SUMMARY COST - INDORAMA INTERNAL ELECTRICAL WORKS

SUB HEAD AMOUNT

I. POINT WIRING - 1,281,250.00

II. CONDUIT & WIRING FOR TELEPHONE 57,850.00


NETWORK / COMPUTER
NETWORK/AUDIO VIDEO.

III. MAIN PANEL/PDU's DB & CABLES - 1,436,285.00

IV. EARTHING 370,700.00

V FIXING OF LIGHTING FIXTURES - 45,000.00

VI SUPPLY OF LIGHTING FIXTURES - 700,400.00

VII CONDUITING FOR FIRE ALARM ,ACCESS 20,000.00


CONTROL, BMS, CCTV, & SECURITY
SYSTEM

VIII PA SYSTEM 89,150.00

IX INVERTER -

X CONSTRUCTION POWER AND LIGHTING 20,000.00

TOTAL COST ( INR ) 4,020,635.00

Discount @ 17% 3,497,952.45

INCLUSIVE OF SERVICE TAX + EDU CESS


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ
I POINT WIRING
The rates of Point Wiring for all items shall include the following:
1 The Point Wiring shall include the wiring of light/outlets of any length from the distribution board
via switch to the point.
2 All the Light Fixtures, 3rd pin of the 6 Amp outlets, switch and outlet boxes, shall be earthed with
1.0 sqmm PVC insulated copper conductor wire ( Green )
3 All 16 Amp outlets shall be earthed with 2.5 sqmm PVC insulated copper conductor wire. ( Green )
4 Embedding of conduits and fittings in walls/ floors etc during construction and/or in chases
including making good as necessary.
5 All accessories necessary to complete the wiring as specified.
6 Wherever flexible conduit is required, GI flexible conduit of suitable size with checknut/coupler
shall be used.

S. No. Description Unit Qty Unit. Rate Amount Image

I Point Wiring
1 Wiring for the following light points with 2 x
2.5 sq. mm + 1 x 1.5sqmm (green ) PVC
insulated copper conductor FR wires of
650/1100 Volts grade in concealed / exposed
PVC conduits/ PVC Trunking as called for
including providing 6 amp flush type switches
(as, approved),including providing and fixing
of White Polycarbonate modular cover
plate for switch boxes.

a One point controlled by one 6 amp switch. Nos 75 1,000.00 75,000.00


( DB to First Light Point )
b Light Points Directly controlled from MCB Nos 800.00 -
( MCB costed seperately )to First Light Point.

2 Wiring to looped light points with 2x1.5 sq. Nos 250 400.00 100,000.00
mm. FR/PVC insulated copper conductor
1100 V grade wires in concealed or surface
mounted 20/25 mm dia PVC conduit /
existing MS Trunking as required.
Including earthing of fixtures and outlet
box with 1.5 sq. mm. FR PVC insulated
copper conductor 1100 V grade green earth
wire. (Including providing GI flexible
conduit from 'Tee' to fixture).

3 Supplying and fixing of 2 nos. 6 amp outlet Nos 120 650.00 78,000.00
international / universal type pin
including providing 1 no. 6 amp indicator
switch ( Red ) housed in 16 gauge MS box
with approved White Polycarbonate
modular cover for outlet boxes.( For UPS,
wiring & conduiting are separate items ).
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

4 Supplying and fixing of 1 nos. 6 amp 5-pin Nos 120 310.00 37,200.00
outlet with ROUND PIN including providing
1 no. 6 amp switch housed in 16 gauge MS
box with approved White Polycarbonate
modular cover for outlet boxes.( For Raw
Power at W/Station , wiring and
conduiting are separate items)

5 Supplying and fixing of 1 nos. 16 amp 5-pin Nos 2 500.00 1,000.00


outlet with round pin including providing 1 no.
16 amp switch housed in 16 gauge MS box
with approved White Polycarbonate
modular cover for outlet boxes.( For UPS,
wiring and conduiting are separate items)

6 Providing and fixing in position of the


following sizes of PVC conduit including all
accessories as required.

a 25 mm dia PVC conduit RM 1000 60.00 60,000.00


32 mm dia PVC conduit RM 150 75.00 11,250.00
7 Supplying and drawing of the following size of -
PVC insulated PVC sheathed copper conductor
FR sheathed copper conductor FR wires of
650/1100 V grade in existing
conduits/Raceway.( For UPS power+ Raw
Power @ workstations )

a 3 x 2.5 sq. mm copper flex cable/ wire RM 3000 65.00 195,000.00


8 Wiring for , 6 amp light plug outlet with 1.5 Nos 30 1,200.00 36,000.00
sq. mm PVC insulated copper conductor FR
wires in concealed/exposed PVC conduits
including providng 6 amp switch, MS box for
housing switches sockets, approved White
Polycarbonate modular cover to outlet
boxes and earthing. ( Raw Power-
Housekeeping)

