos 970 60 58,200
0 0
2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200
mm Sweep including supply of 19 mm heavy gauge GI down rod of length as required
complete. nos 17 83 1,411
0 0
3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust
Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top
as required. nos 17 83 1,411
0 0
4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and
commissioning of 240 Volt single phase Buzzer as required complete. nos 1,206 60 72,360
0 0
TOTAL SUB-HEAD - VI carried over to Summary 0 2,150,511
0 0
SUB HEAD VII : LIGHTNING PROTECTION 0 0
0 0
1 Air Terminal & Accessories 0 0
Supplying, Erection & commissioning of External Lightning Wide Area Protection System
based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.
Device shall emit electromagnetic impulse in the form of a controlled emission of
streamers into the air 60 microseconds earlier than naturally formed streamers & polarise
the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE
21186 standards. The device shall be mounted at least 5 meter clear to the highest point
by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85
micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm
floor area & upto 600mm height complete as required sets 3 1,779 5,337
0 0
2 Low Impedance high voltage down conductor & accessories 0 0
Supply, installation, testing & commissioning of down conductor. The Down conductor
shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2
fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down the
elevation pole and take the shortest direct route down the outside of the building to the
earth termination network, avoiding any sharp corners, thereby providing a low impedance
path from the air terminal to its earth termination system.
m 300 12 3,600
0 0
3 Lightning Discharge Counter 0 0
Supply, installation, testing & commissioning of Lightning Discharge Counter. The
lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof
IP67 enclosure with fixing clamps, etc. sets 3 237 711
0 0
4 Maintenance Free Earthing 0 0
Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic
Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod
moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,
The earthing pit shall be provided with suitable sturdy Test Well for observation. The Earth
Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures should be
followed as instructed by the Earth Electrode Supplier)
nos 6 1,067 6,402
0 0
5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per Wipro
Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required
nos 3 1,186 3,558
0 0
6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic
ON/OFF of Aviation light as required. nos 3 119 357
0 0
7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper
conductor armoured cable from M/C room DB to aviation light. m 200 30 6,000
0 0
8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical
conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles
complete as required. m 50 12 600
0 0
9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with
suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as required.
m 200 12 2,400
0 0
10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth plate
at one end and vertical conductor strip at the other end including the cost of digging and
back filling complete m 30 18 540
0 0
11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. nos 2 2,964 5,928
0 0
12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various
Lightning arrestor earth pits, including the cost of digging and back filling, complete as
required. m 200 18 3,600
0 0
13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4
Nos. GI bolts, nuts, check nuts and spring washers complete as required. nos 2 12 24
0 0
14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube
having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as
required. nos 1 119 119
0 0
15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports
wherever is required. nos 30 119 3,570
0 0
0 0
TOTAL SUB-HEAD - VII carried over to Summary 0 42,746
0 0
SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM)
0 0
0 0
1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC
illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'
painted in red including the cost of in-built rechargeable batteries suitable for 30 minute
operation and including the cost of accessories for surface or recessed or ceiling
suspended mounting complete as required. nos 514 42 21,588
0 0
2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes
with push button to initiate audio visual alarm with breakable glass cover as per detailed
specifications complete with a steel chain including the cost of accessories for surface
mounted as required nos 514 42 21,588
0 0 0
3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-
hooter units with line matching transformer suitable for broadcast of speech and alarm
siren complete as required suitable for recessed/surface mounting complete with
enclosure as approved by Project Manager and as required.
nos 211 42 8,862
0 0
4 Supply, installation, testing and commissioning of wall recess mounting 24 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete. nos 10 2,371 23,710
0 0
4 Supply, installation, testing and commissioning of wall recess mounting 16 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete.
nos 2 2,371 4,742
0 0
5 Supply, installation, testing and commissioning of wall recess mounting 15 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete.
nos 1 2,371 2,371
0 0
6 Supply, installation, testing and commissioning of wall recess mounting 10 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete. nos 1 2,371 2,371
0 0
7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade
wires in existing concealed/surface MS conduit etc. as per specification and as required
including the cost of crimped termination's.
m 36,500 12 438,000
0 0
8 Supply and laying control cabling with copper conductor PVC insulated and PVC
sheathed armoured Control cables in existing pipes/conduits or on existing tray including
the cost of making connections, complete etc. etc. as per specification and as required as
below: 0 0
0 0
a) 10 core 2.5 sq mm m 5,100 36 183,600
TOTAL SUB-HEAD -VIII carried over to Summary 706,832
Total
30,584,691.31
PART - A -- INTERNAL ELECTRICAL WORK FOR TOWERS, BASEMENTS, EWS, CLUB & SHOPPING COMPLEX
PALM GARDEN GROUP HOUSING AT SECTOR 83, GURGAON
TENDER FOR INTERNAL ELECTRICAL WORKS
Sl
No.
Description Unit
Qty labour Labour Amount
SUB-HEAD - I (WIRING)
1 Wiring for primary light points for switch controlled points with 3 x 1.5 sq. mm PVC
insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick
PVC surface/concealed conduit including the cost of providing circuit wiring with 3 x 2.5 sq
mm PVC insulated stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing a 6 amp 240 Volt grid
plate mounted switch with moulded cover plate in 1.6 mm thick G.I box etc. complete as
per specifications and as per direction Project in-charge.
nos 33,315 109 3,623,006
2 Wiring for primary light points for MCB controlled points with 3 x 2.5 sq. mm PVC insulated
stranded copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including cost of providing saddles etc for surface conduiting
and/or cost of cutting and filling chases for recessed conduiting etc. complete as per
specifications and as per direction of Project in-charge. (Cost of MCB shall be paid in DB
item) nos 1,087 109 118,211
3 Wiring for secondary light points with 3x1.5 sq. mm PVC insulated stranded copper
conductor 1100 Volt grade wires in surface/concealed 20/25 mm dia 2 mm thick PVC
conduit including cost of providing saddles etc for surface conduiting and/or cost of cutting
and filling chases for recessed conduiting etc. complete as per specification and as per
direction of Project in-charge. nos 6,650 94 623,438
4 Wiring for Two-way light points switch controlled with 1.5 sq. mm PVC insulated stranded
copper conductor 1100 Volt grade wires in 20/25 mm dia 2 mm thick PVC
surface/concealed conduit including the cost of providing circuit wiring with 2.5 sq mm
PVC insulated stranded copper conductor 1100 volt grade wires and including cost of
providing saddles etc for surface conduiting and/or cost of cutting and filling chases for
recessed conduiting and including the cost of providing and fixing two sets of 6 amp 240
Volt grid plate mounted switch with moulded cover plate in 1.6 mm thick G.I box and
including the cost of running 1.5 sq mm PVC insulated copper conductor wire for loop
earthing etc. complete as per specifications and as per direction of Project in-charge.
