INTELLIGENT DISPLAY UNIT
DS/DA Series
Ordering information
D 16 R S S D
Basic unit
Temperature/Humidity input
2
R PT sensor input
2
DT
Temperature/Humidity input+
RS485 communication output
2
RT
PT sensor input+
RS485 communication output
2
S Serial input
P Parallel input
T RS485 communication input
E Expansion unit
R Red
G Green
16
1
W16 X H24mm (W9.0 X H16.0mm)
22 W20 X H33mm (W11.2 X H22.5mm)
40 W40 X H60mm (W22.4 X H40.0mm)
60 W60 X H96mm (W33.6 X H60.0mm)
S 7 Segment
A 16 Segment
D Display unit
Item
Display method
Size(Character size)
Display color
Unit type
1: The 16 size model does not have the parallel input model and does not support 16 Segment display method.
2: The temperature/humidity input, PT sensor input, temperature/humidity input+RS485 communication output,
PT sensor input+RS485 communication output models will be released.
M A N U A L
Unit-display unit
1)Unit name plate type
2)Unit name plate insertion
This unit is for displaying unit by inserting a name
plate. It has only 16, 22 sizes. (Sold separately)
It provides unit-printed name plates as an accessory. You can select the desired unit name plate
and insert this plate. (Single-stage unit name plate: 19 types, Dual-stage unit name plate: 2 types)
Remove the protection sheet and insert the unit name plate at between the case and the reector.
Size
Color
Red Green
16mm DU16-R DU16-G
22mm DU22-R DU22-G
Model
Dual-stage unit name plate
Single-stage unit name plate
Protection
sheet
Unit name plate
insertion space
Case
Reflector
Caution: Be sure
about the correct
insert direction.
Specication
Model
Basic unit DS16- S/T D 22- S/P/T D 40- S/P/T D 60- S/P/T
Expansion unit DS16- E D 22- E D 40- E D 60- E
Input method
D - S: Serial
D - P: Parallel(Dynamic Parallel 1, Dynamic Parallel 2)
D - T: RS485 communication(Modbus protocol)
Display color Green, Red (Select by model)
Power supply 12-24VDC
Allowable voltage range 90 to 110% of rated voltage
Current
consumption
Red type Max. 20mA Max. 25mA Max. 55mA Max. 65mA
Green type Max. 15mA Max. 20mA Max. 40mA Max. 45mA
Character size W9H16mm W11.2H22.5mm W22.4H40mm W33.6 H60mm
Max. clock
1
Serial input: Max. 2kHz
Parallel input: Dynamic Parallel 1: Max. 3kHz
Dynamic Parallel 2: Max. 1.5kHz
Input logic
1
Selectable Positive logic (PNP), Negative logic (NPN) (Change by function set switch)
Input resistance
1
20
Input level
1
High: 4.5-24VDC, Low: 0-1.2VDC
Display character Displays 64 types of character and sign (0 to 9, A to Z, 27 signs, decimal point)
The number of max.
multi-stage connection
Serial/RS485 communication input: 24 units
Parallel: Dynamic Parallel 1: 6 units(4Bit), 4 units(6Bit)
Dynamic Parallel 2: 24 units(6Bit)
Noise resistance 500V the square wave noise (pulse width: 1 ) by the noise simulator
Environ
ment
Ambient temp. -10 to 55, Storage: -25 to 65
Ambient humidity 35 to 85%RH, Storage: 35 to 85%RH
Acce
ssory
Basic unit Cap: Right/Left 1EA
Cap: Right/Left 1EA
Connector: 1EA
Connector: 1EA
2
Expansion unit - Ribbon cable: 1EA(50mm)
Apporaval
Unit weight Approx. 12g Approx. 17g Approx. 28g Approx. 60g
1: It is only for the Serial, Parallel input models.
2: It is only for the Parallel input model.
Environment resistance is rated at no freezing or condensation.
It is only for the RS485 communication input model.