9 UPS Wiring for , 6 amp light plug outlet with Nos 10 1,200.00 12,000.00
1.5 sq. mm PVC insulated copper conductor
FR wires in concealed/exposed PVC conduits
including providng 6 amp switch, MS box for
housing switches sockets, approved White
Polycarbonate modular cover to outlet
boxes and earthing. ( HVAC Fire Dampers )
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

10 Wiring for 16 amp power outlet points with 4 Set 4 3,600.00 14,400.00
sq. mm PVC insulated copper conductor wires (Two
for the first socket outlet and 2.5 sq. mm PVC outlets
insulated copper conductor FR wires for the )
second outlet 650/1100 Volts grade in
concealed/exposed PVC conduits as called for
including providing 16 amp flush type 6 pin
socket and switch, MS outlet boxes for power
outlets. Approved White Polycarbonate
modular cover to outlet boxes and earthing.
(Only two outlets shall be connected to each
circuit)

11 Wiring for 16 amp power outlet points with 4 Nos 2 3,200.00 6,400.00
sq. mm PVC insulated copper conductor wire
of 650/1100 Volts grade in
concealed/exposed PVC conduits including
providing 16 amp flush type combined 6 pin
sockets and switch, approved White
Polycarbonate modular cover to MS outlet
boxes and earthing. (Only one outlet shall be
connected to each circuit).

12 Supplying and fixing of 32 amp 3-pin (phase, Nos 8 2,500.00 20,000.00


neutral and earth),1-phase industrial socket
for AC POWER, including supplying plug top
complete with MCB as required and as per
specifications. Industrial Plug Socket MDS
Cat No.607851 or equivalent ( Wiring is
taken seperately)

13 Supplying and drawing of the following size of


PVC insulated copper conductor FR wires of
650/1100 V grade in existing conduits,
complete as required and as per
specifications.
a 3 x 6 sq. mm copper flexible cable. ( FOR RM 200 165.00 33,000.00
SINGLE PHASE A/C)

14 Supplying and fixing of 32 amp 3-PIN Nos 10 6,500.00 65,000.00


ROUND ( 1 phase + 1 Neutral +earth) for 1-
phase IP 66 rated Surface SOcket Outlet
complete with Mounting Enclosure and 3 Pin
Angle Plug ( IP 56 ), complete as required
and as per specifications.FOR RACK POWER
IN SERVER ROOM. CLIPSAL/Bals make
or Equal

15 Supplying and fixing of EGA BOX outlet Nos 2 6,000.00 12,000.00


including supplying 18 gauge MS PAINTED
outlet boxes of suitable size, and with 6/16
amp Socket and switch, complete as required
and as per specifications.
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

16 Supplying and fxng in position of the following


sizes of exposed/concealed PVC conduit
including all accessories complete as required
and as per specifications.

a 25 mm dia PVC conduit RM 250 60.00 15,000.00


b 32 mm dia PVC conduit RM 50 75.00 3,750.00

17 Providing and fixing on floor of following sizes


of Raceway made on 16 gauge sheet steel
Stove Enamelled Blue with all accessories
as required complete as required (DATA
RACEWAY)

a 450mm x 40mm (3mm thick cover) RM 0 -


b 400mm x 40mm (3mm thick cover) RM 0 -
c 350mm x 40mm (3mm thick cover) RM 0 -
d 300mm x 40mm (3mm thick cover) RM 0 -
e 250mm x 40mm (3mm thick cover) RM 0 -
f 200mm x 40mm (3mm thick cover) RM 75 1,900.00 142,500.00
g 150mm x 40mm (2mm thick cover) RM 50 1,650.00 82,500.00
h 100mm x 40mm (2mm thick cover) RM 75 1,250.00 93,750.00
i 65mm x 40mm (2mm thick cover) RM 75 1,000.00 75,000.00