nos 72 109 7,830
5 Wiring for Ceiling/bracket fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing fan hook box, a 6 amp 240 volt single pole
grid plate mounted switch with moulded cover plate in a recessed 1.6 mm thick G.I box
with including cost of providing stepped electronic fan regulator as required etc. complete
as per specification and as per direction of Project in-charge.
nos 8,726 109 948,953
6 Wiring for Exhaust fan points with 3 x 1.5 sq. mm PVC insulated stranded copper
conductor 1100 volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed
conduit including the cost of providing circuit wiring with 3 x 2.5 sq mm PVC insulated
stranded copper conductor 1100 volt grade wires and including cost of providing saddles
etc for surface conduiting and/or cost of cutting and filling chases for recessed conduiting
and including the cost of providing and fixing 5 pin 6 amp shuttered socket outlet a 6 amp
240 volt single pole grid plate mounted switch with moulded cover plate in a recessed 1.6
mm thick G.I box etc. complete as per specification and as per direction of Project in-
charge.( This shall include socket and plug top near fan & switch shall be put near
entrance to toilet/kitchen) nos 5,294 109 575,723
7 Wiring for a 5 pin 240 volt 6 amp single phase and neutral switch socket outlet with 3 x 1.5
sq. mm PVC insulated stranded copper conductor 1100 Volt grade wires in 20/25 mm dia
2 mm thick PVC surface/concealed conduit including the cost of providing circuit wiring
with 3 x 2.5 sq mm PVC insulated stranded copper conductor 1100 volt grade wires and
including cost of providing saddles etc as required for surface conduiting and/or cost of
cutting and filling chases as required and providing and fixing of a combined 5 pin 240 volt
6 amp socket outlet with safety shutters and 6 amp 240 volt single pole grid plate mounted
switch with moulded cover plate in recessed 1.6 mm thick G.I box etc. complete as per
specification and as per direction of Project in-charge.
nos 17,842 120 2,141,040
8 Wiring as in Item 7 above looped from an adjacent 6 amp switch socket outlet as required
and providing and fixing of a modular type 5 pin 240 Volt 6 amp shuttered socket outlet
and a modular type 6 amp 240 Volt single pole switch in a recessed 1.6 mm thick G.I
boxes with internal wiring and moulded front plates as per approved sample complete as
per specification and as per direction of Project in-charge.
nos 50 86 4,275
9 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (1 outlet
wired on 1 circuit) with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100 volt
grade wires in 20/25mm dia 2 mm thick PVC surface/concealed conduit including cost of
providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases as required and including providing and fixing of a 6 pin 240 volt 16 amp socket
outlet with safety shutters and 16 amp 240 volt single pole grid plate mounted switch with
moulded cover plate in a recessed 1.6 mm thick G.I boxes etc. complete as per
specification and as per direction of Project in-charge.
nos 1,206 150 180,900
10 Wiring for 6 pin 240 volt 16 amp single phase and neutral switch socket outlets (2 outlets
wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt grade wires, 3
x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second outlet, in 20/25
mm dia 2 mm thick PVC surface/concealed conduit including cost of providing saddles etc
as required for surface conduiting and/or cost of cutting and filling chases and including
providing and fixing of two sets of 6 pin 240 volt 16 amp socket outlet with safety shutters
and 16 amp 240 volt single pole grid plate mounted switches with moulded cover plate in a
recessed 1.6 mm thick G.I box etc. complete and as per direction of Project in-charge.
1,528 150 229,200
11 Wiring for 2 nos 6 pin 240 volt 20/20 amp looped single phase and neutral switch socket
(2 outlets wired on 1 circuit) with PVC insulated stranded copper conductor 1100 volt
grade wires, 3 x 4.0 sq mm upto the first outlet and 3 x 4.0 sq mm from first to the second
outlet, in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost of
providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases and including providing and fixing of two sets of 6 pin 240 volt 20 amp socket
outlet with safety shutters and 20 amp 240 volt single pole grid plate mounted switches
with moulded cover plate in a recessed 1.6 mm thick G.I box etc. complete and as per
direction of Project in-charge.(Ist point for A/C & IInd for geyser)This shall include socket
& plug top near geyser and controlling switch at door.
nos 4,190 150 628,500
7 Wiring for AC points with 3 x 4.0 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/concealed conduit including cost
of providing saddles etc as required for surface conduiting and/or cost of cutting and filling
chases as required and including providing and fixing of a 6 pin 240 volt 20 amp socket
outlet with safety shutters with moulded cover plate in recessed 1.6 mm thick GI box
including providing and fixing a 20 amp single pole 240 volt 20 amp switch with moulded
cover plate in recessed 1.6 mm thick G.I box located separately as per
drawings/instructions for AC controls complete as per specification and as per direction of
Project in-charge.(one outlet on one circuit) nos 414 169 69,863
13 Point wiring for 20 amp single phase socket outlets with 3 x 4 sq mm PVC insulated 1100
volt grade stranded copper conductor wires in 20/25 mm dia 2 mm thick PVC recessed
and/or surface conduiting system including the cost of cutting/making good chases in brick
work and including the cost of supplying and fixing 20/25 amp 10 kA SP MCB, industrial
type metal clad outlet in recessed 1.6 mm thick G.I box, metal clad plug top etc. complete
as per specifications and as per direction of Project in-charge.
nos 5 206 1,031
14 Wiring for bell push with 3 x 1.5 sq. mm PVC insulated stranded copper conductor 1100
volt grade wires in 20/25 mm dia 2 mm thick PVC surface/ concealed conduit including
cost of providing saddles etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing a grid plate mounted 6 amp
240 volt Bell push with moulded cover plate in recessed zinc chromate passivated 1.6 mm
thick GI box etc. complete as per specifications and as per direction of Project in-charge.