RS485 communication specication
EP-KE-13-031A
Comm. protocol Modbus RTU with 16bit CRC
Connection type RS485
Application standard Compliance with EIA RS485
Max. connection 31units (address: 01 to 32)
Comm. type Two-wire half duplex
Comm. distance Max. 800m
Comm. speed 4800/9600/19200/38400bps
Comm. response time 5 , 20
Start bit 1bit(Fixed)
Data bit 8bit(Fixed)
Parity bit None(Fixed)
Stop bit 1bit(Fixed)
Protocol Modbus RTU
Connection of units
Dimensions
1)DS16/D 22
Connect a basic unit, expansion units,
a unit-display unit from the left and
connect the caps the end of right and left.
The middle bracket (sold separately) helps to
protect deflection when connecting over 7 units.
Use one middle bracket per 7 units.
The basic unit supplies the power for
expansion units and the unit-display unit
and DATA input.
2)D 40/D 60
Connect expansion connectors of units using a ribbon cable (accessory) as (Figure 1).
If the distance between expansion units is far as (Figure 2), you can connect the cable at the
soldering pad. To use a soldering pad, remove the protection cover which only expansion units have.
Expansion unit 2 Expansion unit 1
Remove of protection cover
To operate the function set switch of the D40, D60
models, you should remove the protection cover.
Press the connection parts (4 points) of the protection cover
at the top/bottom of the product with a at-head screwdriver
and the protection cover is removed.
Flat-head
screw driver
1)Serial input model
Part descriptions and function setting
Only the basic unit model has the function set switch and the input terminal.
The DS16, D 22 models have them at the side, and the D 40, D 60 models have them at the rear.
Expansion connector
Using for connecting units.
Refer to Connection of units.
The above specications are subject to change without notice.
Input terminals
No Code Function
1 VCC 12-24VDC
2 GND 0V
3 DATA Data input
4 CLOCK CLOCK input
5 LATCH LATCH input
Function set switches
1: Decimal number display: The other data
except 0 to 9 are blanked.
2: 5bit data input is compatible with Autonics pulse
meter (MP5W) and panel meter (MT4Y, MT4W).
No
Switch
Function
OFF ON
S1
Pos.
logic (PNP)
Neg.
logic (NPN)
Input logic
S2 Not used Used Zero Blanking
S3 Not used Used
Decimal number
display
1
S4 8Bit 5Bit
2
DATA input Bit
For the D 22- S, connect the connector to
input terminal.
Factory default
3)RS485 communication input model
No Switch Function
S1
Communication
response time
S2 Communication
speed selection
(bps)
S3
J1
to
J16
Communication
address selection
Input terminal
No. Code Function
1 VCC 12-24VDC
2 GND 0V
3 - -
No. Code Function
4 A(+) RS485 A(+)
5 B(-) RS485 B(-)
For D 22- T connect the connector to input terminal.
Expansion connector
Using for connecting units.
Refer to Connection of units.
Function set switches
Using for setting communication response time,
communication speed, and communication address.
DS16- T D 22- T
DS40/DA40- T DS60/DA60- T
Integrated device management program (DAQMaster)
DAQMaster is able to display I/O source
value, unit, and user setting value.
For more information, please refer to the
DAQMater user manual.
Visit our website (www.autonics.com) to
download DAQMaster program.
Operating
system
Window 98/NT/XP/Vista/Window7
PC
Min. spec.: IBM PC compatible computer of above
the Intel Pentium 3
Memory Min. spec.: 256MB
Hard disk Above 1 GB free space of hard disk
Resolution Above 1024 X 768 graphic card or monitor
Others Communication port: RS232 serial port, USB port
It is only for the RS485 communication
input model.
2)Parallel input model
No.
Switch
Function
OFF ON
S1 Pos. logic (PNP) Neg. logic (NPN) Input logic
S2 Not used Used Zero Blanking
S3 6Bit 4Bit Data input bit
S4 Dynamic 1 Dynamic 2 Dynamic 1/2 selection
J1 All Zero Blanking
2
1: : 4bit data input is compatible with Autonics pulse meter (MP5Y, MP5W) and
panel meter (MT4Y, MT4W).