18 Providing and fixing on floor of following sizes


of JUNCTION BOXES for above Raceway
made of 16 gauge sheet steel Stove
Enamalled Blue with all accessories as
required complete as required (DATA
RACEWAY)
a 450mm x 40mm (3mm thick cover) Nos -
b 400mm x 40mm (3mm thick cover) Nos -
c 350mm x 40mm (3mm thick cover) Nos -
d 300mm x 40mm (3mm thick cover) Nos 0 -
e 250mm x 40mm (3mm thick cover) Nos 0 -
f 200mm x 50mm (3mm thick cover) Nos 4 1,200.00 4,800.00
g 150mm x 50mm (3mm thick cover) Nos 8 1,050.00 8,400.00
h 100mm x 50mm (3 mm thick cover) Nos 8 975.00 7,800.00
i 65mm x 50mm (3mm thick cover) Nos 10 900.00 9,000.00

19 Providing and fixing on floor of following sizes


of Raceway made on 16 gauge sheet steel
Stove enammeled ORANGE with all
accessories as required including supply &
fixing of approved MS Painted junction box
complete as required, complete as
required(POWER RACEWAY)

a 200mm x 50mm (2mm thick cover) RM 0 -


b 150mm x 50mm (2mm thick cover) RM 0 -
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

c 100mm x 50mm (2mm thick cover) RM 0 -


d 65mm x 50mm (2mm thick cover) RM 75 1,100.00 82,500.00

20 Supplying ,testing & installing 10 inch Nos 0 -


Exhaust fans , Newtek make

Total Carried over to Summary I 1,281,250.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

II CONDUIT AND WIRING FOR VOICE/DATA NETWORK /AUDIO VIDEO.

1 Providing and fixing in position MS anodized Nos 120 60.00 7,200.00


computer outlet / telephone box 16 gauge
suitable for fixing of jack complete as
required.

2 Providing and fixing in position following sizes


of PVC conduits including providing all
accessories concealed / exposed as required

a 25 mm dia PVC conduit RM 350 55.00 19,250.00


b 32 mm dia PVC conduit RM 0 75.00 -
c 25 mm dia GI Flexible conduit RM 550 35.00 19,250.00
d 32 mm dia GI Flexible conduit RM 0 45.00 -

6 Providing and fixing in position MS anodised Nos 4 225.00 900.00


TV outlet box 16 gauge with white poly
carbonate modular cover plate including
supplying, fixing of co-axial type T.V. socket
outlet complete as required.

8 Supply & laying of RG-59 (Commscope make) RM 250 45.00 11,250.00


cable for TV in existing conduit complete as
required

10 Supply & fixing of 20 Pair, 0.61mm dia RM 0 165.00 -


Armoured Telephone Cable.

Total carried over to SummaryII 57,850.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

III
MAIN PANELS/PDU's/ DB'S & CABLES & CABLE TRAYS

The rates shall include the following:


1 Earthing all components, frames etc
2 Effecting adequate and proper connections and terminations, with thimbles etc.
3 Painting, lettering, ferruling on DB's and providing its circuit diagram
4 Painting all metal parts with approved enamel paints.

1 ELECTRICAL DIST: PANELS


Design, manufacture, supply, installation, testing
and comissioning of 2 mm thick MS sheet steel
fabricated cubicle type Panel dust and vermin proof
complete with hinged and lockable doors. All the
panels shall be floor mounted and dead front
construction complete with interrconnections by
copper tapes / wires and painting. The distribution
boards shall be provided with one no. of
multifunction meter machsmart 96 of Neptune Ducati
make or equivalent along with associated C.T.'s &
P.T.'s in the incoming switch. The current density of
the bus bar to be used in panel shall be 1.3 sq
mm/amp. AS PER ENCLOSED SLD

A Main Panel ( As Per SLD ) Set 1 315,000.00 315,000.00

B UPS DIST PANEL ( AS PER SLD ) Set 1 187,500.00 187,500.00

C UPS OUTGOING PANEL ( AS PER SLD) Set 1 135,000.00 135,000.00

D UTILITY PANEL ( AS PER SLD) Set 1 75,000.00 75,000.00

2 Supplying the following 16 SWG Distribution


Boards . Including proper labling as directed
alongwith separate Neutral Link for each Phase,
Earth link and separate dedicated Earth link in
case of UPS Distribution Boards as well as
necessary Bus links etc.

