DESIGN CALCULATIONS

FOR
DESIGN OF 11 kV, 1100A SEGREGATED PHASE BUSDUCT
AND ACCESSORIES
An Interconnection between
LA, SC, PT, & CT Panel &11 kV HT Switch Board

PROJECT:

2 x 15 MW COGEN POWER PLANT


{ INDORAMA PETROCHEMICALS LTD., BUTIBORI, NAGPUR}

CONSULTANT:
M/s. DESEIN PRIVATE LIMITED.,

Contents:
Page 1 of 13

1.

Design Parameters

2.

Thermal Withstand Capability

3.

Evaluated Heat loss of Conductor

4.

Enclosure Temperature Rise

5.

Mechanical Stress Withstand Capability

6.

Voltage Drop Calculations

7.

Reference Documents

Page 2 of 13

Design parameters
1

Nominal System Voltage

11 kV

Rated Voltage

12 kV

BIL Rating.

12 kV / 35 kV / 75 kVP

Encl. Dimension

1196 mm x 400 mm

Encl. Material

3mm Thk. Aluminium

Busbar Material

Copper

Busbar Size

100 x 10 mm

8. Cross Sectional Area

1000 Sq. mm

9. Barrier Material

2mm Thk. Aluminium

10. Short Circuit Current

40 kA.

8. Duration of Short Circuit

3 Sec.

9. Momentary Peak Withstand Current

102 kAp

10. Design Ambient Temperature

500 C

11. Max. Temperature Rise of Conductor Carrying Rated Current -

350 C

12. Max. Temperature Rise of Enclosure

200 C

13. Max. Temperature of Conductor Carrying

3000 C

1100 A

Fault Current
17. Rated Current

Page 3 of 13

Thermal Withstand Capability


Continuous Current Rating
Derating Factors:
Derating Factor of Enclosure :
Conductor to Enclosure Ratio

Conductor Cross Section


Enclosure Cross Section

Ratio =

1000 x 3
1196 x 400

Ratio <

1%

For Indoor Installation

0.65

Derating Factor for Proximity:


Proximity

Phase Spacing (S) Width (a)


Width (a) + Thickness (b)

400 100
100 + 10

2.72

From the Graph Proximity Factor = 1.0


Derating Factor for Temperature Rise:
Temperature Rise of 35 0 C Rise above 50 0 C Ambient

1
2

35
50

0.61

0.61

= 0.805
Derating Factor for Black-Matt finish

1.2

Derating Factor for Non Magnetic Enclosure

1.0

Page 4 of 13

Total De-rating factor

0.65 x 1 x 0.805 x 1.2 x 1

0.6279

AC Current rating as per Copper for Busbar by Copper development Association in Free Air for
above Busbar @ 50 0 C over an ambient of 40 0 C.

2065 A

Rating of busbar for above size conductor

2065 x 0.6279

1296.61 A

Page 5 of 13

Calculation of Short Circuit Rating:


The Cross Section area required for Thermal Withstand capability is given by the formula
A 2
0.051 ---I

(1 + 0.0076 ) - 1

Area of Cross Section required

( Sq. mm )

Isc

Equivalent Short Circuit Current

40

kA (rms)

Short Circuit Duration

03

Max. Permissible Temp. During short circuit -

(300-85 = 215) 0 C

Where A

Second

Therefore

A
0.051 ----40

The Cross section area actually adopted

(1 + 0.0076 x 215 ) - 1

388.69

Sq mm

1000

Sq. mm

Which is more than what is required for Thermal withstand capability

Page 6 of 13

Heat Loss in Conductor


Heat loss in conductor at 85 0 C
Rdc @ 20 0 C =
=
Rdc @ 85 0 C =

3 x 11002 x Rac

l / A
17.2

Micro Ohms / Mt.

Ro { 1 + ( T2 - To ) }

17.2 { 1 + 0.0039 ( 85 - 20 ) }

21.56 Micro Ohms / Mt.

S.E.R Calculation
=

( f/ Rdc ) for 1000 Mts.