2: When every number is 0, it becomes All Zero Blanking.
Ex) When displaying 000045 using two basic units,
Uses All Zero Blanking Does not use All Zero Blanking
1234
D 22- P
2
4
6
8
10
12
14
1
5
7
9
11
13
3
J1
S1 S2 S3 S4
ON
D 60- P
1234
S1 S2 S3 S4
ON
J1
2
4
6
8
10
12
14
1
5
7
9
11
13
3
Expansion connector
Using for connecting units. Refer to
Connection of units
Function set switches
No.
Dynamic Parallel 1 Dynamic Parallel 2
1
4Bit DATA input 6Bit DATA input 6Bit DATA input
Code Function Code Function Code Function
1 VCC 12-24VDC VCC 12-24VDC VCC 12-24VDC
2 GND 0V GND 0V GND 0V
3 LE5 LATCH 5 LE3 LATCH 3 LATCH LATCH input
4 LE4 LATCH 4 LE2 LATCH 2 CLOCK CLOCK input
5 LE3 LATCH 3 LE1 LATCH 1 - -
6 LE2 LATCH 2 LE0 LATCH 0 UNIT Unit
7 LE1 LATCH 1 DP Point DP Point
8 LE0 LATCH 0 D5 2
5
data D5 2
5
data
9 DP Point D4 2
4
data D4 2
4
data
10 D3 2
3
data D3 2
3
data D3 2
3
data
11 D2 2
2
data D2 2
2
data D2 2
2
data
12 D1 2
1
data D1 2
1
data D1 2
1
data
13 D0 2
0
data D0 2
0
data D0 2
0
data
14 GND 0V GND 0V GND 0V
1: When selecting Dynamic Parallel 2, 6Bit data input and all zero blank OFF
are fixed.
Input terminals
D 40- P
J1
2
4
6
8
10
12
14
1
5
7
9
11
13
3
S1 S2 S3 S4
1234
ON
J1
Basic
unit
Basic
unit
Basic
unit
Basic
unit
You can use both the 7 segment display method model and the 16 segment display method model mixed.
DS16- S
5
4
3
2
1
D 22- S
5
4
3
2
1
D 60- S D 40- S

Caution: Before removing the protection cover, power must


be turned OFF.
Input DATA chart
Hi 2Bit
Lo 4Bit
This chart is for positive logic (PNP).
Unit-display unit function
It is only available to use the unit-display unit with serial 5bit, parallel 4/6bit Dynamic 1 input
when connecting the unit-display unit and turning ON it. (Do not input data to the unit-display unit. )
To display two data using zero blanking function
Using the unit-display unit: If sending unit data signal after no.1 data (000123), it applies zero
blanking function when displaying no.2 data (04567).
Do not transmit unit data to the basic unit/expansion unit. Unit division bit (D7) of unit data is
used only for unit division. When transmitting unit data to the basic/expansion unit, unit division
bit (D7) displays the ignored data value. Zero blanking does not operate normally.
Upper/Lower selection,
ON/Flash function
ON/Flash function
Not using the unit-display unit: If sending no-unit data (HXXXLLLL) after no.1 data(00123), it
applies zero blanking function to display no.2 data.
In this case, transmitted data should be added one to the display digits.
(no-unit data is added)
When do not using unit-display unit, no-unit data is used for data division. If it does not send
no-unit data(HXXXLLLL), it displays no.1 data (00123) and no.2 data (04567) as one data.
Zero-blanking function is applied to no.1 data only.
The unit-display unit does not use the upper bit over D4. (Dont care: X)
1: If this data is not for the unit-display unit, it maintains former state.
When selecting 5Bit data input for the serial input model, or 4Bit data input for the parallel input model, it
displays only shaded part (0 to 9, A to F). If there is no input data after supplying the power, the basic unit
differently displays by each input method; serial input model displays S, parallel input model displays P, and
RS485 communication input model displays T.