a Sheet metal enclosed, VTPN DB with 1 No Nos 0 -


250 A TP MCCB ( DPX 250 ER Icu=36 kA )
incomer and outgoing 12 Nos. of 63 amp TP
MCB ( FOR A/C PANEL) WITH METER BOX
INCLUDING VOLTMETER ( ANALOGUE 0-
500V, AMMETER 0-300A, WITH
NECESSARY CT'S. PLS CHECK SLD )
LEGRAND MAKE CAT NO. 6078 22 + 6077
75 OR EQUAL
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

b Sheet metal enclosed, VTPN DB with 1 No Nos 0 -


125 A MCCB incomer and outgoing 10 A SP
MCB's as required, for UPS DB. LEGRAND
MAKE Cat No. 6077 91 OR EQUAL

c Sheet metal enclosed, VTPN DB with 1 No Nos 0 -


150 A MCCB incomer and outgoing 24 Nos. of
16 amp SP MCB FOR RACK POWER
DISTRIBUTION SOCKET

d Sheet metal enclosed, VTPN DB with 1 No Nos 0 -


100 A MCCB incomer and outgoing 12 Nos. of
63 amp TP &N MCB

e Supply, installation, testing & commissioning Nos 0 7,500.00 -


of 100 A FP MCCB, 25KA service breaking
capacity and 100 Amp trip setting in sheet
steel enclosure along with ON indication lamp
complete as required.( INCOMNG TO UPS

f Supply, installation, testing & commissioning Nos 4 4,500.00 18,000.00


of Surface Mounted Socket Outlet with 63A FP
MCB provision, for 3 Phase, IP 67 rated,
Neptune Bals make ( Insulated Plug & Socket
) or Equal, complete with Plug.(FOR 3
Phase AC's)
g Sheet metal enclosed, double door,08 way Nos 3 17,500.00 52,500.00
TPN DB with 24 Nos. of 10/20 amp SPMCB
i.e. 24 Nos. of 10/20 amp SPMCB arranged in
3 rows & controlled by 1 No. 63 amp 4P MCB
& neutral link, and Per Phase Isolation with
20 AMP DP MCB, complete with Busbar,
Shrouded Neutral Link + Earth Link ( UPS
DB'S)

h Sheet metal enclosed, double door,10 way -


TPN DB with 30 Nos. of 10/20 amp SPMCB
i.e. 10 Nos. of 10/20 amp SPMCB arranged in
3 rows & controlled by 1 No. 63 amp 4P MCB
& neutral link, and Per Phase Isolation with
DP MCB, complete with Busbar, Shrouded
Neutral Link + Earth Link
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

i Sheet metal enclosed, double door,12 way Nos 3 18,500.00 55,500.00


TPN DB with 36 Nos. of 10/20 amp SPMCB
i.e. 12 Nos. of 10/20 amp SPMCB arranged in
3 rows & controlled by 1 No. 63 amp 4P MCB
& neutral link, and Per Phase Isolation with
32 AMP DP MCB, complete with Busbar,
Shrouded Neutral Link + Earth Link ( 4 Row
of 13 Modules DB) LEGRAND CAT No. 6077
65 or Equal ( L&P DB'S)

j Sheet metal enclosed, double door,6 way TPN Nos 2 14,500.00 29,000.00
DB with 18 Nos. of 10/20 amp SPMCB i.e. 18
Nos. of 10/20 amp SPMCB arranged in 3 rows
& controlled by 1 No. 40 amp TPN MCB &
neutral link, with 20 DP MCB protection for
Each Phase, complete with Neutral + Earth
Links. ( FOR SRV UPS DB'S)

k Sheet metal enclosed, double door, 4 way Nos 2 6,500.00 13,000.00


SPN DB with 4 Nos of 16 amps,SP MCB and
controlled by 1 No. 40 amp DP MCB and
neutral link. ( EMG LIGHT DB'S)

3 Supply, Install Test and Commission the


following:
a 4 nos. 16 sq mm PVC insulated copper RM 0 - -
conductor wires in 50 mm dia PVC conduit.
Including providing 2 no. 6 sq mm PVC
insulated green copper earth wire.

b 4 nos. 10 sq mm PVC insulated copper RM -


conductor wires in 38 mm dia PVC conduit.
Including providing 2 no. 4 sq mm PVC
insulated green copper earth wire.

c 4 nos. 6 sq mm PVC insulated copper RM -


conductor wires in 32 mm dia PVC conduit.
Including providing 2 no. 2.5 sq mm PVC
insulated green copper earth wire.

g 2 nos. 10 sq mm PVC insulated copper RM 40 600.00 24,000.00


conductor wires in 38 mm dia PVC conduit.
Including providing 1 no. 4 sq mm PVC
insulated green copper earth wire.
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