nos 1,206 101 122,108
15 Supplying and Laying of 2 mm thick PVC conduiting system recessed/surface including
cost of providing GI fish wire saddles, Bends (PVC), Junction Boxes (MS) etc. and/or cost
of cutting and filling chases for recessed conduiting complete with accessories as per
specifications and as per direction of Project in-charge.
a) 25 mm m 189,000 14 2,551,500
b) 32 mm m 1,080 14 15,390
c) 40 mm m 1,080 14 15,390
d) 50 mm m 580 16 9,135
16 Supplying and fixing of the following MS Conduits including the cost of draw/junction boxes
with accessories as required and including the cost of GI fish wire etc. complete as per
specifications and as per direction of Project in-charge.
a) 25 mm dia 16 SWG m 30,080 23 699,360
b) 32 mm dia 16 SWG m 480 28 13,320
c) 38 mm dia 14 SWG m 480 32 15,480
d) 50 mm dia 14 SWG m 480 43 20,520
17 Supplying and drawing following sizes of PVC insulated copper conductor single core
stranded cables in existing surface / recessed conduits as per specifications and/or as per
direction of Project in-charge. as required.
a) 3 x 1.5 sq mm (P+N+E) m 4,500 23 101,250
b) 3 x 2.5 sq mm (P+N+E) m 3,000 19 56,250
c) 3 x 4.0 sq mm (P+N+E) m 1,600 18 28,800
d) 3 x 6.0 sq mm (P+N+E) m 400 23 9,000
18 Supply, installation, testing and commissioning of the following switches, sockets in
recessed 1.6 mm thick GI box with moulded cover plate, including internal connections,
complete as per specifications and/or as per direction of Project in-charge.
a) 6 amp switch with box and cover plate nos 443 18 7,974
b) 6 amp switch and 5 pin socket outlet with box and cover plate nos 443 18 7,974
c) 16 amp switch and 6 pin socket outlet with box and cover plate nos 60 18 1,080
TOTAL SUB-HEAD - I carried over to Summary 12,826,499
SUB-HEAD - II (LOW TENSION SYSTEM)
1 Wiring for telephone points with 4 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc for
surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system.. nos 5,473 109 595,189
2 Wiring for telephone points with 2 pair 0.61 mm annealed tinned electrolytic copper
conductor PVC insulated unshielded twisted wire in 25 mm dia 2 mm thick PVC
surface/concealed conduit upto central point and including cost of providing saddles etc for
surface conduiting and/or cost of cutting and filling chases for recessed conduiting and
including the cost of providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed 1.6 mm thick GI box complete as
required for telephone/intercom system. nos 20 86 1,710
3 Supply and fixing of the following sheet steel clad wall/recess/floor mounting telephone tag
block of Krone make constructed from 14 SWG sheet steel, finished with powder coated
paint, with hinged gasketted door and complete with adequately rated and sized telephone
terminal block to receive incoming and outgoing wires. The cost shall be complete with
fixing arrangements, foundations etc as required
a) 10 Pair nos 13 134 1,736
b) 20 Pair nos 4 178 711
c) 30 Pair nos 8 356 2,844
d) 50 Pair nos 95 356 33,773
e) 300 Pair nos 2 2,668 5,336
f) 400 Pair nos 11 3,557 39,130
4 Supply, laying clamped to wall with suitable clamps saddles and bolts/ in ground including
the cost of digging and back filling with sand and brick protection as required and testing
and commissioning of the following multi core 0.61 mm annealed tinned copper conductor
PVC insulated and PVC sheathed and overall PVC sheathed armoured telephone cables
including making terminal joints, complete as per specification and /or as per direction of
Project in-charge.
a) 10 Pair m 80 5 420
b) 20 Pair m 50 8 413
c) 30 Pair m 300 18 5,400
d) 50 Pair m 4,030 27 108,810
5 Supply and fixing of co-axial outlets for TV with moulded cover plate in recessed zinc
chromate passivated MS boxes, including termination complete in all respects as per
specification and / or as per direction of Project in-charge.. nos 5,367 45 241,515
6 Supply and laying of coaxial cable RG-59 for Branch line in existing surface/concealed
conduits upto the central point complete in all respects as per specification and / or as per
direction of Project in-charge. m 155,750 4 584,063
7 Supply, erection and commissioning of 3 way / 4 way spliter for cable TV in MS enclosure
with 3 mm thick hylum sheet cover as required at site and /or as per direction of Project in-
charge. nos 934 45 42,030
8 Supply, erection and commissioning of 6 way tap off in MS enclosures with 3 mm thick
hylum sheet cover for cable TV as required at site and /or as per direction of Project in-
charge.. nos 149 178 26,485
TOTAL SUB-HEAD - II carried over to Summary 1,689,562
SUB-HEAD - III (SUBMAINS AND CABLES)
1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 6,850 18 123,300
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 81 40 3,220
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 405 49 19,744
1.1 Wiring for Submains with PVC insulated stranded copper conductor 1100 volt grade wires
in surface/concealed conduit including cost of providing saddles, Bends (PVC), Junction
Boxes (MS) etc including the cost of cutting and filling chases as required and as per
specification and as per direction of Project in-charge.
a) 2 x 10 sq mm in PVC 25 mm dia 2 mm thick conduit m 1,900 18 34,200
b) 4 x 10 sq mm in PVC 32 mm dia 2 mm thick conduit m 30,000 40 1,192,500
c) 4 x 16 sq mm in PVC 40 mm dia 2 mm thick conduit m 4,200 49 204,750
2 Supply and laying in cable Tray/clamped to wall with suitable clamps saddles and bolts/ in
ground including the cost of digging and back filling with sand and brick protection as
required and including testing and commissioning of the following 1100 volt grade
armoured PVC/XLPE insulated and sheathed aluminium conductor armoured cable
complete as required. The costs shall include providing a gap of 1D between all the cables
being laid and properl clamping with cable clamps and ties. Prices shall include providing
and fixing of Identification tags for all cables and route markers for cables in ground etc.
as per specification and or as per direction of Project in-charge.

