MECHANI CAL SYSTEM CRI TERI A SPECI FI CATI ONS : TABLE 2.9.1 - UNITARY AIR CONDITI ONERS AND CONDENSING UNITS, ELECTRICALLY OPERATED (Voluntary guidelines for use in energ y effciency programs. For Terms and Usage, please see the CEE website at www.cee1.org.) EQUI PMENT T YPE SI ZE C ATEGORY SUB- C ATEGORY OR RATI NG CONDI TI ON REQUI RED EFFI CI ENC Y AI R CONDI TI ONERS, AI R COOLED < 65,000 Btu/h Split System 15.0 SEER 12.5 EER Single Package 15.0 SEER 12.0 EER 65,000 Btu/h and < 135,000 Btu/h Split System and Single Package 12.2 EER 14.0 IEER 135,000 Btu/h and < 240,000 Btu/h Split System and Single Package 12.2 EER 13.4 IEER 240,000 Btu/h and < 760,000 Btu/h Split System and Single Package 11.0 EER 11.6 IEER > 760,000 Btu/h Split System and Single Package 10.2 EER 11.4 IEER AI R CONDI TI ONERS, WATER AND E VAPORATI VELY COOLED All Sizes Split System and Single Package 14.0 EER AI R CONDI TI ONERS, WATER COOLED < 65,000 Btu/h Split System and Single Package 14.0 EER > 65,000 Btu/h and < 135,000 Btu/h Split System and Single Package 13.8 EER 15.1 IEER > 135,000 Btu/h Split System and Single Package 13.8 EER 14.6 IEER AI R CONDI TI ONERS, E VAPORATI VELY COOLED < 65,000 Btu/h Split System and Single Package 14.0 EER > 65,000 Btu/h and < 135,000 Btu/h Split System and Single Package 13.8 EER 15.1 IEER > 135,000 Btu/h Split System and Single Package 13.3 EER 14.1 IEER a. For electrical resistance heating section types, increase required minimum EER by 0.2. Source: Consortium for Energ y Effciency (June 2009). CEEs high-effciency specifcations are periodically revised. For the most current version, please see the CEE website at www.cee1.org/com/ hecac/hecac-main.php3 13.8 12.0 > > > 12.0 13.0 10.6 12.1 59 CORE PERFORMANCE REQUIREMENTS 2.9 MECHANICAL EQUIPMENT EFFICIENCY REQUIREMENTS TABLE 2. 9. 2 - UNI TARY AND APPLI ED HEAT PUMPS, ELECTRI CALLY OPERATED (Voluntary guidelines for use in energ y effciency programs. For Terms and Usage, please see the CEE website at www.cee1.org.) EQUI PMENT T YPE SI ZE C ATEGORY SUB- C ATEGORY OR RATI NG CONDI TI ON REQUI RED EFFI CI ENC Y AI R COOLED, ( COOLI NG MODE ) < 65,000 Btu/h Split System 15.0 SEER* 12.5 EER Single Package 15.0 SEER* 12.0 EER* 65,000 Btu/h and < 135,000 Btu/h Split System and Single Package 11.7 EER 13.0 IEER 135,000 Btu/h and <240,000 Btu/h Split System and Single Package 11.7 EER 12.5 IEER 240,000 Btu/h Split System and Single Package 10.7 EER 11.5 IEER AI R COOLED ( HE ATI NG MODE ) < 65,000 Btu/h (Cooling Capacity) Split System 9.0 HSPF Single Package 8.5 HSPF 65,000 Btu/h and < 135,000 Btu/h (Cooling Capacity) 47 o F db/43 o F wb Outdoor Air 3.4 COP 17 o F db/15 o F wb Outdoor Air 2.4 COP > 135,000 Btu/h (Cooling Capacity) 47 o F db/43 o F wb Outdoor Air 3.2 COP 17 o F db/15 o F wb Outdoor Air 2.1 COP WATER SOURCE ( COOLI NG MODE ) < 135,000 Btu/h (Cooling Capacity) 