4 Supplying, Receiving, unloading, storing -


layiing, effecting proper connections, testing
and commissioning of following sizes of 1.1
KV grade XLPE insulated Copper
conductor Armoured /
Unarmoured/Flexible cables laid on
existing overhead cable trays or over MS
supports in masonry trenches including
providing the MS supports and clamps for
fixig to supports in an approved manner
complete as required and as per
specifications.
a 4 x 70 SQ MM Cu Arm Cable RM 0 -
b 4 x 50 SQ MM Cu Arm Cable RM 0 -
c 4 x 16 SQ MM Cu Arm Cable RM 130 785.00 102,050.00
d 4 x 10 SQ MM Cu Arm Cable RM 50 668.00 33,400.00
e 3X6 SQ.MM Cu.Flexible Cable RM 100 268.00 26,800.00
f 3X4 SQ.MM Cu.Flexible Cable RM. 0 -
g 1x25 SQ.MM Cu Flexible Cable RM 200 350.00 70,000.00
h 1x 16 SQ MM Cu Flexible cable RM 50 197.00 9,850.00

5 Cable termination of the following XLPE


insulated Copper conductor armoured
cables of 1100V grade including cost of
thimbles / lugs, single compression nickel
plated brass glands, cables sockets, insulation
tape and crimping etc. complete as required.

a 4 x 70 SQ MM Cu Arm Cable Nos 0 -


b 4 x 50 SQ MM Cu Arm Cable Nos 0 -
c 4 x 16 SQ MM Cu Arm Cable Nos 8 350.00 2,800.00
d 4 x 10 SQ MM Cu Arm Cable Nos 0 -
e 3X6 SQ.MM Cu.Flexible Wire Nos 0 -
f 3X4 SQ.MM Cu.Flexible Wire Nos 0 -
g 1x25 SQ.MM Cu Flexible Cable Nos 20 100.00 2,000.00
h 1x 16 SQ MM Cu Flexible cable Nos 8 100.00 800.00

6 Supplying, Receiving unloading, storing


laying, effecting proper connections, testing
and commissioning of following sizes of 1.1
KV XLPE insulated Aluminium Armoured
cables in existing overhead cable trays or
over MS Supports in masonry trenches
including providing the MS supports and
clamps for fixing to supports in an approved
manner complete as required and as per
specifications.

a 3½ x 240 SQ MM RM 100 1,150.00 115,000.00


b 3½ x 185 SQ MM RM 0 -
c 3½ x 150 SQ MM RM 0 -
d 3½ x 120 SQ MM RM 0 -
e 4 x 95 SQ MM RM 30 712.00 21,360.00
f 4 x 70 SQ MM RM 0 -
g 4 x 50 SQ MM RM 0 -
h 4 x 35 SQ MM RM 0 -
i 4 x 25 SQ MM RM 150 287.00 43,050.00
j 4 x 16 SQ MM RM 75 215.00 16,125.00
k 4 x10 SQ MM RM 0 165.00 -
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

l 3 x 10 SQ MM RM 0 -
m 3 X 4 SQ MM RM 0 -

7 Cable termination of the following XLPE


insulated aluminum conductor armoured
cables of 1100V grade including cost of
thimbles / lugs, single compression nickel
plated brass glands, cables sockets, insulation
tape and crimping etc. complete as required.

a 3½ x 240 SQ MM Set 2 800.00 1,600.00


b 3½ x 185 SQ MM Set 0 -
c 3½ x 150 SQ MM Set 0 -
d 3½ x 120 SQ MM Set 0 -
e 4 x 95 SQ MM Set 2 550.00 1,100.00
f 4 x 70 SQ MM Set 0 -
g 4 x 50 SQ MM Set 2 -
h 4 x 35 SQ MM Set 0 -
i 4 x 25 SQ MM Set 6 300.00 1,800.00
j 4 x 16 SQ MM Set 0 250.00 -
k 4 x10 SQ MM Set 2 150.00 300.00
l 3 x 10 SQ MM Set 0 0
m 3 X 4 SQ MM Set 0 0

8 PERFORATED/LADDER Type Cable Tray


(For Power Cables)
Providing and fixing the following
Perforated/Ladder type MS Painted Cable
Tray alongwith necessary hanging material
,coupler plates, nuts, bolts and washers with the
following specifications. (All accessories like
tees, bends vertical / horizontal shall be factory
prefabricated and cost of these to be included in
the rate. Site fabricated accessories are not
acceptable).

a 150 mm wide, 50 mm high, 1.6 mm thick RM 100 350.00 35,000.00


cable tray.( LADDER TYPE )
b 300 mm wide, 50 mm high, 1.6 mm thick RM 75 650.00 48,750.00
cable tray.( LADDER TYPE )
c 300 mm wide, 50 mm high, 1.6 mm thick RM 50 700.00 35,000.00
cable tray.( Perforated TYPE )
Total carried over to Summary III 1,436,285.00
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