50 / 21.56 x 10-3

48.157

From the Graph S.E.R

Rac

= 1.15

1.15 x 21.56

24.79 Micro Ohms / Mt.

Heat loss in conductor at 85 0 C

3 x 11002 x 24.79 x 10-6

89.99 W / Mts.

Total Heat Generated = 89.99 W / Mts.

Page 7 of 13

Enclosure Temperature Rise


Enclosure Height

400 mm

Enclosure Width

1196 mm

Ambient Temp.

50 0 C

Max. Encl. Temp.

70 0 C

emissivity

0.9

Heat Dissipated by Convection


= 2x

7.66 (20)1.25
(400)0.25

x 0.400 +

5.92 (20)1.25

x 1.196

(1196)0.25

= 2 x [ 28.97 + 50.92 ]
Wc

= 159.78 W / Mts.

Heat Dissipated by Radiation


= 5.70 x 10-8 x 0.9 [ (343)4 (323)4 ] x 3.192
Wr

= 484.16 W / Mts.

Total Heat Dissipated = Wc + Wr


= 159.78 + 484.16
= 643.94 W / Mts.

Since the Heat Dissipation Capability is Higher than Heat Generated, the Temperature Rise of
Conductor will be less than 20 0 C

Page 8 of 13

Mechanical Stress Withstand Capability


1. Instantaneous Maximum Short Circuit Force are calculated using the formula
1.42 x 10-7 x (40)2 x 106
Fm

Fm

--------------------------------------0.4
568 Kg / M

2. Steady State Force ( Fs ):


Steady State Force ( Fs )

0.375 x 568

213 Kg / M

3. Steady state force acting on Top of the Insulator ( Cf ) =

Fs x ( H1 + H2 )
H1

H1

- Height of the Insulator

150 mm

H2

- Height of the neutral axis of the


conductor above the Insulator

5 mm

Fs

- Steady State Force

213 Kg / M

213 ( 150 + 5 )
150

Cf =

220 Kg / M

4. Permissible Span of the Support Insulator

C S of Insulator
F.S. x Cf

CS
FS
Cf

960 Kgs
2.5
220 Kg / Mtr.

- Cantilever Strength of Insulator


- Factor of Safety
- Cantilever Force at the Top of Insulator

960
2.5 x 220

Insulator Support Span

1.75 Mts.

Page 9 of 13

Maximum Adopted Support Span

1.75 Mts.

5. Max. Bending Moment

F.S x ( S )2
8

Cf

- Cantilever Force ( Steady State Force )

220 Kg / Mtr.

- Insulator Span

1.75 Mtr.

220 ( 1.75 )2
8

M
6. Max. Fiber Stress

84.21 Kg Mtr.

M
Z

84.21
16.67 x (10)-6

F
Copper permissible limit is

0.50 x 107 Kg / M2

- 245 N / mm2

2.5 x 107

Kg / M2

Hence safe

Page 10 of 13

Voltage Drop Calculations


Rated Current =

1100 A

Rac

24.79 Micro Ohms / Mt.

Reactance Calculation

1.26 x

Phase Spacing (S)


Width (a) + Thickness (b)

1.26 x

400
100 + 10

4.58

From the Graph Reactance

= 57 Micro Ohms / ft.

X = 57 x 3.28
= 186.96 Micro Ohms / Mt.

Voltage Drop at Rated Current at 0.8 P.F = 3 x 1100 x [ (R cos ) + ( X sin ) ] x 10-6
= 3 x 1100 x [ (24.79 x 0.8) + (186.96 x 0.6) ] x 10-6
VD = 0.25 Volts / Mts.

Page 11 of 13

Reference Documents :
a. Copper for Busbar

By Copper Development Association

b. Aluminium for Busbars.

By Mr. A. G. Thomas and Mr. P. J. Rata

Page 12 of 13

Page 13 of 13

Você também pode gostar