Input circuit
Positive logic (PNP) input
100
20
Input IC
Input IC
Negative logic (NPN) input
100
20
5V
Input level
High: 4.5-24VDC, Low: 0-1.2VDC
No(Address) Func R/W Parameter Parameter name Description Setting range Default
400001(0000) 03/06/16 R/W - Zero Blanking Setting Zero Blanking ON/OFF 0: OFF, 1: ON 0
400002(0001) 03/06/16 R/W - Digit 1, 2 1, 2 display data
Refer to the
Input DATA
chart.
0
400003(0002) 03/06/16 R/W - Digit 3, 4 3, 4 display data 0
400004(0003) 03/06/16 R/W - Digit 5, 6 5, 6 display data 0
400005(0004) 03/06/16 R/W - Digit 7, 8 7, 8 display data 0
400006(0005) 03/06/16 R/W - Digit 9, 10 9, 10 display data 0
400007(0006) 03/06/16 R/W - Digit 11, 12 11, 12 display data 0
400008(0007) 03/06/16 R/W - Digit 13, 14 13, 14 display data 0
400009(0008) 03/06/16 R/W - Digit 15, 16 15, 16 display data 0
400010(0009) 03/06/16 R/W - Digit 17, 18 17, 18 display data 0
400011(000A) 03/06/16 R/W - Digit 19, 20 19, 20 display data 0
400012(000B) 03/06/16 R/W - Digit 21, 22 21, 22 display data 0
400013(000C) 03/06/16 R/W - Digit 23, 24 23, 24 display data 0
400014 to 400050 03/06/16 R/W Reserved
Display data
Communication setting
1)Application of system organization
USB B type
Terminating resistance
(100 to 120 )
B(-)
A(+)
ON OFF
A(+)
RS485
DEVICE
#1
RS485
DEVICE
#2
RS485
DEVICE
#30
RS485
DEVICE
#31
A(+) A(+) B(-) B(-) B(-)
USB RS485
It is recommended to use Autonics communication converter;
SCM-US48I (USB to RS485 converter, sold separately),
SCM-38I (RS232C to RS485 converter, sold separately).
Please use twist pair wire for RS485 communication.
It is only for the RS485 communication
input model.
2)Modbus Address Mapping
Digit 1, 3, 5, ... 23 data
D7 D6 D5 D4 D3 D2 D1 D0
Data
Point Unit Unit, point are displayed when it is H.
Digit 2, 4, 6, ... 24 data
D7 D6 D5 D4 D3 D2 D1 D0
Data input method
General parallel input is only for the basic unit (Dynamic Parallel 1).
4/6Bit Data 3+ Point 3
4/6Bit Data 2+ Point 2
4/6Bit Data 1+ Point 1
4/6Bit Data 0+ Point 0
LATCH 0
Data 3 + point 3
Data 2 + point 2
Data 1 + point 1
Data 0 + point 0
103 102 101 100
Dynamic
Parallel 1
4Bit
Connectable 1 basic unit and 5 expansion units(6Digit)
Ex) 10digit organization: (1 basic unit + 5 expansion units)+(1 basic unit + 3 expansion units)
6Bit
Connectable 1 basic unit and 3 expansion units(4Digit)
Ex) 10Digit organization: (1 basic unit + 3 expansion units)2+(1 basic unit + 1 expansion units)
Dynamic
Parallel 2
6Bit
Connectable 1 basic unit and 23 expansion units(24Digit)
Ex) 30Digit organization: (1 basic unit + 23 expansion units)+(1 basic unit + 5 expansion units)
Example of unit organization by data input
EX: Displays 10H38M(10 hours 38 minutes)
2)Parallel input model
1)Serial input model
6Bit Dynamic Parallel 1 input(Ex: Displays 50.80kg)
LATCH
0 to 3
LLLHLH LLLLLL LLHLLL LLLLLL
LATCH 0
LATCH 1
LATCH 2
LATCH 3
Pw
t1 t3 t2
4Bit Dynamic Parallel 1 input(Ex: Displays ACE007.)