IV EARTHING & GROUNDING


1 Supplying and fixing of the following tapes /
wires including excavation and filling complete
with all necessary fixing accessories and
effecting connections.

a 50 x 6 MM GI TAPE RM 0 - -
b 40 x 6 MM GI TAPE RM 0 - -
c 25 x 6 MM GI TAPE RM 0 - -
d 8 SWG bare GI wire. RM 0 30 -
e 50 x 6 MM COPPER TAPE RM - -

f 25 x 3 MM COPPER TAPE RM -
g 25 x 3 MM COPPER TAPE in PVC SLEEVE RM 150 450.00 67,500.00
2 Providing earthing stations (B Class GI pipe Each 0 - -
earthing) complete as per I.S. specifications
(GI pipe shall be 50 MM dia) (GI pipe 16 feet
and depth of pit 17 feet). (With Heavy Duty
Manhole)

3 Providing earthing stations (16 SWG Copper Each 6 13,500.00 81,000.00


pipe/plate earthing) complete as per I.S.
specifications IS 3043 (Copper pipe shall be 40
MM dia, 10 Ft Long) (Copper plate
600x600x3mm). (With Heavy Duty Manhole)

4. Providing and laying the following UPVC pipe


including digging and back filling of trench up to
a maximum depth of 600 mm.

c. 110 MM DIA RM 0 - -
(6 KG PER SQ CM -
e. 50 MM DIA RM 0 - -
(6 KG PER SQ CM - CLASS
5. Providing and laying the following GI pipe
including digging and back filling of trench up to
a maximum depth of 750 mm.
a. 100 MM DIA (B Class) RM 30 500.00 15,000.00
6. Providing manholes 600 x 600 x 600 MM Each 4 1,500.00 6,000.00
deep along with CI ( Heavy ) manholes covers.

7. Providing and drawing the following PVC


Insulated Copper Conductor 1100 Volt grade
flexible Cable ( GREEN COLOR ) including cost
of thimbles / lugs insulation tape and crimping
etc. complete as required including
terminations.
a 35 SQ MM RM 0 -
b 25 SQ MM RM 300 282.00 84,600.00
c 16 SQ MM RM 300 177.00 53,100.00
d 10 SQ MM RM 0 -
e 6 SQ MM RM 400 60.00 24,000.00

8. Providing and fixing the following MS conduit


recessed /surface mounted as directed.(earth
pit to facility)
a 20 mm dia 16 SWG RM 0
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

b 25 mm dia 16 SWG RM 150 120.00 18,000.00


c 32 mm dia 14 SWG RM 50 160.00 8,000.00

9 Providing and fixing 16 SWG MS Set 3 4,500.00 13,500.00


enclosure600x200x75mm deep along with
MS Cover. Including providing 2 no. insulated
supports, 2(50x6) mm thick copper strip (Nickel
plated) with suitable holes to fix dedicated earth
wires complete with lugs. "Dedicated Earth" to
be inscribed on the cover of the enclosure.

Total carried over to Summary IV 370,700.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

V FIXING OF LIGHTING FIXTURES


The rates for Fixing of Light fixtures and fans shall include all fixing accessories
that may be required to make the installation complete in all respects such as :
1 Providing connecting wires and channel support wherever required
2 Internal wiring between accessories
3 Self interlocking connector block for connecting fixture to point.
4 Earthing of Fixtures with 1.0 sqmm PVC insulated copper conductor wire.
5 Approved down rods/ GI chain/ clamps and other components and accessories.

1 Receiving, fixing in position, effecting proper Nos 300 150.00 45,000.00


connections, testing and commissioning of 1 x
36 watt fluorescent fixtures/2 x 36 watt
fluorescent fixtures fixed surface mounted on
ceiling or wall mounted with all fixing
accessories as required.

2 Receiving, fixing in position, effecting proper Nos 0 150.00 -


connections, testing and commissioning of 1 x
36 / 4 x 18 watt fluorescent fixtures/2 x 26
watt fluorescent fixtures fixed recessed in
ceiling with chains hung from slab with all
fixing accessories as required, along with
providing PVC flexible conduit from junction
box at slab level to fixture.

3 Receiving, fixing in position, effecting proper Nos 0 100.00 -


connections, testing and commissioning of PL
13/ 18 W, MR 16 / 12V , AR-111, lamp fixture
recessed in ceiling including providing and
fixing of required G.l. sheet n which fixture
shall be clamped complete as required and
with all accessories, along with providing PVC
flexible conduit from junction box at slab level
to fixture.