85 o F Entering Water 14.0 EER WATER-SOURCE ( HE ATI NG MODE ) < 135,000 Btu/h (Cooling Capacity) 70 o F Entering Water 4.6 COP a. For electrical resistance heating section types, increase required minimum EER and IEER by 0.2. Source: Consortium for Energ y Effciency (2010). CEEs high-effciency specifcations are periodically revised. For the most current version, please see the CEE website at www.cee1.org/com/ hecac/hecac-main.php3 * These CEE Tier 2 values (as of June 2010) were incorporated into Core Performance in June 2010, version 1.02. TABLE 2. 9. 3 PACKAGE TERMI NAL AI R CONDI TI ONERS AND HEAT PUMPS, ELECTRI CALLY OPERATED EQUI PMENT T YPE SI ZE C ATEGORY REQUI RED EFFI CI ENC Y AI R CONDI TI ONERS < 7,000 Btu/h 11.9 EER & HE AT PUMPS ( COOLI NG MODE ) 7,000 Btu/h and < 10,000 Btu/h 11.3 EER 10,000 Btu/h and <13,000 Btu/h 10.7 EER 13,000 Btu/h 9.5 EER 11.1 10.7 10.1 12.1 11.7 10.7 60 CORE PERFORMANCE REQUIREMENTS 2.9 MECHANICAL EQUIPMENT EFFICIENCY REQUIREMENTS TABLE 2. 9. 4 BOI LERS T YPE FUEL SI ZE C ATEGORY TEST PROCEDURE EFFICIENCY REQUIREMENT ( 3 MANUFACTURERS) STE AM GAS < 300,000 Btu/hr DOE 10 CFR Part 430 83.4% 83% AFUE 300,000 - 2,500,000 Btu/hr DOE 10 CFR Part 431 80.6% 81% Et > 2,500,000 Btu/hr 80.5% 82% Ec OI L < 300,000 Btu/hr DOE 10 CFR Part 430 85.6% 85% AFUE 300,000 - 2,500,000 Btu/hr DOE 10 CFR Part 431 83.0% 83% Et > 2,500,000 Btu/hr 83.5% 84% Ec HOT WATER GAS < 300,000 Btu/hr DOE 10 CFR Part 430 97.3% 97% AFUE 300,000 - 2,500,000 Btu/hr DOE 10 CFR Part 431 94.5% 97% Et > 2,500,000 Btu/hr 94.5% 94% Ec OI L < 300,000 Btu/hr DOE 10 CFR Part 430 88.6% 90% AFUE 300,000 - 2,500,000 Btu/hr DOE 10 CFR Part 431 85.3% 88% Et > 2,500,000 Btu/hr 86.2% 87% Ec Et = t her mal ef f i c i enc y, Ec = Combus t i on Ef f i c i enc y * Systems must be designed with lower operating hot water temperatures (<150F) and use hot water reset to take advantage of the much higher effciencies of condensing boilers. TABLE 2. 9. 5 CHI LLERS EQUI PMENT T YPE SI ZE C ATEGORY REQUI RED EFFI CI ENC Y- CHI LLERS OPTI ONAL COMPLI ANCE PATH- REQUI RED EFFI CI ENC Y- CHI LLERS WI TH VSD FULL LOAD ( K W/ TON) I PLV ( K W/ TON) FULL LOAD ( K W/ TON) I PLV ( K W/ TON) AI R COOLED W/ CONDENSER All 1.2 1.0 N/A N/A AI R COOLED W/ O CONDENSER All 1.08 1.08 N/A N/A WATER COOLED, RECI PROC ATI NG All 0.840 0.630 N/A N/A WATER COOLED, ROTARY SCREW AND SCROLL < 90 tons 0.780 0.600 N/A N/A 90 tons and < 150 tons 0.730 0.550 N/A N/A 150 tons and 300 tons 0.610 0.510 N/A N/A > 300 tons 0.600 0.490 N/A N/A 61 CORE PERFORMANCE REQUIREMENTS 2.9 MECHANICAL EQUIPMENT EFFICIENCY REQUIREMENTS EQUI PMENT T YPE SI ZE C ATEGORY REQUI RED EFFI CI ENC Y- CHI LLERS OPTI ONAL COMPLI ANCE PATH- REQUI RED EFFI CI ENC Y- CHI LLERS WI TH VSD WATER COOLED, CENTRI FUGAL < 150 tons 0.610 0.620 0.630 0.400 150 tons and 300 tons 0.590 0.560 0.600 0.400 > 300 tons and 600 tons 