Index 1 1.Synopsis 2 2.Introduction 3 3.Experimental Procedure 4 3.1 Injection of a single IDMT overcurrent relay 4 3.11 Objective 4 3.12 Procedure 4 3.2 Co-ordination of 3 IDMT overcurrent relays 5 3.21 Objective 5 3.22 Procedure 5 3.3 IDMT protection of a closed ring 6 4.Results 7 4.1 Tabulated results. 7 4.2 Graphical results 8 4.2 Graphical results 9 5.Disscussion 10 5.1 IDMT operation 10 5.11 The effect of plug setting (p.s.) 10 5.12 The effect of Time Multiplier (TM) setting 10 5.2 Standard Characteristic of relay 11 5.3 Advantage of IDMT relays 11 5.4 Calculation of TM 12 6.Conclusion 13 7.Reference Material 14 8.Equipment used 14 9.Index of drawings, tables and graphs 15 - 1 - 1.Synopsis
The aim of the experiment was to investigate the operation, inverse characteristic and to determine the purpose of time and plug settings for overcurrent relays in electrical supply systems. By configuring these settings correctly, and by co-ordinating the operation of the relays, it is possible to isolate the smallest section of the system in the shortest time possible, thereby minimising unnecessary disruption to other consumers whilst preventing damage to equipment within the faulty section. - 2 - 2.Introduction
In a radial feeder configuration, supplied from one end only, discrimination of faults can be achieved by incorporating time delays at each relay point. This enables the relay closest to the fault to trip, isolating the faulty circuit without affecting the other non-faulty circuits. A disadvantage of this system is that for faults near the source the fault current can be much greater than at the opposite end of the feeder due to the impedance.
AC 1.5s 1.0s 0.5s F Low impedance = high fault current Greater impedance = less fault current A B C
Fig. 1 Radial feeder
For a fault at F in fig.1, the circuit breaker at C opens before those at A and B, leaving most of the feeder operational. The relays have a time grading of 0.5s (to allow for relay and circuit breaker operation plus error allowance), illustrating discrimination by time grading only.
The disadvantage can be overcome by employing relays with an inverse current / time characteristic i.e. the time delays are reduced for higher currents. These relays are known as IDMT relays (inverse definite minimum time). A minimum time of operation is incorporated to ensure co-ordination between the relays when the fault level does not vary along the feeder. - 3 - 3.Experimental Procedure
3.1 Injection of a single IDMT overcurrent relay
3.11 Objective
To investigate the inverse characteristic and to determine the purpose of time and plug settings.
3.12 Procedure
Variac Fault 1 A2 A 10:1 Current transformer Ammeter Timer module
Fig.2 Circuit diagram for testing of single IDMT relay
The relay to be tested is at position A2. An ammeter was connected in series via a 10:1 current transformer. With fault switch F1 closed and circuit breaker A2 activated, power is applied and a timer activated. The current can be varied by the variac.
Using currents in the range 1 to 10A, obtain a family of time/current graphs for:
A) A constant ps=100% (plug setting) and a set of TMs (time multiplier) of 0.5,0.75 and 1 B) A constant TM=1 and a set of pss of 0.5, 0.75, 1
From the above the Standard characteristic of the relay can be determined (i.e. t vs. p.s.m)
- 4 - 3.Experimental Procedure (cont.)
3.2 Co-ordination of 3 IDMT overcurrent relays
3.21 Objective
To attempt to achieve optimum co-ordination from the relay setting available.
3.22 Procedure
Supply Load Load Fault on 1 Fault on 2 Fault on 3 A1 A2 C1 B2 C2 B1
Fig.3 Power system simulator
Only relays A2, B2 and C2 have timing facilities. An ammeter should be connected between the ammeter terminals. Series resistors (representing feeder impedances) in the primary circuit are set to give currents of 5A and 3A for the faults at F2 and F3 respectively if the variac is set to have 10A for a fault at F1.
All timers are started by closure of A2. Circuit breakers at B2 and C2 can be prevented from tripping by connection of the appropriate trip link. However, all timers will be stopped by the appropriate relay.
The following steps were taken:
i) Set variac to 100% o/p ii) Set the plug setting on each relay to 1.0 (100%) iii) Set the time multiplier of relay C2 to 0.1 iv) With the fault at F3, the time of operation of C2 was measured. (t 3 =0.66s) - 5 -
3.Experimental Procedure (cont.)
v) Relay C2 was disabled by setting TM very high. With the fault at F3, the TM of B2 was adjusted by trial and error until it tripped at (t 3 +0.5)s. The value of B2 TM and operation time was noted (TM=0.28 and 1.10s). B2 and C2 were now co-ordinated. vi) Relays B2 and A2 were now co-ordinated in a similar manner with the operation of relay A2 being 0.5s slower than B2. (t 2 =1.30s, t 1 =0.8s, A2 TM=0.24) vii) The circuit was now tested to ensure correct operation and co-ordination of the relays in the clockwise direction.