a) 3 -1/2 core 300 Sq mm XLPE m 1,000 27 27,000
b) 3 -1/2 core 240 Sq mm XLPE m 50 27 1,350
c) 3 -1/2 core 185 Sq mm XLPE m 100 27 2,700
d) 3 -1/2 core 70 Sq mm XLPE m 4,800 27 129,600
e) 3 -1/2 core 50 Sq mm XLPE m 600 58 34,650
f) 4 core 35 Sq mm XLPE m 100 27 2,700
g) 4 core 25 Sq mm XLPE m 200 23 4,500
h) 4 core 16 Sq mm XLPE m 1,200 18 21,600
i) 4 core 10 Sq mm XLPE m 7,000 18 126,000
j) 4 core 6 Sq mm XLPE m 100 18 1,800
k) 2 core 10 Sq mm XLPE m 1,000 18 18,000
3 Providing and fixing of Cable jointing of the following XLPE cables 1100 Volt grade
including cost of tinned copper heavy duty lugs, double compression glands, insulation
tape and all requisite material for completion of joints.
a) 3 -1/2 core 300 Sq mm XLPE nos 40 178 7,110
b) 3 -1/2 core 240 Sq mm XLPE nos 2 178 356
c) 3 -1/2 core 185 Sq mm XLPE nos 4 133 531
d) 3 -1/2 core 70 Sq mm XLPE nos 418 45 18,810
e) 3 -1/2 core 50 Sq mm XLPE nos 26 45 1,170
f) 4 core 35 Sq mm XLPE nos 2 45 90
g) 4 core 25 Sq mm XLPE nos 4 18 72
h) 4 core 16 Sq mm XLPE nos 66 18 1,188
i) 4 core 10 Sq mm XLPE nos 248 18 4,464
j) 4 core 6 Sq mm XLPE nos 4 9 36
k) 2 core 10 Sq mm XLPE nos 50 9 450
4 Supply and fixing of 14 SWG sheet steel slotted cable trays as per approved design and
MS painted angle supports spaced 1000 mm apart throughout the length as specified,
including the cost of 1 meter MS threaded rod hangers duly painted, hooks, dash
fasteners etc. for suspension from ceiling etc. as per specification and/or as per direction
of Project in-charge.
a) 150 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 50 23 1,125
b) 300 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 23 2,250
c) 450 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 300 23 6,750
d) 600 mm x 50 mm x 50 mm (with 40 x 40 x 6 mm MS angle supports and 10 mm dia MS
rod hangers) m 100 31 3,075
5 Supply and fixing of additional length of MS rod hangers duly painted with 1 coat of primer
and 2 coats enamel paint for supporting the Cable Trays for extension of the supports as
in item no. 4 above. kg 1,010 16 15,908
6 Supply and fixing Ladder type cable trays with 100 mm vertical sides on both ends as per
approved design of the following sizes, including cost of providing and fixing of 15 x 30 x
15 mm MS channel supports spaced 250 mm apart throughout the length with necessary
fixing arrangements with angle iron supports etc. as per specification and /or as per
direction of Project in-charge. Rate shall include providing and applying paint 1 coat of
primer and 2 coats of enamel paint for all the MS material .
a) 900 mm m 80 210 16,800
b) 750 mm m 150 210 31,500
c) 600 mm m 150 210 31,500
d) 450 mm m 350 173 60,375
e) 300 mm m 650 173 112,125
f) 150 mm m 40 155 6,210
7 Providing and fixing Steel work welded in built up sections/ framed work including cutting,
fixing in position with fasteners, including a priming coat of primer and two coats of
approved synthetic enamel paint.
a) In grating, frames, ladders, brackets, similar works kg 530 16 8,348
8 Supply and laying of the following RCC Hume pipe NP-2 grade including excavation,
refilling including compaction of soil as required for cable entry including the cost of sealing
the ends as required complete in all respects, as per spacification and /or as per direction
of Project in-charge.
a) 150 mm dia m 680 53 36,210
b) 200 mm dia m 500 71 35,625
c) 300 mm dia m 500 107 53,250
9 Providing and making of manhole chamber with masonry bricks and plastering inside with
1:3:6 and fixing of Heavy duty frame and pre cast RCC cover as required.
a) 600 x 600 x 750 mm deep nos 34 533 18,131
b) 450 x 450 x 750 mm deep nos 34 400 13,592
TOTAL SUB-HEAD - III carried over to Summary 2,434,662

SUB-HEAD - IV (DISTRIBUTION SYSTEM)
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with interconnections
and neutral bar assembly, earthing terminals complete as approved by Project Manager.
Padlocking facility shall be provided on the door.
a) 12 WAY SPN
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings nos R/O 2,837 0
b) 12 WAY SPN
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal
magnetic protective releases out goings. nos R/O 1,607 0
c) 6 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 1,229 #VALUE!
d) 8 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 3,499 #VALUE!
e) 8 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings nos R/O 4,728 0
f) 12 WAY TPN with Timer on 2-phases-Vertial DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings nos R/O 6,052 0
g) Incomer DB for Penthouses-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp SPN 10 kA MCB with thermal magnetic protective releases out goings.
nos R/O 473 0
h) 8 Way VTPN
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos R/O 3,499 0
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor
level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,
with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and with
2 runs of aluminium strip for earthing as required .
a) 400 amps m R/O 1,892 0
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 1,796 0
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos R/O 1,986 0
4 Meter Boards Tap-Off Boxes
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary
for large meter boards. Cable gland plates shall be provided at top and bottom both and
windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH
meter & meter to MCB shall be done by using adequately rated flexible single core
copper wire. The boards shall be treated with all anticorrosive process before painting as
per standards with final approved shade of powder coated as approved 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4
wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to
match with site conditions.
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards.
a) 6 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 12,292 0
b) 5 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 8 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 11,725
c) 4 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 10,401
d) 3 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 6 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 8,510
e) 2 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 4 way terminal
block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 5,673
f) 9 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) SPN MCB and
provision for fixing of 63 Amp DHBVN approved 0-40 amp Single phase dual register
electronic energy meter (projection mounted & for tariff application) for recording dual
electric supply from grid and DG complete with control and internal wiring for the same.
Dual meter shall also have facility for pre-paid measurement complete with 12 way
terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos R/O 17,966
5 Dual Pre-Paid meter
Design,supply ,installation testing and commissioning of BIS approved single phase dual
energy meter for recording dual electric supply from grid and DG with KWH & KVAH max
demand communication port,billing,storage facilities ,control panel for sensing supply from
DG sets, data transfer & receiving hub, AMR system. DLC with energy management
software with load manager system and recharge coupon generation software &
connecting accessories for prepaid system.