Basic
unit 1
Basic
unit 1
Basic
unit 1
Basic
unit 1
Expansion
unit 1
Expansion
unit 1
Expansion
unit 1
Expansion
unit 1
Expansion
unit 23
Expansion
unit 23
Expansion
unit 2
Expansion
unit 3
Expansion
unit 5
LATCH
0 to 5
Point
Point
Point
4Bit
data
6Bit
data
6Bit
data
4Bit
data
LATCH 0
LATCH 1
LATCH 2
LATCH 3
LATCH 4
LATCH 5
Point
HLHL HHLL HHHL LLLL LLLL LHHH
Pw
t1 t3 t2
Clock: Max. 3kHz
5Bit Serial input(Ex: Displays 12.8 )
1Bit data
CLOCK
LATCH
L
START
H L L H L L L L L H L H L L
SHIFT
P
o
in
t
P
o
in
t
P
o
in
t
P
o
in
t
U
n
it
U
n
it
U
n
it
P
o
in
t
P
o
in
t
Data Data Data
tw
0.5ms ta
These are examples for positive logic (PNP).
Clock: Max. 2kHz
Caution: The unit-display unit is available only for turning ON. Do not input data to the unit-display unit.
ta: 0.2ms(Min.)
tw: 0.25ms(Min.)
ta: 0.2ms(Min.)
tw: 0.25ms(Min.)
100 1022 1023 1021 101
6Bit Dynamic Parallel 2 input(Ex: Displays AB.C...W)
Unit
CLOCK
LATCH
0.66ms
LLHLHL LLHLHH HLLLLL LLHHLL XXLLHL
6Bit
data
CLOCK
LATCH
Point
Unit
ta
tw
ta: 0.3ms(Min.), tw: 0.33ms(Min.)
Clock: Max. 15kHz
3)RS485 communication input model
RS485+
RS485-
Byte
Counter
Data(400001) Data(400002) Data(400003) Data(400004)
Error
Check(CRC16)
Hi Lo Hi Lo Hi Lo Hi Lo Lo Hi
08H 00H 01H 01H 00H 11H 03H 08H 16H D4H 59H
Slave
Address
Function
Starting Address No. of Register
Hi Lo Hi Lo
01H 10H 00H 00H 00H 04H
Query(Master)
Response(Slave)
Slave
Address
Function Starting Address No. of Register Error Check(CRC16)
Hi Lo Hi Lo Lo Hi
01H 10H 00H 00H 00H 04H C1H CAH
Zero
Blanking
ON
8Bit Serial input(Ex: Displays 25 )
1Bit data
CLOCK
LATCH
START
M
S
B
(2
)
M
S
B
(2
)
M
S
B
(1
)
M
S
B
(1
)
M
S
B
(0
)
M
S
B
(0
)
L
S
B
(2
)
L
S
B
(2
)
L
S
B
(1
)
L
S
B
(1
)
L
S
B
(0
)
L
S
B
(0
)
L L L L L L L L L L L L L L L L H H H H H X X X
SHIFT
Data Data Data
0.5ms ta
tw
Communication address: 1, Communication speed: 9600bps, Data Bit: 8Bit, Start/Stop Bit: 1Bit, Parity Bit: None
Thank you very much for selecting Autonics products.
For your safety, please read the following before using.
Caution for your safety
Warning
Please keep these instructions and review them before using this unit.
Please observe the cautions that follow;
Warning
Caution
The following is an explanation of the symbols used in the operation manual.
Serious injury may result if instructions are not followed.
Product may be damaged, or injury may result if instructions are not followed.
Caution: Injury or danger may occur under special conditions.
1. In case of using this unit with machinery (Ex: nuclear power control, medical equipment, ship,
vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention
equipment, etc) which may cause damages to human life or property, it is required to install
fail-safe device.
It may cause a re, human injury or damage to property.
2. Do not disassemble or modify this unit. Please contact us if it is required.
It may cause electric shock or a re.