Relay position TM A2 0.24 B2 0.28 C2 0.1
3.3 IDMT protection of a closed ring
In order to achieve disconnection of the faulty section only, the following procedure should be followed.
a) Set the relays A2, B2 and C2 as per the procedure above b) Set the relays at A1, B1 and C1 to have the same p.s. and TM as A2, B2 and C2 respectively. c) The ring is now protected. Check for the correct tripping of the circuit breakers for faults on each section at one time (i.e. apply fault at F3, then F2, then F1) and note the operation of the relays.
Fig. 4 Current and time readings with calculated psm for tm=1 and ps=0.5
Current (I) Time (S) p.s.m. 2.24 27.70 2.99 3.30 10.98 4.40 4.40 7.72 5.87 5.40 6.22 7.20 6.40 5.32 8.53 7.55 4.66 10.07 8.70 4.22 11.60 9.90 3.82 13.20
Fig. 5 Current and time readings with calculated psm for tm=1 and ps=0.75
Current (I) Time (S) p.s.m. 2.90 28.22 2.90 4.00 12.70 4.00 5.10 8.88 5.10 6.15 7.18 6.15 7.25 6.10 7.25 8.30 5.44 8.30 9.55 4.86 9.55
Fig. 6 Current and time readings with calculated psm for tm=1 and ps=1.0
The plug setting multiplier is calculated using: r s I p.s. I p.s.m. ! " Where I s =secondary current in amps, p.s.=plug setting and I r =rated current (1A) - 7 - 4.Results (cont.)
4.2 Graphical results
Current versus time 0.00 2.00 4.00 6.00 8.00 10.00 12.00 0.00 5.00 10.00 15.00 20.00 25.00 30.00 Time (s) C u r r e n t
( I ) ps=0.5 ps=0.75 ps=1
Fig. 7 Current versus time graph for various values of ps (tm=1)
Current versus Time 0.0 2.0 4.0 6.0 8.0 10.0 12.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 Time in seconds C u r r e n t
i n
a m p s tm=0.5 tm=0.75 tm=1 Fig. 8 Current versus time graph for various values of tm (ps=1)
- 8 - 4.Results (cont.) 4.2 Graphical results Time versus plug setting multiplier 0.00 5.00 10.00 15.00 20.00 25.00 30.00 0.00 5.00 10.00 15.00 20.00 25.00 Plug setting multiplier T i m e
i n
s e c o n d s ps=0.5 ps=0.75 ps=1 Fig. 9 Time versus plug multiplier setting
"Standard Characteristic" of the relay 0.00 5.00 10.00 15.00 20.00 25.00 30.00 0.00 5.00 10.00 15.00 20.00 25.00 Plug setting multiplier T i m e
i n
s e c o n d s
Fig. 10 Standard characteristic of the relay derived from the results obtained in fig. 8 - 9 - 5.Disscussion
5.1 IDMT operation.
The IDMT relay works on the induction principle, where a aluminium or copper disc rotates between the poles of an electromagnet and a damping magnet. The fluxes induce eddy currents in the disc which interact and produce rotational torque. The disc rotates to a point where it operates a pair of contacts that break the circuit and remove the fault condition.
5.11 The effect of plug setting (p.s.)
The plug setting (p.s.) of the relay changes the number of turns in the exciting coil. The winding of the coil is provided with seven taps, which are brought to the front panel and the required tap is selected by a push-in plug. With the plug in the first position (0.5), the whole of the coil is utilised, and the relay is most sensitive. In the seventh position (2.0), only a quarter of the coil is utilised and hence four times more current is required to operate the relay. The seven plug positions are marked 0.5, 0.75, 1, 1.25, 1.5, 1.75, and 2.0 (or 50%, 75%, 100% etc). Should the plug be removed altogether, the relay automatically defaults to the 2.0 or 200% setting.
The effect of altering the plug setting is that for a given current, the greater the plug setting, the longer the time of operation (see fig.6).