1 phase digital electronic energy meter (for tariff application) nos R/O 3,404
ALTERNATIVELY
1 Supply, erection, testing and commissioning of the following sheet steel clad wall recess
mounting dust and vermin proof distribution boards constructed from 18 SWG sheet steel
IP 42 construction, duly powder coated with hinged gasketted door and housing the
following complete with suitably rated PVC insulated copper busbars with interconnections
and neutral bar assembly, earthing terminals complete as approved by Project Manager.
Padlocking facility shall be provided on the door.
a) 12 WAY SPN
1-40 amp DP MCB incoming with 32 amp ON position latched contactor and 24 hours
programe timer for operation of incoming and 12 no. 6/16/20 amps SP 10 kA MCB with
thermal magnetic protective releases out goings nos 18 533 9,599
b) 12 WAY SPN
1-63 amp SPN 10 kA MCB with thermal magnetic protective releases incoming with 1-63
amp DP 30 mA ELCB incoming and 12 nos 6/16/20/25 amps SP 10 kA MCB with thermal
magnetic protective releases out goings. nos 20 533 10,665
c) 6 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 6 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 1,098 675 741,150
d) 8 WAY TPN (per phase isolation)-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 3
single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming and 8 no.
6/16/20/32 amps SP 10 kA MCB with thermal magnetic protective releases out goings.
nos 5 900 4,500
e) 8 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1-63 amp30 mA DP ELCB incoming and 8 no. 6/16/20
amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 8 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings nos 35 4,160 145,609
f) 12 WAY TPN with Timer on 2-phases-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with
1 single phase bank comprising of 1- 63 amp 30 mA DP ELCB incoming and 12 no.
6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out goings
2 single phase banks each comprising of 1-63 amp 30 mA DP ELCB incoming with 32
amp ON position latched contactor and 24 hours programe timer for operation of incoming
and 12 no. 6/16/20 amps SP 10 kA MCB with thermal magnetic protective releases out
goings nos 10 1,334 13,343
g) Incomer DB for Penthouses-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 2 nos
63 amp TPN 10 kA MCB with thermal magnetic protective releases out goings.
nos 72 712 51,246
h) 8 Way VTPN-Vertical DB
1-63 amp TPN 10 kA MCB with thermal magnetic protective releases incoming with 8 nos
6-32 amp 10 kA TP MCB with thermal magnetic protective releases out goings nos 2 890 1,779
j) 8 WAY SPN
1-32 amp SPN MCB incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings nos 1 445 445
k) 4 WAY SPN
1-32 amp SPN MCB incoming and 4 nos 6/16/20 amps SP 10 kA MCB with thermal
magnetic protective releases out goings nos 194 356 68,967
2 Design, manufacture, supplying, fixing, testing and commissioning of the following 2 mm
thick sheet steel enclosed, wall mounting, dust and vermin proof with IP 42 protection
triple pole and with 100% neutral Rising Mains with PVC insulated aluminium busbars
with a maximum current density of 1.0 amp per sq mm and suitable to withstand a
symmetrical fault level of 45 kA at 415 volts, complete with fire proof barriers at every floor
level, expansion joints, thrust pads to support weight of busbars, fully gasketed covers,
with arrangement to plug in tap off boxes as required and connecting chamber for
incoming isolator, powder coating, complete with fixing arrangements as required and with
2 runs of aluminium strip for earthing as required .
a) 400 amps m 620 672 416,640
3a Supplying, erection, testing and commissioning of Tap-Off Boxes with 125 amp TPN
MCCB (25 kA) and cable end boxes as required nos 169 890 150,326
3b Supplying, erection, testing and commissioning of Tap-Off Boxes with 160 amp TPN
MCCB (25 kA) and cable end boxes as required nos 12 1,334 16,011
4 Meter Boards Tap-Off Boxes
Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever necessary
for large meter boards. Cable gland plates shall be provided at top and bottom both and
windows for meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH
meter & meter to MCB shall be done by using adequately rated flexible single core
copper wire. The boards shall be treated with all anticorrosive process before painting as
per standards with final approved shade of powder coated as approved 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for 415 V, 3 phase, 4
wire, 50 Hz supply system. Boards shall be fabricated in length, height, depth etc to
match with site conditions.
An approval shall be taken for each panel before manufacturing. Galvanised hardwares
with zinc passivation shall be used in fabrication of boards.
a) 6 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
6 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 6 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 8
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 153 3,113 476,213
b) 5 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
5 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 5 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 8
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 6 3,113 18,675
c) 4 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
4 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 4 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 6
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 2,846 22,764
d) 3 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
3 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 3 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 6
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 4 2,223 8,892
e) 2 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 150
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
2 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 2 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with 4
way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 8 1,778 14,226
f) 9 WAY
Incomer
Provision for direct cable connection to busbars
Bus Bars
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%
capacity.
Outgoings
9 nos meter chambers each of size 350mm x 350 mm having 6 mm thick bakelite sheet
sealing & locking arrangement complete with supply of 9 nos 63A(10kA) FP MCB and
provision for fixing of 63 Amp DHBVN approved three phase 4 wire unbalanced load
digital electronic dual KWH enegy meters (projection mounted & for tariff application) for
recording dual electric supply from grid and DG complete with control and internal wiring
for the same. Dual meter shall also have facility for pre-paid measurement complete with
12 way terminal block to connect 2 x 2.5 sq.mm control wire including control wiring.
nos 2 7,115 14,229
5 Dual Pre-Paid meter
Design,supply ,installation testing and commissioning of BIS approved three phase 4wire
dual energy meter for recording dual electric supply from grid and DG with KWH & KVAH
max demand communication port,billing,storage facilities ,control panel for sensing supply
from DG sets, data transfer & receiving hub, AMR system. DLC with energy management
software with load manager system and recharge coupon generation software &
connecting accessories for prepaid system.
3 phase digital electronic energy meter (for tariff application) nos 1,026 356 364,743
6 Design ,supply ,installation, testing and commissioning of required software to make the
kWH meter functional in coordination with kWH meter manufacturer and facility
mangement team for prepaid/postpaid tariff application system for dual resistor (
recording) KWH meter to effectively monitor/control the tariff as per individual site
condition complete with latest version of computer & printer etc as required. ( Integrated
with existing software installed) job 1
7 Design, manufacture, supply, installation, testing and commissioning of cubical type
electrical control panel comprising of necessary contactors.PLA relays terminals etc to
provide signaled DC supply to the dual source energy meters.( Integrated with existing
software installed) set 1 2,668 2,668
8 Design, manufacture, supplying, fixing in position, testing and commissioning of the
following rating Adopter Box for Rising Mains complete with interconnections as required.