0.570 0.510 0.580 0.400 > 600 tons 0.550 0.510 0.550 0.400 a. Compliance with full load effciency numbers and IPLV numbers are both required. b. Only chillers with variable speed drives (VSD) may use the optional compliance path for chiller effciency. c. Water-cooled centrifugal water-chilling packages that are not designed for operation at ARI Standard 550/590 test conditions (and thus cannot be tested to meet the requirements of Table 2.9.5) of 44 F leaving chilled water temperature and 85 F entering condenser water temperature shall meet the applicable full load and IPLV/NPLV requirements. TABLE 2. 9. 6 ABSORPTI ON CHI LLERS EQUI PMENT T YPE REQUI RED EFFI CI ENC Y FULL LOAD COP ( I PLV) AI R COOLED, SI NGLE EFFEC T 0.60, but only allowed in heat recovery applications WATER COOLED, SI NGLE EFFEC T 0.70, but only allowed in heat recovery applications DOUBLE EFFEC T DI REC T FI RED 1.0(1.05) DOUBLE EFFEC T I NDI REC T FI RED 1.20 For additional references and information about this measure, visit www.advancedbuildings. net/reference-materials/reference-materials-access-form. TABLE 2. 9. 7 VARI ABLE REFRI GERANT FLOW MULTI SPLI T AI R CONDI TI ONERS EQUI PMENT T YPE SI ZE C ATEGORY HEATI NG SEC TI ON T YPE VRF AI R COOLED ( COOLI NG MODE ) < 65,000 Btu/h All 15.0 SEER 12.5 EER > 65,000 Btu/h and < 135,000 Btu/h Resistance or None 11.7 EER 14.9 IEER > 135,000 Btu/h and < 240,000 Btu/h Resistance or None 11.7 EER 14.4 IEER > 240,000 Btu/h Resistance or None 10.5 EER 13.0 IEER SS WE EA MR EQ credit 1 LEED Relationship 62 CORE PERFORMANCE REQUIREMENTS 2.9 MECHANICAL EQUIPMENT EFFICIENCY REQUIREMENTS TABLE 2. 9. 8 VARI ABLE REFRI GERANT FLOW MULTI SPLI T HEAT PUMP EQUI PMENT T YPE SI ZE C ATEGORY HEATI NG SEC TI ON T YPE SUBC ATEGORY MI NI MUM EFFI CI ENC Y REQUI REMENTS TEST PROCEDURE VRF AI R COOLED ( COOLI NG MODE ) < 65,000 Btu/h All Multisplit 15.0 SEER AHRI 1230 12.5 EER > 65,000 Bth/h and < 135,000 Btu/h Resistance or None Multisplit 11.3 EER 14.2 IEER Multisplit with Heat Recovery 11.1 EER 14.0 IEER > 135,000 Btu/h and < 240,000 Btu/h Resistance or None Multisplit 10.9 EER 13.7 IEER Multisplit with Heat Recovery 10.7 EER 13.5 IEER > 240,000 Btu/h Resistance or None Multisplit 10.3 EER 12.5 IEER Multisplit with Heat Recovery 10.1 EER 12.3 IEER VRF AI R COOLED ( HE ATI NG MODE ) < 65,000 Btu/h - Multisplit 9.0 HSPF > 65,000 Bth/h and < 135,000 Btu/h - 47F db/43F wb Outdoor Air 3.4 COP - 17F db/15F wb Outdoor Air 2.4 COP 135,000 Btu/h - 47F db/43F wb Outdoor Air 3.2 COP - 17F db/15F wb Outdoor Air 2.1 COP VRF WATER SOURCE ( COOLI NG MODE ) < 135,000 Btu/h All Multisplit System - 86 Entering Water 14.0 EER Multisplit System with Heat Recovery 86 Entering Water 13.8 EER VRF WATER SOURCE ( HE ATI NG MODE ) < 135,000 Btu/h 68 Entering Water 4.6 COP 75 Introduction Design Process Strategies Core Performance Requirements Enhanced Performance