4 Receiving, fixing in position effecting proper Nos 0 -


connections testing and commissioning of PL/
Pendant lamp fixed surface mounted on
ceiling or wall mounted complete as required
with all accessories.

5 Receiving, fixing in position effecting proper Nos 0 75.00 -


connections testing and commissioning of 1 x
18/ 1 x 36 W Flourscent Patti fittings in
Cove/Pelmets as required with all
accessories.
6 Receiving, fixing in position effecting proper Nos 0 -
connections testing and commissioning of PL/
Wall light/ Uplighters/ fixed surface mounted
on ceiling or wall mounted complete as
required with all accessories.

Total carried over to Summary V Rs 45,000.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

VI SUPPLY OF LIGHTING FIXTURES

1 Supply of the following


fluorescent/Incandescent/MR-16, MR-11, etc
light fixtures with all accessories, such as
spring loaded side holders, copper/electronic
ballasts, starters, power factor compensators,
MS housing to house electronic ballasts,
complete with tubes.

A 2x36W CFL recess mounted Direct-Indirect Nos 50 3,200.00 160,000.00


luminaire with 2nos. of 36W CFL -
Wipro/Thorn/Philips

B 2x18W recess mounted down light with Nos 80 1,500.00 120,000.00


high efficiency satin finished anodised
aluminium reflector with frosted diffuser
and 2nos. 18W CFL lamp - Wipro WCP
27218 SGW

C Wipro/Philips/Thorn Make 2 x 36 W CFL , T8 0 -


Industrial Chanel with Stove Enamaled
reflector, Complete with lamps Cat No. Wipro
WCF 26236 (INDUSTRIAL SUSPENDED)

D FLOOD LIGHT FIXTURE WITH 150W LAMP 0 -


DOUBLE ENDED (CAT.NO.-MFH 51150)
(SYSMMETRIC) WIPRO/PHILIPS/THORN,
complete with control gear and bracket.
E WIPRO/THORN/PHILIPS MAKE 1X18W WALL 0 1,300.00 -
Light in reinforced Thermoplastic with
Polycarbonate diffuser (CAT.NO.-FWP
42118).
F Philips make 1 x 28 W T 5 Batten Fitting Nos 150 750.00 112,500.00
( TCH 128/2005/840
G Philips/Wipro/Thorn make 1 x 28 W Batten Nos 0 -
Fitting (Blue colour tube light in cove
server rm & telcon)
2 Supply of following PL lamp / MR-16/AR-111
fixtures complete with all accessories and PL
lamp / halogen lamps with transformer,
complete as required.
A Artlite Cat No. RL-3165 with 1 x 18W PL lamp Nos -

B WIPRO/THORN/ARTLITE TYPE DLSD 50R 95G. Nos 30 850.00 25,500.00


12V/ 50W lamp
C Pendant Light Fixture with decorative glass Nos 6 3,500.00 21,000.00
(basic cost Rs 1500/= )
D 1 xQR-111 Fixt:Thorn Cat No:QMLD 1050 Nos -
E 2 xQR-111 Fixt:Thorn Cat No:QMLD 2050 Nos 8 4,300.00 34,400.00

3 Wall Lights Artlite ( Basic cost Rs 800/= ) Nos -


4 Table Lamps, of approved design, (basic cost Nos -
Rs 1750/=)
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

5 Wall Mount Up Lighters, Reiz/Artlite make. Nos -


( Basic cost Rs 1200/=)
6 Uplighters in Toilets Artlite make ( Basic Price Nos 0 1,250.00 -
Rs 850/= )
7. EMERGENCY LIGHT (EXIT SIGN ) Nos 8 6,500.00 52,000.00
Thorn/Pierlite FVSP 108 N (Non Maintain)
8 Decorative light fixture s as per Architect's Lot 1 175,000.00 175,000.00
approval. Basic cost, including lamp and all
taxes Rs 150000/

VI Total carried over to Summary VI Rs. 700,400.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

VII
CONDUITING FOR FIRE ALARM ,ACCESS CONTROL, BMS, CCTV, & SECURITY SYSTEM

3 Providing and fixing the following MS conduit


surface mounted as directed.(fire alarm)

a 20 mm dia 16 SWG RM 200 70.00 14,000.00


b 25 mm dia 16 SWG RM 50 120.00 6,000.00
c 32 mm dia 14 SWG RM 0 -
4 Providing and laying 2 core 1.5 sq mm, PVC RM 0 -
insulated and PVC sheathed cable in existing
MS conduit for Fire Alarm System.