The Adopter box shall be complete with voltmeter and ammeter with requisite CT's
a) 1-400 amp TPN switch isolator nos 24 1,423 34,146
9 Supplying and laying of following sizes 2 mm thick PVC conduit in recess/surface including
providing coupler, junction boxes complete as required from DG panel to all meter boards
( to get 24V DC signal to energy meter to record consumotions ON DG seperately)
a 25mm dia PVC conduit m 3,200 9 28,800
b 20 mm dia 2 mm thick PVC conduit from meter board to display unit in the apartment
m 31,000 8 232,500
c Supplying and laying of 2 x 2.5sq.mm PVC insulated copper wire m 3,500 9 31,500
9.1 Supplying and laying of 0.61 mm dia PVC insulated copper conductor wires in existing
conduit from Meter Board to freedom display units.
Three pair 0.61 mm dia (telephone wire) m 31,000 4 116,250
10 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free standing,
dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors
complete with interconnections, tinned copper crimping lugs, bonding to earth and powder
coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a
fault level of 25 MVA symmetrical at 415 volts.
All switchboards shall have provision for entry of cables from the top or bottom as
required.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders
doors and switch handles shall be lockable in OFF position.
The short circuit rating for MCCB's shall be Ics values
10.1 SWITCHBOARD - TOWER (1 TO 12)
INCOMINGS
2 nos 630 amp 4P Switch Isolator complete with

a) 3 nos Cast resin current transformers of 630/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 no. 3 phase 4 wire unbalanced load, Digital kWH CT operated meter alongwith CTs
class 1.0 accuracy 10 VA Burden.
d) 1 set of RYB Phase indicating lamps (LED type)
e) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 800
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The main neutral busbar is to be of 50%
capacity.
BUS COUPLER
1 nos 630 amp 4P Switch Isolator complete
INTERLOCKING
The Incoming & Buscoupler shall be electrically & mechanically interlocked such that
incomers cannot be paralleled.
OUTGOING UNITS

LEFT HAND SECTION
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
1 no. 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
RIGHT HAND SECTION
1 no. 400 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
2 no. 160 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 2,625 31,500
10.2 SWITCHBOARD - LIFTS-TOWER (1 TO 12)
INCOMINGS
1 no. 160 amp 4-P Changeover switch complete with
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 set of RYB Phase indicating lamps (LED type)
d) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS
3 nos 100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
3 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
1 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 3,557 42,687
10.3 SWITCHBOARD - BASEMENT VENTILATION
INCOMINGS
1 nos 160 amp TPN Switch Isolator complete with
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 160/5 ratio Class 1.0 for metering
b) 1 no AVF digital meter (Ampere,Voltage Frequency)
c) 1 set of RYB Phase indicating lamps (LED type)
d) Red / Green ON/OFF indicator (LED type)

BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100%

OUTGOING UNITS
8 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 12 3,557 42,687
11 Design manufacture, supply installation testing and commissioning of 1250 VA Inverter
system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries
backup of minimum 4 hour duration including, batteries, battery chargers, rectifiers,
transformers, controls, protection and instruments etc complete as required.
nos 12 5,863 70,353
12 Design, manufacture, supplying fixing in position, testing and commissioning of the
following front operated cubicle type, front access 2mm thick steel enclosed free standing,
dust and vermin proof, switchboard with IP42 protection with hinged and lockable doors
complete with interconnections, tinned copper crimping lugs, bonding to earth and powder
coating suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system, and suitable for a
fault level of 25 MVA symmetrical at 415 volts.
All switchboards shall have provision for entry of cables from the top or bottom as
required.
All live accessible parts shall be shrouded and all equipment shall be finger touch proof.
The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and
busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders
doors and switch handles shall be lockable in OFF position.
The short circuit rating for MCCB's shall be Ics values
A. EWS MAIN PANEL
INCOMING
1 nos 400 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 400
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity.
INDICATING PANEL
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering
b) 1 no ammeter of 96 mm sq scaled 0-400 amps with 3 way and OFF selector switch
c) 1 no voltmeter of 96 mm sq scaled 0- 500 volts with 3 way & OFF selector switch
d) 1 set of three White phase indicating lamps
OUTGOING UNITS
11 nos.100 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with ON/OFF indicating lamps
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 28,367 28,367
B EWS COMMON PANEL
INCOMING
2 nos 100 amp 4P Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 100
amps having a maximum current density of 1.0 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 100%
capacity.
INDICATING PANEL
The incomers shall have the following indicating panel
a) 3 nos Cast resin current transformers of 100/5 ratio Class 1.0 for metering
b) 1 no ammeter of 96 mm sq scaled 0-100 amps with 3 way and OFF selector switch
c) 1 no voltmeter of 96 mm sq scaled 0- 100 volts with 3 way & OFF selector switch
d) 1 set of three White phase indicating lamps
INTERLOCKING
The Incoming shall be interlocked such that incomers cannot be paralleled.
OUTGOING UNITS
4 nos 63 amp 10 KA TPN MCB with thermal magnetic protective releases with ON
indication.
2 nos 63 amp 10 KA SPN MCB with thermal magnetic protective releases with ON
indication.
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 3,557 3,557
E SWITCHBOARD - CLUB
INCOMING
1 nos 400 amp TPN Switch Isolator complete with
a) 3 nos Cast resin current transformers of 400/5 ratio Class 1.0 for metering
b) 1 no digital electronic ammeter 400 amps
c) 1 no digital electronic voltmeter 500 volts
d) 1 set of three White phase indicating lamps (LED type)
e) Red / Green ON/OFF indicator (LED type)
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbars rated at 600
amps having a maximum current density of 1 amp per sq mm suitable to with stand
symmetrical fault level of 25 M.V.A. at 415 volts. The neutral busbar is to be of 50%
capacity.