Strategies Energy Modeling Appendices 3.3 Additional Lighting Power Reductions PURPOSE To reduce connected lighting load to achieve the requirements of the Energy Policy Act of 2005 and qualify for Federal tax incentives. CRI TERI A Reduce connected lighting load by at least 40% below the allowances of the ASHRAE 90.1 reference standard used by EPAct 05, while meeting all of the lighting control requirements of that standard. (Note that EPAct05 uses the 2001 version of the ASHRAE 90.1 standard as a reference point, even though newer versions of 90.1 are in force.) GENERAL Projects which meet the lighting power density (LPD) and control requirements of Core Performance are well on their way to qualifying for federal tax incentives under the Energy Policy act of 2005 (EPAct 05). An additional effort on the part of the design team to reduce connected lighting load can result in eligibility of the project to receive tax incentives. For tax-exempt public projects, the tax incentive can be transferred directly to the design team. The basic requirements of EPAct 05 are to reduce LPD by 25% to 40% below the requirements of ASHRAE 90.1-2001, and to implement the interior and exterior lighting control requirements of that standard. Achieving this qualifes the project for a Federal tax deduction of $0.30 to $0.60 per square foot of building area under the current policy. (Increases in the incentive level and program extensions are currently under consideration; current program requirements should be verifed.) The goal of this Criteria is to achieve a 40% reduction in connected lighting load (compared to the EPAct 05 baseline) which represents approximately a 20% reduction below the a reduction of 10% or more from the requirements listed in Criteria 2.8. Specifc targets are shown in the LPD table below, which is derived from typical LPD requirements of ASHRAE 90.1-2001 as listed in Table 9.3.1.1 of that standard and Criteria 2.8 of the Core Performance Guide. Note that the values in this table represent only a subset of building. For additional references and information about this measure, visit www.advancedbuildings. net/reference-materials/reference-materials- access-form. TABLE 3. 3.1 - APPROXI MATE LPD REQUI REMENTS FOR ACHI EVI NG EPACT05 BUI LDI NG AREA T YPE 40 % LI GHTI NG POWER DENSI T Y REDUC TI ON TARGET CONVENTI ON CENTER 0.85 DI NI NG 0.89 0.9-1.15 E XERCI SE CENTER 0.79 0.85 GYMNASI UM 0.9 1.0 HOSPI TAL / HE ALTH C ARE 0.95 LI BRARY 0.9 OFFI CE 0.73 0.78 PERFORMI NG ART S THE ATER 0.9 POLI CE / FI RE STATI ON 0.78 RELI GI OUS BUI LDI NG 0.95 1.32 RETAI L 1.15 SCHOOL / UNI VERSI T Y 0.89 0.9 TOWN HALL 0.83 0.85 WAREHOUSE 0.59 0.72 (For additional space types, see ASHRAE 90.1-2001 Table 9.3.1.1) National Wildlife Federation Headquarters, Reston, Virginia Courtesy of Hedrich-Blessing SS WE EA MR EQ credit 1 LEED Relationship