5 Providing and laying RG - 6 cable in existing RM 0 -


PVC conduit for CCTV System.

6 Providing and laying PVC insulated, shielded RM 0 -


12 core 24 AWG stranded copper conductor
control cabling for CCTV System in existing
PVC conduit.
7 Providing and fixing the following MS conduit
surface mounted as directed.
a 20 mm dia 16 SWG RM 0 -
b 25 mm dia 16 SWG RM 0 -
c 32 mm dia 14 SWG RM 0 -
8 Providing and fixing 16 SWG single Nos
compartment MS trunking with 16 SWG
openable covers at regular intervals along with
necessary cable support system as directed
including providing and fixing accessories like
suitable Clamps, Dash Fasteners, Cable Ties,
Gaskets etc. complete in all respects. (All
Trunking is to be cleaned thoroughly, before
pulling any wires / cables). Including earthing
of the trunking with 4 sq. mm. PVC insulated
Yellow + Green Copper Earth Wire with proper
thimbles. All joints of MS Trunking shall be
provided with proper couplers as directed.
Including providing 300x300x50 mm deep
Junction Boxes as required. (Please note
Junction Boxes shall be part of the trunking item
and shall not be paid extra).

a 40 x 150 x 40 mm deep (painted Grey in RM 0 -


colour)

9 Providing and laying PVC insulated, shielded and RM 0 -


sheathed 8 core 24 AWG stranded copper
conductor control cabling for BMS System in
existing Raceway or conduit.

10 Providing and laying PVC insulated, sheathed 4 RM 0 -


core 24 AWG stranded copper conductor control
cabling for BMS in existing MS conduit.

Total carried over to Summary VII Rs 20,000.00


MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

VIII CONDUTING, WIRING & SUPPLY, INSTALL OF PA SYSTEM


1. Providing and fixing BOSCH make Nos
40 950.00 38,000.00
Speakers. Speakers shall be LBD (6 Watts
Read Power) including linematching
transformer (Ceiling Recessed with mounting
clamp - White colour)
2. Providing and fixing BOSCH make Amplifier Nos 1 18,500.00 18,500.00
shall be LBD 8148 + LBD 8733
3. Four channel Audio mixer with Goose call No 1 8,900.00 8,900.00
station (LBB 1950)

4. Providing and fixing Volume Control with Nos 0 -


operating knob in GI outlet Box complete with
cover plate and blank plate. (Sample to be
approved by Architect)
5. Providing and fixing Mass Volume Control with Nos 0 -
operating knob in GI outlet Box complete with
cover plate and blank plate. (Sample to be
approved by Architect)
6. Wiring to speakers in existing conduit. 24 / RM 450 35.00 15,750.00
0.20 mm PVC insulated twin twisted flexible
annealed tinned copper wire.
7. Providing and fixing the following PVC conduit
surface mounted as directed.
a. 20 mm dia 16 SWG RM 200 40.00 8,000.00
b. 25 mm dia 16 SWG RM 0 -

VIII Total carried over to Summary 89,150.00


Rs.
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

IX
SUPPLY & INSTALLATION OF INVERTER
1. Supplying, installation, testing and Set 0 -
commissioning of 10 KVA invertor DSP pure
Sinewave output single phase input and single
phase output including batteries suitable for 15
minutes back up, trolley on wheels to house the
batteries. The inverter should have the following
features :
- Quick change-over from Mains to Inverter Mode

- Constant Voltage Throughout


- DSP (Digital Signal Processing) based Pure Sine
Wave Output)
- High and Low Input voltage Protection for
connected appliances
- Software controlled auto reset feature for
overload, short circuit and low battery
- LCD display for all protections and helping steps

- Auto self test for Inverter on LCD Display


- LCD Display for battery level and load level
- Appliances which run on Sine-I do not produce
any humming / disturbing noise
- Enhances battery life
- Generator Compatibility

IX Total carried over to Summary Rs -


Rs.

X Providing Construction Lighting ( Power LS 1 20,000.00 20,000.00


will be supplied at a Single Point by the
Owner), with sufficient Nos of Lamps and
Patti Fittings and Multi Socket Points,
necessary DB, etc as required.
MPHASIS PH-4 INDORE
FIRST FLOOR 21 AUG 2008
INTERNAL ELECTRICAL BOQ

S. No. Description Unit Qty Unit. Rate Amount Image

Você também pode gostar