OUTGOING UNITS
2 nos 125 amp 25 kA TPN MCCB with overcurrent bimetallic release and short circuit
magnetic release complete with Digital Electronic Energy Meter with requisite CT suitable
for remote data logging
S
12 nos 63 amp 10 kA TPN MCB with thermal magnetic release complete with Digital
Electronic Energy Meter with requisite CT suitable for remote data logging
The Switchboard shall be complete with all interconnections, risers, internal wiring, labels
etc complete as required nos 1 1,778 1,778
3 Design, fabrication, assembling, wiring & supply, installation, testing & commissioning of
meter boards fabricated out of 14 gauge CRCA painted sheet steel in cubicle formation
with reinforcement of suitable size angle iron, channels, T irons, flats wherever
necessary. Cable gland plates shall be provided at top and bottom both and windows for
meter reading, locking arrangement (pad-lock & seal) with wiring upto KWH meter &
meter to MCB shall be done by using adequately rated flexible single core copper wire.
The boards shall be treated with all anticorrosive process before painting as per
standards with final approved shade of powder coated as approved, 2 nos. earthing
terminals shall be provided for 3 phase meter boards and to be connected with the
earthing of rising mains by 2 nos. 25 X 6 mm GI strips. The boards shall be suitable for
415 V, 3 phase, 4 wire, 50 Hz supply system. Boards shall be fabricated in length, height,
depth etc to match with site conditions.
The Meter Board shall be in Non-compartmentalized construction.
An approval shall be taken for each panel before manufacturing.
A SHOPPING METER BOARD
INCOMING
1 nos 100 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical
fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
OUTGOING UNITS
1 no 63 amp TPN 10 kA MCB with thermal magnetic protective releases.
4 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.
14-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision
for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic
energy meter.
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 1 890 890
B METER BOARD -EWS
INCOMING
1 nos 100 amp TPN Switch Isolator complete with
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral busbar rated at 100 amp
having a maximum current density of 1 amp per sq. mm suitable to withstand symmetrical
fault level of 25 M.V.A at 415 volts .The neutral busbar is of 100% capacity.
OUTGOING UNITS
2 no 32 amp TPN 10 kA MCB with thermal magnetic protective releases.
20-32 amp SPN 10 kA MCB with thermal magnetic protective releases each with provision
for fixing of 32 A DHBVNL approved Single phase digital dual register prepaid electronic
energy meter.
The switchboard shall be complete with all interconnection, riser , internal wiring, labels
etc. complete as required. nos 9 890 8,006
C Design,Supply installation testing & commissioning of BIS approved single phase dual
register energy meter for recording dual electric supply from grid and DG with kWH &
kWAh max demand communication port, billing storage facilities, control panel for sensing
supply from DG sets, data transfer & receiving hub,AMR system. DLC with energy
management software with load manager system & recharge coupon generation software
& connecting accessories for prepaid system.
single phase dual register digital electronic prepaid energy meter ( for tariff application)
nos 194 890 172,563

TOTAL SUB-HEAD - IV carried over to Summary 3,398,270
SUB HEAD V : EARTHING
1 Supplying and laying of the following earthing clamped to wall with suitable clamps saddles
and fixing bolts/ in ground/RCC slab along with submain conduit including the cost of
digging and back filling with sand and brick protection as required and complete as
required to comply with IS 3043:1987
a) 25 mm x 6 mm GI strip m 3,800 14 51,300
b) 8 SWG GI Wire m 102,200 1 128,016
c) 6 SWG GI Wire m 20,400 2 45,900
2 Supply and laying of the following GI pipe in ground including excavation, refilling as
required for earth strips etc. as required complete
a) 80 mm dia m 181 45 8,145
3 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 20 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. nos 80 2,223 177,840
4 Providing and laying earth connections from earth electrode with 2 x 6 SWG GI wire in 25
mm dia. GI pipe from earth electrode as required as per specifications. m 181 18 3,258
TOTAL SUB HEAD V carried over to Summary 414,459
SUB-HEAD -VI (FIXTURES AND FITTINGS)
1a Supply of the following light fixtures complete with housing, reflectors, all accessories i.e.
copper wound ballast, HPF condensors, starters, holders etc. complete as required
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 800/-) Nos. 780 206 160,290
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories (base Rate Rs 600/-) Nos. 3,693 151 556,720
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories (base Rate Rs 800/-) Nos. 790 241 190,193
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) Nos. 530 125 66,383
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories (base Rate Rs 450/-) Nos. 24 104 2,502
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories (base Rate Rs 1200/-) Nos. 970 284 274,995
1b Receiving, assembling, erection, connecting, testing and commissioning of the following
light fixtures complete with housing, reflectors, all accessories i.e. copper wound ballast,
HPF condensors, starters, holders etc. complete as required
a) 1x18 W CFL recess mounting downlighter as approved including providing lamps and
other accessories Nos. 780 45 35,100
b) 1x18 W CFL surface mounting downlighter as approved including providing lamps and
other accessories Nos. 3,693 45 166,185
c) 1x28 W T5 lamp surface mounting box type fixture as approved including providing lamps
and other accessories Nos. 790 45 35,550
d) 1x11 W CFL lamp surface mounting bulk head fixture as approved including providing
lamps and other accessories Nos. 530 45 23,850
e) 1x11 W CFL lamp surface mounting wall bracket fixture as approved including providing
lamps and other accessories Nos. 24 45 1,080
f) 2x28 W T5 lamp pendat mounting box type fixture as approved including providing
downrods, lamps and other accessories Nos. 970 45 43,650
2 Supply, fixing, testing and commissioning of 240 Volt single phase ceiling fans of 1200 mm
Sweep including supply of 19 mm heavy gauge GI down rod of length as required
complete. Nos. 17 62 1,058
3 Supply, fixing, testing and commissioning of 240 Volt single phase heavy duty Exhaust
Fans 300 mm dia complete with all accessories as required and with 6 amp 3 pin plug top
as required. Nos. 17 62 1,058
4 Receiving, storing, transportation at site, unpacking, assembling, fixing, testing and
commissioning of 240 Volt single phase Buzzer as required complete. Nos. 1,206 45 54,270
TOTAL SUB-HEAD - VI carried over to Summary
SUB HEAD VII : LIGHTNING PROTECTION
1 Air Terminal & Accessories
Supplying, Erection & commissioning of External Lightning Wide Area Protection System
based on pro-active Early Streamer Emission (ESE) Technology type SATELIT-3-60.