E.g.: For a fault current of 6A (from fig.6): Plug Setting 0.5 0.75 1 Approximate Operation Time (s) 4.74 6.66 8.88
Fig.11 Example of differing times of operation for different plug settings
5.12 The effect of Time Multiplier (TM) setting
The TM (time multiplier) setting of the relay adjusts the backstop of the rotating disc. The time of operation is proportional to the distance through which the disc must rotate in order to operate the contacts. With the time multiplier set to one, the backstop is as far back as it can go (180#), and the disc has to move through its maximum travel in order to operate the contacts. If the time multiplier is set to zero then the backstop is positioned so that the contacts are permanently closed.
Fig.12 Table of degrees of disc rotation for differing time multiplier settings
The effect of altering the time multiplier setting is that for a given current, the greater the time multiplier setting, the longer the time of operation (see fig.7).
- 10 - 5.Disscussion (cont.)
5.2 Standard Characteristic of relay
The standard characteristic is a graph of time versus the plug multiplier setting (psm), this avoids one graph with many curves and can be used to calculate the actual time of operation for the relay. Psm can be calculated where:
r s I p.s. I p.s.m. ! " Where I s =secondary current in amps, p.s.=plug setting and I r =rated current (either 1A or 5A)
As the standard curve is for a TM = 1, then the actual time of operation (T a ) is given by: 1 a T T.M. T ! " Where T 1 = time obtained from standard characteristic graph for given fault condition.
Example
Using fig.9,
A 5A relay is supplied via a 200/10 current transformer with a plug setting of 175% and a time multiplier of 0.2. Find the operating time if the fault current is 1.5kA.
Secondary current I s =(1500!10)/200=75A
r s I p.s. I p.s.m. ! " = 5 1.75 75 ! " p.s.m. = 8.57
From fig.9, T 1 =5.4s $ = 0.2 ! 5.4 = 1 a T T.M. T ! " 1.08s
5.3 Advantage of IDMT relays
The major advantage of IDMT relays is their ability to discriminate. As discussed earlier (see introduction) without this feature faults near the source would receive a large fault current, but by the introduction and correct setting of the IDMT relay this can be reduced to a minimum. By correct setting of the relays only the parts of the system after the fault will suffer a loss of supply and therefore only the smallest portion of the system will be affected. If the fault is closer to the source, a large part will be affected , but this will still be the smallest possible portion.
By using IDMT relays in conjunction with directional relays, the protection of a ring system can be achieved. Once the system is set correctly, then discrimination is possible so that the nearest relay to the fault operates to isolate the smallest possible section in the shortest time. - 11 - 5.Disscussion (Cont.)
5.4 Calculation of TM
Given that the assumed fault currents for F1=10A, F2=5A and F3=3A, calculate the TM for B2 and A2 (CT=1:1) and compare with measured results, give % difference and possible sources of error.
If ps=1 then: (B2) r s I p.s. I ! " p.s.m. = 1 1 5 ! " p.s.m. =5 With reference to fig.9, T 1 =9 T a =1.1 s (measured value) If T , then 1 a T T.M. ! " 1 a T T T.M. " = 9 1.1 =0.122
(A2) r s I p.s. I p.s.m. ! " = 1 1 10 p.s.m. ! " =10 With reference to fig.9, T 1 =4.8 T a =0.8 s (measured value) If , then 1 a T T.M. T ! " 1 a T T " T.M. = 4.8 1.3 =0.271
Our measured results were B2 TM=0.28 and A2 TM=0.24
Possible errors could arise from: % Reading of the graph % Reading of the instruments % Calibration of relay scales and instruments % The use of assumed values of current rather than measured values - 12 - 6.Conclusion
The purpose of protection is to monitor for unwanted conditions and when such conditions arise to remove the fault condition in the shortest time possible whilst leaving unaffected areas operational. The design of the system must have a high level of sensitivity to fault conditions whilst remaining operational during non-fault conditions. - 13 - 7.Reference Material
Fig.13 Serial numbers of equipment used - 14 - 9.Index of drawings, tables and graphs
Figure number Description 1 Radial feeder 2 Circuit diagram for testing of single IDMT relay 3 Power system simulator 4 Current and time readings with calculated psm for tm=1 and ps=0.5 5 Current and time readings with calculated psm for tm=1 and ps=0.75 6 Current and time readings with calculated psm for tm=1 and ps=1.0 7 Current versus time graph for various values of ps (tm=1) 8 Current versus time graph for various values of tm (ps=1) 9 Time versus plug multiplier setting 10 Standard characteristic of the relay derived from the results obtained in fig. 8 11 Example of differing times of operation for different plug settings 12 Table of degrees of disc rotation for differing time multiplier settings 13 Serial numbers of equipment used