FOR
DESIGN OF 11 kV, 1100A SEGREGATED PHASE BUSDUCT
AND ACCESSORIES
An Interconnection between
LA, SC, PT, & CT Panel &11 kV HT Switch Board
PROJECT:
CONSULTANT:
M/s. DESEIN PRIVATE LIMITED.,
Contents:
Page 1 of 13
1.
Design Parameters
2.
3.
4.
5.
6.
7.
Reference Documents
Page 2 of 13
Design parameters
1
11 kV
Rated Voltage
12 kV
BIL Rating.
12 kV / 35 kV / 75 kVP
Encl. Dimension
1196 mm x 400 mm
Encl. Material
Busbar Material
Copper
Busbar Size
100 x 10 mm
1000 Sq. mm
9. Barrier Material
40 kA.
3 Sec.
102 kAp
500 C
350 C
200 C
3000 C
1100 A
Fault Current
17. Rated Current
Page 3 of 13
Ratio =
1000 x 3
1196 x 400
Ratio <
1%
0.65
400 100
100 + 10
2.72
1
2
35
50
0.61
0.61
= 0.805
Derating Factor for Black-Matt finish
1.2
1.0
Page 4 of 13
0.6279
AC Current rating as per Copper for Busbar by Copper development Association in Free Air for
above Busbar @ 50 0 C over an ambient of 40 0 C.
2065 A
2065 x 0.6279
1296.61 A
Page 5 of 13
(1 + 0.0076 ) - 1
( Sq. mm )
Isc
40
kA (rms)
03
(300-85 = 215) 0 C
Where A
Second
Therefore
A
0.051 ----40
(1 + 0.0076 x 215 ) - 1
388.69
Sq mm
1000
Sq. mm
Page 6 of 13
3 x 11002 x Rac
l / A
17.2
Ro { 1 + ( T2 - To ) }
17.2 { 1 + 0.0039 ( 85 - 20 ) }
S.E.R Calculation
=
50 / 21.56 x 10-3
48.157
Rac
= 1.15
1.15 x 21.56
89.99 W / Mts.
Page 7 of 13
400 mm
Enclosure Width
1196 mm
Ambient Temp.
50 0 C
70 0 C
emissivity
0.9
7.66 (20)1.25
(400)0.25
x 0.400 +
5.92 (20)1.25
x 1.196
(1196)0.25
= 2 x [ 28.97 + 50.92 ]
Wc
= 159.78 W / Mts.
= 484.16 W / Mts.
Since the Heat Dissipation Capability is Higher than Heat Generated, the Temperature Rise of
Conductor will be less than 20 0 C
Page 8 of 13
Fm
--------------------------------------0.4
568 Kg / M
0.375 x 568
213 Kg / M
Fs x ( H1 + H2 )
H1
H1
150 mm
H2
5 mm
Fs
213 Kg / M
213 ( 150 + 5 )
150
Cf =
220 Kg / M
C S of Insulator
F.S. x Cf
CS
FS
Cf
960 Kgs
2.5
220 Kg / Mtr.
960
2.5 x 220
1.75 Mts.
Page 9 of 13
1.75 Mts.
F.S x ( S )2
8
Cf
220 Kg / Mtr.
- Insulator Span
1.75 Mtr.
220 ( 1.75 )2
8
M
6. Max. Fiber Stress
84.21 Kg Mtr.
M
Z
84.21
16.67 x (10)-6
F
Copper permissible limit is
0.50 x 107 Kg / M2
- 245 N / mm2
2.5 x 107
Kg / M2
Hence safe
Page 10 of 13
1100 A
Rac
Reactance Calculation
1.26 x
1.26 x
400
100 + 10
4.58
X = 57 x 3.28
= 186.96 Micro Ohms / Mt.
Voltage Drop at Rated Current at 0.8 P.F = 3 x 1100 x [ (R cos ) + ( X sin ) ] x 10-6
= 3 x 1100 x [ (24.79 x 0.8) + (186.96 x 0.6) ] x 10-6
VD = 0.25 Volts / Mts.
Page 11 of 13
Reference Documents :
a. Copper for Busbar
Page 12 of 13
Page 13 of 13