Device shall emit electromagnetic impulse in the form of a controlled emission of
streamers into the air 60 microseconds earlier than naturally formed streamers & polarise
the tip with a voltage between 35 kV & 45 kV . Device confirming to NFC17-102 or UNE
21186 standards. The device shall be mounted at least 5 meter clear to the highest point
by Support Mast of 50mm dia Schedule 80 MS Pipe duly galvanized with minimum 85
micron zinc coating with foundation to suite Mast with concrete to cover 300mmX300mm
floor area & upto 600mm height complete as required
Sets 3 1,334 4,003
2 Low Impedance high voltage down conductor & accessories
Supply, installation, testing & commissioning of down conductor. The Down conductor
shall be of 25X3mm GI strip/Tape. They should be fixed to the structure by means of 2
fasteners every 1.0 meters horizontally & 0.5 meter vertically, It should then run down the
elevation pole and take the shortest direct route down the outside of the building to the
earth termination network, avoiding any sharp corners, thereby providing a low impedance
path from the air terminal to its earth termination system. M 300 9 2,700
3 Lightning Discharge Counter
Supply, installation, testing & commissioning of Lightning Discharge Counter. The
lightning event counter suitable for 1.0KA - 100KA . Counter housed in weather proof
IP67 enclosure with fixing clamps, etc. Sets 3 178 533
4 Maintenance Free Earthing
Supply, Installation, Testing & Commissioning of long life, Maintenance Free Electrolytic
Earthing System Earth pit should consists of 3 nos. 1.2 meters long 14mm dia MS Rod
moleculerly bonded with 250 micron copper coating and treated with 10 kgs of Terec+,
The earthing pit shall be provided with suitable sturdy Test Well for observation. The Earth
Pit shall be covered with 25mm thick gravel/ tiles The Installation procedures should be
followed as instructed by the Earth Electrode Supplier)
Nos. 6 800 4,802
5 Supplying fixing, testing and commissioning of LED Aviation lights, complete as per Wipro
Cat WAN 20001 or Bajaj Cat BJAOL-1, complete with flasher etc as required Nos. 3 890 2,669
6 Supplying, fixing, testing and commissioning of photochromatic switch for automatic
ON/OFF of Aviation light as required. Nos. 3 89 268
7 Wiring for aviation light with 3 core 2.5 sq.mm XLPe insulated PVC sheathed copper
conductor armoured cable from M/C room DB to aviation light. M 200 23 4,500
8 Supply and fixing GI strip 25 mm x 6 mm along outside wall/ columns as vertical
conductors with suitable GI fasteners, brass fixing screws, copper clamps & saddles
complete as required. M 50 9 450
9 Supply and fixing GI strip 25 mm x 6 mm along roof as horizontal conductors with
suitable GI fasteners, brass fixing screws, copper clamps & saddles complete as required.
M 200 9 1,800
10 Supply and laying in ground of GI strip 32 mm x 6 mm for connecting to the GI earth plate
at one end and vertical conductor strip at the other end including the cost of digging and
back filling complete M 30 14 405
11 Providing and making earthpits including the cost of 600 mm x 600 mm x 6 mm GI plate
electrode 50 mm dia GI pipe, CI funnel with wiremesh charcoal, salt, all earth work,
masonry enclosure with CI frame & cover plate having locking arrangement complete as
per IS 3043:1987. Nos 2 2,223 4,446
12 Supplying and laying in ground of GI strip 32 mm x 6 mm for interconnecting the various
Lightning arrestor earth pits, including the cost of digging and back filling, complete as
required. M 200 14 2,700
13 Supply and fixing testing joints made of 25 mm x 6 mm thick GI strip 125 mm long with 4
Nos. GI bolts, nuts, check nuts and spring washers complete as required. Nos 2 9 18
14 Providing and fixing Lightning Conductor Finials made of 25 mm dia 300 mm long GI tube
having a single prong at the top with 85 mm dia 6 mm thick GI base plate complete as
required. Nos 1 89 89
15 Supply and fixing of DMC/SMC insulator complete with GI clamps, Nut Bolts supports
wherever is required. Nos 30 89 2,678
TOTAL SUB-HEAD - VII carried over to Summary 32,060
SUB-HEAD -VIII (FIRE DETECTION & ALARM SYSTEM)
1 Supply, installation, testing and commissioning of wall or ceiling mounted 240 Volt AC
illuminated Signs having on its front a white perspex sheet with the letters 'FIRE EXIT'
painted in red including the cost of in-built rechargeable batteries suitable for 30 minute
operation and including the cost of accessories for surface or recessed or ceiling
suspended mounting complete as required. Nos 514 32 16,191
2 Supply installation testing and commissioning of dust and vermin proof Manual call boxes
with push button to initiate audio visual alarm with breakable glass cover as per detailed
specifications complete with a steel chain including the cost of accessories for surface
mounted as required Nos 514 32 16,191
3 Supply installation test and commissioning of the following 8 ohm size speaker-cum-hooter
units with line matching transformer suitable for broadcast of speech and alarm siren
complete as required suitable for recessed/surface mounting complete with enclosure as
approved by Project Manager and as required. Nos 211 32 6,647
4 Supply, installation, testing and commissioning of wall recess mounting 24 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete. Nos 10 1,778 17,783
4 Supply, installation, testing and commissioning of wall recess mounting 16 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete. Nos 2 1,778 3,557
5 Supply, installation, testing and commissioning of wall recess mounting 15 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the
cost of mounting accessories as required, complete. Nos 1 1,778 1,778
6 Supply, installation, testing and commissioning of wall recess mounting 10 zone
microprocessor based Conventional Fire Control Panel with PA amplifier and 5 potential
free contacts as per detailed specifications with alarms, controls and indications as per
detailed specifications and with an integral power supply unit and complete with a suitably
rated set of batteries and trickle charged from 240 volt AC mains supply, including the cost
of mounting accessories as required, complete. Nos. 1 1,778 1,778
7 Wiring with 2 core 1.5 Sqmm standard copper conductor FRLS 660/1100 volts grade
wires in existing concealed/surface MS conduit etc. as per specification and as required
including the cost of crimped termination's. M 36,500 9 328,500
8 Supply and laying control cabling with copper conductor PVC insulated and PVC
sheathed armoured Control cables in existing pipes/conduits or on existing tray including
the cost of making connections, complete etc. etc. as per specification and as required as
below:

a) 10 core 2.5 sq mm M 5,100 27 137,700
TOTAL SUB-HEAD -VIII carried over to Summary 530,124
n