1. This unit shall not be used outdoors.
It may shorten the life cycle of the product or cause electric shock.
2. Please observe the rated specications.
It may shorten the life cycle of the product.
3. In cleaning the unit, do not use water or organic solvent. And use dry cloth.
It may cause electric shock or a re.
4. Do not use this unit where there are ammable or explosive gases, humidity, direct ray of
the sun, radiant heat, vibration, impact etc.
It may cause a re or explosion.
5. Do not inow dust or wire dregs into the unit.
It may cause a re or malfunction.
Caution
Panel cut-out
Panel cut-out
Panel cut-out
Panel cut-out
Accessory Sold separately (Middle bracket)
Accessory and sold separately
Pw: 0.33ms(Min.)
t1: 0.05ms(Min.)Data LATCH
t2: 0.23ms(Min.)Data move
t3: 0.05ms(Min.)Data LATCH
Pw=t1+t2+t3
Pw: 0.33ms(Min.)
t1: 0.05ms(Min.)Data LATCH
t2: 0.23ms(Min.)Data move
t3: 0.05ms(Min.)Data LATCH
Pw=t1+t2+t3
Caution: The unit-display unit is available only for turning ON. Do not input data to the unit-display unit.
6Bit
data
Point
Basic
unit 1
Basic
unit 1
Basic
unit 1
Basic
unit 1
4/6Bit Data 3+ Point 3
4/6Bit Data 2+ Point 2
4/6Bit Data 1+ Point 1
4/6Bit Data 0+ Point 0
LATCH 0
Data format
Proximity sensors
Area sensors
Door/Door side sensors
Counter
Rotary encoders
Power controllers
Panel meters
Temperature controllers
Tachometer/Pulse(Rate) meters
Temperature/Humidity transducers
Switching power supplies
Stepping motors/drivers/motion controllers
Field network devices
Laser marking system(CO2, Nd:YAG)
Laser welding/soldering system
Photoelectric sensors
Fiber optic sensors
Pressure sensors
Timers
Display units
Sensor controllers
Graphic/Logic panels
Satisable Partner For Factory Automation
HEAD QUARTERS :
41-5, Yongdang-dong, Yangsan-si, Gyeongnam, 626-847,
Korea
OVERSEAS SALES :
Bldg. 402 3rd Fl., Bucheon Techno Park, 193, Yakdae-dong,
Wonmi-gu, Bucheon-si, Gyeonggi-do, 420-734, Korea
TEL:82-32-610-2730 / FAX:82-32-329-0728
E-mail : sales@autonics.com
The proposal of a product improvement
and development : product@autonics.com
Major products
Middle
bracket
Expansion
connector
Cap
Cap
Unit-display
unit
Basic
unit Expansion
unit
Expansion unit
Cable length: Max. 1m Ribbon cable
(Figure 1) (Figure 2)
Soldering
pad
Soldering
pad
Cap
Connector for
D 22-S/T
Connector for
D -P
For DS16
(BK-D16R)
For DS22/DA22
(BK-D22R)
Ribbon cable
(50mm)
Unit
N: The number of units
Panel thickness: 1.5 to 4mm
(Unit: mm)
Unit
Unit
Unit
Factory default
Factory default
1. This unit must be mounted on the Panel.
2. This is non-insulated product. Use insulated power for power supply.
3. Input signal line
Shorten the cable distance between the external device and this product.
Use shield cable when input wiring is long. Wire the input signal line separately from the power line.
4. Dielectric or insulation resistance test when this unit is installed in the control panel.
Separate the unit from the control panel. Short circuit all terminals of the unit.
5. Do not use this unit at below places.
Place where there are severe vibration or impact. Place where strong alkalis or acids are used.
Place where there are direct ray of the sun
Place where strong magnetic field or electric noise are generated
6. Installation environment
It shall be used indoor Altitude Max. 2,000m
Pollution Degree 2 Installation Category I
Caution for using
It may cause malfunction if above instructions are not followed.
Tighten it with below 0.5N.m.